PD2083-EL-CA-A4-009 Outdoor Lighting Calculation (Hazira DT & SV Stations 2,3,4 & OPAL RT) 12-07-2018

The document provides the outdoor lighting design calculation for the Balance Works of the HDNPL Project at Hazira Delivery Terminal, SV Stations 2, 3, 4, and OPaL Dahej Receiving Terminal. It details the scope, reference documents, considerations including lighting levels, and attachments for areas like roads, tank farms, pump houses, scrap launcher, filters, and process areas. Calculations were performed using lighting software considering a maintenance factor of 0.7 to achieve the desired average lux levels per design standards and OISD norms.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
158 views24 pages

PD2083-EL-CA-A4-009 Outdoor Lighting Calculation (Hazira DT & SV Stations 2,3,4 & OPAL RT) 12-07-2018

The document provides the outdoor lighting design calculation for the Balance Works of the HDNPL Project at Hazira Delivery Terminal, SV Stations 2, 3, 4, and OPaL Dahej Receiving Terminal. It details the scope, reference documents, considerations including lighting levels, and attachments for areas like roads, tank farms, pump houses, scrap launcher, filters, and process areas. Calculations were performed using lighting software considering a maintenance factor of 0.7 to achieve the desired average lux levels per design standards and OISD norms.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Balance Works of the HDNPL Project

Comments Resolution Sheet

PROJECT The Balance Works of the HDNPL Project


CLIENT ONGC Petro additions Ltd.
PMC Engineers India Limited.
CONTRACTOR JSIW Infrastructure Pvt. Ltd.
Dwg/Doc. No. PD2083-EL-CA-A4-009 Rev 1
Dwg/Doc. Name Outdoor Lighting Calculation

Clause/ Ref. Owner/PMC


Sr. No. Comments Clarifications/ Resolutions
No. Comments
Contractor has not indicated maintenance factor
1 considered in the calculation. Check and consider 0.7 in Noted & Incorporated
the calculation.
Lighting Manufacture Company are using
Contractor to clarify by which method lighting calculation
2 AGI Software for lighting calculation of
is done for outdoor area.
outdoor area
The layouts furnished are not legible. Contractor to
3 Noted & Incorporated
furnish lux level layouts for each area.
Please include the following note in the illumination
document :
- The illumination levels shall be demonstrated at Site
after lighting installation. The actual measured lux levels
Noted & incorporated in outdoor lighting
4 at various locations shall be more than the design lux
layout.
levels. Additional lighting fixtures, if
required, to achieve the desired lux levels shall be
provided by JSIW without any time and cost implication
to Owner.

Contractor has not furnished lighting calculation for SV


5 Noted & Incorporated
stations and OPaL RT. Contractor to furnish the same.

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 1 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

Project Details

PROJECT The Balance Works of the HDNPL Project


CLIENT ONGC Petro additions Ltd.
PMC Engineers India Limited.
CONTRACTOR JSIW Infrastructure Pvt. Ltd.

Outdoor Lighting Design Calculation


(Hazira DT, SV Stations 2, 3, 4 & OPAL RT)

Document No: PD2083-EL-CA-A4-009


(Ref. Approved Doc. No. PD2083-EL-CA-A4-009 Rev 1 dt. 26.09.12)

1 09.07.18 Revised Submission HK RCR

Issued for Comment &


0 13.06.18 HK RCR
Approval

Prepared Checked By Reviewed Approved


Rev Date Purpose
By JSIW JSIW BY EIL By EIL/OPaL

Page 1 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 2 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

TABLE OF CONTENTS
Sr.
Description Page No.
No.

1 SCOPE 3

2 REFERENCE DOCUMENTS/DRAWINGS 3

3 CONSIDERATION 3-4

4 CALCULATION 5

5 CONCLUSION 5

6 ATTACHEMENTS 5

Page 2 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 3 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

1. SCOPE:

This document covers Outdoor Lighting Design Calculation at Hazira DT, SV Stations 2, 3, 4 and OPAL
Dahej RT for Hazira-Dahej Naptha Pipeline Project (HDNPL Project). The Outdoor Lighting Design
Calculation have been carried out using lighting software of one of the leading lighting fixture
manufacturers- CG-which has an extensive integral fixture datasheet for all the applications.

1.1 The Lighting of the following are is considered:

Hazira DT

• Lighting Around Scrapper Launcher


• Lighting in Booster Pump House Shed
• Lighting in Mainline Pump House Shed
• Lighting Around Filters
• Road Lighting

Dahej Receiving Terminal

• Lighting Around Scrapper Receiver


• Lighting Around Sump Tank & Pump
• Lighting Around SRV Skid & Filters
• Road Lighting

2. REFERENCE DOCUMENTS/DRAWINGS:

Datasheet for Lighting Fixtures Schedule : B098-00-16-50-DS-02 Rev A

Electrical Job Specification : B098-000-16-50-SP-02 Rev A

Engineering Design Basis (Electrical) : B098-00-16-50-DB-01 Rev A

Engineering Design Basis (Electrical) : B098-00-16-50-DB-02 Rev A

Design Philosophy for Electrical Facilities : 6-51-0099, Rev 6

3. CONSIDERATION:

The following design basis has been adopted for the design of the indoor lighting system.

Page 3 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 4 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

3.1 Lighting Levels:

The following average normal lighting levels shall be provided after allowing maintenance factor 0.7
for outdoor areas. Lux level indicated is as per Bid document Standard Specification No. 6-51-0099
Rev 6 and OISD Norms 149.

Location Average Lux

Road & Tank Farm 20

Pump House, Shed 100

Scrapper Launcher 60

Filters 60

Process Area & Pipe racks 60

Metering Area 60

Around SRV Skids 60

Sump Tank 100

3.2 Type of Lighting Fixtures and Lamps:

a. Hazira Dispatch Terminal:

Area Type of Lighting Fixtures Mounting Details Certified

Lighting Around 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Scrapper Launcher Wellglass Lighting Fixture (Pole mounted)

Lighting in Booster 60W LED Flameproof Mounting Height 9 Mtr. Flameproof


Pump Shed Wellglass Lighting Fixture (Suspended type) & 4 Mtr. Column
mounted
Lighting in Mainline 60W LED Flameproof Mounting Height 9 Mtr. Flameproof
Shed Wellglass Lighting Fixture ( Suspended type) & 4 Mtr. Column
mounted
Lighting Around 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Filters Wellglass Lighting Fixture (Pole mounted)

Road Lighting 90W LED Street Light Mounting Height 9 Mtr. Safe Area
(Pole Mounted)

Page 4 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 5 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

b. OPAL Receiving Terminal:

Area Type of Lighting Fixtures Mounting Details Certified

Lighting Around 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Metering Area & Wellglass Lighting Fixture (Pole mounted)
Control Valve Area

Sump Tank 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Wellglass Lighting Fixture (Pole mounted)

Lighting Around 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Filters Area & SRV Wellglass Lighting Fixture (Pole mounted)
Skid Area

Approach Road 90W LED Street Light Mounting Height 9 Mtr. Safe Area
Lighting (Pole Mounted)

c. SV Stations: (SV-02, SV-03 & SV-04)

Area Type of Lighting Fixtures Mounting Details Certified

Lighting Around SV 60W LED Flameproof Mounting Height 4.5 Mtr. Flameproof
Wellglass Lighting Fixture (Pole mounted)

Road Lighting 90W LED Street Light Mounting Height 9 Mtr. Safe Area
(Pole Mounted)

Lighting Around 90W LED Street Light Mounting on Parapet Wall Safe Area
Repeater Building

4. CALCULATION:

We have provided the Plant Layout in Autocad Formats to Lighting Manufacturer Company “CG” for
Calculation. The Plant layout in Autocad formats were converted into DXF files forming the base
document for the lighting software. The programme takes into account the obstruction effect of the
equipment interfering with the lighting, as indicated by the computer printouts attached with this

Page 5 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 6 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

calculation. Placement of fixtures in the simulation, in order to determine the illumination levels, is
carried out as per attached calculation results. “AGI” software have used for Calculation.

