Training Manual B 737-300/400/500: ATA 24 Electrical Power
Training Manual B 737-300/400/500: ATA 24 Electrical Power
B 737-300/400/500
ATA 24
ELECTRICAL POWER
Page: i
TABLE OF FIGURES
Figure 1 AC Power Philosophy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 36 VSCF - Wet Pad Cavity . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Figure 2 Elec. Power System - AC / DC Power Supply . . . . . . . . . 5 Figure 37 Generator Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 3 Elec. Power System - Standby Power . . . . . . . . . . . . . . . . 7 Figure 38 Generator Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 4 Location - Main System Components . . . . . . . . . . . . . . . . 9 Figure 39 Generator Control Unit Schematic . . . . . . . . . . . . . . . . . . 79
Figure 5 Location - External Power Panel P19 . . . . . . . . . . . . . . . . 11 Figure 40 Electrical Smoke Isolation . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 6 Location - Forward Attendants Panel . . . . . . . . . . . . . . . . . 13 Figure 41 Transfer Bus Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Figure 7 Location - Main Power Breakers . . . . . . . . . . . . . . . . . . . . . 15 Figure 42 AC Power Annunciator Lights . . . . . . . . . . . . . . . . . . . . . . 85
Figure 8 Location - Panel P6 / M400 / M238 . . . . . . . . . . . . . . . . . . 17 Figure 43 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 9 Location / Interior - P6 Panel . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 44 VSCF Differential Protection . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 10 Location - AC Generator / VSCF . . . . . . . . . . . . . . . . . . . 21 Figure 45 Diff. Protection Current Transformer . . . . . . . . . . . . . . . . 91
Figure 11 Location - AC Generator / CSD . . . . . . . . . . . . . . . . . . . . 23 Figure 46 Differenz CSD/GEN and VSCF . . . . . . . . . . . . . . . . . . . . 93
Figure 12 Electrical Power Control Panel (Upper) . . . . . . . . . . . . . . 25 Figure 47 VSCF Cooling and Lubrication . . . . . . . . . . . . . . . . . . . . . 95
Figure 13 Elec. Panel (Upper - New Generation) . . . . . . . . . . . . . . 27 Figure 48 VSCF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Figure 14 Electrical Power Control Panel (Lower) . . . . . . . . . . . . . . 29 Figure 49 VSCF Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 15 Elec. Power Control Panel (Lower) cont. . . . . . . . . . . . . 31 Figure 50 VSCF BIT Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Figure 16 Electrical Power Annunciator Panel M238 . . . . . . . . . . . 33 Figure 51 DC Power System Schematic . . . . . . . . . . . . . . . . . . . . . . 105
Figure 17 M 238 DC Bus Indicating Lights . . . . . . . . . . . . . . . . . . . . 35 Figure 52 DC Equipment Installation . . . . . . . . . . . . . . . . . . . . . . . . . 107
Figure 18 M 238 AC Bus Indicating Lights . . . . . . . . . . . . . . . . . . . . 37 Figure 53 DC POWER SYSTEM TR-Unit . . . . . . . . . . . . . . . . . . . . 109
Figure 19 M 238 Generator Malfunction Lights . . . . . . . . . . . . . . . . 39 Figure 54 DC External Power Receptacle . . . . . . . . . . . . . . . . . . . . 111
Figure 20 M400 Power System Test Module . . . . . . . . . . . . . . . . . . 41 Figure 55 DC POWER SYSTEM Battery . . . . . . . . . . . . . . . . . . . . 113
Figure 21 M400 AC Voltage / Frequency Metering . . . . . . . . . . . . . 43 Figure 56 Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 22 M400 DC Voltage Metering . . . . . . . . . . . . . . . . . . . . . . . . 45 Figure 57 External Power Schematic . . . . . . . . . . . . . . . . . . . . . . . . 117
Figure 23 M400 AC Amperes Metering . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 58 External Power Contactors . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 24 CSD - Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 59 Ground Service Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 25 CSD - Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Figure 60 Bus Protection Panel (BBP) . . . . . . . . . . . . . . . . . . . . . . . 123
Figure 26 CSD Wet Pad Cavity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Figure 61 Standby Bus Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 27 CSD - Oil Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Figure 62 Static Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Figure 28 Constant Speed Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Figure 63 Galley Power Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Figure 29 CSD Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Figure 64 Automatic Galley Load Shedding . . . . . . . . . . . . . . . . . . . 131
Figure 30 AC System Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 31 Engine Generator System Schematic . . . . . . . . . . . . . . . 63
Figure 32 VSCF - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Figure 33 VSCF - Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Figure 34 VSCF Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 35 VSCF - Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Page: ii
Lufthansa Technical Training
ELECTRICAL POWER 737-300/400/500
GENERAL
24-00
24-00 GENERAL
AC POWER PHILOSOPHY
Electrical power is generated by one generator on each engine and by one The APU Generator can supply:
APU generator. S On Ground:
Two different types of generators may be installed at the same time. They will AC GEN BUS 1, AC GEN BUS 2, TRANSFER BUS 1 and TRANSFER
have no differences in system behavior and indication. BUS 2
S Type 1: Each engine generator is connected to its respective engine S In Air:
through a CSD which converts variable engine RPM to the constant speed
AC GEN BUS 1 or AC GEN BUS 2, TRANSFER BUS 1 and TRANFER
needed to produce 400 Hz used by the electrical system components.
BUS 2
S Type 2: Each VSCF (Variable Speed Constant Frequency) Generator is
driven directly from the engine gear box, rotating at a variable speed. The
variable frequency is converted to constant 400 Hz using a solid state, high
power inverter.
There are three basic principles of operation for the electrical system:
S 1. There is no paralleling of the AC sources of power.
S 2. The last source of power switched onto the system takes priority
and will automatically disconnect the existing source.
S 3. There is no automatic connection of electrical power sources. All
sources must be manually connected through the movement of a
switch.
In flight each generator normally powers its own generator bus. If one genera-
tor is inoperative, the APU generator may be used to power the inoperative
generator’s bus.
Each Generator system consists of a generator bus and a transfer bus. If there
is a failure of a generator bus, the associated transfer bus can be supplied au-
tomatically from the powered generator bus. Each transfer bus has an
For Training Purposes Only
EXTERNAL APU
MAIN POWER GENERATOR MAIN
ENGINE UNIT ENGINE
GEN No 1 GEN No 2
3o
3o 115/200 V
115/200 V
EXT AC BUS
3o 3o
115/200 V APU APU 115/200 V
EPC 1 EPC 2 GB 1 GB 2
GB 1
GB 2
NORMAL NORMAL
LOAD LOAD
OFF OFF
For Training Purposes Only
POWER SUPPLY
AC POWER SUPPLY control computers. The TR-3 disconnect relay can be opened manually for
The normal inflight configuration of the power system has engine generator 1 smoke procedure with the BUS TRANSFER SWITCH in OFF position.
connected to generator bus 1, main bus 1 and transfer bus 1. Generator 2 is TR voltage range is 24 - 30 V.
connected to generator bus 2, main bus 2 and transfer bus 2. These systems The battery bus has two possible sources of power: the battery or battery
are separate. In the event of an inoperative generator, the APU generator can charger through the hot battery bus or from TR-3. Under normal operating
be connected to one of the generator busses thereby restoring full electrical conditions, a relay controlled by the battery switch connects the TR-3 to the
power. battery bus. If TR-3 should fail the battery bus will automatically seek its power
With the airplane on the ground and external power connected, placing the source from the hot battery bus.
Ground Power switch momentarily to ON will trip both engine generators and Placing the Battery switch to OFF removes the ground for the controlling relays
connect external power to both generator busses simultaneously. When the and will cause the battery bus to lose power unless the electrical standby
APU is operating, electrical power output of its generator can be connected to power switch is in BAT position. With the electrical standby power switch in
generator bus 1 and/or generator bus 2 through the respective control BAT, the hot battery bus will power the battery bus regardless of TR-3 output.
switches. Whenever ground power is on both generator busses, and APU or an
The hot battery bus and the switched hot battery bus receive power from the
engine generator power is applied to one generator bus, ground power contin-
battery charger if a generator is operating or from the battery if AC power is not
ues to supply power to the other generator bus.
available. The hot battery bus remains powered at all times. The switched hot
The transfer busses normally receive their power from the respective generator battery bus is powered when battery switch is in ON position.
bus. If a generator bus loses power, the respective transfer bus will automati-
cally receive power from the other generator bus. In addition the protective
auto load-shedding circuit turns off all galley power. GROUND SERVICE BUS
This feature ensures that the remaining generator will not be overloaded. The ground service bus is normally powered through generator bus 1. When
The electrical system monitors itself for correct voltage, frequency, ground the airplane is on the ground and external power is connected, placing the
faults in the generator or excessive current draw from any generator. If any Ground Service Switch (located on fwd attendant’s panel) to ON will connect
malfunction develops, the generator affected will be automatically disconnected the ground service bus directly to the external power source without energizing
from its generator bus. the other airplane electrical busses. This bus contains most of the cabin lighting
and other equipment needed for cleaning.
DC POWER SUPPLY
For Training Purposes Only
R6 R4
NORM ALT GROUND TRANSFER 2
R3 TRANSFER 1 SERVICE ALT NORM
115V AC
GRD SERVICE
BUSSES
R89
BATTERY CHARGER
TRANSFER
STANDBY POWER
TRANSFER MANUAL
GRD
DC EXT PWR
RECEPTACLE
R6 R4
NORM ALT GROUND TRANSFER 2
R3 TRANSFER 1 SERVICE ALT NORM
115V AC
GRD SERVICE
BUSSES
R89
BATTERY CHARGER
TRANSFER
STANDBY POWER
TRANSFER MANUAL
GRD
DC EXT PWR
RECEPTACLE
GENERATOR
NO. 2 (RH)
EXTERNAL
POWER
RECEPTACLE
ELECTRONIC
COMPARTMENT
ACCESS DOOR
GENERATOR
NO. 1 (LH)
APU
GENERATOR
AC LINE (3 PHASE)
DC LINE (28V)
T-R UNIT NO. 1
T-R UNIT NO. 2
STATIC
INVERTER
BATTERY
For Training Purposes Only
CHARGER
BATTERY
FWD ELECTRONIC
COMPARTMENT
ACCESS DOOR
EXTERNAL POWER
PANEL P19
For Training Purposes Only
RECEPTACLE
GROUND SERVICE
SWITCH
INOP INOP
-0+
400
DC CPS
-50 +50
FREQ 420
110 120
20
AC
DC VOLTS 40 VOLTS 30
1 2
LOW OIL STANDBY LOW OIL ALTERNATE INSTALLATION
1 PRESSURE PWR OFF PRESSURE 1 DRIVE 1
For Training Purposes Only
DISCONNECT DISCONNECT
S TRU 1 fails in flight, or display. The Display Test is terminated automatically after a complete test cycle
or when the RECALL/RESET switch has been pushed during the Display Test.
