Triconex™

Tricon™ 11.5 and Later 11.x Systems


Field Terminations Guide

*9720159-001* *2.0*

9720159-001, Rev 2.0


March 2021

https://www.se.com
Information in this document is subject to change without notice. Companies, names and data used in examples
herein are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form
or by any means, electronic or mechanical, for any purpose, without the express written permission of Schneider
Electric Systems USA, Inc.

© 2004–2021 Schneider Electric. All rights reserved.

Schneider Electric, EcoStruxure, Triconex, Tricon, and TriStation are trademarks and the property of Schneider
Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective owners.

Original Instructions
The original English version of this document has been verified by Schneider Electric. It is the only version of the
document that contains “original instructions.”

Translated versions of this document must bear the words “translation of the original instructions,” in the translated
language, and must be accompanied by the original English instructions.
Contents

Preface xi
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
We Welcome Your Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi

Chapter 1 Introduction to Field Terminations 1


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
External Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Basic Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
RG 1.180 Termination Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hazardous Location (Nonincendive) Termination Panels . . . . . . . . . . . . . . . . . . . . . . 4
Termination Panels with Interposing Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bypass Panel for Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Termination Panel with RTD/TC/AI Input Signal Conditioning . . . . . . . . . . . . . . . . 5
Termination Panel 9251-210F for Digital Output Module 3603B . . . . . . . . . . . . . . . . . 5
Termination Panel 9863-710F for Analog Output Module 3806E . . . . . . . . . . . . . . . . 5
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Interface Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fanned-Out Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Special Cables (Relay Loopback). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 2 Field Termination Options and Installation 10


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Determining Field Termination Options by Module Model Number. . . . . . . . . . . . . . . . . 11
Determining Field Termination Options by Module Type . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Digital Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pulse Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Pulse Totalizer Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Supervised Digital Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Supervised/Non-Supervised Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . 18
Dual Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Relay Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermocouple Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Analog Output Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
HART Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
iv Contents

Installation and Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23


Installing a Termination Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Removing or Replacing a Termination Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Installing a Fanned-Out Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Removing or Replacing a Fanned-Out Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Chapter 3 Digital Input Termination Panels 33


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
16-Point Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9561-810F (115 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9562-810F (48 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
9563-810F (24 V, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
9563-910F (24 V, commoned, resistor protected, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . 43
32-Point Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
9565-810F (48 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
9566-710F (24 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9566-810F (24 VDC, commoned, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
16-Point Non-Commoned Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
9561-110F (115 V, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Basic Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
9551-110F (115 V, basic, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9552-610F (48 V, basic, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9553-610F (24 V, basic, 16/32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
9750-310F (24 VDC, basic, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
9750-410F (48 VDC, basic, 32 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Pulse Input and Pulse Totalizer Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
9753-110F (8 PI pts./16 PTI pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Bypass Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
BP9228-010F (24 V, bypass, 32 pts., for 32 pt. modules) . . . . . . . . . . . . . . . . . . . . . . . 78
BP9229-010F (24 V, bypass, 32 pts., for 64 pt. modules) . . . . . . . . . . . . . . . . . . . . . . . 80

Chapter 4 Digital Output Termination Panels 83


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
8-Point Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9661-510F (115 VAC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9661-810F (120 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9662-710F (24 VDC low-power, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9662-910F (24 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9667-910F (48 VDC, commoned, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
16-Point Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9661-610F (115 VAC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9661-910F (120 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9662-610F (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9662-810F (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Contents v

9663-610F (115 VAC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114


9664-810F (120 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
9667-810F (48 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
16-Point Non-Commoned Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
9251-210F (120 VDC, non-commoned, 16 pts., 3603B module). . . . . . . . . . . . . . . . . 124
9661-110F (115 VAC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
9662-110F (24 VDC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
9664-110F (115 VAC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
9667-110F (48 VDC, non-commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
9668-110F (non-commoned relay output, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Basic Digital Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
9651-110F (basic digital/relay output, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
9652-610F (48 VDC, basic, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
9653-610F (24 VDC, basic, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Commoned Interposing Relay Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
9670-610F (115 VAC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . 152
9671-810F (24 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . 155
9672-810F (48 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . . 160
9673-810F (120 VDC, commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . . . . . 163
Non-Commoned Interposing Relay Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
9670-110F (115 VAC, non-commoned interposing relay, 16 pts.). . . . . . . . . . . . . . . 167

Chapter 5 Analog Input and Analog Output Termination Panels 171


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
16-Point Current Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
9761-210F (current input, 0–5 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
9761-410F (current input, 0–10 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
9762-210F (current input, 0–5 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
9762-410F (current input, 0–10 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
9771-210F (current input, 0–5 VDC, user configurable, 16 pts.) . . . . . . . . . . . . . . . . 186
32-Point Current Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
9750-210F (current input, 0–5 VDC, basic, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
9760-210F (current input, 0–5 VDC, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
9760-410F (current input, 0–10 VDC, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
9765-210F (3-wire current input, 0–5 VDC, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Thermocouple Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
9765-610F (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
9766-210F (TC input, upscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
9766-510F (TC input, downscale, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Voltage Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
9750-810F (0–5 VDC/0–10 VDC voltage input, basic, 32 pts.) . . . . . . . . . . . . . . . . . 213
9753-110F (0–5 VDC/0–10 VDC voltage input, basic, 16 pts.) . . . . . . . . . . . . . . . . . 215
9763-810F (0–5 VDC/0–10 VDC voltage input, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . 219
RTD/TC/AI Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
vi Contents

9764-310F (RTD/TC/AI input, 0–5 VDC, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 224


Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
9863-710F (3806E module, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
9853-610F (current output, basic, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
9881-810F (3807 module, 4 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246

Chapter 6 Hazardous Location (Nonincendive) Termination Panels 249


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Field Wiring in Hazardous Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Cable and Load Parameters (Entity Parameters) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Electrical Code Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Current Limiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Grounding and Installation Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Ground Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Analog Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
9791-610F (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
9787-110F (0-5 VDC voltage input, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
9785-610F (TC input, downscale, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
9784-610F (TC input, upscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
9786-110F (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
9789-610F (4-20 mA, high-density, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
9861-610F (3805E/H module, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
9871-810F (3807 module, 4 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Digital Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
9572-610F (24 VDC, commoned, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
9570-610F (24 VDC, high-density, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
9571-610F (24 VDC, fail-safe, 32 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Digital Output Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
9671-610F (24 VDC, commoned, supervised, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . 296
Pulse Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
9793-110F (pulse input, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302

Chapter 7 RG 1.180 Termination Panels 307


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
Analog Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308
9790-610F (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
9795-610F (4-20 mA, 0–5 VDC, 16 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
9792-610F (4-20 mA, 0-5 VDC, 16 pts., user-configurable, 16 VDC–56 VDC field) 318
9783-110F (0-5 VDC voltage input, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
9782-110F (TC input, upscale/downscale, 16 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . 328
Analog Output Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Contents vii

9860-610F (3805E/H module, 8 pts.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331


Pulse Input Term Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
9794-110F (pulse input, 8 pts.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336
RTD/TC/AI Input Term Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338

Chapter 8 Fanned-Out Cables 339


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Description of Fanned-Out Cables (9101-010F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Fanned-Out Cables with Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Connecting 32-Point Digital Input Modules to Fanned-Out Cables . . . . . . . . . . . . 341
Connecting 64-Point Digital Input Modules to Fanned-Out Cables . . . . . . . . . . . . 345
Fanned-Out Cables with Digital Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Connecting 16-Point Digital Output Modules to Fanned-Out Cables. . . . . . . . . . . 346
Connecting 32-Point Digital Output Modules to Fanned-Out Cables. . . . . . . . . . . 352
Connecting 32-Point Relay Output Modules to Fanned-Out Cables. . . . . . . . . . . . 356

Appendix A Re-Keying Connectors 359


Re-Configuring a System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
I/O Connector Key Positions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
Re-Keying a Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367
Re-Keying a Fanned-Out Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368

Appendix B Fanned-Out Cable Pinouts 369


Signal Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Connector #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
Connector #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373

Appendix C Recommended Replacement Parts 377

Appendix D Panel Dimensions 381

Appendix E Shield Ground 385

Appendix F Panel Labels 387


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
16-Point Non-Commoned DI/DO/RO Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
16-Point Non-Commoned AI/TI Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
16-Point Commoned AI/DI/DO Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
32-Point Commoned AI/DI Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
16-Point Commoned AI ATEX/RG 1.180 Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
16-Point RTD/TC/AI Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393

Appendix G Part Number Cross-Reference 395

Appendix H Minimum Bend Radiuses of Cables 399

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
viii Contents

Appendix I Low-Density Chassis I/O Module Compatibility 405


Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
Module Upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406
ETP Upgrades for Compatibility with I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
3700 and 3700A AI Module ETP Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
3704E AI Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
3604E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410
3614E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
3615E DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
3624 DO Module ETP Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
Model 3807 BPAO Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416

Appendix J Using V8 ETPs with v11 Systems 417

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ix

Safety Information

Important Information
Read these instructions carefully and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may
appear throughout this manual or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.

This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.

NOTICE
NOTICE is used to address practices not related to physical injury.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction, installation, and
operation of electrical equipment and has received safety training to recognize and avoid the hazards
involved.
x

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARCH FLASH

• Use appropriate personal protective equipment (PPE) and follow safe electrical work practices.
See NFPA 70E or CSA Z462.
• This equipment must only be installed and serviced by qualified electrical personnel.
Failure to follow these instructions will result in death or serious injury.

WARNING
UNINTENDED EQUIPMENT OPERATION

• Only allow persons with expertise and training in Triconex systems and ISA 84/IEC 61511 to pro-
gram, install, alter, and apply this product.
• Follow all local and national safety codes and standards.
• Follow the recommendations provided in the Triconex System Security Reference Guide, available
on the Global Customer Support website.
• Validate the control program with the installed safety system according to ISA 84/IEC 61511.
Failure to follow these instructions can result in death, serious injury, environmental damage, or
equipment damage.
Preface

This guide includes information on external termination products for EcoStruxure™ Triconex™
Tricon™ 11.5 and later 11.x systems.

Related Documents
• Planning and Installation Guide for Tricon 11.5 and Later 11.x Systems
• Safety Considerations Guide for Tricon 11.5 and Later 11.x Systems
• TriStation 1131 Developer’s Guide

Technical Support
Customers in the U.S. and Canada can obtain technical support from the Global Customer
Support (GCS) center at the website listed below. International customers should contact their
regional support center.
https://pasupport.schneider-electric.com/ (registration required)

We Welcome Your Comments


To help us improve future versions of Triconex documentation, we want to know about any
corrections, clarifications, or further information you would find useful.
Email us at:
[email protected]
This email address is only for documentation feedback. If you have a technical problem or
question, please contact the Global Customer Support (GCS) center.
Thank you for your feedback.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
xii Preface

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
1
Introduction to Field Terminations

Overview 2
External Termination Panels 2
Cables 6

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
2 Chapter 1 Introduction to Field Terminations

Overview
This chapter introduces the Triconex external field termination products for the Tricon system.
All cables and termination panels are built to withstand harsh industrial environments. The
environmental specifications for components used on these products are the same as for a
Tricon chassis. For more information, see the Planning and Installation Guide for Tricon 11.5 and
Later 11.x Systems.

External Termination Panels


An external termination panel (ETP) is an electrically-passive printed circuit board (PCB) to
which field wiring is easily attached. A panel connector, terminal blocks, and optional
components are mounted to the PCB and enclosed in a DIN-rail compatible plastic housing. A
termination panel and associated cable pass input signals from the field directly to an input
module, or pass output signals from an output module directly to field wiring. This
arrangement permits the removal or replacement of I/O modules without disturbing field
wiring.
Standard termination panels are best for remote marshaling of field wiring where maximum
flexibility, high density and simple maintenance is desired. Standard termination panels allow
you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from a Tricon
chassis.
A standard termination panel consists of a PCB with all necessary components—such as two-
piece terminal blocks, resistors, fuses and blown-fuse indicators—mounted on a DIN-rail
compatible plastic housing. The housing snaps into mounting rails in accordance with
DIN 50 22.
Compression terminals on the standard panel are designed for use with 24- to 12-gauge (0.3
mm2 to 2.1 mm2) wiring. Some panels have an optional current-limiting series resistor, others
have a fuse with a blown-fuse indicator, to protect the field wiring and field device.
Standard termination panels are pre-configured for a specific application. For instance,
commoned standard termination panels can be ordered with commoned power-and-return, or
redundant DC power configurations with a diode-ORing. The thermocouple input termination
panel provides cold-junction temperature sensors and can be ordered with upscale, downscale,
or programmable burnout detection. A standard termination panel for analog voltage inputs
provides commoned or non-commoned signal returns, while the current-mode version has a
precision resistor at each input point to convert current to voltage.
Each standard termination panel is packaged with a matched interface cable that connects the
panel to the backplane of a Tricon chassis. A female connector at one end of the cable is keyed
to match the male connector on the Tricon chassis backplane. A male connector on the other end
of the cable attaches to the standard termination panel.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
External Termination Panels 3

In addition to standard termination panels, there are other types of termination panels,
including:
• Basic termination panels
• Hazardous location (nonincendive) termination panels
• RG 1.180 Termination Panels
• Termination panels with interposing relays
• Bypass panels for digital inputs
• Termination panels with RTD/TC/AI input signal conditioning
• Termination panels for 3603B digital output modules
• Termination panels for 3806E analog output modules

Basic Termination Panels


Basic termination panels are a low-cost means of connecting field wiring to a Tricon controller.
Basic termination panels allow you to marshal field signals in a separate enclosure up to 99 feet
(30 meters) from a Tricon chassis.
A basic termination panel consists of a PCB—with panel connector and terminal blocks—
mounted on a DIN rail-compatible plastic housing. The housing snaps onto mounting rails in
accordance with DIN 50 022. Current-to-voltage conversion resistors are also mounted on
analog input panels configured for current input. You must provide any other components
required for your application.
The panel connector and terminal blocks are directly interconnected via the PCB. The
compression terminals on the terminal blocks are designed for use with 24- to 12-gauge (0.3
mm2 to 2.1 mm2) wiring.
Refer to Appendix B, Fanned-Out Cable Pinouts for signal labels and connector pin numbers.
Each signal label indicates the corresponding screw terminal on the termination panel. The
panel connector’s pin numbers match those on the Tricon chassis backplane’s connector.
A basic termination panel is packaged with a cable that connects between a Tricon chassis
backplane and the basic termination panel. A female connector on one end of the cable is keyed
to match the male connector on the Tricon chassis backplane. A male connector on the opposite
end of the cable is keyed to match the male connector on the termination panel.
Basic termination panels are available in these configurations:
• Digital input panels
• Digital output panels
• Relay output panels
• Analog input panels
• Analog output panels
• Pulse input panels
• Pulse totalizer input panels

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
4 Chapter 1 Introduction to Field Terminations

RG 1.180 Termination Panels


RG 1.180 termination panels are suitable for use in applications that need to meet the
requirements of Regulatory Guide 1.180, “Guidelines for Evaluating Electromagnetic and
Radio-Frequency Interference in Safety-Related Instrumentation and Control Systems, Revision
1” published by the U.S. Nuclear Regulatory Commission.

Hazardous Location (Nonincendive) Termination Panels


Hazardous location (nonincendive) termination panels are suitable for use in Zone 2, and Class
1, Division 2 field circuits. These panels contain extra circuitry designed to limit power available
to the field terminals and have been examined and certified by TÜV Rheinland as being
nonincendive. This guarantees that if the field wires are accidentally opened, shorted, or
grounded, and the Tricon controller is operating normally, the wiring and attached devices will
not release sufficient energy to cause ignition in the specified flammable atmosphere.

Termination Panels with Interposing Relays


Termination panels with interposing relays can be used with most digital output modules and
are recommended for these applications:
• Load currents greater than 2 amps
• Field voltages greater than 115 VAC
• Voltage-level conversions
• Motor-starter circuit compatibility
Interposing relay panels are available in these configurations:
• 16-point commoned
• 16-point non-commoned
The digital outputs of the interposing relays are not fault-tolerant. However, each relay
provides an auxiliary contact that can be fed into a digital input to send a loopback signal to the
control program. A user-written loopback check in the control program can ensure that the relay
has achieved its commanded state. The loopback cable must be ordered separately.
Each interposing relay panel provides the capability to common power and return through a
factory-mounted bus-bar arrangement.
Each interposing relay panel consists of:
• A 7 in x 19 in (18 cm x 48 cm) rack-mountable panel with terminals for 16 digital
outputs and 16 digital inputs.
• Two ELCO connectors mounted on the panel for connecting to digital input modules
using digital input cables 9141-010F, 9142-010F, or 9143-010F.
• An EIA standard RS-310-C plate on which the termination panel is mounted.
• A digital output module and a cable compatible with the selected coil voltage.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
External Termination Panels 5

Bypass Panel for Digital Inputs


Bypass termination panels can be used to connect digital inputs using a bank of 32 pre-wired
switches. Bypass panels have a master keyswitch and terminals for redundant +24 VDC power
sources. Each input point contains an ON status indicator and can be energized only if the
master keyswitch is ON and the corresponding point switch is ON. Each point has a location for
a user-definable label.
Each bypass termination panel comes with one or two 10-foot (3-meter) cables for connecting
the termination panel to a Tricon chassis backplane.

Termination Panel with RTD/TC/AI Input Signal Conditioning


Termination panels which use industry-standard analog signal conditioners provide a flexible,
user-configurable interface to resistive thermal devices (RTDs), thermocouples, and 4-20 mA
transmitters. Each termination panel supports 16 points and each analog module can support
up to 2 panels. These termination panels are compatible with any signal conditioners in the 1 to
5 volt output range. For example, the 7B series of signal conditioners from Analog Devices are
known to work well.

Termination Panel 9251-210F for Digital Output Module 3603B


The special 16-point non-commoned digital output termination panel 9251-210F is required for
use with the 16-point non-commoned digital output module 3603B.

Termination Panel 9863-710F for Analog Output Module 3806E


The special analog output termination panel 9863-710F, with buffered loopback signals, is
available for use with the high-current analog output module 3806E.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
6 Chapter 1 Introduction to Field Terminations

Cables
Three types of cables can be used with the Tricon controller:
• Interface Cables
• Fanned-Out Cables
• Special Cables (Relay Loopback)
You can order standard Triconex interface cables and I/O bus cables that meet flame test ratings
as described in this table.

Cable Rating
Interface cables FT4 Vertical Flame Test-Cables in Cable
(connect external termination panels to I/O modules) Trays per C.S.A. C22.2 No. 0.3-92 Para 4.11.4a

I/O bus cables FT6 Horizontal Flame & Smoke Test-per


(connect chassis) C.S.A. C22.2 No. 0.3-92 Appendix Bb

a. Cables will be marked with FT4 or CMG rating, but they all actually meet the more stringent FT4
rating.
b. Cables will be marked with FT6 or CMR rating, but they all actually meet the more stringent FT6
rating.

The above cables may also be ordered as Low Smoke Zero Halogen (LSZH) cables. These
equivalent cables are made of XLPE (cross-linked polyethylene), which is non-halogenated and
flame-retardant, providing fire safety characteristics of low smoke, low toxicity, and low
corrosion in applications where the protection of people and equipment from toxic and
corrosive gases is critical. These cables are certified to a series of IEC60754 and IEC60332
standards that define emissions levels.

Interface Cables
Interface cables are packaged with all external termination panels. Each interface cable has a
female connector on one end for connection to the male connector on a Tricon chassis backplane.
The opposite end has a keyed male connector for connection to a termination panel.
There are two types of interface cables: ninety-degree cables that exit ninety degrees from the
back cover of the female connector, and zero-degree cables that exit zero degrees (straight) from
the back cover of the female connector. LSZH cables are available as ninety-degree cables only.
Zero-degree cables are designed to be used with G-Series Enclosures for Tricon controllers, that
have front access. For more information on G-Series Enclosures for Tricon Systems, see the
G-Series Enclosures Product Specification Sheet, PSS Number: PSS 21H-2X8 B3, on the Global
Customer Support (GCS) center website at https://pasupport.schneider-electric.com.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Cables 7

Figure 1 Ninety-Degree (Standard) Interface Cable

Figure 2 Zero-Degree (Front Entry) Interface Cable

External termination panel model numbers that end with a “Z” contain zero-degree interface
cables. Model numbers for ninety-degree configurations are referenced throughout this guide.
It is implied that where a model number is referenced for a ninety-degree configuration, a zero-
degree configuration is also available. For cable part numbers, see Table 222 Part Number
Cross-Reference—Tricon ETPs (page 395).
Although the standard length of all interface cables is 10 feet (3 meters), you may order any
length cable up to 90 feet (27.4 meters) in 10-foot increments using the last two digits of the
termination panel’s model number to specify length in feet. For example, specify 9xxx-x50F if
you want a 50-foot (15 meter) cable instead of the standard 10-foot (3-meter) cable.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8 Chapter 1 Introduction to Field Terminations

Fanned-Out Cables
Fanned-out cables are a lower-cost alternative to using external termination panels. Fanned-out
cables allow you to marshal field signals in a separate enclosure up to 99 feet (30 meters) from
a Tricon chassis. One end of a fanned-out cable has a female connector that connects to a Tricon
chassis backplane. The other end of the cable contains 50 fanned-out leads, each individually
labeled with its corresponding connector pin number.
Each fanned-out cable has the following characteristics:
• PVC outer covering
• 56-pin connector at one end
• 50 stranded, stripped, tinned and labeled 22-gauge leads at opposite end
Fanned-out cables should only be used with digital input and digital output modules. They are
not certified for use with analog signals. Contact the Global Customer Support (GCS) center if
you need a fanned-out cable for handling analog signals.
Although the normal length of all fanned-out cables is 10 feet (3 meters), any length cable can
be ordered up to 90 feet (27.4 meters) in 10-foot increments, using the last two digits of the cable
model number to specify the length in feet. For example, the model number 9101-050F specifies
a 50-foot cable instead of the normal 10-foot cable.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Cables 9

Special Cables (Relay Loopback)


If your application requires a special cable, it must be ordered separately. For example, if you
want to verify relay activation on a relay termination panel using a digital output module, you
must order a relay loopback cable to connect between the relay termination panel and a digital
input module. Currently, the only special cable available is the relay loopback cable (914x-010F).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
2
Field Termination Options and
Installation

Overview 11
Determining Field Termination Options by Module Model Number 11
Determining Field Termination Options by Module Type 15
Installation and Removal 23

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Overview
This chapter provides information for determining field termination options using module model numbers or
module types, and it describes how to install and remove termination panels and fanned-out cables.

Determining Field Termination Options by Module Model Number


This table identifies which termination products you can use with a given I/O module. Match your module model
number in the left column to termination options on the right.

Table 1 Termination Product Options (Listed by Module Model Number)


Module Commoned Non-Common. Basic Nonincendive RG 1.180 Fanned-out Bypass ERT Loop-Back
Module Description
Model # Term Panels Term Panels Term Panels Term Panels Term Panels Cables Panels Cables/Panels

3501E DI, 115 VAC/VDC, 32 pts. 9561-810F 9561-110F 9551-110F n/a n/a 9101-010F n/a 9141-010F
3501T

3502E DI, 48 VAC/VDC, 32 pts. 9562-810F n/a 9552-610F n/a n/a 9101-010F n/a 9142-010F

3503E DI, 24 VAC/VDC, 32 pts. 9563-810F n/a 9553-610F 9572-610F n/a 9101-010F BP9228-010F 9143-010F
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems

9563-910F

3504E DI, 24/48 VDC, 9566-810F, 24V n/a 9750-310F, 24V 9570-610F, 24V n/a n/a BP9229-010F n/a
non-isolated, 64 pts. 9565-810F, 48V 9750-410F, 48V n/a

3505E DI, 24 VDC, low threshold, 9563-810F n/a 9553-610F 9572-610F n/a 9101-010F BP9228-010F 9143-010F
32 pts. 9563-910F

3510 PI, 20-20,000 Hz, 8 pts. n/a n/a 9753-110F n/a n/a n/a n/a n/a

3511 PI, 20-20,000 Hz, 8 pts. n/a n/a 9753-110F 9793-110F 9794-110F n/a n/a n/a

3515 Pulse totalizer, 24 VDC, n/a n/a 9753-110F 9572-610F n/a n/a n/a n/a
32 pts.

3564 DI, 24 VDC, single, 64 pts. 9566-710F n/a 9553-610F 9571-610F n/a 9101-010F n/a n/a

3601E DO, 115 VAC, 16 pts. 9661-610F 9661-110F 9651-110F n/a n/a 9101-010F n/a 9670-110F
9663-610F 9664-110F 9670-610F

3601T DO, 115 VAC, 16 pts. 9663-610F 9664-110F n/a n/a n/a n/a n/a n/a

3603B DO, 120 VDC, 16 pts. n/a 9251–210 n/a n/a n/a n/a n/a n/a

Overview
11
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems

12
Chapter 2
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module Commoned Non-Common. Basic Nonincendive RG 1.180 Fanned-out Bypass ERT Loop-Back
Module Description
Model # Term Panels Term Panels Term Panels Term Panels Term Panels Cables Panels Cables/Panels

3603E DO, 120 VDC, 16 pts. 9661-910Fa n/a 9651-110F n/a n/a 9101-010F n/a 9673-810Fa

Field Termination Options and Installation


9664-810Fa

3603T DO, 120 VDC, 16 pts. 9664-810Fa n/a n/a n/a n/a n/a n/a 9673-810Fa

3604E DO, 24 VDC, 16 pts. 9662-810F 9662-110F 9653-610F 9671-610F n/a 9101-010F n/a 9671-810F

3607E DO, 48 VDC, 16 pts. 9667-810F 9667-110F 9652-610F n/a n/a 9101-010F n/a 9672-810F

3611E DO, 115 VAC, 8 pts. 9661-510F n/a n/a n/a n/a n/a n/a n/a

3613E DO, 120 VDC, 8 pts. 9661-810F n/a n/a n/a n/a n/a n/a n/a

3614E DO, 24 VDC, 8 pts. 9662-910F n/a n/a n/a n/a n/a n/a n/a

3615E DO, 24 VDC, low power, 9662-710F n/a n/a n/a n/a n/a n/a n/a
8 pts.

3617E DO, 48 VDC, 8 pts. 9667-910F n/a n/a n/a n/a n/a n/a n/a

3623 DO, 120 VDC, 16 pts. 9661-910F n/a 9651-110F n/a n/a 9101-010F n/a n/a

3623T DO, 120 VDC, 16 pts. 9664-810F n/a n/a n/a n/a n/a n/a n/a

3624 DO, 24 VDC, self-protected, 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a n/a
16 pts.

3625 DO, 24 VDC, self-protected, 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
3625A 32 pts.

3636R Relay output n/a 9668-110F 9651-110F n/a n/a 9101-010F n/a n/a
3636T (non-triplicated), 32 pts.

3664 Dual DO, 24 VDC, self- 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
protected, 32 pts.

3674 Dual DO, 24 VDC, self- 9662-610F n/a 9653-610F 9671-610F n/a 9101-010F n/a 9671-810Fb
protected, 32 pts.

3805E AO, 4–20 mA, 8 pts. n/a n/a 9853-610F 9861-610F 9860-610F n/a n/a n/a
3805H

2870H AO HART Interface n/a n/a 9853-610F 9861-610F 9860-610F n/a n/a n/a

3806E AO, 6 4–20 mA outputs, n/a n/a 9863-710F n/a n/a n/a n/a n/a
2 20–320 mA outputs (special panel)

3807 AO, 4 bipolar -60 to 60 mA 9881-810F n/a n/a 9871-810F n/a n/a n/a n/a
outputs
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module Basic Term Nonincendive RG 1.180 Fanned-out Bypass ERT Loop-Back
Module Description Upscale Downscale
Model # Panels Term Panels Term Panels Cables Panels Cables/Panels

3706A Thermocouple input, type J, 9766-210F 9766-510F n/a 9784-610F, n/a n/a n/a n/a
K, T, differential, 32 pts. upscale
9785-610F,
downscale

3708E Thermocouple input, type 9765-610F 9765-610F n/a 9786-110F 9782-110F n/a n/a n/a
E, J, K, T, isolated, 16 pts.

Module 3-Wire 2-Wire Nonincendive RG 1.180


Module Description Voltage Basic RTD/TC/AI
Model # 4-20 mA 4-20 mA Term Panels Term Panels

3700 AI, 0–5 VDC, differential, n/a 9763-810F 9761-210F, 9791-610F, 9790-610F, 9753-110F, 0–5 V 9764-310Fc
3700A 32 pts. 0–5 V current input current input
9771-210F, 9787-110F, 9792-610F, 4-20
0–5 V voltage input mA, 0-5 V,
16 VDC–56 VDC
field
9783-110F,
voltage input

Determining Field Termination Options by Module Model Number


9764-310F,
RTD/TC/AI
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems

inputc

2770H AI HART Interface n/a n/a 9761-210F, 9791-610F, 9790-610F, n/a n/a
0–5 V current input current input
9771-210F,
0–5 V

3701 AI, 0–10 VDC, differential, n/a 9763-810F 9761-410F n/a n/a 9753-110F, 0–10 V n/a
32 pts.

3703Ed AI, 0–5/0–10 VDC, isolated, n/a 9763-810F 9762-210F, 9791-610F, 9790-610F, 9753-110F, 0–5/0–10 V n/a
16 pts. 0–5 V current input 4–20 mA, 0–5 V
9762-410F, 9787-110F, 9792-610F, 4-20
0–10 V voltage input mA, 0-5 V,
9771-210F, 16 VDC–56 VDC
0–5 V field
9795-610F,
4–20 mA, 0–10 V
9783-110F,
voltage input

3704Ed AI, 0–5/0–10 VDC, 9765-210F, n/a 9760-210F, 9789-610F, n/a 9750-210F, 4–20 mA n/a
non-isolated, 64 pts. 0–5V 0–5 V 4–20 mA 9750-810F, 0–5/0–10 V
9760-410F,
0–10 V

13
Field Terminations Guide for Tricon 11.5 and Later 11.x Systems

14
Chapter 2
Table 1 Termination Product Options (Listed by Module Model Number) (continued)
Module 3-Wire 2-Wire Nonincendive RG 1.180
Module Description Voltage Basic RTD/TC/AI
Model # 4-20 mA 4-20 mA Term Panels Term Panels

3720 AI, 0–5 VDC, single-ended, 9765-210F, n/a 9760-210F, 9789-610F, n/a 9750-210F, 4–20 mA n/a

Field Termination Options and Installation


64 pts. 0–5 V 0–5 V 4–20 mA 9750-810F, 0–5 V

3721d AI; 0 to 5 VDC or –5 to +5 n/a n/a 9761-210F, 9791-610F, 9790-610F, 4–20 9753-110F, 0–5 V 9764-310Fc
VDC; differential; 32 pts. 0–5 V current input mA, 0–5 V
9761-410F, 9787-110F, 9792-610F, 4-20
0–10 V voltage input mA, 0-5 V
9771-210F, 16 VDC–56 VDC
0–5 V field
9795-610F, 4–20
mA, 0–10 V
9783-110F,
voltage input
9764-310F,
RTD/TC/AI
inputc

a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is commoned.
b. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-protected and commoned.
c. Signal conditioners must be ordered separately. A total of 16 is required for each termination panel.
d. Must be configured with the TriStation 1131 software.
For more information on using Model 3625/A, 3720, 3721, and 3807 I/O Modules with low-density applications, see Appendix I,
Low-Density Chassis I/O Module Compatibility.
Determining Field Termination Options by Module Type 15

Determining Field Termination Options by Module Type


This section identifies external field termination products you can use with each type of module.
Topics include:
• Digital Input Modules on page 15
• Pulse Input Modules on page 16
• Pulse Totalizer Input Modules on page 17
• Digital Output Modules on page 17
• Supervised Digital Output Modules on page 18
• Supervised/Non-Supervised Digital Output Modules on page 18
• Dual Digital Output Modules on page 19
• Relay Output Modules on page 19
• Analog Input Modules on page 20
• Thermocouple Input Modules on page 22
• Analog Output Modules on page 22
• HART Interface Modules on page 23

Digital Input Modules


This table identifies termination products you can use with 32-point digital input modules.

Table 2 Termination Products for 32-Point Digital Input Modules


115 V AC/DC 48 V AC/DC 24 V AC/DC 24 VDC
Termination Option
(3501E/T) (3502E) (3503E) (3505E)
Standard termination 9561-810F 9562-810F 9563-810F 9563-810F
panel, commoned 9563-910F 9563-910F
Standard termination 9561-110F n/a n/a n/a
panel, non-commoned
Basic termination panel 9551-110F 9552-610F 9553-610F 9553-610F
Nonincendive n/a n/a 9572-610F 9572-610F
termination panel
Bypass panel n/a n/a BP9228-010F BP9228-010F
Fanned-out cable 9101-010F 9101-010F 9101-010F 9101-010F
Relay cable 9141-010F 9142-010F 9143-010F 9143-010F

You need two termination panels (or cables) for each 32-point or 64-point DI module. Also, you
can mix any combination of two termination products listed in a particular module’s column.
For example, for a 115 VAC/VDC module you may use two 9561-810F commoned panels, or

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16 Chapter 2 Field Termination Options and Installation

one 9561-810F commoned panel and one 9561-110F non-commoned panel, or one 9551-110F
basic panel and one 9101-010F fanned-out cable.
This table identifies termination products you can use with 64-point digital input modules.

Table 3 Termination Products for 64-Point Digital Input Modules


24 VDC
Termination Option 24/48 VDC (3504E)
(3564)
Standard termination panel, commoned 9566-810F (24 V) 9566-710F
9565-810F (48 V)
Basic termination panel 9750-310F (24 V) 9553-610F
9750-410F (48 V)
Nonincendive termination panel 9570-610F 9571-610F
Bypass panel BP9229-010F n/a

Fanned-out cable n/a 9101-010F

Pulse Input Modules


This table identifies termination products you can use with pulse input modules. You can use
only one termination listed in a particular module’s column.

Table 4 Termination Products for 8-Point Pulse Input Modules


Termination Option 20 Hz–20 kHz (3510) 20 Hz–20 kHz (3511)
Basic termination panel 9753-110F 9753-110F
Nonincendive termination panel n/a 9793-110F
RG 1.180 Term Panel n/a 9794-110F

You need one termination panel for each 8-point PI module.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 17

Pulse Totalizer Input Modules


This table identifies termination products you can use with pulse totalizer input modules.

Table 5 Termination Products for 32-Point Pulse Totalizer Input Modules


Termination Option 0–1 kHz (3515)
Basic termination panel 9753-110F
Nonincendive termination panel 9572-610F
Fanned-out cable Contact Schneider Electric for availability of pulse totalizer
fanned-out cables.

You need two termination panels for each 32-point pulse totalizer input module.

Digital Output Modules


This table identifies termination products you can use with 16-point non-supervised digital
output modules.

Table 6 Termination Products for 16-Point Non-Supervised Digital Output Modules


Termination 115 VAC 115 VAC 120 VDC 120 VDC 120 VDC 24 VDC 48 VDC
Option (3601E) (3601T) (3603B) (3603E) (3603T) (3604E) (3607E)
Standard 9661-610F 9663-610F n/a 9661-910Fa 9664-810Fa 9662-810F 9667-810F
termination panel, 9663-610F 9664-810Fa
commoned

Standard 9661-110F 9664-110F n/a n/a n/a 9662-110F 9667-110F


termination panel, 9664-110F
non-commoned

Basic termination 9651-110F n/a n/a 9651-110F 9651-110F 9653-610F 9652-610F


panel

Nonincendive n/a n/a n/a n/a n/a 9671-610F n/a


termination panel
Relay panel, 9670-610F n/a n/a 9673-810Fa 9673-810Fa 9671-810F 9672-810F
commoned
Relay panel, 9670-110F n/a n/a n/a n/a n/a n/a
non-commoned

Special panel, n/a n/a 9251- n/a n/a n/a n/a


non-commoned 210F

Fanned-out cable 9101-010F n/a n/a 9101-010F n/a 9101-010F 9101-010F

a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is commoned.

