Source/Grid Data: 0 % Calc

The document provides technical specifications for an electrical power grid including source voltage, fault current, transformer ratings, load characteristics, and calculations of impedance values and short circuit current. It summarizes the key parameters of a 33kV power system including a 15MVA transformer, an 8MVA load consisting of 80% motor load, and calculates the per unit impedance and 7.27kA short circuit current at the fault location.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views6 pages

Source/Grid Data: 0 % Calc

The document provides technical specifications for an electrical power grid including source voltage, fault current, transformer ratings, load characteristics, and calculations of impedance values and short circuit current. It summarizes the key parameters of a 33kV power system including a 15MVA transformer, an 8MVA load consisting of 80% motor load, and calculates the per unit impedance and 7.27kA short circuit current at the fault location.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

Source/Grid Data

Source Voltage 33 kV
Source Fault Current 31.5 kA
Source Fault MVA 1800.46681 MVA
Source X/R 14
Base MVA 100 MVA
Nominal kV (Bus kV) / Base kV
Primary 33 kV
Sec 11 kV
Transformer Data
Number Of Transfo 1 Nos
Transfo MVA 15 MVA
Transfo Z % 10 %
Transfo X/R 18.6
Transformer Volt Ratio
Primary 33 kV
Sec 11 kV
Transformer Primary Tap 100 %
So, if +2.5% tap is applied on primary side, you can enter
0 %
102.5%
Calc

Load Data
Type 80 %Motor 20 % Static
S 8 MVA
Power Factor 0.8
P 6.4 MW (kW = kVA * CosØ)
Q 4.8 MVAR (Q = Sqrt (S2-P2))

New Ratio and Base kV


Primary 33

Sec 11

Zpu for Power Grid / Source


Zbase = 10.89000 Ohm Zpu = 0.0555

Zohms = 0.6048 Ohm Xpu = 0.0554

Rpu = 0.00396

Zpu for Transformer

Zpu = 0.66667 66.67 %

Xpu = 0.66570524788 66.57 %

Rpu = 0.03579060472 3.58 %

Zpu Total at Fault Location


Zpu (Source) + Zpu (Trafo) = Zpu Total = 0.722208
Xpu = 0.7211052526
Rpu = 0.0397477479
X/R = 18.142041

3-Phase Short Circuit Current

Ik" Short Circuit kA 7.27 kA


Vb 33
Sbase 100
33 kV
11 kV

15 MVA
10 %Zo
18.6 X/R

9.985579 %X
0.536859 %R

66.66667 %Zn
66.57052 %X
3.57906 %R

Load Data

Type 100 %Motor 0 % Static


S 12 MVA
pf 0.8
P 9.6 MW (kW = kVA * CosØ)
Q 7.2 MVAR (Q = Sqrt (S2-P2))

Ppu 0.096
Qpu 0.072
Spu 0.12
Vs 1
Delta V
Vr 1