S TRU 2 and TRU 3 fail in flight
Maintenance Messages, if any exist, are displayed after the Display Test. The
S ELEC Light
first message will automatically be displayed. Push the RECALL/RESET switch
- The ELEC light will come on for these fault messages: each time after the Display Test to see the subsequent messages. Push the
S STAT INV INOP RECALL/RESET switch after the last message and an informational message
-The Static Inverter is defective. to clear the fault messages will be displayed.
S BAT CHGR INOP The Maintenance Messages will be removed when the RECALL/TEST button
-The Battery Charger is defective. is pressed and held for approximately 6 seconds.
DC VOLTS AC VOLTS
BAT
DISCHARGE TR UNIT ELEC
RECALL/RESET
OFF
OFF
BAT
GALLEY
ON ON
DC AC
- Both External Power Contactors will be tripped. Start Switch is not in the OFF position.
AC Ammeter
Displays the Load of the respective Generator
DRIVE TEMP
RISE
DRIVE TEMP
RISE
M238 LOCATION
DC BUS
MALFUNCTION LIGHTS
INDICATION LIGHTS
AC BUS
INDICATION LIGHTS
(COVERED)
For Training Purposes Only
DC ANNUNCIATOR LIGHTS
The Lights on the Annunciator Lights Module M238 illuminate when power is
on:
S DC Bus No.1
S DC Bus No. 2
S DC Standby Bus
S External Power T-R Unit is energized
S T-R Unit No. 3 has output power
The INDICATE/TEST switch S2 on the module must be set to INDICATE for
the lights to illuminate.
When the INDICATE-TEST switch is set to TEST, all lights except EXT PWR
TR are grounded and connected to the 28-Volt DC Bat Bus. The EXT PWR TR
light, which is always connected to Bus Protection Panel, is grounded. This
verifies that all lamps on the M238 module are operable.
For Training Purposes Only
EXT PWR
TR STBY BATT HV LV
ERASE AC BUS
S1 OA
NO.1 NO.2
INDICATE
OC
S2
NORMAL
TEST
FAULT
28V DC WHEN INDICATE
R2 EXTERNAL POWER
IS ATTACHED
TEST
S2 INDICATE
TEST SWITCH
28V DC
BUS 1 DC BUS PWR ON
DC BUS INDICATION
BUS NO. 1
NO.1 NO.2 TR 3
28V DC W W W
BUS 2
DC BUS INDICATION
BUS NO. 2
For Training Purposes Only
BATT
28V DC W
TR 3
DC BUS INDICATION
TR NO. 3 W W
EXT PWR TR STBY DC IND
28V DC
BAT BUS
DC BUS INDICATION
BAT
28V DC
STBY BUS
DC BUS INDICATION
STBY
115V AC
STANDBY
BUS AC STANDBY BUS
INDICATION
115V AC AC INDICATION
GROUND GRD SERVICE A
AC BUS PWR ON
SERVICE
BUS
OA
AC INDICATION
GRD SERVICE C NO. 1 NO. 2 NO. 1 NO. 2 GRD STBY
TRANS TRANS SVC
OC
115V AC AC INDICATION
TRANSFER TRANSFER BUS 1 A
BUS 1
AC BUS INDICATION LIGHTS
AC INDICATION
AC BUS PWR ON
TRANSFER BUS 1 C
L21 L23 L28 L27
OA L19 L25
AC INDICATION
BUS NO. 1 A OA NO. 1 OA NO. 2 OA NO. 1 OA NO. 2 OA GRD SVC OA STBY
115V AC TRANS TRANS
MAIN BUS 1
L20 L22 L26
OC L24 L29
AC INDICATION
BUS NO. 1 C OC NO. 1 OC NO. 2 OC NO. 1 OC NO. 2 OC GRD SVC
TRANS TRANS
AC INDICATION
115V AC BUS NO. 2 A
MAIN BUS 2
AC INDICATION
BUS NO. 2 C
For Training Purposes Only
AC INDICATION
115V AC TRANSFER BUS 2 A
TRANSFER
BUS 2
AC INDICATION
TRANSFER BUS 2 C
Operation
All lights have 28 Volt DC Battery Bus power available (provided the battery
switch is in ON). A ground will be connected within a GCU by energizing the
trip coil of the applicable fault light relay.
If the trip coil of the relay has been energized, it will be latched in the Trip posi-
tion by a permanent magnetic latch, and can only be released by energizing
the reset coil. The only possibility for energizing the reset coils and deleting the
FF, HV and LV lights is by pushing the ERASE button.
The only possibility for energizing the reset coil and deleting the MT lights is by
switching the respective GEN Switch to the ON position.
The ERASE button has no effect on the MT lights.
Reasons for indication:
S High Voltage (HV): Voltage > 130 V
S Low Voltage (LV): Voltage < 100 V
S Feeder Fault (FF): Overcurrent or Differential Protection (VSCF Fault)
S Manual Trip (MT): Generator Breaker Switch to OFF or CSD Disconnect
Switch to Disconnect position.
For Training Purposes Only
28V DC
BATTERY DC BUS PWR ON GEN 1 GEN 2 APU
BUS NO. 1 NO. 2 TR3 FF MT FF MT FF MT
DC BUS INDICATION
BAT
ON
TEST AC BUS PWR ON
ERASE
ERASE /
OA
S2 INDICATOR
MANUAL TEST SWITCH S1
S1 ERASE NO. 1 NO. 2 NO. 1 NO. 2 GRD STBY
CONTROL SWITCH TRANS TRANS SVC
INDICATE
/
OC
OFF S2
APU
MANUAL TRIP TEST
MT
INTERNALS
RESET SAME AS FF W
G-3
W
LV
DIFFERENTIAL
PROTECTION HV W
DC W
G5 APU GENERATOR
CONTROL UNIT (P6)
TRIP
GEN 2
FEEDER FAULT
MT
FF W
INTERNALS
RESET
SAME AS W
G-3 LV
UNDER
VOLTAGE HV W
W
DC
G4 GENERATOR CONTROL
TRIP UNIT 2 (P6) GEN 1
For Training Purposes Only
LOW VOLTAGE
MT
FF W
RESET W
LV
OVER HV W
VOLTAGE
W
DC
S2 S1
POWER SYSTEM TEST
F G 6 7
E H 5 8
JACKS FOR
EXTERNAL D A 4 1
MEASURING C B 3 2
For Training Purposes Only
PART NO.
SER. NO.
AC DC
C F
115V AC G
EXTERNAL B
E H NC
POWER A C
BUS PROTECTION PANEL AC
A
P6-12 CIRCUIT BREAKER PANEL D J1 J2
B
C
400
AC INDICATION NC NC 380 420
115V AC GROUND GND SERVICE C
CPS
SERVICE BUS AC INDICATION FREQ
GND SERVICE B 1
NC
AC INDICATION 3 2
GND SERVICE A
F G
S1 WAFER SWITCH FREQUENCY METER
AC INDICATION H NC
TRANSFER BUS 2 C E
115V AC
TRANSFER B
AC INDICATION
BUS 2 TRANSFER BUS 2 B 110 120
A
AC INDICATION D 100
TRANSFER BUS 2 A 130
C B 0 30
POWER SYSTEM TEST AC
F G 6 7 VOLTS
AC INDICATION E H 5 8
115V AC BUS NO 2 C D A 4 1
MAIN BUS 2 AC INDICATION C B 3 2
BUS NO 2 B
AC VOLTMETER
AC INDICATION
BUS NO 2 A
AC DC
F G APU GEN
AC INDICATION E H NC GEN 1 GEN 2
115V AC TRANSFER BUS 1 C
A GRD
TRANSFER AC INDICATION TEST
TRANSFER BUS 1 B J1 J2 PWR
BUS 1 A POSITION OF M400 SW S1
AC INDICATION D POSITION OF M400 SWITCH S2 STBY
TRANSFER BUS 1 A B PWR RESID
C VOLTS
A B C D E F
AC INDICATION
BUS NO 1 C 1 MAIN BUS 1 MAIN BUS 1 MAIN BUS 1 XFR BUS 1 XFR BUS 1 XFR BUS 1
115V AC A B C A B C
MAIN BUS 1 AC INDICATION
BUS NO 1 B MAIN BUS 2 MAIN BUS 2 MAIN BUS 2 XFR BUS 2 XFR BUS 2 XFR BUS 2 RESIDUAL VOLTS SWITCH
2
AC INDICATION A B C A B C
BUS NO 1 A
3 GND SVCE GND SVCE GND SVCE EXT PWR EXT PWR
For Training Purposes Only
4 1 GCR CLOSE
FIRE SW
3 SIGNAL
CLOSE SIGNAL 2 NO. 1 GEN G3 GENERATOR
NORMAL FIELD CONTROL UNIT 1 (P6)
ENGINE GENERATOR GEN 1
BREAKER 1 (RIGHT SIDE CONT P5-4 AC
NOSE WHEEL WELL) UNIT S1 WAFER SWITCH SYSTEMS AND
FIRE APU MODULE
M400 POWER SYSTEM TEST MODULE (P6)
S8 ENG 1
FIRE SW
A
POWER SYSTEM TEST
F G 6 7
APU B E H 5 8 S2 SWITCH POSITION
METER
GENERATOR D A 4 1 READING
C 3 2 A B C D E F
C B GEN 1
T9 CURRENT A B C A B C
TRANSFORMER AMMETER
ASSEMBLY GEN 2
AC DC A B C A B C
AMMETER
APU GEN A B C A B C
A AMMETER
ENGINE 2 B
GENERATOR
C
T8 CURRENT
TRANSFORMER
ASSEMBLY
ENGINE 1 B
GENERATOR
C
GENERATOR 1 GENERATOR 2
AMMETER AMMETER
K2 K1
K3
100
For Training Purposes Only
50 150
F G AC
H 0 200
E AMPERES
28V DC
BUS 1 A
DC BUS
INDICATION D
BUS 1
C B
APU GENERATOR
AMMETER
P6-5 CIRCUIT BREAKER S2 WAFER SWITCH
PANEL
MAIN
ELECTRICAL
GENERATOR CONNECTOR
ATTACHMENT AND HARNESS VENT
STUDS (12) VALVE
SIGHT
GLASS
DIFFERENTIAL
LOW OIL
PRESSURE
INDICATOR PRESSURE
SWITCH
DISCONNECT
SOLENOID
WET SPLINE
SERVICE PORT
OUTPUT
PAD DRAIN
CHARGE
FILTER
OIL INLET
PORT
GOVERNOR
ADJUSTMENT
COVER RESET
HANDLE DRAIN PLUG
(6 o’clock (RESERVOIR) QAD RING
position)
LOCKBOLT
OIL OUTLET WET SPLINE
DOWN CONNECTION SERVICE PORT
CSD SERVICING
General - Stop for five minutes.