You need one termination panel (or cable) for each 16-point non-supervised DO module.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
18 Chapter 2 Field Termination Options and Installation

Supervised Digital Output Modules


This table identifies termination products you can use with 8-point supervised digital output
modules. You can use only one of the terminations listed in a particular module’s column.

Table 7 Termination Products for 8-Point Supervised Digital Output Modules


115 VAC 120 VDC 24 VDC 24 VDC (low power) 48 VDC
Termination Option
(3611E) (3613E) (3614E) (3615E) (3617E)
Standard termination 9661-510F 9661-810F 9662-910F 9662-710F 9667-910F
panel, commoned

You need one termination panel (or cable) for each 8-point or 16-point supervised DO module.

Table 8 Termination Products for 16-Point Supervised Digital Output Modules


Termination Option 120 VDC (3623) 120 VDC (3623T) 24 VDC (3624)
Standard termination panel, 9661-910F 9664-810F 9662-610F
commoned
Basic termination panel 9651-110F 9651-110F 9653-610F
Nonincendive termination panel n/a n/a 9671-610F
Fanned-out cable 9101-010F n/a 9101-010F

Supervised/Non-Supervised Digital Output Modules


This table identifies termination products you can use with 32-point supervised/non-
supervised digital output modules.

Table 9 Termination Products for 32-Point Supervised/Non-Supervised Digital Output


Modules
Termination Option 24 VDC (3625/A)
Standard termination panel, commoned 9662-610F
Basic termination panel 9653-610F
Nonincendive termination panel 9671-610F
Fanned-out cable 9101-010F
ERT loop-back panel 9671-810Fa

a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-
protected and commoned.

You need two termination panels (or cables) for each 32-point digital output module. Also, you
can mix any combination of two termination products listed. For example, you may use two
9662-610F panels, or one 9653-610F basic panel and one 9101-010F fanned-out cable, and so on.
For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 19

Dual Digital Output Modules


This table identifies termination products you can use with dual digital output modules.

Table 10 Termination Products for 32-Point Dual Digital Output Modules


Termination Option 24 VDC (3664, 3674)
Standard termination panel, commoned 9662-610F
Basic termination panel 9653-610F
Nonincendive termination panel 9671-610F
Relay panel, commoned 9671-810Fa
Fanned-out cable 9101-010F

a. Point blown-fuse indicator will not illuminate when point fuse is removed. Each point is self-
protected and commoned.

You need two termination panels (or cables) for each 32-point dual digital output module. Also,
you can mix any combination of two termination products listed. For example, you may use two
9662-610F panels, or one 9653-610F basic panel and one 9101-010F fanned-out cable, and so on.

Relay Output Modules


This table identifies termination products you can use with relay output modules.

Table 11 Termination Products for 32-Point Relay Output Modules


Termination Option Non-Commoned, Normally Open (3636R, 3636T)
Standard termination panel, non-commoned 9668-110F
Basic termination panel, non-commoned 9651-110F
Fanned-out cable 9101-010F

You need two termination panels (or cables) for each 32-point relay output module. Also, you
can mix any combination of two termination products listed. For example, you may use two
9668-110F panels, two 9651-110F basic panels, or one 9668-110F panel and one 9651-110F basic
panel.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
20 Chapter 2 Field Termination Options and Installation

Analog Input Modules


This table identifies termination products you can use with analog input modules.

Table 12 Termination Products for 16-Point Analog Input Modules


Termination Option 0–5 VDC or 0–10 VDC (3703E)
Standard termination panel, voltage input 9763-810F
Standard termination panel, current input 9762-210F (0–5 V)
9762-410F (0–10 V)
Standard termination panel, current input, 9771-210F (0–5 V)
user configurable
Basic termination panel, voltage input 9753-110F
Nonincendive termination panel, current input 9791-610F
Nonincendive termination panel, voltage input 9787-110F
RG 1.180 Term Panel 9790-610F (4–20 mA, 0–5 V)
9792-610F (4-20 mA, 0-5 V, 16 VDC–56 VDC field)
9795-610F (4–20 mA, 0–10 V)
9783-110F (voltage input)
Fanned-out cable Contact Schneider Electric for availability of
analog fanned-out cables.

You need one termination panel for each 16-point AI module.


This table identifies termination products you can use with 32-point analog input modules.

Table 13 Termination Products for 32-Point Analog Input Modules


0–10 VDC 0 to 5 VDC or –5 to +5
Termination Option 0–5 VDC (3700A)
(3701) VDC (3721)
Standard termination panel, 9763-810F 9763-810F n/a
voltage input
Standard termination panel, 9761-210F 9761-410F 9761-210F
current input
Standard termination panel, 9771-210F n/a 9771-210F (0–5 V)
current input, 9761-410F (0–10 V)
user configurable
Basic termination panel, voltage 9753-110F 9753-110F 9753-110F
input
Nonincendive termination panel, 9791-610F n/a 9791-610F
current input
Nonincendive termination panel, 9787-110F n/a 9787-110F
voltage input

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Determining Field Termination Options by Module Type 21

Table 13 Termination Products for 32-Point Analog Input Modules (continued)


0–10 VDC 0 to 5 VDC or –5 to +5
Termination Option 0–5 VDC (3700A)
(3701) VDC (3721)
RG 1.180 Term Panel 9790-610F n/a 9790-610F
(current input) (4–20 mA, 0–5 V)
9792-610F (4–20 mA, 0– 9792-610F (4–20 mA, 0–5
5 V, 16 VDC–56 VDC V, 16VDC–56 VDC field)
field) 9795-610F
9783-110F (4–20 mA, 0–10 V)
(voltage input) 9783-110F
9764-310F, (voltage input)
RTD/TC/AI input 9764-310F, RTD/TC/AI
input
RTD/TC/AI panel 9764-310F n/a n/a

Fanned-out cable Contact Schneider Electric for availability of analog fanned-out


cables.

You need two termination panels (or cables) for each 32-point AI module. Also, you can mix any
combination of two termination products listed in a particular module’s column. For example,
with 0–5 VDC modules you may choose two 9763-810F panels, or a 9753-110F basic panel and a
9764-310F RTD/TC/AI panel, and so on. For low-density applications, see Appendix I, Low-
Density Chassis I/O Module Compatibility.

Table 14 Termination Products for 64-Point Analog Input Modules


0–5 VDC or 0–10 VDC
Termination Option 0–5 VDC (3720)
(3704E)
Standard termination panel, 3-wire 9765-210F 9765-210F
Xmtr
Standard termination panel, current 9760-210F (0–5 V) 9760-210F
input 9760-410F (0–10 V)
Basic termination panel, current input 9750-210F (0–5 V) 9750-210F
Basic termination panel, voltage input 9750-810F (0–5 V/0–10 V) 9750-810F (0–5 V)
Nonincendive termination panel, 9789-610F 9789-610F
current input
Fanned-out cable Contact Schneider Electric for availability of analog fanned-
out cables.

You need two termination panels (or cables) for each 64-point AI module. Also, you can mix any
combination of two termination products listed. For example, you may choose two 9760-210F
panels, or a 9750-210F basic panel and a 9760-210F panel, and so on. For low-density
applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
22 Chapter 2 Field Termination Options and Installation

Thermocouple Input Modules


This table identifies termination products you can use with 16-point thermocouple input
modules. You can use only one termination listed in a particular module’s column.

Table 15 Termination Products for 16-Point Thermocouple Input Modules


Termination Option Type E, J, K, and T; High-Density (3708E)
Standard termination panel 9765-610F
Nonincendive termination panel 9786-110F
RG 1.180 Term Panel 9782-110F

You need one termination panel for each 16-point thermocouple input module.
This table identifies termination products you can use with 32-point thermocouple input
modules.

Table 16 Termination Products for 32-Point Thermocouple Input Modules


Termination Option Type J, K, and T; Differential; Non-Isolated (3706A)
Standard termination panel, upscale 9766-210F
Standard termination panel, downscale 9766-510F
Nonincendive termination panel, upscale 9784-610F
Nonincendive termination panel, downscale 9785-610F

You need two termination panels for each 32-point thermocouple input module. Also, you can
use a 9766-210F panel with a 9766-510F panel.

Analog Output Modules


This table identifies termination products you can use with 8-point analog output modules.

Table 17 Termination Products for 8-Point Analog Output Modules


6, 4–20 mA; 2, 20–320 mA
Termination Option 4–20 mA (3805E/H)
(3806E)
Basic termination panel 9853-610F n/a
Special panel n/a 9863-710F
(Recommended for use in
turbine-control
applications)
Nonincendive termination 9861-610F n/a
panel
RG 1.180 Term Panel 9860-610F n/a
Fanned-out cable Contact Schneider Electric for availability of analog fanned-out cables.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 23

You need one termination panel for each 8-point AO module.


This table identifies termination products you can use with 4-point bipolar analog output
modules.

Table 18 Termination Products for 4-Point Bipolar Analog Output Modules


Termination Option Bipolar -60 to 60 mA (3807)
Standard termination panel 9881-810F
Nonincendive termination 9871-810F
panel
Fanned-out cable Contact Schneider Electric for availability of analog fanned-out cables.

You need one termination panel for each 4-point BPAO module. For low-density applications,
see Appendix I, Low-Density Chassis I/O Module Compatibility.

HART Interface Modules


This table identifies termination products you can use with HART™ AI and HART AO interface
modules.

Table 19 Termination Products for HART Interface Modules


HART AI Interface HART AO Interface
Termination Option
(2770H) (2870H)
Standard termination panel, current input 9761-210F n/a
9771-210F
Basic termination panel n/a 9853-610F
Nonincendive termination panel 9791-610F 9861-610F
RG 1.180 termination panel 9790-610F 9860-610F

Installation and Removal


This section explains how to install and remove termination panels and fanned-out cables.
Topics include:
• Installing a Termination Panel on page 24
• Removing or Replacing a Termination Panel on page 30
• Installing a Fanned-Out Cable on page 31
• Removing or Replacing a Fanned-Out Cable on page 32
Perform the installation, removal, and replacement procedures according to the safety
requirements for your environment.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
24 Chapter 2 Field Termination Options and Installation

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH

Install the recommended fuse type and value. To avoid electrical shock and equipment damage while
removing a blown fuse, use the fuse-extractor tool (#158000–01) supplied with the system.

Failure to follow these instructions will result in death or serious injury.

The connector on each external termination panel, interface cable, and special cable is factory-
keyed by voltage and module type to protect against accidental connection to an incompatible
product. If you use a fanned-out cable instead of a termination panel, you must re-key its
connector according to Appendix A, Re-Keying Connectors.

Installing a Termination Panel


This procedure explains how to install a termination panel.

Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
2 Remove incoming power from the Tricon system (optional).
3 Mount the termination panel on a DIN rail as shown in these pictures.
These termination panels cannot be installed on a DIN rail. They must be installed on a
standard 19 inch (47.5 cm) rack (Electronics Industries Association Standard #RS-310-C):
• 9251-210F
• 9670-110F
• 9670-610F
• 9671-810F
• 9672-810F
• 9673-810F
• BP9228-010F
• BP9229-010F
• 9764-310F

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 25

Place the bottom of the


DIN rail into the lower
brackets on the back of
the term panel.

After placing the bottom


of the DIN rail, place the
top of the DIN rail into
the upper brackets and
snap the top rail edge
into the grooves.

This picture shows a


term panel being
mounted properly on a
DIN rail.

For applications requiring high shock/vibration or seismic immunity, attach a ground


terminal block to the DIN rail at either end of the term panel (or string of term panels) to
prevent the term panel(s) from sliding along the DIN rail, as shown in this picture. Please
contact the Global Customer Support (GCS) center for details.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
26 Chapter 2 Field Termination Options and Installation

Front Side

ELCO connector

4 Attach one end of the interface cable to the ELCO connector on the termination panel.
• Ensure that the mating surfaces of the ELCO connectors on the cable and the
termination panel do not have any bent pins or other damage, and that both male
and female keys match.
• Position the connector on the cable so that it is aligned with the connector on the
termination panel.

Ensure that the


male and female
keys match.

• Mate the two connectors together until the threaded end of the thumbscrew is
making contact with the nut in the female connector. You may need to slightly rock
the connector on the cable while mating it to the connector on the termination
panel.
• As you apply pressure to the top of the connector on the cable, use your other hand
to turn the thumbscrew clockwise until the connectors are mated completely. The
minimum torque requirement is 8.85 lbf in (10.0 d-Nm).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 27

Turn the
thumbscrew
clockwise...
...until the
connectors are
fully mated.

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

You must use gasket 2000098-100 on the male side of all ELCO connectors used in ATEX installations,
and replace it before the end of its five-year life span. Schneider Electric recommends that you use the
gasket in all hazardous locations requiring nonincendive circuits. (Order Schneider Electric part number
3000793-001 for a kit of 25 gaskets.)

Failure to follow these instructions can result in death, serious injury, environmental damage, or
equipment damage.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
28 Chapter 2 Field Termination Options and Installation

gasket
installed gasket

5 Attach the other end of the interface cable to the ELCO connector directly above the
corresponding I/O module on the Tricon chassis backplane in the same manner as you
connected the cable to the termination panel, as described in step 4.
6 Attach the wires from your field devices to the screw terminals on the termination panel.
See the Torque Specifications for Field Wiring Terminals section.
7 Perform a static check of the wiring.
8 If Tricon system power was removed in step 1, restore power to the Tricon system.
9 Apply field power to the termination panel.
10 Verify that all I/O points are connected to the appropriate field devices and are
operating correctly.
To inspect input points and force output points, see the Planning and Installation Guide for
Tricon 11.5 and Later 11.x Systems.
11 Load and test the control program using the TriStation 1131™ software.
If the program operates as intended, you are ready to enable the process equipment according
to the safety requirements for your environment.
If you need additional information on how to install external field termination panels, contact
the Global Customer Support (GCS) center.

Torque Specifications for Field Wiring Terminals


Tighten the screws on the field wiring and power terminals of the ETPs in the list below to this
torque:
4.425–5.310 lbf in (0.3688–0.4425 lbf ft) (0.5–0.6 Nm)

9551-110F 9653-610F 9667-910F 9765-210F 9793-110F


9552-610F 9661-610F 9667-810F 9765-610F 9794-110F
9553-610F 9661-110F 9668-110F 9766-210F 9795-610F
9561-810F 9661-810F 9750-410F 9766-510F 9853-610F
9561-110F 9661-510F 9750-810F 9771-210F 9860-610F
9562-810F 9661-910F 9750-210F 9782-110F 9861-610F
9563-810F 9662-110F 9750-310F 9783-110F 9863-710F
9565-810F 9662-910F 9753-110F 9784-610F

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 29

9566-710F 9662-610F 9760-410F 9785-610F


9566-810F 9662-710F 9760-210F 9786-110F
9570-610F 9662-810F 9761-210F 9787-110F
9571-610F 9663-610F 9761-410F 9789-610F
9572-610F 9664-110F 9762-410F 9790-610F
9651-110F 9664-810F 9762-210F 9791-610F
9652-610F 9667-110F 9763-810F 9792-610F

Tighten the screws on the field wiring and power terminals of the ETPs in the list below to this
torque:
12.0 lbf in (1.0 lbf ft) (1.36 Nm)

9670-110F
9670-610F
9671-610F
9671-810F
9672-810F
9673-810F

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
30 Chapter 2 Field Termination Options and Installation

Removing or Replacing a Termination Panel


This procedure explains how to remove or replace a termination panel.

Procedure
1 Remove field power from the termination panel.
2 Detach all I/O points connected to the appropriate field wiring.
3 Detach the wires from your field devices to the screw terminals on the termination
panel.
4 Detach the interface cable from the ELCO connector on the termination panel.
• As you pull the connector on the cable, use your other hand to turn the thumbscrew
counter-clockwise. You may need to rock the connector slightly while pulling.
• Ensure that the mating surfaces of the ELCO connectors on the cable and the
termination panel do not have any bent pins or other damage.
5 Detach the other end of the interface cable from the ELCO connector on the Tricon
chassis backplane in the same manner as you disconnected the cable from the
termination panel, as described in step 4.

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH

Verify that power to the termination panel is off and that steps 1-4 have been followed. Dangerous
voltage may be present on the ELCO connector.

Failure to follow these instructions will result in death or serious injury.

6 Dismount the termination panel from the DIN or rack rail.


7 To replace a termination panel, follow the procedure in Installing a Termination Panel
on page 24.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Installation and Removal 31

Installing a Fanned-Out Cable


This procedure explains how to install a fanned-out cable.

Procedure
1 Set up the Tricon chassis and install the I/O modules as described in the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
2 Remove incoming power from the Tricon system (optional).
3 Re-key the female connector on the fanned-out cable to match the male connector on the
Tricon chassis backplane. For instructions, see Appendix A, Re-Keying Connectors.
4 Attach the fanned-out cable connector to the panel connector that is above the
corresponding I/O module.
5 Connect the fanned-out cable wires to the field devices or marshaling termination.
6 Perform a static check of the wiring.
7 If Tricon system power was removed in step 1, restore power to the Tricon system.
8 Apply field power to the devices connected to the fanned out cable.
9 Verify the connection of all I/O points to the appropriate field wiring by using the
TriStation 1131 software to inspect input points and force output points.
To inspect input points and force output points, see the Planning and Installation Guide for
Tricon 11.5 and Later 11.x Systems.
10 Load and test the control program using the TriStation 1131 software.
If you need additional information on how to install fanned-out cables, contact the Global
Customer Support (GCS) center.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32 Chapter 2 Field Termination Options and Installation

Removing or Replacing a Fanned-Out Cable


This procedure explains how to remove or replace a fanned-out cable.

Procedure
1 Remove field power from the termination panel.
2 Detach the fanned-out cable connector that is above the corresponding I/O module.
3 Detach the fanned-out wires from the field termination panel or the field devices.

DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH

Verify that power to the termination panel is off and that steps 1-3 have been followed. Dangerous
voltage may be present on the ELCO connector.

Failure to follow these instructions will result in death or serious injury.

4 To replace a fanned-out cable, follow the procedure in Installing a Fanned-Out Cable on


page 31.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
3
Digital Input Termination Panels

Overview 34
16-Point Commoned Digital Input Term Panels 34
32-Point Commoned Digital Input Term Panels 45
16-Point Non-Commoned Digital Input Term Panels 56
Basic Digital Input Term Panels 58
Pulse Input and Pulse Totalizer Input Term Panels 71
Bypass Term Panels 77

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
34 Chapter 3 Digital Input Termination Panels

Overview
This chapter describes external field termination panels you can use with digital input modules.
Digital input termination panels are available in these configurations:
• 16-point commoned
• 32-point commoned
• Non-commoned
• Basic
• Bypass

16-Point Commoned Digital Input Term Panels


This section describes 16-point commoned digital input term panels. Model numbers of these
term panels are:
• 9561-810F (115 V, commoned, 16 pts.)
• 9562-810F (48 V, commoned, 16 pts.)
• 9563-810F (24 V, commoned, 16 pts.)
• 9563-910F (24 V, commoned, resistor protected, 16 pts.)
This figure represents a typical 16-point commoned digital input termination panel with fuses
and blown-fuse indicators.
SN REV A 7400165-
F10

F12

F14

F16
F2

F4

F6

F8
PWR

J1

F13

F15
F11
CR1

CR2

F1

F3

F5

F7

F9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

Figure 3 Typical 16-Point Commoned DI Term Panel with Fuse Protection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 35

This figure represents a typical 16-point commoned digital input termination panel with
resistors.

SN REV A 7400165-

R10

R12

R14

R16
R2

R4

R6

R8
PWR

J1
CR1

CR2

R13

R15
R11
R1

R3

R5

R7

R9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

Figure 4 Typical 16-Point Commoned DI Term Panel with Resistor Protection

9561-810F (115 V, commoned, 16 pts.)


Termination panel 9561–810F is compatible with 115 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9561–810F have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9561–810F.

Table 20 Specifications for Term Panel 9561–810F


Feature Description
Panel type Commoned
Points 16
Leakage current per point Maximum: 3.3 mA
Typical: 2.5 mA

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
36 Chapter 3 Digital Input Termination Panels

Compatible Modules
This table describes digital input modules compatible with 9561–810F.

Table 21 Modules Compatible with 9561–810F


Module Model Points per
Module Description Fuse
Number Module
3501E 32 115 VAC/VDC, non-commoned, isolated, TMR 1A, slow
3501T 32 115 VAC/VDC, non-commoned, isolated, TMR 1A, slow

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9561–810F with a
DC power supply to the field.

Termination panel
SN REV A 7400165-
F10

F12

F14

F16
F2

F4

F6

F8
PWR

J1

F13

F15
F11
CR1

CR2

F1

F3

F5

F7

F9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+

F+
F–

F–
PS1

PS2

DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply

Figure 5 Field Wiring for 9561-810F with a 3501E or 3501T Module and a DC Power Supply

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 37

This figure illustrates how to connect a 32-point digital input module and a 9561-810F with an
AC power supply to the field.
Termination panel
SN REV A 7400165-

Hot
AC

F10

F12

F14

F16
F2

F4

F6

F8
Power
Neutral

PWR
Supply

J1

F13

F15
F11
F1

F3

F5

F7

F9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+

F+
F–

F–
PS1

PS2

Typical point (1 of 16
points shown)

Field
Contact

Figure 6 Field Wiring for 9561-810F with a 3501E or 3501T Module and an AC Power Supply

Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with a
commoned digital input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE

AC/DC Input Circuit

Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A

Threshold to
Detect Input
to
other Opto-Isolator Mux B
points

PWR (AC Hot)

PS1

PS1

PS2 Threshold to
to Detect Input
spare
PS2 module Opto-Isolator Mux C

(AC Neutral)
PWR

* LEDs are blown-fuse indicators

Figure 7 Simplified Schematic of a 3501E or 3501T DI Module with a 9561-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
38 Chapter 3 Digital Input Termination Panels

9562-810F (48 V, commoned, 16 pts.)


Termination panel 9562-810F is compatible with 48 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9562-810F have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9562-810F.

Table 22 Specifications for Term Panel 9562-810F


Feature Description
Panel type Commoned
Points 16
Leakage current per point Maximum: 3.5 mA
Typical: 2.0 mA

Compatible Modules
This table describes digital input modules compatible with 9562-810F.

Table 23 Modules Compatible with 9562-810F


Module Model Points per
Module Description Fuse
Number Module
3502E 32 48 VAC/VDC, commoned in groups of 8, TMR 1A, slow
with self-test

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 39

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9562-810F to the
field.

Termination panel
SN REV A 7400165-

F10

F12

F14

F16
F2

F4

F6

F8
PWR

J1

F13

F15
F11
CR1

CR2

F1

F3

F5

F7

F9

16/32
10/26

12/28
13/29
14/30
15/31
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+

F+
F–

F–
PS1

PS2

DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply

Figure 8 Field Wiring for 9562-810F with a 3502E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
40 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST

AC/DC Input Circuit

Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A

opto-
isolated

Test A

to
other
points Threshold to
(AC Hot)
Detect Input
PWR Opto-Isolator Mux B

PS1

PS1

PS2
Test B
PS2
(AC Neutral)
PWR

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

* LEDs are blown-fuse indicators

Figure 9 Simplified Schematic of a 3502E DI Module with a 9562-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 41

9563-810F (24 V, commoned, 16 pts.)


Termination panel 9563-810F is compatible with 24 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9563-810F have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9563-810F.

Table 24 Specifications for Term Panel 9563-810F


Feature Description
Panel type Commoned
Points 16
Leakage current per point Maximum: 3.3 mA
Typical: 2.5 mA

Compatible Modules
This table describes digital input modules compatible with 9563-810F.

Table 25 Modules Compatible with 9563-810F


Module Model Points per
Module Description Fuse
Number Module
3503E 32 24 VAC/VDC, commoned in groups of 8, TMR with 1A, slow
self-test
3505E 32 24 VDC, low-threshold, commoned in groups of 8 1A, slow
with self test, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
42 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9563-810F to the
field.

Termination panel
SN REV A 7400165-

F10

F12

F14

F16
F2

F4

F6

F8
PWR

J1

F13

F15
F11
CR1

CR2

F1

F3

F5

F7

F9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
F+

F+
F–

F–
PS1

PS2

DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply

Figure 10 Field Wiring for 9563-810F with a 3503E or 3505E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Input Term Panels 43

Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST

AC/DC Input Circuit

Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A

opto-
isolated

Test A

to
other
points Threshold to
(AC Hot)
Detect Input
PWR Opto-Isolator Mux B

PS1

PS1

PS2
Test B
PS2
(AC Neutral)
PWR

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

* LEDs are blown-fuse indicators

Figure 11 Simplified Schematic of a 3503E or 3505E DI Module with a 9563-810F Panel

9563-910F (24 V, commoned, resistor protected, 16 pts.)


Termination panel 9563-910F is compatible with 24 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
180 ohm resistor.
The modules compatible with 9563-910F have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
44 Chapter 3 Digital Input Termination Panels

Specifications
This table describes specifications for 9563-910F.

Table 26 Specifications for Term Panel 9563-910F


Feature Description
Panel type Commoned, resistor protected
Points 16

Compatible Modules
This table describes digital input modules compatible with 9563-910F.

Table 27 Modules Compatible with 9563-910F


Module Model Points per
Module Description
Number Module
3503E 32 24 VAC/VDC, commoned in groups of 8, TMR with self-test
3505E 32 24 VDC, low-threshold, commoned in groups of 8, TMR with self-test

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9563-910F to the
field.

Termination panel
SN REV A 7400165-
R10

R12

R14

R16
R2

R4

R6

R8
PWR

J1
CR1

CR2

R13

R15
R11
R1

R3

R5

R7

R9
10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

DC Typical point (1 of 16
Power points shown).
Supply
Field
DC Contact
Power
Supply

Figure 12 Field Wiring for 9563-910F with a 3503E or 3505E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 45

Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self-
test (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

180 Ohms opto-


isolated

Test A

to Threshold to
other Detect Input
points Opto-Isolator Mux B

PS1

PS2
Test B
PS1

PS2
Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

Figure 13 Simplified Schematic of a 3503E or 3505E DI Module with a 9563-910F Panel

32-Point Commoned Digital Input Term Panels


This section describes 32-point commoned digital input term panels, which are available with
fuses and blown fuse indicators or resistors for field device protection. Model numbers of these
term panels are:
• 9565-810F (48 VDC, commoned, 32 pts.) (fuse protection)
• 9566-710F (24 VDC, commoned, 32 pts.) (resistor protection)
• 9566-810F (24 VDC, commoned, 32 pts.) (resistor protection)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
46 Chapter 3 Digital Input Termination Panels

This figure represents a typical 32-point commoned digital input term panel that has fuses and
blown-fuse indicators for field device protection.
SN REV A 7400150-

F10

F12

F14

F16

F18

F20

F22

F24

F26

F28

F30

F32
F2

F4

F6

F8

J1
CR1

CR2

F13

F15
F11
F1

F3

F5

F7

F9

F17

F19

F21

F23

F25

F27

F29

F31
17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

Figure 14 Typical 32-Point Commoned DI Term Panel with Fuse Protection

This figure represents a typical 32-point commoned digital input term panel that has resistors
for field device protection.
SN REV A 7400150-
R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

Figure 15 Typical 32-Point Commoned DI Term Panel with Resistor Protection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 47

9565-810F (48 VDC, commoned, 32 pts.)


Termination panel 9565-810F is compatible with 24/48 volt DC digital input modules and has
32 input points and commoned power terminals (PWR+ and PWR–). Each input point is
protected by a fuse with a blown-fuse indicator. You should use term panel 9565-810F in 48 volt
applications.
The modules compatible with 9565-810F have 64 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9565-810F.

Table 28 Specifications for Term Panel 9565-810F


Feature Description
Panel type Commoned
Points 32
Leakage current per point Maximum: 3.5 mA
Typical: 2.0 mA

Compatible Modules
This table describes digital input modules compatible with 9565-810F.

Table 29 Modules Compatible with 9565-810F


Module Model Points per
Module Description Fuse
Number Module
3504E 64 24/48 VDC, commoned, high-density, DC-coupled, 1A, slow
TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
48 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a 9565-810F to the
field.

Termination panel
SN REV A 7400150-

F10

F12

F14

F16

F18

F20

F22

F24

F26

F28

F30

F32
F2

F4

F6

F8

J1
CR1

CR2

F13

F15
F11
F1

F3

F5

F7

F9

F17

F19

F21

F23

F25

F27

F29

F31
17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply

Figure 16 Field Wiring for 9565-810F with a 3504E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 49

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 48 VDC high-density DC-coupled
digital input module (1 of 64 module points shown) with a 9565-810F.

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

LED *
Mux
1A, slow
to
spare 1
Amp ADC

64

Hi-Ref
Low-Ref

to Mux
other
points
10K 1
Amp ADC

PS1 64

PS2
Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

* LEDs are blown-fuse indicators

Figure 17 Simplified Schematic of a 3504E DI Module in a 48 V Application with a 9565-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
50 Chapter 3 Digital Input Termination Panels

9566-710F (24 VDC, commoned, 32 pts.)


Termination panel 9566-710F is compatible with 24 VDC digital input modules and has 32 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
180 ohm current-limiting resistor.
The modules compatible with 9566-710F have 64 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9566-710F.

Table 30 Specifications for Term Panel 9566-710F


Feature Description
Panel type Commoned
Points 32

Compatible Modules
This table describes digital input modules compatible with 9566-710F.

Table 31 Modules Compatible with 9566-710F


Module Model Points per
Module Description
Number Module
3564 64 24 VDC, commoned, single

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 51

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a 9566-710F to the
field.

Termination panel
SN REV A 7400150-

R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply

Figure 18 Field Wiring for 9566-710F with a 3564 Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
52 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24 VDC digital input module with
a 9566-710F (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT DIGITAL INPUT MODULE

to
spare
Test ON Relays
(opto-isolated)
180 Ohms
to other
points &
sensors

to
other
points
A

Threshold Detect
PS1 Opto-Isolator B

PS2
C

Test OFF Relays


PS1 (opto-isolated)
to
PS2 other
points

Figure 19 Simplified Schematic of a 3564 DI Module with a 9566-710F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 53

9566-810F (24 VDC, commoned, 32 pts.)


Termination panel 9566-810F is compatible with 24/48 VDC digital input modules and has 32
input points and commoned power terminals (PWR+ and PWR–). Each input point is protected
by a 180 ohm current-limiting resistor. You should use term panel 9566-810F in 24 volt
applications.
The modules compatible with 9566-810F have 64 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9566-810F.

Table 32 Specifications for Term Panel 9566-810F


Feature Description
Panel type Commoned
Points 32

Compatible Modules
This table describes digital input modules compatible with 9566-810F.

Table 33 Modules Compatible with 9566-810F


Module Model Points per
Module Description
Number Module
3504E 64 24/48 VDC, commoned, high-density, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
54 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a 9566-810F to the
field.

Termination panel
SN REV A 7400150-

R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

PS1
DC Typical point (1 of 32
Power points shown).
Supply
Field
Contact
PS2
DC
Power
Supply

Figure 20 Field Wiring for 9566-810F with a 3504E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned Digital Input Term Panels 55

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned high-density 24 VDC digital input
module with a 9566-810F (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

Mux
to
spare 1
Amp ADC
180 Ohms
64

Hi-Ref
Low-Ref

to Mux
other
points
2.7K 1
Amp ADC

PS1 64

PS2 Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Figure 21 Simplified Schematic of a 3504E DI Module in a 24 V Application with a 9566-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
56 Chapter 3 Digital Input Termination Panels

16-Point Non-Commoned Digital Input Term Panels


This section describes non-commoned digital input term panels. Model numbers of these term
panels are:
• 9561-110F (115 V, non-commoned, 16 pts.)
This figure represents a typical 16-point non-commoned digital input termination panel with
fuses and blown-fuse indicators.

SN REV A 7400168-

F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
CONTACT

9
PWR

Figure 22 Typical 16-Point Non-Commoned DI Term Panel

9561-110F (115 V, non-commoned, 16 pts.)


Termination panel 9561-110F is compatible with 115 VAC/VDC digital input modules and has
16 input points and 16 power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9561-110F have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9561-110F.

Table 34 Specifications for Term Panel 9561-110F


Feature Description
Panel type Non-commoned
Points 16
Leakage current per point Maximum: 3.3 mA
Typical: 2.5 mA

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Input Term Panels 57

Compatible Modules
This table describes digital input modules compatible with 9561-110F.

Table 35 Modules Compatible with 9561-110F


Module Model Points per
Module Description Fuse
Number Module
3501E 32 115 VAC/VDC, non-commoned, isolated, TMR 1A, slow
3501T 32 115 VAC/VDC, non-commoned, isolated, TMR 1A, slow

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9561-110F to the
field.

Termination panel
SN REV A 7400168-

F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
CONTACT

9
PWR

Hot
AC Typical point (1 of 16
Power points shown).
Supply Neutral
Field
Contact

Figure 23 Field Wiring for 9561-110F with a 3501E or 3501T Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
58 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned digital input module with a
9561-110F (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE

AC/DC Input Circuit

Leg-to-Leg Bridge AC
LED * Isolation Rectifier Smoothing
Threshold to
Detect Input
1A, slow Opto-Isolator Mux A
PWR1

CONTACT

CONTACT

PWR1

Threshold to
Detect Input
Opto-Isolator Mux B

Threshold to
to Detect Input
spare Opto-Isolator Mux C
module

* LEDs are blown fuse-indicators

Figure 24 Simplified Schematic of a 3501E or 3501T DI Module with a 9561-110F Panel

Basic Digital Input Term Panels


This section describes basic digital input term panels, which are available in 16-point and
32-point configurations.
Model numbers of these term panels are:
• 9551-110F (115 V, basic, 16 pts.)
• 9552-610F (48 V, basic, 16 pts.)
• 9553-610F (24 V, basic, 16/32 pts.)
• 9750-310F (24 VDC, basic, 32 pts.)
• 9750-410F (48 VDC, basic, 32 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 59

This figure represents a typical 16-point or 32-point basic digital input termination panel.

J1

DIDO PANEL

REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
A A
TM
TRICONEX

7400143-
C C

E E

Figure 25 Typical 16-Point/32-Point Basic DI Term Panel

9551-110F (115 V, basic, 16 pts.)


Termination panel 9551-110F is compatible with 115 VAC/VDC digital input modules and has
16 input points.
The modules compatible with 9551-110F have 32 points, which means you must use two term
panels for each digital input module.

Specifications
This table describes specifications for 9551-110F.

Table 36 Specifications for Term Panel 9551-110F


Feature Description
Panel type Basic
Points 16

Compatible Modules
This table describes digital input modules compatible with 9551-110F.

Table 37 Modules Compatible with 9551-110F


Module Model Points per
Module Description
Number Module
3501E 32 115 VAC/VDC, non-commoned, isolated, TMR
3501T 32 115 VAC/VDC, non-commoned, isolated, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
60 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9551-110F to the
field.

Termination panel
REV A 7400143- AC HOT/+DC
SN
A

E
C

32
1A, slow
30
28
26
24
Field
22
Contact
J1

20
18
2A (IN1 +)
16
14
12
10
8

2E (IN1 –)
6
4
2
A

E
C

DIDO PANEL TM TRICONEX

AC NEUTRAL/RETURN

Figure 26 Field Wiring for 9551-110F with a 3501E or 3501T Module

Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module without self-test and a
9551-110F (1 of 32 module points shown).

TERMINATION CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE


PANEL

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

IN

IN

Threshold to
Detect Input
Opto-Isolator Mux B

Threshold to
to Detect Input
spare Opto-Isolator Mux C
module

Figure 27 Simplified Schematic of a 3501E or 3501T DI Module with a 9551-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 61

9552-610F (48 V, basic, 16 pts.)


Termination panel 9552-610F is compatible with 48 VAC/VDC digital input modules and has
16 input points.
The modules compatible with 9552-610F have 32 points, which means you must use two term
panels for each digital input module.

