Tricon Field Termination Guide
Tricon Field Termination Guide
*9720159-001* *2.0*
https://www.se.com
Information in this document is subject to change without notice. Companies, names and data used in examples
herein are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form
or by any means, electronic or mechanical, for any purpose, without the express written permission of Schneider
Electric Systems USA, Inc.
Schneider Electric, EcoStruxure, Triconex, Tricon, and TriStation are trademarks and the property of Schneider
Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective owners.
Original Instructions
The original English version of this document has been verified by Schneider Electric. It is the only version of the
document that contains “original instructions.”
Translated versions of this document must bear the words “translation of the original instructions,” in the translated
language, and must be accompanied by the original English instructions.
Contents
Preface xi
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
We Welcome Your Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
iv Contents
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Contents v
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
vi Contents
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Contents vii
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
viii Contents
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ix
Safety Information
Important Information
Read these instructions carefully and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may
appear throughout this manual or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction, installation, and
operation of electrical equipment and has received safety training to recognize and avoid the hazards
involved.
x
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARCH FLASH
• Use appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E or CSA Z462.
• This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only allow persons with expertise and training in Triconex systems and ISA 84/IEC 61511 to pro-
gram, install, alter, and apply this product.
• Follow all local and national safety codes and standards.
• Follow the recommendations provided in the Triconex System Security Reference Guide, available
on the Global Customer Support website.
• Validate the control program with the installed safety system according to ISA 84/IEC 61511.
Failure to follow these instructions can result in death, serious injury, environmental damage, or
equipment damage.
Preface
This guide includes information on external termination products for EcoStruxure™ Triconex™
Tricon™ 11.5 and later 11.x systems.
Related Documents
• Planning and Installation Guide for Tricon 11.5 and Later 11.x Systems
• Safety Considerations Guide for Tricon 11.5 and Later 11.x Systems
• TriStation 1131 Developer’s Guide
Technical Support
Customers in the U.S. and Canada can obtain technical support from the Global Customer
Support (GCS) center at the website listed below. International customers should contact their
regional support center.
https://pasupport.schneider-electric.com/ (registration required)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
xii Preface
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
1
Introduction to Field Terminations
Overview 2
External Termination Panels 2
Cables 6
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
2 Chapter 1 Introduction to Field Terminations
Overview
This chapter introduces the Triconex external field termination products for the Tricon system.
All cables and termination panels are built to withstand harsh industrial environments. The
environmental specifications for components used on these products are the same as for a
Tricon chassis. For more information, see the Planning and Installation Guide for Tricon 11.5 and
Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
External Termination Panels 3
In addition to standard termination panels, there are other types of termination panels,
including:
• Basic termination panels
• Hazardous location (nonincendive) termination panels
• RG 1.180 Termination Panels
• Termination panels with interposing relays
• Bypass panels for digital inputs
• Termination panels with RTD/TC/AI input signal conditioning
• Termination panels for 3603B digital output modules
• Termination panels for 3806E analog output modules
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
4 Chapter 1 Introduction to Field Terminations
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
External Termination Panels 5
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
6 Chapter 1 Introduction to Field Terminations
Cables
Three types of cables can be used with the Tricon controller:
• Interface Cables
• Fanned-Out Cables
• Special Cables (Relay Loopback)
You can order standard Triconex interface cables and I/O bus cables that meet flame test ratings
as described in this table.
Cable Rating
Interface cables FT4 Vertical Flame Test-Cables in Cable
(connect external termination panels to I/O modules) Trays per C.S.A. C22.2 No. 0.3-92 Para 4.11.4a
a. Cables will be marked with FT4 or CMG rating, but they all actually meet the more stringent FT4
rating.
b. Cables will be marked with FT6 or CMR rating, but they all actually meet the more stringent FT6
rating.
The above cables may also be ordered as Low Smoke Zero Halogen (LSZH) cables. These
equivalent cables are made of XLPE (cross-linked polyethylene), which is non-halogenated and
flame-retardant, providing fire safety characteristics of low smoke, low toxicity, and low
corrosion in applications where the protection of people and equipment from toxic and
corrosive gases is critical. These cables are certified to a series of IEC60754 and IEC60332
standards that define emissions levels.
Interface Cables
Interface cables are packaged with all external termination panels. Each interface cable has a
female connector on one end for connection to the male connector on a Tricon chassis backplane.
The opposite end has a keyed male connector for connection to a termination panel.
There are two types of interface cables: ninety-degree cables that exit ninety degrees from the
back cover of the female connector, and zero-degree cables that exit zero degrees (straight) from
the back cover of the female connector. LSZH cables are available as ninety-degree cables only.
Zero-degree cables are designed to be used with G-Series Enclosures for Tricon controllers, that
have front access. For more information on G-Series Enclosures for Tricon Systems, see the
G-Series Enclosures Product Specification Sheet, PSS Number: PSS 21H-2X8 B3, on the Global
Customer Support (GCS) center website at https://pasupport.schneider-electric.com.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Cables 7
External termination panel model numbers that end with a “Z” contain zero-degree interface
cables. Model numbers for ninety-degree configurations are referenced throughout this guide.
It is implied that where a model number is referenced for a ninety-degree configuration, a zero-
degree configuration is also available. For cable part numbers, see Table 222 Part Number
Cross-Reference—Tricon ETPs (page 395).
Although the standard length of all interface cables is 10 feet (3 meters), you may order any
length cable up to 90 feet (27.4 meters) in 10-foot increments using the last two digits of the
termination panel’s model number to specify length in feet. For example, specify 9xxx-x50F if
you want a 50-foot (15 meter) cable instead of the standard 10-foot (3-meter) cable.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8 Chapter 1 Introduction to Field Terminations
Fanned-Out Cables
Fanned-out cables are a lower-cost alternative to using external termination panels. Fanned-out
cables allow you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from
a Tricon chassis. One end of a fanned-out cable has a female connector that connects to a Tricon
chassis backplane. The other end of the cable contains 50 fanned-out leads, each individually
labeled with its corresponding connector pin number.
Each fanned-out cable has the following characteristics:
• PVC outer covering
• 56-pin connector at one end
• 50 stranded, stripped, tinned and labeled 22-gauge leads at opposite end
Fanned-out cables should only be used with digital input and digital output modules. They are
not certified for use with analog signals. Contact the Global Customer Support (GCS) center if
you need a fanned-out cable for handling analog signals.
Although the normal length of all fanned-out cables is 10 feet (3 meters), any length cable can
be ordered up to 90 feet (27.4 meters) in 10-foot increments, using the last two digits of the cable
model number to specify the length in feet. For example, the model number 9101-050F specifies
a 50-foot cable instead of the normal 10-foot cable.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Cables 9
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
2
Field Termination Options and
Installation
Overview 11
Determining Field Termination Options by Module Model Number 11
Determining Field Termination Options by Module Type 15
Installation and Removal 23
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Overview
This chapter provides information for determining field termination options using module model numbers or
module types, and it describes how to install and remove termination panels and fanned-out cables.
3501E DI, 115 VAC/VDC, 32 pts. 9561-810F 9561-110F 9551-110F n/a n/a 9101-010F n/a 9141-010F
3501T
3502E DI, 48 VAC/VDC, 32 pts. 9562-810F n/a 9552-610F n/a n/a 9101-010F n/a 9142-010F
3503E DI, 24 VAC/VDC, 32 pts. 9563-810F n/a 9553-610F 9572-610F n/a 9101-010F BP9228-010F 9143-010F
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
9563-910F
3504E DI, 24/48 VDC, 9566-810F, 24V n/a 9750-310F, 24V 9570-610F, 24V n/a n/a BP9229-010F n/a
non-isolated, 64 pts. 9565-810F, 48V 9750-410F, 48V n/a
3505E DI, 24 VDC, low threshold, 9563-810F n/a 9553-610F 9572-610F n/a 9101-010F BP9228-010F 9143-010F
32 pts. 9563-910F
3510 PI, 20-20,000 Hz, 8 pts. n/a n/a 9753-110F n/a n/a n/a n/a n/a
3511 PI, 20-20,000 Hz, 8 pts. n/a n/a 9753-110F 9793-110F 9794-110F n/a n/a n/a
3515 Pulse totalizer, 24 VDC, n/a n/a 9753-110F 9572-610F n/a n/a n/a n/a
32 pts.
3564 DI, 24 VDC, single, 64 pts. 9566-710F n/a 9553-610F 9571-610F n/a 9101-010F n/a n/a
3601E DO, 115 VAC, 16 pts. 9661-610F 9661-110F 9651-110F n/a n/a 9101-010F n/a 9670-110F
9663-610F 9664-110F 9670-610F
3601T DO, 115 VAC, 16 pts. 9663-610F 9664-110F n/a n/a n/a n/a n/a n/a
3603B DO, 120 VDC, 16 pts. n/a 9251–210 n/a n/a n/a n/a n/a n/a
Overview
11
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
12
Chapter 2
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module Commoned Non-Common. Basic Nonincendive RG 1.180 Fanned-out Bypass ERT Loop-Back
Module Description
Model # Term Panels Term Panels Term Panels Term Panels Term Panels Cables Panels Cables/Panels
3603E DO, 120 VDC, 16 pts. 9661-910Fa n/a 9651-110F n/a n/a 9101-010F n/a 9673-810Fa
3603T DO, 120 VDC, 16 pts. 9664-810Fa n/a n/a n/a n/a n/a n/a 9673-810Fa
3604E DO, 24 VDC, 16 pts. 9662-810F 9662-110F 9653-610F 9671-610F n/a 9101-010F n/a 9671-810F
3607E DO, 48 VDC, 16 pts. 9667-810F 9667-110F 9652-610F n/a n/a 9101-010F n/a 9672-810F
3611E DO, 115 VAC, 8 pts. 9661-510F n/a n/a n/a n/a n/a n/a n/a
3613E DO, 120 VDC, 8 pts. 9661-810F n/a n/a n/a n/a n/a n/a n/a
3614E DO, 24 VDC, 8 pts. 9662-910F n/a n/a n/a n/a n/a n/a n/a
3615E DO, 24 VDC, low power, 9662-710F n/a n/a n/a n/a n/a n/a n/a
8 pts.
3617E DO, 48 VDC, 8 pts. 9667-910F n/a n/a n/a n/a n/a n/a n/a
3623 DO, 120 VDC, 16 pts. 9661-910F n/a 9651-110F n/a n/a 9101-010F n/a n/a
3623T DO, 120 VDC, 16 pts. 9664-810F n/a n/a n/a n/a n/a n/a n/a
3624 DO, 24 VDC, self-protected, 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a n/a
16 pts.
3625 DO, 24 VDC, self-protected, 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
3625A 32 pts.
3636R Relay output n/a 9668-110F 9651-110F n/a n/a 9101-010F n/a n/a
3636T (non-triplicated), 32 pts.
3664 Dual DO, 24 VDC, self- 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
protected, 32 pts.
3674 Dual DO, 24 VDC, self- 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
protected, 32 pts.
3805E AO, 4–20 mA, 8 pts. n/a n/a 9853-610F 9861-610F 9860-610F n/a n/a n/a
3805H
2870H AO HART Interface n/a n/a 9853-610F 9861-610F 9860-610F n/a n/a n/a
3806E AO, 6 4–20 mA outputs, n/a n/a 9863-710F n/a n/a n/a n/a n/a
2 20–320 mA outputs (special panel)
3807 AO, 4 bipolar -60 to 60 mA 9881-810F n/a n/a 9871-810F n/a n/a n/a n/a
outputs
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module Basic Term Nonincendive RG 1.180 Fanned-out Bypass ERT Loop-Back
Module Description Upscale Downscale
Model # Panels Term Panels Term Panels Cables Panels Cables/Panels
3706A Thermocouple input, type J, 9766-210F 9766-510F n/a 9784-610F, n/a n/a n/a n/a
K, T, differential, 32 pts. upscale
9785-610F,
downscale
3708E Thermocouple input, type 9765-610F 9765-610F n/a 9786-110F 9782-110F n/a n/a n/a
E, J, K, T, isolated, 16 pts.
3700 AI, 0–5 VDC, differential, n/a 9763-810F 9761-210F, 9791-610F, 9790-610F, 9753-110F, 0–5 V 9764-310Fc
3700A 32 pts. 0–5 V current input current input
9771-210F, 9787-110F, 9792-610F, 4-20
0–5 V voltage input mA, 0-5 V,
16 VDC–56 VDC
field
9783-110F,
voltage input
inputc
2770H AI HART Interface n/a n/a 9761-210F, 9791-610F, 9790-610F, n/a n/a
0–5 V current input current input
9771-210F,
0–5 V
3701 AI, 0–10 VDC, differential, n/a 9763-810F 9761-410F n/a n/a 9753-110F, 0–10 V n/a
32 pts.
3703Ed AI, 0–5/0–10 VDC, isolated, n/a 9763-810F 9762-210F, 9791-610F, 9790-610F, 9753-110F, 0–5/0–10 V n/a
16 pts. 0–5 V current input 4–20 mA, 0–5 V
9762-410F, 9787-110F, 9792-610F, 4-20
0–10 V voltage input mA, 0-5 V,
9771-210F, 16 VDC–56 VDC
0–5 V field
9795-610F,
4–20 mA, 0–10 V
9783-110F,
voltage input
3704Ed AI, 0–5/0–10 VDC, 9765-210F, n/a 9760-210F, 9789-610F, n/a 9750-210F, 4–20 mA n/a
non-isolated, 64 pts. 0–5V 0–5 V 4–20 mA 9750-810F, 0–5/0–10 V
9760-410F,
0–10 V
13
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
14
Chapter 2
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module 3-Wire 2-Wire Nonincendive RG 1.180
Module Description Voltage Basic RTD/TC/AI
Model # 4-20 mA 4-20 mA Term Panels Term Panels
3720 AI, 0–5 VDC, single-ended, 9765-210F, n/a 9760-210F, 9789-610F, n/a 9750-210F, 4–20 mA n/a
3721d AI; 0 to 5 VDC or –5 to +5 n/a n/a 9761-210F, 9791-610F, 9790-610F, 4–20 9753-110F, 0–5 V 9764-310Fc
VDC; differential; 32 pts. 0–5 V current input mA, 0–5 V
9761-410F, 9787-110F, 9792-610F, 4-20
0–10 V voltage input mA, 0-5 V
9771-210F, 16 VDC–56 VDC
0–5 V field
9795-610F, 4–20
mA, 0–10 V
9783-110F,
voltage input
9764-310F,
RTD/TC/AI
inputc
a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is commoned.
b. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-protected and commoned.
c. Signal conditioners must be ordered separately. A total of 16 is required for each termination panel.
d. Must be configured with the TriStation 1131 software.
For more information on using Model 3625/A, 3720, 3721, and 3807 I/O Modules with low-density applications, see Appendix I,
Low-Density Chassis I/O Module Compatibility.
Determining Field Termination Options by Module Type 15
You need two termination panels (or cables) for each 32-point or 64-point DI module. Also, you
can mix any combination of two termination products listed in a particular module’s column.
For example, for a 115 VAC/VDC module you may use two 9561-810F commoned panels, or
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16 Chapter 2 Field Termination Options and Installation
one 9561-810F commoned panel and one 9561-110F non-commoned panel, or one 9551-110F
basic panel and one 9101-010F fanned-out cable.
This table identifies termination products you can use with 64-point digital input modules.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 17
You need two termination panels for each 32-point pulse totalizer input module.
a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is commoned.
You need one termination panel (or cable) for each 16-point non-supervised DO module.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
18 Chapter 2 Field Termination Options and Installation
You need one termination panel (or cable) for each 8-point or 16-point supervised DO module.
a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-
protected and commoned.
You need two termination panels (or cables) for each 32-point digital output module. Also, you
can mix any combination of two termination products listed. For example, you may use two
9662-610F panels, or one 9653-610F basic panel and one 9101-010F fanned-out cable, and so on.
For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 19
a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-
protected and commoned.
You need two termination panels (or cables) for each 32-point dual digital output module. Also,
you can mix any combination of two termination products listed. For example, you may use two
9662-610F panels, or one 9653-610F basic panel and one 9101-010F fanned-out cable, and so on.
You need two termination panels (or cables) for each 32-point relay output module. Also, you
can mix any combination of two termination products listed. For example, you may use two
9668-110F panels, two 9651-110F basic panels, or one 9668-110F panel and one 9651-110F basic
panel.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
20 Chapter 2 Field Termination Options and Installation
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 21
You need two termination panels (or cables) for each 32-point AI module. Also, you can mix any
combination of two termination products listed in a particular module’s column. For example,
with 0–5 VDC modules you may choose two 9763-810F panels, or a 9753-110F basic panel and a
9764-310F RTD/TC/AI panel, and so on. For low-density applications, see Appendix I, Low-
Density Chassis I/O Module Compatibility.
You need two termination panels (or cables) for each 64-point AI module. Also, you can mix any
combination of two termination products listed. For example, you may choose two 9760-210F
panels, or a 9750-210F basic panel and a 9760-210F panel, and so on. For low-density
applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
22 Chapter 2 Field Termination Options and Installation
You need one termination panel for each 16-point thermocouple input module.
This table identifies termination products you can use with 32-point thermocouple input
modules.
You need two termination panels for each 32-point thermocouple input module. Also, you can
use a 9766-210F panel with a 9766-510F panel.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 23
You need one termination panel for each 4-point BPAO module. For low-density applications,
see Appendix I, Low-Density Chassis I/O Module Compatibility.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
24 Chapter 2 Field Termination Options and Installation
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH
Install the recommended fuse type and value. To avoid electrical shock and equipment damage while
removing a blown fuse, use the fuse-extractor tool (#158000–01) supplied with the system.
The connector on each external termination panel, interface cable, and special cable is factory-
keyed by voltage and module type to protect against accidental connection to an incompatible
product. If you use a fanned-out cable instead of a termination panel, you must re-key its
connector according to Appendix A, Re-Keying Connectors.
Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
2 Remove incoming power from the Tricon system (optional).
3 Mount the termination panel on a DIN rail as shown in these pictures.
These termination panels cannot be installed on a DIN rail. They must be installed on a
standard 19 inch (47.5 cm) rack (Electronics Industries Association Standard #RS-310-C):
• 9251-210F
• 9670-110F
• 9670-610F
• 9671-810F
• 9672-810F
• 9673-810F
• BP9228-010F
• BP9229-010F
• 9764-310F
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 25
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
26 Chapter 2 Field Termination Options and Installation
Front Side
ELCO connector
4 Attach one end of the interface cable to the ELCO connector on the termination panel.
• Ensure that the mating surfaces of the ELCO connectors on the cable and the
termination panel do not have any bent pins or other damage, and that both male
and female keys match.
• Position the connector on the cable so that it is aligned with the connector on the
termination panel.
• Mate the two connectors together until the threaded end of the thumbscrew is
making contact with the nut in the female connector. You may need to slightly rock
the connector on the cable while mating it to the connector on the termination
panel.
• As you apply pressure to the top of the connector on the cable, use your other hand
to turn the thumbscrew clockwise until the connectors are mated completely. The
minimum torque requirement is 8.85 lbf in (10.0 d-Nm).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 27
Turn the
thumbscrew
clockwise...
...until the
connectors are
fully mated.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
You must use gasket 2000098-100 on the male side of all ELCO connectors used in ATEX installations,
and replace it before the end of its five-year life span. Schneider Electric recommends that you use the
gasket in all hazardous locations requiring nonincendive circuits. (Order Schneider Electric part number
3000793-001 for a kit of 25 gaskets.)
Failure to follow these instructions can result in death, serious injury, environmental damage, or
equipment damage.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
28 Chapter 2 Field Termination Options and Installation
gasket
installed gasket
5 Attach the other end of the interface cable to the ELCO connector directly above the
corresponding I/O module on the Tricon chassis backplane in the same manner as you
connected the cable to the termination panel, as described in step 4.
6 Attach the wires from your field devices to the screw terminals on the termination panel.
See the Torque Specifications for Field Wiring Terminals section.
7 Perform a static check of the wiring.
8 If Tricon system power was removed in step 1, restore power to the Tricon system.
9 Apply field power to the termination panel.
10 Verify that all I/O points are connected to the appropriate field devices and are
operating correctly.