The CSD sight glass has different ranges for the oil level on the left and right NOTE: The time will let the oil level become stable.
engines. This is because the left and right engines are at different angles. The S Look at the oil level in the sight glass on the CSD.
oil quantity of the CSD is 10.7 pints. The oil quantity of the external system is - If the oil level is below the bottom of the applicable range, add oil to the
2.75 pints.The total oil quantity for a dry CSD oil system is 13.45 pints for each CSD.
engine.
- If the oil level is above the top of the applicable range, drain some oil
The oil level shown on the sight glass of a disconnected CSD can show more from the CSD.
oil than there is. Expanded air can push the oil from the oil cooler into the CSD.
S Remove the coupling from the case pressure-fill valve and install the cap.
To get an accurate indication of the oil level, fill the CSD and look at the sight
glass again. Leakage of the seal in the CSD will let oil flow from the CSD to the
spline cavity. A defective input shaft seal will cause these indications:
S The oil level in the CSD will decrease.
S The oil level in the spline cavity will increase.
CSD PRESSURE
FILL PORT
CSD CSD
OIL COOLER
For Training Purposes Only
FAN CASE
SCAVENGE
FILTER
ACCESSORY
GEARBOX
SPLINE CAVITY
FILLPORT WET PAD
CAVITY VENT TO
ENGINE
DRAINS
SPLINE CAVITY
STANDPIPE INDICATOR CAP
DRAIN & OVERFLOW
STAND
PIPE
INPUT SPLINE
Oil Cooler
The CSD oil cooler is used for cooling the oil from the CSD.
It is located in an opening on the right hand side of the engine fan duct.
The cooler is a small oil/air heat exchanger using fan air. A pressure relief valve
is installed in the cooler assembly. On the outlet fitting is an HIGH OIL TEM-
PERATURE switch installed.
During engine operation, hot oil from the CSD passes through the cooler; fan
air provides the cooling for the oil. If the cooler becomes blocked on the oil
side, a pressure relief valve cracks open at 50 psi differential pressure and is
fully open at 90 psi differential pressure allowing oil to bypass the cooler core.
CSD Line Filter (Scavenge Filter)
The Line oil filter collects contamination from the oil. This prevents damage to
the CSD and oil cooler.
The line filter has a pop-out button. The pop-out button extends when the oil
pressure becomes to high. This is an indication that the oil filter element is full
of contamination and will not let the oil flow through it.
The line oil filter is on the fan case at the 5 o clock position.
For Training Purposes Only
CSD COOLER
LINE OIL
FILTER
HOUS-
ENGINE FAN ING
CASE
HIGH OIL
TEMPERATURE
SWITCH FWD
DESCRIPTION OPERATION
Hydraulic System
The constant speed drive consists of two positive displacement axial slipper Disconnect
piston-type hydraulics units and mechanical axial geared differential which per- The disconnect solenoid is activated by 28 volt dc from a guarded switch on
forms the speed summing function. One hydraulic unit is of fixed displacement the P5 panel. The normally closed contacts of the switch connect a ground to
and the other one is a variable displacement type. the disconnect solenoid; thus both sides of the coil are grounded to prevent the
The hydraulic system consists of the charge pump, the scavenge pump and possibility of voltage pickup and inadvertantly tripping the CSD. A second sec-
the charge relief valve. The charge pump is located in the system between the tion of this switch - provides 28 volt dc to the trip coil of the generator control
all-attitude reservoir and the transmission. It supplies oil to the hydraulic units, relay, tripping off the generator field. The CSD re-connection is by an external
governor, control piston and the lubricating system. The charge pump forces reset handle.
the oil through the charge filter which incorporates a differential indicator (not NOTE: Diconnect of the CSD is allowed only, when Engine is running. Re-con-
used). Connected to the charge line is a low oil pressure switch which operates nect is allowed only, on a stopped Engine.
at 120-160 psi. The scavenge pump is located in the system between the
transmission sump and the external oil cooler. The scavenge pump picks up An overrunning clutch is provided in the output shaft permitting the generator to
lube oil and internal leakage and pumps it through the external oil cooler into motor freely at rotational speeds above that of the drive output.
the all-attitude reservoir Temperature Monitoring
Governor Heat produced by the transmission is absorbed by the oil in the unit and dissi-
The governor is a spring-biased, flyweight operated sleeve valve. It functions pated in an oil cooler at the fwd end of the engine. The hot oil passes through
to control porting of charge oil to the control cylinder. The rotating sleeve valve an external filter (Scavenge Filter) then trough the cooler.
is driven by the output gear and hence is responsive to transmission output Two variable resistance temperature bulbs measure the oil temperature on ei-
speed. Flyweights pivoted on this sleeve move a valve stem located within the ther side of the oil cooler. One bulb measures the input oil temperature to the
sleeve against the bias of a spring. The valve allows Increasing or decreasing CSD and is read on a meter on P5 panel. A switch on the panel alters the cir-
oil pressure application to the control cylinder which in turn controls the variable cuit to include the oil out temperature bulb so that the meter can indicate the
displacement hydraulic unit. rise in oil temperature through the CSD.
Normal temperature rise of the oil through the transmission is about 10 0C at
continuous full load with an inlet oil temperature of about 80 0C - 90 0C (Nor-
For Training Purposes Only
mal) at normal input speeds. The oil in the transmission serves as a lubricant,
as a coolant and as the hydraulic medium of the drive.
The oil returning from the cooler is deaerated in a swirl chamber in the reser-
voir. If the temperature of the oil reaches 157 0C a thermo switch in the in-line
closes illuminating the HIGH OIL TEMP light on the P5 panel.
A vent valve is provided to prevent negative pressure and retain positive pres-
sure. Oil quantity is indicated by a sight gage.
RESET HANDLE
1 2
AXIAL GEAR LOW OIL STANDBY LOW OIL
DIFFERENTIAL PRESSURE PWR OFF PRESSURE
INPUT SPLINE 4300 - 8600 RPM 6000 RPM TO HIGH OIL HIGH OIL
STANDBY POWER
IN ACCESSORY DISCONNECT GENERATOR TEMP TEMP
GEAR BOX DRIVE
SPLINE
CAVITY
PRESSURE CASE
FILL CHECK DRAIN &
VALVE MAGNETIC
FIRE MASTER
PLUG
WARN CAUTION
PUSH TO RESET PUSH TO RESET
ELEC
SUPPLY CHARGE
PRESSURE
CONTROL
PRESSURE RETURN OIL
-0+
DC +50 400
-50 CPS
FREQ 420
110 120
GOVERNOR 20
ADJUSTMENT 100 AC 130
DC VOLTS 40 0 VOLTS 30
SCREW
ADJUSTMENT
CAP
TR 1 APU GEN
BAT TR 2 GEN 1 GEN 2
BAT GRD
TR 3 TEST
BUS PWR
GOVERNOR
For Training Purposes Only
ADJUSTMENT
SCREW
ADJUSTMENT
SCREW
O-RING 1 TURN = 14 Hz
ADJUSTMENT CAP
24-20 AC GENERATION
GENERAL
The ac generation system consists of generators, manual controls, generator Each of the GCU’s (and also the bus protection panel - BPP) contains a trans-
control relays (GCR), generator control units (GCU), main power circuit break- former rectifier unit (TRU). The TRU converts the 3-phase ac power to 28 volt
ers (GB) and annunciator lights. dc power for the control and protection circuits during normal system operation.
If the ac power is not available or the TRU has failed, the power for the control
AC Generator with CSD
and protection circuits is available from the switched hot battery bus. With
A rotating electromagnetic field causes the output voltage - three phase electri- the battery switch in ON position the switched hot battery bus is con-
cal power at 115 volts and a constant frequency of 400 Hz- to be induced in the nected to the three GCU‘s and the BPP as a back-up power for each of the TR
stationary generator armature. The engine-driven generators are driven by units.
CSD’s. A complete generator assembly consists of an ac exciter generator, a
rotating rectifier and a main generator. Generator Breaker
The generator breakers connect the 115 volt ac, 400 Hz, 3-phase power to the
AC Generator/VSCF (Variable Speed Constant Frequency)
distribution system from the engine and APU generators.
The VSCF is interchangeable with the CSD and generator assembly. The
VSCF gets power from a variable speed shaft on the accessory gearbox on the Annunciator Lights
engine. It converts this to three phase electrical power at 115 volts and a The annunciator lights indicate the situation of the ac system and the genera-
constant frequency of 400 Hz. tors.
Generator Manual Controls
Manual controls and monitoring devices for the electrical power system are on
the forward overhead panel P5. The switches for latching contactors are mo-
mentary. There is an ac ammeter for each engine. The ac voltmeter and fre-
quency meter monitor various systems as determined by the selector switches
below the meters.
Generator Control Relay (GCR)
The GCR, located in the generator control unit, energizes the generator field.
For Training Purposes Only
The GCR and the generator field circuit are normally closed. The GCR’s may
be opened or closed by the GEN switches on the pilot’s forward overhead
panel P5 or opened by signals from the GCU protection circuits.
APU
EXT GEN
PWR
EPC 1 EPC 2
For Training Purposes Only
APU GB 1 APU GB 2
GB 1 GB 2
XFER XFER
RLY 1 RLY 2
CL = CLOSE SIGNAL
TR = TRIP SIGNAL
AC GENERATOR / CSD
General Temperatur Compensation
A rotating electromagnetic field causes the output voltage to be induced in the The thermistor, mounted on the exciter frame, has an inverse temperature re-
stationary generator armature. This rotating field is excited by an integral ac sistance characteristic. The high resistance at low or normal ambient tempera-
exciter, in which the output is converted to dc by rectifiers in the generator rotor ture blocks current flow in one of the parallel wires and causes the overall
shaft. The engine-driven generators are driven by CSDs. A complete generator shunt field resistance to be about that of the remaining single wire. At the
assembly consists of an ac exciter generator, a rotating rectifier and a main higher temperature resulting from normal operation, the resistance of each
generator. The ac exciter consists of a six-pole stationary dc field and a rotat- single wire increases to approximately double. At the same time, the resistance
ing armature. of the thermistor drops to a negligible value permitting approximately equal cur-
rent to flow in each wire. The combined resistance of the two parallel wires at
Operation higher temperatures is approximately equal to that of the single wire at low
The operation of the unit is as follows: temperature, temperature compensation is thereby provided.