Specifications
This table describes specifications for 9552-610F.

Table 38 Specifications for Term Panel 9552-610F


Feature Description
Panel type Basic
Points 16

Compatible Modules
This table describes digital input modules compatible with 9552-610F.

Table 39 Modules Compatible with 9552-610F


Module Model Points per
Module Description
Number Module
3502E 32 48 VAC/VDC, commoned in groups of 8 with self test, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
62 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9552-610F to the
field.

Termination panel
REV A 7400143- AC HOT/+DC
SN
A

E
C

32
1A, slow
30
28
26
24
Field
22
Contact
J1

20
18
2A (IN1 +)
16
14
12
10
8

2E (IN1 –)
6
4
2
A

E
C

DIDO PANEL TM TRICONEX

AC NEUTRAL/RETURN

Figure 28 Field Wiring for 9552-610F with a 3502E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 63

Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with self-test and a
9552-610F (1 of 32 module points shown).

TERMINATION CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST


PANEL

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

opto-
IN isolated

IN Test A

Threshold to
Detect Input
Opto-Isolator Mux B

Test B

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

Figure 29 Simplified Schematic of a 3502E DI Module with a 9552-610F Panel

9553-610F (24 V, basic, 16/32 pts.)


Termination panel 9553-610F is compatible with 24 VAC/VDC and 24 VDC digital input
modules and has 16 input points when used with 32-point modules and 32 input points when
used with 64-point modules.
You must use two term panels for each digital input module.

Specifications
This table describes specifications for 9553-610F.

Table 40 Specifications for Term Panel 9553-610F


Feature Description
Panel type Basic
Points 16 when used with 32-point modules
32 when used with 64-point modules

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
64 Chapter 3 Digital Input Termination Panels

Compatible Modules
This table describes digital input modules compatible with 9553-610F.

Table 41 Modules Compatible with 9553-610F


Module Model Points per
Module Description
Number Module
3503E 32 24 VAC/VDC, commoned in groups of 8 with self test, TMR
3505E 32 24 VDC, low-threshold, commoned in groups of 8, TMR
3564 64 24 VDC, commoned, single

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a 9553-610F to the
field.

Termination panel
REV A 7400143- AC HOT/+DC
SN
A

E
C

32
1A, slow
30
28
26
24
Field
22
Contact
J1

20
18
2A (IN1 +)
16
14
12
10
8

2E (IN1 –)
6
4
2
A

E
C

DIDO PANEL TM TRICONEX

AC NEUTRAL/RETURN

Figure 30 Field Wiring for 9553-610F with a 3503E or 3505E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 65

This figure illustrates how to connect a 64-point digital input module and a 9553-610F without
commoned return to the field.

Termination panel
+DC
7400144-
REV A

32
30
28
26
24
4C, 8C or 12C
22
(PWR)
** 1A, slow
J1

20
18
16
14
12
10
8
6 4E (IN4)
4
2
SN

2A (IN1)
A

E
C

14C to 32C
(RTN)
*

RTN
* One RTN connection is required. More than one is okay.
** One PWR connection is required. More than one is okay.
Figure 31 Field Wiring for 9553-610F with a 3564 Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
66 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with self-test and a
9553-610F (1 of 32 module points shown).

TERMINATION CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST


PANEL

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

opto-
IN isolated

IN Test A

Threshold to
Detect Input
Opto-Isolator Mux B

Test B

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

Figure 32 Simplified Schematic of a 3503E or 3505E DI Module with a 9553-610F Panel

This is a simplified schematic of a typical 64-point commoned digital input module and a
9553-610F (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT DIGITAL INPUT MODULE

to
spare
Test ON Relays
(opto-isolated)
PWR + to other
points &
sensors
IN +

Threshold Detect
Opto-Isolator B

C
RTN
Test OFF Relays
(opto-isolated)
to to
other other
points points

Figure 33 Simplified Schematic of a 3564 DI Module with a 9553-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 67

9750-310F (24 VDC, basic, 32 pts.)


Termination panel 9750-310F is compatible with 24/48 VDC digital input modules and has 32
input points.
The modules compatible with 9750-310F have 64 points, which means you must use two term
panels for each digital input module.

Specifications
This table describes specifications for 9750-310F.

Table 42 Specifications for Term Panel 9750-310F


Feature Description
Panel type Basic
Points 32

Compatible Modules
This table describes digital input modules compatible with 9750-310F.

Table 43 Modules Compatible with 9750-310F


Module Model Points per
Module Description
Number Module
3504E 64 24/48 VDC, commoned, high-density, DC-coupled, TMR, configured
as 24 VDC when used with 9750-310F

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
68 Chapter 3 Digital Input Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a 9750-310F to the
field.
e at o pa e
24 VDC
7400144-
REV A

32
30
28
26
24
Typical 2 of 32
1A, slow
22
points shown
J1

20
18
16
14 1A, slow Field
12
Contacts
10
8
6 4E (IN4)
4
2
SN

2A (IN1)
A

**
14C to 32C (RTN)
*

RTN

* One RTN connection is required. More than one is okay.

**A ballast resistor may be required to satisfy whetting current of relay contacts.
Figure 34 Field Wiring for 9750-310F with a 3504E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Input Term Panels 69

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24/48 VDC high-density DC-
coupled digital input module with a 9750-310F (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

Mux
to
spare 1
* Amp ADC

IN + 64

RTN
Hi-Ref
Low-Ref
to
other
points Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

* For noise immunity, install a 1W, 2.7 kilohms ballast resistor because relay contact applications resistors should be sized to satisfy
the required whetting current.

Figure 35 Simplified Schematic of a 3504E DI Module with a 9750-310F Panel

9750-410F (48 VDC, basic, 32 pts.)


Termination panel 9750-410F is compatible with 24/48 VDC digital input modules and has 32
input points.
The modules compatible with 9750-410F have 64 points, which means you must use two term
panels for each digital input module.

Specifications
This table describes specifications for 9750-410F.

Table 44 Specifications for Term Panel 9750-410F


Feature Description
Panel type Basic
Points 32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
70 Chapter 3 Digital Input Termination Panels

Compatible Modules
This table describes digital input modules compatible with 9750-410F.

Table 45 Modules Compatible with 9750-410F


Module Model Points per
Module Description
Number Module
3504E 64 24/48 VDC, commoned, high-density, DC-coupled, TMR, configured
as 48 VDC when used with 9750-410F

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a 9750-410F to the
field.

Termination panel
48 VDC
7400144-
REV A

32
30
28
26
24
Typical 2 of 32
1A, slow
22
points shown
J1

20
18
16
14 1A, slow Field
12
Contacts
10
8
6 4E (IN4)
4
2
SN

2A (IN1)
A

**
14C to 32C (RTN)
*

RTN
One RTN connection is required. More than one is okay.
* A ballast resistor may be required to satisfy whetting current of relay contacts.
**
Figure 36 Field Wiring for 9750-410F with a 3504E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 71

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned 24/48 VDC high-density DC-
coupled digital input module with a 9750-410F (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

Mux
to
spare 1
* Amp ADC

IN + 64

RTN
Hi-Ref
Low-Ref
to
other
points Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

* For noise immunity, install a 1W, 2.7 kilohms ballast resistor because relay contact applications resistors should be sized to satisfy
the required whetting current.

Figure 37 Simplified Schematic of a 3504E DI Module with a 9750-410F Panel

Pulse Input and Pulse Totalizer Input Term Panels


This section describes pulse input and pulse totalizer input term panels.
Model numbers of these term panels are:
• 9753-110F (8 PI pts./16 PTI pts.)
This figure represents a typical 8-point pulse input or 16-point pulse totalizer input termination
panel.

J1
DIDO PANEL

REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8

A A
TM
TRICONEX

7400143-

C C

E E

Figure 38 Typical 8-Point Pulse Input or 16-Point Pulse Totalizer Input Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
72 Chapter 3 Digital Input Termination Panels

9753-110F (8 PI pts./16 PTI pts.)


Termination panel 9753-110F is compatible with pulse input modules and pulse totalizer input
modules.
When used with pulse input modules, 9753-110F has 8 differential-input signal terminals (IN+
and IN–).
When used with pulse totalizer input modules, 9753-110F has 16 input signal terminals (IN+
and IN–). The pulse totalizer input modules compatible with 9753-110F have 32 points, which
means you must use two term panels for each pulse totalizer input module.

Specifications
This table describes specifications for 9753-110F.

Table 46 Specifications for Term Panel 9753-110F


Feature Description
Panel type Basic
Points 8 when used with pulse input modules
16 when used with pulse totalizer input modules

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 73

Compatible Modules
This table describes pulse input and pulse totalizer input modules compatible with 9753-110F.

Table 47 Modules Compatible with 9753-110F


Module Model Points per
Module Description
Number Module
3510 8 20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 50
ms typical input update rate
3511 8 20 Hz to 20 KHz pulse input, non-commoned, AC-coupled, 25
ms typical input update rate
3515 32 0 to 1 kHz pulse totalizer input, non-commoned

Field Wiring Diagrams


This figure illustrates how to connect an 8-point pulse input module and a 9753-110F to the field.

Termination panel
REV A 7400143-
SN
A

E
C

32

30
Typical passive
speed sensor
28
26
24
22
J1

20
18
16
14
12
10
8
6 2E (IN1 –)
4
2 F–
Typical 1 of 8
points shown
A

E
C

DIDO PANEL TM
TRICONEX F+

2A (IN1 +) **

*
* Functional earth ground (quiet ground) is recommended for shield connections.
For shield grounding instructions, see Appendix E.
** When possible, install a terminating resistor as shown. For further information, see Technical Application Note (TAN) #006.

Figure 39 Field Wiring for 9753-110F with a 3510 or 3511 PI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
74 Chapter 3 Digital Input Termination Panels

This figure illustrates how to connect a 32-point pulse totalizer input module and a 9753-110F
to the field.

Termination panel
REV A 7400143-
+24 VDC
SN

E
C
32

30

28
26
24
22
*
J1

20
18
2A (IN1 +)
16
14
Active
12 Pulse
10 Sensor
8
6 2E (IN1 –)
4
2
A

E
C

TM
DIDO PANEL TRICONEX

RTN

* Quiet Earth
Figure 40 Field Wiring for 9753-110F with a 3515 Pulse Totalizer Input Module

With the 3515 pulse totalizer input module, sensor pulse outputs should be the push-pull type.
You may use high-side or low-side, solid-state output, but maximum frequency may be reduced
based on cable distance. Do not use mechanical relay/switch contacts. To prevent point-to-
point cross-talk, use individually shielded, twisted-pair wire for lengths greater than 50 feet (15
meters).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input and Pulse Totalizer Input Term Panels 75

Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
9753-110F (1 of 8 module points shown).

TERMINATION CABLE BACKPLANE 8-POINT PULSE INPUT MODULES


PANEL

to
spare Comparator
AC coupled A
Counter/ Micro-
Timer Processor

to
other
points
IN1

IN1

Comparator
AC coupled B
Counter/ Micro-
Timer Processor

to
other
points

Comparator
AC coupled
C
Counter/ Micro-
Timer Processor

to
other
points

Figure 41 Simplified Schematic of a 3510 or 3511 PI Module with a 9753-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
76 Chapter 3 Digital Input Termination Panels

This is a simplified schematic of a typical 32-point non-commoned pulse totalizer input module
with a 9753-110F (1 of 32 module points shown).

TERMINATION CABLE BACKPLANE 32-POINT TOTALIZER INPUT MODULE


PANEL

AC/DC Input Circuit

Leg-to-
Leg
Isolation To
Threshold Counters
Detect
Opto-Isolator Leg A

IN

IN To
Threshold Counters
Detect
Opto-Isolator Leg B

To
Threshold Counters
to Detect
spare Opto-Isolator Leg C
module

Figure 42 Simplified Schematic of a 3515 Pulse Totalizer Input Module with a 9753-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 77

Bypass Term Panels


This section describes bypass term panels, which are available for 32-point and 64-point digital
input modules.
Model numbers of these term panels are:
• BP9228-010F (24 V, bypass, 32 pts., for 32 pt. modules)
• BP9229-010F (24 V, bypass, 32 pts., for 64 pt. modules)
This figure represents a typical 32-point bypass termination panel that is compatible with
32-point digital input modules.

FRONT
2 AMP
250V

BLOWN
FUSE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
ON

OFF
TRICONEX

REAR

TB2
P2 1 2 3 4 5 6 P1
TB4 TB5
+24 RTN GND +24 RTN GND

TB3
1 2

Figure 43 Typical 32-Point Bypass Term Panel for 32-Point DI Modules

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
78 Chapter 3 Digital Input Termination Panels

This figure represents a typical 32-point bypass termination panel that is compatible with
64-point digital input modules.

FRONT
2 AMP
250V

BLOWN
FUSE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
ON

OFF
TRICONEX

REAR

TB2
1 2 3 4 5 6

P1 TB4 TB5
+24 RTN GND +24 RTN GND

TB3
1 2

Figure 44 Typical 32-Point Bypass Term Panel for 64-Point DI Modules

For more description of bypass termination panels, see Bypass Panel for Digital Inputs on
page 5.

BP9228-010F (24 V, bypass, 32 pts., for 32 pt. modules)


Termination panel BP9228-010F is compatible with 24 VAC/VDC and 24 VDC digital input
modules, has 32 input points, and is supplied with two interface cables.
The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x 482.5
mm) and complies with EIA Standard RS-310-C. Each cable is keyed to the appropriate digital
input module. P1 connects points 1-16, and P2 connects points 17-32. A 6-terminal barrier strip
has terminals for redundant 24 VDC power with diode ORing provided on the panel. Each
screw terminal accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to
3.3 mm2) wires.

Specifications
This table describes specifications for BP9228-010F.

Table 48 Specifications for Term Panel BP9228-010F


Feature Description
Panel type Bypass
Points 32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 79

Compatible Modules
This table describes digital input modules compatible with BP9228-010F.

Table 49 Modules Compatible with BP9228-010F


Module Model Points per
Module Description
Number Module
3503E 32 24 VAC/VDC, commoned in groups of 8 with self-test
3505E 32 24 VDC, low-threshold, commoned in groups of 8 with self-test

Field Wiring Diagrams


This figure illustrates how to connect a 32-point digital input module and a BP9228-010F.
(optional)
+24 VDC +24 VDC
Power Power
Supply Supply

REAR

TB2
P2 1 2 3 4 5 6 P1
TB4 TB5
+24 RTN GND +24 RTN GND

TB3
1 2

Protective earth
(AC safety ground)

Figure 45 Field Wiring for BP9228-010F with a 3503E or 3505E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
80 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module with a BP9228-010F (1
of 32 module points shown).

BYPASS PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST

+24V LED

4 AC/DC Input Circuit


Keyswitch
Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
LED
Opto-Isolator Mux A
to
other
Bypass points
switch Test
A
RTN
2
Threshold to
5 Detect Input
Opto-Isolator Mux B

Test
B
3

Threshold to
to Input
Detect
AC safety spare
ground module Opto-Isolator Mux C

Test
C

Figure 46 Simplified Schematic of a 3503E or 3505E DI Module with a BP9228-010F Panel

BP9229-010F (24 V, bypass, 32 pts., for 64 pt. modules)


Termination panel BP9229-010F is compatible with 24 VDC digital input modules and has 32
input points.
The panel is 3.5 inches high, 4.0 inches deep, and 19 inches wide (88.9 mm x 101.6 mm x
482.5 mm), and complies with EIA Standard RS-310-C. The cable is keyed to the appropriate
digital input module. P1 connects points 1-32. A 6-terminal barrier strip has terminals for
redundant 24 VDC power with diode ORing provided on the panel. Each screw terminal
accepts either #6 ring-lug terminals, or 24-gauge to 12-gauge (0.2 mm2 to 3.3 mm2) wires.
The modules compatible with BP9229-010F have 64 points, which means you must use two term
panels for each digital input module.

Specifications
This table describes specifications for BP9229-010F.

Table 50 Specifications for Term Panel BP9229-010F


Feature Description
Panel type Bypass
Points 32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Bypass Term Panels 81

Compatible Modules
This table describes digital input modules compatible with BP9229-010F.

Table 51 Modules Compatible with BP9229-010F


Module Model Points per
Module Description
Number Module
3504E 64 24 VDC, commoned

Field Wiring Diagrams


This figure illustrates how to connect a 64-point digital input module and a BP9229-010F.
(optional)
+24 VDC +24 VDC
Power Power
Supply Supply

REAR

TB2

1 2 3 4 5 6
P1 TB4 TB5

+24 RTN GND +24 RTN GND

TB3
1 2

Protective earth
(AC safety ground)

Figure 47 Field Wiring for BP9229-010F with a 3504E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
82 Chapter 3 Digital Input Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 64-point digital input module with a BP9229-010F (1
of 32 module points shown).

BYPASS PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

+24V LED3

1 Mux

1
4 Amp ADC

Keyswitch
64

Hi-Ref
LED4 Low-Ref
to
other Mux
Bypass points
switch
1
RTN
Amp ADC

2
64
5
Hi-Ref
Low-Ref

Mux

3 1
Amp ADC
6

64
to
AC safety spare
ground module Hi-Ref
Low-Ref

Figure 48 Simplified Schematic of a 3504E DI Module with a BP9229-010F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
4
Digital Output Termination Panels

Overview 84
8-Point Commoned Digital Output Term Panels 84
16-Point Commoned Digital Output Term Panels 99
16-Point Non-Commoned Digital Output Term Panels 122
Basic Digital Output Term Panels 137
Commoned Interposing Relay Term Panels 151
Non-Commoned Interposing Relay Term Panels 167

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
84 Chapter 4 Digital Output Termination Panels

Overview
This chapter describes external field termination panels you can use with digital output
modules. Digital output termination panels are available in these configurations:
• 8-point commoned
• 16-point commoned
• Non-commoned
• Basic
• Commoned interposing relay
• Non-commoned interposing relay

8-Point Commoned Digital Output Term Panels


This section describes 8-point commoned digital output term panels, which are available in AC
versions or DC versions. Model numbers of these term panels are:
• 9661-510F (115 VAC, commoned, 8 pts.)
• 9661-810F (120 VDC, commoned, 8 pts.)
• 9662-710F (24 VDC low-power, commoned, 8 pts.)
• 9662-910F (24 VDC, commoned, 8 pts.)
• 9667-910F (48 VDC, commoned, 8 pts.)
This figure represents a typical 8-point commoned AC digital output termination panel with
fuses and blown-fuse indicators.

SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+
L–

L–
PS1

PS2

CR8

CR6

CR3

Figure 49 Typical 8-Point Commoned AC DO Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 85

This figure represents a typical 8-point commoned DC digital output termination panel with
fuses and blown-fuse indicators.

SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

Figure 50 Typical 8-Point Commoned DC DO Term Panel

This table identifies primary and secondary fuse locations for each output point on an 8-point
commoned digital output term panel.

Table 52 Fuse Identification for 8-Point Commoned DO Term Panels


Primary Secondary
Point
Fuse Fuse
1 F1 F9
2 F2 F10
3 F3 F11
4 F4 F12
5 F5 F13
6 F6 F14
7 F7 F15
8 F8 F16

9661-510F (115 VAC, commoned, 8 pts.)


Termination panel 9661-510F is compatible with 115 VAC digital output modules and has 8 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
86 Chapter 4 Digital Output Termination Panels

Specifications
This table describes specifications for 9661-510F.

Table 53 Specifications for Term Panel 9661-510F


Feature Description
Panel type Commoned
Points 8

Compatible Modules
This table describes digital output modules compatible with 9661-510F.

Table 54 Modules Compatible with 9661-510F


Module Model Points per Primary Secondary
Module Description
Number Module Fuse Fuse
3611E 8 115 VAC, commoned, supervised, 2.5A, fast None
galvanically-isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point supervised AC digital output module with
shorted load detection and a 9661-510F to the field.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+
L–

L–

Load*
PS1

PS2

CR8

CR6

CR3

PS1
Hot
AC
Power
Neutral
Supply

* A load must be installed at every point to prevent missing-load alarm.


If a field is not available, install a 2.2 kilohms, 10 W load resistor.

Figure 51 Field Wiring for 9661-510F with a 3611E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 87

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised AC digital output
module with a commoned digital output panel (1 of 8 points shown).

8-POINT SUPERVISED AC DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

to
Voltage Voltage hot
spare
LED *
Loopback Sensor
A 2.5A, fast
Output PS1 +
Switch
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
Drive
Circuitry Voltage/ Voltage/
Current Current
B
Sensor Sensor
L–
Output
Switch PS1 –
Drive
to other
Circuitry C A C points

C
Output
Switch
Drive
Circuitry Voltage Voltage
Loopback Sensor

* LEDs are blown-fuse indicators

Figure 52 Simplified Schematic of a 3611E DO Module with a Commoned DO Panel

9661-810F (120 VDC, commoned, 8 pts.)


Termination panel 9668-810F is compatible with 120VDC digital output modules and has 8 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9661-810F.

Table 55 Specifications for Term Panel 9661-810F


Feature Description
Panel type Commoned
Points 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
88 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9661-810F.

Table 56 Modules Compatible with 9661-810F


Module Model Points per Primary Secondary
Module Description
Number Module Fuse Fuse
3613E 8 120 VDC, commoned, supervised, 1A, fast 0.125A, fast
galvanically-isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point supervised DC digital output module and a
9661-810F to the field without shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+

Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 2.2 kilohms, 10 W load resistor.

Figure 53 Field Wiring for 9661-810F with a 3613E Module and No Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 89

This figure illustrates how to connect an 8-point supervised DC digital output module and a
9661-810F to the field with shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7

1
2
3
4
5
6
7
8
L+

L+
Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

PS3
+5 VDC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 2.2 kilohms, 10 W load resistor.

Figure 54 Field Wiring for 9661-810F with a 3613E Module and Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
90 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).

8-POINT SUPERVISED DC DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +

C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare

* LEDs are blown-fuse indicators

Figure 55 Simplified Schematic of a 3613E DO Module with a Commoned DO Panel

9662-710F (24 VDC low-power, commoned, 8 pts.)


Termination panel 9662-710F is compatible with 24 VDC low-power digital output modules and
has 8 load terminals and commoned power terminals (PWR+ and PWR–). Each output point is
protected by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9662-710F.

Table 57 Specifications for Term Panel 9662-710F


Feature Description
Panel type Commoned
Points 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 91

Compatible Modules
This table describes digital output modules compatible with 9662-710F.

Table 58 Modules Compatible with 9662-710F


Module Model Points per Primary Secondary
Module Description
Number Module Fuse Fuse
3615E 8 24 VDC, low-power, commoned, 0.25A, fast 0.125A, fast
supervised, galvanically-isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-710F to the field without shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+

Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 56 Field Wiring for 9662-710F with a 3615E Module and No Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
92 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-710F to the field with shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1

8
2
3
4
5
6
7
L+

L+
Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

PS3
+5 VDC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 57 Field Wiring for 9662-710F with a 3615E Module and Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 93

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).

8-POINT SUPERVISED DC DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +

C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare

* LEDs are blown-fuse indicators

Figure 58 Simplified Schematic of a 3615E DO Module with a Commoned DO Panel

9662-910F (24 VDC, commoned, 8 pts.)


Termination panel 9662-910F is compatible with 24 VDC digital output modules and has 8 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9662-910F.

Table 59 Specifications for Term Panel 9662-910F


Feature Description
Panel type Commoned
Points 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
94 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9662-910F.

Table 60 Modules Compatible with 9662-910F


Module Model Points per Primary Secondary
Module Description
Number Module Fuse Fuse
3614E 8 24 VDC, commoned, supervised, 1A, fast 0.125A, fast
galvanically-isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-910F to the field without shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+

Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 59 Field Wiring for 9662-910F with a 3614E Module and No Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 95

This figure illustrates how to connect an 8-point supervised DC digital output module and a
9662-910F to the field with shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7

1
2
3
4
5
6
7
8
L+

L+
Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

PS3
+5 VDC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 60 Field Wiring for 9662-910F with a 3614E Module and Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
96 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).

8-POINT SUPERVISED DC DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +

C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare

* LEDs are blown-fuse indicators

Figure 61 Simplified Schematic of a 3614E DO Module with a Commoned DO Panel

9667-910F (48 VDC, commoned, 8 pts.)


Termination panel 9667-910F is compatible with 48 VDC digital output modules and has 8 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9667-910F.

Table 61 Specifications for Term Panel 9667-910F


Feature Description
Panel type Commoned
Points 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8-Point Commoned Digital Output Term Panels 97

Compatible Modules
This table describes digital output modules compatible with 9667-910F.

Table 62 Modules Compatible with 9667-910F


Module Model Points per Primary Secondary
Module Description
Number Module Fuse Fuse
3617E 8 48 VDC, commoned, supervised, 1.25A, fast 0.125A, fast
galvanically-isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point supervised DC digital output module and a
9667-910F to the field without shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16


J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1
2
3
4
5
6
7
8
L+

L+

Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 62 Field Wiring for 9667-910F with a 3617E Module and No Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
98 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect an 8-point supervised DC digital output module and a
9667-910F to the field with shorted load detection.

Termination panel
SN REV A 7300167-

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR9

F1 F3 F5 F7 F9 F11 F13 F15


CR2
CR1
CR7
1

8
2
3
4
5
6
7
L+

L+
Load*
L–

L–
PS1

PS2

SPWR
CR8

CR6

CR3

PS1
DC
Power
Supply

PS2
DC
Power
Supply

PS3
+5 VDC
Power
Supply

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470 ohms, 10 W load resistor.

Figure 63 Field Wiring for 9667-910F with a 3617E Module and Shorted Load Detection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 99

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned supervised DC digital output
module with a commoned digital output panel (1 of 8 points shown).

8-POINT SUPERVISED DC DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

to
Dual
Voltage
Voltage
hot
spare
LED *
Loopback
Sensor
A
Output PS1 +
Switch
PS2 +
Drive A B
Circuitry to other
points
A "C
Output L+
Switch
to other
Drive points
Circuitry Voltage/ Voltage/
L–
Current Current
B
Sensor Sensor PS1 –
Output
LED * PS2 –
Switch
Drive
Circuitry C A C SPWR +

C
to other
Output points
Switch
Drive SPWR –
Circuitry Voltage Voltage
Loopback Sensor
to
hot
spare

* LEDs are blown-fuse indicators

Figure 64 Simplified Schematic of a 3617E DO Module with a Commoned DO Panel

16-Point Commoned Digital Output Term Panels


This section describes 16-point commoned digital output term panels, which are available in AC
versions or DC versions, and with fuses or without fuses. Model numbers of these term panels
are:
• 9661-610F (115 VAC, commoned, 16 pts.)
• 9661-910F (120 VDC, commoned, 16 pts.)
• 9662-610F (24 VDC, commoned, 16 pts.)
• 9662-810F (24 VDC, commoned, 16 pts.)
• 9663-610F (115 VAC, commoned, 16 pts.)
• 9664-810F (120 VDC, commoned, 16 pts.)
• 9667-810F (48 VDC, commoned, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
100 Chapter 4 Digital Output Termination Panels

This figure represents a typical 16-point commoned DC digital output termination panel with
fuses and blown-fuse indicators.

SN REV A 7400166-
CR
1

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR
2

F1 F3 F5 F7 F9 F11 F13 F15


10

12
13
14
15
16
11
9
1
2
3
4
5
6
7
8
L+

L+
L–

L–
PS1

PS2

Figure 65 Typical 16-Point Commoned DC DO Term Panel with Fuses

This figure represents a typical 16-point commoned digital output panel without fuses.
SN REV A 7400166-
CR
1

J1
CR
2

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+

L+
L–

L–
PS1

PS2

Figure 66 Typical 16-Point Commoned DO Term Panel without Fuses

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 101

This figure represents a typical 16-point commoned AC digital output termination panel with
fuses and blown-fuse indicators for the 3601E module.
SN REV A 7400166-

F2 F4 F6 F8 F10 F12 F14 F16

J1
F1 F3 F5 F7 F9 F11 F13 F15

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+

L+
L–

L–
PS1

PS2

Figure 67 Typical 16-Point Commoned AC DO Term Panel with Fuses for 3601E

This figure represents a typical 16-point commoned AC digital output termination panel with
fuses and blown-fuse indicators for the 3601T module.
SN REV A 7400233-
C
A
B

D
H

K
F

J
E

M
N

P
L
R

V
U
S
T
W

Z
X
Y
a

d
b

c
e

f
J1

F2 F4 F6 F8 F10 F12 F14 F16


h

j
m
CR3

n
k

s
r

t
p

w
v

x
u

y
CC
z

AA
BB
DD

JJ
HH
EE
FF
MM
NN
KK
LL

F1 F3 F5 F7 F9 F11 F13 F15


L+

L+
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L-

L-
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1

PS2

Figure 68 Typical 16-Point Commoned AC DO Term Panel with Fuses for 3601E or 3601T

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
102 Chapter 4 Digital Output Termination Panels

9661-610F (115 VAC, commoned, 16 pts.)


Termination panel 9661-610F is compatible with 115 VAC digital output modules and has 16
load terminals and commoned power terminals (PWR+ and PWR–). Each output point is
protected by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9661-610F.

Table 63 Specifications for Term Panel 9661-610F


Feature Description
Panel type Commoned
Points 16
Maximum total current 30 amps

Compatible Modules
This table describes digital output modules compatible with 9661-610F.

Table 64 Modules Compatible with 9661-610F


Module Model Points per Primary
Module Description
Number Module Fuse
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 103

Field Wiring Diagrams


This figure illustrates how to connect the 16-point AC digital output module 3601E and a
9661-610F to the field.

Termination panel
SN REV A 7400166-

F2 F4 F6 F8 F10 F12 F14 F16

J1
F1 F3 F5 F7 F9 F11 F13 F15

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+

L+
L–

L–
PS1

PS2

PS1
AC Hot
Power
Supply Neutral Typical point (1 of 16
points shown)

Load

Figure 69 Field Wiring for 9661-610F with a 3601E Module

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned AC digital output module
with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED *
A
PS1 +
Output (Hot)
Switch
Drive
Circuitry A B to other
points
L+
A "B
Output
Switch
Drive L–
Circuitry
PS1 –
(Neutral)
B to other
points
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators

Figure 70 Simplified Schematic of a 3601E DO Module with a Commoned DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
104 Chapter 4 Digital Output Termination Panels

9661-910F (120 VDC, commoned, 16 pts.)


Termination panel 9661-910F is compatible with 120 VDC digital output modules and has 16
load terminals and commoned power terminals (PWR+ and PWR–). Each output point is
protected by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9661-910F.

Table 65 Specifications for Term Panel 9661-910F


Feature Description
Panel type Commoned
Points 16
Maximum total current 16 amps

Compatible Modules
This table describes digital output modules compatible with 9661-910F.

Table 66 Modules Compatible with 9661-910F


Module Model Points per Primary
Module Description
Number Module Fuse
3603E 16 120 VDC, commoned, opto-isolated, TMR 1A, fast
3623 16 120 VDC, commoned, supervised, opto-isolated, TMR 1A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 105

Field Wiring Diagrams


This figure illustrates how to connect a 16-point DC digital output module and a 9661-910F to
the field (1 of 16 points shown).

Figure 71 Field Wiring for 9661-910F with a 3603E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
106 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect the 16-point supervised DC digital output module 3623
and a 9661-910F to the field (8 of 16 points shown).

Termination panel
SN REV A 7400166-

CR1

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR2

F1 F3 F5 F7 F9 F11 F13 F15

16
1
L+

L+
Load*
L–

L–
PS1

PS2

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* A load must be installed at every point to prevent a missing-load alarm. If a field load is not available,
install a 2.2 kilohms, 10 W load resistor

Figure 72 Field Wiring for 9661-910F with a 3623 Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 107

Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with a
commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output
Switch
Drive L–
Circuitry
PS1 –
to other to other
B points points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs will not turn on if fuses are removed because the 3603E module is commoned and does not require fusing.

Figure 73 Simplified Schematic of a 3603E DO Module with a Commoned DO Panel

This is a simplified schematic of a typical 16-point commoned supervised DC digital output


module with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


OVD Switch #1

A Voltage
B Loopback to other
C Detector points LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators

Figure 74 Simplified Schematic of a 3623 DO Module with a Commoned DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
108 Chapter 4 Digital Output Termination Panels

9662-610F (24 VDC, commoned, 16 pts.)


Termination panel 9662-610F is compatible with 24 VDC digital output modules and has 16 load
terminals and commoned power terminals (PWR+ and PWR–).
When using 32-point modules, you must use two term panels for each digital output module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9662-610F.

Table 67 Specifications for Term Panel 9662-610F


Feature Description
Panel type Commoned
Points 16
Maximum total currenta 16 amps

a. When the 9662-610F panel is used with the Model 3625/A DO Module, the maximum total current is
10 amps per termination panel to limit the power dissipation of the module

Compatible Modules
This table describes digital output modules compatible with 9662-610F.

Table 68 Modules Compatible with 9662-610F


Module Model Points per
Module Description
Number Module
3624 16 24 VDC, commoned, supervised, opto-isolated, self-protected, TMR
3625/Aa 32 24 VDC, commoned, supervised/non-supervised, self-protected, TMR
3664 32 24 VDC, commoned, opto-isolated, self-protected, dual
3674 32 24 VDC, commoned, opto-isolated, self-protected, dual

a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 109

Field Wiring Diagrams


This figure illustrates how to connect a 16-point or 32-point supervised DC digital output
module with self protection and a 9662-610F to the field (1 of 16 points shown).

Termination panel
SN REV A 7400166-

CR1

J1
CR2

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+

L+
Load*
L–

L–
PS1

PS2

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* When using a Model 3624 module, a load must be installed at every point to prevent missing - load alarm. If a field
load is not available, install a 470 ohms, 10 W load resistor.

Figure 75 Field Wiring for 9662-610F with a 3624, 3625, or 3625A Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
110 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect a 32-point DC dual digital output module with self
protection and a 9662-610F to the field (1 of 32 points shown).

Termination panel
SN REV A 7400166-

CR1

J1
CR2

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L+

L+
L–

L–
PS1

PS2

PS1
DC Typical point (1 of 16
Power points shown)
Supply
Load

PS2
DC
Power
Supply

Figure 76 Field Wiring for 9662-610F with a 3664 or 3674 Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 111

Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with
self protection and a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

OVD Switch #1

A Voltage
B Loopback to other
C Detector points

A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 77 Simplified Schematic of a 3624 DO Module with a Commoned DO Panel

This is a simplified schematic of a typical 32-point commoned DC digital output module with
self protection and a commoned digital output panel (1 of 32 points shown).

32-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


A
Output
Switch
Drive
Circuitry PS1 +

PS2 +
A or C *to other to other
A B points points
Output L+
Switch
Drive
Circuitry

L–
B
Output PS1 –
Switch to other
Drive points
Circuitry
PS2 –

C A or C

C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector

* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by termination panels.

Figure 78 Simplified Schematic of a 3625 or 3625A DO Module with a Commoned DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
112 Chapter 4 Digital Output Termination Panels

This is a simplified schematic of a typical 32-point commoned dual DC digital output module
with self protection and a commoned digital output panel (1 of 16 points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

A Voted PS1 +
Output
B PS2 +
Drive
C Circuitry to other
points
L+

A Voted
Drive
B L–
Output
C Circuitry
PS1 –
to other
points PS2 –

A Loopback
B Detector/
C Isolator
to
hot
spare

to other points

Figure 79 Simplified Schematic of a 3664 or 3674 DO Module with a Commoned DO Panel

9662-810F (24 VDC, commoned, 16 pts.)


Termination panel 9662-810F is compatible with 24 VDC digital output modules and has 16 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9662-810F.

Table 69 Specifications for Term Panel 9662-810F


Feature Description
Panel type Commoned
Points 16
Maximum total current 16 amps

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 113

Compatible Modules
This table describes digital output modules compatible with 9662-810F.