To inspect input points and force output points, see the Planning and Installation Guide for
Tricon 11.5 and Later 11.x Systems.
11 Load and test the control program using the TriStation 1131™ software.
If the program operates as intended, you are ready to enable the process equipment according
to the safety requirements for your environment.
If you need additional information on how to install external field termination panels, contact
the Global Customer Support (GCS) center.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 29
Tighten the screws on the field wiring and power terminals of the ETPs in the list below to this
torque:
12.0 lbf in (1.0 lbf ft) (1.36 Nm)
9670-110F
9670-610F
9671-610F
9671-810F
9672-810F
9673-810F
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
30 Chapter 2 Field Termination Options and Installation
Procedure
1 Remove field power from the termination panel.
2 Detach all I/O points connected to the appropriate field wiring.
3 Detach the wires from your field devices to the screw terminals on the termination
panel.
4 Detach the interface cable from the ELCO connector on the termination panel.
• As you pull the connector on the cable, use your other hand to turn the thumbscrew
counter-clockwise. You may need to rock the connector slightly while pulling.
• Ensure that the mating surfaces of the ELCO connectors on the cable and the
termination panel do not have any bent pins or other damage.
5 Detach the other end of the interface cable from the ELCO connector on the Tricon
chassis backplane in the same manner as you disconnected the cable from the
termination panel, as described in step 4.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH
Verify that power to the termination panel is off and that steps 1-4 have been followed. Dangerous
voltage may be present on the ELCO connector.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 31
Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
2 Remove incoming power from the Tricon system (optional).
3 Re-key the female connector on the fanned-out cable to match the male connector on the
Tricon chassis backplane. For instructions, see Appendix A, Re-Keying Connectors.
4 Attach the fanned-out cable connector to the panel connector that is above the
corresponding I/O module.
5 Connect the fanned-out cable wires to the field devices or marshaling termination.
6 Perform a static check of the wiring.
7 If Tricon system power was removed in step 1, restore power to the Tricon system.
8 Apply field power to the devices connected to the fanned out cable.
9 Verify the connection of all I/O points to the appropriate field wiring by using the
TriStation 1131 software to inspect input points and force output points.
To inspect input points and force output points, see the Planning and Installation Guide for
Tricon 11.5 and Later 11.x Systems.
10 Load and test the control program using the TriStation 1131 software.
If you need additional information on how to install fanned-out cables, contact the Global
Customer Support (GCS) center.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32 Chapter 2 Field Termination Options and Installation
Procedure
1 Remove field power from the termination panel.
2 Detach the fanned-out cable connector that is above the corresponding I/O module.
3 Detach the fanned-out wires from the field termination panel or the field devices.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH
Verify that power to the termination panel is off and that steps 1-3 have been followed. Dangerous
voltage may be present on the ELCO connector.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
3
Digital Input Termination Panels
Overview 34
16-Point Commoned Digital Input Term Panels 34
32-Point Commoned Digital Input Term Panels 45
16-Point Non-Commoned Digital Input Term Panels 56
Basic Digital Input Term Panels 58
Pulse Input and Pulse Totalizer Input Term Panels 71
Bypass Term Panels 77
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
34 Chapter 3 Digital Input Termination Panels
Overview
This chapter describes external field termination panels you can use with digital input modules.
Digital input termination panels are available in these configurations:
• 16-point commoned
• 32-point commoned
• Non-commoned
• Basic
• Bypass
F12
F14
F16
F2
F4
F6
F8
PWR
J1
F13
F15
F11
CR1
CR2
F1
F3
F5
F7
F9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 35
This figure represents a typical 16-point commoned digital input termination panel with
resistors.
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
PWR
J1
CR1
CR2
R13
R15
R11
R1
R3
R5
R7
R9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
Specifications
This table describes specifications for 9561–810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
36 Chapter 3 Digital Input Termination Panels
Compatible Modules
This table describes digital input modules compatible with 9561–810F.
Termination panel
SN REV A 7400165-
F10
F12
F14
F16
F2
F4
F6
F8
PWR
J1
F13
F15
F11
CR1
CR2
F1
F3
F5
F7
F9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+
F+
F–
F–
PS1
PS2
DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply
Figure 5 Field Wiring for 9561-810F with a 3501E or 3501T Module and a DC Power Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 37
This figure illustrates how to connect a 32-point digital input module and a 9561-810F with an
AC power supply to the field.
Termination panel
SN REV A 7400165-
Hot
AC
F10
F12
F14
F16
F2
F4
F6
F8
Power
Neutral
PWR
Supply
J1
F13
F15
F11
F1
F3
F5
F7
F9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+
F+
F–
F–
PS1
PS2
Typical point (1 of 16
points shown)
Field
Contact
Figure 6 Field Wiring for 9561-810F with a 3501E or 3501T Module and an AC Power Supply
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with a
commoned digital input panel (1 of 32 module points shown).
Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A
Threshold to
Detect Input
to
other Opto-Isolator Mux B
points
PS1
PS1
PS2 Threshold to
to Detect Input
spare
PS2 module Opto-Isolator Mux C
(AC Neutral)
PWR
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
38 Chapter 3 Digital Input Termination Panels
Specifications
This table describes specifications for 9562-810F.
Compatible Modules
This table describes digital input modules compatible with 9562-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 39
Termination panel
SN REV A 7400165-
F10
F12
F14
F16
F2
F4
F6
F8
PWR
J1
F13
F15
F11
CR1
CR2
F1
F3
F5
F7
F9
16/32
10/26
12/28
13/29
14/30
15/31
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+
F+
F–
F–
PS1
PS2
DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
40 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).
TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST
Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A
opto-
isolated
Test A
to
other
points Threshold to
(AC Hot)
Detect Input
PWR Opto-Isolator Mux B
PS1
PS1
PS2
Test B
PS2
(AC Neutral)
PWR
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 41
Specifications
This table describes specifications for 9563-810F.
Compatible Modules
This table describes digital input modules compatible with 9563-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
42 Chapter 3 Digital Input Termination Panels
Termination panel
SN REV A 7400165-
F10
F12
F14
F16
F2
F4
F6
F8
PWR
J1
F13
F15
F11
CR1
CR2
F1
F3
F5
F7
F9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+
F+
F–
F–
PS1
PS2
DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 43
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).
TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST
Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A
opto-
isolated
Test A
to
other
points Threshold to
(AC Hot)
Detect Input
PWR Opto-Isolator Mux B
PS1
PS1
PS2
Test B
PS2
(AC Neutral)
PWR
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
44 Chapter 3 Digital Input Termination Panels
Specifications
This table describes specifications for 9563-910F.
Compatible Modules
This table describes digital input modules compatible with 9563-910F.
Termination panel
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
PWR
J1
CR1
CR2
R13
R15
R11
R1
R3
R5
R7
R9
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 45
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).
TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
Test A
to Threshold to
other Detect Input
points Opto-Isolator Mux B
PS1
PS2
Test B
PS1
PS2
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
46 Chapter 3 Digital Input Termination Panels
This figure represents a typical 32-point commoned digital input term panel that has fuses and
blown-fuse indicators for field device protection.
SN REV A 7400150-
F10
F12
F14
F16
F18
F20
F22
F24
F26
F28
F30
F32
F2
F4
F6
F8
J1
CR1
CR2
F13
F15
F11
F1
F3
F5
F7
F9
F17
F19
F21
F23
F25
F27
F29
F31
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
This figure represents a typical 32-point commoned digital input term panel that has resistors
for field device protection.
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 47
Specifications
This table describes specifications for 9565-810F.
Compatible Modules
This table describes digital input modules compatible with 9565-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
48 Chapter 3 Digital Input Termination Panels
Termination panel
SN REV A 7400150-
F10
F12
F14
F16
F18
F20
F22
F24
F26
F28
F30
F32
F2
F4
F6
F8
J1
CR1
CR2
F13
F15
F11
F1
F3
F5
F7
F9
F17
F19
F21
F23
F25
F27
F29
F31
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 49
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 48 VDC high-density DC-coupled
digital input module (1 of 64 module points shown) with a 9565-810F.
LED *
Mux
1A, slow
to
spare 1
Amp ADC
64
Hi-Ref
Low-Ref
to Mux
other
points
10K 1
Amp ADC
PS1 64
PS2
Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
50 Chapter 3 Digital Input Termination Panels
Specifications
This table describes specifications for 9566-710F.
Compatible Modules
This table describes digital input modules compatible with 9566-710F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 51
Termination panel
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
52 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24 VDC digital input module with
a 9566-710F (1 of 64 module points shown).
to
spare
Test ON Relays
(opto-isolated)
180 Ohms
to other
points &
sensors
to
other
points
A
Threshold Detect
PS1 Opto-Isolator B
PS2
C
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 53
Specifications
This table describes specifications for 9566-810F.
Compatible Modules
This table describes digital input modules compatible with 9566-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
54 Chapter 3 Digital Input Termination Panels
Termination panel
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 55
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned high-density 24 VDC digital input
module with a 9566-810F (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
180 Ohms
64
Hi-Ref
Low-Ref
to Mux
other
points
2.7K 1
Amp ADC
PS1 64
PS2 Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
56 Chapter 3 Digital Input Termination Panels
SN REV A 7400168-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
CONTACT
9
PWR
Specifications
This table describes specifications for 9561-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Input Term Panels 57
Compatible Modules
This table describes digital input modules compatible with 9561-110F.
Termination panel
SN REV A 7400168-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
CONTACT
9
PWR
Hot
AC Typical point (1 of 16
Power points shown).
Supply Neutral
Field
Contact
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
58 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned digital input module with a
9561-110F (1 of 32 module points shown).
Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A
PWR1
CONTACT
CONTACT
PWR1
Threshold to
Detect Input
Opto-Isolator Mux B
Threshold to
to Detect Input
spare Opto-Isolator Mux C
module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 59
This figure represents a typical 16-point or 32-point basic digital input termination panel.
J1
DIDO PANEL
REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
TRICONEX
7400143-
C C
E E
Specifications
This table describes specifications for 9551-110F.
Compatible Modules
This table describes digital input modules compatible with 9551-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
60 Chapter 3 Digital Input Termination Panels
Termination panel
REV A 7400143- AC HOT/+DC
SN
A
E
C
32
1A, slow
30
28
26
24
Field
22
Contact
J1
20
18
2A (IN1 +)
16
14
12
10
8
2E (IN1 –)
6
4
2
A
E
C
AC NEUTRAL/RETURN
Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module without self-test and a
9551-110F (1 of 32 module points shown).
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
IN
IN
Threshold to
Detect Input
Opto-Isolator Mux B
Threshold to
to Detect Input
spare Opto-Isolator Mux C
module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 61
Specifications
This table describes specifications for 9552-610F.
Compatible Modules
This table describes digital input modules compatible with 9552-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
62 Chapter 3 Digital Input Termination Panels
Termination panel
REV A 7400143- AC HOT/+DC
SN
A
E
C
32
1A, slow
30
28
26
24
Field
22
Contact
J1
20
18
2A (IN1 +)
16
14
12
10
8
2E (IN1 –)
6
4
2
A
E
C
AC NEUTRAL/RETURN
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 63
Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with self-test and a
9552-610F (1 of 32 module points shown).
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
opto-
IN isolated
IN Test A
Threshold to
Detect Input
Opto-Isolator Mux B
Test B
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
Specifications
This table describes specifications for 9553-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
64 Chapter 3 Digital Input Termination Panels
Compatible Modules
This table describes digital input modules compatible with 9553-610F.
Termination panel
REV A 7400143- AC HOT/+DC
SN
A
E
C
32
1A, slow
30
28
26
24
Field
22
Contact
J1
20
18
2A (IN1 +)
16
14
12
10
8
2E (IN1 –)
6
4
2
A
E
C
AC NEUTRAL/RETURN
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 65
This figure illustrates how to connect a 64-point digital input module and a 9553-610F without
commoned return to the field.
Termination panel
+DC
7400144-
REV A
32
30
28
26
24
4C, 8C or 12C
22
(PWR)
** 1A, slow
J1
20
18
16
14
12
10
8
6 4E (IN4)
4
2
SN
2A (IN1)
A
E
C
14C to 32C
(RTN)
*
RTN
* One RTN connection is required. More than one is okay.
** One PWR connection is required. More than one is okay.
Figure 31 Field Wiring for 9553-610F with a 3564 Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
66 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with self-test and a
9553-610F (1 of 32 module points shown).
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
opto-
IN isolated
IN Test A
Threshold to
Detect Input
Opto-Isolator Mux B
Test B
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
This is a simplified schematic of a typical 64-point commoned digital input module and a
9553-610F (1 of 32 module points shown).
to
spare
Test ON Relays
(opto-isolated)
PWR + to other
points &
sensors
IN +
Threshold Detect
Opto-Isolator B
C
RTN
Test OFF Relays
(opto-isolated)
to to
other other
points points
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 67
Specifications
This table describes specifications for 9750-310F.
Compatible Modules
This table describes digital input modules compatible with 9750-310F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
68 Chapter 3 Digital Input Termination Panels
32
30
28
26
24
Typical 2 of 32
1A, slow
22
points shown
J1
20
18
16
14 1A, slow Field
12
Contacts
10
8
6 4E (IN4)
4
2
SN
2A (IN1)
A
**
14C to 32C (RTN)
*
RTN
**A ballast resistor may be required to satisfy whetting current of relay contacts.
Figure 34 Field Wiring for 9750-310F with a 3504E DI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 69
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24/48 VDC high-density DC-
coupled digital input module with a 9750-310F (1 of 32 module points shown).
Mux
to
spare 1
* Amp ADC
IN + 64
RTN
Hi-Ref
Low-Ref
to
other
points Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
* For noise immunity, install a 1W, 2.7 kilohms ballast resistor because relay contact applications resistors should be sized to satisfy
the required whetting current.
Specifications
This table describes specifications for 9750-410F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
70 Chapter 3 Digital Input Termination Panels
Compatible Modules
This table describes digital input modules compatible with 9750-410F.
Termination panel
48 VDC
7400144-
REV A
32
30
28
26
24
Typical 2 of 32
1A, slow
22
points shown
J1
20
18
16
14 1A, slow Field
12
Contacts
10
8
6 4E (IN4)
4
2
SN
2A (IN1)
A
**
14C to 32C (RTN)
*
RTN
One RTN connection is required. More than one is okay.
* A ballast resistor may be required to satisfy whetting current of relay contacts.
**
Figure 36 Field Wiring for 9750-410F with a 3504E DI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 71
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24/48 VDC high-density DC-
coupled digital input module with a 9750-410F (1 of 32 module points shown).
Mux
to
spare 1
* Amp ADC
IN + 64
RTN
Hi-Ref
Low-Ref
to
other
points Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
* For noise immunity, install a 1W, 2.7 kilohms ballast resistor because relay contact applications resistors should be sized to satisfy
the required whetting current.
J1
DIDO PANEL
REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
TRICONEX
7400143-
C C
E E
Figure 38 Typical 8-Point Pulse Input or 16-Point Pulse Totalizer Input Term Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
72 Chapter 3 Digital Input Termination Panels
Specifications
This table describes specifications for 9753-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 73
Compatible Modules
This table describes pulse input and pulse totalizer input modules compatible with 9753-110F.
Termination panel
REV A 7400143-
SN
A
E
C
32
30
Typical passive
speed sensor
28
26
24
22
J1
20
18
16
14
12
10
8
6 2E (IN1 –)
4
2 F–
Typical 1 of 8
points shown
A
E
C
DIDO PANEL TM
TRICONEX F+
2A (IN1 +) **
*
* Functional earth ground (quiet ground) is recommended for shield connections.
For shield grounding instructions, see Appendix E.
** When possible, install a terminating resistor as shown. For further information, see Technical Application Note (TAN) #006.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
74 Chapter 3 Digital Input Termination Panels
This figure illustrates how to connect a 32-point pulse totalizer input module and a 9753-110F
to the field.
Termination panel
REV A 7400143-
+24 VDC
SN
E
C
32
30
28
26
24
22
*
J1
20
18
2A (IN1 +)
16
14
Active
12 Pulse
10 Sensor
8
6 2E (IN1 –)
4
2
A
E
C
TM
DIDO PANEL TRICONEX
RTN
* Quiet Earth
Figure 40 Field Wiring for 9753-110F with a 3515 Pulse Totalizer Input Module
With the 3515 pulse totalizer input module, sensor pulse outputs should be the push-pull type.
You may use high-side or low-side, solid-state output, but maximum frequency may be reduced
based on cable distance. Do not use mechanical relay/switch contacts. To prevent point-to-
point cross-talk, use individually shielded, twisted-pair wire for lengths greater than 50 feet (15
meters).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 75
Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
9753-110F (1 of 8 module points shown).
to
spare Comparator
AC coupled A
Counter/ Micro-
Timer Processor
to
other
points
IN1
IN1
Comparator
AC coupled B
Counter/ Micro-
Timer Processor
to
other
points
Comparator
AC coupled
C
Counter/ Micro-
Timer Processor
to
other
points
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
76 Chapter 3 Digital Input Termination Panels
This is a simplified schematic of a typical 32-point non-commoned pulse totalizer input module
with a 9753-110F (1 of 32 module points shown).
Leg-to-
Leg
Isolation To
Threshold Counters
Detect
Opto-Isolator Leg A
IN
IN To
Threshold Counters
Detect
Opto-Isolator Leg B
To
Threshold Counters
to Detect
spare Opto-Isolator Leg C
module
Figure 42 Simplified Schematic of a 3515 Pulse Totalizer Input Module with a 9753-110F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 77
FRONT
2 AMP
250V
BLOWN
FUSE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
ON
OFF
TRICONEX
REAR
TB2
P2 1 2 3 4 5 6 P1
TB4 TB5
+24 RTN GND +24 RTN GND
TB3
1 2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
78 Chapter 3 Digital Input Termination Panels
This figure represents a typical 32-point bypass termination panel that is compatible with
64-point digital input modules.
FRONT
2 AMP
250V
BLOWN
FUSE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
ON
OFF
TRICONEX
REAR
TB2
1 2 3 4 5 6
P1 TB4 TB5
+24 RTN GND +24 RTN GND
TB3
1 2
For more description of bypass termination panels, see Bypass Panel for Digital Inputs on
page 5.
Specifications
This table describes specifications for BP9228-010F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 79
Compatible Modules
This table describes digital input modules compatible with BP9228-010F.
REAR
TB2
P2 1 2 3 4 5 6 P1
TB4 TB5
+24 RTN GND +24 RTN GND
TB3
1 2
Protective earth
(AC safety ground)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
80 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with a BP9228-010F (1
of 32 module points shown).
BYPASS PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST
+24V LED
Test
B
3
Threshold to
to Input
Detect
AC safety spare
ground module Opto-Isolator Mux C
Test
C
Specifications
This table describes specifications for BP9229-010F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 81
Compatible Modules
This table describes digital input modules compatible with BP9229-010F.
REAR
TB2
1 2 3 4 5 6
P1 TB4 TB5
TB3
1 2
Protective earth
(AC safety ground)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
82 Chapter 3 Digital Input Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 64-point digital input module with a BP9229-010F (1
of 32 module points shown).
+24V LED3
1 Mux
1
4 Amp ADC
Keyswitch
64
Hi-Ref
LED4 Low-Ref
to
other Mux
Bypass points
switch
1
RTN
Amp ADC
2
64
5
Hi-Ref
Low-Ref
Mux
3 1
Amp ADC
6
64
to
AC safety spare
ground module Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
4
Digital Output Termination Panels
Overview 84
8-Point Commoned Digital Output Term Panels 84
16-Point Commoned Digital Output Term Panels 99
16-Point Non-Commoned Digital Output Term Panels 122
Basic Digital Output Term Panels 137
Commoned Interposing Relay Term Panels 151
Non-Commoned Interposing Relay Term Panels 167
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
84 Chapter 4 Digital Output Termination Panels
Overview
This chapter describes external field termination panels you can use with digital output
modules. Digital output termination panels are available in these configurations:
• 8-point commoned
• 16-point commoned
• Non-commoned
• Basic
• Commoned interposing relay
• Non-commoned interposing relay
SN REV A 7300167-
L+
L–
L–
PS1
PS2
CR8
CR6
CR3
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 85
This figure represents a typical 8-point commoned DC digital output termination panel with
fuses and blown-fuse indicators.