The software generated reports of the calculations are attached as Annexure.

5. CONCLUSION:

The lighting fixtures are proposed (in software model) in such a way that the average required Lux
level is achieved.

The Lighting layout drawings has prepared based on the arrangement proposed in lighting
calculations.

Summary of required and calculated illumination:

At Hazira DT:

Sr. Location Required Lux Achieved Lux


No. Level Level

1 Lighting Around Scrapper Launcher 60 60.58

2 Lighting in Booster Pump House Shed 100 154.12

3 Lighting in Mainline Pump House Shed 100 110.90

4 Lighting Around Filters 60 60.10

5 Road Area Lighting 20 26.35

At OPAL RT:

Sr. Location Required Lux Achieved Lux


No. Level Level

1 Lighting Around Metering Area & Control 60 69.78


Valve Area

2 Lighting Around Sump Tank 100 126.91

3 Lighting Around Filter Area & SRV Skid Area 60 84.58

4 Approach Road Lighting 20 40.81

Page 6 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 7 of 24
Balance Works of the HDNPL Project
Outdoor Lighting Calculation (Hazira DT & SV
Stations 2,3,4 & OPAL RT)
Doc. No. PD2083-EL-CA-A4-009

At SV-03:

Sr. Location Required Lux Achieved Lux


No. Level Level

1 Lighting Around SV 60 64.55

2 Lighting Around Repeater Building 20 61.31

3 Road Lighting 20 61.31

At SV-04:

Sr. Location Required Lux Achieved Lux


No. Level Level

1 Lighting Around SV 60 64.59

2 Lighting Around Repeater Building 20 50.10

3 Road Lighting 20 61.31

Still Plot Layout of SV-02 have not finalized. Hence calculation for same have not done. But
lighting of same shall be done as per SV-03 & SV-04.

6. ATTACHEMENTS:

Annexure 1 - Software generated report for ONGC Hazira Dispatch Terminal (Total Sheets-05)

Annexure 2- Software generated report for OPAL RT Terminal (Total Sheets-04)

Annexure 3- Software generated report for SV-03 & SV-04 Terminal (Total Sheets-06)

Page 7 of 5

12-JUL-2018
SHANKAR CHINTAKUNTLA (C262)

Page 8 of 24
HAZIRA DT ROAD LIGHTING
BATTERY LIMIT
E-1310.220 CL OF EXISTING ROAD
28500

12060
1500
NEW PIPE WAY
EXISTING PIPE WAY

7340
1250
NEW PIPE WAY
6600
RCC PIT
5500
F.G.L. 100.000

1000

13100
(TYP)
10000

500 2000

2750

2250
CL. OF SUMP TANK & PUMP

4054.6
0-TT-00-102 (CL.EL. 98.385) E F
D
0-PA-SM-101

2250
3000
6400 1800 6500 2500 13000 8000
E-1277.220 CL. OF NEW ROAD 6M WIDE SLOPE R.T.L. 100.300 1
(TYP)

3750
3000
6500 (TYP)
ROAD ROAD HP 100.300

6000
1

7500
27321.2 4000
BL 99.60
2
CL. OF LAN PUMP
01-PA-CF-101
FGL 101.550

6000
2

2000
HS-1

MAINTENANCE BAY
23000

9600
4500
E-1264.470 CL. OF NEW ROAD 6M WIDE
Z Z
N12
MAIN LINE PUMP

6000
6500
BL 99.60
HOUSE
3
EX 'd' CL. OF LAN PUMP
4 01-PA-CF-101
5000 10000 5000
CL. OF MAIN LINE PUMP
01-PA-CF-102A

6000
HP 100.350

9600
4
ROAD

10000
3000

52500
F.G.L. 100.000
(TYP)

6000
CL. OF ARN PUMP
EOT CRANE

ROAD
01-PA-CF-101

(TYP)
F.G.L. 100.000
5
9000 11000 C 6
A B

9600
BOOSTER PUMP

6000
HOUSE
AREA FOR METERING

11000
X X

NEW PIPE WAY


5500 5500 7
CL. OF ARN PUMP
01-PA-CF-101

HPP 100.300
AREA FOR METERING
F.G.L. 101.550

6000
8615 E-1232.222 24.5 30.6 32.8
31000

CL. OF NEW ROAD 6M WIDE

8800
FFL 102.450 8000 (TYP) 5000
24.8 31.3 35.1
ROAD

9600
24.6 31.9 36.3
8
24.3 31.9

7000
R.T.L. 101.850

36.8
CONTROL BUILDING
7000
(TYP)

23.9 31.5 36.4

6000
23.1 30.5 34.7 CL. OF ARN PUMP
01-PA-CF-101
FILTER
21.7 29.1 32.5
9
FILTER AREA

4000
20.6 27.1 29.8

6 600
MAINTENANCE BAY

4500
HOT CRANE
19.6 25.4 27.1 FILTER DIRECTLY BURIED CABLE
(500W x 700D) TYP
18.9 23.7 25.3 10
BATTERY LIMIT

4000

2 500
1.2M WIDE FOOTPATH 23.5 24.8
18.3
CL. OF NEW ROAD 6M WIDE

FILTER HP 100.300 CL. OF DOSING PUMP


19.0 23.5 24.8
F.G.L. 100.000

00-PA-RP-103B
24.1 24.6 CL. OF DOSING TANK

9000
19.7 B.T.L. 102.100)
(TYP)

00-11-00-10

4000
20.8 25.1 25.6 CL. OF DOSING PUMP

6100
00-PA-RP-103A
22.1 26.9 27.8 FILTER

2000

BATTERY LIMIT
13000
3000
TOS EL. 101.425

3000
CRADDLE TROLLEY 1500 16489
FOR LAUNCHER
E-1210.222 CL. OF SCRAPER LAUNCHER
01-EL-00-101
SCRAPPER

3000
R.T.L. 101.850 LAUNCHER
(TYP)

ROAD
5000 10000 15000 10000 2500 3500 15000 15000 21000

CL. OF NEW ROAD 6M WIDE


4600
DG
ROOM 10000 25000 10000 11000
SLOPE

F.G.L. 100.000
HP 101.850 R.T.L. 100.300

(TYP)
(TYP)

10400

SLOPE

SLOPE

SHANKAR CHINTAKUNTLA (C262)