Table 70 Modules Compatible with 9662-810F


Module Model Points per Primary
Module Description
Number Module Fuse
3604E 16 24 VDC, non-commoned, opto-isolated, TMR 2.5A, fast

Field Wiring Diagrams


This figure illustrates how to connect the 16-point DC digital output module 3604E and a
9662-810F to the field (1 of 16 points shown).

Figure 80 Field Wiring for 9662-810F with a 3604E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
114 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned DC digital output module
with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
* LEDs are blown-fuse indicators
Figure 81 Simplified Schematic of a 3604E DO Module with a Commoned DO Panel

9663-610F (115 VAC, commoned, 16 pts.)


Termination panel 9663-610F is compatible with 115 VAC digital output modules and has 16
load terminals and commoned power terminals (PWR+ and PWR–). Each output point is
protected by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9663-610F.

Table 71 Specifications for Term Panel 9663-610F


Feature Description
Panel type Commoned
Points 16
Maximum total current 30 amps

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 115

Compatible Modules
This table describes digital output modules compatible with 9663-610F.

Table 72 Modules Compatible with 9663-610F


Module Model Points per Primary
Module Description
Number Module Fuse
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast
3601T 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Wiring Diagrams


This figure illustrates how to connect the 16-point AC digital output module 3601E or 3601T and
a 9663-610F to the field (1 of 16 points shown).

Termination panel
SN REV A 7400233-
C
A
B

D
H

K
F

J
E

M
N

P
L
R

V
U
S
T
W

Z
X
Y
a

d
b

c
e

f
J1

F2 F4 F6 F8 F10 F12 F14 F16


h

j
m
CR3

n
k

s
r

t
p

w
v

x
u

y
CC
z

AA
BB
DD

JJ
HH
EE
FF
MM
NN
KK
LL

F1 F3 F5 F7 F9 F11 F13 F15


L+

L+
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
L-

L-
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1

PS2

PS1
AC Hot
Power
Supply Neutral
Typical point
(1 of 16 points shown)

Load

Figure 82 Field Wiring for 9663-610F with a 3601E or 3601T Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
116 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned AC digital output module
with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED
*
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output 200V 200V 200V
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators


*
Figure 83 Simplified Schematic of a 3601E or 3601T DO Module with a Commoned DO Panel

9664-810F (120 VDC, commoned, 16 pts.)


Termination panel 9664-810F is compatible with 120 VDC digital output modules and has 16
load terminals and commoned power terminals (PWR+ and PWR–). Each output point is
protected by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9664-810F.

Table 73 Specifications for Term Panel 9664-810F


Feature Description
Panel type Commoned
Points 16
Maximum total current 16 amps

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 117

Compatible Modules
This table describes digital output modules compatible with 9664-810F.

Table 74 Modules Compatible with 9664-810F


Module Model Points per Primary
Module Description
Number Module Fuse
3603E 16 120 VDC, commoned, opto-isolated, TMR 1A, fast
3603T 16 120 VDC, commoned, opto-isolated, TMR 1A, fast
3623T 16 120 VDC, commoned, supervised, opto-isolated, TMR 1A, fast

Field Wiring Diagrams


This figure illustrates how to connect the 16-point DC digital output module 3603E or 3603T and
a 9664-810F to the field (1 of 16 points shown).

Figure 84 Field Wiring for 9664-810F with a 3603E or 3603T Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
118 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect the 16-point supervised DC digital output module 3623T
and a 9664-810F to the field (8 of 16 points shown).

Termination panel
SN REV A 7400166-

CR1

F2 F4 F6 F8 F10 F12 F14 F16

J1
CR2

F1 F3 F5 F7 F9 F11 F13 F15

16
1
L+

L+
Load*
L–

L–
PS1

PS2

PS1
DC
Power
Supply

PS2
DC
Power
Supply

* A load must be installed at every point to prevent a missing-load alarm. If a field load is not available,
install a 2.2 kilohms, 10 W load resistor

Figure 85 Field Wiring for 9664-810F with a 3623T Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 119

Simplified Schematics
This is a simplified schematic of a typical 16-point commoned DC digital output module with a
commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output
Switch
Drive L–
Circuitry
PS1 –
to other to other
B points points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs will not turn on if fuses are removed because the 3603E and 3603T modules are commoned and do not require fusing.

Figure 86 Simplified Schematic of a 3603E or 3603T DO Module with a Commoned DO Panel

This is a simplified schematic of a typical 16-point commoned supervised DC digital output


module with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


OVD Switch #1

A Voltage
B Loopback to other
C Detector points LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output OVD Switch #2
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators

Figure 87 Simplified Schematic of a 3623T DO Module with a Commoned DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
120 Chapter 4 Digital Output Termination Panels

9667-810F (48 VDC, commoned, 16 pts.)


Termination panel 9667-810F is compatible with 48 VDC digital output modules and has 16 load
terminals and commoned power terminals (PWR+ and PWR–). Each output point is protected
by a fuse with a blown-fuse indicator.

Specifications
This table describes specifications for 9667-810F.

Table 75 Specifications for Term Panel 9667-810F


Feature Description
Panel type Commoned
Points 16
Maximum total current 16 amps

Compatible Modules
This table describes digital output modules compatible with 9667-810F.

Table 76 Modules Compatible with 9667-810F


Module Model Points per Primary
Module Description
Number Module Fuse
3607E 16 48 VDC, non-commoned, opto-isolated, TMR 1.5A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Commoned Digital Output Term Panels 121

Field Wiring Diagrams


This figure illustrates how to connect the 16-point DC digital output module 3607E and a
9667-810F to the field (1 of 16 points shown).

Figure 88 Field Wiring for 9667-810F with a 3607E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
122 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned DC digital output module
with a commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


LED *
A
Output PS1 +
Switch
Drive PS2 +
Circuitry A B to other
points
L+
A "B
Output
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
* LEDs are blown-fuse indicators
Figure 89 Simplified Schematic of a 3607E DO Module with a Commoned DO Panel

16-Point Non-Commoned Digital Output Term Panels


This section describes non-commoned digital output term panels. Model numbers of these term
panels are:
• 9251-210F (120 VDC, non-commoned, 16 pts., 3603B module)
• 9661-110F (115 VAC, non-commoned, 16 pts.)
• 9662-110F (24 VDC, non-commoned, 16 pts.)
• 9664-110F (115 VAC, non-commoned, 16 pts.)
• 9667-110F (48 VDC, non-commoned, 16 pts.)
• 9668-110F (non-commoned relay output, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 123

This figure represents a typical 16-point non-commoned digital output termination panel for
the 3603B module.

+ – + 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 –

POWER

LOAD

1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

LOAD

POWER

+ – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

Figure 90 Typical 16-Point Non-Commoned DO Term Panel for Module 3603B

This figure represents a typical 16-point non-commoned digital output termination panel for
modules 3601E, 3604E, and 3607E.
SN REV A 7400169-
F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

10 F9

12

13

14

15

16
11
1

9
LOAD
PWR

Figure 91 Typical 16-Point Non-Commoned DO Term Panel for Modules 3601E, 3604E, and 3607E

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
124 Chapter 4 Digital Output Termination Panels

This figure represents a typical 16-point non-commoned digital output termination panel for
module 3601T.
SN REV A 7400234-

F10

F12

F16
F14
F2

F6

F8
F4

A
B
C

D
H
F

K
E

M
N
L

P
R

V
S
T
U
W

Z
X
Y
a

d
b

c
f
e

j
h
l

m
CR5

n
r
s
t
p
v
w
x
u

y
CC
z

AA
BB
DD

JJ
EE
FF
HH
KK
LL
MM
NN
F1 F3 F5 F7 F9 F11 F13 F15

J1
LOAD

10

12

13

14

15

16

LOAD
11
1

10

12

13

14

15

16
11
PWR

PWR
Figure 92 Typical 16-Point Non-Commoned DO Term Panel for Module 3601T

This figure represents a typical 16-point non-commoned relay output termination panel.
SN REV A 7400172-
F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

10 F9

12

13

14

15

16
11
1

9
LOAD
PWR

Figure 93 Typical 16-Point Non-Commoned Relay Output Term Panel

9251-210F (120 VDC, non-commoned, 16 pts., 3603B module)


Termination panel 9251-210F has 16 non-commoned output points and is compatible with only
3603B digital output modules.
The 9251-210F is a 6.75 in. x 8.5 in. termination panel mounted on a 7 in. x 19 in. EIA Standard
#RS-310-C mounting plate with a smoked-plexiglass cover (two pieces) and a 10-foot cable. The
mounting plate has room for two termination panels. If you order a second termination panel
you can mount it on the first mounting plate and save or discard the second mounting plate.
Each output point has a:
• Positive and negative terminal for connecting to a field load.
• Positive and negative terminal for connecting field power.
• Blown-fuse indicator (LED).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 125

Specifications
This table describes specifications for 9251–210.

Table 77 Specifications for Term Panel 9251–210


Feature Description
Panel type Non-commoned
Points 16
Leakage current per point Maximum: 3.3 mA
Typical: 2.5 mA
Torque specification Do not exceed 10 inch-pounds (1.13 Nm) of torque when securing the
#6 screws on the termination panel.

Compatible Modules
This table describes digital output modules compatible with 9251–210.

Table 78 Modules Compatible with 9251–210


Module Model Points per
Module Description Fuse
Number Module
3603B 16 120 VDC, non-commoned, TMR 1A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
126 Chapter 4 Digital Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9251–210 to the
field (1 of 16 points shown).

DC +
Power

Supply

Protective earth
(AC safety ground)

+ – + 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 –

POWER

LOAD

Typical point
1 2 3 4 5 6 7 8
(1 of 16 points shown)

9 10 11 12 13 14 15 16
Load

LOAD

POWER

+ – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

Figure 94 Field Wiring for 9251-210F with a 3603B Module

Each terminal accepts either #6 ring-lug terminals or 24-gauge to 12-gauge (0.3 mm2 to 2.1 mm2)
wires.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 127

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

A
LED
*
Output PWR1 +
Switch
Drive
Circuitry A B

A "B
Output
Switch
Drive
LOAD 1 +
Circuitry

B
Output
Switch
Drive LOAD 1 –
Circuitry A B
C PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators

** Installed on ETP 9251-210

Figure 95 Simplified Schematic of a 3603B DO Module with a Non-Commoned DO Panel

9661-110F (115 VAC, non-commoned, 16 pts.)


Termination panel 9661-110F is compatible with 115 VAC digital output modules and has:
• 16 LOAD+ and LOAD– terminals
• 16 PWR+ and PWR– terminals
• 16 fuses with blown-fuse indicators

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
128 Chapter 4 Digital Output Termination Panels

Specifications
This table describes specifications for 9661-110F.

Table 79 Specifications for Term Panel 9661-110F


Feature Description
Panel type Non-commoned
Points 16

Compatible Modules
This table describes digital output modules compatible with 9661-110F.

Table 80 Modules Compatible with 9661-110F


Module Model Points per
Module Description Fuse
Number Module
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9661-110F to the
field (1 of 16 points shown).

Termination panel
SN REV A 7400169-
F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
1

9
LOAD
PWR

Typical point
+ (1 of 16 points shown)
Power
Supply –
Load

Figure 96 Field Wiring for 9661-110F with a 3601E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 129

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B

A "B
Output
Switch
Drive
LOAD 1 +
Circuitry

B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators


Figure 97 Simplified Schematic of a 3601E DO Module with a Non-Commoned DO Panel

9662-110F (24 VDC, non-commoned, 16 pts.)


Termination panel 9662-110F is compatible with 24 VDC digital output modules and has:
• 16 LOAD+ and LOAD– terminals
• 16 PWR+ and PWR– terminals
• 16 fuses with blown-fuse indicators

Specifications
This table describes specifications for 9662-110F.

Table 81 Specifications for Term Panel 9662-110F


Feature Description
Panel type Non-commoned
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
130 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9662-110F.

Table 82 Modules Compatible with 9662-110F


Module Model Points per
Module Description Fuse
Number Module
3604E 16 24 VDC, non-commoned, opto-isolated, TMR 2.5A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9662-110F to the
field (1 of 16 points shown).

Termination panel
SN REV A 7400169-

F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
1

9
LOAD
PWR

Typical point
+ (1 of 16 points shown)
Power
Supply –
Load

Figure 98 Field Wiring for 9662-110F with a 3604E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 131

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B

A "B
Output
Switch
Drive
LOAD 1 +
Circuitry

B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators


Figure 99 Simplified Schematic of a 3604E DO Module with a Non-Commoned DO Panel

9664-110F (115 VAC, non-commoned, 16 pts.)


Termination panel 9664-110F is compatible with 115 VAC digital output modules and has:
• 16 LOAD+ and LOAD– terminals
• 16 PWR+ and PWR– terminals
• 16 fuses with blown-fuse indicators

Specifications
This table describes specifications for 9664-110F.

Table 83 Specifications for Term Panel 9664-110F


Feature Description
Panel type Non-commoned
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
132 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9664-110F.

Table 84 Modules Compatible with 9664-110F


Module Model Points per
Module Description Fuse
Number Module
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast
3601T 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9664-110F to the
field (1 of 16 points shown).

Termination panel
SN REV A 7400234-
F10

F12

F16
F14
F2

F6

F8
F4

A
B
C

D
H
F

K
E

M
N
L

P
R

V
S
T
U
W

Z
X
Y
a

d
b

c
f
e

j
h
l

m
CR5

n
r
s
t
p
v
w
x
u

y
CC
z

AA
BB
DD

JJ
EE
FF
HH
KK
LL
MM
NN

F1 F3 F5 F7 F9 F11 F13 F15


J1

10

12

13

14

15

16
11
1

9
LOAD

LOAD
10

12

13

14

15

16
11
1

9
PWR

PWR

+
Power Typical point
Supply – (1 of 16 points shown)

Load

Figure 100 Field Wiring for 9664-110F with a 3601E or 3601T Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 133

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

LED *
A
Output PWR1 +
Switch
Drive
Circuitry
A B
200V
A "B
Output
Switch
Drive
LOAD 1 +
Circuitry

B
200V
Output
Switch
Drive LOAD 1 ñ
Circuitry
C A B PWR1 ñ
C
Output
to
Switch hot
Drive spare
A Voltage
Circuitry
B Loopback
C Detector

* LEDs are blown-fuse indicators


Figure 101 Simplified Schematic of a 3601E or 3601T DO Module with a Non-Commoned DO Panel

9667-110F (48 VDC, non-commoned, 16 pts.)


Termination panel 9667-110F is compatible with 48 VDC digital output modules and has:
• 16 LOAD+ and LOAD– terminals
• 16 PWR+ and PWR– terminals
• 16 fuses with blown-fuse indicators

Specifications
This table describes specifications for 9667-110F.

Table 85 Specifications for Term Panel 9667-110F


Feature Description
Panel type Non-commoned
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
134 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9667-110F.

Table 86 Modules Compatible with 9667-110F


Module Model Points per
Module Description Fuse
Number Module
3607E 16 48 VDC, non-commoned, opto-isolated, TMR 1.25A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9667-110F to the
field (1 of 16 points shown).

Termination panel
SN REV A 7400169-

F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
1

9
LOAD
PWR

Typical point
+ (1 of 16 points shown)
Power
Supply –
Load

Figure 102 Field Wiring for 9667-110F with a 3607E Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned Digital Output Term Panels 135

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a non-commoned digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

LED *
A
Output PWR1 +
Switch
Drive
Circuitry A B

A "B
Output
Switch
Drive
LOAD 1 +
Circuitry

B
Output
Switch
Drive LOAD 1 –
Circuitry
C A B PWR1 –
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

* LEDs are blown-fuse indicators


Figure 103 Simplified Schematic of a 3607E DO Module with a Non-Commoned DO Panel

9668-110F (non-commoned relay output, 16 pts.)


Termination panel 9668-110F is a non-commoned relay output panel and has:
• 16 LOAD+ and LOAD– terminals
• 16 PWR+ and PWR– terminals
• 16 fuses
The modules compatible with 9668-110F have 32-points, which means that you must use two
term panels for each relay output module. Each term panel comes with two sets of labels: 1-16
and 17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9668-110F.

Table 87 Specifications for Term Panel 9668-110F


Feature Description
Panel type Non-commoned relay output
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
136 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes relay output modules compatible with 9668-110F.

Table 88 Modules Compatible with 9668-110F


Module Model Points per
Module Description Fuse
Number Module
3636R 32 Non-commoned, simplex, normally open, galvanically- 2.5A, fast
isolated
3636T 32 Non-commoned, simplex, normally open, galvanically- 2.5A, fast
isolated

Field Wiring Diagrams


This figure illustrates how to connect a 32-point relay output module and a 9668-110F to the
field (1 of 32 points shown).

Termination panel
SN REV A 7400172-
F13

F14

F15

F16
F5

F6

F7

F8

J1

F10

F12
F11
F1

F2

F3

F4

F9
10

12

13

14

15

16
11
1

9
LOAD
PWR

Typical point
+ (1 of 16 points shown)
Power
Supply –
Load

Figure 104 Field Wiring for 9668-110F with a 3636R or 3636T Relay Output Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 137

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned relay output module with a
non-commoned relay output panel (1 of 32 points shown).

32-POINT RELAY OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

Point
Register
PWR1 +

+V +V

Voted
Output
Drive
Point Circuitry
Register
LOAD 1 +

Loopback
Detector/
Isolator

LOAD 1 –
Point
Register
PWR1 –

to
spare
module

Figure 105 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Non-Commoned
Relay Output Panel

Basic Digital Output Term Panels


This section describes basic digital output term panels.
Model numbers of these term panels are:
• 9651-110F (basic digital/relay output, 16 pts.)
• 9652-610F (48 VDC, basic, 16 pts.)
• 9653-610F (24 VDC, basic, 16 pts.)
This figure represents a typical 16-point basic digital output/relay output termination panel.

J1
DIDO PANEL

REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8

A A
TM

7400143-

C C
TRICONEX

E E

Figure 106 Typical 16-Point Basic DO and Relay Output Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
138 Chapter 4 Digital Output Termination Panels

9651-110F (basic digital/relay output, 16 pts.)


Termination panel 9651-110F has:
• 16 digital output terminals (LOAD)
• 16 power terminals (PWR)
• 16 return terminals (RTN)
Termination panel 9651-110F is compatible with:
• 115 VAC, 16-point digital output modules
• 120 VDC, 16-point digital output modules
• 32-point relay output modules
Note When using 32-point modules, you must use two term panels for each relay output
module.
When using modules that are not self-protected, it is up to you to provide protection for
all outpoint points.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 139

Specifications
This table describes specifications for 9651-110F.

Table 89 Specifications for Term Panel 9651-110F


Feature Description
Panel type Basic digital output and basic relay output
Points 16

Compatible Modules
This table describes digital output modules and relay output modules compatible with
9651-110F.

Table 90 Modules Compatible with 9651-110F


Module Model Points per
Module Description
Number Module
3601E 16 115 VAC, non-commoned, opto-isolated, TMR
3603E 16 120 VDC, commoned, opto-isolated, TMR
3623 16 120 VDC, commoned, supervised, opto-isolated, TMR
3636R 32 Non-commoned, simplex, normally open, galvanically-isolated
3636T 32 Non-commoned, simplex, normally open, galvanically-isolated

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
140 Chapter 4 Digital Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9651-110F to the
field (1 of 16 points shown).

Termination Panel
REV A 7400143-
AC HOT/+DC
SN
Recommended
A

E
C Wiring Connections
32
30 2.5 A, fast acting
28
26
24
22
Solenoid,
J1

20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4

***
2
A

TM
DIDO PANEL TRICONEX

2A (PWR1) Typical for One-Point


2E (RTN1) *
** AC NEUTRAL/RETURN

* One PWR connection per point is recommended.


** One RTN connection per point is recommended.
*** To prevent missing-load alarm, install a load at each unused point.
If a field load is not available for model 3623, install a 2.2 kilohms, 10 W load resistor.

Figure 107 Field Wiring for 9651-110F with a 3601E, 3603E, or 3623 DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 141

This figure illustrates how to connect a 32-point relay output module and a 9651-110F to the
field (1 of 32 points shown).

+DC
Termination panel
REV A 7400143-
SN 2.5A, slow

E
C
32
Solenoid,
30 2A (C1) 2E (C1) relay, etc.
28
26
24
22
J1

20
18
16
14
12
10
8
6
4
2
A

TM
DIDO PANEL TRICONEX

RETURN

* 37.5
When switching reactive loads, de-rate the output switching power to 25% of maximum (500 VA for AC applications,
W for DC applications). When switching incandescent lamps, use the inrush current when calculating the
required output switching power. For specifications, contact the lamp manufacturer. The inrush current may be
10-15 times the rated nominal load current of the lamp.

Figure 108 Field Wiring for 9651-110F with a 3636R or 3636T Relay Output Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
142 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 109 Simplified Schematic of a 3601E DO Module with a Basic DO Panel

This is a simplified schematic of a typical 16-point commoned digital output module with a
basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

to other
B points
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 110 Simplified Schematic of a 3603E DO Module with a Basic DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 143

This is a simplified schematic of a typical 16-point commoned supervised digital output module
with a basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL
OVD Switch #1

A Voltage
B Loopback to other
C Detector points

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output OVD Switch #2
Switch
Drive RTN1 (2E)
Circuitry

B
Output
to other
Switch points
Drive
Circuitry
C A B

C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 111 Simplified Schematic of a 3623 DO Module with a Basic DO Panel

This is a simplified schematic of a typical 32-point relay output module with a basic digital
output panel (1 of 32 points shown).

32-POINT RELAY OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

to
spare
module
Point
Register

+V +V
2A (C1)

Voted
Output
Drive
Point Circuitry
Register

Loopback
Detector/
Isolator 2E (C1)

Point
Register

Figure 112 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Basic DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
144 Chapter 4 Digital Output Termination Panels

9652-610F (48 VDC, basic, 16 pts.)


Termination panel 9652-610F is compatible with 48 VDC digital output modules and has:
• 16 digital output terminals (LOAD)
• 16 power terminals (PWR)
• 16 return terminals (RTN)
Note
When using modules that are not self-protected, such as the 3607E, it is up to you to provide
protection for all outpoint points.

Specifications
This table describes specifications for 9652-610F.

Table 91 Specifications for Term Panel 9652-610F


Feature Description
Panel type Basic digital output
Points 16

Compatible Modules
This table describes digital output modules compatible with 9652-610F.

Table 92 Modules Compatible with 9652-610F


Module Model Points per
Module Description
Number Module
3607E 16 48 VDC, non-commoned, opto-isolated, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 145

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9652-610F to the
field (1 of 16 points shown).

Termination Panel
REV A 7400143-
AC HOT/+DC
SN
Recommended

E
Wiring Connections

C
32
30 2.5 A, fast acting
28
26
24
22
Solenoid,
J1

20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4

***
2
A

TM
DIDO PANEL TRICONEX

2A (PWR1) Typical for One-Point


2E (RTN1) *
** AC NEUTRAL/RETURN

* One PWR connection per point is recommended.


** One RTN connection per point is recommended.
*** To prevent missing-load alarm, install a load at each unused point.

Figure 113 Field Wiring for 9652-610F with a 3607E DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
146 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 114 Simplified Schematic of a 3607E DO Module with a Basic DO Panel

9653-610F (24 VDC, basic, 16 pts.)


Termination panel 9653-610F is compatible with 24 VDC digital output modules and has:
• 16 digital output terminals (LOAD)
• 16 power terminals (PWR)
• 16 return terminals (RTN)
When using 32-point modules, you must use two term panels for each relay output module.
When using modules that are not self-protected, such as the 3604E, it is up to you to provide
protection for all outpoint points. Modules 3624, 3625, 3625A, 3664, and 3674 have built-in
protection.

Specifications
This table describes specifications for 9653-610F.

Table 93 Specifications for Term Panel 9653-610F


Feature Description
Panel type Basic digital output
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 147

Compatible Modules
This table describes digital output modules compatible with 9653-610F.

Table 94 Modules Compatible with 9653-610F


Module Model Points per
Module Description
Number Module
3604E 16 24 VDC, non-commoned, opto-isolated, TMR
3624 16 24 VDC, commoned, supervised, opto-isolated, self-protected, TMR
3625/Aa 32 24 VDC, commoned, supervised/non-supervised, self-protected, TMR
3664 32 24 VDC, commoned, opto-isolated, self-protected, dual
3674 32 24 VDC, commoned, opto-isolated, self-protected, dual

a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9653-610F to the
field (1 of 16 points shown).

Termination Panel
REV A 7400143-
+DC
SN
Recommended
A

Wiring Connections
C

32
30
28
26
24
22
Solenoid,
J1

20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4

***
2
A

TM
DIDO PANEL TRICONEX

2A (PWR1) Typical for One-Point


2E (RTN1) *
** RETURN

* One
One PWR connection per point is recommended.

****
* To prevent
RTN connection per point is recommended.
missing-load alarm, install a load at each unused point.

Figure 115 Field Wiring for 9653-610F with a 3604E DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
148 Chapter 4 Digital Output Termination Panels

This figure illustrates how to connect a 16-point or 32-point digital output module with self-
protection and a 9653-610F to the field (1 of 16 points shown).

Termination Panel
REV A 7400143-
+DC
SN
Recommended

E
Wiring Connections

C
32
30
28
26
24
22
Solenoid,
J1

20
2C (LOAD1)
18 relay, etc.
16
14
12
10
8
6
4

***
2
A

TM
DIDO PANEL TRICONEX

2A (PWR1) Typical for One-Point


2E (RTN1) *
** RETURN

* One PWR connection per point is recommended.


** One RTN connection per point is recommended.
*** When using a 3624 module, install a load at each unused point to prevent missing-load alarm.

Figure 116 Field Wiring for 9653-610F with a 3624, 3625, or 3625A DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Basic Digital Output Term Panels 149

This figure illustrates how to connect a 32-point dual digital output module with self-protection
and a 9653-610F to the field (1 of 32 points shown).
For proper operation, one PWR connection per point is required.

Termination panel
REV A 7400143-
+DC
SN

E
C
32
30
28
26
24
22
Solenoid,
J1

20
18 relay, etc.
16 2C (LOAD1)
14
12
10
8
6
4 2E (RTN1)
2
A

TM
DIDO PANEL TRICONEX
2A (PWR1)

RETURN
*
* One RTN connection is required. More than one is recommended.

Figure 117 Field Wiring for 9653-610F with a 3664 or 3674 DO Module

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 118 Simplified Schematic of a 3604E DO Module with a Basic DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
150 Chapter 4 Digital Output Termination Panels

This is a simplified schematic of a typical 16-point commoned supervised digital output module
with a basic digital output panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL
OVD Switch #1

A Voltage
B Loopback to other
C Detector points

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output OVD Switch #2
Switch
Drive RTN1 (2E)
Circuitry

B
Output
to other
Switch points
Drive
Circuitry
C A B

C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 119 Simplified Schematic of a 3624 DO Module with a Basic DO Panel

This is a simplified schematic of a typical 32-point commoned supervised digital output module
with a basic digital output panel (1 of 32 points shown).

32-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


A
Output
Switch
Drive
Circuitry PWR1 (2A)

A or C *to other
A B points
Output LOAD1 (2C)
Switch
Drive
Circuitry

RTN1 (2E)
B
Output
Switch
Drive
Circuitry

C A or C

C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector

* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by termination panels.

Figure 120 Simplified Schematic of a 3625 or 3625A DO Module with a Basic DO Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 151

This is a simplified schematic of a typical 32-point commoned dual digital output module with
a basic digital output panel (1 of 32 points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE TERMINATION


PANEL

A Voted PWR1 (2A)


Output
B
Drive
C Circuitry
LOAD1 (2C)

RTN1 (2E)
A Voted
Drive
B
Output
C Circuitry

A Loopback
B Detector/
C Isolator
to
hot
spare

to other points

Figure 121 Simplified Schematic of a 3664 or 3674 DO Module with a Basic DO Panel

Commoned Interposing Relay Term Panels


This section describes commoned interposing relay termination panels. Model numbers of these
panels are:
• 9670-610F (115 VAC, commoned interposing relay, 16 pts.)
• 9671-810F (24 VDC, commoned interposing relay, 16 pts.)
• 9672-810F (48 VDC, commoned interposing relay, 16 pts.)
• 9673-810F (120 VDC, commoned interposing relay, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
152 Chapter 4 Digital Output Termination Panels

This figure represents a typical 16-point commoned interposing relay termination panel.

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

CR1 CR2

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV

R20
R19
R18
p R27
R28
R29
RELAY EXTERNAL TERMINATOR
© 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Figure 122 Typical 16-Point Commoned Interposing Relay Panel

For more description of interposing relay term panels, see Termination Panels with Interposing
Relays on page 4.

9670-610F (115 VAC, commoned interposing relay, 16 pts.)


Termination panel 9670-610F is compatible with 115 VAC digital output modules and has:
• 16 relay points (C and NO)
• 2 terminals (PW1 + and –) for primary power and return
• 2 terminals (PW2 + and –) for redundant power and return
• An individual fuse with blown-fuse indicator for relay coil and loopback circuit
Each terminal accepts either #6 ring-lug terminals or 24-to-12-gauge (0.3mm2 to 2.1mm2) wires.
Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.

Specifications
This table describes specifications for 9670-610F.

Table 95 Specifications for Term Panel 9670-610F


Feature Description
Panel type Commoned interposing relay
Points 16
Relay type Compact, general-purpose power relays with hold-down clamps
Relay contact rating 10A @ 30 VDC or 277 VAC

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 153

Table 95 Specifications for Term Panel 9670-610F (continued)


Feature Description
Relay switching power AC: 2500 VA
(see CAUTION below) DC: 90 W
Relay maximum output Once per scan
cycle rate
Relay expected life at 100,000 operations
maximum rated load
Relay isolation 1000 VAC minimum
1500 VDC minimum
Power consumption per Less than 2 watts
relay

When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.

Compatible Modules
This table describes digital output modules compatible with 9670-610F.

Table 96 Modules Compatible with 9670-610F


Module Model Points per
Module Description Fuse
Number Module
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
154 Chapter 4 Digital Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9670-610F to the
field (1 of 16 points shown).

AC Hot
AC
Power
AC Neutral
Supply

Protective earth
(AC safety ground)

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

CR1 CR2

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
RELAY EXTERNAL TERMINATOR
R19 R28
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Typical point (1 of
Contact #1 16 points shown)
(NO)

Figure 123 Field Wiring for 9670-610F with a 3601E DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 155

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a commoned interposing relay panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

A
*
LED

Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A "B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points

to
spare
module

* LEDs are blown-fuse indicators


Figure 124 Simplified Schematic of a 3601E DO Module with a Commoned Interposing Relay Panel

9671-810F (24 VDC, commoned interposing relay, 16 pts.)


Termination panel 9671-810F is compatible with 24 VDC digital output modules and has:
• 16 relay points (C and NO)
• 2 terminals (PW1 + and –) for primary power and return
• 2 terminals (PW2 + and –) for redundant power and return
• An individual fuse with blown-fuse indicator for relay coil and loopback circuit
When using 32-point modules, you must use two term panels for each digital output module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.
Each terminal accepts either #6 ring-lug terminals or 24-to-12-gauge (0.3mm2 to 2.1mm2) wires.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
156 Chapter 4 Digital Output Termination Panels

Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.

Specifications
This table describes specifications for 9671-810F.

Table 97 Specifications for Term Panel 9671-810F


Feature Description
Panel type Commoned interposing relay
Points 16
Relay type Compact, general-purpose power relays with hold-down clamps
Relay contact rating 10A @ 30 VDC or 277 VAC
Relay switching power AC: 2500 VA
(see CAUTION below) DC: 90 W
Relay maximum output Once per scan
cycle rate
Relay expected life at 100,000 operations
maximum rated load
Relay isolation 1000 VAC minimum
1500 VDC minimum
Power consumption per Less than 2 watts
relay
Torque specification Do not exceed 10 inch-pounds (1.13 Nm) of torque when securing leads
to the #6 terminal.

When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.

Compatible Modules
This table describes digital output modules compatible with 9671-810F.

Table 98 Modules Compatible with 9671-810F


Module Model Points per
Module Description Fuse
Number Module
3604E 16 24 VDC, non-commoned, opto-isolated, TMR 2.5A, fast
3625/Aa 32 24 VDC, commonedb, supervised/non-supervised, 2.5A, fast
self-protected, TMR
3664 32 24 VDC, commoned, opto-isolated, self-protected, dual 2.5A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 157

Table 98 Modules Compatible with 9671-810F (continued)


Module Model Points per
Module Description Fuse
Number Module
3674 32 24 VDC, commoned, opto-isolated, self-protected, dual 2.5A, fast

a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module may
be powered from four independent field power sources, but only if the voltage from those sources is
within 5% of the highest voltage supplied. If this restriction is not followed, the module will still
operate but may experience voter faults and generate an alarm.
b. For the 3625 module, field power is commoned to all points, so that if power is present on one point,
it is present on all points. For the 3625A module, field power is commoned in groups of 16 points and
is separated by termination panels.

Field Wiring Diagrams


This figure illustrates how to connect a 16-point or 32-point digital output module and a
9671-810 to the field (1 of 16 or 32 points shown).

DC
Power
Supply

DC
Power
Supply

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

CR1 CR2

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
R28 RELAY EXTERNAL TERMINATOR
R19
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Typical point (1 of 16 or 32 points shown)


Contact #1
(NO)

Figure 125 Field Wiring for 9671-810F with a 3604E, 3625, 3625A, 3664, or 3674 DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
158 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry C A B
POWER1 ñ
C
Output
PW1 +
Switch
Drive to
A Voltage
Circuitry spare PW1 ñ
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 ñ
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator commoned
points

to
spare
module

* LEDs are blown-fuse indicators

Figure 126 Simplified Schematic of a 3604E DO Module with a Commoned Interposing Relay Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 159

This is a simplified schematic of a typical 32-point commoned digital output module with a
commoned interposing relay panel (1 of 32 points shown).

32-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

A
Output
Switch
Drive
LED *
Circuitry
POWER1 +

CONTACT
A or C A B *to other (1C)
points
Output CONTACT
Switch (1NO)
Drive
Circuitry

B
Output
Switch
Drive
Circuitry

C A or C

C
Current
Output Loopback POWER1 –
Switch Detector
Drive Analog/
Circuitry Digital
Mux
PW1 +
A Voltage
B Loopback to
C Detector hot PW1 –
spare

PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator commoned
points

to
spare
module

* LEDs will not turn on if fuses are removed because the 3625 and 3625A modules are self-protected and do
not require fusing.

Figure 127 Simplified Schematic of a 3625 or 3625A DO Module with a Commoned Interposing Relay
Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
160 Chapter 4 Digital Output Termination Panels

This is a simplified schematic of a typical 32-point non-commoned digital output module with
a commoned interposing relay panel (1 of 32 points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

LED
*
A Voted POWER1 +

B Output
CONTACT
Drive
C (1C)
Circuitry
CONTACT
(1NO)

A Voted
B Output
C Drive
Circuitry

POWER1 –

Loopback PW1 +
Detector/
Isolator to
hot PW1 –
spare

to other points
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points

to
spare
module

* LEDs will not turn on if fuses are removed because the 3664 and 3674 modules are self-protected and do
not require fusing.

Figure 128 Simplified Schematic of a 3664 or 3674 DO Module with a Commoned Interposing Relay
Panel

9672-810F (48 VDC, commoned interposing relay, 16 pts.)


Termination panel 9672-810F is compatible with 48 VDC digital output modules and has:
• 16 relay points (C and NO)
• 2 terminals (PW1 + and –) for primary power and return
• 2 terminals (PW2 + and –) for redundant power and return
• An individual fuse with blown-fuse indicator for relay coil and loopback circuit
Each terminal accepts either #6 ring-lug terminals or 24-to-12-gauge (0.3mm2 to 2.1mm2) wires.
Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 161

Specifications
This table describes specifications for 9672-810F.