SN REV A 7300167-
J1
CR9
L+
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
This table identifies primary and secondary fuse locations for each output point on an 8-point
commoned digital output term panel.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
86 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9661-510F.
Compatible Modules
This table describes digital output modules compatible with 9661-510F.
Termination panel
SN REV A 7300167-
L+
L–
L–
Load*
PS1
PS2
CR8
CR6
CR3
PS1
Hot
AC
Power
Neutral
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 87
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised AC digital output
module with a commoned digital output panel (1 of 8 points shown).
to
Voltage Voltage hot
spare
LED *
Loopback Sensor
A 2.5A, fast
Output PS1 +
Switch
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
Drive
Circuitry Voltage/ Voltage/
Current Current
B
Sensor Sensor
L–
Output
Switch PS1 –
Drive
to other
Circuitry C A C points
C
Output
Switch
Drive
Circuitry Voltage Voltage
Loopback Sensor
Specifications
This table describes specifications for 9661-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
88 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9661-810F.
Termination panel
SN REV A 7300167-
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
Figure 53 Field Wiring for 9661-810F with a 3613E Module and No Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 89
This figure illustrates how to connect an 8-point supervised DC digital output module and a
9661-810F to the field with shorted load detection.
Termination panel
SN REV A 7300167-
J1
CR9
1
2
3
4
5
6
7
8
L+
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
PS3
+5 VDC
Power
Supply
Figure 54 Field Wiring for 9661-810F with a 3613E Module and Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
90 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).
to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +
C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare
Specifications
This table describes specifications for 9662-710F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 91
Compatible Modules
This table describes digital output modules compatible with 9662-710F.
Termination panel
SN REV A 7300167-
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
Figure 56 Field Wiring for 9662-710F with a 3615E Module and No Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
92 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-710F to the field with shorted load detection.
Termination panel
SN REV A 7300167-
J1
CR9
8
2
3
4
5
6
7
L+
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
PS3
+5 VDC
Power
Supply
Figure 57 Field Wiring for 9662-710F with a 3615E Module and Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 93
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).
to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +
C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare
Specifications
This table describes specifications for 9662-910F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
94 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9662-910F.
Termination panel
SN REV A 7300167-
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
Figure 59 Field Wiring for 9662-910F with a 3614E Module and No Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 95
This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-910F to the field with shorted load detection.
Termination panel
SN REV A 7300167-
J1
CR9
1
2
3
4
5
6
7
8
L+
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
PS3
+5 VDC
Power
Supply
Figure 60 Field Wiring for 9662-910F with a 3614E Module and Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
96 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).
to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +
C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare
Specifications
This table describes specifications for 9667-910F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 97
Compatible Modules
This table describes digital output modules compatible with 9667-910F.
Termination panel
SN REV A 7300167-
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
Figure 62 Field Wiring for 9667-910F with a 3617E Module and No Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
98 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect an 8-point supervised DC digital output module and a
9667-910F to the field with shorted load detection.
Termination panel
SN REV A 7300167-
J1
CR9
8
2
3
4
5
6
7
L+
L+
Load*
L–
L–
PS1
PS2
SPWR
CR8
CR6
CR3
PS1
DC
Power
Supply
PS2
DC
Power
Supply
PS3
+5 VDC
Power
Supply
Figure 63 Field Wiring for 9667-910F with a 3617E Module and Shorted Load Detection
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 99
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).
to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +
C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
100 Chapter 4 Digital Output Termination Panels
This figure represents a typical 16-point commoned DC digital output termination panel with
fuses and blown-fuse indicators.
SN REV A 7400166-
CR
1
J1
CR
2
12
13
14
15
16
11
9
1
2
3
4
5
6
7
8
L+
L+
L–
L–
PS1
PS2
This figure represents a typical 16-point commoned digital output panel without fuses.
SN REV A 7400166-
CR
1
J1
CR
2
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+
L+
L–
L–
PS1
PS2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 101
This figure represents a typical 16-point commoned AC digital output termination panel with
fuses and blown-fuse indicators for the 3601E module.
SN REV A 7400166-
J1
F1 F3 F5 F7 F9 F11 F13 F15
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+
L+
L–
L–
PS1
PS2
Figure 67 Typical 16-Point Commoned AC DO Term Panel with Fuses for 3601E
This figure represents a typical 16-point commoned AC digital output termination panel with
fuses and blown-fuse indicators for the 3601T module.
SN REV A 7400233-
C
A
B
D
H
K
F
J
E
M
N
P
L
R
V
U
S
T
W
Z
X
Y
a
d
b
c
e
f
J1
j
m
CR3
n
k
s
r
t
p
w
v
x
u
y
CC
z
AA
BB
DD
JJ
HH
EE
FF
MM
NN
KK
LL
L+
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L-
L-
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1
PS2
Figure 68 Typical 16-Point Commoned AC DO Term Panel with Fuses for 3601E or 3601T
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
102 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9661-610F.
Compatible Modules
This table describes digital output modules compatible with 9661-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 103
Termination panel
SN REV A 7400166-
J1
F1 F3 F5 F7 F9 F11 F13 F15
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+
L+
L–
L–
PS1
PS2
PS1
AC Hot
Power
Supply Neutral Typical point (1 of 16
points shown)
Load
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned AC digital output module
with a commoned digital output panel (1 of 16 points shown).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
104 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9661-910F.
Compatible Modules
This table describes digital output modules compatible with 9661-910F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 105
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
106 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect the 16-point supervised DC digital output module 3623
and a 9661-910F to the field (8 of 16 points shown).
Termination panel
SN REV A 7400166-
CR1
J1
CR2
16
1
L+
L+
Load*
L–
L–
PS1
PS2
PS1
DC
Power
Supply
PS2
DC
Power
Supply
* A load must be installed at every point to prevent a missing-load alarm. If a field load is not available,
install a 2.2 kilohms, 10 W load resistor
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 107
Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with a
commoned digital output panel (1 of 16 points shown).
* LEDs will not turn on if fuses are removed because the 3603E module is commoned and does not require fusing.
A Voltage
B Loopback to other
C Detector points LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
108 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9662-610F.
a. When the 9662-610F panel is used with the Model 3625/A DO Module, the maximum total current is
10 amps per termination panel to limit the power dissipation of the module
Compatible Modules
This table describes digital output modules compatible with 9662-610F.
a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 109
Termination panel
SN REV A 7400166-
CR1
J1
CR2
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+
L+
Load*
L–
L–
PS1
PS2
PS1
DC
Power
Supply
PS2
DC
Power
Supply
* When using a Model 3624 module, a load must be installed at every point to prevent missing - load alarm. If a field
load is not available, install a 470 ohms, 10 W load resistor.
Figure 75 Field Wiring for 9662-610F with a 3624, 3625, or 3625A Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
110 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect a 32-point DC dual digital output module with self
protection and a 9662-610F to the field (1 of 32 points shown).
Termination panel
SN REV A 7400166-
CR1
J1
CR2
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+
L+
L–
L–
PS1
PS2
PS1
DC Typical point (1 of 16
Power points shown)
Supply
Load
PS2
DC
Power
Supply
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 111
Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with
self protection and a commoned digital output panel (1 of 16 points shown).
OVD Switch #1
A Voltage
B Loopback to other
C Detector points
A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
This is a simplified schematic of a typical 32-point commoned DC digital output module with
self protection and a commoned digital output panel (1 of 32 points shown).
PS2 +
A or C *to other to other
A B points points
Output L+
Switch
Drive
Circuitry
L–
B
Output PS1 –
Switch to other
Drive points
Circuitry
PS2 –
C A or C
C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector
* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by termination panels.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
112 Chapter 4 Digital Output Termination Panels
This is a simplified schematic of a typical 32-point commoned dual DC digital output module
with self protection and a commoned digital output panel (1 of 16 points shown).
A Voted PS1 +
Output
B PS2 +
Drive
C Circuitry to other
points
L+
A Voted
Drive
B L–
Output
C Circuitry
PS1 –
to other
points PS2 –
A Loopback
B Detector/
C Isolator
to
hot
spare
to other points
Specifications
This table describes specifications for 9662-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 113
Compatible Modules
This table describes digital output modules compatible with 9662-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
114 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned DC digital output module
with a commoned digital output panel (1 of 16 points shown).
Specifications
This table describes specifications for 9663-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 115
Compatible Modules
This table describes digital output modules compatible with 9663-610F.
Termination panel
SN REV A 7400233-
C
A
B
D
H
K
F
J
E
M
N
P
L
R
V
U
S
T
W
Z
X
Y
a
d
b
c
e
f
J1
j
m
CR3
n
k
s
r
t
p
w
v
x
u
y
CC
z
AA
BB
DD
JJ
HH
EE
FF
MM
NN
KK
LL
L+
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L-
L-
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1
PS2
PS1
AC Hot
Power
Supply Neutral
Typical point
(1 of 16 points shown)
Load
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
116 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned AC digital output module
with a commoned digital output panel (1 of 16 points shown).
Specifications
This table describes specifications for 9664-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 117
Compatible Modules
This table describes digital output modules compatible with 9664-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
118 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect the 16-point supervised DC digital output module 3623T
and a 9664-810F to the field (8 of 16 points shown).
Termination panel
SN REV A 7400166-
CR1
J1
CR2
16
1
L+
L+
Load*
L–
L–
PS1
PS2
PS1
DC
Power
Supply
PS2
DC
Power
Supply
* A load must be installed at every point to prevent a missing-load alarm. If a field load is not available,
install a 2.2 kilohms, 10 W load resistor
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 119
Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with a
commoned digital output panel (1 of 16 points shown).
* LEDs will not turn on if fuses are removed because the 3603E and 3603T modules are commoned and do not require fusing.
A Voltage
B Loopback to other
C Detector points LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
120 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9667-810F.
Compatible Modules
This table describes digital output modules compatible with 9667-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 121
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
122 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned DC digital output module
with a commoned digital output panel (1 of 16 points shown).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 123
This figure represents a typical 16-point non-commoned digital output termination panel for
the 3603B module.
+ – + 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 –
POWER
LOAD
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
LOAD
POWER
+ – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
This figure represents a typical 16-point non-commoned digital output termination panel for
modules 3601E, 3604E, and 3607E.
SN REV A 7400169-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
10 F9
12
13
14
15
16
11
1
9
LOAD
PWR
Figure 91 Typical 16-Point Non-Commoned DO Term Panel for Modules 3601E, 3604E, and 3607E
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
124 Chapter 4 Digital Output Termination Panels
This figure represents a typical 16-point non-commoned digital output termination panel for
module 3601T.
SN REV A 7400234-
F10
F12
F16
F14
F2
F6
F8
F4
A
B
C
D
H
F
K
E
M
N
L
P
R
V
S
T
U
W
Z
X
Y
a
d
b
c
f
e
j
h
l
m
CR5
n
r
s
t
p
v
w
x
u
y
CC
z
AA
BB
DD
JJ
EE
FF
HH
KK
LL
MM
NN
F1 F3 F5 F7 F9 F11 F13 F15
J1
LOAD
10
12
13
14
15
16
LOAD
11
1
10
12
13
14
15
16
11
PWR
PWR
Figure 92 Typical 16-Point Non-Commoned DO Term Panel for Module 3601T
This figure represents a typical 16-point non-commoned relay output termination panel.
SN REV A 7400172-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
10 F9
12
13
14
15
16
11
1
9
LOAD
PWR
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 125
Specifications
This table describes specifications for 9251–210.
Compatible Modules
This table describes digital output modules compatible with 9251–210.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
126 Chapter 4 Digital Output Termination Panels
DC +
Power
–
Supply
Protective earth
(AC safety ground)
+ – + 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 –
POWER
LOAD
Typical point
1 2 3 4 5 6 7 8
(1 of 16 points shown)
9 10 11 12 13 14 15 16
Load
LOAD
POWER
+ – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
Each terminal accepts either #6 ring-lug terminals or 24-gauge to 12-gauge (0.3 mm2 to 2.1 mm2)
wires.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 127
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).
A
LED
*
Output PWR1 +
Switch
Drive
Circuitry A B
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry
B
Output
Switch
Drive LOAD 1 –
Circuitry A B
C PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
128 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9661-110F.
Compatible Modules
This table describes digital output modules compatible with 9661-110F.
Termination panel
SN REV A 7400169-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
1
9
LOAD
PWR
Typical point
+ (1 of 16 points shown)
Power
Supply –
Load
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 129
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).
LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry
B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Specifications
This table describes specifications for 9662-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
130 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9662-110F.
Termination panel
SN REV A 7400169-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
1
9
LOAD
PWR
Typical point
+ (1 of 16 points shown)
Power
Supply –
Load
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 131
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).
LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry
B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Specifications
This table describes specifications for 9664-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
132 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9664-110F.
Termination panel
SN REV A 7400234-
F10
F12
F16
F14
F2
F6
F8
F4
A
B
C
D
H
F
K
E
M
N
L
P
R
V
S
T
U
W
Z
X
Y
a
d
b
c
f
e
j
h
l
m
CR5
n
r
s
t
p
v
w
x
u
y
CC
z
AA
BB
DD
JJ
EE
FF
HH
KK
LL
MM
NN
10
12
13
14
15
16
11
1
9
LOAD
LOAD
10
12
13
14
15
16
11
1
9
PWR
PWR
+
Power Typical point
Supply – (1 of 16 points shown)
Load
Figure 100 Field Wiring for 9664-110F with a 3601E or 3601T Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 133
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).
LED *
A
Output PWR1 +
Switch
Drive
Circuitry
A B
200V
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry
B
200V
Output
Switch
Drive LOAD 1 ñ
Circuitry
C A B PWR1 ñ
C
Output
to
Switch hot
Drive spare
A Voltage
Circuitry
B Loopback
C Detector
Specifications
This table describes specifications for 9667-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
134 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9667-110F.
Termination panel
SN REV A 7400169-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
1
9
LOAD
PWR
Typical point
+ (1 of 16 points shown)
Power
Supply –
Load
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 135
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).
LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry
B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Specifications
This table describes specifications for 9668-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
136 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes relay output modules compatible with 9668-110F.
Termination panel
SN REV A 7400172-
F13
F14
F15
F16
F5
F6
F7
F8
J1
F10
F12
F11
F1
F2
F3
F4
F9
10
12
13
14
15
16
11
1
9
LOAD
PWR
Typical point
+ (1 of 16 points shown)
Power
Supply –
Load
Figure 104 Field Wiring for 9668-110F with a 3636R or 3636T Relay Output Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 137
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned relay output module with a
non-commoned relay output panel (1 of 32 points shown).
Point
Register
PWR1 +
+V +V
Voted
Output
Drive
Point Circuitry
Register
LOAD 1 +
Loopback
Detector/
Isolator
LOAD 1 –
Point
Register
PWR1 –
to
spare
module
Figure 105 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Non-Commoned
Relay Output Panel
J1
DIDO PANEL
REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
7400143-
C C
TRICONEX
E E
Figure 106 Typical 16-Point Basic DO and Relay Output Term Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
138 Chapter 4 Digital Output Termination Panels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 139
Specifications
This table describes specifications for 9651-110F.
Compatible Modules
This table describes digital output modules and relay output modules compatible with
9651-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
140 Chapter 4 Digital Output Termination Panels
Termination Panel
REV A 7400143-
AC HOT/+DC
SN
Recommended
A
E
C Wiring Connections
32
30 2.5 A, fast acting
28
26
24
22
Solenoid,
J1
20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4
***
2
A
TM
DIDO PANEL TRICONEX
Figure 107 Field Wiring for 9651-110F with a 3601E, 3603E, or 3623 DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 141
This figure illustrates how to connect a 32-point relay output module and a 9651-110F to the
field (1 of 32 points shown).
+DC
Termination panel
REV A 7400143-
SN 2.5A, slow
E
C
32
Solenoid,
30 2A (C1) 2E (C1) relay, etc.
28
26
24
22
J1
20
18
16
14
12
10
8
6
4
2
A
TM
DIDO PANEL TRICONEX
RETURN
* 37.5
When switching reactive loads, de-rate the output switching power to 25% of maximum (500 VA for AC applications,
W for DC applications). When switching incandescent lamps, use the inrush current when calculating the
required output switching power. For specifications, contact the lamp manufacturer. The inrush current may be
10-15 times the rated nominal load current of the lamp.
Figure 108 Field Wiring for 9651-110F with a 3636R or 3636T Relay Output Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
142 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
This is a simplified schematic of a typical 16-point commoned digital output module with a
basic digital output panel (1 of 16 points shown).
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
to other
B points
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 143
This is a simplified schematic of a typical 16-point commoned supervised digital output module
with a basic digital output panel (1 of 16 points shown).
A Voltage
B Loopback to other
C Detector points
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output OVD Switch #2
Switch
Drive RTN1 (2E)
Circuitry
B
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
This is a simplified schematic of a typical 32-point relay output module with a basic digital
output panel (1 of 32 points shown).
to
spare
module
Point
Register
+V +V
2A (C1)
Voted
Output
Drive
Point Circuitry
Register
Loopback
Detector/
Isolator 2E (C1)
Point
Register
Figure 112 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Basic DO Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
144 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9652-610F.
Compatible Modules
This table describes digital output modules compatible with 9652-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 145
Termination Panel
REV A 7400143-
AC HOT/+DC
SN
Recommended
E
Wiring Connections
C
32
30 2.5 A, fast acting
28
26
24
22
Solenoid,
J1
20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4
***
2
A
TM
DIDO PANEL TRICONEX
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
146 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Specifications
This table describes specifications for 9653-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 147
Compatible Modules
This table describes digital output modules compatible with 9653-610F.
a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.
Termination Panel
REV A 7400143-
+DC
SN
Recommended
A
Wiring Connections
C
32
30
28
26
24
22
Solenoid,
J1
20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4
***
2
A
TM
DIDO PANEL TRICONEX
* One
One PWR connection per point is recommended.
****
* To prevent
RTN connection per point is recommended.
missing-load alarm, install a load at each unused point.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
148 Chapter 4 Digital Output Termination Panels
This figure illustrates how to connect a 16-point or 32-point digital output module with self-
protection and a 9653-610F to the field (1 of 16 points shown).
Termination Panel
REV A 7400143-
+DC
SN
Recommended
E
Wiring Connections
C
32
30
28
26
24
22
Solenoid,
J1
20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4
***
2
A
TM
DIDO PANEL TRICONEX
Figure 116 Field Wiring for 9653-610F with a 3624, 3625, or 3625A DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 149
This figure illustrates how to connect a 32-point dual digital output module with self-protection
and a 9653-610F to the field (1 of 32 points shown).
For proper operation, one PWR connection per point is required.
Termination panel
REV A 7400143-
+DC
SN
E
C
32
30
28
26
24
22
Solenoid,
J1
20
18 relay, etc.
16 2C (LOAD1)
14
12
10
8
6
4 2E (RTN1)
2
A
TM
DIDO PANEL TRICONEX
2A (PWR1)
RETURN
*
* One RTN connection is required. More than one is recommended.
Figure 117 Field Wiring for 9653-610F with a 3664 or 3674 DO Module
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
150 Chapter 4 Digital Output Termination Panels
This is a simplified schematic of a typical 16-point commoned supervised digital output module
with a basic digital output panel (1 of 16 points shown).
A Voltage
B Loopback to other
C Detector points
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output OVD Switch #2
Switch
Drive RTN1 (2E)
Circuitry
B
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
This is a simplified schematic of a typical 32-point commoned supervised digital output module
with a basic digital output panel (1 of 32 points shown).
A or C *to other
A B points
Output LOAD1 (2C)
Switch
Drive
Circuitry
RTN1 (2E)
B
Output
Switch
Drive
Circuitry
C A or C
C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector
* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by termination panels.
Figure 120 Simplified Schematic of a 3625 or 3625A DO Module with a Basic DO Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 151
This is a simplified schematic of a typical 32-point commoned dual digital output module with
a basic digital output panel (1 of 32 points shown).
RTN1 (2E)
A Voted
Drive
B
Output
C Circuitry
A Loopback
B Detector/
C Isolator
to
hot
spare
to other points
Figure 121 Simplified Schematic of a 3664 or 3674 DO Module with a Basic DO Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
152 Chapter 4 Digital Output Termination Panels
This figure represents a typical 16-point commoned interposing relay termination panel.