(1) The exciter field is supplied dc power from the voltage regulator. This
Permanent Magnets (PM)
causes a three-phase voltage in the exciter armature. The ac voltage is recti-
fied and fed to the ac generator rotating field. This field generates the useful ac Six permanent magnets are mounted on the exciter frame between the six sta-
output voltage in the ac generator stator. tor poles. These magnets, alternately reversed in polarity, provide a built-in
residual voltage which results in main generator voltage build-up and elimi-
(2) The exciter stator has a shunt field winding connected between terminals F
nates the need for field flashing or for a starting relay.
and A.
(3) Current supplied by the voltage regulator to the shunt field winding provides Generator Cooling
excitation for the exciter generator. The current controls the exciter output to Generator cooling is by ducting engine fan air from an air outlet on the engine
the main ac generator. The shunt field winding consists of two wires wound in through the generator. During both ground and inflight operation, air which has
parallel in six series coils mounted on the six main poles. The coils are alter- passed through the generator is directed overboard through an air exit in the
nately reversed in polarity over the six poles, on one end both insulated wires engine cowling.
are connected to a common F terminal. On the opposite end, one wire is con-
nected directly to the A terminal and the other wire is connected through a
thermistor to the A terminal.
For Training Purposes Only
CURRENT TO GCU DP F
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
TRANSFORMER
CT PM
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
T4 T5 T6
ROTOR DC EXCITER
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
110 STATOR
120 C
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
STATOR
100 AC
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ
VOLTS 130
0 30 T1 T2 T3 T
OA OB OC PM PM NTC
THERMISTOR
POWER LIMITING GENERATOR A
METERING
GENERATOR
AMMETER
OF DETECTOR TRIP GB
UF
For Training Purposes Only
CLOSE TRIP TR
FROM CT
DP
TRIP GCR + GB
DETECTOR POWER
GEN BKR 1
SUPPLY
CONTROL
GB SW. MT TRIP GCR + GB CIRCUITS
OFF
115V AC GENERATOR CONTROL UNIT
GEN BUS 1
VSCF
General
The VSCF (Variable Speed Constant Frequency) changes mechanical energy
from a variable speed shaft on the accessory gearbox to constant frequency
electrical power.
The VSCF is on the left side of the engine at the 8 o’clock position. A quick at-
tach-detach (QAD) adapter kit holds the VSCF to the front of the accessory
gearbox.
The VSCF is interchangeable with the constant speed drive and generator as-
sembly.
The VSCF weighs approximately 140 pounds (63.5 kg).
A Built In Test (BIT) feature is included in the VSCF unit. Fault data are displayed
by two red LED’s located adjacent to a test toggle-switch or two test push-buttons.
For Training Purposes Only
CURRENT
TRANSFORMER
LEADS
POWER AND BIT
EXCITATION NEUTRAL SWITCH
LEADS TERMINALS
MAIN
CONNECTOR BIT
CASE BUTTONS
BIT
LIGHTS PRESSURE-FILL
VALVE
BIT
LIGHTS
INPUT
SHAFT
LOCK-
VSCF GENERATOR/CONVERTER
WIRE
OVERFILL
DRAIN
COOLING FITTING
AIR SIGHT
GLASS
For Training Purposes Only
INLET
AC GENERATOR / VSCF
General Generator Converter Control Unit (GCCU)
The variable speed constant frequency generator/converter (VSCF) is inter- The generator converter control unit (GCCU) uses a microprocessor to oper-
changeable with the CSD and generator assembly. The VSCF gets power ate. It gets power from the permanent magnet generator (PMG) in the genera-
from a variable speed shaft on the accessory gearbox on the engine. It con- tor housing. The GCCU has two important functions:
verts this to three phase electrical power at 115 volts and a constant frequency (a) The GCCU controls the generator and the inverter.
of 400 Hz.
S The voltage regulator in the GCCU sends a signal to the field of the genera-
Components tor to control the generator output voltage.
These are the components of the VSCF: S The GCCU also controls the output transistors in the inverter. It makes
them come on and go off at the correct times to make the output voltage
(1) The generator converts shaft energy at variable speeds to three phase
waveform.
electrical power at 115 volts. The output frequency of the generator depends
on the engine speed; it varies from 1370 to 2545 Hz. (b) The GCCU also monitors the operation of the VSCF.
(2) The dc filter rectifies the generator output to 270 volts dc. The dc filter also S The GCCU monitors the dc link voltage from the dc filter. It uses this signal
uses large capacitors to remove the ripple from the dc link voltage. to control the generator output voltage.
(3) The inverter uses six large transistors to convert the dc link voltage to a S The GCCU monitors the generator output voltage. It uses this signal as
three phase, pulse-width modulated (PWM) waveform. Inside the inverter is feedback for the voltage regulator.
the neutral forming transformer. This adds a neutral lead to the three-wire out- S The GCCU monitors the operation of the internal circuitry of the VSCF. The
put of the transistors. The neutral forming transformer permits the transistors GCCU looks for failures and stores failure data for use during BIT testing.
to equally share a load that is not balanced. S The GCCU monitors the output of the VSCF through the CT/EMI filter. This
(4)The ac filter uses capacitors to change the PWM waveform from the inverter information helps the GCCU find failures that are external to the VSCF.
to a three phase sinusoid at 115 volts and 400 Hz.
(5)The current transformer/electromagnetic interference (CT/EMI) filter moni-
tors the output current of the VSCF. It also removes unwanted signals from the
VSCF output.
For Training Purposes Only
OUTPUT:
INPUT: 3-PHASE, 4-WIRE,
VARIABLE SPEED 115 VOLT, 400 HZ
SHAFT POWER 60 KVA ELECTRICAL
FROM THE 3-PHASE POWER
ACCESSORY 3-WIRE
GEARBOX ON 115V AC 3-PHASE
270V DC 3-PHASE
THE ENGINE 1370 TO 4-WIRE
(DC LINK PWM
2545 HZ VOLTAGE) 115V AC
WAVEFORM
400 HZ
A
DC FILTER CT/EMI B
GENERATOR INVERTER AC FILTER
(RECTIFIER) FILTER C
N
DC LINK
FIELD
VOLTAGE
EXCITATION OUTPUT
SIGNAL
FROM THE TRANSISTOR
AND
POWER VOLTAGE CONTROL
INVERTER
SUPPLY REGULATOR
STATUS
FROM
PMG
GENERATOR
For Training Purposes Only
OUTPUT
SIGNAL VSCF
OUTPUT
SIGNAL
GCCU
CONTROLS,
MONITORS,
BIT
Figure 33 VSCF - Block Diagram
FRA US/E do/ur 17.11.99 Page: 67
Lufthansa Technical Training
ELECTRICAL POWER 737-300/400/500
AC GENERATION
24-20
MAIN
CONNECTOR
GCCU
CT/EMI FILTER
AC FILTER
DC FILTER
AIR
OUTLET
DUCT BIT
SWITCH
OIL PUMP
GENERATOR
HEAT
For Training Purposes Only
EXCHANGER
GEARBOX
INVERTER
Figure 34 VSCF Components
FRA US/E ur 17.11.99 Page: 69
Lufthansa Technical Training
ELECTRICAL POWER 737-300/400/500
AC GENERATION
24-20
VSCF SERVICING
General NOTE: Leakage of the seal in the VSCF will let oil flow from the VSCF to the
A sight glass on the VSCF shows the oil level in the VSCF oil system. A stand- spline cavity. The input shaft seal can be defective if these two indications oc-
pipe on the accessory gearbox on each engine shows the oil level in the spline cur after you fill the VSCF with oil:
cavity. S The oil level in the VSCF decreases.
The oil quantity of the VSCF is 6 pints. The oil quantity of the external system S The oil level in the spline cavity increases.
is 2.75 pints. The total oil quantity for the VSCF oil system is 8,75 pints for
each engine.
VSCF Oil Fill Procedure
VSCF Oil Level Check
Make sure that you have the correct oil for the VSCF.
The VSCF sight glass has different ranges for the oil level on the left and right
S Remove the cap from the case pressure-fill valve.
engines. This is because the left and right engines are at different angles.
S ON VSCFs WITH OVERFILL DRAIN FITTINGS, remove the overfill drain
S After engine shutdown allow 15 minutes to elapse before checking VSCF oil
fitting if you did not do this before.
level.
S Connect the coupling to the case pressure-fill valve.
S Release the pressure from the VSCF by the Vaccum Break Valve
(if installed). S Set the pressure from the service cart to 5-40 psig.
S ON VSCFs WITH OVERFILL DRAIN FITTINGS, remove the overfill drain CAUTION: DO NOT PUT TOO MUCH OIL INTO THE GENERATOR
fitting. DRIVE. TOO MUCH OIL WILL CAUSE THE GENERATOR
NOTE: If you do not release the air pressure, the sight glass can show an in- DRIVE TO BECOME TOO HOT AND CAUSE DAMAGE TO
correct oil level. THE GENERATOR DRIVE.
S Fill the VSCF until the oil level increases to the middle of the NORMAL
WARNING: REMOVE THE OVERFILL DRAIN FITTING SLOWLY. HOT
range on the sight glass. If you replaced the VSCF, motor the engine (with-
GAS OR OIL CAN COME OUT WHEN THE ENGINE IS HOT.
out fuel) for 1 minute.
HOT GAS OR OIL CAN BURN YOU.
S Permit five minutes for the oil level to become stable.
CAUTION: DO NOT REMOVE THE VACUUM BREAK VALVE FROM THE
S Look at the oil level in the sight glass on the VSCF.
VSCF. IF YOU REMOVE THE VACUUM BREAK VALVE, YOU
CAN DAMAGE THE VSCF. - If the oil level is below the bottom of the applicable range, add oil to the
VSCF.
