Concentric: A Ruskin Company
Concentric: A Ruskin Company
CONCENTRIC
Product Information & Applications
Concentrics
Table of Contents
02
510 & 515 Series
flush mount
concentric diffuser system
with filter grill
RRS’s 510 & 515 SERIES concentric diffuser systems are designed to provide a single point air distribution system. The
systems may be used with either a “T-Bar” ceiling or a plaster ceiling.
515 series — same as the 510 series, with an additional 4" fiberglass filter in the return section.
hanging
support from
the diffuser
03
510 & 515 Series
2.25
Typical specifications
Furnish and install Ruskin Rooftop TRANSITION
DIFFUSER BOX
Systems “510 & 515 Series” BOOT
concentric diffuser systems. The system
shall consist of an aluminum supply
diffuser with an aluminum eggcrate
return. It shall also have a permanent
(not adhesive) anti-sweat gasket and (OPTIONAL FILTER)
hanging supports. All units that are five
(5) tons and smaller shall have a molded
fiberglass interior transition.
ALUMINUM
DIFFUSER
ANTI-SWEAT RETURN GRILL
GASKET
Static Throw in Neck Jet Noise UNIT Static Throw in Neck Jet Noise UNIT
Model # CFM Pressure Feet Velocity Velocity Level WEIGHT Model # CFM Pressure Feet Velocity Velocity Level WEIGHT
600 0.09 10-14 234 417 18 27.00 4500 0.31 25-34 922 1795 40 151.00
800 0.11 12-18 313 556 20 27.00 01-510-50 5000 0.34 24-33 938 1829 40 151.00
01-510-16
1000 0.14 15-20 391 691 20 27.00 5400 0.39 32-41 1083 2107 45 151.00
01-515-16
1200 0.17 16-22 469 833 25 27.00 5600 0.36 28-37 1000 2082 45 158.00
1400 0.20 17-24 547 972 30 27.00 6000 0.42 40-50 1071 2230 45 158.00
01-510-60
1000 0.14 15-20 391 694 20 27.00 6400 0.50 43-52 1143 2379 50 158.00
1200 0.17 16-22 469 833 25 27.00 6600 0.54 45-56 1179 2454 50 158.00
1400 0.20 17-24 547 972 30 27.00 7200 0.39 26-35 996 2093 45 197.00
01-510-18
1600 0.24 18-25 625 1111 30 27.00 8000 0.50 42-51 1107 2326 50 197.00
01-515-18 01-510-80
1800 0.30 20-28 703 1250 35 27.00 8400 0.56 44-54 1162 2442 50 197.00
2000 0.36 21-29 781 1389 40 27.00 8800 0.63 48-59 1217 2558 50 197.00
2200 0.40 22-30 859 1528 40 27.00 9600 0.41 32-41 1036 2159 45 197.00
2600 0.17 19-24 663 1294 30 42.00 01-510-100 10000 0.45 37-46 1079 2249 45 197.00
2800 0.20 20-28 714 1393 35 42.00 10400 0.50 42-51 1122 2339 50 197.00
01-510-20 3000 0.25 21-29 765 1492 35 42.00 10000 0.57 37-46 713 1506 35 244.00
3200 0.31 22-29 816 1592 40 42.00 11000 0.72 46-56 785 1657 35 244.00
01-510-300
3400 0.37 22-30 867 1692 40 42.00 12000 0.90 54-66 856 1808 40 244.00
3600 0.17 22-29 844 1646 34 104.00 13000 1.10 62-75 927 1958 40 244.00
01-510-22 4000 0.21 24-33 938 1829 40 104.00
4400 0.27 28-37 1032 2011 40 104.00
1. All data is based on the Air Diffusion Council guidelines.
2. Throw data is based on Terminal Velocities of 75 FPM using isothermal air.
3. “Neck Velocity” is the speed in feet per minute of the air coming into the diffusers – similar to duct velocity.*
4. “Jet Velocity” is the speed in feet per minute of the air exiting the diffusers.*
5. Actual noise levels are less than those shown.
* Jet velocity is higher than neck velocity on the (510) flush mount diffusers because the air gets “pinched down”
as it exits – similar to high pressure water coming out of a garden hose with a sprayer.