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CR1 CR2
R20
R19
R18
p R27
R28
R29
RELAY EXTERNAL TERMINATOR
© 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
For more description of interposing relay term panels, see Termination Panels with Interposing
Relays on page 4.
Specifications
This table describes specifications for 9670-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 153
When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.
Compatible Modules
This table describes digital output modules compatible with 9670-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
154 Chapter 4 Digital Output Termination Panels
AC Hot
AC
Power
AC Neutral
Supply
Protective earth
(AC safety ground)
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CR1 CR2
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
Typical point (1 of
Contact #1 16 points shown)
(NO)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 155
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a commoned interposing relay panel (1 of 16 points shown).
A
*
LED
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A "B
Output
Switch
Drive
Circuitry
B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points
to
spare
module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
156 Chapter 4 Digital Output Termination Panels
Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.
Specifications
This table describes specifications for 9671-810F.
When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.
Compatible Modules
This table describes digital output modules compatible with 9671-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 157
a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.
b. For the 3625 module, field power is commoned to all points, so that if power is present on one point,
it is present on all points. For the 3625A module, field power is commoned in groups of 16 points and
is separated by termination panels.
DC
Power
Supply
DC
Power
Supply
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CR1 CR2
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
Figure 125 Field Wiring for 9671-810F with a 3604E, 3625, 3625A, 3664, or 3674 DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
158 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).
LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry
B
Output
Switch
Drive
Circuitry C A B
POWER1 ñ
C
Output
PW1 +
Switch
Drive to
A Voltage
Circuitry spare PW1 ñ
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 ñ
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator commoned
points
to
spare
module
Figure 126 Simplified Schematic of a 3604E DO Module with a Commoned Interposing Relay Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 159
This is a simplified schematic of a typical 32-point commoned digital output module with a
commoned interposing relay panel (1 of 32 points shown).
A
Output
Switch
Drive
LED *
Circuitry
POWER1 +
CONTACT
A or C A B *to other (1C)
points
Output CONTACT
Switch (1NO)
Drive
Circuitry
B
Output
Switch
Drive
Circuitry
C A or C
C
Current
Output Loopback POWER1 –
Switch Detector
Drive Analog/
Circuitry Digital
Mux
PW1 +
A Voltage
B Loopback to
C Detector hot PW1 –
spare
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator commoned
points
to
spare
module
* LEDs will not turn on if fuses are removed because the 3625 and 3625A modules are self-protected and do
not require fusing.
Figure 127 Simplified Schematic of a 3625 or 3625A DO Module with a Commoned Interposing Relay
Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
160 Chapter 4 Digital Output Termination Panels
This is a simplified schematic of a typical 32-point non-commoned digital output module with
a commoned interposing relay panel (1 of 32 points shown).
32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL
LED
*
A Voted POWER1 +
B Output
CONTACT
Drive
C (1C)
Circuitry
CONTACT
(1NO)
A Voted
B Output
C Drive
Circuitry
POWER1 –
Loopback PW1 +
Detector/
Isolator to
hot PW1 –
spare
to other points
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points
to
spare
module
* LEDs will not turn on if fuses are removed because the 3664 and 3674 modules are self-protected and do
not require fusing.
Figure 128 Simplified Schematic of a 3664 or 3674 DO Module with a Commoned Interposing Relay
Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 161
Specifications
This table describes specifications for 9672-810F.
When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
162 Chapter 4 Digital Output Termination Panels
Compatible Modules
This table describes digital output modules compatible with 9672-810F.
DC
Power
Supply
DC
Power
Supply
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CR1 CR2
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 163
Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).
LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry
B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points
to
spare
module
Figure 130 Simplified Schematic of a 3607E DO Module with a Commoned Interposing Relay Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
164 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9673-810F.
When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 165
Compatible Modules
This table describes digital output modules compatible with 9673-810F.
DC
Power
Supply
DC
Power
Supply
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CR1 CR2
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
Figure 131 Field Wiring for 9673-810F with a 3603E or 3603T DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
166 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).
LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry
B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points
to
spare
module
* LEDs will not turn on in fuses are removed because the 3603E and 3603T modules are commoned and do not require fusing.
Figure 132 Simplified Schematic of a 3603E or 3603T DO Module with a Commoned Interposing Relay
Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Non-Commoned Interposing Relay Term Panels 167
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
For more description of interposing relay term panels, see Termination Panels with Interposing
Relays on page 4.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
168 Chapter 4 Digital Output Termination Panels
Specifications
This table describes specifications for 9670-110F.
When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.
Compatible Modules
This table describes digital output modules compatible with 9670-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Non-Commoned Interposing Relay Term Panels 169
Hot
AC
Power
Neutral
Supply
Protective earth
Typical point (1 of (AC safety ground)
16 points shown)
+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –
POWER POWER
CONTACT CONTACT
C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO
Typical point (1 of
16 points shown)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
170 Chapter 4 Digital Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point AC digital output module with a non-
commoned interposing relay panel (1 of 16 points shown).
32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL
A
LED
*
Output POWER1 +
Switch
CONTACT
Drive
(1C)
Circuitry A B
CONTACT
(1NO)
A "B
Output
Switch
Drive
Circuitry
B
Output
Switch
Drive
Circuitry
C A B
C POWER1 –
Output
Switch
Drive PW1 +
A Voltage
Circuitry
B Loopback to
hot PW1 –
C Detector spare
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)
PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing
Threshold Detect
Opto-Isolator
to
spare
module
Figure 135 Simplified Schematic of a 3601E DO Module with a Non-Commoned Interposing Relay
Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
5
Analog Input and Analog Output
Termination Panels
Overview 172
16-Point Current Input Term Panels 172
32-Point Current Input Term Panels 192
Thermocouple Input Term Panels 202
Voltage Input Term Panels 211
RTD/TC/AI Input Term Panels 223
Analog Output Term Panels 234
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
172 Chapter 5 Analog Input and Analog Output Termination Panels
Overview
This chapter describes external field termination panels you can use with analog input modules
and analog output modules.
Analog input termination panels are available in these configurations:
• Current input
— 16-point
— 16-point, user-configurable
— 32-point
— 32-point, 3-wire
— 32-point, basic
• Thermocouple input
— 16-point
— 32-point
• Voltage input
— 16-point
— 16-point, basic
— 32-point, basic
• Panels for use with signal conditioners, which interface with resistive thermal devices,
thermocouples, and 4-20 mA transmitters (RTD/TC/AI)
Analog output termination panels are available in 8-point current output and 4-point bipolar
output configurations.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 173
R10
R12
R14
R16
R2
R4
R6
R8
J1
R13
R15
R11
R1
R3
R5
R7
R9
CR1
CR2
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
This figure represents a typical 16-point, current input, user-configurable, termination panel.
SN REV A 7400195-
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W12
W13
W14
W15
W16
W11
W17
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
CR3
T+
T+
CR2
CR4
PS1 PS2
T-
T-
A
A
CR1
CR5
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
174 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9761-210F.
Compatible Modules
This table describes analog input modules compatible with 9761-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 175
NOTICE
HAZARD OF EXCESSIVE HEATING
• Install a 0.5 amp, slow blow, external fuse on PS1+ and PS2+ of each ETP.
Installing an external fuse can help mitigate potential damage if multiple points are shorted simulta-
neously, for example, during a catastrophic failure of a junction box. Note that the ETP can indefi-
nitely tolerate a F+ short to GND on any single point, at 24 V.
• Check the accuracy of an analog input point after it has been damaged by an F– short to 24 V.
Failure to follow these instructions can result in equipment damage.
Termination panel
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
J1
R13
R15
R11
R1
R3
R5
R7
R9
CR1
CR2
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
Shield Ground
Figure 138 Field Wiring for 9761-210F with a 3700, 3700A, or 3721 AI Module or a 2770H HART AI
Interface Module
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
176 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
180 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 139 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9761-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 177
This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).
HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE
1 Amp ADC
180 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
TERMINATION PANEL FIELD
Low-Ref
CABLE
Figure 140 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 AI Module
and a 9761-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
178 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9761-410F.
Compatible Modules
This table describes analog input modules compatible with 9761-410F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 179
Termination panel
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
J1
R13
R15
R11
R1
R3
R5
R7
R9
CR1
CR2
16/32
10/26
12/28
13/29
14/30
15/31
11/27
8/24
9/25
1/17
2/18
3/19
4/20
5/21
6/22
7/23
+
+
–
–
PS1
PS2
Shield Ground
Figure 141 Field Wiring for 9761-410F with a 3701 or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
180 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
180 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
500 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 142 Simplified Schematic of a 3701 or 3721 AI Module with a 9761-410F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 181
Specifications
This table describes specifications for 9762-210F.
Compatible Modules
This table describes analog input modules compatible with 9762-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
182 Chapter 5 Analog Input and Analog Output Termination Panels
Termination panel
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
J1
R13
R15
R11
R1
R3
R5
R7
R9
CR1
CR2
16/32
10/26
12/28
13/29
14/30
15/31
11/27
8/24
9/25
1/17
2/18
3/19
4/20
5/21
6/22
7/23
+
+
–
–
PS1
PS2
Shield Ground
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 183
Simplified Schematics
This is a simplified schematic of a typical 16 -point non-commoned analog input module with a
current input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
180 Ohms 16
Hi-Ref
Low-Ref
Mux
to
other
points
250 Ohms 1 Amp ADC
PS1
16
PS2
Hi-Ref
PS1 Low-Ref
PS2
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Specifications
This table describes specifications for 9762-410F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
184 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9762-410F.
Termination panel
SN REV A 7400165-
R10
R12
R14
R16
R2
R4
R6
R8
J1
R13
R15
R11
R1
R3
R5
R7
R9
CR1
CR2
10/26
12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+
+
–
–
PS1
PS2
Shield Ground
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 185
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
180 Ohms 16
Hi-Ref
Low-Ref
Mux
to
other
points
500 Ohms 1 Amp ADC
PS1
16
PS2
Hi-Ref
PS1 Low-Ref
PS2
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
186 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9771-210F.
Compatible Modules
This table describes analog input modules compatible with 9771-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 187
NOTICE
HAZARD OF EXCESSIVE HEATING
• Install a 0.5 amp, slow blow, external fuse on PS1+ and PS2+ of each ETP.
Installing an external fuse can help mitigate potential damage if multiple points are shorted simulta-
neously, for example, during a catastrophic failure of a junction box. Note that the ETP can indefi-
nitely tolerate a F+ short to GND on any single point, at 24 V.
• Check the accuracy of an analog input point after it has been damaged by an F– short to 24 V.
Failure to follow these instructions can result in equipment damage.
SN REV A 7400195-
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W12
W13
W14
W15
W16
W11
W17
R28
R30
R32
R10
R12
R14
R16
R18
R20
R22
R24
R26
R2
R4
R6
R8
J1
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
CR3
T+
T+
CR2
CR4
PS1 PS2
T-
T-
A
A
CR1
CR5
DC
Power
Supply
Shield Ground
Figure 147 Field Wiring for 9771-210F with a 3700, 3700A, 3703E, or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
188 Chapter 5 Analog Input and Analog Output Termination Panels
This figure illustrates how to connect a 16-point or 32-point analog input module or a HART
analog input interface module and a 9771-210F to the field and another system, such as a DCS
(1 of 16 or 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.
SN REV A 7400195-
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
W12
W13
W14
W15
W16
W11
This jumper must be
W17
removed in sharing
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
applications.
J1
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
CR3
T+
T+
CR2
CR4
PS1 PS2
T-
T-
A
A
CR1
CR5
DCS
*
PS1 Typical point (1 of 16 points shown)
DC
Power
Supply +
Field Xmtr
PS2 – (4-20 mA)
DC
Power
Supply
Shield Ground
* Return may be connected to an unused A terminal with the W jumper in place or to a –PS terminal.
Figure 148 Field Wiring for 9771-210F with a 3700, 3700A, 3703E, or 3721 AI Module or a 2770H HART
AI Interface Module—Sharing with Another System
Sharing a transmitter between the Tricon controller and another system may violate restrictions
regarding the segregation of safety and control functions. The sharing capability of this
termination panel should only be used in those applications where these restrictions do not
exist, or can be otherwise mitigated.
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 189
Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a current input
panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
PS1
180 Ohms
IN 32
Hi-Ref
IN
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
A
W ** 1 Amp ADC
PS1
PS2
W17 * Hi-Ref
32
Low-Ref
* When the 9771-210F panel is used with a 3700A or a 3721 module, do not remove the W17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the W jumper may be removed.
Figure 149 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9771-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
190 Chapter 5 Analog Input and Analog Output Termination Panels
This is a simplified schematic of a typical 16-point analog input module with a current input
panel (1 of 16 module points shown).
to
spare Mux
PS1
180 Ohms
16
IN
Hi-Ref
IN Low-Ref
Mux
to
other
points
250 Ohms 1 Amp ADC
16
A
Hi-Ref
Low-Ref
Mux
W **
1 Amp ADC
PS1 16
W17 * Hi-Ref
PS2
Low-Ref
* For extended common-mode operation, you must remove the W17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the W jumper may be removed.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 191
This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).
HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE
to
spare Mux
Isolation/filtering
PS1
180 Ohms
IN 32
Hi-Ref
IN
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
A
W ** 1 Amp ADC
PS1
W17 * Hi-Ref
32
PS2
Low-Ref
FIELD
TERMINATION PANEL
CABLE
Figure 151 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 AI Module
and a 9771-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
192 Chapter 5 Analog Input and Analog Output Termination Panels
SN J1
REV A
A
7400144-
E
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
10
22
23
12
24
13
25
14
26
15
27
16
28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1
PS2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 193
Specifications
This table describes specifications for 9750-210F.
Compatible Modules
This table describes analog input modules compatible with 9750-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
194 Chapter 5 Analog Input and Analog Output Termination Panels
Termination panel
+24 VDC
7400144-
REV A
32
30 50 mA, fast acting or Typical 2 of 32
28 180 Ohm, 3W resistor points shown
26
24
22
J1
20
18
50 mA, fast acting or Field
Xmtrs
16
180 Ohm, 3W resistor
14
(4-20 mA)
12
10
8 4E (IN2 +)
6
4
2
SN
E
C
2A (IN1 +)
2
14C to 32C (RTN)
*
RTN
Figure 154 Field Wiring for 9750-210F with a 3704E or 3720 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 195
Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a basic current
input panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
IN1 + 64
64
Hi-Ref
Low-Ref
Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Figure 155 Simplified Schematic of a 3704E or 3720 AI Module with a 9750-210F Panel
Specifications
This table describes specifications for 9760-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
196 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9760-210F.
Termination panel
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
p
PS1
PS2
DC
Power
Supply
Shield Ground
Figure 156 Field Wiring for 9760-210F with a 3704E or 3720 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 197
Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a current input
panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
180 Ohms 64
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms 1
Amp ADC
PS1 64
PS2
Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Figure 157 Simplified Schematic of a 3704E or 3720 AI Module with a 9760-210F Panel
Specifications
This table describes specifications for 9760-410F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
198 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9760-410F.
Termination panel
SN REV A 7400150-
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
J1
CR1
CR2
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1
PS2
DC
Power
Supply
Shield Ground
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 199
Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a current input
panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
180 Ohms 64
Hi-Ref
Low-Ref
to Mux
other
points
500 Ohms 1
Amp ADC
PS1 64
PS2
Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
200 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9765-210F.
Compatible Modules
This table describes analog input modules compatible with 9765-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 201
Termination panel
SN REV A 7400153-
J1
CR1
CR2
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
T+
T+
T+
T+
T–
T–
T–
T–
RTN
RTN
RTN
RTN
PS1
PS2
Shield Ground
Figure 160 Field Wiring for 9765-210F with a 3704E or 3720 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
202 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 64-point, 3-wire analog input module with a current
input panel (1 of 64 module points shown).
to
spare
Mux
50 mA
1
T Amp ADC
Isolation/
250 filtering
Ohms 64
500 mA
T
Hi-Ref
Low-Ref
12K
RTN
LED * to
Mux
other 1
points Amp ADC
PS1 64
PS2 Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Figure 161 Simplified Schematic of a 3704E or 3720 AI Module with a 9765-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 203
SN REV A 7400171-
J1
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+
+
–
–
Figure 162 Typical 16-Point Thermocouple Input Term Panel
Specifications
This table describes specifications for 9765-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
204 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes thermocouple input modules compatible with 9765-610F.
Termination panel
SN REV A 7400171-
J1
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+
+
–
Typical point
(1 of 16 points shown)
+
Shield Ground
Figure 163 Field Wiring for 9765-610F with a 3708E Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 205
Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Figure 164 Simplified Schematic of a 3708E Thermocouple Input Module with a 9765-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
206 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9766-210F.
Compatible Modules
This table describes thermocouple input modules compatible with 9766-210F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 207
Termination panel
SN REV A 7400171-
J1
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+
+
–
Typical point
(1 of 16 points shown)
+
Shield Ground
Figure 165 Field Wiring for 9766-210F with a 3706A Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
208 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
+V
1 Amp ADC
22M
32
Hi-Ref
Low-Ref
22M
Mux
–V
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 166 Simplified Schematic of a 3706A Thermocouple Input Module with a 9766-210F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 209
Specifications
This table describes specifications for 9766-510F.
Compatible Modules
This table describes thermocouple input modules compatible with 9766-510F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
210 Chapter 5 Analog Input and Analog Output Termination Panels
Termination panel
SN REV A 7400171-
J1
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+
+
–
Typical point
(1 of 16 points shown)
+
Shield Ground
Figure 167 Field Wiring for 9766-510F with a 3706A Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 211
Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
–V
1 Amp ADC
22M
32
Hi-Ref
Low-Ref
22M
Mux
+V
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 168 Simplified Schematic of a 3706A Thermocouple Input Module with a 9766-510F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
212 Chapter 5 Analog Input and Analog Output Termination Panels
This figure represents a typical 16-point voltage input basic termination panel.
J1
DIDO PANEL
REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
TRICONEX
7400143-
C C
E E
SN REV A 7400171-
J1
10
12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+
+
–
This figure represents a typical 32-point voltage input basic termination panel.
SN J1
REV A
A
7400144-
E
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 213
Specifications
This table describes specifications for 9750-810F.
Compatible Modules
This table describes analog input modules compatible with 9750-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
214 Chapter 5 Analog Input and Analog Output Termination Panels
RTN
Termination panel
7400144-
REV A
Typical
unused point
32
30
28 Typical 1 of 32
26 points shown
24
3720: 18C to 32C
(FGND)
22
J1
20
3704E: 14C to 32C
18
(RTN) V 0-5 or 0-10 VDC
16
14
12
10
8
6
4
2
SN
C
A
2A (IN1)
Figure 172 Field Wiring for 9750-810F with a 3704E or 3720 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 215
Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a basic current
input panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
IN1 64
Hi-Ref
Low-Ref
RTN
Mux
to
other 1
points Amp ADC
64
Hi-Ref
Low-Ref
Mux
1
Amp ADC
64
Hi-Ref
Low-Ref
Figure 173 Simplified Schematic of a 3704E or 3720 AI Module with a 9750-810F Panel
Specifications
This table describes specifications for 9753-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
216 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9753-110F.
Figure 174 Field Wiring for 9753-110F with a 3700, 3700A, or 3701 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 217
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
218 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a basic current
input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
IN1 + 32
Hi-Ref
IN1 –
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 177 Simplified Schematic of a 3700, 3700A, 3701, or 3721 AI Module with a 9753-110F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 219
This is a simplified schematic of a typical 16-point analog input module with a basic current
input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
16
IN
Hi-Ref
IN Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Specifications
This table describes specifications for 9763-810F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
220 Chapter 5 Analog Input and Analog Output Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9763-810F.
Figure 179 Field Wiring for 9763-810F with a 3700, 3700A, or 3701 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 221
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
222 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a voltage input
panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 181 Simplified Schematic of a 3700, 3700A, 3701 AI Module with a 9763-810F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 223
This is a simplified schematic of a typical 16-point analog input module with a voltage input
panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
7B47
7B47
7B47
7B32
7B32
7B32
7B32
7B34
7B34
7B34
7B34
7B34
7B34
7B34
7B34
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
ISOLATED
ISOLATED
ISOLATED
ISOLATED
PROCESS
PROCESS
PROCESS
PROCESS
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
TC INPUT
TC INPUT
TC INPUT
TC INPUT
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
J2
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
J3 J4 J5 J6
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
224 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9764-310F.