F.G.L. 100.000
(TYP)

22000
PC07
2 NOS. Ø500

15000
01-ELP-003-HZ
01-LP-003-HZ
E-1180.220 R.L.T. 99.837 CL OF EXISTING ROAD

N-1141.000

N-1130.000
E-1283.000

E-1268.000

E-1207.000
BATTERY LIMIT BATTERY LIMIT
Luminaire Schedule **NOTE**

12-JUL-2018
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description HEIGHT OF POLE CONSIDERED AS IN LEGEND,.
LSTP-90-CDL 9644 0.700 CALCULATION POINTS CONSIDERED AT G.L.
18 90W LED SL
STREETLIGHT POLE 9M TILT 15DEG.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 9 of 24
ROAD_1_Illum Illuminance Lux 26.35 36.8 18.3 0.69 0.50
HAZIRA DT BOOSTER PUMP HOUSE
BATTERY LIMIT
E-1310.220 CL OF EXISTING ROAD
28500

12060
1500
NEW PIPE WAY
EXISTING PIPE WAY

7340
1250

NEW PIPE WAY


6600

RCC PIT
5500
F.G.L. 100.000 1000

13100
(TYP)
10000

500 2000
2750

2250
CL. OF SUMP TANK & PUMP

4054.6
0-TT-00-102 (CL.EL. 98.385) E F
D

2250
0-PA-SM-101
3000

6400 1800 6500 2500 13000 8000


E-1277.220 CL. OF NEW ROAD 6M WIDE SLOPE R.T.L. 100.300 1
(TYP)
ELP1-A-R1-03

3750
3000
6500 (TYP)
ROAD ROAD HP 100.300

6000
1

7500
27321.2 4000
BL 99.60
2
CL. OF LAN PUMP
01-PA-CF-101
FGL 101.550

6000
2

2000
HS-1

MAINTENANCE BAY
23000

LP1-B-R1-03 3

9600
4500
E-1264.470 CL. OF NEW ROAD 6M WIDE
Z Z
N12
MAIN LINE PUMP

6000
BL 99.60

6500
HOUSE
ELP1-A-Y1-03 3
EX 'd' CL. OF LAN PUMP
4 01-PA-CF-101
5000 10000 5000
CL. OF MAIN LINE PUMP
01-PA-CF-102A

6000
HP 100.350

9600
4
ROAD

10000
3000

52500
F.G.L. 100.000
(TYP)

6000
EOT CRANE CL. OF ARN PUMP
ROAD
01-PA-CF-101
LP1-A-B4-02 LP1-A-B4-03

(TYP)
F.G.L. 100.000
LP1-A-B4-01
5
9000 11000 C 6
A B

9600
BOOSTER PUMP
ELP1-A-B2-01 LP1-B-B2-01

6000
HOUSE
AREA FOR METERING

11000
X X

NEW PIPE WAY


5500 5500 7
CL. OF ARN PUMP
01-PA-CF-101

AREA FOR METERING


HPP 100.300
F.G.L. 101.550 LP1-B-Y1-03 ELP1-A-B1-01
31000

6000
8615 E-1232.222 CL. OF NEW ROAD 6M WIDE
8000 (TYP)

8800
FFL 102.450 5000
ROAD

9600
8

7000
R.T.L. 101.850

CONTROL BUILDING
7000
(TYP)

6000
CL. OF ARN PUMP
FILTER 01-PA-CF-101
9
FILTER AREA

4000

6 600
MAINTENANCE BAY

4500
HOT CRANE
FILTER DIRECTLY BURIED CABLE
(500W x 700D) TYP

ROAD
10
BATTERY LIMIT

4000
1.2M WIDE FOOTPATH

2 500
CL. OF NEW ROAD 6M WIDE

FILTER HP 100.300 CL. OF DOSING PUMP


F.G.L. 100.000

00-PA-RP-103B
CL. OF DOSING TANK

9000
B.T.L. 102.100)
(TYP)

00-11-00-10

4000
CL. OF DOSING PUMP

6100
00-PA-RP-103A
ELP1-A-B1-02 FILTER

2000

BATTERY LIMIT
13000
3000
TOS EL. 101.425

3000
CRADDLE TROLLEY 1500 16489
FOR LAUNCHER
E-1210.222 CL. OF SCRAPER LAUNCHER
01-EL-00-101
SCRAPPER

3000
R.T.L. 101.850 LAUNCHER
(TYP)
5000 10000 15000 10000 2500 3500 15000 15000 21000

CL. OF NEW ROAD 6M WIDE


4600
DG
ROOM 10000 25000 10000 11000
SLOPE

F.G.L. 100.000
HP 101.850 R.T.L. 100.300

(TYP)
(TYP)

10400
LP1-B-B1-02

SLOPE

SLOPE
F.G.L. 100.000

SHANKAR CHINTAKUNTLA (C262)


(TYP)

22000
PC07
2 NOS. Ø500

15000
01-ELP-003-HZ
01-LP-003-HZ
E-1180.220 R.L.T. 99.837 CL OF EXISTING ROAD

N-1141.000

N-1130.000
E-1283.000

E-1268.000

E-1207.000
BATTERY LIMIT BATTERY LIMIT
Luminaire Schedule
**NOTE**

12-JUL-2018
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF FIXTURE CONSIDERED 9M.
38 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 10 of 24
BOOSTER PUMP HOUSE Illuminance Lux 154.12 380 7.4 0.05 0.02
FILTER AREA HAZIRA DT FILTER AREA
BATTERY LIMIT
E-1310.220 CL OF EXISTING ROAD
28500

12060
1500
NEW PIPE WAY
EXISTING PIPE WAY

7340
1250

NEW PIPE WAY


6600

RCC PIT
5500
F.G.L. 100.000
1000

13100
(TYP)
10000

500 2000
2750

2250
CL. OF SUMP TANK & PUMP

4054.6
0-TT-00-102 (CL.EL. 98.385) E F
D

2250
0-PA-SM-101
3000

6400 1800 6500 2500 13000 8000


E-1277.220 CL. OF NEW ROAD 6M WIDE SLOPE R.T.L. 100.300 1
(TYP)
ELP1-A-R1-03

3750
3000

6500 (TYP)
ROAD ROAD HP 100.300

6000
1

7500
27321.2 4000
BL 99.60
2
CL. OF LAN PUMP
01-PA-CF-101
FGL 101.550

6000
2

2000
HS-1

MAINTENANCE BAY
23000

9600
4500
E-1264.470 CL. OF NEW ROAD 6M WIDE
Z Z
N12
MAIN LINE PUMP

6000
BL 99.60

6500
ELP1-A-Y5-02
HOUSE
ELP1-A-Y1-03 3
EX 'd' CL. OF LAN PUMP
4 01-PA-CF-101
5000 10000 5000
CL. OF MAIN LINE PUMP
01-PA-CF-102A