For Training Purposes Only
CASE
PRESSURE-FILL
VALVE
ADD
OVERFILL
DRAIN
FITTING 1
FULL
A (LEFT ENGINE)
SEE
ADD
For Training Purposes Only
SIGHT GLASS A
VSCF
VSCF
ACCESSORY
STANDPIPE ACCESSORY
GEAR BOX
GEARBOX
For Training Purposes Only
SPLINE CAVITY
DRAIN FITTING
AND CAP
SEE A
SPLINE CAVITY
DRAIN FITTING
CAP SPLINE CAVITY
A DRAIN FITTING
ENGINE
(LEFT SIDE) SPLINE CAVITY
Figure 36 VSCF - Wet Pad Cavity
FRA US/E ur 17.11.99 Page: 73
Lufthansa Technical Training
ELECTRICAL POWER 737-300/400/500
AC GENERATION
24-20
GENERATOR BREAKER
Purpose Monitor
The two engine generator breakers connect 115 volt ac, 400 Hz, 3-phase The breaker position is monitored by the amber BUS OFF and blue GEN OFF
power to the distribution system from the engine generators. BUS lights on the P5-4 panel
ENGINE GENERATOR
BREAKER 1
ACCESS
ENGINE GENERATOR PANEL
BREAKER 2
AC LEAD (6)
ACCESS
PANEL CONNECTOR
ATTACHMENT
(4 PLACES)
FWD
TYPICAL GENERATOR BREAKERS
115/200 V AC
3
For Training Purposes Only
CLOSE
SPRING
TRIP
Engine Shutdown
The overfrequency and unterfrequency circuits are set to operate at 425 to 435
Hertz and 360 to 370 Hertz respectively. A time delay 0.25 to 0.60 second pre-
vents transients from the generator causing the GB to trip. The circuit also pro-
vides for a lockout of undervoltage protection during normal shutdown of the
For Training Purposes Only
system.
When an engine is shut down, the engine-driven generator will reach an under-
freuency condition there tripping the GB and disconnecting the generator from
the load bus.
CSD FIRE
ANNUNCIATOR DISC HANDLE
PANEL M238 SWITCH
GEN 1
FF MT BACK - UP
FROM BATTERY
(BAT SW. ON)
HV LV ON
OFF
GENERATOR
CONTROL + SWITCH
DC PROTECTION
POWER CIRCUITS
SUPPLY TRIP
VOLTAGE
REGULATOR CLOSE
GCR FIELD
EXCITATION
CONTROL
CIRCUITS
AC
GENERATOR
CONTROL UNIT
(GCU) GENERATOR
AC
115 /
For Training Purposes Only
200 V AC DC
POR PERMANENT
TO GEN MAGNETS
BUS
RECTIFYING
GENERATOR 6000 RPM DIODES
BREAKER (GB) INPUT FROM
CSD
VOLT F FREQUENCY
METER V METER
BUS TRANS
115V AC O A
GEN 1 F U
OV - OVER VOLTAGE OA TRANSFER T TRANSFER
F
UV - UNDER VOLTAGE OB BUS OFF O BUS OFF
OF - OVER FREQUENCY BUS BUS
UF - UNDER FREQUENCY OC L7 OFF OFF
DP - DIFFERENTIAL PROTECTION
OC - OVER CURRENT GEN OFF APU GEN GEN OFF
L8
BUS OFF BUS BUS
TR
OFF OFF
S3
CONTROL ON ON
28V DC POWER GEN 1 APU GEN GEN 2
SWITCHED CONTROL SUPPLY APU
HOT BAT BUS GENERATOR 1
(P6-4) P5-4 AC SYSTEM GENERATOR AND APU PANEL
TRIP
P6 LOAD CONTROL - RIGHT
TRIP
OA
OB 115V AC
CSD DISCONNECT K602 GCR CLOSE GEN BUS 1
LOCKOUT OC
OFF
K603 GCR
TO M400 OC
DP
R349 XFR
OV CONT RLY 1
NORM TRIP UV
VOLTAGE TO M238
FIRE ANN LTS
BUILD UP MASTER
RELAY ENG 1 FIRE MDL MAN CAUTION
ON TRIP LT TO APU
HANDLE A
S3 GEN 1 SW RESET DIFFERENTIAL
PROTECTION MASTER TEST
K601 A
GRD POWER TO VOLTAGE PRESS TO TEST
SWITCH EPC
REGULATOR CLOSE
EPC 1 CONTROL MASTER DIM L7 BUS 1 OFF LIGHT
APU GEN
SWITCH APU
APU GB 1
GB
CLOSE
B
APU GEN DIFF
NC BKR 1 PROT
K801 PR B
TO R349
For Training Purposes Only
K1 GEN 1
RELAY TRANSFER L8 GEN 1 OFF BUS LIGHT
CONTROL
RELAY P5-4 AC SYSTEM GENERATOR AND
P5-4 AC SYSTEM GEN AND APU PANEL
APU PANEL TEST
POINT
K3/K4 EXTERNAL
POWER CONTACTOR 1
OF MANUAL TRIP OR EP TRIP
NOTE: GENERATOR 1 SCHEMATIC SHOWN.
UF APU GB TRIP GENERATOR 2 APU GENERATOR
28V DC TRIP SCHEMATICS SIMILAR.
LOGIC TO GCU 2
K604 GB TRIP CLOSE
CONTROL
G5 APU GEN GENERATOR BREAKER 1
CONT UNIT G3 GENERATOR CONTROL UNIT 1 (P6) (RIGHT SIDE-NOSE
WHEEL WELL)
BUS TRANSFER
General For Example (Bus Transfer Switch in OFF position):
Each Transfer Bus has an associated Transfer Relay which automatically se- S If the Bus Transfer Switch has been switched to the OFF position (in case
lects the opposite Generator Bus as a power supply if its normal Generator Bus of smoke procedure), the TR 3 Disconnect Relay is deenergized and there-
fails and the Transfer Switch is in AUTO position. fore the parallel switching of DC Bus No.1 and DC Bus No. 2 is eliminated.
When a Generator fails, the Alternate coils of the Transfer Relays can not
Transfer Relays be energized and the respective Transfer Bus is isolated.
The Transfer Relays No. 1 and No. 2 are located in the P6 panel. The Relay
contacts have three positions:
S Normal
S Alternate
S Off
The position of the contacts is controlled by auxiliary contacts of the GB’s or
EPC’s, Transfer Control Relays and the position of the Bus Transfer Switch.
Normal Operation
During normal operation,
S Generator No. 1 powers Generator Bus No. 1 through closed GB 1. The
Generator Bus No. 1 supplies over the Transfer Relay No. 1 (Norm coil en-
ergized) Transfer Bus No. 1.
S Generator No. 2 powers Generator Bus No. 2 through closed GB 2. The
Generator Bus No. 2 supplies over the Transfer Relay No. 2 (Norm coil en-
ergized) Transfer Bus No. 2.
Alternate Operation
If one Generator fails, the respective GB trips and the associated Transfer
For Training Purposes Only
Relay Alternate coil will be energized. The respective Transfer Bus is supplied
by the still powered Generator Bus from the other side (Bus Transfer Switch
must be in AUTO position).
For Example (Bus Transfer Switch in AUTO position):
S If Generator No.1 fails, the GB 1 trips and the Gen Bus No.1 looses the
power. The Norm coil of Transfer Relay 1 will be deenergized and the Alter-
nate coil is being energized. The Transfer Bus No.1 is supplied by the Gen
Bus No. 2.
TRANSFER TRANSFER
RELAY BUS TRANSFER RELAY
NO. 1 NO. 2
BAT CHARGER
TRANSFER
TR 1 TR 2 TR 3
For Training Purposes Only
TR 3 DISCONNECT
DC BUS 1 RELAY DC BUS 2
energized. TRANSFER BUS OFF light for Transfer Bus No. 2 extinguishes
when normal or alternate coil of Transfer Relay 2 is energized.
TRANSFER
CONTROL-1
TRANSFER NORM
CONTROL-2
TO
P6-4 CIRCUIT BREAKER PANEL FROM 115V AC
115V AC TRANSFER
DC BUS IND GEN BUS BUS 1
28V DC TRANSFER
BAT BUS
DC BUS
INDICATION BAT TO BUS
OFF LT
P6-5 CIRCUIT BREAKER PANEL
ALT
0.25 S
MCD&T
A
A MCD&T
R3 TRANSFER RELAY 1
L6 TRANSFER BUS 1 DPR 1
OFF LIGHT
XFR CONT ENG GB1 28V DC
BUS TRANS RLY R349
A TO BAT 115V AC
O U G3 GENERATOR CONTROL UNIT 1
F CHARGER POWER
TRANSFER T TRANSFER
BUS OFF F O BUS OFF
EPC1
BUS BUS
OFF OFF
GEN OFF APU GEN GEN OFF APU GB1
BUS OFF BUS BUS R89 BATTERY CHARGER
TRANSFER RELAY
MCD&T
A
A MCD&T
TO 28V DC TO 28V DC
L2 TRANSFER BUS 2 BUS 1 BUS 2
OFF LIGHT
NORM
R9 TR 3 DISCONNECT
AUTO RELAY TO
FROM
TO BUS 115V AC 115V AC
OFF LT GEN BUS TRANSFER
For Training Purposes Only
BUS 2
0.25 S
OFF
S2 BUS TRANSFER DPR 1
SWITCH ALT
P5-4 AC SYSTEM GENERATOR AND APU PANEL XFR CONT ENG GB2
28V DC
RLY R350
APU GB2
28 VDC
28 VDC GCU 2
GCU 1
For Training Purposes Only
K1-3
SEAL-IN RELAY
P5-4
APU SPEED
SWITCH 95 %
28V DC
NO. 1 GEN TRIP
CONT
VOLTAGE FIELD
NORM POWER EXCITER
REG SUPPLY XFMR
GEN TEST
ON
OVER
OC CURRENT
DETECTOR
S3 GEN 1 SW NC AC PWR TEST
TO GEN 1 LOADS
DPR 2
T4 DIFF CUR XFMR (P6)
DP
DPR 1 NOTE:
____ GENERATOR 1 SCHEMATIC SHOWN. GENERATOR 2 AND APU
GENERATOR SCHEMATICS SIMILAR.
G3 GENERATOR 1 CONTROL UNIT 1 (P6)
28V DC
NO. 1 GEN TRIP
CONT DP
SINGALS
CONTROL F
P6-4 CIRCUIT BRK PNL CLOSE GCR
POWER CONTROL
SUPPLY K603 GCR
K901 BR A
VOLTAGE FIELD
NORM EXCITER
REG POWER
SUPPLY XFMR
ON GEN TEST
OVER
OC CURRENT
DETECTOR
S3 GEN 1 SW NC AC PWR TEST
T1
T7 CUR XFMR ASSY (LOWER 41 CEILING) DIFF
1 2 34 CUR
VSCF XFMR
TRIP
GENERATOR/
CONVERTER
115V AC
GEN BUS 1 1 1
(TYPICAL) 2 2
CLOSE
GEN 1 3 3
LOAD CB
OA OB OC 4 4
TO C801
GEN BKR 1 C801 GEN BKR 1
ENG 1
TO GEN 1 LOADS
For Training Purposes Only
DPR 2
T4 DIFF CUR XFMR (P6)
DP
NOTE:
____ GENERATOR 1 SCHEMATIC SHOWN.
DPR 1 GENERATOR 2 SCHEMATIC SIMILAR.