Compatible Modules
This table describes analog input modules compatible with 9764-310F.
For more information on analog input modules, see the Planning and Installation Guide for Tricon
11.5 and Later 11.x Systems.
The input-signal conditioning modules used on Triconex termination panels are manufactured
by Analog Devices and Dataforth. Signal conditioning modules must be ordered separately and
are available from Schneider Electric or directly from Analog Devices or Dataforth.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 225
This table describes temperature and other input parameters for available signal conditioning
modules. For detailed specifications, visit the Analog Devices Web site or the Dataforth Web
site.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
226 Chapter 5 Analog Input and Analog Output Termination Panels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 227
* 7B47
7B47
7B47
7B47
7B32
7B32
7B32
7B32
7B34
7B34
7B34
7B34
7B34
7B34
7B34
7B34
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
ISOLATED
ISOLATED
ISOLATED
ISOLATED
PROCESS
PROCESS
PROCESS
PROCESS
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
TC INPUT
TC INPUT
TC INPUT
TC INPUT
U1 U2 U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
J2
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
J3 J4 J5 J6
**
* A signal conditioning module or shorting plug 1600048-300 must be installed on all points.
** Unused points must be shorted at the +, –, and x terminals. The diagram shows a typical point.
An optional shield is available for use with conditioning modules to help meet EMC
requirements.
This figure illustrates how to connect a 9764-310F with RTD input-signal conditioning modules
to a field device (1 of 16 points shown).
7B34
7B34
7B34
7B34
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
ISOLATED
ISOLATED
ISOLATED
ISOLATED
R12
12
13
14
15
16
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10 11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
11
J5
Shield
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
228 Chapter 5 Analog Input and Analog Output Termination Panels
This figure illustrates how to connect a 9764-310F with TC input-signal conditioning modules
to a field device (1 of 16 points shown).
7B47
7B47
7B47
7B47
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
R4
ISOLATED
ISOLATED
ISOLATED
ISOLATED
TC INPUT
TC INPUT
TC INPUT
TC INPUT
12
13
14
15
16
U1 U2 U3 U4
11
12
13
14
15
16
R1 R2 R3 R4
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
*
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
J3
* Shield
This figure illustrates how to connect a 9764-310F with AI input-signal conditioning modules to
a field device (1 of 16 points shown).
7B32
7B32
7B32
7B32
DEVICES CURRENT INPUT
ANALOG
PROCESS
PROCESS
PROCESS
ISOLATED
ISOLATED
ISOLATED
ISOLATED
U5 U6 U7 U8
R5 R6 R7 R8
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
J4
+
Field
– Transmitter
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 229
J2
+ - + -
Pin-Out Information
This table describes the pin-out information for the 9764-310F RTD/TC/AI panel.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
230 Chapter 5 Analog Input and Analog Output Termination Panels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 231
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
232 Chapter 5 Analog Input and Analog Output Termination Panels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 233
a. NC = No connect
b. X = Third wire (sense signal)
c. SH = Shield
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
234 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a RTD/TC/AI
panel (1 of 32 module points shown).
to
P1 spare Mux
Isolation/filtering
P2
1 Amp ADC
LED * Hi-Ref
32
Com Low-Ref
Mux
+ 1 Amp ADC
7BXX
–
Typical Signal
Conditioner
x 32
Hi-Ref
Low-Ref
y
rfu **
–
Mux
CJ
Thermocouple
***
1 Amp ADC
x
32
Hi-Ref
Low-Ref
Figure 189 Simplified Schematic of a 3700 or 3700A AI Module with a 9764-310F (RTD/TC/AI) Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 235
TRICONEX
E E
7400143-
C C
TM
A A
SN
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
HCAO PANEL
REV A
CH5 Volts
CH1 Volts
J1
J1
DIDO PANEL
REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
TRICONEX
7400143-
C C
E E
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20
C19
REV B
L12
0° C≤TA≤+60° C
C14
C15
SN L15 L16
L6
R19
L13 L14
L5 C12
L9 L10
L4 C10
L7 L8
C5
L3
C8
C7
C2
C3
L1
R20
!
C35
C36
C26
C37
C38
C39
C40
C41
C42
C43
TB7 TB8
C44
R2
R1
TB1—TB4
J4
L+ 1 2 3 4 2 3
1 4
C27
C25
C45
L-
J5 1 2 3 4 1 2 3 4 P1 P2
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
236 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9863-710F.
Compatible Modules
This table describes analog output modules compatible with 9863-710F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 237
+24 VDC
A22 (PWRA)
+24 VDC
A24 (PWRB)
Termination panel
REV A 7400143-
SN
C
A
36 BOUT1
BOUT5
***
34
32
30
28
26
E24 (RTN)
24
22
J1
20
18
E22 (RTN)
16
14
RTN
12
10
**
8
6 E20 (RTN8)
4
2
C
A
A20 (OUT8)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
238 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 3806E analog output module with a 9863-710F panel
(1 of 8 module points shown).
A Loop power
PWRA (22A)
Selector
Logic
Current
loopback PWRB (24A)
DAC
RTN (22E)
B RTN (24E)
Selector
Logic Current
loopback
DAC
OUT2 (6A)
Typical points
2-4
6-8
C RTN2 (6E)
Selector
Logic
Current
loopback
DAC
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 239
Pin-Outs
This table describes pin-outs for the 9863-710F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
240 Chapter 5 Analog Input and Analog Output Termination Panels
CGND is the controller protective earth (chassis ground). Pins r, s, X and Y on the panel
connector are not used.
Dual-Coil Actuator
A single high-current analog output supplies the signal for both coils of the dual coil actuator.
The current is divided according to the impedance of the two coils.
The power produced by the actuator coils is a function of the number of coils and the current
through them. If only one coil is used, the current must double to maintain the same power.
VOLTAGE-TO-CURRENT CONVERTER
COIL 1
CONTROLLER
OUTPUT V/I
(20 - 360 mA)
COIL 2
COIL STATUS
FEEDBACK
Because the controller output is a constant current, failure of one coil diverts all the current
through the remaining coil, thus maintaining the correct actuator output. For example: If the
controller output is 160 mA and the coil impedance is equal, the controller output is split evenly,
supplying 80 mA to each coil. If one coil fails, all of the controller output current goes to the
remaining good coil, effectively doubling the force that the failed coil produced before the
failure.
The voltage-to-current converter across the controller output responds to changes in the output
voltage that would result from the loss of a coil. The volt/amp characteristics of the good coils
are programmed into the controller. A significant deviation in the volt/amp characteristics
causes an alarm to be issued.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 241
DUAL-COIL
COIL 1 CURRENT
ACTUATOR
VOLTAGE-TO-CURRENT CONVERTER
TP 2A
COIL 1
PIN AA TP 2E
CONTROLLER
OUTPUT V/I Point 1
(20 - 360 mA)
PIN LL TP 4A
COIL 2
TP 4E
TP 28A TP 28E
COIL STATUS
FEEDBACK
DUAL-COIL
COIL 2 CURRENT
ACTUATOR
VOLTAGE-TO-CURRENT CONVERTER
TP 12A
COIL 1
PIN e TP 12E
CONTROLLER
OUTPUT V/I Point 5
(20 - 360 mA)
PIN b TP 14A
COIL 2
TP 14E
TP 30A TP 30E
COIL STATUS
FEEDBACK
Voltage-to-Current Converter
This is a simplified schematic of a voltage-to-current converter.
+ 5
INPUT
0-28 VDC
- 3
+ 1
LOGIC SUPPLY E TO I
24 VDC CONVERTER
- 2
+ 4
OUTPUT
4-20 mA
- 6
EQUIVALENT CIRCUIT
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
242 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9853-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 243
Compatible Modules
This table describes analog output modules compatible with 9853-610F.
+24 VDC
22A (PWRA)
+24 VDC
24A (PWRB)
Termination panel
REV A 7400143-
SN
A
E
C
32
30
28
26
24E (RTN)
24
22
J1
20
18 22E (RTN)
16
14
RTN
12
10
*
8
16E (RTN8)
6
4
2
A
E
C
TM
DIDO PANEL TRICONEX
2E (RTN1)
Load **
2A (OUT1)
16A (OUT8)
Figure 198 Field Wiring for 9853-610F with a 3805E or 3805H AO Module or 2870H HART AO Interface
Module
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
244 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
a basic current output panel (1 of 8 module points shown).
A Loop power
PWRA (22A)
Selector
Logic
Current
loopback PWRB (24A)
DAC
RTN (22E)
B RTN (24E)
Selector
Logic Current
loopback
DAC
OUT1 (2A)
C RTN1 (2E)
Selector
Logic
Current
loopback
DAC
Figure 199 Simplified Schematic of a 3805E or 3805H AO Module with a 9853-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 245
This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with a
basic current output panel (1 of 8 module points shown).
A Loop power
PWRA (22A)
Selector
Logic
Current
loopback PWRB (24A)
DAC
RTN (22E)
B RTN (24E)
Selector
Logic OUT1 (2A)
Current
loopback
DAC
RTN1 (2E)
Selector
Logic
Current
loopback
VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER
RS-485 HART
CABLE CONTROLLER
Figure 200 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9853-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
246 Chapter 5 Analog Input and Analog Output Termination Panels
Specifications
This table describes specifications for 9881-810F.
Table 146 Cable and Load Parameters for Term Panel 9881-810F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications
For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 247
Compatible Modules
This table describes the analog output module compatible with 9881-810F.
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20
C19
REV B
L12
0° C≤TA≤+60° C
C14
C15
SN L15 L16
L6
R19
L13 L14
L5 C12
L9 L10
L4 C10
L7 L8
C5
L3
C8
C7
C2
C3
L1
R20
!
C35
C36
C26
C37
C38
C39
C40
C41
C42
C43
TB7 TB8
C44
R2
R1
TB1—TB4
J4
L+ 1 2 3 4 2 3
1 4
C27
C25
C45
L-
J5 1 2 3 4 1 2 3 4 P1 P2
PS2
Typical -
DC
unused Power
point + Supply
Typical point
(1 of 4 points shown) PS1
- DC
Power
Point 1 Point 1 + Supply
Torque Motor Coil Optional
(Load) Redundant Torque
Motor Coil
Figure 201 Field Wiring for 9881-810F with a 3807 Bipolar Analog Output Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
248 Chapter 5 Analog Input and Analog Output Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 4-point Bipolar Analog Output module with an analog
output panel (1 of 4 module points shown with 1.0 Henry snubber 301 Ω, 680 nF). The
connection to the coil-diagnostic input is hardwired on the termination panel.
A
Loop power
+18 / -18 P1 PWR
DAC
P2 PWR
ADC
P1 RTN
Channel
Select
P2 RTN
B
Protective
+18 / -18
Earth
DAC
Source
Current
L+
ADC Coil
L-
Channel
Select Sink 301:
Current
L+
C Redundant
+18 / -18 680nF Coil
L-
DAC
Channel
Select
Figure 202 Simplified Schematic of a 3807 Bipolar Analog Output Module with a 9881-810F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
6
Hazardous Location (Nonincendive)
Termination Panels
Overview 250
Field Wiring in Hazardous Locations 250
Grounding and Installation Recommendations 251
Analog Input Term Panels 253
Analog Output Term Panels 277
Digital Input Term Panels 285
Digital Output Term Panels 296
Pulse Input Term Panels 302
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
250 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Overview
This chapter describes external field termination panels (ETPs) with nonincendive circuits that
you can use in hazardous locations.
This table identifies ETPs that use nonincendive circuits as approved by TÜV Rhineland.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Grounding and Installation Recommendations 251
Current Limiting
Each of the following termination panels has a 190-to-310-ohm positive temperature coefficient
(PTC) resistor:
• 9791-610F
• 9789-610F
• 9572-610F
• 9570-610F
• 9571-610F
• 9671-610F
The PTC resistor acts as a resettable fuse and an over-current protection device. When the
current through the resistor increases, the resistor self-heats and drives up its own resistance
until the current and temperature reach equilibrium. The maximum working current of each
ETP listed above is 28 mA and is specified in the Cable and Load Parameters table for each ETP.
Grounding
Each hazardous location ETP described in this chapter purposefully connects the signal and
protective earth ground. This connection prevents a difference of potential that could
potentially spark and cause an ignition.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
252 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
+
DIN rail
J1
J1
Gaskets
You must use gasket 2000098-100 on the male side of all ELCO connectors used in hazardous
location installations, and replace it before the end of its five-year life span. Schneider Electric
recommends that you use the gasket in all hazardous locations requiring nonincendive circuits.
(Order Schneider Electric part number 3000793-001 for a kit of 25 gaskets.)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 253
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
254 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes general specifications for 9791-610F.
Table 150 Cable and Load Parameters for Term Panel 9791-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (F–) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 255
Compatible Modules
This table describes analog input modules compatible with 9791-610F.
When used with the 9791-610F, the accuracy of the 3700A, 3703E, and 3721 modules may be
affected by up to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result, the
accuracy of these modules is +0.15% to –0.23% FSR, at 140° F (60° C).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
256 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B &7$& 7400275
as short as possible
17
R
SN SN
R25
18
R1
R1
R
9
R
TB1 TB4 TB1
5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2
R2
R
10
R
R27
20
R3
R3
R
11
R
R28
3
21
R4
R4
R
12
R
R29
22
R5
R5
R
13
R
R30
23
5
5
R
14
!
R
R31
24
R7
R7
R
15
R
R32
R8
R8
J1
5
J2 J2
L+ /
J3 J3
L- 3 3 L-
Shield Ground
Figure 205 Field Wiring for 9791-610F with a 3700A, 3703E, or 3721 AI Module or 2770H HART AI
Interface Module
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 257
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).
* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers
Figure 206 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9791-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
258 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).
HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE
1 Amp ADC
~ 10V
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
*ATEX
Mux
PE GND
32
Hi-Ref
FIELD
TERMINATION PANEL Low-Ref
CABLE
* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers
Figure 207 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 Analog
Input Module and a 9791-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 259
Specifications
This table describes general specifications for 9787-110F.
Table 153 Cable and Load Parameters for Term Panel 9787-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Input Connection (I+ and I–) Specifications when Used with 3700A
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
260 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Table 153 Cable and Load Parameters for Term Panel 9787-110F (continued)
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
L external, maximum Lo La 1H
Compatible Modules
This table describes analog input modules compatible with 9787-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 261
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1 TB1
EXT TERM TRICON
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ
V
Field
Source
Figure 208 Field Wiring for 9787-110F with a 3700A, 3703E, or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
262 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
voltage input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
+V
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
-V
1 Amp ADC
*ATEX
32
Hi-Ref
Low-Ref
PE GND
Mux
PE GND
1 Amp ADC
32
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 263
This is a simplified schematic of a typical 16-point commoned analog input module with a
voltage input panel (1 of 16 module points shown).
to
spare Mux
+V 1 Amp ADC
~
16
Hi-Ref
Low-Ref
~ Mux
-V Amp ADC
1
*ATEX
16
Hi-Ref
Low-Ref
PE GND Mux
16
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
264 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes general specifications for 9785-610F.
Table 156 Cable and Load Parameters for Term Panel 9785-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications
Compatible Modules
This table describes the thermocouple input module compatible with 9785-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 265
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1 TB1
EXT TERM TRICON
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
Typical point
RISRLQWVVKRZQ
-
Shield Ground
Figure 211 Field Wiring for 9785-610F with a 3706A Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
266 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
+V
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
-V
1 Amp ADC
*ATEX
32
Hi-Ref
Low-Ref
PE GND
Mux
PE GND
1 Amp ADC
32
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 267
Specifications
This table describes general specifications for 9784-610F.
Table 159 Cable and Load Parameters for Term Panel 9784-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications
Compatible Modules
This table describes the thermocouple input module compatible with 9784-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
268 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1 TB1
EXT TERM TRICON
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
Typical point
RISRLQWVVKRZQ
-
Shield Ground
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 269
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
EXT TERM TRICON TB1 TB1
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
Typical point
RISRLQWVVKRZQ
-
Shield Ground
Figure 213 Field Wiring for 9784-610F with a 3706A Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
270 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
+V +V
1 Amp ADC
22M
32
Hi-Ref
Low-Ref
22M
Mux
-V -V
32
Hi-Ref
Low-Ref
PE GND
Mux
PE GND
1 Amp ADC
32
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 271
Specifications
This table describes general specifications for 9786-110F.
Table 162 Cable and Load Parameters for Term Panel 9786-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
272 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Compatible Modules
This table describes the analog input module compatible with 9786-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 273
&7$&
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1
EXT TERM TRICON
REV B
$7(;(0&$,7&
J2
/
7400272
SN
J3
L-
Typical
unused point
Typical point
RISRLQWVVKRZQ
-
Shield Ground
Figure 215 Field Wiring for 9786-110F with a 3708E Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
274 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).
to
spare Mux
+V ADC
1 Amp
16
Hi-Ref
Low-Ref
Mux
-V 1 Amp ADC
*ATEX
16
Hi-Ref
Low-Ref
PE GND Mux
1 Amp ADC
PE GND
16
Hi-Ref
Low-Ref
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 275
Specifications
This table describes general specifications for 9789-610F.
Table 165 Cable and Load Parameters for Term Panel 9789-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw ≤ 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (–) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
276 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Compatible Modules
This table describes the analog input modules compatible with 9789-610F.
When used with the 9789-610F, the accuracy of modules 3704E and 3720 may be affected by up
to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result: the accuracy of module
3704E is +0.25% to –0.33% FSR, at 140° F (60° C), the accuracy of module 3720 is +0.15% to –
0.23% FSR, at 140° F (60° C).
$:*
12
20
28
10
18
19
26
27
11
13
15
21
23
29
31
14
22
30
24
17
25
16
32
4
2
4
5
3
6
5
1
6
1
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
DVVKRUWDV
SRVVLEOH
R34
R35
R36
R38
R42
R43
R44
R46
R50
R51
R52
R54
R58
R59
R60
R62
R37
R45
R53
R61
R40
R48
R56
R64
R39
R47
R55
R63
R33
R41
R49
R57
R34
R35
R33
J3
R65
R66
R67
R68
R69
R70
R71
R72
R73
R74
R75
R76
R77
R78
R79
R80
R81
R82
R83
R84
R85
R86
R87
R88
R89
R90
R91
R92
R93
R94
R95
R96
R65
R66
R67
TB1 TB2 TB1
!
12
14
18
19
20
22
26
27
28
30
13
21
29
16
24
32
15
23
17
31
25
11
2
6
5
8
7
1
J1 J4 J1
/ / /
J2 J5 J2
/ / /
P1 P2
6KLHOG*URXQG
Figure 217 Field Wiring for 9789-610F with a 3704E or 3720 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 277
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned analog input module with a
4-20 mA, high-density input panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
Hi-Ref
Low-Ref
to Mux
other
points 1
250 Ohms 10V
Amp ADC
PS1 64
PS2 Hi-Ref
Low-Ref
PS1
PS2 Mux
1
*ATEX Amp ADC
PE GND
64
Hi-Ref
PE GND
Low-Ref
* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers
Figure 218 Simplified Schematic of a 3704E or 3720 Analog Input Module with a 9789-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
278 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes specifications for 9861-610F.
Table 168 Cable and Load Parameters for Term Panel 9861-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 279
Compatible Modules
This table describes the analog output module compatible with 9861-610F.
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
$7(;(0&$2
7400270 C17
C20
C19
REV B
L12
&7$&
C14
C15
SN L15 /
/
L11
L13 L14
L5 C12
L9 L10
L4 C10
L7 L8
C5
L3
C8
C7
C2
C3
L1
L2
!
C35
&
&
C37
C38
C39
C40
C41
C42
C43
TB7 TB8
C44
R2
R1
TB1—TB4
J4
/
C27
C25
C45
L-
J5 P1 P2
PS1
- DC
Load
Power
+ Supply
Figure 219 Field Wiring for 9861-610F with a 3805E or 3805H AO Module or a 2870H HART AO
Interface Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
280 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
an analog output panel (1 of 8 module points shown).