The drop down (530) diffusers have enough face area in the supply grills so that the air velocity does not
increase significantly as it exits the concentric. That is why “Neck Velocity” and “Jet Velocity” are the same for
the drop downs.
04
FLUSH MOUNT
CONCENTRIC DIFFUSER SYSTEM
WITH FILTER GRILL
Dimensional Data
Duct
Model # A B C D E F G H Size
01-510-16 47 5 / 8 23 5 / 8 13 1 / 2 21 45 22 1 / 2 11 1 /4 10 1 / 2 16 RD
01-515-16
01-510-18 47 5 / 8 23 5 / 8 13 1 / 2 21 45 22 1 / 2 11 1 /4 10 1 / 2 18 RD
01-515-18
01-510-20 47 5 / 8 29 5 / 8 16 5 / 8 27 45 22 1 / 2 11 1 /4 13 1 / 2 20 RD
Dimensional Data
Duct
Model # A B C D E F G H I J Size
01-510-22 47 5 / 8 35 5 / 8 23 1 /4 33 45 4 1 /2 18 2 1 /4 28 2 1 /2 18x28
01-510-50 47 5 / 8 41 5 / 8 29 1 /4 39 45 4 1 /2 18 2 1 /4 32 3 1 /4 18x32
01-510-60 47 5 / 8 47 5 / 8 29 1 /4 45 45 4 1 /2 18 2 1 /4 36 4 1 /2 18x36
01-510-80 59 5 / 8 59 5 / 8 35 1 /4 57 57 4 1 /2 24 2 1 /4 48 4 1 /2 24x48
01-510-100 59 5 / 8 59 5 / 8 35 1 /4 57 57 4 1 /2 24 2 1 /4 54 1 1 /2 24x54
01-510-300 63 5 / 8 63 5 / 8 40 63 1 / 8 63 1 / 2 4 1 / 2 28 1 1 /4 60 1 1 /2 28x60
05
530 & 535 Series
RRS’s 530 & 535 SERIES concentric diffuser systems are designed to provide a single point air distribution system
with the added benefit of having directional air control. The systems may be used with either a “T-Bar” ceiling, a plaster ceiling, or
with no ceiling at all.
535 Series — Same as the 530 series, with an additional 1" Hogs Hair filter in the return section.
built in
hanging rings turning vane
06
SIDE DISCHARGE
CONCENTRIC DIFFUSER SYSTEM
WITH FILTER GRILL
DIFFUSER BOX
Typical specifications
Furnish and install Ruskin Rooftop Systems “530 & 535
Series” concentric diffuser systems. The system shall ANTI-SWEAT
consist of an aluminum double deflection supply diffuser GASKET DOUBLE
with an aluminum eggcrate return. ALL EXPOSED DEFLECTION GRILL
SURFACES (BELOW CEILING) MUST BE BRUSHED
ALUMINUM. It shall also have a permanent (not adhesive) TRANSITION
anti-sweat gasket and hanging supports. All units that BOOT
are five (5) tons and smaller shall have a molded
fiberglass interior transition. (OPTIONAL FILTER)
RETURN GRILL
600 0.09 8-15 210 20 38.00 5600 0.36 39-49 920 30 217.00
01-530-16 800 0.11 9-16 281 20 38.00 5800 0.39 42-51 954 30 217.00
01-535-16 1000 0.14 10-17 351 20 38.00 01-530-60 6000 0.42 44-54 1022 30 217.00
1200 0.17 11-18 421 20 38.00 01-535-60 6200 0.46 45-55 1056 30 217.00
1200 0.17 11-18 421 20 38.00 6400 0.50 46-55 1090 30 217.00
1400 0.20 12-19 491 20 38.00 6600 0.54 47-56 1124 30 217.00
01-530-18 1600 0.24 12-20 561 20 38.00 7200 0.39 33-38 827 25 238.00
01-535-18 1800 0.30 13-21 632 20 38.00 7600 0.43 36-41 873 25 238.00
01-530-80
2000 0.36 14-23 702 20 38.00 8000 0.50 39-44 918 30 238.00
01-535-80
2200 0.40 16-25 772 20 38.00 8400 0.56 43-49 964 30 238.00
2600 0.17 24-29 669 20 82.00 8800 0.63 47-55 1010 30 238.00
2800 0.20 25-30 720 25 82.00 9200 0.74 49-57 1056 50 238.00
01-530-20
3000 0.25 27-33 772 25 82.00 9400 0.80 50-58 1079 55 238.00
01-535-20
3200 0.31 28-35 823 25 82.00 9600 0.83 52-62 1102 55 238.00
01-530-100
3400 0.37 30-37 874 30 82.00 9800 0.86 55-63 1125 55 238.00
01-535-100
3600 0.17 25-33 851 30 122.00 10000 1.00 57-65 1148 55 238.00
3800 0.18 27-35 898 30 122.00 10200 1.07 60-68 1171 60 238.00
01-530-22
4000 0.21 29-37 946 30 122.00 10400 1.16 63-71 1194 60 238.00
01-535-22