6000
HP 100.350

9600
4
ROAD

10000
3000

52500
F.G.L. 100.000
(TYP)

6000
EOT CRANE CL. OF ARN PUMP
ROAD

01-PA-CF-101

(TYP)
F.G.L. 100.000
5
9000 11000 C 6
A B

9600
BOOSTER PUMP

6000
9.2 28.1 18.4 27.0 HOUSE
AREA FOR METERING

11000
X X

NEW PIPE WAY


5500 5500 7
CL. OF ARN PUMP
01-PA-CF-101

AREA FOR METERING


HPP 100.300
F.G.L. 101.550 LP1-B-Y1-03
31000

6000
8615 E-1232.222 CL. OF NEW ROAD 6M WIDE 1.9
3.3 4.0 2.9
8000 (TYP)

8800
FFL 102.450 5000
ROAD

9600
8
1.9 8.6 32.7 12.7

7000
R.T.L. 101.850

CONTROL BUILDING
7000
(TYP)

6000
CL. OF ARN PUMP
FILTER 01-PA-CF-101
3.1 29.6 276 47.9 9
FILTER AREA

4000

6 600
MAINTENANCE BAY

4500
HOT CRANE
FILTER DIRECTLY BURIED CABLE
(500W x 700D) TYP

ROAD
10
BATTERY LIMIT

4000
1.2M WIDE FOOTPATH
390

2 500
4.0 38.8 57.5
CL. OF NEW ROAD 6M WIDE

FILTER HP 100.300 CL. OF DOSING PUMP


F.G.L. 100.000

00-PA-RP-103B
CL. OF DOSING TANK

9000
B.T.L. 102.100)
(TYP)

00-11-00-10

4000
CL. OF DOSING PUMP

6100
4.0 00-PA-RP-103A
ELP1-A-B1-02 39.9 351 50.9
FILTER

2000

BATTERY LIMIT
13000
3000
TOS EL. 101.425

3000
CRADDLE TROLLEY 1500 16489
FOR LAUNCHER
E-1210.222 CL. OF SCRAPER LAUNCHER
01-EL-00-101
SCRAPPER

3000
R.T.L. 101.850 LAUNCHER
(TYP)
5000 10000 15000 10000 2500 3500 15000 15000 21000

CL. OF NEW ROAD 6M WIDE


4600
DG
ROOM 10000 25000 10000 11000
SLOPE

F.G.L. 100.000
HP 101.850 R.T.L. 100.300

(TYP)
(TYP)

10400
LP1-B-B1-02

SLOPE

SLOPE
F.G.L. 100.000

SHANKAR CHINTAKUNTLA (C262)


(TYP)

22000
PC07
2 NOS. Ø500

15000
01-ELP-003-HZ
01-LP-003-HZ
E-1180.220 R.L.T. 99.837 CL OF EXISTING ROAD

N-1141.000

N-1130.000
E-1283.000

E-1268.000

E-1207.000
BATTERY LIMIT BATTERY LIMIT

12-JUL-2018
Luminaire Schedule
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF POLE CONSIDERED IS 4.5M,
12 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary

Page 11 of 24
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.
FILTER AREA Illuminance Lux 60.10 390 1.9 0.03 NA
HAZIRA DT MAINLINE PUMP HOUSE
BATTERY LIMIT
E-1310.220 CL OF EXISTING ROAD
28500

12060
1500
NEW PIPE WAY
EXISTING PIPE WAY

7340
1250

NEW PIPE WAY


6600

RCC PIT
5500
F.G.L. 100.000
1000

13100
(TYP)
10000

500 2000
2750

2250
LP1-B-Y1-02
CL. OF SUMP TANK & PUMP

4054.6
0-TT-00-102 (CL.EL. 98.385) E F
D

2250
0-PA-SM-101
3000

6400 1800 6500 2500 13000 8000


E-1277.220 CL. OF NEW ROAD 6M WIDE SLOPE R.T.L. 100.300 1
(TYP)

3750
3000

6500 (TYP)
ROAD ROAD HP 100.300

6000
1

7500
27321.2 4000
2
133 102 104 89.7
CL. OF LAN PUMP
01-PA-CF-101
FGL 101.550

6000
2

2000
HS-1

MAINTENANCE BAY
23000

3
194 73.2 86.8 205

9600
4500
E-1264.470 CL. OF NEW ROAD 6M WIDE
Z Z
N12
MAIN LINE PUMP

6000
BL 99.60

6500
HOUSE
ELP1-A-Y1-03 75.6 67.6 89.7 228 3
EX 'd' CL. OF LAN PUMP
4 01-PA-CF-101
5000 10000 5000
CL. OF MAIN LINE PUMP
01-PA-CF-102A

6000
150 60.7 57.1 130
HP 100.350

9600
4
ROAD

10000
3000

52500
F.G.L. 100.000
(TYP)

6000
96.4 90.7 94.8 89.0 CL. OF ARN PUMP
ROAD

01-PA-CF-101
EOT CRANE

(TYP)
F.G.L. 100.000
5
9000 11000 C 6
A B

9600
BOOSTER PUMP

6000
HOUSE ELP1-A-R5-05
AREA FOR METERING

11000
X X

NEW PIPE WAY


5500 5500 7
CL. OF ARN PUMP
01-PA-CF-101

AREA FOR METERING


HPP 100.300
F.G.L. 101.550
31000

6000
8615 E-1232.222 CL. OF NEW ROAD 6M WIDE
8000 (TYP)

8800
FFL 102.450 5000
ROAD

9600
8

7000
R.T.L. 101.850

CONTROL BUILDING
7000
(TYP)

6000
CL. OF ARN PUMP
FILTER 01-PA-CF-101
9
FILTER AREA

4000

6 600
MAINTENANCE BAY

4500
HOT CRANE
FILTER DIRECTLY BURIED CABLE
(500W x 700D) TYP

ROAD
10
BATTERY LIMIT

4000
1.2M WIDE FOOTPATH

2 500
CL. OF NEW ROAD 6M WIDE

FILTER HP 100.300 CL. OF DOSING PUMP


F.G.L. 100.000

00-PA-RP-103B
CL. OF DOSING TANK

9000
B.T.L. 102.100)
(TYP)

00-11-00-10

4000
CL. OF DOSING PUMP

6100
00-PA-RP-103A
ELP1-A-B1-02 FILTER

2000

BATTERY LIMIT
13000
3000
TOS EL. 101.425

3000
CRADDLE TROLLEY 1500 16489
FOR LAUNCHER ELP1-A-R3-01
E-1210.222 CL. OF SCRAPER LAUNCHER
01-EL-00-101
SCRAPPER

3000
R.T.L. 101.850 LAUNCHER
(TYP)
5000 10000 15000 10000 2500 3500 15000 15000 21000

CL. OF NEW ROAD 6M WIDE


4600
DG
ROOM 10000 25000 10000 11000
SLOPE

F.G.L. 100.000
HP 101.850 R.T.L. 100.300

(TYP)
(TYP)

10400
LP1-B-B1-02

SLOPE

SLOPE
F.G.L. 100.000

SHANKAR CHINTAKUNTLA (C262)


(TYP)