A Loop power
PWRA
Selector
Logic
Current
loopback PWRB
DAC
RTN
B RTN
Selector
Logic Current
PE GND
loopback *ATEX
PE GND
DAC
OUT2
Typical point
30V
C RTN2
Selector
Logic
Current
loopback
DAC
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 281
This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with
an analog output panel (1 of 8 module points shown).
A Loop power
PWRA
Selector
PWRB
Logic
Current
loopback RTN
DAC RTN
PE GND
*ATEX
B PE GND
Selector
Logic OUT2
Current
loopback Typical point
DAC
~ 30V
RTN2
Selector
Logic
Current
loopback
VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER
RS-485 HART
CABLE CONTROLLER
Figure 221 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9861-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
282 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes specifications for 9871-810F.
Table 171 Cable and Load Parameters for Term Panel 9871-810F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications
For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 283
Compatible Modules
This table describes the analog output module compatible with 9871-810F.
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20
C19
REV B
L12
0° C≤TA≤+60° C
C14
C15
SN L15 L16
L6
R19
L13 L14
L5 C12
L9 L10
L4 C10
L7 L8
C5
L3
C8
C7
C2
C3
L1
R20
!
C35
C36
C26
C37
C38
C39
C40
C41
C42
C43
TB7 TB8
C44
R2
R1
TB1—TB4
J4
L+ 1 2 3 4 2 3
1 4
C27
C25
C45
L-
J5 1 2 3 4 1 2 3 4 P1 P2
PS2
Typical -
DC
unused Power
point + Supply
Typical point
(1 of 4 points shown) PS1
- DC
Power
Point 1 Point 1 + Supply
Torque Motor Coil Optional
(Load) Redundant Torque
Motor Coil
Figure 222 Field Wiring for 9871-810F with a 3807 Bipolar Analog Output Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
284 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 4-point Bipolar Analog Output module with an analog
output panel (1 of 4 module points shown with 1.0 Henry snubber 301 Ω, 680 nF). The
connection to the coil-diagnostic input is hardwired on the termination panel.
A
Loop power
+18 / -18 P1 PWR
DAC
P2 PWR
ADC
P1 RTN
Channel
Select
P2 RTN
B
* ATEX Protective
Earth
+18 / -18
DAC
Source
Current
L+
ADC Coil
L-
Channel
Select Sink 301:
Current
L+
C
Redundant
+18 / -18 680nF Coil
L-
DAC
Channel
Select
Figure 223 Simplified Schematic of a 3807 Bipolar Analog Output Module with a 9871-810F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 285
Specifications
This table describes general specifications for 9572-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
286 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Table 174 Cable and Load Parameters for Term Panel 9572-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (F–) Specifications
Compatible Modules
This table describes digital input modules compatible with 9572-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 287
TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B &7$& 7400275
as short as possible
17
R
SN SN
R25
18
R1
R1
R
9
R
TB1 TB4 TB1
'21276(3(5$7(
5
:+(1(1(5*,=('
19
R2
R2
R
10
R
R27
20
R3
R3
R
11
R
R28
3
21
R4
R4
R
12
R
R29
22
R5
R5
R
13
R
R30
23
5
5
R
14
!
R
R31
24
R7
R7
R
15
R
R32
R8
R8
J1
5
TB2 TB3 TB5 7%
J2 J2
/ /
J3 J3
L- P1 P2 L-
Figure 224 Field Wiring for 9572-610F with a 3503E or 3505E DI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
288 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
This figure illustrates how to connect a 3515 pulse totalizer input module and a 9572-610F to the
field (1 of 32 module points shown).
TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B &7$& 7400275
as short as possible
17
R
SN SN
R25
18
R1
R1
R
9
R
TB1 TB4 TB1
'21276(3(5$7(
5
:+(1(1(5*,=('
19
R2
R2
R
10
R
R27
20
R3
R3
R
11
R
R28
3
21
R4
R4
R
12
R
R29
22
R5
R5
R
13
R
R30
23
5
5
R
14
!
R
R31
24
R7
R7
R
15
R
R32
R8
R8
J1
5
TB2 TB3 TB5 7%
J2 J2
/ /
J3 J3
L- P1 P2 L-
*
$,1
$FWLYH
Pulse
Sensor
2E (IN1 –)
RTN
Energy Not
limited energy limited
Figure 225 Field Wiring for 9572-610F with a 3515 Pulse Totalizer Input Module
With the 3515 pulse totalizer input module, sensor pulse outputs should be the push-pull type.
You may use high-side or low-side, solid-state output, but maximum frequency may be reduced
based on cable distance. Do not use mechanical relay/switch contacts. To prevent point-to-
point cross-talk, use individually shielded, twisted-pair wire for lengths greater than 50 feet (15
meters).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 289
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with a
commoned input panel (1 of 32 module points shown).
TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
Test A
30V
to
other Threshold to
points Detect Input
250 Ohms Opto-Isolator Mux B
PS1
PS2
Test B
PS1
PS2
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
*ATEX module
PE GND
Test C
PE GND
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
290 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
This is a simplified schematic of a typical 32-point pulse totalizer input module with a
commoned input panel (1 of 32 module points shown).
Leg-to-
Leg
Isolation To
Threshold Counters
Detect
Opto-Isolator Leg A
To
Threshold
~ 30V Detect
Counters
to Opto-Isolator Leg B
other
points
250 Ohms
PS1
PS2
PS1
To
PS2 Threshold Counters
to Detect
spare Opto-Isolator Leg C
*ATEX module
PE GND
PE GND
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 291
Specifications
This table describes general specifications for 9570-610F.
Table 177 Cable and Load Parameters for Term Panel 9570-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 18 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (–) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
292 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Compatible Modules
This table describes the digital input module compatible with 9570-610F.
'21276(3$5$7(:+(1(1(5*,=('
$:*
12
20
28
10
18
19
26
27
11
13
15
21
23
29
31
14
22
30
24
17
25
16
32
4
2
4
5
3
6
5
1
6
1
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
DVVKRUWDV
SRVVLEOH
R34
R35
R36
R38
R42
R43
R44
R46
R50
R51
R52
R54
R58
R59
R60
R62
R37
R45
R53
R61
R40
R48
R56
R64
R39
R47
R55
R63
R33
R41
R49
R57
R34
R35
R33
J3
R65
R66
R67
R68
R69
R70
R71
R72
R73
R74
R75
R76
R77
R78
R79
R80
R81
R82
R83
R84
R85
R86
R87
R88
R89
R90
R91
R92
R93
R94
R95
R96
R65
R66
R67
TB1 TB2 TB1
!
12
14
18
19
20
22
13
26
27
28
30
21
29
16
15
24
23
32
17
31
25
11
2
6
5
8
7
1
J1 J4 J1
/ / /
J2 J5 J2
/ / /
P1 P2
36 6HFRQGWHUPSDQHO
7\SLFDOSRLQW
RISRLQWVVKRZQ '&
Power
6XSSO\
)LHOG
&RQWDFW 36
'&
Power
6XSSO\
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 293
Simplified Schematics
This is a simplified schematic of a typical 64-point commoned digital input module with a
commoned input panel (1 of 64 module points shown).
Mux
to
spare 1
Amp ADC
310 Ohms Max
64
Hi-Ref
30V Low-Ref
to Mux
other
points
2.7K 1
Amp ADC
PS1 64
PS2 Hi-Ref
Low-Ref
PS1
PS2 Mux
1
Amp ADC
*ATEX
64
PE GND
Hi-Ref
Low-Ref
PE GND
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
294 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes general specifications for 9571-610F.
Table 180 Cable and Load Parameters for Term Panel 9571-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 15 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Output Connection (+ and –) Specifications
Compatible Modules
This table describes the digital input module compatible with 9571-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 295
'21276(3$5$7(:+(1(1(5*,=('
$:*
12
20
28
10
18
19
26
27
11
13
15
21
23
29
31
14
22
30
24
17
25
16
32
4
2
4
5
3
6
5
1
6
1
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
DVVKRUWDV
SRVVLEOH
R34
R35
R36
R38
R42
R43
R44
R46
R50
R51
R52
R54
R58
R59
R60
R62
R37
R45
R53
R61
R40
R48
R56
R64
R39
R47
R55
R63
R33
R41
R49
R57
R34
R35
R33
J3
R65
R66
R67
R68
R69
R70
R71
R72
R73
R74
R75
R76
R77
R78
R79
R80
R81
R82
R83
R84
R85
R86
R87
R88
R89
R90
R91
R92
R93
R94
R95
R96
R65
R66
R67
TB1 TB2 TB1
!
10 TB3 TB4 TB5 TB6
12
14
18
19
20
22
13
26
27
28
30
21
29
16
15
24
23
32
17
31
25
11
2
6
5
8
7
1
J1 J4 J1
/ / /
J2 J5 J2
/ / /
P1 P2
36 6HFRQGWHUPSDQHO
7\SLFDOSRLQW
RISRLQWVVKRZQ '&
Power
6XSSO\
)LHOG
&RQWDFW 36
'&
Power
6XSSO\
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
296 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 64-point, fail-safe, commoned digital input module
with a commoned input panel (1 of 64 module points shown).
to
spare
Test ON Relays
310 Ohms Max (opto-isolated)
to other
points &
sensors
Threshold Detect
PS1 Opto-Isolator B
PS2
C
*ATEX
PE GND
PE GND
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 297
When using 32 point modules, you must use two term panels for each digital output module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.
Specifications
This table describes general specifications for 9671-610F.
Table 183 Cable and Load Parameters for Term Panel 9671-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 16 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Output Connection (F+) Specifications
Compatible Modules
This table describes digital output modules compatible with 9671-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
298 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module
may be powered from four independent field power sources, but only if the voltage from those
sources is within 5% of the highest voltage supplied. If this restriction is not followed, the module
will still operate but may experience voter faults and generate an alarm.
TRICONEX - 7400274
REV B
&7$& SN
'21275(029()86(:+(1(1(5*,=('
'21276(3$5$7(:+(1(1(5*,=('
$7(;&20021(' '2
EXT TERM TRICON
7%
!
2
5
8
7
/
J2
3 3 L- Load *
J3
36
'&
3RZHU
Supply
-
36
'&
3RZHU
Supply -
$ORDGPXVWEHLQVWDOOHGDWHYHU\SRLQWWRSUHYHQWPLVVLQJORDGDODUP,IDILHOGORDGLVDYDLODEOHLQVWDOOD2KP:ORDGUHVLVWRU
Figure 232 Field Wiring for 9671-610F with a 3604E, 3624, 3625, or 3625A DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 299
This figure illustrates how to connect a 3664 or a 3674 dual digital output module and a
9671-610F to the field (1 of 32 module points shown).
'21275(029()86(:+(1(1(5*,=('
'21276(3$5$7(:+(1(1(5*,=('
$7(; COMMONED DO
$7(; COMMONED DO
TB1 TB1
!
10
12
14
13
15
11
2
5
8
7
1
9
/
J2
P1 P2 L- P1 P2
J3
PS2
Load
DC
Power
Supply -
Figure 233 Field Wiring for 9671-610F with a 3664 or 3674 DO Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
300 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a commoned output panel (1 of 16 module points shown).
A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B points
L+
A "B 310 Ohms Max
Output 30V
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot *ATEX
Drive PE GND
spare
Circuitry
A Voltage
B Loopback
C Detector
PE GND
This is a simplified schematic of a typical 16-point, supervised, digital output module with self
protection and a commoned digital output panel (1 of 16 module points shown).
OVD Switch #1
A Voltage
B Loopback to other
C Detector points
A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B points
L+
A "B 310 Ohms Max
Output OVD Switch #2 30V
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output *ATEX
to
Switch hot PE GND
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
PE GND
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 301
This is a simplified schematic of a typical 32-point, supervised, digital output module with self
protection and a commoned digital output panel (1 of 32 module points shown).
PS2 +
A or C
*to other to other
A B points points
Output L+
Switch
Drive 310 Ohms Max
Circuitry
30V
L–
B
Output PS1 –
Switch to other
Drive points
Circuitry
PS2 –
C A or C
C
Current
Output Loopback
Switch Detector **ATEX
Drive Analog/ PE GND
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector
PE GND
*For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the
3625A module, field power is commoned in groups of 16 points and is separated by termination panels.
**ATEX-required protective earth (chassis ground) to functional earth jumpers
Figure 236 Simplified Schematic of a 3625 or 3625A Digital Output Module with a 9671-610F Panel
This is a simplified schematic of a typical 32-point, dual digital output module with self
protection and a commoned digital output panel (1 of 32 module points shown).
A Voted PS1 +
Output
B PS2 +
Drive
to other
C Circuitry points
L+
310 Ohms Max
A Voted 30V
Drive
B L–
Output
C Circuitry
PS1 –
to other
points PS2 –
A Loopback
Detector/
*ATEX
B PE GND
C Isolator
to
hot
spare
Figure 237 Simplified Schematic of a 3664 or 3674 Digital Output Module with a 9671-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
302 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Specifications
This table describes specifications for 9793-110F.
Table 186 Cable and Load Parameters for Term Panel 9793-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Input Connection (I+ and I–) Specifications
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 303
Compatible Modules
This table describes pulse input modules compatible with 9793-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
304 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
&7$&
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1
EXT TERM TRICON
REV B
$7(;(0&$,7&
J2
/
7400272
SN
J3
L-
F
Typical point
F– (1 of 8 points shoZn
RT
**
*
* )XQFWLRQDOHDUWKJURXQGTXLHWJURXQGLVUHFRPPHQGHGIRUVKLHOGFRQQHFWLRQV)RUVKLHOGJURXQGLQJLQVWUXFWLRQVVHH$SSHQGL[(
* * :KHQSRVVLEOHLQVWDOODWHUPLQDWLQJUHVLVWRUDVVKRZQ)RUIXUWKHULQIRUPDWLRQVHH7HFKQLFDO$SSOLFDWLRQ1RWH7$1RQWKH
*OREDO&XVWRPHU6XSSRUW*&6FHQWHUZHEVLWH
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 305
Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
pulse input panel (1 of 8 module points shown).
to
spare Comparator
+15
AC coupled A
Counter/ Micro-
Timer Processor
-15 to
other
points
IN1
IN1
+15
Comparator
+15
14V AC coupled B
Counter/ Micro-
Timer Processor
14V
-15 to
other
-15 points
*ATEX
PE GND Comparator
+15
AC coupled
C
PE GND
Counter/ Micro-
Timer Processor
-15 to
other
points
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
306 Chapter 6 Hazardous Location (Nonincendive) Termination Panels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
7
RG 1.180 Termination Panels
Overview 308
Analog Input Term Panels 308
Analog Output Term Panels 331
Pulse Input Term Panels 336
RTD/TC/AI Input Term Panels 338
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
308 Chapter 7 RG 1.180 Termination Panels
Overview
In October 2003, the United States Nuclear Regulatory Commission (NRC) issued Revision 1 of
Regulatory Guide 1.180, “Guidelines for Evaluating Electromagnetic and Radio-Frequency
Interference in Safety-Related Instrumentation and Control Systems.” Regulatory Guide 1.180
endorses design, installation, and testing practices acceptable to the NRC staff for addressing
the effects of EMI/RFI and power surges on safety-related instrumentation and control (I&C)
systems in a nuclear power plant environment.
This chapter describes external termination panels (ETPs) that can be used in applications that
are required to meet RG 1.180 guidelines. Note that throughout this manual these term panels
are referred to as “RG 1.180” termination panels.
This table identifies RG 1.180 ETPs.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 309
Specifications
This table describes general specifications for 9790-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
310 Chapter 7 RG 1.180 Termination Panels
Compatible Modules
This table describes analog input modules compatible with 9790-610F.
When used with the 9790-610F, the accuracy of the 3700A, 3703E, and 3721 modules may be
affected by up to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result, the
accuracy of these modules is +0.15% to –0.23% FSR, at 140° F (60° C).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 311
TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B &7$& 7400275
as short as possible
17
R
SN SN
R25
18
R1
R1
R
9
R
TB1 TB4 TB1
5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2
R2
R
10
R
R27
20
R3
R3
R
11
R
R28
3
21
R4
R4
R
12
R
R29
22
R5
R5
R
13
R
R30
23
5
5
R
14
!
R
R31
24
R7
R7
R
15
R
R32
R8
R8
J1
5
TB2 TB3 TB5 7%
J2 J2
L+ /
J3 J3
L- 3 3 L-
Shield Ground
Figure 240 Field Wiring for 9790-610F with a 3700A, 3703E, or 3721 AI Module or 2770H HART AI
Interface Module
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
312 Chapter 7 RG 1.180 Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
190–310 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 241 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9790-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 313
This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
190–310 Ohms 16
Hi-Ref
Low-Ref
Mux
to
other
points
250 Ohms 1 Amp ADC
PS1
16
PS2
Hi-Ref
PS1 Low-Ref
PS2
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Figure 242 Simplified Schematic of a 3703E Analog Input Module with a 9790-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
314 Chapter 7 RG 1.180 Termination Panels
This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).
HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE
to
spare Mux
HART 2071H HART Isolation/filtering
CONTROLLER MUX Module
1 Amp ADC
190-310 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
TERMINATION PANEL FIELD
Low-Ref
CABLE
Figure 243 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 Analog
Input Module and a 9790-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 315
Specifications
This table describes general specifications for 9795-610F.
Compatible Modules
This table describes analog input modules compatible with 9795-610F.
When used with the 9795-610F, the accuracy of these modules may be affected by up to –0.08%
Full-Scale Range (FSR), at maximum temperature. As a result, the accuracy of these modules is
+0.15% to –0.23% FSR, at 140° F (60° C).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
316 Chapter 7 RG 1.180 Termination Panels
TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B &7$& 7400275
as short as possible
17
R
SN SN
R25
18
R1
R1
R
9
R
TB1 TB4 TB1
5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2
R2
R
10
R
R27
20
R3
R3
R
11
R
R28
3
21
R4
R4
R
12
R
R29
22
R5
R5
R
13
R
R30
23
5
5
R
14
!
R
R31
24
R7
R7
R
15
R
R32
R8
R8
J1
5
J2 J2
L+ /
J3 J3
L- 3 3 L-
Shield Ground
Figure 244 Field Wiring for 9795-610F with a 3703E or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 317
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
190–310 Ohms
32
Hi-Ref
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
PS1
PS2
32
PS1 Hi-Ref
PS2 Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 245 Simplified Schematic of a 3721 Analog Input Module with a 9795-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
318 Chapter 7 RG 1.180 Termination Panels
This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
190–310 Ohms 16
Hi-Ref
Low-Ref
Mux
to
other
points
250 Ohms 1 Amp ADC
PS1
16
PS2
Hi-Ref
PS1 Low-Ref
PS2
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Figure 246 Simplified Schematic of a 3703E Analog Input Module with a 9795-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 319
voltage is dependent on the loop power provided on the ETP (T+) within the range of 16 VDC
to 56 VDC.
Vloop > Vfield – Vdiode – ((300 Ohms) * ICC Transmitter) – 5.3 VDC
When using 32-point modules, you must use two term panels for each analog input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.
Specifications
This table describes specifications for 9792-610F.
Compatible Modules
This table describes analog input modules compatible with 9792-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
320 Chapter 7 RG 1.180 Termination Panels
When used with the 9792-610F, the accuracy of these modules may be affected by up to -0.08%
Full-Scale Range (FSR), at maximum temperature. As a result, the accuracy of these modules is
+0.15% to -0.23% FSR, at 140° F (60° C).
12 AWG,
as short as possible
T+
PS2
Typical point (1 of 16 points shown) DC
Power
Supply
+
Field Xmtr PS1
– (4-20 mA) DC
Power
Supply
Shield Ground
Figure 247 Field Wiring for 9792-610F with a 3700, 3700A, 3703E, or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 321
This figure illustrates how to connect a 16-point or 32-point analog input module and a
9792-610F to the field and another system, such as a DCS (1 of 16 or 32 module points shown).
See Appendix E, Shield Ground for shield ground installation guidelines.