G3 GENERATOR 1 CONTROL UNIT 1 (P6)
APU ACCESSORY
GEAR DRIVE
GENERATOR
POWER FEEDER
LEAD CONNECTOR
For Training Purposes Only
FROM
GENERATOR
ENGINE DIFF. CURRENT TRANSFORMER APU DIFF. CURRENT TRANSFORMER LOAD DIFF. CURRENT TRANSFORMER
If a VSCF is installed, the GCU is still in use and controls the respective Gener-
ator Control Relay (GCR) and the Generator Breaker (GB).
Voltage Regulation CSD/GEN
If a CSD/Generator is installed, the Generator delivers Residual Volts
(ca. 18 V) when the GCR is open and the Engine is running. When GCR is
closed, the Generator will be excited and the exciting voltage is regulated by
the Voltage Regulator (VR) in the GCU.
CSD/GEN VSCF
APU
EP
For Training Purposes Only
Operation
The VSCF uses MIL-L-7808 or MIL-L-23699 oil for cooling and lubrication.
The oil also gives viscous damping for the generator bearings to reduce vibra-
tion.
The oil pump is inside the generator case. It causes 2.0 to 4.5 gallons (7.6 to
17.0 liters) of oil to flow each minute. The flow rate is related to the engine
speed.
The generator shaft turns the oil pump through a set of gears at a ratio of 1 to
2.27. This keeps the speed of the oil pump below 12,000 rpm. The oil pump
keeps approximately 30 psig (207 kPa) of pressure in the oil system. If the oil
For Training Purposes Only
system becomes blocked, the bypass valve opens at approximately 250 psig
(1,724 kPa). This prevents damage to the oil pump.
CT/EMI
GCCU
DC FILTER AC FILTER
CASE
AIR/OIL HEAT PRESSURE-
FILL
EXCHANGER VALVE
TO GEN DRIVE OIL AIR
TEMP METERS T
EXHAUST
ON P5-5 LOW OIL
PRESSURE
SWITCH
OIL-OUT GENERATOR
TEMPERATURE STATOR TO LOW OIL
SENSOR PRESSURE
ENGINE- OIL LIGHT ON
ACCESSORY SPEED GENERATOR
BYPASS P5-5
GEAR-BOX INCREASER ROTOR PUMP
VALVE
250 PSI SIGHT
GLASS
INVERTER HOUSING
AND OIL RESERVOIR
TO GEN DRIVE OIL
TEMP METERS T OVERFILL
ON P5-5 DRAIN FITTING
CASE VSCF GENERATOR/CONVERTER
For Training Purposes Only
OIL-IN DRAIN
TEMPERATURE PLUG
SENSOR
COOL AIR TO HIGH OIL LINE
OIL FILTER POP-OUT
FROM THE TEMP LIGHT BUTTON
FAN DUCT ON P5-5 OIL COOLER
OIL
OVERHEAT
OIL SWITCH
315 F (157 C)
AIR
1 VSCF SYSTEM
POR POR
US 1 = < 50% N2
US 2 = < 55% N2 CONV
G
FREQ
2 CONTR
CURRENT FLOW =
GB IS CLOSED GB
SPEED
SWITCH 2
TABLE:
1+2 CURRENT
SENSE 0V: GFS OPEN
1 SEE VOLTAGE 8V: GFS CLOSE AND INTERNAL FAIL
TABLE CONTROL
18V: GFS CLOSE AND INTERNAL FAIL
AND GCR/GB OPEN
115V: GFS CLOSE AND INTERNAL FAIL
8V
AND (GCR CLOSE OR VR FAIL)
REF 18 V
115 V
GFS
For Training Purposes Only
GCR VR
BIAS GCR OPEN/CLOSE
A
FILTER F
VSCF
GCU
VSCF OPERATION
Operation During Engine Start
1. At 20 to 30% N2, there is enough voltage from the PMG to operate the
GCCU. At 45 to 50% N2, the GCCU commands the inverter to create 15 to
20 volts (phase to neutral) at 360 Hz. This simulates the residual voltage
from the CSD/generator operation.
2. The GCCU now looks at the input from the voltage regulator in the
GCU.
- (a) If there is less than 5 volts dc, the GCCU knows that the GCR
in the GCU is open. The voltage stays at 15-20 V and 360 Hz
until the GCR closes.
- (b) If there is more than 5 volts dc, the GCCU knows that the GCR
in the GCU is closed. Then, at approximately 50% N2, the GCCU
controls the voltage to 115 V and 400 Hz. Now, you can push
the GEN switch to connect the VSCF to the ac buses.
Operation During Engine Shutdown
1. When the engine speed decreases to about 50% N2, the GCCU controls
the frequency back to 360 Hz. The voltage stays at 115 volts. Then,
the GCU will see an underfrequency condition and opens the generator
breaker.
2. At 45 to 50% N2, the GCCU sees a generator underspeed condition.
Then, it disconnects the generator field and stops the inverter.
3. At 20 to 30% N2, the PMG voltage is too low to operate the GCCU and the
GCCU stops.
For Training Purposes Only
1 VSCF SYSTEM
POR POR
US 1 = < 50% N2
US 2 = < 55% N2 CONV
G
FREQ
2 CONTR
CURRENT FLOW =
GB IS CLOSED GB
SPEED
SWITCH 2
TABLE:
1+2 CURRENT
SENSE 0V: GFS OPEN
1 SEE VOLTAGE 8V: GFS CLOSE AND INTERNAL FAIL
TABLE CONTROL
18V: GFS CLOSE AND INTERNAL FAIL
AND GCR/GB OPEN
115V: GFS CLOSE AND INTERNAL FAIL
8V
AND (GCR CLOSE OR VR FAIL)
REF 18 V
115 V
GFS
For Training Purposes Only
GCR VR
BIAS GCR OPEN/CLOSE
A
FILTER F
VSCF
GCU
VSCF PROTECTION - After 2 to 3 seconds, the GCCU will try to set the VSCF voltage back to
15-20 volts again. NOTE: During the 2 to 3 seconds time, the VSCF
Operation During a Failure Condition voltage will be 5-10 volts.
1. The VSCF has built-in test (BIT) circuits. The microprocessor in the A. If the VSCF can operate, it will set the output voltage to 15-20 volts.
GCCU always monitors the operation of the VSCF. Then, the GCU will see a ”power ready” condition.
2. If a failure occurs in the VSCF, the GCCU stores data in the non-volatile Now, you can push the GEN switch to ON. The VSCF voltage will go to
memory (NVM). You can use this data in the shop to do trouble-shooting 115 volts and the GCR and the GB will close.
on the VSCF.
Subsequently, after you manually disconnect the VSCF (push the GEN
- The VSCF has a RS-232 serial port on the main connector. This per- switch to OFF or do a transfer to a different power source), the VSCF
mits you to use an ”IBM compatible PC” to get failure data from the NVM voltage will go to 8 volts and stay there.
in the GCCU.
B. If the VSCF can not operate, the output voltage will go to 8 volts and
3. The GCCU has protective functions which are also in the GCU. Thus, the stay there. The GCU will not see a ”power ready” condition and you can
GCU protective functions are back-ups for the GCCU protective functions. not manually connect the GB. When you push the GEN switch to ON,
These protective functions are: the GCR and the GB will not close.
- Overvoltage (130 +/- 3 volts) 5. If the voltage regulator in the GCU has a failure, the VSCF will keep the
- Undervoltage (100 +/- 3 volts) output voltage between 120 and 125 volts. The VSCF will not disconnect
- Overfrequency (430 +/- 5 Hz) in this case.
- Underfrequency (365 +/- 5 Hz) When you manually open the GB, the output voltage will go to 15-20
- Overcurrent (180.5 +/- 13.5 Amps) volts (Usually, it would stay at 115 volts). The GCU will see an undervol-
- Differential Protection (25 +/- 5 Amps) tage condition and energizes the ”LV” light.
4. If a failure occurs in the VSCF, these things occur: 6. The GCCU also has open phase protection. The open phase protection
operates when the low phase has less than 5 +/- 1 Amps and the next low-
- A bad VSCF will put a signal into the differential protection circuits. This est phase has more than 10 +/- 2 Amps.
will cause the GCU to energize the feeder fault (FF) light on the M238
annunciator panel. Then, the GCU will open the GCR and the GB. This A. This function is not in the GCU. Only the GCCU has the open phase
disconnects the VSCF from the ac buses. protection.
- The GCCU disconnects the generator field. This will make the VSCF B. If the GCCU finds an open phase, it sets a latch relay. When you push
output voltage go to 0 volts. the BIT switch to INDICATE, the AIRCRAFT OPEN PHASE DE-
For Training Purposes Only
Protective Funktion Conditions for Failure VSCF opens GB and Generator Field VSCF BIT light on Indication from the
energizes ”FF” light ? opened? GCU
VSCF Failure Internal problem Yes Yes (1) ”VSCF FAULT None
DETECTED”
Failure of the voltage re- Incorrect or missing No (2) No None ”LV” light (5)
gulator in the GCU waveform at ”F” lead
Overvoltage 130 +/- 3 V Yes Yes (1) ”VSCF FAULT ”HV” light & GB open (3)
DETECTED”
Undervoltage 100 +/- 3 V Yes Yes (1) ”VSCF FAULT ”LV” light & GB open (3)
DETECTED”
Overfrequency 430 +/- 5 Hz Yes Yes (1) ”VSCF FAULT GB open (3)
DETECTED”
Underfrequency 365 +/- 5 Hz Yes Yes (1) ”VSCF FAULT GB open (3)
DETECTED”
Overcurrent (4) 180,5 +/- 13,5 A Yes No None ”FF” light & GB open (3)
Differential Protection 25 +/- 5 A Yes Yes (1) None ”FF” light & GB open (3)
Open Phase <5 +/- 1 A on the Low- Yes No ”AIRCRAFT OPEN None
Phase PHASE DETECTED”
>10 +/- 2 A on the next
Phase
(1) = After 2 to 3 seconds, the generator field will connect again. If the VSCF
can operate, the voltage will go to 15 - 20 Volts; if the VSCF cannot oper-
ate, the voltage will go to 5 - 10 Volts.
(2) = The GB stays closed; the voltage goes to 120 - 125 volts.
For Training Purposes Only
(3) = The GCU will only do this function if the VSCF does not react first.
(4) = The GCU sets the overcurrent protection at 185 +/- 18 Amps
(5) = The GCU energizes The ”LV” light after you manually open the GB.
NOTE: The ”INDICATE” position is also used for an electrically reset of the
VSCF, if it has been disconnected by the CSD DISC switch on P5.