22000
PC07
2 NOS. Ø500

15000
01-ELP-003-HZ
01-LP-003-HZ
E-1180.220 R.L.T. 99.837 CL OF EXISTING ROAD

N-1141.000

N-1130.000
E-1283.000

E-1268.000

E-1207.000
BATTERY LIMIT BATTERY LIMIT
Luminaire Schedule

12-JUL-2018
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
MOUNTING HEIGHT CONSIDERED IS 9 MTR.
19 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 12 of 24
MAIN LINE PUMP HOUSE Illuminance Lux 110.90 228 57.1 0.51 0.25
HAZIRA DT SCRAPPER LAUNCHER AREA
BATTERY LIMIT
E-1310.220 CL OF EXISTING ROAD
28500

12060
1500
NEW PIPE WAY
EXISTING PIPE WAY

7340
1250

NEW PIPE WAY


6600

RCC PIT
5500
F.G.L. 100.000

1000

13100
(TYP)
10000

500 2000
2750

2250
ELP1-A-Y1-01
CL. OF SUMP TANK & PUMP

4054.6
0-TT-00-102 (CL.EL. 98.385) E F
D

2250
0-PA-SM-101

3000
6400 1800 6500 2500 13000 8000
E-1277.220 CL. OF NEW ROAD 6M WIDE SLOPE R.T.L. 100.300 1
(TYP)

3750
3000
6500 (TYP)
ROAD ROAD HP 100.300

6000
1

7500
27321.2 4000
BL 99.60
2
CL. OF LAN PUMP
01-PA-CF-101
FGL 101.550

6000
2

2000
HS-1

MAINTENANCE BAY
23000

9600
4500
E-1264.470 CL. OF NEW ROAD 6M WIDE
Z Z
N12
MAIN LINE PUMP

6000
BL 99.60

6500
HOUSE
3
EX 'd' CL. OF LAN PUMP
4 01-PA-CF-101
5000 10000 5000
CL. OF MAIN LINE PUMP
01-PA-CF-102A

6000
HP 100.350

9600
4
ROAD

10000
3000

52500
F.G.L. 100.000
(TYP)

6000
EOT CRANE CL. OF ARN PUMP

ROAD
01-PA-CF-101

(TYP)
F.G.L. 100.000
5
9000 11000 C 6
A B

9600
BOOSTER PUMP

6000
HOUSE
AREA FOR METERING

11000
X X

NEW PIPE WAY


5500 5500 7
CL. OF ARN PUMP
01-PA-CF-101

AREA FOR METERING


HPP 100.300
F.G.L. 101.550
31000

6000
8615 E-1232.222 CL. OF NEW ROAD 6M WIDE
8000 (TYP)

8800
FFL 102.450 5000
ROAD

9600
8

7000
R.T.L. 101.850

CONTROL BUILDING
7000
(TYP)

6000
CL. OF ARN PUMP
FILTER 01-PA-CF-101
9
FILTER AREA

4000

6 600
MAINTENANCE BAY

4500
HOT CRANE
FILTER DIRECTLY BURIED CABLE
(500W x 700D) TYP

ROAD
10
BATTERY LIMIT

4000
1.2M WIDE FOOTPATH

2 500
CL. OF NEW ROAD 6M WIDE

FILTER HP 100.300 CL. OF DOSING PUMP


F.G.L. 100.000

00-PA-RP-103B
CL. OF DOSING TANK

9000
B.T.L. 102.100)
(TYP)

00-11-00-10

4000
CL. OF DOSING PUMP

6100
00-PA-RP-103A
FILTER

2000

BATTERY LIMIT
13000
3000
TOS EL. 101.425

3000
CRADDLE TROLLEY 1500 16489
FOR LAUNCHER ELP1-A-R3-01
E-1210.222 CL. OF SCRAPER LAUNCHER
01-EL-00-101
SCRAPPER

3000
R.T.L. 101.850
LP1-B-R3-01 LAUNCHER
(TYP)
5000 10000 15000 10000 2500 3500 15000 15000 21000

CL. OF NEW ROAD 6M WIDE


4600
DG
ROOM 10000 25000 10000 11000
SLOPE

F.G.L. 100.000
HP 101.850 R.T.L. 100.300

(TYP)
(TYP)

10400

SLOPE

SLOPE
F.G.L. 100.000

SHANKAR CHINTAKUNTLA (C262)


(TYP)

22000
PC07
2 NOS. Ø500

15000
01-ELP-003-HZ
01-LP-003-HZ
E-1180.220 R.L.T. 99.837 CL OF EXISTING ROAD

N-1141.000

N-1130.000
E-1283.000

E-1268.000

E-1207.000
BATTERY LIMIT BATTERY LIMIT
Luminaire Schedule

12-JUL-2018
**NOTE**
Symbol Qty Label Total Lamp Lumens LLF Description NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
HEIGHT OF POLE CONSIDERED IS 4.5MTR
2 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING.
CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 13 of 24
LIGHTING AROUND SCRAPPER 0.3 0.01 N.A.
LAUNCHER
Illuminance Lux 60.58 0.3
OPAL RT METERING AREA & SUMP TANK
R.T.L 99.552 CL.OF
L EXISTING ROAD 6M WIDE BATTERY LIMIT R.T.L 99.500
N 2401352.291
E 252415.282

13717

R.T.L 99.500
SLOPE 1:20
ROAD
CL OF SLIDING SADDLE

CL OF FIXED SADDLE
LAN+ARN PIPELINE
E-252437.792

E-252459.842
9100 19950

R.T.L 100.150
28200
A
HPP 100.150 6000
6500

4024

16100
FGL. EL.99.800

CL.OF ROAD 6M WIDE


1000

BATTERY LIMIT
BATTERY LIMIT

1000 A
TYP.

5200

L
2250

4500
CL.OF ROAD 4M WIDE R.T.L 100.150

HPP 100.150
SRV SKID
FILTER AREA

HPP 100.150

7250

4998
B D C A
EDGE OF
SRV SKID (SRV-1101)
PAVED AREA

24000
PIPE CORRIDOR
EXISTING ROAD 6M WIDE

METERING AREA
22.0 22.1 62.3 249
92.1 41.6 246
CL.OF
L
30.0 8.2 15.6 134

04-HS-02
247 42.7 91.4
97.0

METERING AREA
3.1 3.2 8.9 SUMP TANK
72.8 45.2

CONTROL VALVE AREA


248
FGL. EL.99.800 2.9 3.2 8.4 91.0 FGL. EL.99.600
249 48.9 127

8000
21.1 7.3 14.5 117
87.8 38.2 227
T.O.GR EL.99.632
21.9 20.1 68.9 239
RCC PIT
T.O.PIT EL.100.300
EP-01
R.T.L 100.150 C OF ROAD 6M WIDE
L
ROAD R.T.L 100.150

CL OF SCRAPER RECEIVER & CRADDEL

CL OF SUMP TANK & SUMP PUMPS

SHANKAR CHINTAKUNTLA (C262)


04-MR-00-101

EXISTING TANK

E 252489.292
(CLEL.97.267)
04-TT-00-301
N 2401261.374
Luminaire Schedule

12-JUL-2018
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF POLE CONSIDERED 4.5M,
9 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 14 of 24
METERING AREA Illuminance Lux 69.78 249 2.9 0.04 0.01
SUMP TANK Illuminance Lux 126.91 249 38.2 0.30 0.15
OPAL RT ROAD
R.T.L 99.552 CL.OF EXISTING ROAD 6M WIDE BATTERY LIMIT R.T.L 99.500
L
N 2401352.291
E 252415.282

13717

22.4 29.2

R.T.L 99.500
25.9 34.2 24.0

SLOPE 1:20
36.01 41.1 30.0

ROAD
37.5 47.5 34.6
37.3 50.3 37.5
CL OF SLIDING SADDLE

CL OF FIXED SADDLE
LAN+ARN PIPELINE

47.1 57.2 43.0


E-252437.792

E-252459.842
9100 19950
46.2 58.4 46.3

R.T.L 100.150
28200
A
49.7 61.7 47.7
HPP 100.150 6000
6500
52.3 66.0 31.9
4024

16100
46.9 62.4 51.8
FGL. EL.99.800

ROAD 6M WIDE
1000

BATTERY LIMIT
1000
BATTERY LIMIT

A 39.2 53.4 48.9


TYP.