Table 99 Specifications for Term Panel 9672-810F


Feature Description
Panel type Commoned interposing relay
Points 16
Relay type Compact, general-purpose power relays with hold-down clamps
Relay contact rating 10A @ 30 VDC or 277 VAC
Relay switching power AC: 2500 VA
(see CAUTION below) DC: 90 W
Relay maximum output Once per scan
cycle rate
Relay expected life at 100,000 operations
maximum rated load
Relay isolation 1000 VAC minimum
1500 VDC minimum
Power consumption per Less than 2 watts
relay
Torque specification Do not exceed 10 inch-pounds (1.13 Nm) of torque when securing the
#6 screws on the termination panel.

When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
162 Chapter 4 Digital Output Termination Panels

Compatible Modules
This table describes digital output modules compatible with 9672-810F.

Table 100 Modules Compatible with 9672-810F


Module Model Points per
Module Description Fuse
Number Module
3607E 16 48 VDC, non-commoned, opto-isolated, TMR 1.25A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9672-810F to the
field (1 of 16 points shown).

DC
Power
Supply

DC
Power
Supply

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

CR1 CR2

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
R28 RELAY EXTERNAL TERMINATOR
R19
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Typical point (1 of 16 or 32 points shown)


Contact #1
(NO)

Figure 129 Field Wiring for 9672-810F with a 3607E DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 163

Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points

to
spare
module

* LEDs are blown-fuse indicators

Figure 130 Simplified Schematic of a 3607E DO Module with a Commoned Interposing Relay Panel

9673-810F (120 VDC, commoned interposing relay, 16 pts.)


Termination panel 9673-810F is compatible with 120 VDC digital output modules and has:
• 16 relay points (C and NO)
• 2 terminals (PW1 + and –) for primary power and return
• 2 terminals (PW2 + and –) for redundant power and return
• An individual fuse with blown-fuse indicator for relay coil and loopback circuit
Each terminal accepts either #6 ring-lug terminals or 24-to-12-gauge (0.3mm2 to 2.1mm2) wires.
Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
164 Chapter 4 Digital Output Termination Panels

Specifications
This table describes specifications for 9673-810F.

Table 101 Specifications for Term Panel 9673-810F


Feature Description
Panel type Commoned interposing relay
Points 16
Relay type Compact, general-purpose power relays with hold-down clamps
Relay contact rating 10A @ 30 VDC or 277 VAC
Relay switching power AC: 2500 VA
(see CAUTION below) DC: 90 W
Relay maximum output Once per scan
cycle rate
Relay expected life at 100,000 operations
maximum rated load
Relay isolation 1000 VAC minimum
1500 VDC minimum
Power consumption per Less than 2 watts
relay
Torque specification Do not exceed 10 inch-pounds (1.13 Nm) of torque when securing leads
to the #6 terminal.

When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Commoned Interposing Relay Term Panels 165

Compatible Modules
This table describes digital output modules compatible with 9673-810F.

Table 102 Modules Compatible with 9673-810F


Module Model Points per
Module Description Fuse
Number Module
3603E 16 120 VDC, commoned, opto-isolated, TMR 1A, fast
3603T 16 120 VDC, commoned, opto-isolated, TMR 1A, fast

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9673-810F to the
field (1 of 16 points shown).

DC
Power
Supply

DC
Power
Supply

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

CR1 CR2

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
R28 RELAY EXTERNAL TERMINATOR
R19
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Typical point (1 of 16 or 32 points shown)


Contact #1
(NO)

Figure 131 Field Wiring for 9673-810F with a 3603E or 3603T DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
166 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point DC digital output module with a commoned
interposing relay panel (1 of 16 points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

LED *
A
Output POWER1 +
Switch
CONTACT
Drive (1C)
A B
Circuitry
CONTACT
(1NO)
A B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry C A B
POWER1 –
C
Output
PW1 +
Switch
Drive to
Circuitry
A Voltage
spare PW1 –
B Loopback module
C Detector
PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing to
Threshold Detect other
Opto-Isolator points

to
spare
module

* LEDs will not turn on in fuses are removed because the 3603E and 3603T modules are commoned and do not require fusing.

Figure 132 Simplified Schematic of a 3603E or 3603T DO Module with a Commoned Interposing Relay
Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Non-Commoned Interposing Relay Term Panels 167

Non-Commoned Interposing Relay Term Panels


This section describes non-commoned interposing relay termination panels. Model numbers of
these panels are:
• 9670-110F (115 VAC, non-commoned interposing relay, 16 pts.)
This figure represents a typical 16-point non-commoned interposing relay termination panel.

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
R19 R28 RELAY EXTERNAL TERMINATOR
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Figure 133 Typical 16-Point Non-Commoned Interposing Relay Panel

For more description of interposing relay term panels, see Termination Panels with Interposing
Relays on page 4.

9670-110F (115 VAC, non-commoned interposing relay, 16 pts.)


Termination panel 9670-110F is compatible with 115 VAC digital output modules and has:
• 16 common (C) terminals for connecting to a relay contact
• 16 normally-open (NO) terminals for connecting to a relay contact
• 16 + terminals for connecting +DC or AC hot
• 16 – terminals for connecting DC return or AC neutral
• An individual fuse with blown-fuse indicator for relay coil and loopback circuit
Each terminal accepts either #6 ring-lug terminals or 24-to-12-gauge (0.3mm2 to 2.1mm2) wires.
Relay contacts are not protected by a fuse to allow maximum flexibility for the application. You
must provide the necessary contact protection for your application.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
168 Chapter 4 Digital Output Termination Panels

Specifications
This table describes specifications for 9670-110F.

Table 103 Specifications for Term Panel 9670-110F


Feature Description
Panel type Non-commoned interposing relay
Points 16
Relay type Compact, general-purpose power relays with hold-down clamps
Relay contact rating 10A @ 30 VDC or 277 VAC
Relay switching power AC: 2500 VA
(see CAUTION below) DC: 90 W
Relay maximum output Once per scan
cycle rate
Relay expected life at 100,000 operations
maximum rated load
Relay isolation 1000 VAC minimum
1500 VDC minimum
Power consumption per Less than 2 watts
relay

When switching reactive loads, you should de-rate the switching power of the outputs to 25%
of maximum (625 VA for AC applications or 22.5 watts for DC applications). When switching
incandescent lamps, the inrush current can be 10 to 15 times the rated nominal load current of
the lamp. Use the inrush current to calculate the required output switching power. Contact the
lamp manufacturer for detailed specifications regarding inrush amplitude and duration.

Compatible Modules
This table describes digital output modules compatible with 9670-110F.

Table 104 Modules Compatible with 9670-110F


Module Model Points per
Module Description Fuse
Number Module
3601E 16 115 VAC, non-commoned, opto-isolated, TMR 3A, fast

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Non-Commoned Interposing Relay Term Panels 169

Field Wiring Diagrams


This figure illustrates how to connect a 16-point digital output module and a 9670-110F to the
field (1 of 16 points shown).

Hot
AC
Power
Neutral
Supply

Protective earth
Typical point (1 of (AC safety ground)
16 points shown)

+ 1 – + 2 – + 3 – + 4 – + 5 – + 6 – + 7 – + 8 – + PW1 – + PW2 – + 9 – + 10 – + 11 – + 12 – + 13 – + 14 – + 15 – + 16 –

POWER POWER

F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16

R25 TRICONEX CORP.


R17 R26 ASSY. NO. 7400121- REV
R18 R27
RELAY EXTERNAL TERMINATOR
R19 R28
R20 R29 © 1990 SERIAL NO.
R21 MODEL NUMBER VOLTAGE R30 MADE IN U.S.A.
R22 ISOLATED REDUNDANT DIGITAL OUTPUT R31 DIGITAL INPUT
R23 COMMON R32
R24 RACK/CHASSIS/SLOT
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16

CONTACT CONTACT

C 1 NO C 2 NO C 3 NO C 4 NO C 5 NO C 6 NO C 7 NO C 8 NO C 9 NO C 10 NO C 11 NO C 12 NO C 13 NO C 14 NO C 15 NO C 16 NO

Typical point (1 of
16 points shown)

Figure 134 Field Wiring for 9670-110F with a 3601E DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
170 Chapter 4 Digital Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point AC digital output module with a non-
commoned interposing relay panel (1 of 16 points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE RELAY OUTPUT PANEL

A
LED
*
Output POWER1 +
Switch
CONTACT
Drive
(1C)
Circuitry A B
CONTACT
(1NO)
A "B
Output
Switch
Drive
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C POWER1 –
Output
Switch
Drive PW1 +
A Voltage
Circuitry
B Loopback to
hot PW1 –
C Detector spare

PW2 +
TYPICAL DIGITAL INPUT POINT (OPTIONAL)

PW2 –
Bridge Current-
rectifier limiting
Optical isolation
AC
Smoothing
Threshold Detect
Opto-Isolator

to
spare
module

* LEDs are blown-fuse indicators

Figure 135 Simplified Schematic of a 3601E DO Module with a Non-Commoned Interposing Relay
Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
5
Analog Input and Analog Output
Termination Panels

Overview 172
16-Point Current Input Term Panels 172
32-Point Current Input Term Panels 192
Thermocouple Input Term Panels 202
Voltage Input Term Panels 211
RTD/TC/AI Input Term Panels 223
Analog Output Term Panels 234

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
172 Chapter 5 Analog Input and Analog Output Termination Panels

Overview
This chapter describes external field termination panels you can use with analog input modules
and analog output modules.
Analog input termination panels are available in these configurations:
• Current input
— 16-point
— 16-point, user-configurable
— 32-point
— 32-point, 3-wire
— 32-point, basic
• Thermocouple input
— 16-point
— 32-point
• Voltage input
— 16-point
— 16-point, basic
— 32-point, basic
• Panels for use with signal conditioners, which interface with resistive thermal devices,
thermocouples, and 4-20 mA transmitters (RTD/TC/AI)
Analog output termination panels are available in 8-point current output and 4-point bipolar
output configurations.

16-Point Current Input Term Panels


This section describes 16-point current input term panels. Model numbers of these term panels
are:
• 9761-210F (current input, 0–5 VDC, 16 pts.)
• 9761-410F (current input, 0–10 VDC, 16 pts.)
• 9762-210F (current input, 0–5 VDC, 16 pts.)
• 9762-410F (current input, 0–10 VDC, 16 pts.)
• 9771-210F (current input, 0–5 VDC, user configurable, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 173

This figure represents a typical 16-point current input termination panel.


SN REV A 7400165-

R10

R12

R14

R16
R2

R4

R6

R8
J1

R13

R15
R11
R1

R3

R5

R7

R9
CR1

CR2

10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

Figure 136 Typical 16-Point Current Input Term Panel

This figure represents a typical 16-point, current input, user-configurable, termination panel.

SN REV A 7400195-
W1

W2
W3

W4
W5

W6
W7

W8

W9
W10

W12
W13

W14

W15

W16
W11
W17

R10

R12

R14
R16
R18

R20

R22

R24
R26
R28

R30
R32
R2

R4

R6
R8
J1

R13
R15

R17
R19
R21

R23

R25
R27

R29
R31
R11
R1

R3

R5

R7

R9
CR3

T+

T+
CR2

CR4

PS1 PS2
T-

T-
A

A
CR1

CR5

Figure 137 Typical 16-Point Current Input User-Configurable Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
174 Chapter 5 Analog Input and Analog Output Termination Panels

9761-210F (current input, 0–5 VDC, 16 pts.)


Termination panel 9761-210F is compatible with 0 to 5 VDC analog input modules, -5 to +5 VDC
analog input modules, and HART analog input interface modules. It has 16 power output
terminals (+) and 16 current input terminals (–).
Each positive terminal is current-limited with a 180 ohm series resistor. Each input has a
precision 250 ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9761-210F have 32 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-16 and
17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9761-210F.

Table 105 Specifications for Term Panel 9761-210F


Feature Description
Panel type Current input
Points 16

Compatible Modules
This table describes analog input modules compatible with 9761-210F.

Table 106 Modules Compatible with 9761-210F


Module Model Points per
Module Description
Number Module
2770H 32 HART analog input interface module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 175

Field Wiring Diagrams


This figure illustrates how to connect a 32-point analog input module or a HART analog input
interface module and a 9761-210F to the field (1 of 32 module points shown). See Appendix E,
Shield Ground for shield ground installation guidelines.

NOTICE
HAZARD OF EXCESSIVE HEATING

• Install a 0.5 amp, slow blow, external fuse on PS1+ and PS2+ of each ETP.
Installing an external fuse can help mitigate potential damage if multiple points are shorted simulta-
neously, for example, during a catastrophic failure of a junction box. Note that the ETP can indefi-
nitely tolerate a F+ short to GND on any single point, at 24 V.
• Check the accuracy of an analog input point after it has been damaged by an F– short to 24 V.
Failure to follow these instructions can result in equipment damage.

Termination panel
SN REV A 7400165-
R10

R12

R14

R16
R2

R4

R6

R8
J1

R13

R15
R11
R1

R3

R5

R7

R9
CR1

CR2

10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

PS1 Typical point


(1 of 32 points shown)
DC
Power
Supply +
Field Xmtr
– (4-20 mA)
PS2
DC
Power
Supply

Shield Ground

Figure 138 Field Wiring for 9761-210F with a 3700, 3700A, or 3721 AI Module or a 2770H HART AI
Interface Module

For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
176 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

180 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 139 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9761-210F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 177

This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).

HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE

HART 2071H HART to


CONTROLLER MUX Module spare Mux
Isolation/filtering

1 Amp ADC

180 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
TERMINATION PANEL FIELD
Low-Ref
CABLE

Figure 140 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 AI Module
and a 9761-210F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
178 Chapter 5 Analog Input and Analog Output Termination Panels

9761-410F (current input, 0–10 VDC, 16 pts.)


Termination panel 9761-410F is compatible with 0–10 VDC analog input modules and has 16
power output terminals (+) and 16 current input terminals (–).
Each positive terminal is current-limited with a 180 ohm series resistor. Each input has a
precision 500 ohm resistor for 0–10 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9761-410F have 32 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-16 and
17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9761-410F.

Table 107 Specifications for Term Panel 9761-410F


Feature Description
Panel type Current input
Points 16

Compatible Modules
This table describes analog input modules compatible with 9761-410F.

Table 108 Modules Compatible with 9761-410F


Module Model Points per
Module Description
Number Module
3701 32 0–10 VDC, non-commoned, differential, DC-coupled, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 179

Field Wiring Diagrams


This figure illustrates how to connect a 32-point analog input module and a 9761-410F to the
field (1 of 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400165-

R10

R12

R14

R16
R2

R4

R6

R8
J1

R13

R15
R11
R1

R3

R5

R7

R9
CR1

CR2

16/32
10/26

12/28
13/29
14/30
15/31
11/27
8/24
9/25
1/17
2/18
3/19
4/20
5/21
6/22
7/23
+

+


PS1

PS2

PS1 Typical point


(1 of 32 points shown)
DC
Power
Supply +
Field Xmtr
– (4-20 mA)
PS2
DC
Power
Supply

Shield Ground

Figure 141 Field Wiring for 9761-410F with a 3701 or 3721 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
180 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

180 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
500 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 142 Simplified Schematic of a 3701 or 3721 AI Module with a 9761-410F Panel

9762-210F (current input, 0–5 VDC, 16 pts.)


Termination panel 9762–210 is compatible with 0–5 VDC analog input modules and has 16
power output terminals (+) and 16 current input terminals (–).
Each positive terminal is current-limited with a 180 Ohm series resistor. Each input has a
precision 250 Ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 181

Specifications
This table describes specifications for 9762-210F.

Table 109 Specifications for Term Panel 9762-210F


Feature Description
Panel type Current input
Points 16

Compatible Modules
This table describes analog input modules compatible with 9762-210F.

Table 110 Modules Compatible with 9762-210F


Module Model Points per
Module Description
Number Module
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), non-commoned, differential, isolated, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
182 Chapter 5 Analog Input and Analog Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 16-point analog input module and a 9762-210F to the
field (1 of 16 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400165-

R10

R12

R14

R16
R2

R4

R6

R8
J1

R13

R15
R11
R1

R3

R5

R7

R9
CR1

CR2

16/32
10/26

12/28
13/29
14/30
15/31
11/27
8/24
9/25
1/17
2/18
3/19
4/20
5/21
6/22
7/23
+

+


PS1

PS2

PS1 Typical point


(1 of 16 points shown)
DC
Power
Supply +
Field Xmtr
– (4-20 mA)
PS2
DC
Power
Supply

Shield Ground

Figure 143 Field Wiring for 9762-210F with a 3703E AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 183

Simplified Schematics
This is a simplified schematic of a typical 16 -point non-commoned analog input module with a
current input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux

1 Amp ADC

180 Ohms 16
Hi-Ref
Low-Ref

Mux
to
other
points
250 Ohms 1 Amp ADC

PS1
16
PS2
Hi-Ref

PS1 Low-Ref

PS2
Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 144 Simplified Schematic of a 3703E AI Module with a 9762-210F Panel

9762-410F (current input, 0–10 VDC, 16 pts.)


Termination panel 9762-410F is compatible with 0–10 VDC analog input modules and has 16
power output terminals (+) and 16 current input terminals (–).
Each positive terminal is current-limited with a 180 Ohm series resistor. Each input has a
precision 500 Ohm resistor for 0–10 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.

Specifications
This table describes specifications for 9762-410F.

Table 111 Specifications for Term Panel 9762-410F


Feature Description
Panel type Current input
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
184 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9762-410F.

Table 112 Modules Compatible with 9762-410F


Module Model Points per
Module Description
Number Module
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–10 VDC), non-commoned, differential, isolated, TMR

Field Wiring Diagrams


This figure illustrates how to connect a 16-point analog input module and a 9762-410F to the
field (1 of 16 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400165-
R10

R12

R14

R16
R2

R4

R6

R8
J1

R13

R15
R11
R1

R3

R5

R7

R9
CR1

CR2

10/26

12/28
13/29
14/30
15/31
16/32
11/27
1/17
2/18
3/19
4/20
5/21
6/22
7/23
8/24
9/25
+

+


PS1

PS2

PS1 Typical point


(1 of 16 points shown)
DC
Power
Supply +
Field Xmtr
– (4-20 mA)
PS2
DC
Power
Supply

Shield Ground

Figure 145 Field Wiring for 9762-410F with a 3703E AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 185

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux

1 Amp ADC

180 Ohms 16
Hi-Ref
Low-Ref

Mux
to
other
points
500 Ohms 1 Amp ADC

PS1
16
PS2
Hi-Ref

PS1 Low-Ref

PS2
Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 146 Simplified Schematic of a 3703E AI Module with a 9762-410F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
186 Chapter 5 Analog Input and Analog Output Termination Panels

9771-210F (current input, 0–5 VDC, user configurable, 16 pts.)


Termination panel 9771-210F is compatible with 0 to 5 VDC, 0 to 10 VDC, and -5 to +5 VDC
analog input modules. It has 16 power output terminals (+) and 16 current input terminals (–).
Each positive terminal is current-limited with a 180 Ohm series resistor. Each input has a
precision 250 Ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
When using 32-point modules, you must use two term panels for each analog input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9771-210F.

Table 113 Specifications for Term Panel 9771-210F


Feature Description
Panel type Current input, user-configurable
Points 16

Compatible Modules
This table describes analog input modules compatible with 9771-210F.

Table 114 Modules Compatible with 9771-210F


Module Model Points per
Module Description
Number Module
2770H 32 HART analog input interface module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 187

Field Wiring Diagrams


This figure illustrates how to connect a 16-point or 32-point analog input module and a
9771-210F to the field (1 of 16 or 32 module points shown). See Appendix E, Shield Ground for
shield ground installation guidelines.

NOTICE
HAZARD OF EXCESSIVE HEATING

• Install a 0.5 amp, slow blow, external fuse on PS1+ and PS2+ of each ETP.
Installing an external fuse can help mitigate potential damage if multiple points are shorted simulta-
neously, for example, during a catastrophic failure of a junction box. Note that the ETP can indefi-
nitely tolerate a F+ short to GND on any single point, at 24 V.
• Check the accuracy of an analog input point after it has been damaged by an F– short to 24 V.
Failure to follow these instructions can result in equipment damage.

SN REV A 7400195-
W1

W2
W3

W4
W5

W6
W7

W8

W9
W10

W12
W13
W14

W15

W16
W11
W17

R28

R30
R32
R10

R12

R14
R16
R18

R20

R22

R24
R26
R2

R4

R6
R8
J1

R13
R15

R17
R19
R21

R23

R25
R27

R29
R31
R11
R1

R3
R5

R7

R9
CR3

T+

T+
CR2

CR4

PS1 PS2
T-

T-
A

A
CR1

CR5

PS1 Typical point (1 of 16 points shown)


DC
Power
Supply +
Field Xmtr
PS2 – (4-20 mA)

DC
Power
Supply

Shield Ground

Figure 147 Field Wiring for 9771-210F with a 3700, 3700A, 3703E, or 3721 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
188 Chapter 5 Analog Input and Analog Output Termination Panels

This figure illustrates how to connect a 16-point or 32-point analog input module or a HART
analog input interface module and a 9771-210F to the field and another system, such as a DCS
(1 of 16 or 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

SN REV A 7400195-

W1

W2
W3

W4
W5

W6
W7

W8

W9
W10

W12
W13

W14

W15

W16
W11
This jumper must be
W17

removed in sharing

R10

R12

R14
R16
R18
R20

R22

R24
R26
R28

R30
R32
R2

R4

R6
R8
applications.
J1

R13
R15

R17
R19
R21

R23

R25
R27

R29
R31
R11
R1

R3
R5

R7

R9
CR3

T+

T+
CR2

CR4

PS1 PS2
T-

T-
A

A
CR1

CR5

DCS
*
PS1 Typical point (1 of 16 points shown)
DC
Power
Supply +
Field Xmtr
PS2 – (4-20 mA)

DC
Power
Supply

Shield Ground

* Return may be connected to an unused A terminal with the W jumper in place or to a –PS terminal.

Figure 148 Field Wiring for 9771-210F with a 3700, 3700A, 3703E, or 3721 AI Module or a 2770H HART
AI Interface Module—Sharing with Another System

Sharing a transmitter between the Tricon controller and another system may violate restrictions
regarding the segregation of safety and control functions. The sharing capability of this
termination panel should only be used in those applications where these restrictions do not
exist, or can be otherwise mitigated.
For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 189

Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a current input
panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering
PS1

PS2 1 Amp ADC

180 Ohms
IN 32
Hi-Ref
IN
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux
A

W ** 1 Amp ADC

PS1

PS2
W17 * Hi-Ref
32

Low-Ref

* When the 9771-210F panel is used with a 3700A or a 3721 module, do not remove the W17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the W jumper may be removed.

Figure 149 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9771-210F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
190 Chapter 5 Analog Input and Analog Output Termination Panels

This is a simplified schematic of a typical 16-point analog input module with a current input
panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux
PS1

PS2 1 Amp ADC

180 Ohms
16
IN
Hi-Ref
IN Low-Ref

Mux
to
other
points
250 Ohms 1 Amp ADC

16
A
Hi-Ref
Low-Ref

Mux

W **
1 Amp ADC

PS1 16
W17 * Hi-Ref
PS2
Low-Ref

* For extended common-mode operation, you must remove the W17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the W jumper may be removed.

Figure 150 Simplified Schematic of a 3703E AI Module with a 9771-210F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Current Input Term Panels 191

This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).

HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE

HART 2071H HART


CONTROLLER MUX Module

to
spare Mux
Isolation/filtering
PS1

PS2 1 Amp ADC

180 Ohms
IN 32
Hi-Ref
IN
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux
A

W ** 1 Amp ADC

PS1
W17 * Hi-Ref
32
PS2
Low-Ref
FIELD
TERMINATION PANEL
CABLE

* The W17 jumper must be installed.


** The W1 through W16 jumpers should not be removed when using the 2770H HART AI Interface Module. Sharing
of field transmitters is not allowed.

Figure 151 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 AI Module
and a 9771-210F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
192 Chapter 5 Analog Input and Analog Output Termination Panels

32-Point Current Input Term Panels


This section describes 32-point current input term panels. Model numbers of these term panels
are:
• 9750-210F (current input, 0–5 VDC, basic, 32 pts.)
• 9760-210F (current input, 0–5 VDC, 32 pts.)
• 9760-410F (current input, 0–10 VDC, 32 pts.)
• 9765-210F (3-wire current input, 0–5 VDC, 32 pts.)
This figure represents a typical 32-point current input basic panel.

SN J1
REV A

A
7400144-

E
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8

Figure 152 Typical 32-Point Current Input Basic Term Panel

This figure represents a typical 32-point current input termination panel.

SN REV A 7400150-
R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
10

22
23
12

24
13

25
14

26
15

27
16

28
29
30
31
32
11
1
2
3
4
5
6
7
8
9
PS1

PS2

Figure 153 Typical 32-Point Current Input Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 193

9750-210F (current input, 0–5 VDC, basic, 32 pts.)


Termination panel 9750-210F is compatible with 0–5 VDC analog input modules and has 32
current input terminals (IN+) and commoned return terminals (RTN).
The modules compatible with 9750-210F have 64 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-32 and
33-64. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9750-210F.

Table 115 Specifications for Term Panel 9750-210F


Feature Description
Panel type Current input, basic
Points 32

Compatible Modules
This table describes analog input modules compatible with 9750-210F.

Table 116 Modules Compatible with 9750-210F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), commoned, high-density, DC-coupled, TMR
3720 64 0–5 VDC, single-ended, high-density, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
194 Chapter 5 Analog Input and Analog Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 64-point analog input module and a 9750-210F to the
field (1 of 64 module points shown).

Termination panel
+24 VDC
7400144-
REV A

32
30 50 mA, fast acting or Typical 2 of 32
28 180 Ohm, 3W resistor points shown
26
24
22
J1

20
18
50 mA, fast acting or Field
Xmtrs
16
180 Ohm, 3W resistor
14
(4-20 mA)
12
10
8 4E (IN2 +)
6
4
2
SN

E
C

2A (IN1 +)

2
14C to 32C (RTN)
*
RTN

* One RTN connection is required. More than one is okay

Figure 154 Field Wiring for 9750-210F with a 3704E or 3720 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 195

Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a basic current
input panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY ANALOG INPUT MODULE

Mux
to
spare 1
Amp ADC

IN1 + 64

250 Ohms (0-5V) Hi-Ref


Low-Ref
IN1 –
Mux
to
other 1
points Amp ADC

64

Hi-Ref
Low-Ref

Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Figure 155 Simplified Schematic of a 3704E or 3720 AI Module with a 9750-210F Panel

9760-210F (current input, 0–5 VDC, 32 pts.)


Termination panel 9760-210F is compatible with 0–5 VDC analog input modules and has 32
power output terminals (+) and 32 current input terminals (–).
Each positive terminal is current-limited with a 180 Ohm series resistor. Each input has a
precision 250 Ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9760-210F have 64 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-32 and
33-64. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9760-210F.

Table 117 Specifications for Term Panel 9760-210F


Feature Description
Panel type Current input
Points 32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
196 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9760-210F.

Table 118 Modules Compatible with 9760-210F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), commoned, high-density, DC-coupled, TMR
3720 64 0–5 VDC, single-ended, high-density, TMR

Field Wiring Diagrams


This figure illustrates how to connect a 64-point analog input module and a 9760-210F to the
field (1 of 64 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400150-
R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9

p
PS1

PS2

PS1 Typical point


(1 of 32 points shown)
DC
Power
Supply +
Field Xmtr
PS2 – (4-20 mA)

DC
Power
Supply

Shield Ground

Figure 156 Field Wiring for 9760-210F with a 3704E or 3720 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 197

Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a current input
panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT ANALOG INPUT MODULE

Mux
to
spare 1
Amp ADC

180 Ohms 64

Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms 1
Amp ADC

PS1 64

PS2
Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Figure 157 Simplified Schematic of a 3704E or 3720 AI Module with a 9760-210F Panel

9760-410F (current input, 0–10 VDC, 32 pts.)


Termination panel 9760-410F is compatible with 0–10 VDC analog input modules and has 32
power output terminals (+) and 32 current input terminals (–).
Each positive terminal is current-limited with a 180 Ohm series resistor. Each input has a
precision 500 ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9760-410F have 64 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-32 and
33-64. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9760-410F.

Table 119 Specifications for Term Panel 9760-410F


Feature Description
Panel type Current input
Points 32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
198 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9760-410F.

Table 120 Modules Compatible with 9760-410F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–10 VDC), commoned, high-density, DC-coupled, TMR

Field Wiring Diagrams


This figure illustrates how to connect a 64-point analog input module and a 9760-410F to the
field (1 of 64 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400150-
R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8

J1
CR1

CR2

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
PS1

PS2

PS1 Typical point


(1 of 32 points shown)
DC
Power
Supply +
Field Xmtr
PS2 – (4-20 mA)

DC
Power
Supply

Shield Ground

Figure 158 Field Wiring for 9760-410F with a 3704E AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 199

Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a current input
panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT ANALOG INPUT MODULE

Mux
to
spare 1
Amp ADC

180 Ohms 64

Hi-Ref
Low-Ref

to Mux
other
points
500 Ohms 1
Amp ADC

PS1 64

PS2
Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Figure 159 Simplified Schematic of a 3704E AI Module with a 9760-410F Panel

9765-210F (3-wire current input, 0–5 VDC, 32 pts.)


Termination panel 9765-210F is a 3-wire current input panel, which is compatible with 0–5 VDC
analog input modules. Each panel has:
• 32 output terminals (T+) for the input terminal of a 3-wire 4–20 mA field transmitter. A
500 mA fast-acting fuse protects each terminal.
• 32 input terminals (T–) for the output terminal of a 4–20 mA field transmitter. A 50 mA
fast-acting fuse protects the precision current-to-voltage resistor.
• 32 return terminals (RTN) for the return terminal of a 3-wire 4–20 mA field transmitter.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9765-210F have 64 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-32 and
33-64. For information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
200 Chapter 5 Analog Input and Analog Output Termination Panels

Specifications
This table describes specifications for 9765-210F.

Table 121 Specifications for Term Panel 9765-210F


Feature Description
Panel type 3-wire current input
Points 32
Leakage current per point Maximum: 3.5 mA
Typical: 2.0 mA
Maximum total current 12 amps

Compatible Modules
This table describes analog input modules compatible with 9765-210F.

Table 122 Modules Compatible with 9765-210F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), commoned, high-density, DC-coupled, TMR
3720 64 0–5 VDC, single-ended, high-density, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Current Input Term Panels 201

Field Wiring Diagrams


This figure illustrates how to connect a 64-point, 3-wire analog input module and a 9765-210F
to the field (1 of 64 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400153-

J1
CR1

CR2

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
T+

T+

T+

T+
T–

T–

T–

T–
RTN

RTN

RTN

RTN
PS1

PS2

PS1 Typical point


DC (1 of 32 points shown)
Power
Supply T+
T– Field Xmtr
PS2 RTN (4-20 mA)
DC
Power
Supply

Shield Ground

Figure 160 Field Wiring for 9765-210F with a 3704E or 3720 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
202 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 64-point, 3-wire analog input module with a current
input panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT ANALOG INPUT MODULES

to
spare
Mux
50 mA
1
T Amp ADC
Isolation/
250 filtering
Ohms 64
500 mA
T
Hi-Ref
Low-Ref

12K
RTN
LED * to
Mux

other 1
points Amp ADC

PS1 64

PS2 Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

*LEDs are blown-fuse indicators.

Figure 161 Simplified Schematic of a 3704E or 3720 AI Module with a 9765-210F Panel

Thermocouple Input Term Panels


This section describes thermocouple input term panels. Model numbers of these term panels
are:
• 9765-610F (TC input, upscale/downscale, 16 pts.)
• 9766-210F (TC input, upscale, 16 pts.)
• 9766-510F (TC input, downscale, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 203

This figure represents a typical 16-point thermocouple input termination panel.

SN REV A 7400171-

J1

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+

+


Figure 162 Typical 16-Point Thermocouple Input Term Panel

9765-610F (TC input, upscale/downscale, 16 pts.)


Termination panel 9765-610F is compatible with isolated thermocouple input modules. Each
panel has:
• 16 thermocouple input points
• TMR cold-junction temperature sensors
• Upscale/downscale open-input bias circuitry

Specifications
This table describes specifications for 9765-610F.

Table 123 Specifications for Term Panel 9765-610F


Feature Description
Panel type Thermocouple input, upscale or downscale
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
204 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes thermocouple input modules compatible with 9765-610F.

Table 124 Modules Compatible with 9765-610F


Module Model Points per
Module Description
Number Module
3708E 16 Type E, J, K, and T, differential, isolated, DC-coupled, TMR, upscale
or downscale open-input detection. (Use the TriStation 1131 software
to configure the thermocouple type and specify upscale or downscale
open-input detection.)

Field Wiring Diagrams


This figure illustrates how to connect a 16-point thermocouple input module and a 9765-610F to
the field (1 of 16 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400171-
J1

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+

+

Typical unused point

Typical point
(1 of 16 points shown)
+

Shield Ground

Figure 163 Field Wiring for 9765-610F with a 3708E Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 205

Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 164 Simplified Schematic of a 3708E Thermocouple Input Module with a 9765-610F Panel

9766-210F (TC input, upscale, 16 pts.)


Termination panel 9766-210F is compatible with non-isolated thermocouple input modules.
Each panel has:
• 16 thermocouple input points
• TMR cold-junction temperature sensors
• Upscale open-input bias circuitry
The modules compatible with 9766-210F have 32 points, which means you must use two term
panels for each thermocouple input module. Each term panel comes with two sets of labels: 1-
16 and 17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
206 Chapter 5 Analog Input and Analog Output Termination Panels

Specifications
This table describes specifications for 9766-210F.

Table 125 Specifications for Term Panel 9766-210F


Feature Description
Panel type Thermocouple input, upscale
Points 16

Compatible Modules
This table describes thermocouple input modules compatible with 9766-210F.

Table 126 Modules Compatible with 9766-210F


Module Model Points per
Module Description
Number Module
3706A 32 Type J, K, and T, differential, non-isolated, DC-coupled, TMR, upscale
open-input detection. (Use the TriStation 1131 software to configure
the thermocouple type.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 207

Field Wiring Diagrams


This figure illustrates how to connect a 32-point thermocouple input module and a 9766-210F to
the field (1 of 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400171-

J1

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+

+

Typical unused point

Typical point
(1 of 16 points shown)
+

Shield Ground

Figure 165 Field Wiring for 9766-210F with a 3706A Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
208 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux
Isolation/filtering
+V
1 Amp ADC

22M

32
Hi-Ref
Low-Ref

22M
Mux

–V

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 166 Simplified Schematic of a 3706A Thermocouple Input Module with a 9766-210F Panel

9766-510F (TC input, downscale, 16 pts.)


Termination panel 9766-510F is compatible with non-isolated thermocouple input modules.
Each panel has:
• 16 thermocouple input points
• TMR cold-junction temperature sensors
• Downscale open-input bias circuitry
The modules compatible with 9766-510F have 32 points, which means you must use two term
panels for each thermocouple input module. Each term panel comes with two sets of labels: 1-
16 and 17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Thermocouple Input Term Panels 209

Specifications
This table describes specifications for 9766-510F.

Table 127 Specifications for Term Panel 9766-510F


Feature Description
Panel type Thermocouple input, downscale
Points 16

Compatible Modules
This table describes thermocouple input modules compatible with 9766-510F.

Table 128 Modules Compatible with 9766-510F


Module Model Points per
Module Description
Number Module
3706A 32 Type J, K, and T, differential, non-isolated, DC-coupled, TMR,
upscale open-input detection. (Use the TriStation 1131 software to
configure the thermocouple type.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
210 Chapter 5 Analog Input and Analog Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 32-point thermocouple input module and a 9766-510F to
the field (1 of 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

Termination panel
SN REV A 7400171-
J1

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+

+

Typical unused point

Typical point
(1 of 16 points shown)
+

Shield Ground

Figure 167 Field Wiring for 9766-510F with a 3706A Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 211

Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux
Isolation/filtering

–V
1 Amp ADC

22M

32
Hi-Ref
Low-Ref

22M
Mux

+V

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 168 Simplified Schematic of a 3706A Thermocouple Input Module with a 9766-510F Panel

Voltage Input Term Panels


This section describes 16-point and 32-point voltage input term panels. Model numbers of these
term panels are:
• 9750-810F (0–5 VDC/0–10 VDC voltage input, basic, 32 pts.)
• 9753-110F (0–5 VDC/0–10 VDC voltage input, basic, 16 pts.)
• 9763-810F (0–5 VDC/0–10 VDC voltage input, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
212 Chapter 5 Analog Input and Analog Output Termination Panels

This figure represents a typical 16-point voltage input basic termination panel.