12 AWG,
as short as possible
T+
DCS
* * PS2
Typical point (1 of 16 points shown) DC
Power
Supply
+
Field Xmtr PS1
– (4-20 mA) DC
Power
Supply
Shield Ground
* Return may be connected to an unused A terminal with the JP jumper in place or to a – PS terminal.
Figure 248 Field Wiring for 9792-610F with a 3700, 3700A, 3703E, or 3721 AI Module—Sharing with
Another System
Sharing a transmitter between the Tricon controller and another system may violate restrictions
regarding the segregation of safety and control functions. The sharing capability of this
termination panel should only be used in those applications where these restrictions do not
exist, or can be otherwise mitigated.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
322 Chapter 7 RG 1.180 Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a current input
panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
PS1
+t
IN 32
3.3 kilohms Hi-Ref
IN
Low-Ref
to Mux
other
points
250 Ohms
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
A
PS1
PS2
JP17 * Hi-Ref
32
Low-Ref
* When the 9792-610F panel is used with a 3700A or a 3721 module, do not remove the JP17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the JP jumper may be removed.
Figure 249 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9792-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 323
This is a simplified schematic of a typical 16-point analog input module with a current input
panel (1 of 16 module points shown).
to
spare Mux
PS1
+t
16
IN
3.3 kilohms Hi-Ref
IN Low-Ref
Mux
to
other
points
250 Ohms 1 Amp ADC
16
A
Hi-Ref
Low-Ref
Mux
JP**
1 Amp ADC
PS1 16
JP17 * Hi-Ref
PS2
Low-Ref
* For extended common-mode operation, you must remove the JP17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the JP jumper may be removed.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
324 Chapter 7 RG 1.180 Termination Panels
Specifications
This table describes general specifications for 9783-110F.
Compatible Modules
This table describes analog input modules compatible with 9783-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 325
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1 TB1
EXT TERM TRICON
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ
V
Field
Source
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
326 Chapter 7 RG 1.180 Termination Panels
&7$&
&7$&
TRICONEX
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1 TB1
EXT TERM TRICON
$7(;(0&$,7&
J2 J2
/ /
7400272
SN
J3 J3
L- L-
Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ
V
Field
Source
Figure 251 Field Wiring for 9783-110F with a 3700A, 3703E, or 3721 AI Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 327
Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
voltage input panel (1 of 32 module points shown).
to
spare Mux
Isolation/filtering
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Mux
1 Amp ADC
32
Hi-Ref
Low-Ref
Figure 252 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9783-110F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
328 Chapter 7 RG 1.180 Termination Panels
This is a simplified schematic of a typical 16-point commoned analog input module with a
voltage input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Figure 253 Simplified Schematic of a 3703E Analog Input Module with a 9783-110F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 329
Specifications
This table describes general specifications for 9782-110F.
Compatible Modules
This table describes the analog input module compatible with 9782-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
330 Chapter 7 RG 1.180 Termination Panels
&7$&
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
! TB2
TB1
EXT TERM TRICON
REV B
$7(;(0&$,7&
J2
/
7400272
SN
J3
L-
Typical
unused point
Typical point
RISRLQWVVKRZQ
-
Shield Ground
Figure 254 Field Wiring for 9782-110F with a 3708E Thermocouple Input Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 331
Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).
to
spare Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Mux
1 Amp ADC
16
Hi-Ref
Low-Ref
Figure 255 Simplified Schematic of a 3708E Thermocouple Input Module with a 9782-110F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
332 Chapter 7 RG 1.180 Termination Panels
Specifications
This table describes specifications for 9860-610F.
Compatible Modules
This table describes the analog output module compatible with 9860-610F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 333
'21276(3$5$7(:+(1(1(5*,=('
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
$7(;(0&$2
7400270 C17
C20
C19
REV B
L12
&7$&
C14
C15
SN L15 /
/
L11
L13 L14
L5 C12
L9 L10
L4 C10
L7 L8
C5
L3
C8
C7
C2
C3
L1
L2
!
C35
&
&
C37
C38
C39
C40
C41
C42
C43
TB7 TB8
C44
R2
R1
TB1—TB4
J4
/
C27
C25
C45
L-
J5 P1 P2
PS1
- DC
Load
Power
+ Supply
Figure 256 Field Wiring for 9860-610F with a 3805E or 3805H AO Module or a 2870H HART AO
Interface Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
334 Chapter 7 RG 1.180 Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
an analog output panel (1 of 8 module points shown).
A Loop power
PWRA
Selector
Logic
Current
loopback PWRB
DAC
RTN
B RTN
Selector
Logic Current
loopback
DAC
OUT2
Typical point
C RTN2
Selector
Logic
Current
loopback
DAC
Figure 257 Simplified Schematic of a 3805E or 3805H Analog Output Module with a 9860-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 335
This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with
an analog output panel (1 of 8 module points shown).
A Loop power
PWRA
Selector
Logic
Current
loopback PWRB
DAC
RTN
B RTN
Selector
Logic OUT2
Current
loopback
Typical point
DAC
RTN2
Selector
Logic
Current
loopback
VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER
RS-485 HART
CABLE CONTROLLER
Figure 258 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9860-610F Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
336 Chapter 7 RG 1.180 Termination Panels
Specifications
This table describes specifications for 9794-110F.
Compatible Modules
This table describes pulse input modules compatible with 9794-110F.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 337
&7$&
TRICONEX
$:*
'21276(3$5$7(
WHEN ENERGIZED
as short as possible
J1
!
TB2
TB1
EXT TERM TRICON
REV B
$7(;(0&$,7&
J2
/
7400272
SN
J3
L-
F
Typical point
F– (1 of 8 points shoZn
RT
**
*
* )XQFWLRQDOHDUWKJURXQGTXLHWJURXQGLVUHFRPPHQGHGIRUVKLHOGFRQQHFWLRQV)RUVKLHOGJURXQGLQJLQVWUXFWLRQVVHH$SSHQGL[(
* * :KHQSRVVLEOHLQVWDOODWHUPLQDWLQJUHVLVWRUDVVKRZQ)RUIXUWKHULQIRUPDWLRQVHH7HFKQLFDO$SSOLFDWLRQ1RWH7$1RQWKH
*OREDO&XVWRPHU6XSSRUW*&6FHQWHUZHEVLWH
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
338 Chapter 7 RG 1.180 Termination Panels
Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
pulse input panel (1 of 8 module points shown).
to
spare Comparator
AC coupled A
Counter/ Micro-
Timer Processor
to
other
points
IN1
IN1
Comparator
AC coupled B
Counter/ Micro-
Timer Processor
to
other
points
Comparator
AC coupled
C
Counter/ Micro-
Timer Processor
to
other
points
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8
Fanned-Out Cables
Overview 340
Description of Fanned-Out Cables (9101-010F) 340
Fanned-Out Cables with Digital Input Modules 341
Fanned-Out Cables with Digital Output Modules 346
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
340 Chapter 8 Fanned-Out Cables
Overview
This chapter describes fanned-out cables and how to use them with digital I/O modules.
If you need a fanned-out cable longer than 10 feet, contact the Global Customer Support (GCS)
center, and read Technical Application Note (TAN) number 002, Crosstalk on Digital Circuits.
Note that access to the Global Customer Support (GCS) center website requires registration.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 341
Table 203 32-point Digital Input Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3501E 115 VAC/VDC, non-commoned, isolated, TMR
3501T 115 VAC/VDC, non-commoned, isolated, TMR
3502E 48 VAC/VDC, commoned in groups of 8, TMR with self-test
3503E 24 VAC/VDC, commoned in groups of 8, TMR with self-test
3505E 24 VAC/VDC, low-threshold, commoned in groups of 8, TMR.with self-test
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
342 Chapter 8 Fanned-Out Cables
AC HOT/+DC
1A, slow
Terminal Field
Contact
Block
2A (IN1 + )
to
2E (IN1 – )
backplane
AC NEUTRAL/RETURN
* Two cables are required for 32 points. Each point must be independently wired.
3501E supports commoned and uncommoned configurations.
3502E, 3503E and 3505E support commoned configurations only.
Figure 261 Field Wiring for 9101-010F with a 3501E, 3501T, 3502E, 3503E, or 3505E Module
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 343
Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module without self test
connected to a fanned-out cable (1 of 32 module points shown).
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
IN
IN
Threshold to
Detect Input
Opto-Isolator Mux B
Threshold to
to Detect Input
spare Opto-Isolator Mux C
module
Figure 262 Simplified Schematic of a 3501E or 3501T DI Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
344 Chapter 8 Fanned-Out Cables
This is a simplified schematic of a typical 32-point digital input module with self test connected
to a fanned-out cable (1 of 32 module points shown).
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A
opto-
IN isolated
IN Test A
Threshold to
Detect Input
Opto-Isolator Mux B
Test B
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module
Test C
Figure 263 Simplified Schematic of a 3502E, 3503E, or 3505E DI Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 345
Table 204 64-point Digital Input Module Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3564 24 VDC, commoned, single
Threshold Detect
Opto-Isolator B
C
RTN
Test OFF Relays
to
(opto-isolated)
other
points
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
346 Chapter 8 Fanned-Out Cables
Simplified Schematics
This is a simplified schematic of a typical 64-point digital input module connected to a fanned-
out cable (1 of 64 module points shown).
+ DC
1A, slow
2A (IN1)
Field
to 14C-32C (RTN)
Contact
backplane
2E (IN2)
RETURN
**
* Two cables are required for 64 points.
** Only one RTN connection is required for proper operation of a 64-point digital input module.
Table 205 16-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3601E 115 VAC, non-commoned, opto-isolated, TMR
3603E 120 VDC, commoned, opto-isolated, TMR
3604E 24 VDC, non-commoned, opto-isolated, TMR
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 347
Table 205 16-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3607E 48 VDC, non-commoned, TMR
3623 120 VDC, commoned, supervised, opto-isolated, TMR
3624 24 VDC, commoned, supervised, opto-isolated, self-protected, TMR
You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.
AC HOT/+DC
Terminal
block
2A (PWR1) * Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)
**
***
AC NEUTRAL/RETURN
*
*For all unused points, PWR and RTN must be connected.
**For all modules, one RTN per point is required.
***To prevent missing-load alarm, install a load at each unused point.
Figure 266 Field Wiring for 9101-010F with a 3601E, 3603E, 3604E, 3607E, or 3623 Module
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
348 Chapter 8 Fanned-Out Cables
This figure illustrates how to connect field wiring to a 16-point commoned digital output
module with self-protection using a fanned-out cable.
+DC
Terminal
block
2A (PWR1) Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)
**
*
RETURN
For proper operation, one RTN connection and one PWR connection per point are required.
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 349
Simplified Schematics
This is a simplified schematic of a typical 16-point commoned digital output module connected
to a fanned-out cable (1 of 16 module points shown).
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
to other
B points
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
350 Chapter 8 Fanned-Out Cables
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Figure 269 Simplified Schematic of a 3601E, 3604E, or 3607E DO Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 351
This is a simplified schematic of a typical 16-point commoned supervised digital output module
connected to a fanned-out cable (1 of 16 module points shown).
A Voltage
B Loopback to other
C Detector points
A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry
B
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
Figure 270 Simplified Schematic of a 3623 or 3624 DO Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
352 Chapter 8 Fanned-Out Cables
Table 206 32-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3625/Aa 24 VDC, commoned, supervised/non-supervised, self-protected, TMR
3664 24 VDC, commoned, opto-isolated, self-protected, dual
3674 24 VDC, commoned, opto-isolated, self-protected, dual
a. The 3625A module may be powered from four independent field power sources, but only if the
voltage from those sources is within 5% of the highest voltage supplied. If this restriction is not
followed, the module will still operate but may experience voter faults and generate an alarm.
You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 353
+DC
Terminal
block
2A (PWR1) Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)
**
*
RETURN
Figure 271 Field Wiring for 9101-010F with a 3625 or 3625A Module
For proper operation, one RTN connection and one PWR connection per point are required.
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
354 Chapter 8 Fanned-Out Cables
This figure illustrates how to connect field wiring to a 32-point dual digital output module using
a fanned-out cable.
+DC
Terminal Solenoid,
block relay, etc.
2A (PWR1)
to 2C (LOAD1)
backplane
2E (RTN1)
RETURN
Figure 272 Field Wiring for 9101-010F with a 3664 or 3674 Module
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 355
Simplified Schematics
This is a simplified schematic of a typical 32-point digital output module connected to a fanned-
out cable (1 of 32 module points shown).
RTN1 (2E)
B
Output
Switch
Drive
Circuitry
C A or C
C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector
* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by fanned-out cables.
Figure 273 Simplified Schematic of a 3625 or 3625A DO Module with a Fanned-Out Cable
This is a simplified schematic of a typical 32-point dual digital output module connected to a
fanned-out cable (1 of 32 module points shown).
RTN1 (2E)
A Voted
Drive
B
Output
C Circuitry
A Loopback
B Detector/
C Isolator
to
hot
spare
to other points
Figure 274 Simplified Schematic of a 3664 or 3674 DO Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
356 Chapter 8 Fanned-Out Cables
Table 207 32-point Relay Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3636R Non- commoned, simplex, galvanically-isolated, normally open
3636T Non- commoned, simplex, galvanically-isolated, normally open
You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.
Terminal
block
2A (C1)
to
2E (C1) Contact #1
backplane
Figure 275 Field Wiring for 9101-010F with a 3636R or 3636T Module
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 357
Simplified Schematics
This is a simplified schematic of a typical 32-point relay output module connected to a fanned-
out cable (1 of 32 module points shown).
A to
spare
module
Point
Register
+V +V
2A (C1)
Voted
B Output
Drive
Point Circuitry
Register
Loopback
Detector/
Isolator
2E (C1)
C
Point
Register
Figure 276 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Fanned-Out Cable
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
358 Chapter 8 Fanned-Out Cables
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
A
Re-Keying Connectors
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
360 Appendix A Re-Keying Connectors
Re-Configuring a System
The purpose of keying connectors by module type and voltage is to protect modules from
inadvertent connection to inappropriate voltages. Termination panels are also keyed. If you use
a fanned-out cable, you must key its connector according to this appendix to ensure module
protection. This appendix provides instructions for re-keying the field interface connectors and
fanned-out cables only. For instructions on repositioning slot keys, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
To re-configure an existing system:
Procedure
1 Reposition the slot’s top and bottom keys.
2 Re-key the corresponding male connector on the backplane.
3 Install a replacement for the termination assembly, or re-key the female connector on the
fanned-out cable.
To re-configure an existing system without rear access:
Procedure
1 Reposition the slot’s top and bottom keys.
2 Re-key the female connector on the cable to match the backplane connector. All unused
slots are delivered from the factory keyed Small=1, Large=1.
3 Mark cable as being modified.
4 Install new or replacement termination assembly.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 361
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
362 Appendix A Re-Keying Connectors
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 363
Regarding termination panel 9251-210F: for the termination panel and the end of the cable that
connects to the termination panel, the keying is Large=1, Small=1. For the chassis and the end
of the cable that connects to the chassis, the keying is Large =1, Small=3.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
364 Appendix A Re-Keying Connectors
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 365
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
366 Appendix A Re-Keying Connectors
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Re-Keying a Connector 367
Re-Keying a Connector
This procedure explains how to re-key a connector on the Tricon chassis backplane.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
To avoid shorts that could lead to damage, Schneider Electric recommends removing all power from
the Tricon system before you re-key the backplane connectors.
Procedure
1 Remove the eight screws that hold the Tricon chassis backplane cover, then remove the
cover.
2 Insert nut driver (part #2000236-001) through the backplane opening and loosen the nut
on the large male key.
3 While you hold the nut in place with the nut driver, remove the large male key
(cylindrical in shape) and reposition it to the correct number for your new module. See
diagram below.
4 Tighten the nut for the large male key.
5 Insert nut driver through the backplane opening and loosen the nut on the small male
key.
6 While you hold the nut in place with the nut driver, remove the small male key
(cylindrical in shape) and reposition it to the correct number for your new module. See
diagram below.
7 Tighten the nut for the small male key.
8 Replace the backplane cover and eight screws.
1
2
6
2
3
5
3
key.vsd
4
3
5
3
2
6
1
1
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
368 Appendix A Re-Keying Connectors
Keys are shown in their default position (1), which is also the position for 115 VAC digital input
terminations.
Procedure
1 Hold the connector in your hand, and loosen (but do not remove the two screws that
secure the cable clamp).
2 Remove the four screws on the connector that fasten it to the housing.
3 Pull the connector away from the housing and rotate the connector slightly to expose the
keying nuts.
4 Loosen the nut on the large hexagonal key using the nut driver (part #2000236-001).
5 While holding the nut in place with the nut driver, remove the large key and reposition
it to the correct number.
6 Tighten the large key nut.
7 Loosen the nut on the small hexagonal key.
8 While holding the nut in place with the nut driver, remove the small key and reposition
it to the correct number.
9 Tighten the small key nut.
10 Replace the female connector in its housing by lining up the thumbscrew with the
opening in the top of the housing.
11 Replace the four screws that secure the female connector to the housing.
12 Tighten the two screws that secure the housing to the cable.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
B
Fanned-Out Cable Pinouts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
370 Appendix B Fanned-Out Cable Pinouts
Signal Names
This table provides a list of signal names and pin numbers that you need to know when
connecting fanned-out cables and basic termination panels. The signal names in the table match
the labels on a fanned-out cable. The pin numbers in the table match the pin numbers on the
connector for the fanned-out cable as well as the panel connector on the Tricon chassis
backplane.
The signal names depend on which backplane connector the fanned-out cable is attached to, as
shown next.
Connector 1
L
N
1
NO
C
NC
L
N
Connector 2
2
NO
RC C
NC
POWER A MP B C COM L 2 R L 3 R L 4 R L 5 R L 6 R L 7 R
REMOTE RUN
1 PROGRAM
A PASS PASS PASS
PASS PASS PASS
PASS PASS PASS
STOP FAULT
FAULT FAULT
FAULT FAULT FAULT
FAULT FAULT FAULT
Ñ LOCAL Ñ ACTIVE ACTIVE ACTIVE
ACTIVE ACTIVE ACTIVE
ACTIVE ACTIVE ACTIVE
LOAD/ LOAD/
MAINT1 MAINT1 FUSE FUSE
MAINT1
1 1
MAINT2 MAINT2 MAINT2
1 1 1TX
115/230 VAC 2 2
1RX
2 2
3 3
NET 1
3 3
PASS 4 4
FAULT 5 5
4 4
ALARM 5 5
6 6
TEMP TX
6 6
RX 7 7
BATT LOW
B 8 8
7 7
2TX
2RX
9 9 8 8
10 10
11 11
12 12
13 13
3TX
NET 2 14 14 3RX
POWER MODULE 15 15
MODEL 8310
16 16
TX 17 17
RX 18 18
19 19
115/230 VAC 4TX
20 20 4RX
21 21
PASS
22 22
FAULT
23 23
ALARM
COM RX COM RX COM RX
TEMP 24 24
COM TX COM TX COM TX COMM 9 9
BATT LOW 25 25
I/O RX I/O RX I/O RX TX 10 10
26 26 PRT
RX
C I/O TX I/O TX I/O TX
27 27
11 11
12 12
28 28
13 13
29 29
14 14
30 30
15 15
31 31
16 16
32 32
POWER MODULE EMP EMP EMP NCM
DIGITAL DIGITAL DIGITAL DIGITAL
EICM
MODEL 8310 3006 3006 3006 4329 INPUT INPUT OUTPUT OUTPUT 4119
3501E 3501E 3603B 3603B
D E F G H I J K L M N O P Q R S
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 371
Connector #1
Table 218 Connector Number 1 Pinouts
Connector #1 I/O Modules
Signal 64 Pt 64 Pt 32 Pt DO/ 8 Pt
Pin # RO AI/TC AO PI
Label SDI AI DI 16 Pt SDO SDO
2A AA IN1 IN1 IN1+ PWR1 PWR1 C1 IN1+ OUT1 IN1+
2C KK * * LOAD1 LOAD1 *
2E LL IN2 IN2 IN1– RTN1 RTN1 C1 IN1– RTN1 IN1–
4A z IN3 IN3 IN2+ PWR2 PWR2 C2 IN2+ OUT2 IN2+
4C DD PWR PWR LOAD2 LOAD2 *
4E EE IN4 IN4 IN2– RTN2 RTN2 C2 IN2– RTN2 IN2–
6A p IN5 IN5 IN3+ PWR3 PWR3 C3 IN3+ OUT3 IN3+
6C u * * LOAD3 LOAD3 *
6E v IN6 IN6 IN3– RTN3 RTN3 C3 IN3– RTN3 IN3–
8A h IN7 IN7 IN4+ PWR4 PWR4 C4 IN4+ OUT4 IN4+
8C k PWR PWR LOAD4 LOAD4 *
8E l IN8 IN8 IN4– RTN4 RTN4 C4 IN4– RTN4 IN4–
10A e IN9 IN9 IN5+ PWR5 PWR5 C5 IN5+ OUT5 IN5+
10C a * * LOAD5 LOAD5 *
10E b IN10 IN10 IN5– RTN5 RTN5 C5 IN5– RTN5 IN5–
12A W IN11 IN11 IN6+ PWR6 PWR6 C6 IN6+ OUT6 IN6+
12C R PWR PWR LOAD6 LOAD6 *
12E S IN12 IN12 IN6– RTN6 RTN6 C6 IN6– RTN6 IN6–
14A L IN13 IN13 IN7+ PWR7 PWR7 C7 IN7+ OUT7 IN7+
14C E RTN RTN LOAD7 LOAD7
14E F IN14 IN14 IN7– RTN7 RTN C7 IN7– RTN7 IN7–
16A M IN15 IN15 IN8+ PWR8 PWR8 C8 IN8+ OUT8 IN8+
16C A RTN RTN LOAD8 LOAD8
16E B IN16 IN16 IN8– RTN8 RTN C8 IN8– RTN8 IN8–
18A BB IN17 IN17 IN9+ PWR9 SEC1 C9 IN9+ *
RTN
18C NN RTN LOAD9 FGNDb *
FGNDa
18E MM IN18 IN18 IN9– RTN9 RTN C9 IN9– *
20A CC IN19 IN19 IN10+ PWR10 SEC2 C10 IN10+ *
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
372 Appendix B Fanned-Out Cable Pinouts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 373
* Reserved for Tricon controller internal use. Do not connect for any purpose.