CL.OF
5200

L
31.0 39.3 41.1

2250
22.9 29.1 30.6

4500
CL.OF ROAD 4M WIDE R.T.L 100.150
HPP 100.150

SRV SKID 16.7 20.9 21.8


FILTER AREA

HPP 100.150

7250

4998
B D C A
EDGE OF
SRV SKID (SRV-1101)
PAVED AREA

24000
PIPE CORRIDOR
CL.OF EXISTING ROAD 6M WIDE

METERING AREA
L

04-HS-02

METERING AREA
SUMP TANK

CONTROL VALVE AREA


FGL. EL.99.800 FGL. EL.99.600

8000
T.O.GR EL.99.632
RCC PIT
T.O.PIT EL.100.300
EP-01
R.T.L 100.150 C OF ROAD 6M WIDE
L
ROAD R.T.L 100.150
31.0 39.3 41.1 49.7

CL OF SCRAPER RECEIVER & CRADDEL


29.1 30.6 61.7
22.9

CL OF SUMP TANK & SUMP PUMPS


16.7 20.9 21.8 47.7

04-MR-00-101

EXISTING TANK

E 252489.292
(CLEL.97.267)
04-TT-00-301
N 2401261.374

SHANKAR CHINTAKUNTLA (C262)


Luminaire Schedule
**NOTE**
Qty Label Total Lamp Lumens LLF Description NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING

12-JUL-2018
Symbol CALCULATION POINTS CONSIDERED AT G.L.
STREETLIGHT POLE 9M TILT 15DEG.
6 LSTP-90-CDL 9644 0.700 90W LED SL
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 15 of 24
ROAD Illuminance Lux 40.81 66.0 16.7 0.41 0.25
OPAL RT SUMP TANK
R.T.L 99.552 CL.OF
L EXISTING ROAD 6M WIDE BATTERY LIMIT R.T.L 99.500
N 2401352.291
E 252415.282

13717

R.T.L 99.500
SLOPE 1:20
ROAD
CL OF SLIDING SADDLE

CL OF FIXED SADDLE
LAN+ARN PIPELINE
E-252437.792

E-252459.842
9100 19950

R.T.L 100.150
28200
A
HPP 100.150 246 91.4 6000 248 127 227
6500
SUMP TANK
41.6 42.7 45.2 48.9 38.2

4024

16100
FGL. EL.99.800

CL.OF ROAD 6M WIDE


249 87.8
92.1 247 72.8
1000

BATTERY LIMIT
BATTERY LIMIT

1000 A
TYP.

5200

L
2250

4500
CL.OF ROAD 4M WIDE R.T.L 100.150

HPP 100.150
SRV SKID
FILTER AREA

HPP 100.150

7250

4998
B D C A
EDGE OF
SRV SKID (SRV-1101)
PAVED AREA

24000
PIPE CORRIDOR
EXISTING ROAD 6M WIDE

METERING AREA
CL.OF
L

04-HS-02

METERING AREA
SUMP TANK

CONTROL VALVE AREA


FGL. EL.99.800 FGL. EL.99.600

8000
T.O.GR EL.99.632
RCC PIT
T.O.PIT EL.100.300
EP-01
R.T.L 100.150 C OF ROAD 6M WIDE
L
ROAD R.T.L 100.150

CL OF SCRAPER RECEIVER & CRADDEL

CL OF SUMP TANK & SUMP PUMPS

SHANKAR CHINTAKUNTLA (C262)


04-MR-00-101

EXISTING TANK

E 252489.292
(CLEL.97.267)
04-TT-00-301
N 2401261.374
Luminaire Schedule

12-JUL-2018
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF POLE CONSIDERED 4.5M,
5 FWL1315-60-CDL 3615.67 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 16 of 24
SUMP TANK Illuminance Lux 126.91 249 38.2 0.30 0.15
OPAL RT FILTER AREA SRV SKID
R.T.L 99.552 CL.OF
L EXISTING ROAD 6M WIDE BATTERY LIMIT R.T.L 99.500
N 2401352.291
E 252415.282

13717

R.T.L 99.500
SLOPE 1:20
ROAD
CL OF SLIDING SADDLE

CL OF FIXED SADDLE
LAN+ARN PIPELINE
E-252437.792

E-252459.842
9100 19950

R.T.L 100.150
28200
A
HPP 100.150 6000
6500

4024

16100
FGL. EL.99.800

ROAD 6M WIDE
1000

BATTERY LIMIT
BATTERY LIMIT

1000 A
TYP.

CL.OF
5200

L
127 147 125 64.3 21.0 201 50.9 142 244 107 10

2250
13.7

4500
CL.OF ROAD 4M WIDE R.T.L 100.150
HPP 100.150
10.2 73.5 150 73.0 37.6 133 124 33.5 88.6 153 62.7 8.7
SRV SKID
FILTER AREA

HPP 100.150
6.6 17.7 28.6 20.7 17.0 26.3 29.4 16.9 22.4 28.7 16.0 5.8

7250

4998
58.9 129 63.7 29.6 99.8 96.1 23.9
B D77.4 C 12.0
A 57.2 7.2
9.1
EDGE OF
SRV SKID (SRV-1101)
PAVED AREA
124 251 131 62.8 215 207 62.7 161 245 95.2
13.2 9.5

24000
PIPE CORRIDOR
EXISTING ROAD 6M WIDE

METERING AREA
CL.OF
L

04-HS-02

METERING AREA
SUMP TANK

CONTROL VALVE AREA


FGL. EL.99.800 FGL. EL.99.600

8000
T.O.GR EL.99.632
RCC PIT
T.O.PIT EL.100.300
EP-01
R.T.L 100.150 C OF ROAD 6M WIDE
L
ROAD R.T.L 100.150

CL OF SCRAPER RECEIVER & CRADDEL

CL OF SUMP TANK & SUMP PUMPS


04-MR-00-101

EXISTING TANK

E 252489.292

SHANKAR CHINTAKUNTLA (C262)


(CLEL.97.267)
04-TT-00-301
N 2401261.374
Luminaire Schedule

12-JUL-2018
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF POLE CONSIDERED 4.5M,
6 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING. CALCULATION POINTS CONSIDERED AT G.L.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 17 of 24
FILTER AREA SRV SKID Illuminance Lux 84.58 251 5.8 0.07 0.02
SV3 AROUND BUILDING AREA
TO JUNA DHANTURIYA