J1
DIDO PANEL

REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8

A A
TM
TRICONEX

7400143-
C C

E E

Figure 169 Typical 16-Point Voltage Input Basic Term Panel

This figure represents a typical 16-point voltage input termination panel.

SN REV A 7400171-
J1

10

12
13
14
15
16
11
1
2
3
4
5
6
7
8
9
+

+

Figure 170 Typical 16-Point Voltage Input Term Panel

This figure represents a typical 32-point voltage input basic termination panel.

SN J1
REV A

A
7400144-

E
10
12
14
16
18
20
22
24
26
28
30

32
2
4
6
8

Figure 171 Typical 32-Point Voltage Input Basic Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 213

9750-810F (0–5 VDC/0–10 VDC voltage input, basic, 32 pts.)


Termination panel 9750-810F is compatible with 0–5 VDC or 0–10 VDC analog input modules
and has 32 voltage input terminals (IN+ and IN–) and commoned return terminals (RTN).
The modules compatible with 9750-810F have 64 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-32 and
33-64. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9750-810F.

Table 129 Specifications for Term Panel 9750-810F


Feature Description
Panel type Voltage input, basic
Points 32

Compatible Modules
This table describes analog input modules compatible with 9750-810F.

Table 130 Modules Compatible with 9750-810F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC or 0-10 VDC), commoned, high-density, DC-coupled,
TMR
3720 64 0-5 VDC, single-ended, high-density, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
214 Chapter 5 Analog Input and Analog Output Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 64-point analog input module and a 9750-810F to the
field (1 of 64 module points shown).

RTN
Termination panel

7400144-
REV A
Typical
unused point
32

30
28 Typical 1 of 32
26 points shown
24
3720: 18C to 32C
(FGND)
22
J1

20
3704E: 14C to 32C
18
(RTN) V 0-5 or 0-10 VDC
16
14
12
10
8
6
4
2
SN

C
A

2A (IN1)

Figure 172 Field Wiring for 9750-810F with a 3704E or 3720 AI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 215

Simplified Schematics
This is a simplified schematic of a typical 64-point analog input module with a basic current
input panel (1 of 64 module points shown).

TERMINATION CABLE BACKPLANE 64-POINT HIGH-DENSITY ANALOG INPUT MODULE


PANEL

Mux
to
spare 1
Amp ADC

IN1 64

Hi-Ref
Low-Ref
RTN
Mux
to
other 1
points Amp ADC

64

Hi-Ref
Low-Ref

Mux

1
Amp ADC

64

Hi-Ref
Low-Ref

Figure 173 Simplified Schematic of a 3704E or 3720 AI Module with a 9750-810F Panel

9753-110F (0–5 VDC/0–10 VDC voltage input, basic, 16 pts.)


Termination panel 9753-110F is compatible with 0 to 5 VDC, -5 to +5 VDC, or 0 to 10 VDC analog
input modules and has 16 voltage input terminals (IN+ and IN–) and commoned return
terminals (RTN).
When using 32 point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Specifications
This table describes specifications for 9753-110F.

Table 131 Specifications for Term Panel 9753-110F


Feature Description
Panel type Voltage input, basic
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
216 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9753-110F.

Table 132 Modules Compatible with 9753-110F


Module Model Points per
Module Description
Number Module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3701 32 0–10 VDC, non-commoned, differential, DC-coupled, TMR
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC or 0-10 VDC), non-commoned, differential, isolated,
TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use TriStation to configure input range),
differential, DC-coupled, TMR

Field Wiring Diagrams


Unused points must be shorted together to avoid module diagnostic errors.
Connect floating field devices to Signal Ground as shown in the field wiring diagrams.
These figures illustrate how to connect a 16-point or 32-point analog input module and a
9753-110F to the field (1 of 16 or 32 module points shown).

Figure 174 Field Wiring for 9753-110F with a 3700, 3700A, or 3701 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 217

Figure 175 Field Wiring for 9753-110F with a 3703E AI Module

Figure 176 Field Wiring for 9753-110F with a 3721 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
218 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a basic current
input panel (1 of 32 module points shown).

TERMINATION CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES


PANEL

to
spare Mux
Isolation/filtering

1 Amp ADC

IN1 + 32
Hi-Ref
IN1 –
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 177 Simplified Schematic of a 3700, 3700A, 3701, or 3721 AI Module with a 9753-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 219

This is a simplified schematic of a typical 16-point analog input module with a basic current
input panel (1 of 16 module points shown).

TERMINATION CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES


PANEL

to
spare Mux

1 Amp ADC

16
IN
Hi-Ref
IN Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 178 Simplified Schematic of a 3703E AI Module with a 9753-110F Panel

9763-810F (0–5 VDC/0–10 VDC voltage input, 16 pts.)


Termination panel 9763-810F is compatible with 0 to 5 VDC, –5 to +5 VDC, or 0 to 10 VDC
analog input modules and has 16 voltage input terminals.
When using 32 point modules, you must use two term panels for each analog input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9763-810F.

Table 133 Specifications for Term Panel 9763-810F


Feature Description
Panel type Voltage input
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
220 Chapter 5 Analog Input and Analog Output Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9763-810F.

Table 134 Modules Compatible with 9763-810F


Module Model Points per
Module Description
Number Module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3701 32 0–10 VDC, non-commoned, differential, DC-coupled, TMR
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC or 0-10 VDC), non-commoned, differential, isolated, TMR

Field Wiring Diagrams


Unused points must be shorted together to avoid module diagnostic errors.
Connect floating field devices to Signal Ground as shown in the field wiring diagrams.
These figures illustrate how to connect a 16-point or 32-point analog input module and a
9763-810F to the field (1 of 16 or 32 module points shown).

Figure 179 Field Wiring for 9763-810F with a 3700, 3700A, or 3701 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Voltage Input Term Panels 221

Figure 180 Field Wiring for 9763-810F with a 3703E AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
222 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a voltage input
panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 181 Simplified Schematic of a 3700, 3700A, 3701 AI Module with a 9763-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 223

This is a simplified schematic of a typical 16-point analog input module with a voltage input
panel (1 of 16 module points shown).

TERMINATION CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES


PANEL

to
spare Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 182 Simplified Schematic of a 3703E AI Module with a 9763-810F Panel

RTD/TC/AI Input Term Panels


This section describes RTD/TC/AI term panels. The model number of these term panels is:
9764-310F (RTD/TC/AI input, 0–5 VDC, 16 pts.)
This figure represents a typical 16-point RTD/TC/AI termination panel.

TRICONEX 7B 16 MODULE BASEPLATE 7400225- REV E SN


J1
7B47

7B47

7B47

7B47

7B32

7B32

7B32

7B32

7B34

7B34

7B34

7B34

7B34

7B34

7B34

7B34
DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG
RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT
ISOLATED

ISOLATED

ISOLATED

ISOLATED

PROCESS

PROCESS

PROCESS

PROCESS
ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED
TC INPUT

TC INPUT

TC INPUT

TC INPUT

U1 U2 U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16


1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16

J2
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16

J3 J4 J5 J6

Figure 183 Typical 16-Point RTD/TC/AI Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
224 Chapter 5 Analog Input and Analog Output Termination Panels

9764-310F (RTD/TC/AI input, 0–5 VDC, 16 pts.)


Termination panel 9764-310F is compatible with 0 to 5 VDC or –5 to +5 VDC analog input
modules and industry-standard signal conditioning modules. Each panel has:
• 16 input points
• Mounting plate
• Redundant power, signal, and earth ground connections
The panel accepts power from +24 VDC to +28 VDC. Each 24 V power source must be able to
provide 0.5 Amps minimally.
The modules compatible with 9764-310F have 32 points, which means you must use two term
panels for each analog input module. Each term panel comes with two sets of labels: 1-16 and
17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9764-310F.

Table 135 Specifications for Term Panel 9764-310F


Feature Description
Panel type RTD/TC/AI
Points 16

Compatible Modules
This table describes analog input modules compatible with 9764-310F.

Table 136 Analog Input Modules Compatible with 9764-310F


Module Model Points per
Module Description
Number Module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

For more information on analog input modules, see the Planning and Installation Guide for Tricon
11.5 and Later 11.x Systems.
The input-signal conditioning modules used on Triconex termination panels are manufactured
by Analog Devices and Dataforth. Signal conditioning modules must be ordered separately and
are available from Schneider Electric or directly from Analog Devices or Dataforth.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 225

This table describes temperature and other input parameters for available signal conditioning
modules. For detailed specifications, visit the Analog Devices Web site or the Dataforth Web
site.

Table 137 Signal Conditioning Module Input Parameters


Schneider
Output Analog Devices Part No.
Description Input Range Electric Part
Range Dataforth Part No.
No.
Isolated, Process Current +4 mA to +20 mA +1 V to +5 V 7B32-011 1600099-001
Input Module SCM7B32-01
Non-Isolated, Linearized +32°F to +248° F +1 V to +5 V 7B14-C-02-1 1600081-001
RTD Input, 10Ω (0° C to +120° C)
Copper,
2-or 3-Wire, α = 0.004274
Isolated Voltage Input 0 mV to +100 mV +1 V to +5 V 7B30-02-1 1600082-001
Isolated, Linearized, –148°F to +212°F +1 V to +5 V 7B34-011 1600087-001
RTD Input, 100Ω (–100°C to +100°C) SCM7B34-01
Platinum,
+32°F to +212°F +1 V to +5 V 7B34-021 1600088-001
2- or 3-Wire, α = 0.00385
(0°C to +100°C) SCM7B34-02
+32°F to +392°F +1 V to +5 V 7B34-031 1600089-001
(0°C to +200°C) SCM7B34-03
+32°F to +1112°F +1 V to +5 V 7B34-041 1600090-001
(0°C to +600°C) SCM7B34-04
–148°F to +212°F +1 V to +5 V 7B34-01-1 1600024-010
(–100°C to +100°C)
Isolated, Linearized, +32°F to +212°F +1 V to +5 V 7B34-02-1 1600024-020
RTD Input, 100Ω (0°C to +100°C)
Platinum,
2- or 3-Wire, α = 0.00385 +32°F to +392°F +1 V to +5 V 7B34-03-1 1600024-030
(continued) (0°C to +200°C)
+32°F to +1112° F +1 V to +5 V 7B34-04-1 1600024-040
(0°C to +600°C)
–58°F to +662°F +1 V to +5 V 7B34-05-1 1600024-080
(–50°C to +350°C)
+32°F to +392°F +1 V to +5 V Contact Schneider 1600083-200
(0°C to +200°C) Electric

+32°F to 1112°F +1 V to +5 V Contact Schneider 1600083-600


(0°C to +600°C) Electric

Isolated, Linearized, +32°F to +573°F +1 V to +5 V 7B34-N-011 1600091-001


RTD Input, 120Ω Nickel, (0°C to +300°C) SCM7B34N-01
2- or 3-Wire, α = 0.00672
+32°F to +392°F +1 V to +5 V 7B34-N-021 1600093-001
(0°C to +200°C) SCM7B34N-02

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
226 Chapter 5 Analog Input and Analog Output Termination Panels

Table 137 Signal Conditioning Module Input Parameters (continued)


Schneider
Output Analog Devices Part No.
Description Input Range Electric Part
Range Dataforth Part No.
No.
Isolated, Linearized, +32°F to +1400°F +1 V to +5 V 7B47-J-011 1600095-001
Type J Thermocouple (0°C to +760°C) SCM7B47J-01
Input Module
–148°F to +572°F +1 V to +5 V 7B47-J-02-1 1600024-130
(–100°C to +300°C)
Isolated, Linearized, +32°F to +2372°F +1 V to +5 V 7B47-K-031 1600096-001
Type K Thermocouple (0°C to +1300°C) SCM7B47K-03
Input Module
–32°F to +1112°F +1 V to +5 V 7B47-K-041 1600097-001
(0°C to +600°C) SCM7B47K-04
Isolated, Linearized, +32°F to +752°F +1 V to +5 V 7B47-T-051 1600098-001
Type T (0°C to +400°C) SCM7B47T-05
Thermocouple Input
–148°F to +392°F +1 V to +5 V 7B47-T-06-1 1600024-200
Module
(–100°C to +200°C)
Isolated, Linearized, +32°F to +1652°F +1 V to +5 V 7B47-E-071 1600094-001
Type E Thermocouple (0°C to +900°C) SCM7B47E-07
Input Module
Isolated, Linearized, +932°F to +3182°F +1 V to +5 V 7B47-R-08-1 1600024-170
Type R Thermocouple (+500°C to
Input Module +1750°C)
Isolated, Linearized, +1292°F to +3182°F +1 V to +5 V 7B47-S-09-1 1600024-180
Type S Thermocouple (+700°C to
Input Module +1750°C)
Isolated, Linearized, +1472°F to +3272°F +1 V to +5 V 7B47-B-10-1 1600024-100
Type B Thermocouple (+800°C to
Input Module +1800°C)
Isolated, Linearized, +392°F to +2372°F +1 V to +5 V 7B47-N-11-1 1600024-160
Type N Thermocouple (+200°C to
Input Module +1300°C)
Shorting plug for unused n/a n/a 18201 1600048-300
points

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 227

Field Wiring Diagrams


The figures in this section illustrate how to connect a 9764-310F with RTD modules, TC
modules, and AI modules to a field device (1 of 16 points shown).
TC AI RTD
(4–20 mA)

TRICONEX 7B 16 MODULE BASEPLATE 7400225- REV E SN


J1

* 7B47

7B47

7B47

7B47

7B32

7B32

7B32

7B32

7B34

7B34

7B34

7B34

7B34

7B34

7B34

7B34
DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG
RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT
ISOLATED

ISOLATED

ISOLATED

ISOLATED

PROCESS

PROCESS

PROCESS

PROCESS
ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED
TC INPUT

TC INPUT

TC INPUT

TC INPUT
U1 U2 U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16


1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16
J2
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16
J3 J4 J5 J6

**
* A signal conditioning module or shorting plug 1600048-300 must be installed on all points.
** Unused points must be shorted at the +, –, and x terminals. The diagram shows a typical point.

Figure 184 9764-310F with RTD/TC/AI Modules

An optional shield is available for use with conditioning modules to help meet EMC
requirements.
This figure illustrates how to connect a 9764-310F with RTD input-signal conditioning modules
to a field device (1 of 16 points shown).
7B34

7B34

7B34

7B34
DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG
RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT
ISOLATED

ISOLATED

ISOLATED

ISOLATED

R12
12
13
14
15
16

U9 U10 U11 U12

R9 R10 R11 R12


12
13
14
15
16
11
10

12
13
14
15
16
1
2
3
4
5
6
7
8
9

10 11

12
13
14
15
16
1
2
3
4
5
6
7
8
9

11

J5
Shield

Point #12 Typical, see 9764-310F RTD/TC/AI ETP Pin-


Outs on page 229 for other points

Figure 185 Field Wiring for 9764-310F with RTD Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
228 Chapter 5 Analog Input and Analog Output Termination Panels

This figure illustrates how to connect a 9764-310F with TC input-signal conditioning modules
to a field device (1 of 16 points shown).
7B47

7B47

7B47

7B47
DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG
R4
ISOLATED

ISOLATED

ISOLATED

ISOLATED
TC INPUT

TC INPUT

TC INPUT

TC INPUT

12
13
14
15
16
U1 U2 U3 U4

11
12
13
14
15
16
R1 R2 R3 R4
1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

*
1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

J3

* Shield

Point #4 Typical, see 9764-310F RTD/TC/AI ETP


Pin-Outs on page 229 for other points
*Install jumper

Figure 186 Field Wiring for 9764-310F with TC Module

This figure illustrates how to connect a 9764-310F with AI input-signal conditioning modules to
a field device (1 of 16 points shown).
7B32

7B32

7B32

7B32
DEVICES CURRENT INPUT
ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG
PROCESS

PROCESS

PROCESS

PROCESS
ISOLATED

ISOLATED

ISOLATED

ISOLATED

U5 U6 U7 U8

R5 R6 R7 R8
1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16
1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

J4

+
Field
– Transmitter

Point #6 Typical, see 9764-310F RTD/TC/AI ETP


Pin-Outs on page 229 for other points

Figure 187 Field Wiring for 9764-310F with AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 229

This figure illustrates how to connect power supplies to an RTD/TC/AI panel.

J2

+ - + -

+24V Power Supplies

Figure 188 Power Wiring for 9764-310F

Pin-Out Information
This table describes the pin-out information for the 9764-310F RTD/TC/AI panel.

Table 138 9764-310F RTD/TC/AI ETP Pin-Outs


Point Connector Pin # TC RTD AI
J3A (upper) 1 NCa NC NC
J3B (lower) 1 Jump NC NC
J3A (upper) 2 NC Xb NC
J3B (lower) 2 Jump NC NC
Point 1
J3A (upper) 3 – and SHc – –
J3B (lower) 3 NC NC NC
J3A (upper) 4 + + and SH +
J3B (lower) 4 NC NC NC
J3A (upper) 5 NC NC NC
J3B (lower) 5 Jump NC NC
J3A (upper) 6 NC X NC
J3B (lower) 6 Jump NC NC
Point 2
J3A (upper) 7 – and SH – –
J3B (lower) 7 NC NC NC
J3A (upper) 8 + + and SH +
J3B (lower) 8 NC NC NC

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
230 Chapter 5 Analog Input and Analog Output Termination Panels

Table 138 9764-310F RTD/TC/AI ETP Pin-Outs (continued)


Point Connector Pin # TC RTD AI
J3A (upper) 9 NC NC NC
J3B (lower) 9 Jump NC NC
J3A (upper) 10 NC X NC
J3B (lower) 10 Jump NC NC
Point 3
J3A (upper) 11 – and SH – –
J3B (lower) 11 NC NC NC
J3A (upper) 12 + + and SH +
J3B (lower) 12 NC NC NC
J3A (upper) 13 NC NC NC
J3B (lower) 13 Jump NC NC
J3A (upper) 14 NC X NC
J3B (lower) 14 Jump NC NC
Point 4
J3A (upper) 15 – and SH – –
J3B (lower) 15 NC NC NC
J3A (upper) 16 + + and SH +
J3B (lower) 16 NC NC NC
J4A (upper) 1 NC NC NC
J4B (lower) 1 Jump NC NC
J4A (upper) 2 NC X NC
J4B (lower) 2 Jump NC NC
Point 5
J4A (upper) 3 – and SH – –
J4B (lower) 3 NC NC NC
J4A (upper) 4 + + and SH +
J4B (lower) 4 NC NC NC
J4A (upper) 5 NC NC NC
J4B (lower) 5 Jump NC NC
J4A (upper) 6 NC X NC
J4B (lower) 6 Jump NC NC
Point 6
J4A (upper) 7 – and SH – –
J4B (lower) 7 NC NC NC
J4A (upper) 8 + + and SH +
J4B (lower) 8 NC NC NC

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 231

Table 138 9764-310F RTD/TC/AI ETP Pin-Outs (continued)


Point Connector Pin # TC RTD AI
J4A (upper) 9 NC NC NC
J4B (lower) 9 Jump NC NC
J4A (upper) 10 NC X NC
J4B (lower) 10 Jump NC NC
Point 7
J4A (upper) 11 – and SH – –
J4B (lower) 11 NC NC NC
J4A (upper) 12 + + and SH +
J4B (lower) 12 NC NC NC
J4A (upper) 13 NC NC NC
J4B (lower) 13 Jump NC NC
J4A (upper) 14 NC X NC
J4B (lower) 14 Jump NC NC
Point 8
J4A (upper) 15 – and SH – –
J4B (lower) 15 NC NC NC
J4A (upper) 16 + + and SH +
J4B (lower) 16 NC NC NC
J5A (upper) 1 NC NC NC
J5B (lower) 1 Jump NC NC
J5A (upper) 2 NC X NC
J5B (lower) 2 Jump NC NC
Point 9
J5A (upper) 3 – and SH – –
J5B (lower) 3 NC NC NC
J5A (upper) 4 + + and SH +
J5B (lower) 4 NC NC NC
J5A (upper) 5 NC NC NC
J5B (lower) 5 Jump NC NC
J5A (upper) 6 NC X NC
J5B (lower) 6 Jump NC NC
Point 10
J5A (upper) 7 – and SH – –
J5B (lower) 7 NC NC NC
J5A (upper) 8 + + and SH +
J5B (lower) 8 NC NC NC

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
232 Chapter 5 Analog Input and Analog Output Termination Panels

Table 138 9764-310F RTD/TC/AI ETP Pin-Outs (continued)


Point Connector Pin # TC RTD AI
J5A (upper) 9 NC NC NC
J5B (lower) 9 Jump NC NC
J5A (upper) 10 NC X NC
J5B (lower) 10 Jump NC NC
Point 11
J5A (upper) 11 – and SH – –
J5B (lower) 11 NC NC NC
J5A (upper) 12 + + and SH +
J5B (lower) 12 NC NC NC
J5A (upper) 13 NC NC NC
J5B (lower) 13 Jump NC NC
J5A (upper) 14 NC X NC
J5B (lower) 14 Jump NC NC
Point 12
J5A (upper) 15 – and SH – –
J5B (lower) 15 NC NC NC
J5A (upper) 16 + + and SH +
J5B (lower) 16 NC NC NC
J6A (upper) 1 NC NC NC
J6B (lower) 1 Jump NC NC
J6A (upper) 2 NC X NC
J6B (lower) 2 Jump NC NC
Point 13
J6A (upper) 3 – and SH – –
J6B (lower) 3 NC NC NC
J6A (upper) 4 + + and SH +
J6B (lower) 4 NC NC NC
J6A (upper) 5 NC NC NC
J6B (lower) 5 Jump NC NC
J6A (upper) 6 NC X NC
J6B (lower) 6 Jump NC NC
Point 14
J6A (upper) 7 – and SH – –
J6B (lower) 7 NC NC NC
J6A (upper) 8 + + and SH +
J6B (lower) 8 NC NC NC

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
RTD/TC/AI Input Term Panels 233

Table 138 9764-310F RTD/TC/AI ETP Pin-Outs (continued)


Point Connector Pin # TC RTD AI
J6A (upper) 9 NC NC NC
J6B (lower) 9 Jump NC NC
J6A (upper) 10 NC X NC
J6B (lower) 10 Jump NC NC
Point 15
J6A (upper) 11 – and SH – –
J6B (lower) 11 NC NC NC
J6A (upper) 12 + + and SH +
J6B (lower) 12 NC NC NC
J6A (upper) 13 NC NC NC
J6B (lower) 13 Jump NC NC
J6A (upper) 14 NC X NC
J6B (lower) 14 Jump NC NC
Point 16
J6A (upper) 15 – and SH – –
J6B (lower) 15 NC NC NC
J6A (upper) 16 + + and SH +
J6B (lower) 16 NC NC NC

a. NC = No connect
b. X = Third wire (sense signal)
c. SH = Shield

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
234 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a RTD/TC/AI
panel (1 of 32 module points shown).

RTD/TC/AI PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
P1 spare Mux
Isolation/filtering
P2

1 Amp ADC

LED * Hi-Ref
32

Com Low-Ref

Mux

+ 1 Amp ADC
7BXX

Typical Signal
Conditioner
x 32
Hi-Ref
Low-Ref
y
rfu **

Mux
CJ
Thermocouple
***
1 Amp ADC
x

32
Hi-Ref
Low-Ref

* LEDs are blown-fuse indicators.


** Reserved for future use.
*** Required jumper for thermocouple.

Figure 189 Simplified Schematic of a 3700 or 3700A AI Module with a 9764-310F (RTD/TC/AI) Panel

Analog Output Term Panels


This section describes analog output term panels. Model numbers of these term panels are:
• 9863-710F (3806E module, 8 pts.)
• 9853-610F (current output, basic, 8 pts.)
• 9881-810F (3807 module, 4 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 235

This figure represents a typical current output termination panel.

TRICONEX
E E

7400143-
C C

TM
A A
SN

36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2

HCAO PANEL
REV A

CH5 Volts

CH1 Volts
J1

Figure 190 Typical Current Output Term Panel

This figure represents a typical basic current output termination panel.

J1
DIDO PANEL

REV A
SN
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8

A A
TM
TRICONEX

7400143-

C C

E E

Figure 191 Typical Basic Current Output Term Panel

This figure represents a typical Bipolar Analog Output termination panel.


DO NOT SEPARATE WHEN ENERGIZED

L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20

C19

REV B
L12
0° C≤TA≤+60° C
C14

C15

SN L15 L16

L6

R19
L13 L14
L5 C12

L9 L10
L4 C10

L7 L8
C5

L3
C8

C7
C2

C3

L1

R20
!

C35

C36

C26
C37

C38

C39

C40

C41

C42

C43

TB7 TB8
C44

R2

R1
TB1—TB4

J4
L+ 1 2 3 4 2 3
1 4
C27
C25

C45

L-
J5 1 2 3 4 1 2 3 4 P1 P2

Figure 192 Typical Bipolar Analog Output Term Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
236 Chapter 5 Analog Input and Analog Output Termination Panels

9863-710F (3806E module, 8 pts.)


Termination panel 9863-710F is for use only with the 3806E analog output module. Each panel
has:
• Two dual-coil 20–320 mA output terminals (OUT and RTN)
• Two 4–20 mA output terminals for monitoring dual-coil output voltages
• Two voltage/current converters
• Six 4–20 mA output terminals (OUT and RTN)
• Terminals for connecting redundant 24 VDC power supplies

Specifications
This table describes specifications for 9863-710F.

Table 139 Specifications for Term Panel 9863-710F


Feature Description
Panel type Analog output
Points 8

Compatible Modules
This table describes analog output modules compatible with 9863-710F.

Table 140 Modules Compatible with 9863-710F


Module Model Points per
Module Description
Number Module
3806E 8 6 4–20 mA outputs, 2 20–320 mA outputs, commoned-return, DC-
coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 237

Field Wiring Diagrams


This figure illustrates how to connect 9863-710F and 4–20 mA outputs to the field. See Figure
196 High-Current Circuits (page 241) for how to connect to the 20–360 mA outputs.

+24 VDC

A22 (PWRA)
+24 VDC
A24 (PWRB)

Termination panel
REV A 7400143-
SN
C
A

36 BOUT1
BOUT5
***
34
32
30
28
26
E24 (RTN)
24
22
J1

20
18
E22 (RTN)
16
14
RTN
12
10
**
8
6 E20 (RTN8)
4
2
C
A

CH5 Volts Points


E2 (RTN1)
2-4
6-8
Load
*
CH1 Volts A2 (OUT1)

HCAO PANEL TM TRICONEX

A20 (OUT8)

* A shorting jumper must be connected to each unused point.


** One RTN connection is required. More than one is okay.
*** Typically connected to current analog input point to monitor 20–320 mA output voltages.

Figure 193 Field Wiring for 9863-710F with a 3806E AO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
238 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 3806E analog output module with a 9863-710F panel
(1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A Loop power
PWRA (22A)

Selector
Logic
Current
loopback PWRB (24A)

DAC
RTN (22E)

B RTN (24E)

Selector
Logic Current
loopback

DAC
OUT2 (6A)

Typical points
2-4
6-8
C RTN2 (6E)

Selector
Logic
Current
loopback

DAC

Figure 194 Simplified Schematic of 3806E AO Module with a 9863-710F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 239

Pin-Outs
This table describes pin-outs for the 9863-710F.

Table 141 9863-710F Pin-Outs


Label Pin No. Signal Description
A2 AA OUT1A Channel 1A out
E2 LL RTN1A Channel 1A return
A4 AA OUT1B Channel 1B out
E4 LL RTN1B Channel 1B return
A6 z OUT2 Channel 2 out
E6 EE RTN2 Channel 2 return
A8 p OUT3 Channel 3 out
E8 v RTN3 Channel 3 return
A10 h OUT4 Channel 4 out
E10 l RTN4 Channel 4 return
A12 e OUT5A Channel 5A out
E12 b RTN5A Channel 5A return
A14 e OUT5B Channel 5B out
E14 b RTN5B Channel 5B return
A16 W OUT6 Channel 6 out
E16 S RTN6 Channel 6 return
A18 L OUT7 Channel 7 out
E18 F RTN7 Channel 7 return
A20 M OUT8 Channel 8 out
E20 B RTN8 Channel 8 return
A22 t PWRA Power A +
E22 x RTN Power A –
A24 j PWRB Power B +
E24 m RTN Power B –
A28 VT1+ Channel 1 V-to-I Out
E28 VT1- Channel 1 V-to-I Return
A30 VT5+ Channel 5 V-to-I Out
E30 VT5- Channel 5 V-to-I Return
A34 T CGND Chassis Ground
C34 H CGND Chassis Ground

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
240 Chapter 5 Analog Input and Analog Output Termination Panels

Table 141 9863-710F Pin-Outs (continued)


Label Pin No. Signal Description
E34 w CGND Chassis Ground
A36 FF CGND Chassis Ground

CGND is the controller protective earth (chassis ground). Pins r, s, X and Y on the panel
connector are not used.

Dual-Coil Actuator
A single high-current analog output supplies the signal for both coils of the dual coil actuator.
The current is divided according to the impedance of the two coils.
The power produced by the actuator coils is a function of the number of coils and the current
through them. If only one coil is used, the current must double to maintain the same power.

HIGH-CURRENT ANALOG OUTPUT DUAL-COIL


EXTERNAL TERMINATION PANEL ACTUATOR

VOLTAGE-TO-CURRENT CONVERTER

COIL 1
CONTROLLER
OUTPUT V/I
(20 - 360 mA)
COIL 2

COIL STATUS
FEEDBACK

Figure 195 High-Current AO Termination Panel Assembly

Because the controller output is a constant current, failure of one coil diverts all the current
through the remaining coil, thus maintaining the correct actuator output. For example: If the
controller output is 160 mA and the coil impedance is equal, the controller output is split evenly,
supplying 80 mA to each coil. If one coil fails, all of the controller output current goes to the
remaining good coil, effectively doubling the force that the failed coil produced before the
failure.
The voltage-to-current converter across the controller output responds to changes in the output
voltage that would result from the loss of a coil. The volt/amp characteristics of the good coils
are programmed into the controller. A significant deviation in the volt/amp characteristics
causes an alarm to be issued.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 241

This is a simplified schematic of the high-current circuits.

DUAL-COIL
COIL 1 CURRENT
ACTUATOR
VOLTAGE-TO-CURRENT CONVERTER
TP 2A

COIL 1
PIN AA TP 2E
CONTROLLER
OUTPUT V/I Point 1
(20 - 360 mA)
PIN LL TP 4A
COIL 2

TP 4E
TP 28A TP 28E

COIL STATUS
FEEDBACK

DUAL-COIL
COIL 2 CURRENT
ACTUATOR

VOLTAGE-TO-CURRENT CONVERTER
TP 12A

COIL 1
PIN e TP 12E
CONTROLLER
OUTPUT V/I Point 5
(20 - 360 mA)
PIN b TP 14A
COIL 2

TP 14E
TP 30A TP 30E

COIL STATUS
FEEDBACK

Figure 196 High-Current Circuits

Voltage-to-Current Converter
This is a simplified schematic of a voltage-to-current converter.

+ 5
INPUT
0-28 VDC
- 3

+ 1
LOGIC SUPPLY E TO I
24 VDC CONVERTER
- 2

+ 4
OUTPUT
4-20 mA
- 6

EQUIVALENT CIRCUIT

Figure 197 Simplified Schematic of a Voltage-to-Current Converter

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
242 Chapter 5 Analog Input and Analog Output Termination Panels

This table describes specifications for the voltage-to-current converter.

Table 142 Voltage-to-Current Converter Specifications


Feature Specification
Voltage 24 VDC, nominal (20–28 VDC maximum range)
Current 20 mA quiescent, with Vsupply = 24 V, Vin = 0, RL = 0,
Is = 4 mA
Input impedance 1 MW Differential Mode
850 kΩ Common Mode
Input voltage range for 4–20 mA out 0–20 V
Maximum input voltage, either ± 100 V continuous
terminal with respect to power ± 200 V pulsed, 0.5 second, 2% duty cycle
supply common
Differential mode frequency response –6 dB/octave from 1 kHz to 8 kHz
–12 dB/octave above 8 kHz
Common mode frequency response –12 dB/octave above 8 kHz
Output range 4–20 mA for 0–20 V input
Maximum load resistance 750 W with Vsupply = 24 V
Offset and linearity ± 0.1 mA maximum over entire range
Power supply sensitivity Output varies less than ± 0.1 mA over entire range, into 500
Ω load, for 20 V < Vsupply < 28 V

9853-610F (current output, basic, 8 pts.)


Termination panel 9853-610F is compatible with 4–20mA output modules and HART analog
output interface modules. Each panel has:
• 8 current output terminals (OUT)
• 8 current return terminals (RTN)
• Terminals for connecting redundant 24 VDC power supplies

Specifications
This table describes specifications for 9853-610F.

Table 143 Specifications for Term Panel 9853-610F


Feature Description
Panel type Current output, basic
Points 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 243

Compatible Modules
This table describes analog output modules compatible with 9853-610F.

Table 144 Modules Compatible with 9853-610F


Module Model Points per
Module Description
Number Module
2870H 8 HART analog output interface module
3805E/H 8 4–20 mA, commoned-return, DC-coupled, TMR

Field Wiring Diagrams


This figure illustrates how to connect an 8-point analog output module or HART analog output
interface module and a 9853-610F to the field (1 of 8 module points shown).

+24 VDC

22A (PWRA)
+24 VDC
24A (PWRB)

Termination panel
REV A 7400143-
SN
A

E
C

32
30
28
26
24E (RTN)
24
22
J1

20
18 22E (RTN)
16
14
RTN
12
10
*
8
16E (RTN8)
6
4
2
A

E
C

TM
DIDO PANEL TRICONEX

2E (RTN1)
Load **
2A (OUT1)

16A (OUT8)

* One RTN connection is required. More than one is okay.


** A shorting jumper must be connected to each unused point.

Figure 198 Field Wiring for 9853-610F with a 3805E or 3805H AO Module or 2870H HART AO Interface
Module

For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
244 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
a basic current output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A Loop power
PWRA (22A)

Selector
Logic
Current
loopback PWRB (24A)

DAC
RTN (22E)

B RTN (24E)

Selector
Logic Current
loopback

DAC
OUT1 (2A)

C RTN1 (2E)

Selector
Logic
Current
loopback

DAC

Figure 199 Simplified Schematic of a 3805E or 3805H AO Module with a 9853-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 245

This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with a
basic current output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE 2870H H A R T FIELD TERMINATION


AO INTERFACE MODULE CABLE PANEL

A Loop power
PWRA (22A)

Selector
Logic
Current
loopback PWRB (24A)

DAC
RTN (22E)

B RTN (24E)

Selector
Logic OUT1 (2A)
Current
loopback

DAC

RTN1 (2E)
Selector
Logic
Current
loopback

VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER

RS-485 HART
CABLE CONTROLLER

Figure 200 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9853-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
246 Chapter 5 Analog Input and Analog Output Termination Panels

9881-810F (3807 module, 4 pts.)


Termination panel 9881-810F is compatible with the 3807 Bipolar Analog Output module. Each
panel has:
• Two, eight position field terminals; support for four points and four redundant point
connections
• Two terminals per point: Out, Rtn (L+, L–)
• Per point snubbers suitable for inductive loads up to 1.0 henry
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection

Specifications
This table describes specifications for 9881-810F.