4200 0.24 32-40 993 30 122.00 10000 .51 46-54 907 30 285.00
4400 0.27 34-42 1040 30 122.00 10500 .58 50-58 953 30 285.00
4600 0.31 26-31 841 30 145.00 11000 .65 53-61 998 30 285.00
01-530-300
4800 0.32 27-32 878 30 145.00 11500 .73 55-64 1043 30 285.00
01-530-50 01-535-300
5000 0.34 28-33 915 30 145.00 12000 .82 58-67 1089 30 285.00
01-535-50
5200 0.36 28-34 951 30 145.00 12500 .91 61-71 1134 30 285.00
5400 0.39 29-35 988 30 145.00 13000 1.00 64-74 1179 35 285.00
1. All data is based on the Air Diffusion Council guidelines. * J et velocity is higher than neck velocity on the (510) flush mount diffusers because the air gets “pinched down”
2. Throw data is based on Terminal Velocities of 75 FPM using isothermal air. as it exits – similar to high pressure water coming out of a garden hose with a sprayer.
3. “Neck Velocity” is the speed in feet per minute of the air coming into the diffusers – similar to duct velocity.* The drop down (530) diffusers have enough face area in the supply grills so that the air velocity does not
4. “Jet Velocity” is the speed in feet per minute of the air exiting the diffusers.* increase significantly as it exits the concentric. That is why “Neck Velocity” and “Jet Velocity” are the same for
5. Actual noise levels are less than those shown. the drop downs.
6. Throw is based on diffuser blades being directed in a straight pattern.
07
530 & 535 Series
Dimensional Data
Duct
Model # A B C D E F G H I J K Size
01-530-16 47 5 / 8 23 5 / 8 11 3 / 8 21 1 / 2 45 1 / 2 22 1 / 2 11 1 / 2 10 3 /4 45 1 / 2 21 1 / 2 7 1/8 16 RD
01-535-16
01-530-18 47 5 / 8 23 5 / 8 11 3 / 8 21 1 / 2 45 1 / 2 22 1 / 2 11 1 / 2 10 3 /4 45 1 / 2 21 1 / 2 7 1/8 18 RD
01-535-18
01-530-20
47 5 / 8 29 5 / 8 14 3 / 8 27 1 / 2 45 1 / 2 22 1 / 2 11 1 / 2 13 3 /4 45 1 / 2 27 1 / 2 8 1/8 20 RD
01-535-20
Dimensional Data
Duct
Model # A B C D E F G H I J k l m Size
01-530-22
47 5 / 8 35 5 / 8 20 5 / 8 33 1 / 2 45 1 / 2 4 1 / 2 18 2 1 / 2 28 2 3 /4 45 1 / 2 33 1 / 2 9 1 / 8 18x28
01-535-22
01-530-50
47 5 / 8 41 5 / 8 24 5 / 8 39 1 / 2 45 1 / 2 4 1 / 2 18 2 1 / 2 32 3 3 /4 45 1 / 2 39 1 / 2 9 1 / 8 18x32
01-535-50
01-530-60 47 5 / 8 47 5 / 8 24 5 / 8 45 1 / 2 45 1 / 2 4 1 / 2 18 2 1 / 2 36 4 3 /4 45 1 / 2 45 1 / 2 10 1 / 8 18x36
01-535-60
01-530-80 59 5 / 8 59 5 / 8 30 5 / 8 57 1 / 2 57 1 / 2 4 1 / 2 24 2 1 / 2 48 4 3 /4 57 1 / 2 57 1 / 2 11 1 / 8 24x48
01-535-80
01-530-100
59 5 / 8 59 5 / 8 30 5 / 8 57 1 / 2 57 1 / 2 4 1 / 2 24 2 1 / 2 54 1 3 /4 57 1 / 2 57 1 / 2 11 1 / 8 24x54
01-535-100
01-530-300
65 5 / 8 65 5 / 8 40 1 / 2 63 1 / 2 63 1 / 2 4 1 / 2 28 1 1 / 2 60 1 3 /4 63 1 / 2 63 1 / 2 12 1 / 8 28x60
01-535-300
08
570 & 575 Series
Specialty diffuser systems
for open ceiling applications
return duct
drop w/ grill
(field supplied)
supply duct
(field supplied)
“575 drum louver
RRS’s 570 SERIES supply diffuser systems are RRS’s 575 SERIES supply diffuser systems are
designed to provide an air distribution system with the designed to provide an air distribution system with the
benefit of having directional air control. The system is ideal benefit of having directional air control. The system is ideal
for open ceiling applications that need single point supply for open ceiling applications that need single point supply
air with control over where the air is distributed. air with long throws. The Drum Louver allows you to “spot”
the air where you need it the most.