Lamp Test
The opposite switch - or the other pushbutton - is labeled ”LAMP TEST”, and
when the switch is in this position (normally done at first), the both LED’s must
illuminate.
M238
BIT TEST
SWITCH
SET RESET
24-30 DC GENERATION
GENERAL DESCRIPTION
Purpose
The 28 volt dc power is used for operation of the airplane systems. The power
is obtained from the battery and from conversion of ac power.
System Description
The system consists of a battery, three transformer rectifiers, battery charger,
static inverter, external dc power receptacle, relays, switches and busses.
Component Locations
The components associated with the dc power are located in the electronics
compartment (battery, transformer rectifiers, battery charger, static inverter,
external dc receptacle), on P5 panel (switches) and in P6 panel (sensor and
relays).
General Operation
If ac power is operating, the three transformer rectifiers (TRU 1, TRU 2 and
TRU 3) and battery charger supply the 28 volt dc power. The inverter converts
battery power to 115 volt ac for the standby system. The external dc is used for
starting APU if battery output is too low. The distribution system consists of a
hot battery bus, dc bus No. 1, dc bus No.2 and standby bus.
For Training Purposes Only
R9
TR 3
DISCONNECT
R41
GEN PWR
CONTROL
28V DC 28V DC 28V DC SWITCHED 28V DC 28V DC 28V DC 28V DC
BUS 1 ELEX BUS 1 HOT BAT BUS HOT BAT BUS BAT BUS BUS 2 ELEX BUS 2
For Training Purposes Only
BAT SWITCH
ON P5 (ON
POS- CONNECTS WDM STANDBY POWER
SWITCHED HOT 24-56-01 SWITCH ON P5
BAT BUS TO BATTERY (BAT POS- CONNECTS
BATTERY) BUS RELAYS HOT BAT BUS &
1 BUILD-IN THE 28V DC BAT BUS)
BUS PROTECTION
PANEL (BPP)
TR-UNIT
General
Three transformer-rectifier (TR) units provide 28-volt dc power by converting
115-volt ac power to 28-volt dc power. TR-units are on electrical equipment
shelf E3-1.
Distribution
The TR-unit No. 1 is supplied with 115-volt ac power from transfer bus No. 1
and supplies 28-volt dc to dc bus No. 1.
The TR-unit No. 2 is supplied with 115-volt ac power from transfer bus No. 2
and supplies 28-volt dc to dc bus No. 2.
The TR-unit No. 3 is supplied with 115-volt ac power from main bus No. 2 and
supplies 28-volt dc to battery bus and acts as a backup for TR-unit No.1 and
TR-unit No. 2.
For Training Purposes Only
STATIC
INVERTER
BATTERY
CHARGER
BATTERY
FWD
ELECTRONIC
COMPARTMENT
ACCESS DOOR
Relay energized/de-energized
S Battery Charger Transfer Relay R 89
For Training Purposes Only
1 1
115V AC + +
GROUND OUTPUT BATTERY EXTERNAL -
SERVICE - CHARGER POWER DC
BUS + BATTERY (J9) (J9) DC EXT PWR
- INTERLOCK RECP (J9)
BAT CHARGER
TR MODE CONT
115V AC R89 R 325 R 39 +TEMP SENSE
MAIN BAT CHARGER BATTERY APU START XFMR RECT
BUS 2 XFR (P6) OVERHEAT (P6) INTERLOCK
(P6) BAT CHG (E3-1)
ALT BAT
CHARGER 28V DC
+ HOT BAT BUS
HOT BATTERY BUS
115V AC
TRANSFER
BUS 2 -
TR UNIT 2
28V DC
NO. 2 ELEX ELEX BUS 2
BATTERY R328 STBY PWR
MAN (P6) R327 AUX TO DC BUS-UNSW
R1 (P6)
TO AMPERE 28V DC
METER BUS 2
DC BUS PWR
NO. 2
BUS TIE 2 BATTERY BUS 28V DC
TRANSFORMER RECTIFIER 2 CONTROL MAN ELEX BUS 1
(E3-1) (P6) NO. 1 ELEX
DC BUS-UNSW
28V DC
INTERNALS BUS 1
115V AC DC BUS PWR
TRANSFER SAME NO. 1 BATTERY BUS
BUS 1 AS DISCONNECT CONTROL
TR2 1 AUTO TO APU BAT SW
TR UNIT 1
AIR/GND INTLK.
TRANSFORMER NORMAL BUS TIE 2 R397 AUX STBY
RECTIFIER 1 PWR AUTO RELAY
(E3-1) R9 TR 3 DISC (P6) SWITCHED
(P6) HOT BAT BUS TO EXT PWR CONT RELAY
AUTO
28V DC
OFF OFF SWITCHED
GEN POWER HOT BAT BUS
115V AC INTERNALS RELAY
MAIN BAT CONTROL
SAME
BUS 2 AS STBY POWER
SW (P5) (P6)
TR2
For Training Purposes Only
TR UNIT 3
R41 GEN PWR CONT
TRANSFORMER ON (P6)
RECTIFIER 3
(E3-1) BAT SW (P5) 28V DC
P6 PANEL BAT BUS
R1 BAT BUS
AUTO (P6)
DC BUS BAT TRANSFER
BAT BUS IND TR 3 CONTROL
TO DC R2 BAT XFR
METERS (P6) R326 BAT BUS
R355 MAN (P6)
BAT BUS (P6)
Maintenance Practices
The nickel-cadmium battery must be serviced at regular intervals determined
by operating conditions. The quantity of water consumed by the battery is de-
termined by operating methods and ambient temperatures.
Electrolyte level rises when the battery charges and lower when the battery
discharges. Distilled or demineralized water should be added to battery cells
only when battery is fully charged.
For Training Purposes Only
T-R UNIT
NO. 1
T-R UNIT
NO. 2
T-R UNIT
NO. 3
BATTERY
CHARGER BATTERY
BATTERY AND
BATTERY SHIELD
SEE A
EXTERNAL DC POWER
CONNECTION PROCEDURE
1. OPEN BATTERY CHARGER CKT BRK
2. CONNECT EXT DC (24-28V)
3. CLOSE EXT POWER DC CKT BRK
DISCONNECT PROCEDURE
1. OPEN EXT POWER DC CKT BKR
2. CLOSE BATTERY CHARGER CKT BKR
3. DISCONNECT EXT DC
BATTERY M6
B
For Training Purposes Only
EXTERNAL POWER
SEE BREAKER TO BE
BATTERY B OPEN EXCEPT WHEN
EXTERNAL
SHIELD (J9) USING POWER
POWER SEE C EXTERNAL
RECEPTACLE BATTERY CHARGER RECEPTACLE
POWER
DC CIRCUIT BREAKER
CIRCUIT
BREAKER C
FWD
A
BATTERY SYSTEM
General Battery Bus
The battery is the alternative source of power to the battery bus. Battery bus It supplies for example:
control is automatic with manual override. Regardless of battery bus source or S most of the Indicating Lights
control, the battery switch must be set to ON to power the battery bus.
S Master Caution System
Operation S Fire Detection System
The battery bus is normally powered by the transformer rectifier unit No. 3 S Passenger Address amplifier
through battery bus relay R 355 which is energized with battery switch in ON S Standby Power System
position. The output of TR-unit No.3 powers relay R 2 bat transfer which de-
energized battery bus auto relay R 1 and battery bus manual relay R 326
(R 326 normally de-energized).
If the output of TR-unit No. 3 is not available, relay R 2 de-energized, relay R1
energized and the battery bus is powered from the hot battery bus. If the
standby power switch is in the BAT position, relay R 326 energizes, connecting
the hot battery bus to the battery bus.
S Clock
S Entry Lights - Dim
S AFC A & B Warning Light
S APU & Engine Generator Control
S Fueling & External Power Control
S Fuel Shut-Off Valve Indication
S IRS No. 1, 2
1 1
115V AC + +
GROUND OUTPUT BATTERY EXTERNAL -
SERVICE - CHARGER POWER DC
BUS + BATTERY (J9) (J9) DC EXT PWR
- INTERLOCK RECP (J9)
BAT CHARGER
TR MODE CONT
115V AC R89 R 325 R 39 +TEMP SENSE
MAIN BAT CHARGER BATTERY APU START XFMR RECT
BUS 2 XFR (P6) OVERHEAT (P6) INTERLOCK
(P6) BAT CHG (E3-1)
ALT BAT
CHARGER 28V DC
+ HOT BAT BUS
HOT BATTERY BUS
115V AC
TRANSFER
BUS 2 -
TR UNIT 2
28V DC
NO. 2 ELEX ELEX BUS 2
BATTERY R328 STBY PWR
MAN (P6) R327 AUX TO DC BUS-UNSW
R1 (P6)
TO AMPERE 28V DC
METER BUS 2
DC BUS PWR
NO. 2
BUS TIE 2 BATTERY BUS 28V DC
TRANSFORMER RECTIFIER 2 CONTROL MAN ELEX BUS 1
(E3-1) (P6) NO. 1 ELEX
DC BUS-UNSW
28V DC
INTERNALS BUS 1
115V AC DC BUS PWR
TRANSFER SAME NO. 1 BATTERY BUS
BUS 1 AS DISCONNECT CONTROL
TR2 1 AUTO TO APU BAT SW
TR UNIT 1
AIR/GND INTLK.
TRANSFORMER NORMAL BUS TIE 2 R397 AUX STBY
RECTIFIER 1 PWR AUTO RELAY
(E3-1) R9 TR 3 DISC (P6) SWITCHED
(P6) HOT BAT BUS TO EXT PWR CONT RELAY
AUTO
28V DC
OFF OFF SWITCHED
GEN POWER HOT BAT BUS
115V AC INTERNALS RELAY
MAIN BAT CONTROL
SAME
BUS 2 AS STBY POWER
SW (P5) (P6)
TR2
For Training Purposes Only
TR UNIT 3
R41 GEN PWR CONT
TRANSFORMER ON (P6)
RECTIFIER 3
(E3-1) BAT SW (P5) 28V DC
P6 PANEL BAT BUS
R1 BAT BUS
AUTO (P6)
DC BUS BAT TRANSFER
BAT BUS IND TR 3 CONTROL
TO DC R2 BAT XFR
METERS (P6) R326 BAT BUS
R355 MAN (P6)
BAT BUS (P6)
BATTERY CHARGER
General APU Interlock
The battery charger is a regulated system to charge nickel-cadmium storage - Airplanes with large (1kW) battery charger prior to line 2247:
batteries. It operates from 115-volt, 400 Hz, 3-phase power. The APU start interlock relay R 39 disconnects battery charger input
The battery charger is on shelf E3-1 in the electronic compartment. The bat- power when the APU start motor is turning. Input power is automatically
tery charger is capable of charging a completely discharged battery to 100 per- restored when the APU reaches starter cutout speed.
cent charge state within 75 minutes. the battery charger operates in the charge - Airplanes with large (1kW) battery charger prior to line 2247 with
mode or in the transformer-rectifier (T-R) mode. SB 24-1096:
The APU start interlock relay R 39 is used to lock battery charger in TR
Transformer-Rectifier Mode (constant voltage) mode while the APU start motor is turning. R 39 does
In the transformer-rectifier mode, the charger provides 28v dc to maintain bat- not remove input power from battery charger.
tery charge, and meets load demands on the battery bus. Internal current limit- - Airplanes with large (1kW) battery charger after line 2247:
ing circuitry reduces the output voltage to limit current to 60 amps. The APU start interlock relay R 39 is used to lock battery charger in TR
(constant voltage) mode while the APU start motor is turning. R 39 does
Charge Mode
not remove input power from battery charger.