Table 145 Specifications for Term Panel 9881-810F


Feature Description
Panel type Current output
Points 4 with 4 redundant connections

This table describes cable and load parameters for 9881-810F.

Table 146 Cable and Load Parameters for Term Panel 9881-810F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.126 mA
Maximum output power Po Po 0.990 W
C external, maximum Co Ca 1.15 µF
L external, maximum Lo La 4.95 mH

For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 247

Compatible Modules
This table describes the analog output module compatible with 9881-810F.

Table 147 Module Compatible with 9881-810F


Module Model Points per
Module Description
Number Module
3807 4 analog output -60 to 60 mA analog outputs, commoned-return, DC-coupled,
TMR with coil-diagnostic inputs

Field Wiring Diagrams


This figure illustrates how to connect a 3807 Bipolar Analog Output module and a 9881-810F to
the field (1 of 4 module points shown).
DO NOT SEPARATE WHEN ENERGIZED

L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20

C19

REV B
L12
0° C≤TA≤+60° C
C14

C15

SN L15 L16

L6

R19
L13 L14
L5 C12

L9 L10
L4 C10

L7 L8
C5

L3
C8

C7
C2

C3

L1

R20
!

C35

C36

C26
C37

C38

C39

C40

C41

C42

C43

TB7 TB8
C44

R2

R1
TB1—TB4

J4
L+ 1 2 3 4 2 3
1 4
C27
C25

C45

L-
J5 1 2 3 4 1 2 3 4 P1 P2

PS2
Typical -
DC
unused Power
point + Supply

Typical point
(1 of 4 points shown) PS1
- DC
Power
Point 1 Point 1 + Supply
Torque Motor Coil Optional
(Load) Redundant Torque
Motor Coil

Energy limited Not energy limited

Figure 201 Field Wiring for 9881-810F with a 3807 Bipolar Analog Output Module

Unused points must be shorted together to avoid module diagnostic errors.


If the I/O cable (the cable that connects the termination panel to the Tricon chassis backplane)
goes outside the cabinet that houses the Tricon chassis, the I/O cable should be routed in a metal
conduit.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
248 Chapter 5 Analog Input and Analog Output Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 4-point Bipolar Analog Output module with an analog
output panel (1 of 4 module points shown with 1.0 Henry snubber 301 Ω, 680 nF). The
connection to the coil-diagnostic input is hardwired on the termination panel.

BPAO MODULE BACKPLANE CABLE TERMINATION PANEL

A
Loop power
+18 / -18 P1 PWR
DAC
P2 PWR

ADC
P1 RTN
Channel
Select
P2 RTN
B
Protective
+18 / -18
Earth
DAC
Source
Current
L+

ADC Coil
L-

Channel
Select Sink 301:
Current
L+
C Redundant
+18 / -18 680nF Coil
L-
DAC

Analog Coil Diagnostic


ADC Inputs Inputs

Channel
Select

Figure 202 Simplified Schematic of a 3807 Bipolar Analog Output Module with a 9881-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
6
Hazardous Location (Nonincendive)
Termination Panels

Overview 250
Field Wiring in Hazardous Locations 250
Grounding and Installation Recommendations 251
Analog Input Term Panels 253
Analog Output Term Panels 277
Digital Input Term Panels 285
Digital Output Term Panels 296
Pulse Input Term Panels 302

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
250 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Overview
This chapter describes external field termination panels (ETPs) with nonincendive circuits that
you can use in hazardous locations.
This table identifies ETPs that use nonincendive circuits as approved by TÜV Rhineland.

Table 148 Nonincendive External Termination Panels


Term Panel Type Term Panel Model Description
Analog Input 9791-610F 4-20 mA, 0–5 VDC, 16 pts.
9787-110F 0-5 VDC voltage input, 16 pts.
9785-610F TC input, downscale, 16 pts.
9784-610F TC input, upscale, 16 pts.
9786-110F TC input, isolated, 16 pts.
9789-610F 4-20 mA, high-density, 32 pts.
Analog Output 9861-610F 3805E/H module, 8 pts.
9871-810F 3807 module, 4 pts.
Digital Input 9572-610F 24 VDC, commoned, 16 pts.
9570-610F 24 VDC, high-density, 32 pts.
9571-610F 24 VDC, fail-safe, 32 pts.
Digital Output 9671-610F 24 VDC, commoned, supervised, 16 pts.
Pulse Input 9793-110F 8 pts.

Field Wiring in Hazardous Locations


The external termination panels (ETPs) described in this chapter are suitable for use in Zone 2,
and Class 1, Division 2 field circuits. These ETPs contain extra circuitry designed to limit power
available to the field terminals. These circuits have been examined and certified by TÜV
Rhineland as being nonincendive. This guarantees that if the field wires are accidentally
opened, shorted, or grounded, and the Tricon controller is operating normally, the wiring and
attached devices will not release sufficient energy to cause ignition in the specified flammable
atmosphere.

Cable and Load Parameters (Entity Parameters)


To ensure that the field circuits are incapable of igniting a specified flammable vapor
atmosphere, the size of the cable and load parameters must be known and controlled. The Cable
and Load Parameters tables in each termination panel section identify the maximum
permissible values of the parameters for each termination panel.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Grounding and Installation Recommendations 251

Electrical Code Approval


The ETPs and associated field wiring in hazardous locations must be installed per the
requirements of the prevailing local electrical codes and the instructions in chapter 3 of the
Planning and Installation Guide for Tricon 11.5 and Later 11.x Systems.
In Europe, the ETPs listed in this chapter are in full compliance with the ATEX Directive and are
suitable for use in Zone 2 Group IIB hazardous locations per the requirements of EN 60079-15,
Electrical apparatus for explosive gas atmospheres - Part 15: Type protection “n”.
In North America, the ETPs listed in this chapter are suitable for use in Class 1, Division 2
Groups C and D hazardous locations per the requirements of ANSI/ISA S12.12.01-2000,
Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions
1 and 2 Hazardous (Classified) Locations.

Current Limiting
Each of the following termination panels has a 190-to-310-ohm positive temperature coefficient
(PTC) resistor:
• 9791-610F
• 9789-610F
• 9572-610F
• 9570-610F
• 9571-610F
• 9671-610F
The PTC resistor acts as a resettable fuse and an over-current protection device. When the
current through the resistor increases, the resistor self-heats and drives up its own resistance
until the current and temperature reach equilibrium. The maximum working current of each
ETP listed above is 28 mA and is specified in the Cable and Load Parameters table for each ETP.

Grounding and Installation Recommendations


This section describes the grounding of termination panels and recommends how to properly
install termination panels used in hazardous locations. For general information about installing
ETPs, please see Chapter 2, Field Termination Options and Installation.

Grounding
Each hazardous location ETP described in this chapter purposefully connects the signal and
protective earth ground. This connection prevents a difference of potential that could
potentially spark and cause an ignition.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
252 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Ground Terminal Blocks


When ETPs are connected in a string, attach a ground terminal block (Schneider Electric part
number 1420115-001) to the grounded DIN rail at either end of each ETP and as well as at either
end of the string of ETPs. Two ETPs can share one terminal block.
This figure shows a string of ETPs connected to a grounded DIN rail with ground terminal
blocks.

+
DIN rail
J1

J1

Ground terminal blocks


J1

Figure 203 ETP String and Ground Terminal Blocks

Gaskets
You must use gasket 2000098-100 on the male side of all ELCO connectors used in hazardous
location installations, and replace it before the end of its five-year life span. Schneider Electric
recommends that you use the gasket in all hazardous locations requiring nonincendive circuits.
(Order Schneider Electric part number 3000793-001 for a kit of 25 gaskets.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 253

gasket installed gasket

Figure 204 Gasket for ELCO Connector

Analog Input Term Panels


This section describes analog input termination panels. Model numbers include:
• 9791-610F (4-20 mA, 0–5 VDC, 16 pts.)
• 9787-110F (0-5 VDC voltage input, 16 pts.)
• 9785-610F (TC input, downscale, 16 pts.)
• 9784-610F (TC input, upscale, 16 pts.)
• 9786-110F (TC input, upscale/downscale, 16 pts.)
• 9789-610F (4-20 mA, high-density, 32 pts.)

9791-610F (4-20 mA, 0–5 VDC, 16 pts.)


Termination panel 9791-610F is compatible with 0 to 5 VDC analog input modules and HART
analog input interface modules. Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for 4-20 mA transmitter (F+, F–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor. Each input has a
precision 250-ohm resistor for 0-to-5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
When using 32-point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
254 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Specifications
This table describes general specifications for 9791-610F.

Table 149 General Specifications for Term Panel 9791-610F


Feature Description
Panel type Current input, 4–20 mA
Points 16

This table describes cable and load parameters for 9791-610F.

Table 150 Cable and Load Parameters for Term Panel 9791-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (F–) Specifications

Maximum input voltage Ui Vmax 9V


Maximum input current Ii Imax 0.036 A
Maximum input power Pi Pi 0.324 W
C internal, maximum Ci Ci 0.088 µF
L internal, maximum Li Li 43 µH
Output Connection (F+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.18 µF
L external, maximum Lo La 4.95 mH

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 255

Compatible Modules
This table describes analog input modules compatible with 9791-610F.

Table 151 Modules Compatible with 9791-610F


Module Model Points per
Module Description
Number Module
2770H 32 HART analog input interface
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
input range), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

When used with the 9791-610F, the accuracy of the 3700A, 3703E, and 3721 modules may be
affected by up to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result, the
accuracy of these modules is +0.15% to –0.23% FSR, at 140° F (60° C).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
256 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 3700A, 3703E, or 3721 analog input module or a HART
analog input interface module and a 9791-610F to the field (1 of 16 or 32 module points shown).
See Appendix E, Shield Ground for shield ground installation guidelines.

TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B ƒ&”7$”ƒ& 7400275
as short as possible

17
R
SN SN

R25
18
R1

R1
R
9
R
TB1 TB4 TB1

5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2

R2
R
10
R

R27
20
R3

R3
R
11
R

R28
3
21
R4

R4
R
12
R

R29
22
R5

R5
R
13
R

R30
23
5

5
R
14

!
R

R31
24
R7

R7
R
15
R

R32
R8

R8


J1
5

TB2 TB3 TB5 7%

J2 J2
L+ /
J3 J3

L- 3 3 L-

Second term panel


if using a 32-point
Typical point 36 module
RIRUSRLQWVVKRZQ -
'&
3RZHU
  Supply
Field Xmtr
- P$
36
- '&
3RZHU
 Supply

Shield Ground

Energy limited Not energy limited

Figure 205 Field Wiring for 9791-610F with a 3700A, 3703E, or 3721 AI Module or 2770H HART AI
Interface Module

For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 257

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).

* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers

Figure 206 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9791-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
258 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).

HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE

HART 2071H HART to


spare Mux
CONTROLLER MUX MODULE
Isolation/filtering

1 Amp ADC

310 Ohms Max


32
Hi-Ref
Low-Ref

~ 10V
to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref
*ATEX

Mux
PE GND

PE GND 1 Amp ADC

32
Hi-Ref
FIELD
TERMINATION PANEL Low-Ref
CABLE

* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers

Figure 207 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 Analog
Input Module and a 9791-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 259

9787-110F (0-5 VDC voltage input, 16 pts.)


Termination panel 9787-110F is compatible with 0 to 5 VDC analog input modules. Each panel
has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
When using 32-point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Specifications
This table describes general specifications for 9787-110F.

Table 152 General Specifications for Term Panel 9787-110F


Feature Description
Panel type Voltage input, 0–5 VDC
Points 16

This table describes cable and load parameters for 9787-110F.

Table 153 Cable and Load Parameters for Term Panel 9787-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Input Connection (I+ and I–) Specifications when Used with 3700A

Maximum input voltage Ui Vmax 32 V


Maximum input current Ii Imax 0.00 A
Maximum input power Pi Pi 0.00 W
C internal, maximum Ci Ci 0.038 µF
L internal, maximum Li Li 0.043 µH
Output Connection (I+ and I–) Specifications when Used with 3703E

Maximum output voltage Uo Voc 15 V


Maximum output current Io Isc 0.005 A
Maximum output power Po Po 0.075 W
C external, maximum Co Ca 20.14 µF

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
260 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Table 153 Cable and Load Parameters for Term Panel 9787-110F (continued)
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
L external, maximum Lo La 1H

Compatible Modules
This table describes analog input modules compatible with 9787-110F.

Table 154 Modules Compatible with 9787-110F


Module Model Points per
Module Description
Number Module
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
input range), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 261

Field Wiring Diagrams


This figure illustrates how to connect a 3700A, 3703E, or 3721 analog input module and a
9787-110F to the field (1 of 16 or 32 module points shown). See Appendix E, Shield Ground for
shield ground installation guidelines.

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1 TB1
EXT TERM TRICON

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ

V
Field
Source

Figure 208 Field Wiring for 9787-110F with a 3700A, 3703E, or 3721 AI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
262 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
voltage input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

+V
1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

-V

1 Amp ADC
*ATEX

32
Hi-Ref
Low-Ref
PE GND

Mux

PE GND

1 Amp ADC

32
Hi-Ref
Low-Ref

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 209 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9787-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 263

This is a simplified schematic of a typical 16-point commoned analog input module with a
voltage input panel (1 of 16 module points shown).

TERMINATION CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES


PANEL

to
spare Mux

+V 1 Amp ADC

~
16
Hi-Ref
Low-Ref

~ Mux

-V Amp ADC
1

*ATEX
16
Hi-Ref
Low-Ref

PE GND Mux

PE GND 1 Amp ADC

16
Hi-Ref
Low-Ref

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 210 Simplified Schematic of a 3703E Analog Input Module with a 9787-110F Panel

9785-610F (TC input, downscale, 16 pts.)


Termination panel 9785-610F is compatible with non-isolated thermocouple input modules.
Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
• TMR cold-junction temperature sensors
• Downscale open-input bias circuitry
The modules compatible with 9785-610F have 32 points, which means you must use two term
panels for each thermocouple input module. Each term panel comes with two sets of labels: 1-16
and 17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
264 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Specifications
This table describes general specifications for 9785-610F.

Table 155 General Specifications for Term Panel 9785-610F


Feature Description
Panel type Thermocouple input, downscale
Points 16

This table describes cable and load parameters for 9785-610F.

Table 156 Cable and Load Parameters for Term Panel 9785-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications

Maximum output voltage UO Vmax 1.5 V


Maximum output current Io Imax 0.00005 A
Maximum output power Po Pi 0.000075 W
C external, maximum Co Ca 1000 µF
L external, maximum Lo La 1H

Compatible Modules
This table describes the thermocouple input module compatible with 9785-610F.

Table 157 Module Compatible with 9785-610F


Module Model Points per
Module Description
Number Module
3706A 32 Type J, K, and T, differential, non-isolated, DC-coupled, TMR, upscale
open-input detection. (Use the TriStation 1131 software to configure
the thermocouple type.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 265

Field Wiring Diagrams


This figure illustrates how to connect a 3706A thermocouple input module and a 9785-610F to
the field (1 of 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1 TB1
EXT TERM TRICON

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel

Typical point
RISRLQWVVKRZQ


-

Shield Ground

Figure 211 Field Wiring for 9785-610F with a 3706A Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
266 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

+V
1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

-V

1 Amp ADC
*ATEX

32
Hi-Ref
Low-Ref
PE GND

Mux

PE GND

1 Amp ADC

32
Hi-Ref
Low-Ref

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 212 Simplified Schematic of a 3706A Thermocouple Input Module with a 9785-610F Panel

9784-610F (TC input, upscale, 16 pts.)


Termination panel 9784-610F is compatible with non-isolated thermocouple input modules.
Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
• TMR cold-junction temperature sensors
• Upscale open-input bias circuitry
The modules compatible with 9784-610F have 32 points, which means you must use two term
panels for each thermocouple input module. Each term panel comes with two sets of labels: 1-16
and 17-32. For information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 267

Specifications
This table describes general specifications for 9784-610F.

Table 158 General Specifications for Term Panel 9784-610F


Feature Description
Panel type Thermocouple input, upscale
Points 16

This table describes cable and load parameters for 9784-610F.

Table 159 Cable and Load Parameters for Term Panel 9784-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications

Maximum output voltage Uo Vmax 1.5 V


Maximum output current Io Imax 0.00005 A
Maximum output power Po Pi 0.000075 W
C external, maximum Co Ca 1000 µF
L external, maximum Lo La 1H

Compatible Modules
This table describes the thermocouple input module compatible with 9784-610F.

Table 160 Module Compatible with 9784-610F


Module Model Points per
Module Description
Number Module
3706A 32 Type J, K, and T, differential, non-isolated, DC-coupled, TMR, upscale
open-input detection. (Use the TriStation 1131 software to configure
the thermocouple type.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
268 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 3706A thermocouple input module and a 9784-610F to
the field (1 of 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1 TB1
EXT TERM TRICON

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel

Typical point
RISRLQWVVKRZQ


-

Shield Ground

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 269

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
EXT TERM TRICON TB1 TB1

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel

Typical point
RISRLQWVVKRZQ


-

Shield Ground

Figure 213 Field Wiring for 9784-610F with a 3706A Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
270 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point thermocouple input module with a
thermocouple input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux
Isolation/filtering

+V +V
1 Amp ADC

22M

32
Hi-Ref
Low-Ref

22M
Mux

-V -V

*ATEX 1 Amp ADC

32
Hi-Ref
Low-Ref
PE GND

Mux

PE GND

1 Amp ADC

32
Hi-Ref
Low-Ref

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 214 Simplified Schematic of a 3706A Thermocouple Input Module with a 9784-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 271

9786-110F (TC input, upscale/downscale, 16 pts.)


Termination panel 9786-110F is compatible with isolated thermocouple input modules.
Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
• TMR cold-junction temperature sensors
• Upscale/downscale open-input bias circuitry

Specifications
This table describes general specifications for 9786-110F.

Table 161 General Specifications for Term Panel 9786-110F


Feature Description
Panel type Thermocouple input, upscale or downscale
Points 16

This table describes cable and load parameters for 9786-110F.

Table 162 Cable and Load Parameters for Term Panel 9786-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Output Connection (I+ and I–) Specifications

Maximum output voltage Uo Vmax 15 V


Maximum output current Io Imax 0.005 A
Maximum output power Po Pi 0.075 W
C external, maximum Co Ca 20.14 µF
L external, maximum Lo La 1H

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
272 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Compatible Modules
This table describes the analog input module compatible with 9786-110F.

Table 163 Module Compatible with 9786-110F


Module Model Points per
Module Description
Number Module
3708E 16 Type E, J, K, and T, differential, isolated, DC-coupled, TMR, upscale
or downscale open-input detection. (Use the TriStation 1131 software
to configure the thermocouple type and specify upscale or downscale
open-input detection.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 273

Field Wiring Diagrams


This figure illustrates how to connect a 3708E thermocouple input module and a 9786-110F to
the field (1 of 16 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

ƒ&”7$”ƒ&
TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1
EXT TERM TRICON

REV B
$7(;(0&$,7&

J2
/

7400272
SN
J3
L-

Typical
unused point

Typical point
RISRLQWVVKRZQ


-

Shield Ground

Figure 215 Field Wiring for 9786-110F with a 3708E Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
274 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux

+V ADC
1 Amp

16
Hi-Ref
Low-Ref

Mux

-V 1 Amp ADC

*ATEX
16
Hi-Ref
Low-Ref

PE GND Mux

1 Amp ADC
PE GND

16
Hi-Ref
Low-Ref

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 216 Simplified Schematic of a 3708E Thermocouple Input Module with a 9786-110F Panel

9789-610F (4-20 mA, high-density, 32 pts.)


Termination panel 9789-610F is compatible with the 3704E or 3720 high-density analog input
modules. Each panel has:
• Four, sixteen-position field terminals; support for 32 points
• Two terminals per point, for dry contact or 4-20 mA transmitter (+, –)
• Two, one-position terminals for protective earth connection
• A four-position terminal for redundant 24 VDC loop power
Each positive terminal is current-limited with a 190-to-310-ohm series resistor. Each input has a
precision 250-ohm resistor for 0-to-5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9789-610F have 64 points, which means you must use two term
panels for each module. Each term panel comes with two sets of labels: 1-32 and 33-64. For
information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 275

Specifications
This table describes general specifications for 9789-610F.

Table 164 General Specifications for Term Panel 9789-610F


Feature Description
Panel type 4–20 mA, high-density
Points 32

This table describes cable and load parameters for 9789-610F.

Table 165 Cable and Load Parameters for Term Panel 9789-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw ≤ 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (–) Specifications

Maximum input voltage Ui Vmax 32 V


Maximum input current Ii Imax 0.036 A
Maximum input power Pi Pi 1.152 W
C internal, maximum Ci Ci 0.088 µF
L internal, maximum Li Li 43 µH
Output Connection (+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.18 µF
L external, maximum Lo La 4.95 mH

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
276 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Compatible Modules
This table describes the analog input modules compatible with 9789-610F.

Table 166 Modules Compatible with 9789-610F


Module Model Points per
Module Description
Number Module
3704E 64 0–5 VDC or 0–10 VDC (use TriStation to configure for 0–5 VDC or 0-10
VDC), commoned, high-density, DC-coupled, TMR
3720 64 0–5 VDC, single-ended, high-density, TMR

When used with the 9789-610F, the accuracy of modules 3704E and 3720 may be affected by up
to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result: the accuracy of module
3704E is +0.25% to –0.33% FSR, at 140° F (60° C), the accuracy of module 3720 is +0.15% to –
0.23% FSR, at 140° F (60° C).

Field Wiring Diagrams


This figure illustrates how to connect a 3704E or 3720 analog input module and a 9789-610F to
the field (1 of 64 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

TRICONEX 7400273 REV B 61 TRICON


ƒ&”7$”ƒ& EXT TERM TRICON $7(;(0&)$,/6$)(',+'',+'$, ƒ&”7$”
'21276(3$5$7(:+(1(1(5*,=('

$:*
12

20

28
10

18

19

26

27
11

13

15

21

23

29

31
14

22

30
24
17

25
16

32
4
2

4
5

3
6

5
1

6
1
R

R
R

R
R

R
R

R
R

R
R
R

R
R

R
DVVKRUWDV
SRVVLEOH
R34

R35

R36

R38

R42

R43

R44

R46

R50

R51

R52

R54

R58

R59

R60

R62
R37

R45

R53

R61
R40

R48

R56

R64
R39

R47

R55

R63
R33

R41

R49

R57

R34

R35
R33
J3
R65

R66

R67

R68

R69

R70

R71

R72

R73

R74

R75

R76

R77

R78

R79

R80

R81

R82

R83

R84

R85

R86

R87

R88

R89

R90

R91

R92

R93

R94

R95

R96

R65

R66

R67
TB1 TB2 TB1
!

TB3 TB4 TB5 TB6


10

12

14

18

19

20

22

26

27

28

30
13

21

29
16

24

32
15

23
17

31
25
11
2

6
5

8
7
1

J1 J4 J1
/ / /

J2 J5 J2
/ / /
P1 P2

7\SLFDOSRLQW 36 6HFRQGWHUPSDQHO


RISRLQWVVKRZQ

'&
Power
  6XSSO\
)LHOG;PWU
 P$
36
 '&
Power
 6XSSO\

6KLHOG*URXQG

(QHUJ\OLPLWHG 1RWHQHUJ\OLPLWHG (QHUJ\OLPLWHG

Figure 217 Field Wiring for 9789-610F with a 3704E or 3720 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 277

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned analog input module with a
4-20 mA, high-density input panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT ANALOG INPUT MODULE

Mux
to
spare 1
Amp ADC

310 Ohms Max 64

Hi-Ref
Low-Ref

to Mux
other
points 1
250 Ohms 10V
Amp ADC

PS1 64

PS2 Hi-Ref
Low-Ref
PS1

PS2 Mux

1
*ATEX Amp ADC

PE GND
64

Hi-Ref
PE GND
Low-Ref

* ATEX-required field return to protective earth (chassis ground) and protective earth to functional earth jumpers
Figure 218 Simplified Schematic of a 3704E or 3720 Analog Input Module with a 9789-610F Panel

Analog Output Term Panels


This section describes analog output termination panels. Model numbers include:
• 9861-610F (3805E/H module, 8 pts.)
• 9871-810F (3807 module, 4 pts.)

9861-610F (3805E/H module, 8 pts.)


Termination panel 9861-610F is compatible with the 3805E and 3805H 4–20 mA output modules
and 2870H HART analog output interface modules. Each panel has:
• Two, eight-position field terminals; support for eight points
• Two terminals per point: Out, Rtn (L+, L–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
278 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Specifications
This table describes specifications for 9861-610F.

Table 167 Specifications for Term Panel 9861-610F


Feature Description
Panel type Current output
Points 8

This table describes cable and load parameters for 9861-610F.

Table 168 Cable and Load Parameters for Term Panel 9861-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.126 A
Maximum output power Po Po 0.990 W
C external, maximum Co Ca 1.15 µF
L external, maximum Lo La 4.95 mH

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 279

Compatible Modules
This table describes the analog output module compatible with 9861-610F.

Table 169 Module Compatible with 9861-610F


Module Model Points per
Module Description
Number Module
2870H 8 HART analog output interface
3805E/H 8 4–20 mA, commoned-return, DC-coupled, TMR

Field Wiring Diagrams


This figure illustrates how to connect a 3805E or 3805H analog output module, or a HART
analog output interface module, and a 9861-610F to the field (1 of 8 module points shown).
'21276(3$5$7(:+(1(1(5*,=('

L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
$7(;(0&$2
7400270 C17

C20

C19
REV B
L12
ƒ&”7$”ƒ&
C14

C15

SN L15 /

/

L11
L13 L14
L5 C12

L9 L10
L4 C10

L7 L8
C5

L3
C8

C7
C2

C3

L1

L2
!

C35

&

&
C37

C38

C39

C40

C41

C42

C43

TB7 TB8
C44

R2

R1
TB1—TB4

J4
/
C27
C25

C45

L-
J5 P1 P2

Typical unused point


PS2
-
DC
Power
Typical point + Supply
(1 of 8 points shown)

PS1
- DC
Load
Power
+ Supply

Energy limited Not energy limited

Figure 219 Field Wiring for 9861-610F with a 3805E or 3805H AO Module or a 2870H HART AO
Interface Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
280 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Unused points must be shorted together to avoid module diagnostic errors.


For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
an analog output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A Loop power
PWRA

Selector
Logic
Current
loopback PWRB

DAC
RTN

B RTN

Selector
Logic Current
PE GND
loopback *ATEX

PE GND

DAC
OUT2

Typical point
30V

C RTN2

Selector
Logic
Current
loopback

DAC

* ATEX-required field return to protective earth (chassis ground) jumpers


Figure 220 Simplified Schematic of a 3805E or 3805H Analog Output Module with a 9861-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 281

This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with
an analog output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE 2870H H A R T FIELD TERMINATION


AO INTERFACE MODULE CABLE PANEL

A Loop power
PWRA

Selector
PWRB
Logic
Current
loopback RTN

DAC RTN

PE GND
*ATEX
B PE GND

Selector
Logic OUT2
Current
loopback Typical point

DAC
~ 30V

RTN2
Selector
Logic
Current
loopback

VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER

RS-485 HART
CABLE CONTROLLER

* ATEX-required field return to protective earth (chassis ground) jumpers

Figure 221 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9861-610F Panel

9871-810F (3807 module, 4 pts.)


Termination panel 9871-810F is compatible with the 3807 Bipolar Analog Output module. Each
panel has:
• Two, eight position field terminals; support for four points and four redundant point
connections
• Two terminals per point: Out, Rtn (L+, L–)
• Per point snubbers suitable for inductive loads up to 1.0 henries
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
282 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Specifications
This table describes specifications for 9871-810F.

Table 170 Specifications for Term Panel 9871-810F


Feature Description
Panel type Current output
Points 4 with 4 redundant connections

This table describes cable and load parameters for 9871-810F.

Table 171 Cable and Load Parameters for Term Panel 9871-810F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 30 V
Maximum voltage Um Um 32 V
Output Connection (L+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.126 mA
Maximum output power Po Po 0.990 W
C external, maximum Co Ca 1.15 µF
L external, maximum Lo La 4.95 mH

For low-density applications, see Appendix I, Low-Density Chassis I/O Module Compatibility.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 283

Compatible Modules
This table describes the analog output module compatible with 9871-810F.

Table 172 Module Compatible with 9871-810F


Module Model Points per
Module Description
Number Module
3807 4 analog output -60 to 60 mA analog outputs, commoned-return, DC-coupled,
TMR with coil-diagnostic inputs

Field Wiring Diagrams


This figure illustrates how to connect a 3807 Bipolar Analog Output module and a 9871-810F to
the field (1 of 4 module points shown).
DO NOT SEPARATE WHEN ENERGIZED

L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
ATEX BPAO ETP
7400305 C17
C20

C19

REV B
L12
0° C≤TA≤+60° C
C14

C15

SN L15 L16

L6

R19
L13 L14
L5 C12

L9 L10
L4 C10

L7 L8
C5

L3
C8

C7
C2

C3

L1

R20
!

C35

C36

C26
C37

C38

C39

C40

C41

C42

C43

TB7 TB8
C44

R2

R1
TB1—TB4

J4
L+ 1 2 3 4 2 3
1 4
C27
C25

C45

L-
J5 1 2 3 4 1 2 3 4 P1 P2

PS2
Typical -
DC
unused Power
point + Supply

Typical point
(1 of 4 points shown) PS1
- DC
Power
Point 1 Point 1 + Supply
Torque Motor Coil Optional
(Load) Redundant Torque
Motor Coil

Energy limited Not energy limited

Figure 222 Field Wiring for 9871-810F with a 3807 Bipolar Analog Output Module

Unused points must be shorted together to avoid module diagnostic errors.


If the I/O cable (the cable that connects the termination panel to the Tricon chassis backplane)
goes outside the cabinet that houses the Tricon chassis, the I/O cable should be routed in a metal
conduit.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
284 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 4-point Bipolar Analog Output module with an analog
output panel (1 of 4 module points shown with 1.0 Henry snubber 301 Ω, 680 nF). The
connection to the coil-diagnostic input is hardwired on the termination panel.

BPAO MODULE BACKPLANE CABLE TERMINATION PANEL

A
Loop power
+18 / -18 P1 PWR
DAC
P2 PWR

ADC
P1 RTN
Channel
Select
P2 RTN
B
* ATEX Protective
Earth
+18 / -18
DAC
Source
Current
L+

ADC Coil
L-

Channel
Select Sink 301:
Current
L+
C
Redundant
+18 / -18 680nF Coil
L-
DAC

Analog Coil Diagnostic


ADC Inputs Inputs

Channel
Select

* ATEX-required field return to protective earth (chassis ground) jumper

Figure 223 Simplified Schematic of a 3807 Bipolar Analog Output Module with a 9871-810F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 285

Digital Input Term Panels


This section describes digital input term panels. Model numbers include:
• 9572-610F (24 VDC, commoned, 16 pts.)
• 9570-610F (24 VDC, high-density, 32 pts.)
• 9571-610F (24 VDC, fail-safe, 32 pts.)

9572-610F (24 VDC, commoned, 16 pts.)


Termination panel 9572-610F is compatible with 24 VDC digital input modules. Each panel has:
• Two, sixteen-position field terminals; support for sixteen points
• Two terminals per point, for dry contact (F+, F–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9572-610F have 32 points, which means you must use two term
panels for each module. Each term panel comes with two sets of labels: 1-16 and 17-32. For
information on how to apply the labels, see Appendix F, Panel Labels.

Specifications
This table describes general specifications for 9572-610F.

Table 173 General Specifications for Term Panel 9572-610F


Feature Description
Panel type Commoned
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
286 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

This table describes cable and load parameters for 9572-610F.

Table 174 Cable and Load Parameters for Term Panel 9572-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 19 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (F–) Specifications

Maximum input voltage Ui Vmax 32 V


Maximum input current Ii Imax 0.0478 A
Maximum input power Pi Pi 1.5296 W
C internal, maximum Ci Ci 0.088 µF
L internal, maximum Li Li 43 µH
Output Connection (F+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.18 µF
L external, maximum Lo La 4.95 mH

Compatible Modules
This table describes digital input modules compatible with 9572-610F.

Table 175 Modules Compatible with 9572-610F


Module Model Points per
Module Description
Number Module
3503E 32 24 VAC/VDC, commoned in groups of 8, TMR with self-test
3505E 32 24 VDC, low-threshold, commoned in groups of 8 with self test, TMR
3515 32 0 to 1 kHz pulse totalizer input, non-commoned

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 287

Field Wiring Diagrams


This figure illustrates how to connect a 3503E or a 3505E digital input module and a 9572-610F
to the field (1 of 32 module points shown).

TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B ƒ&”7$”ƒ& 7400275
as short as possible

17
R
SN SN

R25
18
R1

R1
R
9
R
TB1 TB4 TB1

'21276(3(5$7(

5
:+(1(1(5*,=('
19
R2

R2
R
10
R

R27
20
R3

R3
R
11
R

R28
3
21
R4

R4
R
12
R

R29
22
R5

R5
R
13
R

R30
23
5

5
R
14

!
R

R31
24
R7

R7
R
15
R

R32
R8

R8

J1

5
TB2 TB3 TB5 7%

J2 J2
/ /
J3 J3

L- P1 P2 L-

Second term panel

Typical point PS2


(1 of 32 points shown)
-
'&
Power
 Supply
Field
Contact
PS1
- '&
Power
 Supply

Energy limited Not energy limited

Figure 224 Field Wiring for 9572-610F with a 3503E or 3505E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
288 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

This figure illustrates how to connect a 3515 pulse totalizer input module and a 9572-610F to the
field (1 of 32 module points shown).

TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B ƒ&”7$”ƒ& 7400275
as short as possible

17
R
SN SN

R25
18
R1

R1
R
9
R
TB1 TB4 TB1

'21276(3(5$7(

5
:+(1(1(5*,=('
19
R2

R2
R
10
R

R27
20
R3

R3
R
11
R

R28
3
21
R4

R4
R
12
R

R29
22
R5

R5
R
13
R

R30
23
5

5
R
14

!
R

R31
24
R7

R7
R
15
R

R32
R8

R8

J1

5
TB2 TB3 TB5 7%

J2 J2
/ /
J3 J3

L- P1 P2 L-

9'& Second term panel

*
$ ,1 
$FWLYH
Pulse
Sensor
2E (IN1 –)

RTN

Energy Not
limited energy limited

Figure 225 Field Wiring for 9572-610F with a 3515 Pulse Totalizer Input Module

With the 3515 pulse totalizer input module, sensor pulse outputs should be the push-pull type.
You may use high-side or low-side, solid-state output, but maximum frequency may be reduced
based on cable distance. Do not use mechanical relay/switch contacts. To prevent point-to-
point cross-talk, use individually shielded, twisted-pair wire for lengths greater than 50 feet (15
meters).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 289

Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with a
commoned input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

310 Ohms Max


opto-
isolated

Test A

30V
to
other Threshold to
points Detect Input
250 Ohms Opto-Isolator Mux B

PS1

PS2

Test B
PS1

PS2

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
*ATEX module

PE GND

Test C
PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 226 Simplified Schematic of a 3503E or 3505E Digital Input Module with a 9572-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
290 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

This is a simplified schematic of a typical 32-point pulse totalizer input module with a
commoned input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT TOTALIZER INPUT MODULE

AC/DC Input Circuit

Leg-to-
Leg
Isolation To
Threshold Counters
Detect
Opto-Isolator Leg A

310 Ohms Max

To
Threshold
~ 30V Detect
Counters
to Opto-Isolator Leg B
other
points
250 Ohms

PS1

PS2

PS1
To
PS2 Threshold Counters
to Detect
spare Opto-Isolator Leg C
*ATEX module
PE GND

PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 227 Simplified Schematic of a 3515 Pulse Totalizer Input Module with a 9572-610F Panel

9570-610F (24 VDC, high-density, 32 pts.)