WATER LINE 1
1.5" GI PIPE
N 2395327.369
E 279890.271
TBM-1 ON BORE

2500
ACCESS ROAD
RL-96.212
SOAK-PIT/
ANEROBIC FILTER
(10 USERS) 1.05 87.2 70.7 46.5
108
TUBEWELL PLATEFORM

TUBEWELL
2260X2260
11.5 34.0 69.3 83.3 52.3 89.3 17.0 66.8 59.5
SEPTIC TANK

D.G ROOM
(10 USERS)
12.4 35.2 75.2 73.7 64.6 57.8 54.4 58.4 64.7
TWO POLE
STRUCTURE
IC 10.3 27.9 91.9 74.06 52.2 40.5 40.5 54.4 76.1
AROUND BLDG. AREA
TO TERRACE 6.0 28.2 96.2 76.9 50.4 34.9 38.0 58.7 80.4 84.6

ELECTRICAL
EQUIPMENT
DRINKING
TANK

ROOM
TOILET WATER
6.3 26.0 93.7 73.5 48.4 33.9 38.8 57.2 81.8 90.0
GUARD WATER LINE
ROOM 20.1 76.8 64.8 43.7 33.1 37.2 53.3 77.1 79.6 1.5" GI PIPE
ENTRY
DOOR
17.6 62.0 46.8 33.1 34.3 51.9 71.8 71.7
61.9

TELECOM/
RO

SCADA
VERNDAH

ROOM
W
COMPOUND WALL 3.05m HIGH
13.8 57.5 64.1 48.8 32.4 31.3 49.0 69.1 73.1 (BRICK MASNORY) WITH ADDITIONAL
3000
ERC-01

ERC-02

0.6m HIGH CONCERTINA FENCE


GATE

67.5 49.8 33.7 31.6 47.8 70.1 80.6


12.4 63.0
34.6 48.6 71.1 94.8
13.0 81.9 78.8 54.1 37.8

BATTERY ROOM
CO2 ROOM
56.3 56.3 98.9
19.8 99.7 98.7 65.8 48.8 43.7
TO TERRACE
TANK 104
81.5
19.9 102 87.5 76.1 64.7 60.4 67.6
N 2395294.100
89.7 86.7 85.0 88.5 92.4
18.1 85.6 96.9 88.8 E 279885.457
70
00

00
20807
SV

50
-3 107 103 104
84.0 97.2
1.2M WIDE FOOT PATH
1.2 MD
M V
WID
E STEEL CAGE
FO
OT (7000x5000x2700) N 2395287.990
PA
TH
E 279892.220
40000
HAZIRA-OPaL NAPHTHA FEED PIPELINE(PROPOSED)
04-SV-1303 RO
W

00
50
TO NAVA DHANTURIYA

SHANKAR CHINTAKUNTLA (C262)


0
00
10
RO
W
Luminaire Schedule
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.

12-JUL-2018
Symbol Qty Label Total Lamp Lumens LLF Description
HEIGHT OF POLE CONSIDERED AS IN LEGEND,
CALCULATION POINTS CONSIDERED AT G.L.
6 LSTP-90-CDL 9644 0.700 90W LED STREET LIGHT STREETLIGHT POLE 5M(ON TERRACE) TILT 15DEG.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 18 of 24
AROUND BUILDING AREA Illuminance Lux 61.31 108 4.1 0.07 0.04
SV3 ROAD AREA
TO JUNA DHANTURIYA

WATER LINE 1
1.5" GI PIPE
N 2395327.369
E 279890.271
TBM-1 ON BORE

2500
ACCESS ROAD
RL-96.212 75.2 35.2 12.4
SOAK-PIT/
ANEROBIC FILTER
(10 USERS)
91.9 27.9 10.3
TUBEWELL PLATEFORM

TUBEWELL
2260X2260
96.2 28.2 6.0
SEPTIC TANK

D.G ROOM
(10 USERS)
74.06 64.6 73.7
TWO POLE
STRUCTURE
ROAD
50.4 76.9 52.2
IC
TO TERRACE 96.2 28.2 6.0
DRINKING
TANK

ELECTRICAL
EQUIPMENT
TOILET WATER

ROOM
93.7 26.0 6.3 WATER LINE
GUARD
ROOM 1.5" GI PIPE
ENTRY
DOOR
64.8 76.8 20.1
RO
W
COMPOUND WALL 3.05m HIGH

TELECOM/
VERNDAH
(BRICK MASNORY) WITH ADDITIONAL

SCADA
ROOM
3000
ERC-01

ERC-02
0.6m HIGH CONCERTINA FENCE
GATE

BATTERY ROOM
CO2 ROOM
TO TERRACE
TANK
N 2395294.100
E 279885.457
70
00

00
20807
SV

50
-3
1.2M WIDE FOOT PATH
1 .2 MD
M
W ID V
EF STEEL CAGE
OO (7000x5000x2700)
TP N 2395287.990
AT
H E 279892.220
40000
HAZIRA-OPaL NAPHTHA FEED PIPELINE(PROPOSED)
04-SV-1303 RO
W

00
50
TO NAVA DHANTURIYA

0
00
10

SHANKAR CHINTAKUNTLA (C262)


RO
W
Luminaire Schedule
**NOTE**
Label Total Lamp Lumens LLF Description NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty

12-JUL-2018
HEIGHT OF POLE CONSIDERED AS IN LEGEND,
CALCULATION POINTS CONSIDERED AT G.L.
2 LSTP-90-CDL 3214.67 0.700 90W LEDSTREET LIGHT STREETLIGHT POLE 9M TILT 15DEG.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 19 of 24
ROAD AREA Illuminance Lux 61.31 108 4.1 0.07 0.04
SV3 NEAR SV
TO JUNA DHANTURIYA

WATER LINE 1
1.5" GI PIPE
N 2395327.369
E 279890.271
TBM-1 ON BORE 2500
ACCESS ROAD
RL-96.212
SOAK-PIT/
ANEROBIC FILTER
(10 USERS)
TUBEWELL PLATEFORM

TUBEWELL
2260X2260
SEPTIC TANK

D.G ROOM
(10 USERS)
TWO POLE
STRUCTURE
IC
TO TERRACE
DRINKING
TANK

ELECTRICAL
EQUIPMENT
TOILET WATER

ROOM
GUARD WATER LINE
ROOM 1.5" GI PIPE
ENTRY
DOOR
RO
W
COMPOUND WALL 3.05m HIGH

TELECOM/
VERNDAH
(BRICK MASNORY) WITH ADDITIONAL

SCADA
ROOM
3000
ERC-01

ERC-02

0.6m HIGH CONCERTINA FENCE


GATE

BATTERY ROOM
CO2 ROOM
TO TERRACE
TANK
N 2395294.100
E 279885.457
144
20807

116
66.8 230 75.8 9.7
8.8 SV 1.2M WIDE FOOT PATH
-3
1.2 MD
M V
WID 9.7 16.3 10.2
E STEEL CAGE
FO
OT (7000x5000x2700) N 2395287.990
PA
TH
E 279892.220
40000
HAZIRA-OPaL NAPHTHA FEED PIPELINE(PROPOSED)
04-SV-1303 RO
W