In the charge mode, the battery charger delivers a constant current of 38 amps
to the battery. The output voltage will vary with battery state-of-charge and Battery Overheat
load resistance. When battery voltage reaches a threshold voltage, charging - Airplanes with large (40 AH) battery prior to line 2247:
stops. The threshold voltage is automatically temperature adjusted by a tem- The battery overheat relay R 325 disconnects battery charger input
perature sensor in the battery. power when the battery temperature exceeds 135 deg F.
Operation - Airplanes with large (40 AH) battery prior to line 2247 with SB 24-1096:
Battery overheat relay R 325 and related circuit breaker C 792 do not
The battery charger works with battery’s temperature sensor and interlock to
exist. The Battery overheat function is contained in the battery charger.
prevent battery damage. Charging stops if battery temperature is outside the
The battery charger monitors the temperature sensor in the battery. If
range, or if the battery is disconnected.
the battery temperature exceeds 145 deg F the battery charger will stop
The battery charger will switch to the transformer rectifier mode when the mode supplying 28 v dc to the battery. When the battery temperature drops
control loop is opened by any of the following: below 130 deg F, the battery charger will automatically start supplying
S Auxiliary relay to bat bus relay R 327 energizes due to loss of TRU 3 output. 28 v dc to the battery.
S Standby power manual relay R 328 energizes when STANDBY POWER
For Training Purposes Only
-0+
400
DC CPS
-50 +50 420
FREQ
110 120
20
AC
DC VOLTS 40 VOLTS 30
TR 1 APU GEN
BAT TR 2 GEN 1 GEN 2
ON ON
AC
E/E COMPARTMENT
ACCESS DOOR
AC AND DC METER PANEL (P5-13)
EXT PWR
CONTR R 348
EXT PWR
CONTR
GCU 2 (PR)
OFF R CTRL
APU GCU (PR) L CTRL
GROUND
POWER GCU 1 (PR)
SWITCH EPC 2
APU GB
CLOSE TRIP TRIP
CIRCUIT TRIP
28 V CLOSE
DC
BATT
SW ON APU GB 2 ENG GB 2
APU GCU
K1 K2 ON TRIP CLOSE EXT PWR TRIP
CONTROL TRIP TRIP
RELAY
P5 - 4 (EPCR) CLOSE
CONTROL AND PROTECTION CIRCUITRY
APU GB 1
ENG GB 1 EPC 1
NEGATIVE
SEQUENCE EPCR
DETECTOR SLAVE
RELAY EPC 2 AUX
K2
OVER
VOLTAGE Q7
ENTRY DETECTOR GEN
BUS 1 3 PHASE
LTS
GROUND
SERVICE
DRAIN UNDER EXT BUS
MAST ON PWR
VOLTAGE 7 +/- 2 SEC
HEATER DETECTOR BUS
R 47 GROUND R6
EXT PWR SERVICE GROUND
SENSING SWITCH SERVICE
F
For Training Purposes Only
REFUELING
POWER SELECT
E RELAY R 10
N (E3-3 RACK)
A EXTERNAL Q5 Q2
POWER REFUELING
B POWER CONTROL
TR UNIT 7 1/2 RELAY R 11
C
(E3-3 RACK)
28 V DC
SW HOT BAT BUS
BACKUP FUELING
EXTERNAL POWER (BAT SW ”ON”) CLOSE
PANEL
RECEPTACLE DOOR
OPEN SWITCH (P15)
ACCESS
EXTERNAL PWR
PANEL
CONTACTOR 1 AC LEAD (6)
CONNECTOR
EXTERNAL PWR
CONTACTOR 2
ACCESS
PANEL ATTACHMENT
(4 PLACES)
FWD
115/200 V AC
3
CLOSE
For Training Purposes Only
SPRING
TRIP
TRIP TRIP
R
115V AC TO EXT
WHEN EXT EXTERNAL POWER
POWER CONTACTORS 1 AND 2
POWER CONTROL NEAR NOSE WHEEL WELL
PLUG IS
EXTERNAL POWER EXTERNAL
ATTACHED
GRD SERVICE POWER BUS PROT
JUMPER (P6-12) PANEL AC (P6-12)
F
(PART
OF EXT TO LAV
POWER E MIRROR LTS
LAV MIRROR W
PLUG) EXT PWR (P6-3)
EXT POWER RCPT
L349 EXTERNAL POWER
P19 EXTERNAL POWER PANEL
NORM NOT IN USE (P19)
DC BUS PWR ON
115V AC
NO.1 NO.2 TR3 GEN BUS 1 115V AC
GND SERV BUS
OA CLOSE
PROTECTION
CIRCUITS GROUND POWER
OV UV NSV AVAILABLE LIGHT
P5-5
CLOSE
BACK - UP
FROM BATTERY
(BAT SW. ON)
ON
EXTERNAL
PWR OFF
+ 28V DC
TR UNIT
(PWR SUPPLY)
ON
OFF
GND PWR
CONTROL SWITCH
AND
PROTECTION
CIRCUITRY EPCR LO-
GIC
ENG GB 1,2
APU GB 1,2
EPC TRIP
BUS CONTROL
PROTECTION
PANEL
EXTERNAL A B C N F E
POWER
For Training Purposes Only
RECEPTACLE
TO GEN 115/200 V AC
BUS 1
EPC1
GROUND
TO GEN
POWER
BUS 2
UNIT
EPC2
Figure 60 Bus Protection Panel (BBP)
FRA US/E do/ur 11.11.99 Page: 123
Lufthansa Technical Training
ELECTRICAL POWER 737-300/400/500
ELECTRICAL LOAD DISTRIBUTION
24-50
airplane is on the ground with the standby power switch in AUTO, ground sens-
ing relay R 38 is energized, providing a ground path to energize the standby
power off relay (R 356). With the standby power off relay energized, and the
standby power switch in the AUTO or OFF position, the connection between
the dc standby bus and the battery bus is interrupted, and the static inverter will
not turn on because the turn-on signal path is disabled. Standby power indica-
tor light relay directs power to the standby power off light.
TO STANDBY
28V DC HORIZON
BAT BUS INDICATOR
STANDBY
POWER BATTERY
28V DC
28V DC
BUS 1 STANDBY BUS
STANDBY
POWER TR
115V AC 115V AC
TRANS BUS 1 STANDBY BUS
STANDBY BUS
POWER AC
28V DC
BUS 1
STBY PWR
RELAY R37 STANDBY
AUTO POWER AUTO R328 STANDBY
CONTROL IN SENSE POWER MANUAL R389
INVERTER
VOLTAGE OUT TO R327 CONTROL RELAY
SENSOR
Q1
28V DC
VOLTAGE SENSOR
HOT BAT
BUS
BAT BUS ELECTRICAL SHELF
CONTROL
MANUAL
STANDBY A
AIR POWER OFF ON L5 STANDBY POWER OFF LIGHT
BATTERY
R38
AIR/GRD SWITCH
GRD
28V DC P5 PANEL
HOT BAT
BUS
STANDBY
POWER
IND LIGHT
R330 STANDBY AC STANDBY
POWER IND BUS INDICATION
LIGHT 1 R397 not in all 737/300/400/500
P6 LOAD CONTROL CENTER RIGHT
STATIC INVERTER
General
The static inverter converts 28-volt dc power to 115-volt ac power. It can sup-
ply 1000 watts of power to the ac standby bus. The static inverter is energized
whenever the Inverter Control Relay R 389 energized.
Location
The static inverter is on electrical equipment shelf E3-1.
Control
The power supply to the inverter is controlled by the standby power switch on
the P5 panel.
Monitor
The output of the inverter can be measured by the ac meters on the P5-13
panel by placing the ac meter selector switch in the INV position (if available).
For Training Purposes Only
-0+
400
DC CPS
-50 +50 420
FREQ
E3 RACK
E3-1 SHELF
110 120 E & E COMP
20
AC ACCESS DOOR
DC VOLTS 40 VOLTS 30
TR 1 APU GEN
BAT TR 2 GEN 1 GEN 2
INV POSITON:
BAT GRD
NOT ON ALL AIRPLANES
TR 3 INV
BUS PWR
STBY TEST
STBY TEST PWR
PWR
RESID
For Training Purposes Only
GALLEY VOLTS
OFF OFF
BAT
ON ON
AC
STATIC INVERTER
25-30 GALLEYS
GALLEY POWER CONTROL
General
The forward galley (1) and the aft galley (3) are supplied from the GEN BUS
No.1 with 115/200 Volt AC. The second aft galley (6) are supplied from GEN GALLEY 1
BUS No.2 with 115/200 Volt AC.
Normal Operation
The galleys are supplied with Power, when:
S APU GEN Breaker (1/2) or
S EXT Power Contactor (1/2) or
S GEN Breaker (1/2) are closed and
S Galley Power Switch in ON.
The Galley Switch on the overhead panel P5 provides power to energize the
galley power relays. It provides electrical grounds for relays R61, R119 and
FWD
R62. The galley relays will be energized if the appropriate engine generator
breaker, APU generator breaker, or external power contactor is closed. When
R61,R119 and R62 are energized, the galleys are connected to the repective
generator busses.
Abnormal Operation
The loss of either generator bus causes a loss of power to all galleys.
For example: GALLEY 6 GALLEY 3
If the number 1 generator fails, the Generator Breaker 1 opens, Gen Bus 1 is
deenergized and power is not longer available on the galleys No.1 and No.3.
At the same time XFR CONT RLY 2 (R349) will open. The galley relay R62 is
For Training Purposes Only
TO GALLEY RELAY
R62
TO GALLEY
RELAYS
R 61, R119