Bottom panel
(Panted to match Grill)
A
A
Engineering Data A
NECK Unit
RRS MODEL# CFM VEL. STATIC THROW NOISE weight
internal double deflection grill
600 270 0.04 12-17 20 25.00 air deflector (all 4 sides)
800 364 0.06 16-22 20 25.00
1000 450 0.07 20-28 20 25.00
1200 536 0.09 24-33 20 25.00
01-570-24
1400 625 0.11 28-39 20 25.00
1600 714 0.14 33-44 25 25.00
1800 804 0.16 41-52 30 25.00
2000 893 0.19 46-55 30 25.00 supply duct
3600 810 0.19 49-54 25 51.00
3800 863 0.21 50-55 25 51.00
01-570-36 4000 909 0.23 51-56 30 51.00
4200 955 0.26 53-60 30 51.00
4400 1000 0.30 54-62 30 51.00 double
5400 1116 0.18 45-53 30 80.00 deflection grill
5600 1157 0.19 47-55 30 80.00
5800 1198 0.22 50-57 30 80.00 section a-a
internal air
6000 1240 0.25 53-59 30 80.00 deflector
01-570-40
6200 1281 0.27 54-61 35 80.00
6400 1322 0.30 56-63 35 80.00
6600 1364 0.33 58-65 35 80.00
7000 1405 0.37 59-67 35 80.00
5600 920 0.18 39-49 30 105.00 bottom of
5800 954 0.21 42-51 30 105.00 supply box
6000 1022 0.24 44-54 30 105.00
01-570-60
6200 1056 0.26 45-55 35 105.00
RRS MODEL# A B
6400 1890 0.28 46-55 35 105.00
01-570-24 23 5 /8 7 1 /4
6600 1124 0.30 47-56 35 105.00
7200 827 0.18 33-38 25 175.00 01-570-36 35 5 / 8 9
8000 918 0.20 39-44 25 175.00
01-570-40 40 11
01-570-80 8800 1010 0.22 47-55 30 175.00
9600 1101 0.27 54-62 30 175.00 01-570-60 47 5 / 8 10
10000 1148 0.30 57-65 35 175.00
01-570-80 59 5 / 8 11
11200 1140 0.30 44-65 40 212.00
01-570-300
12000 1300 0.34 52-70 40 212.00 01-570-300 65 5 / 8 11
1. For white diffusers change the “01” numbers to “90.” Example: 90-570-24
2. Special sizes available. Call for details.
10
575 Series
575 Series
DRum louver diffusers
A B
bottom panel
(painted to match grill)
C D
E
unit
RRS MODEL# A B C D E GRILL SIZE weight
grill pivot RRS MODEL# CFM NOISE STATIC THROW NOISE STATIC THROW
point
4000-
01-575-2010 <45 0.420 34-37 <40 0.29 40-45
5000
11
570 & 575 Series
The Duct Cap Accessory is Attached to the Diffuser & Fully Insulated
B B
A A
01-570-8036 36 36
01-570-80
01-570-8042 42 42
01-570-300 01-570-30044 44 44