00
50
TO NAVA DHANTURIYA

SHANKAR CHINTAKUNTLA (C262)


0
00
10
**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
RO
HEIGHT OF POLE CONSIDERED AS IN LEGEND,
W
CALCULATION POINTS CONSIDERED AT G.L.
STREETLIGHT POLE 4.5M TILT 15DEG.
Luminaire Schedule

12-JUL-2018
Symbol Qty Label Total Lamp Lumens LLF Description
1 FWL1315-60-CL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 20 of 24
NEAR SV STATION Illuminance Lux 64.55 244 2.9 0.04 0.01
SV4 AROUND BUILDING AREA
0
2.87
9881
N 23
.030
6141
E 27
4
.698
6140
E 27
26.0
86.9 52.1 25.3
87.8 64.6 43.9 32.8
63.3
L
IGH NA
m H DITIO
87.8 3.05 H AD
LL IT
38.0 WA Y) W E
.508 47.5 68.5 ND R C
60.2 OU ASNO FEN
6105 48.2 MP A
E 27 CO ICK M RTIN
E
(BR NC
64.8 H CO
34.3 HIG
4 64.2 48.1 0.6m
9.71
94.2
16.4
98 79

AROU
N 23 41
61 30.5
E 27 63.9

ND BL
36.0 34.9
93.2 81.5
10.0

DG. AR
EA
.920
6104 38.6 68.6
E 27 9.5 34.1 39.7
65.0
39.8 117
37.8 25.5 26.5 65.7
.06 9
39 87 79
N2
31
76 14 4.1
E2
54.7 86.8
37.6 47.3 48.10
21.5 1.09 50.4
31.5 50.3
75. 660 45.0 48.1 60.6 3
N 23 987 4.43
63.9 9877 UT
1.7 60 74.0 30.0 N 23 BH
E 27 612 .502 BH
AD
6150 TO
E 27 4.16
0
94.2 78.5 9877
17.5 N 23
82.3 .090
42.2 TO
6151
E 27
T ERRACE
22.2 T ANK
11.3
IC

1.2M
28.2 81.5 56.4 13.1
51.8

WI DE
FOOT
32.4 20.7

PA TH
37.5
118.712
E 276
0 IDTH
7. 66 MW
98 75 7.0
N 23 AD
.315 RO AD
EL RO
6115 TT NG
E 27 MA IS TI
EX
9
6. 94
98 75
N 23 84
61 14.9
E 27

SHANKAR CHINTAKUNTLA (C262)


Luminaire Schedule

12-JUL-2018
**NOTE**
Label Total Lamp Lumens LLF Description NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol Qty
HEIGHT OF POLE CONSIDERED AS IN LEGEND,
CALCULATION POINTS CONSIDERED AT G.L.
6 LSTP-90-CDL 9644 0.700 90W LED STREET LIGHT STREETLIGHT POLE 5M(ON TERRACE) TILT 15DEG.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 21 of 24
AROUND BUILDING AREA Illuminance Lux 50.10 117 9.5 0.19 0.08
SV4 NEAR SV
0
2.87
9881
N 23
.030
6141
E 27
4
.698
6140
E 27
L
IGH NA
m H DITIO
3.05 H AD
LL IT
WA Y) W CE
.508 ND R N
OU ASNO A FE
6105 MP N
E 27 CO ICK M ERTI
(BR CONC
H
HIG
4 0.6m
9.71
98 79
N 23 41
61 30.5
E 27
.920
6104
E 27
9
79 .06
3 9 87
N2
31
76 14 4.1
E2
75. 660 3
N 23 987 4.43
9877 UT
1.7 60 N 23 AD
BH
E 27 612 .502 BH
6150 TO
E 27 4.16
0
9877
N 23
.090
6151

8.8
TO
E 27
T ERRACE
T ANK

116
66.8
IC

1.2M

9.7

144
WI DE

230
16.3
FOOT

75.8
PA TH

10.2

9.7
118.712
E 276
0 IDTH
7. 66 MW
98 75 7.0
N 23 AD
.315 RO AD
EL RO
6115 TT NG
E 27 MA IS TI
EX
9
6. 94
98 75
N 23 .984
61 14
E 27

SHANKAR CHINTAKUNTLA (C262)


**NOTE**
NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
HEIGHT OF POLE CONSIDERED AS IN LEGEND,
CALCULATION POINTS CONSIDERED AT G.L.
STREETLIGHT POLE 4.5M TILT 15DEG.
Luminaire Schedule

12-JUL-2018
Symbol Qty Label Total Lamp Lumens LLF Description
1 FWL1315-60-CDL 6508.2 0.700 60W LED FLAMEPROOF WELLGLASS FITTING.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 22 of 24
NEAR SV4 Illuminance Lux 64.59 202 10.3 0.16 0.05
SV4 ROAD AREA
0
2.87
9881
N 23
.030
6141
E 27
4
.698
6140
E 27
L
IGH NA
m H DITIO
3.05 H AD
LL IT
WA Y) W E
.508 ND R C
12.4 OU ASNO FEN
6105 MP A
E 27 CO ICK M RTIN
35.2 (BR NC
E
H CO
75.2 HIG
10.3 0.6m
4
9.71
27.9 98 79
N 23 41
91.9 6.0 61 30.5
E 27
28.2
96.2 73.7
64.6
6
74.0 52.2
.920
6104 76.9
E 27
50.4
6.0
RO

28.2
AD

96.2
6.3
.06 9
26.0 39 87 79
N2
93.7 31
20.1 76 14 4.1
E2
76.8
64.8
75. 660 3
N 23 987 4.43
9877 UT
1.7 60 N 23 BH
E 27 612 .502 AD
6150 BH
TO
E 27 0
4.16
9877
N 23
.090
TO 6151
E 27
T ERRACE
T ANK
IC

1.2M
WI DE
FOOT
PA TH
118.712
E 276
0 IDTH
7. 66 MW
98 75 7.0
N 23 AD
.315 RO AD
EL RO
6115 TT NG
E 27 MA
IS TI
EX
9
6. 94
98 75
N 23 84
61 14.9
E 27

SHANKAR CHINTAKUNTLA (C262)


Luminaire Schedule

12-JUL-2018
**NOTE**
Qty Label Total Lamp Lumens LLF Description NO OBSTRUCTIONS CONSIDERED WHILE DESIGNING.
Symbol HEIGHT OF POLE CONSIDERED AS IN LEGEND,
CALCULATION POINTS CONSIDERED AT G.L.
2 LSTP-90-CDL 3214.67 0.700 90W LEDSTREET LIGHT STREETLIGHT POLE 9M TILT 15DEG.
Calculation Summary
Label Calc Type Units Avg. Max Min Min/Avg. Min/Max.

Page 23 of 24
ROAD AREA Illuminance Lux 61.31 108 4.1 0.07 0.04
1) Emergency lighting is not considered/shown in the layouts. Contractor
to ensure that 20-25% of normal lighting fixtures shall be considered for
emergency lighting.

12-JUL-2018