Note CGND is the Tricon chassis ground (protective earth). Pins r, s, X and Y on the panel
connector are not used.
Connector #2
Table 219 Connector Number 2 Pinouts
Connector #2 I/O Modules
Signal 64 Pt 64 Pt 32 Pt
Pin # DO RO
Label SDI AI AI/DI
2A AA IN33 IN33 IN17+ PWR17 C17
2C KK RTN LOAD17
2E LL IN34 IN34 IN17– RTN17 C17
4A z IN35 IN35 IN18+ PWR18 C18
4C DD PWR RTN LOAD18
4E EE IN36 IN36 IN18– RTN18 C18
6A p IN37 IN37 IN19+ PWR19 C19
6C u RTN LOAD19
6E v IN38 IN38 IN19– RTN19 C19
8A h IN39 IN39 IN20+ PWR20 C20
8C k PWR RTN LOAD20
8E l IN40 IN40 IN20– RTN20 C20
10A e IN41 IN41 IN21+ PWR21 C21
10C a RTN LOAD21
10E b IN42 IN42 IN21– RTN21 C21
12A W IN43 IN43 IN22+ PWR22 C22
12C R PWR RTN LOAD22
12E S IN44 IN44 IN22– RTN22 C22
14A L IN45 IN45 IN23+ PWR23 C23
RTN
14C E RTN LOAD23
FGNDa
14E F IN46 IN46 IN23– RTN23 C23
16A M IN47 IN47 IN24+ PWR24 C24
RTN
16C A RTN LOAD24
FGNDa
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
374 Appendix B Fanned-Out Cable Pinouts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 375
Note CGND is the Tricon chassis ground (protective earth). Pins r, s, X and Y on the panel
connector are not used.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
376 Appendix B Fanned-Out Cable Pinouts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
C
Recommended Replacement Parts
This table contains recommended parts that can be used to replace existing Tricon system parts,
or customize a Tricon system.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
378 Appendix C Recommended Replacement Parts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
379
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
380 Appendix C Recommended Replacement Parts
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
D
Panel Dimensions
This figure illustrates the dimensions described in Table 221 Panel Dimensions (page 382).
SN
Width (across DIN rail)
1
2
3
4
5
6
7
8
L+
L+
L–
L–
PS1
PS2
BOTTOM VIEW
Height (out from DIN rail)
1 2 3 4 5 6 7 8
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
382 Appendix D Panel Dimensions
This table describes the dimensions of each external termination panel (ETP).
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
383
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
384 Appendix D Panel Dimensions
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
E
Shield Ground
This appendix shows how to connect a shield to earth. The typical parts shown are available
from Phoenix Contact. See additional installation guidelines in the Planning and Installation
Guide for Tricon 11.5 and Later 11.x Systems.
J1
J1
7 mm
19.4 mm
23.4 mm
23.5 mm
Safety Ground
Bus Bar
26 mm
35.5 mm
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
386 Appendix E Shield Ground
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
F
Panel Labels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
388 Appendix F Panel Labels
Overview
This appendix shows how to apply termination panel labels. Because some modules (32- and
64-point input modules and 32-point output modules) require a two-panel arrangement to
accommodate all points, each standard panel must have a set of labels that indicate the correct
range of points. For instance, a 64-point module requires two 32-point panels: the first panel
connects points 1–32; the second panel connects points 33–64. Panels that are not used in a two-
panel arrangement are labeled at the factory.
Standard panels that require labels include the appropriate labels as loose-piece parts. Since a
panel can be connected as the first or second panel, a set of labels appropriate for either range is
provided with every panel, with a duplicate label for each row of terminals on each terminal
block. Any unused labels can be stored or discarded.
Attach the appropriate labels to each panel as shown in these illustrations.
SN REV A 7400168-
Panel Type
9561-110F DI
9661-110F DO
9662-110F DO
9667-110F DO
F13
F14
F15
F16
F5
F6
F7
F8
9667-310F DO
J1
9668-110F RO
F10
F12
F11
F1
F2
F3
F4
F9
CONTACT
PWR
Labels (for front and back row) Labels (for front and back row)
+1 – +2 – +3 – +4 – +5 – +6 – +7 – +8 – +9 – + 10 – +11 – + 12 – +13 – + 14 – + 15 – + 16 –
First Panel
Labels (for front and back row) Labels (for front and back row)
+ 17 – + 18 – + 19 – + 20 – + 21 – +22 – + 23 – +24 – + 25 – + 26 – +27 – + 28 – +29 – + 30 – + 31 – + 32 –
Second Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned AI/TI Panels 389
SN REV A 7400171-
Panel Type
9763-810F AI
9765-610F TI
9766-210F TI
9766-510F TI
J1
+
+
ñ
ñ
Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
First Panel
Second Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
390 Appendix F Panel Labels
9561-810F DI
9562-810F DI
9563-810F DI
9661-610F DO
CR
1
F2 F4 F6 F8 F10 F12 F14 F16
9661-710F DO
J1
9661-910F DO CR
2
9662-610F DO
9662-810F DO
9667-610F DO
F1 F3 F5 F7 F9 F11 F13 F15
9667-710F DO
9667-810F DO L+
L+
9761-210F AI
9761-410F AI
Lñ
Lñ
9762-210F AI
PS1
PS2
9762-410F AI
First Panel
Second Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned AI/DI Panels 391
SN REV A 7400150-
Panel Type
9565-710F DI
9565-810F DI
9566-710F DI
R10
R12
R14
R16
R18
R20
R22
R24
R26
R28
R30
R32
R2
R4
R6
R8
9566-810F DI
J1
9567-810F DI
CR1
CR2
9760-210F AI
9760-410F AI
R13
R15
R17
R19
R21
R23
R25
R27
R29
R31
R11
R1
R3
R5
R7
R9
PS1
PS2
Labels (for front and back row) Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
First Panel
Labels (for front and back row) Labels (for front and back row)
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Second Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
392 Appendix F Panel Labels
TRICONEX
Panel Type EXT TERM TRICON
$7(;(0&$,',
17
R
SN
AI
R25
9787-110F
18
R1
R
9
R
TB1 TB4
'21276(3$5$7(
5
9790-610F AI
:+(1(1(5*,=('
19
R2
R
10
R
R27
9791-610F AI
20
R3
R
11
R
R28
9795-610F AI
3
21
R4
R
12
R
R29
22
R5
R
13
R
R30
23
5
R
14
!
R
R31
24
R7
R
15
R
R32
R8
J1
5
TB2 TB3 TB5 7%
J2
/
J3
L- P1 P2
First Panel
Second Panel
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point RTD/TC/AI Panels 393
7B47
7B47
7B47
7B47
7B32
7B32
7B32
7B32
7B34
7B34
7B34
7B34
7B34
7B34
7B34
7B34
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
DEVICES
ANALOG
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
ISOLATED
ISOLATED
ISOLATED
ISOLATED
PROCESS
PROCESS
PROCESS
PROCESS
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
ISOLATED
TC INPUT
TC INPUT
TC INPUT
TC INPUT
U1 U2 U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
10
12
13
14
15
16
J2
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
1
2
3
4
5
6
7
8
9
11
1
2
3
4
5
6
7
8
9
11
10
12
13
14
15
16
10
12
13
14
15
16
J3 J4 J5 J6
First Panel
Labels (for front and back row) Labels (for front and back row) Labels (for front and back row) Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Second Panel
Labels (for front and back row) Labels (for front and back row) Labels (for front and back row) Labels (for front and back row)
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
394 Appendix F Panel Labels
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
G
Part Number Cross-Reference
Table 222 identifies the termination panel part number and the cable part number included in
each external termination panel (ETP) kit.
The table includes these types of cables:
• FT4: Ninety-degree cables that meet FT4 flame test ratings. Add “F” at the end of the
ETP kit base model number to obtain the complete model number. For example, 9551-
110F.
• FT4 Z: Zero-degree cables, designed to be used with G-Series Enclosures for Tricon
systems that have front access. Add “F-Z” at the end of the ETP kit base model number
to obtain the complete model number. For example, 9551-110F-Z.
• LSZH: Low Smoke Zero Halogen ninety-degree cables. Kits are not available for these
configurations, the Termination Panel Base Part Number and LSZH Cable must be
ordered separately.
For more information about these cables, see Interface Cables on page 6.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
396 Appendix G Part Number Cross-Reference
Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
397
Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
398 Appendix G Part Number Cross-Reference
Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
H
Minimum Bend Radiuses of Cables
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
400 Appendix H Minimum Bend Radiuses of Cables
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
401
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
402 Appendix H Minimum Bend Radiuses of Cables
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
403
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
404 Appendix H Minimum Bend Radiuses of Cables
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I
Low-Density Chassis I/O Module
Compatibility
Overview 406
Module Upgrades 406
ETP Upgrades for Compatibility with I/O Modules 407
Model 3807 BPAO Compatibility 416
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
406 Appendix I Low-Density Chassis I/O Module Compatibility
Overview
This appendix describes the compatibility of Model 3720, 3721, 3625, and 3625A I/O Modules
with low-density Tricon systems that have been upgraded to v10.2.x or later. This appendix also
describes the external termination kit that you can use to install the Model 3807 Bipolar AO
module in low-density systems that have been upgraded to v10.2.x or later.
To install Model 3720, 3721, 3625, or 3625A I/O Modules in low-density Tricon systems, in most
cases, you must upgrade the termination panels and interface cables, and install a new chassis
interface module. In most instances, you have the option of using RETMA-rail-mount
termination panels or equivalent DIN-rail-mount termination panels.
Upgrade ETP kits are available that include ETPs, cables, and new chassis interface modules.
Some existing ETPs used in low-density systems are compatible with Model 3720, 3721, 3625,
and 3625A I/O Modules. The existing ETP models that are compatible with these I/O modules
are identified in this appendix.
Module Upgrades
This table lists existing I/O modules and identifies the newer I/O modules that they can be
upgraded with in low-density Tricon systems that have been upgraded to v10.2.x or later.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 407
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
408 Appendix I Low-Density Chassis I/O Module Compatibility
Table 225 3700 and 3700A AI Module—Upgrade to 3721 with RETMA-Rail ETP Kits
RETMA-Rail RETMA-Rail ETP Upgrade RETMA-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
2750-2a Current input, 2750-210L 2 x 4000184-510 (cable)
0–5 VDC, 32 pts. 1 x 3000280-500 (interface module)
1 x 3000142-220 (ETP)
2750-8b Voltage input, 2750-810L 2 x 4000184-510 (cable)
0–5 VDC, 32 pts. 1 x 3000280-500 (interface module)
1 x 3000142-280 (ETP)
a. This ETP does not require an upgrade kit for compatibility with Model 3721 AI Modules in low-
density systems; however, if you want to add additional AI points, use the 2750-2L.
b. This ETP does not require an upgrade kit for compatibility with Model 3721 AI Modules in low-
density systems; however, if you want to add additional AI points, use the 2750-8L.
This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3700 and Model 3700A AI Modules in low-density systems
when you are upgrading to the Model 3721 AI Module.
Table 226 3700 and 3700A AI Module—Upgrade to 3721 with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9761-210F Current input, 9761-210FL 2 x 4000182-510 (cable)
0–5 VDC, 1 x 3000280-500 (interface module)
-5–5 VDC, 16 pts.
2 x 3000510-510 (ETP)
9763-810F Voltage input, 9763-810FL 2 x 4000182-510 (cable)
0–5 VDC, 1 x 3000280-500 (interface module)
-5–5 VDC,
0–10 VDC, 16 pts. 2 x 3000580-110 (ETP)
a. The 9764-310FL also is the only upgrade ETP kit available for these obsolete RETMA-rail ETP kit
models: 2790-1, 2790-11, 2790-12, 2790-13, 2790-14, 2790-15, 2790-16, 2790-17, 2790-2, 2790-21, 2790-22,
2790-23, 2790-24, 2790-25, 2790-26, 2790-27, 2790-3T, 2790-4T.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 409
a. This ETP does not require a new kit for compatibility with Model 3720 AI Modules in low-density
systems.
This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3704E AI Modules in low-density systems when you are
upgrading to the Model 3720 AI Module.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
410 Appendix I Low-Density Chassis I/O Module Compatibility
Table 229 3604E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA-Rail RETMA-Rail ETP Upgrade RETMA-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
2652-1 24 VDC, 2652-110L 2 x 4000172-310 (cable)
non-commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000120-310 (ETP)
2652-6 24 VDC, 2652-610L 2 x 4000172-310 (cable)
1x8 commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000120-360 (ETP)
2652-8 24 VDC, 2652-810L 2 x 4000172-310 (cable)
redundant, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000120-380 (ETP)
2661-1 24 VDC, 2661-110L 2 x 4000172-310 (cable)
external relay, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000290-310 (ETP)
2661-8 24 VDC, commoned, 9671-810FLa 2 x 4000186-310 (cable)
interposing relay, 1 x 3000280-300 (interface module)
fused, 16 pts.
1 x 3000290-380 (ETP)
a. This high-density upgrade ETP kit is the only option for compatibility with Model 3625 or 3625A DO
Modules in low-density systems.
When you use the supervisory function of the Model 3625 or 3625A DO Module with the 9671-
810FL or the 2661-110L ETPs, only the ELCO termination cable and the relay coil will be
monitored for field fault detection.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 411
This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3604E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
Table 230 3604E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9662-110F 24 VDC, 9662-110FL 2 x 4000185-310 (cable)
non-commoned, 1 x 3000280-300 (interface module)
fused, 16 pts.
1 x 3000570-310 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)
9671-810F 24 VDC, 9671-810FL 2 x 4000186-310 (cable)
commoned, 1 x 3000280-300 (interface module)
interposing relay,
fused, 16 pts. 1 x 3000290-380 (ETP)
When you use the supervisory function of the Model 3625 or 3625A DO Module with the 9671-
810F or the 9671-810FL ETPs, only the ELCO termination cable and the relay coil will be
monitored for field fault detection.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
412 Appendix I Low-Density Chassis I/O Module Compatibility
Table 231 3614E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA- Upgrade
RETMA-Rail ETP
Rail ETP RETMA-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
2652-5 24 VDC, 2652-510L0 2 x 4000174-310 (cable) Use this kit if
1x16 1 x 3000280-300 (interface module) you have four
commoned, eight-point ETPs
8 pts.
2652-510L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-350 (ETP)
2652-510L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-350 (ETP)
2652-510L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-350 (ETP)
2652-510L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-350 (ETP)
2652-9 24 VDC, 2652-910L0 2 x 4000174-310 (cable) Use this kit if
redundant, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-910L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-390 (ETP)
2652-910L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-390 (ETP)
2652-910L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-390 (ETP)
2652-910L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-390 (ETP)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 413
This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3614E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.
Table 232 3614E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail Upgrade
DIN-Rail ETP
ETP DIN-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
9662-910F 24 VDC, 9662-910FL0 2 x 4000173-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
fused, 8 pts. eight-point ETPs
9662-910FL1 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000550-380 (ETP)
9662-910FL2 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000550-380 (ETP)
9662-910FL3 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000550-380 (ETP)
9662-910FL4 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000550-380 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)
If connected, you must disconnect 5 V shorted-load detection power (PS3) for the ETP to
function correctly.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
414 Appendix I Low-Density Chassis I/O Module Compatibility
Table 233 3615E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA- Upgrade
RETMA-Rail ETP
Rail ETP RETMA-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
2652-55 24 VDC, 1x16 2652-55L0 2 x 4000174-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-55L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-355 (ETP)
2652-55L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-355 (ETP)
2652-55L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-355 (ETP)
2652-55L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-355 (ETP)
2652-95 24 VDC, 2652-95L0 2 x 4000174-310 (cable) Use this kit if
redundant, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-95L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-395 (ETP)
2652-95L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-395 (ETP)
2652-95L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-395 (ETP)
2652-95L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-395 (ETP)
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 415
This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3615E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.
Table 234 3615E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail Upgrade
DIN-Rail ETP
ETP DIN-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
9662-710F 24 VDC, 9662-710FL0 2 x 4000173-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
low-power, eight-point ETPs
fused, 8 pts.
9662-710FL1 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000550-390 (ETP)
9662-710FL2 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000550-390 (ETP)
9662-710FL3 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000550-390 (ETP)
9662-710FL4 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000550-390 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
2 x 3000410-360 (ETP)
If connected, you must disconnect 5 V shorted-load detection power (PS3) for the ETP to
function correctly.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
416 Appendix I Low-Density Chassis I/O Module Compatibility
Table 235 3624 DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)
This kit contains nonincendive circuits and can be used in hazardous locations. When using the
Model 3807 Bipolar AO module in hazardous locations, you must install ETPs and associated
field wiring according to the requirements of the prevailing local electrical codes and the
instructions in Chapter 3 of the Planning and Installation Guide for Tricon 11.5 and Later 11.x
Systems.
In Europe, the ETP in this kit is in full compliance with the ATEX Directive and is suitable for
use in Zone 2 Group IIB hazardous locations per the requirements of EN 60079-15, Electrical
apparatus for explosive gas atmospheres - Part 15: Type protection “n”.
In North America, the ETP in this kit is suitable for use in Class 1, Division 2 Groups C and D
hazardous locations per the requirements of ANSI/ISA S12.12.01-2000, Nonincendive Electrical
Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous
(Classified) Locations.
This kit can also be used for applications in non-hazardous (non-ATEX) locations.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
J
Using V8 ETPs with v11 Systems
Selected version 8 “low-density” external termination panels (ETPs) can be used with version
11 systems as identified in Table 236 V8 ETPs Compatible with v11 Systems (page 417). The
cables and ETPs must be ordered separately. In some cases, 2 cables must be ordered per ETP.
Each ETP kit includes 1 or 2 external termination panels on a 19 inch RETMA compatible plate.
The V8 User’s Guide for Field Termination should be used for all ETP application and field
wiring information.
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
418 Appendix J Using V8 ETPs with v11 Systems
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
419
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
420 Appendix J Using V8 ETPs with v11 Systems
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Schneider Electric Systems USA, Inc.
38 Neponset Avenue
Foxborough, MA 02035-2037
United States of America
www.schneider-electric.com