Termination panel 9570-610F is compatible with the 3504E 24 VDC, high-density digital input
module. Each panel has:
• Four, sixteen-position field terminals; support for 32 points
• Two terminals per point, for dry contact
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9570-610F have 64 points, which means you must use two term
panels for each module. Each term panel comes with two sets of labels: 1-32 and 33-64. For
information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 291

Specifications
This table describes general specifications for 9570-610F.

Table 176 General Specifications for Term Panel 9570-610F


Feature Description
Panel type Commoned, high-density
Points 32

This table describes cable and load parameters for 9570-610F.

Table 177 Cable and Load Parameters for Term Panel 9570-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 18 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Input Connection (–) Specifications

Maximum input voltage Ui Vmax 32 V


Maximum input current Ii Imax 0.0145 A
Maximum input power Pi Pi 0.464 W
C internal, maximum Ci Ci 0.058 µF
L internal, maximum Li Li 30.0 µH
Output Connection (+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.18 µF
L external, maximum Lo La 4.96 mH

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
292 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Compatible Modules
This table describes the digital input module compatible with 9570-610F.

Table 178 Module Compatible with 9570-610F


Module Model Points per
Module Description
Number Module
3504E 64 24 VDC, commoned, high-density, DC-coupled, TMR

Field Wiring Diagrams


This figure illustrates how to connect a 3504E digital input module and a 9570-610F to the field
(1 of 64 module points shown).

TRICONEX 7400273 REV B 61 TRICON


ƒ&”7$”ƒ& EXT TERM TRICON $7(;(0&)$,/6$)(',+'',+'$, ƒ&”7$”

'21276(3$5$7(:+(1(1(5*,=('
$:*
12

20

28
10

18

19

26

27
11

13

15

21

23

29

31
14

22

30
24
17

25
16

32
4
2

4
5

3
6

5
1

6
1
R

R
R

R
R

R
R

R
R

R
R
R

R
R

R
DVVKRUWDV
SRVVLEOH
R34

R35

R36

R38

R42

R43

R44

R46

R50

R51

R52

R54

R58

R59

R60

R62
R37

R45

R53

R61
R40

R48

R56

R64
R39

R47

R55

R63
R33

R41

R49

R57

R34

R35
R33
J3
R65

R66

R67

R68

R69

R70

R71

R72

R73

R74

R75

R76

R77

R78

R79

R80

R81

R82

R83

R84

R85

R86

R87

R88

R89

R90

R91

R92

R93

R94

R95

R96

R65

R66

R67
TB1 TB2 TB1
!

TB3 TB4 TB5 TB6


10

12

14

18

19

20

22
13

26

27

28

30
21

29
16
15

24
23

32
17

31
25
11
2

6
5

8
7
1

J1 J4 J1
/ / /

J2 J5 J2
/ / /
P1 P2

36 6HFRQGWHUPSDQHO
7\SLFDOSRLQW 
RISRLQWVVKRZQ '&
Power
 6XSSO\
)LHOG
&RQWDFW 36
 '&
Power
 6XSSO\

(QHUJ\OLPLWHG 1RWHQHUJ\OLPLWHG (QHUJ\OLPLWHG

Figure 228 Field Wiring for 9570-610F with a 3504E DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 293

Simplified Schematics
This is a simplified schematic of a typical 64-point commoned digital input module with a
commoned input panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT HIGH-DENSITY DIGITAL INPUT MODULE

Mux
to
spare 1
Amp ADC
310 Ohms Max

64

Hi-Ref

30V Low-Ref

to Mux
other
points
2.7K 1
Amp ADC

PS1 64

PS2 Hi-Ref
Low-Ref
PS1

PS2 Mux

1
Amp ADC

*ATEX
64
PE GND
Hi-Ref
Low-Ref
PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 229 Simplified Schematic of a 3504E Digital Input Module with a 9570-610F Panel

9571-610F (24 VDC, fail-safe, 32 pts.)


Termination panel 9571-610F is compatible with the 3564 24 VDC, fail-safe digital input module.
Each panel has:
• Four, sixteen-position field terminals; support for 32 points
• Two terminals per point, for dry contact
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor.
The panel supports redundant 24 VDC power sources with diode ORing.
The modules compatible with 9571-610F have 64 points, which means you must use two term
panels for each module. Each term panel comes with two sets of labels: 1-32 and 33-64. For
information on how to apply the labels, see Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
294 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Specifications
This table describes general specifications for 9571-610F.

Table 179 General Specifications for Term Panel 9571-610F


Feature Description
Panel type Commoned, fail-safe
Points 32

This table describes cable and load parameters for 9571-610F.

Table 180 Cable and Load Parameters for Term Panel 9571-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 15 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Output Connection (+ and –) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.19 µF
L external, maximum Lo La 4.96 mH

Compatible Modules
This table describes the digital input module compatible with 9571-610F.

Table 181 Module Compatible with 9571-610F


Module Model Points per
Module Description
Number Module
3564 64 24 VDC, commoned, fail-safe, single

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Input Term Panels 295

Field Wiring Diagrams


This figure illustrates how to connect a 3564 digital input module and a 9571-610F to the field
(1 of 64 module points shown).

TRICONEX 7400273 REV B 61 TRICON


ƒ&”7$”ƒ& EXT TERM TRICON $7(;(0&)$,/6$)(',+'',+'$, ƒ&”7$”

'21276(3$5$7(:+(1(1(5*,=('
$:*

12

20

28
10

18

19

26

27
11

13

15

21

23

29

31
14

22

30
24
17

25
16

32
4
2

4
5

3
6

5
1

6
1
R

R
R

R
R

R
R

R
R

R
R
R

R
R

R
DVVKRUWDV
SRVVLEOH

R34

R35

R36

R38

R42

R43

R44

R46

R50

R51

R52

R54

R58

R59

R60

R62
R37

R45

R53

R61
R40

R48

R56

R64
R39

R47

R55

R63
R33

R41

R49

R57

R34

R35
R33
J3
R65

R66

R67

R68

R69

R70

R71

R72

R73

R74

R75

R76

R77

R78

R79

R80

R81

R82

R83

R84

R85

R86

R87

R88

R89

R90

R91

R92

R93

R94

R95

R96

R65

R66

R67
TB1 TB2 TB1

!
10 TB3 TB4 TB5 TB6

12

14

18

19

20

22
13

26

27

28

30
21

29
16
15

24
23

32
17

31
25
11
2

6
5

8
7
1

J1 J4 J1
/ / /

J2 J5 J2
/ / /
P1 P2

36 6HFRQGWHUPSDQHO
7\SLFDOSRLQW 
RISRLQWVVKRZQ '&
Power
 6XSSO\
)LHOG
&RQWDFW 36
 '&
Power
 6XSSO\

(QHUJ\OLPLWHG 1RWHQHUJ\OLPLWHG (QHUJ\OLPLWHG

Figure 230 Field Wiring for 9571-610F with a 3564 DI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
296 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 64-point, fail-safe, commoned digital input module
with a commoned input panel (1 of 64 module points shown).

TERMINATION PANEL CABLE BACKPLANE 64-POINT DIGITAL INPUT MODULE

to
spare
Test ON Relays
310 Ohms Max (opto-isolated)
to other
points &
sensors

310 Ohms Max


30V
to
other
points
A

Threshold Detect
PS1 Opto-Isolator B

PS2
C

Test OFF Relays


PS1 (opto-isolated)
to
PS2 other
points

*ATEX

PE GND

PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 231 Simplified Schematic of a 3564 Digital Input Module with a 9571-610F Panel

Digital Output Term Panels


This section describes digital output term panel 9671-610F (24 VDC, commoned, supervised,
16 pts.).

9671-610F (24 VDC, commoned, supervised, 16 pts.)


Termination panel 9671-610F is compatible with 24 VDC, commoned, supervised digital output
modules. Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point for field devices: L+, L–
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
The panel supports redundant 24 VDC power sources with diode ORing.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 297

When using 32 point modules, you must use two term panels for each digital output module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes general specifications for 9671-610F.

Table 182 General Specifications for Term Panel 9671-610F


Feature Description
Panel type Commoned, supervised
Points 16

This table describes cable and load parameters for 9671-610F.

Table 183 Cable and Load Parameters for Term Panel 9671-610F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Working voltage Uw Uw 16 to 32 V
Maximum voltage Um Um 32 V
Maximum working current n/a n/a 0.028 A
Output Connection (F+) Specifications

Maximum output voltage Uo Voc 32 V


Maximum output current Io Isc 0.169 A
Maximum output power Po Po 1.347 W
C external, maximum Co Ca 1.16 µF
L external, maximum Lo La 4.96 mH

Compatible Modules
This table describes digital output modules compatible with 9671-610F.

Table 184 Modules Compatible with 9671-610F


Module Model Points per
Module Description
Number Module
3604E 16 24 VDC, non-commoned, opto-isolated, TMR
3624 16 24 VDC, commoned, supervised, opto-isolated, self-protected, TMR
3625/Aa 32 24 VDC, commoned, supervised/non-supervised, self-protected, TMR
3664 32 24 VDC, commoned, opto-isolated, self-protected, dual
3674 32 24 VDC, commoned, opto-isolated, self-protected, dual

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
298 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

a. Schneider Electric recommends that the termination panels for the 3625 and 3625A modules are
wired in parallel and powered from the same redundant field power sources. The 3625A module
may be powered from four independent field power sources, but only if the voltage from those
sources is within 5% of the highest voltage supplied. If this restriction is not followed, the module
will still operate but may experience voter faults and generate an alarm.

Field Wiring Diagrams


This figure illustrates how to connect a 3604E, 3624, 3625, or 3625A digital output module and
a 9671-610F to the field (16 of 16 points shown).

TRICONEX - 7400274
REV B
ƒ&”7$”ƒ& SN

'21275(029()86(:+(1(1(5*,=('
'21276(3$5$7(:+(1(1(5*,=('
$7(;&20021(' '2
EXT TERM TRICON

7%

TB3 TB4 TB5 7% TB2

!










2


5

8
7


/

J2
3 3 L- Load *

J3

36

'&
3RZHU
Supply
-

36
'&

3RZHU
Supply -

Not energy limited Energy limited

$ORDGPXVWEHLQVWDOOHGDWHYHU\SRLQWWRSUHYHQWPLVVLQJORDGDODUP,IDILHOGORDGLVDYDLODEOHLQVWDOOD2KP:ORDGUHVLVWRU

Figure 232 Field Wiring for 9671-610F with a 3604E, 3624, 3625, or 3625A DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 299

This figure illustrates how to connect a 3664 or a 3674 dual digital output module and a
9671-610F to the field (1 of 32 module points shown).

TRICONEX J1 7400274 TRICONEX


REV B
ƒ&”7$”ƒ& SN ƒ&”7$”ƒ&

'21275(029()86(:+(1(1(5*,=('
'21276(3$5$7(:+(1(1(5*,=('

$7(; COMMONED DO
$7(; COMMONED DO

EXT TERM TRICON


EXT TERM TRICON

TB1 TB1

TB3 TB4 TB5 7% TB2 TB3 TB4 TB5 7%

!
10

12

14
13


15
11
2


5

8
7
1

9
/

J2
P1 P2 L- P1 P2

J3

PS1 Second term panel



DC
Power Typical point
Supply
- RISRLQWVVKRZQ

PS2
 Load
DC
Power
Supply -

Not energy limited Energy limited

Figure 233 Field Wiring for 9671-610F with a 3664 or 3674 DO Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
300 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 16-point non-commoned digital output module with
a commoned output panel (1 of 16 module points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B points
L+
A "B 310 Ohms Max
Output 30V
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot *ATEX
Drive PE GND
spare
Circuitry
A Voltage
B Loopback
C Detector
PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 234 Simplified Schematic of a 3604E Digital Output Module with a 9671-610F Panel

This is a simplified schematic of a typical 16-point, supervised, digital output module with self
protection and a commoned digital output panel (1 of 16 module points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

OVD Switch #1

A Voltage
B Loopback to other
C Detector points

A
Output PS1 +
Switch
Drive PS2 +
to other
Circuitry A B points
L+
A "B 310 Ohms Max
Output OVD Switch #2 30V
Switch
Drive L–
Circuitry
PS1 –
B to other
points PS2 –
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output *ATEX
to
Switch hot PE GND
Drive spare
Circuitry
A Voltage
B Loopback
C Detector
PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 235 Simplified Schematic of a 3624 Digital Output Module with a 9671-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Digital Output Term Panels 301

This is a simplified schematic of a typical 32-point, supervised, digital output module with self
protection and a commoned digital output panel (1 of 32 module points shown).

32-POINT DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL


A
Output
Switch
Drive
Circuitry PS1 +

PS2 +
A or C
*to other to other
A B points points
Output L+
Switch
Drive 310 Ohms Max
Circuitry
30V

L–
B
Output PS1 –
Switch to other
Drive points
Circuitry
PS2 –

C A or C

C
Current
Output Loopback
Switch Detector **ATEX
Drive Analog/ PE GND
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector
PE GND

*For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the
3625A module, field power is commoned in groups of 16 points and is separated by termination panels.
**ATEX-required protective earth (chassis ground) to functional earth jumpers
Figure 236 Simplified Schematic of a 3625 or 3625A Digital Output Module with a 9671-610F Panel

This is a simplified schematic of a typical 32-point, dual digital output module with self
protection and a commoned digital output panel (1 of 32 module points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE CABLE TERMINATION PANEL

A Voted PS1 +
Output
B PS2 +
Drive
to other
C Circuitry points
L+
310 Ohms Max

A Voted 30V
Drive
B L–
Output
C Circuitry
PS1 –
to other
points PS2 –

A Loopback
Detector/
*ATEX
B PE GND
C Isolator
to
hot
spare

to other points PE GND

* ATEX-required protective earth (chassis ground) to functional earth jumpers

Figure 237 Simplified Schematic of a 3664 or 3674 Digital Output Module with a 9671-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
302 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Pulse Input Term Panels


This section describes pulse input term panel 9793-110F (pulse input, 8 pts.).

9793-110F (pulse input, 8 pts.)


Termination panel 9793-110F is compatible with pulse input modules. Each panel has:
• Two, sixteen-position field terminals; support for 8 points
• Two terminals per point for differential analog input: I+, I–
• Two, one-position terminals for protective earth connection

Specifications
This table describes specifications for 9793-110F.

Table 185 Specifications for Term Panel 9793-110F


Feature Description
Panel type Pulse input
Points 8

This table describes cable and load parameters for 9793-110F.

Table 186 Cable and Load Parameters for Term Panel 9793-110F
IEC ISA
Feature Description for Zone 2 Group IIB
Symbol Symbol
Operating temperature range Tamb Tamb 32° F to 140° F (0° C to 60° C)
Input Connection (I+ and I–) Specifications

Maximum input voltage Ui Vmax 32 V


Maximum input current Ii Imax 0.00355 A
Maximum input power Pi Pi 0.1136 W
C internal, maximum Ci Ci 0.038 µF
L internal, maximum Li Li 0.043 µH
Output Connection (I+ and I–) Specifications

Maximum output voltage Uo Voc 15 V


Maximum output current Io Isc 0.005 A
Maximum output power Po Po 0.075 W
C external, maximum Co Ca 20.14 µF
L external, maximum Lo La 1H

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 303

Compatible Modules
This table describes pulse input modules compatible with 9793-110F.

Table 187 Modules Compatible with 9793-110F


Module Model Points per
Module Description
Number Module
3511 8 20 Hz to 20 kHz pulse input, non-commoned, AC-coupled,
25 ms typical input update rate

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
304 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 3511 pulse input module and a 9793-110F to the field.

ƒ&”7$”ƒ&
TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1
EXT TERM TRICON

REV B
$7(;(0&$,7&

J2
/

7400272
SN
J3
L-

IN1 – Typical passive Typical


speed sensor unused point
IN1 

F
Typical point
F– (1 of 8 points shoZn 
RT

**

*
* )XQFWLRQDOHDUWKJURXQG TXLHWJURXQG LVUHFRPPHQGHGIRUVKLHOGFRQQHFWLRQV)RUVKLHOGJURXQGLQJLQVWUXFWLRQVVHH$SSHQGL[(
* * :KHQSRVVLEOHLQVWDOODWHUPLQDWLQJUHVLVWRUDVVKRZQ)RUIXUWKHULQIRUPDWLRQVHH7HFKQLFDO$SSOLFDWLRQ1RWH 7$1 RQWKH
*OREDO&XVWRPHU6XSSRUW *&6 FHQWHUZHEVLWH

Figure 238 Field Wiring for 9793-110F with a 3511 PI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 305

Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
pulse input panel (1 of 8 module points shown).

TERMINATION CABLE BACKPLANE 8-POINT PULSE INPUT MODULES


PANEL

to
spare Comparator
+15
AC coupled A
Counter/ Micro-
Timer Processor

-15 to
other
points
IN1

IN1
+15
Comparator
+15
14V AC coupled B
Counter/ Micro-
Timer Processor
14V
-15 to
other
-15 points

*ATEX

PE GND Comparator
+15
AC coupled
C
PE GND
Counter/ Micro-
Timer Processor

-15 to
other
points

* ATEX-required protective earth (chassis ground) to functional earth jumpers


Figure 239 Simplified Schematic of a 3511 PI Module with a 9793-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
306 Chapter 6 Hazardous Location (Nonincendive) Termination Panels

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
7
RG 1.180 Termination Panels

Overview 308
Analog Input Term Panels 308
Analog Output Term Panels 331
Pulse Input Term Panels 336
RTD/TC/AI Input Term Panels 338

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
308 Chapter 7 RG 1.180 Termination Panels

Overview
In October 2003, the United States Nuclear Regulatory Commission (NRC) issued Revision 1 of
Regulatory Guide 1.180, “Guidelines for Evaluating Electromagnetic and Radio-Frequency
Interference in Safety-Related Instrumentation and Control Systems.” Regulatory Guide 1.180
endorses design, installation, and testing practices acceptable to the NRC staff for addressing
the effects of EMI/RFI and power surges on safety-related instrumentation and control (I&C)
systems in a nuclear power plant environment.
This chapter describes external termination panels (ETPs) that can be used in applications that
are required to meet RG 1.180 guidelines. Note that throughout this manual these term panels
are referred to as “RG 1.180” termination panels.
This table identifies RG 1.180 ETPs.

Table 188 RG 1.180 External Termination Panels


Term Panel Type Term Panel Model Description
Analog Input 9790-610F 4-20 mA, 0–5 VDC, 16 pts.
9795-610F 4-20 mA, 0–10 VDC, 16 pts.
9792-610F 4-20 mA, 0-5 VDC, 16 pts., 16 VDC–56 VDC field
9783-110F 0-5 VDC, voltage input, 16 pts.
9782-110F TC input, isolated, 16 pts.
Analog Output 9860-610F 8 pts.
Pulse Input 9794-110F 16 pts.
RTD/TC/AI 9764-310F RTD/TC/AI input, 16 pts.
Input

Analog Input Term Panels


This section describes analog input termination panels that you can use in applications that
need to meet RG 1.180 requirements. Model numbers include:
• 9790-610F (4-20 mA, 0–5 VDC, 16 pts.)
• 9795-610F (4-20 mA, 0–5 VDC, 16 pts.)
• 9792-610F (4-20 mA, 0-5 VDC, 16 pts., user-configurable, 16 VDC–56 VDC field)
• 9783-110F (0-5 VDC voltage input, 16 pts.)
• 9782-110F (TC input, upscale/downscale, 16 pts.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 309

9790-610F (4-20 mA, 0–5 VDC, 16 pts.)


Termination panel 9790-610F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with 0 to 5 VDC analog input modules and HART analog input
interface modules. Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for 4-20 mA transmitter (F+, F–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor. Each input has a
precision 250-ohm resistor for 0-to-5 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
When using 32-point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Specifications
This table describes general specifications for 9790-610F.

Table 189 General Specifications for Term Panel 9790-610F


Feature Description
Panel type Current input, 4–20 mA
Points 16

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
310 Chapter 7 RG 1.180 Termination Panels

Compatible Modules
This table describes analog input modules compatible with 9790-610F.

Table 190 Modules Compatible with 9790-610F


Module Model Points per
Module Description
Number Module
2770H 32 HART analog input interface
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
input range), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

When used with the 9790-610F, the accuracy of the 3700A, 3703E, and 3721 modules may be
affected by up to –0.08% Full-Scale Range (FSR), at maximum temperature. As a result, the
accuracy of these modules is +0.15% to –0.23% FSR, at 140° F (60° C).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 311

Field Wiring Diagrams


This figure illustrates how to connect a 3700A, 3703E, or 3721 analog input module, or a HART
analog input interface module, and a 9790-610F to the field (1 of 16 or 32 module points shown).
See Appendix E, Shield Ground for shield ground installation guidelines.

TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B ƒ&”7$”ƒ& 7400275
as short as possible

17
R
SN SN

R25
18
R1

R1
R
9
R
TB1 TB4 TB1

5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2

R2
R
10
R

R27
20
R3

R3
R
11
R

R28
3
21
R4

R4
R
12
R

R29
22
R5

R5
R
13
R

R30
23
5

5
R
14

!
R

R31
24
R7

R7
R
15
R

R32
R8

R8

J1
5
TB2 TB3 TB5 7%

J2 J2
L+ /
J3 J3

L- 3 3 L-

Second term panel


if using a 32-point
Typical point 36 module
RIRUSRLQWVVKRZQ -
'&
3RZHU
  Supply
Field Xmtr
- P$
36
- '&
3RZHU
 Supply

Shield Ground

Energy limited Not energy limited

Figure 240 Field Wiring for 9790-610F with a 3700A, 3703E, or 3721 AI Module or 2770H HART AI
Interface Module

For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
312 Chapter 7 RG 1.180 Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

190–310 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 241 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9790-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 313

This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux

1 Amp ADC

190–310 Ohms 16
Hi-Ref
Low-Ref

Mux
to
other
points
250 Ohms 1 Amp ADC

PS1
16
PS2
Hi-Ref

PS1 Low-Ref

PS2
Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 242 Simplified Schematic of a 3703E Analog Input Module with a 9790-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
314 Chapter 7 RG 1.180 Termination Panels

This is a simplified schematic of a Model 2770H HART Analog Input Interface Module with a
current input panel (1 of 32 module points shown).

HART CONTROLLER RS-485 2770H HART AI INTERFACE MODULE BACKPLANE 32-POINT ANALOG INPUT MODULES
CABLE

to
spare Mux
HART 2071H HART Isolation/filtering
CONTROLLER MUX Module

1 Amp ADC

190-310 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
TERMINATION PANEL FIELD
Low-Ref
CABLE

Figure 243 Simplified Schematic of a 2770H HART AI Interface Module with a 3700A or 3721 Analog
Input Module and a 9790-610F Panel

9795-610F (4-20 mA, 0–5 VDC, 16 pts.)


Termination panel 9795-610F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with 0 to 10 VDC analog input modules. Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for 4-20 mA transmitter (F+, F–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a 190-to-310-ohm series resistor. Each input has a
precision 500-ohm resistor for 0-to-10 VDC current-to-voltage conversion.
The panel supports redundant 24 VDC power sources with diode ORing.
When using 32-point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 315

Specifications
This table describes general specifications for 9795-610F.

Table 191 General Specifications for Term Panel 9795-610F


Feature Description
Panel type Current input, 4–20 mA
Points 16

Compatible Modules
This table describes analog input modules compatible with 9795-610F.

Table 192 Modules Compatible with 9795-610F


Module Model Points per
Module Description
Number Module
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
input range), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

When used with the 9795-610F, the accuracy of these modules may be affected by up to –0.08%
Full-Scale Range (FSR), at maximum temperature. As a result, the accuracy of these modules is
+0.15% to –0.23% FSR, at 140° F (60° C).

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
316 Chapter 7 RG 1.180 Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 3703E or 3721 analog input module and a 9795-610F to
the field (1 of 16 or 32 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

TRICONEX
EXT TERM TRICON EXT TERM
$7(;(0&$,', $7(;(0&
$:*
7400275 REV B ƒ&”7$”ƒ& 7400275
as short as possible

17
R
SN SN

R25
18
R1

R1
R
9
R
TB1 TB4 TB1

5
'21276(3$5$7(
:+(1(1(5*,=('
19
R2

R2
R
10
R

R27
20
R3

R3
R
11
R

R28
3
21
R4

R4
R
12
R

R29
22
R5

R5
R
13
R

R30
23
5

5
R
14

!
R

R31
24
R7

R7
R
15
R

R32
R8

R8


J1
5

TB2 TB3 TB5 7%

J2 J2
L+ /
J3 J3

L- 3 3 L-

Second term panel


if using a 32-point
Typical point 36 module
RIRUSRLQWVVKRZQ -
'&
3RZHU
  Supply
Field Xmtr
- P$
36
- '&
3RZHU
 Supply

Shield Ground

Energy limited Not energy limited

Figure 244 Field Wiring for 9795-610F with a 3703E or 3721 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 317

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
current input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

190–310 Ohms
32
Hi-Ref
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC
PS1

PS2

32
PS1 Hi-Ref
PS2 Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 245 Simplified Schematic of a 3721 Analog Input Module with a 9795-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
318 Chapter 7 RG 1.180 Termination Panels

This is a simplified schematic of a typical 16-point non-commoned analog input module with a
current input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux

1 Amp ADC

190–310 Ohms 16
Hi-Ref
Low-Ref

Mux
to
other
points
250 Ohms 1 Amp ADC

PS1
16
PS2
Hi-Ref

PS1 Low-Ref

PS2
Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 246 Simplified Schematic of a 3703E Analog Input Module with a 9795-610F Panel

9792-610F (4-20 mA, 0-5 VDC, 16 pts., user-configurable, 16 VDC–56 VDC


field)
Termination panel 9792-610F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with 0 to 5 VDC and -5 to +5 VDC analog input modules. Each
panel has:
• Three, sixteen-position field terminals; support for 16 points
• One terminal per point for power output (T+)
• Two terminals per point for 4-20 mA transmitter (T-, A); points are jumper configurable
• Two, one-position terminals for protective earth connection
Each positive terminal is current-limited with a series 250 ohm PTC in parallel with a 3.3 kilohm
resistor. Each input has a precision 250 ohm resistor for 0–5 VDC current-to-voltage conversion.
The panel supports redundant 16 VDC–56 VDC power sources with diode ORing.
When configuring the 9792-610F termination panel to a compatible analog input module, use
the following equation to determine the appropriate field voltage. Transmitter compliance

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 319

voltage is dependent on the loop power provided on the ETP (T+) within the range of 16 VDC
to 56 VDC.
Vloop > Vfield – Vdiode – ((300 Ohms) * ICC Transmitter) – 5.3 VDC

Equation Element Description


Vloop Transmitter compliance voltage
Vfield External power supply
Vdiode 0.8 VDC worst-case
ICC Transmitter See transmitter datasheet for value
300 Ohms Corresponds to PTC resistance (250 Ohms + 20% component
tolerance)
5.3 VDC Corresponds to I*R drop of 20 mA loop current, with 6% over-
range across precision 250 Ohm resistance

When using 32-point modules, you must use two term panels for each analog input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.

Specifications
This table describes specifications for 9792-610F.

Table 193 Specifications for Term Panel 9792-610F


Feature Description
Panel type Current input, user-configurable
Points 16

Compatible Modules
This table describes analog input modules compatible with 9792-610F.

Table 194 Modules Compatible with 9792-610F


Module Model Points per
Module Description
Number Module
3700 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
for 0–5 VDC), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
320 Chapter 7 RG 1.180 Termination Panels

When used with the 9792-610F, the accuracy of these modules may be affected by up to -0.08%
Full-Scale Range (FSR), at maximum temperature. As a result, the accuracy of these modules is
+0.15% to -0.23% FSR, at 140° F (60° C).

Field Wiring Diagrams


This figure illustrates how to connect a 16-point or 32-point analog input module and a
9792-610F to the field (1 of 16 or 32 module points shown). See Appendix E, Shield Ground for
shield ground installation guidelines.

12 AWG,
as short as possible

T+

Second term panel

PS2
Typical point (1 of 16 points shown) DC
Power
Supply
+
Field Xmtr PS1
– (4-20 mA) DC
Power
Supply

Shield Ground

Figure 247 Field Wiring for 9792-610F with a 3700, 3700A, 3703E, or 3721 AI Module

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 321

This figure illustrates how to connect a 16-point or 32-point analog input module and a
9792-610F to the field and another system, such as a DCS (1 of 16 or 32 module points shown).
See Appendix E, Shield Ground for shield ground installation guidelines.

This jumper must be


removed in sharing
applications.

12 AWG,
as short as possible

T+

Second term panel

DCS
* * PS2
Typical point (1 of 16 points shown) DC
Power
Supply
+
Field Xmtr PS1
– (4-20 mA) DC
Power
Supply

Shield Ground

* Return may be connected to an unused A terminal with the JP jumper in place or to a – PS terminal.

Figure 248 Field Wiring for 9792-610F with a 3700, 3700A, 3703E, or 3721 AI Module—Sharing with
Another System

Sharing a transmitter between the Tricon controller and another system may violate restrictions
regarding the segregation of safety and control functions. The sharing capability of this
termination panel should only be used in those applications where these restrictions do not
exist, or can be otherwise mitigated.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
322 Chapter 7 RG 1.180 Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 32-point analog input module with a current input
panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering
PS1

PS2 1 Amp ADC

250 ohm PTC

+t
IN 32
3.3 kilohms Hi-Ref
IN
Low-Ref

to Mux
other
points
250 Ohms

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux
A

JP** 1 Amp ADC

PS1

PS2
JP17 * Hi-Ref
32

Low-Ref

* When the 9792-610F panel is used with a 3700A or a 3721 module, do not remove the JP17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the JP jumper may be removed.

Figure 249 Simplified Schematic of a 3700, 3700A, or 3721 AI Module with a 9792-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 323

This is a simplified schematic of a typical 16-point analog input module with a current input
panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES

to
spare Mux
PS1

PS2 1 Amp ADC

250 ohm PTC

+t
16
IN
3.3 kilohms Hi-Ref
IN Low-Ref

Mux
to
other
points
250 Ohms 1 Amp ADC

16
A
Hi-Ref
Low-Ref

Mux

JP**
1 Amp ADC

PS1 16
JP17 * Hi-Ref
PS2
Low-Ref

* For extended common-mode operation, you must remove the JP17 jumper.
** To aid sharing the field transmitter with another system (for example, a DCS), the JP jumper may be removed.

Figure 250 Simplified Schematic of a 3703E AI Module with a 9792-610F Panel

9783-110F (0-5 VDC voltage input, 16 pts.)


Termination panel 9783-110F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with 0 to 5 VDC analog input modules. Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
When using 32-point modules, you must use two term panels for each module. Each term panel
comes with two sets of labels: 1-16 and 17-32. For information on how to apply the labels, see
Appendix F, Panel Labels.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
324 Chapter 7 RG 1.180 Termination Panels

Specifications
This table describes general specifications for 9783-110F.

Table 195 General Specifications for Term Panel 9783-110F


Feature Description
Panel type Voltage input, 0–5 VDC
Points 16

Compatible Modules
This table describes analog input modules compatible with 9783-110F.

Table 196 Modules Compatible with 9783-110F


Module Model Points per
Module Description
Number Module
3700A 32 0–5 VDC, non-commoned, differential, DC-coupled, TMR, +6% input
over-range measurement
3703E 16 0–5 VDC or 0–10 VDC (use the TriStation 1131 software to configure
input range), non-commoned, differential, isolated, TMR
3721 32 0 to 5 VDC or –5 to +5 VDC (use the TriStation 1131 software to
configure input range), differential, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 325

Field Wiring Diagrams


This figure illustrates how to connect a 3700A, 3703E, or 3721 analog input module and a
9783-110F to the field (1 of 16 or 32 module points shown). See Appendix E, Shield Ground for
shield ground installation guidelines.

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1 TB1
EXT TERM TRICON

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ

V
Field
Source

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
326 Chapter 7 RG 1.180 Termination Panels

ƒ&”7$”ƒ&

ƒ&”7$”ƒ&
TRICONEX

TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1 TB1
EXT TERM TRICON

EXT TERM TRICON


REV B
$7(;(0&$,7&

$7(;(0&$,7&
J2 J2
/ /

7400272
SN
J3 J3
L- L-

Typical
unused point Second term panel
if using a 32-point
Typical point module
RIRUSRLQWVVKRZQ

V
Field
Source

Figure 251 Field Wiring for 9783-110F with a 3700A, 3703E, or 3721 AI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 327

Simplified Schematics
This is a simplified schematic of a typical 32-point non-commoned analog input module with a
voltage input panel (1 of 32 module points shown).

TERMINATION PANEL CABLE BACKPLANE 32-POINT ANALOG INPUT MODULES

to
spare Mux
Isolation/filtering

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Mux

1 Amp ADC

32
Hi-Ref
Low-Ref

Figure 252 Simplified Schematic of a 3700A or 3721 Analog Input Module with a 9783-110F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
328 Chapter 7 RG 1.180 Termination Panels

This is a simplified schematic of a typical 16-point commoned analog input module with a
voltage input panel (1 of 16 module points shown).

TERMINATION CABLE BACKPLANE 16-POINT ANALOG INPUT MODULES


PANEL

to
spare Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 253 Simplified Schematic of a 3703E Analog Input Module with a 9783-110F Panel

9782-110F (TC input, upscale/downscale, 16 pts.)


Termination panel 9782-110F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with isolated thermocouple input modules.
Each panel has:
• Two, sixteen-position field terminals; support for 16 points
• Two terminals per point, for differential analog input (I+, I–)
• Two, one-position terminals for protective earth connection
• TMR cold-junction temperature sensors
• Upscale/downscale open-input bias circuitry

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Input Term Panels 329

Specifications
This table describes general specifications for 9782-110F.

Table 197 General Specifications for Term Panel 9782-110F


Feature Description
Panel type Thermocouple input, upscale or downscale
Points 16

Compatible Modules
This table describes the analog input module compatible with 9782-110F.

Table 198 Module Compatible with 9782-110F


Module Model Points per
Module Description
Number Module
3708E 16 Type E, J, K, and T, differential, isolated, DC-coupled, TMR, upscale
or downscale open-input detection. (Use the TriStation 1131 software
to configure the thermocouple type and specify upscale or downscale
open-input detection.)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
330 Chapter 7 RG 1.180 Termination Panels

Field Wiring Diagrams


This figure illustrates how to connect a 3708E thermocouple input module and a 9782-110F to
the field (1 of 16 module points shown). See Appendix E, Shield Ground for shield ground
installation guidelines.

ƒ&”7$”ƒ&
TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

! TB2
TB1
EXT TERM TRICON

REV B
$7(;(0&$,7&

J2
/

7400272
SN
J3
L-

Typical
unused point

Typical point
RISRLQWVVKRZQ


-

Shield Ground

Figure 254 Field Wiring for 9782-110F with a 3708E Thermocouple Input Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 331

Simplified Schematics
This is a simplified schematic of a typical 16-point thermocouple input module with a
thermocouple input panel (1 of 16 module points shown).

TERMINATION PANEL CABLE BACKPLANE 16-POINT THERMOCOUPLE INPUT MODULES

to
spare Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Mux

1 Amp ADC

16
Hi-Ref
Low-Ref

Figure 255 Simplified Schematic of a 3708E Thermocouple Input Module with a 9782-110F Panel

Analog Output Term Panels


This section describes analog output term panel 9860-610F (3805E/H module, 8 pts.), which you
can use in applications that need to meet RG 1.180 requirements.

9860-610F (3805E/H module, 8 pts.)


Termination panel 9860-610F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with 3805E and 3805H 4–20 mA output modules and 2870H
HART analog output interface modules. Each panel has:
• Two, eight-position field terminals; support for eight points
• Two terminals per point: Out, Rtn (L+, L–)
• A four-position terminal for redundant 24 VDC loop power
• Two, one-position terminals for protective earth connection

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
332 Chapter 7 RG 1.180 Termination Panels

Specifications
This table describes specifications for 9860-610F.

Table 199 Specifications for Term Panel 9860-610F


Feature Description
Panel type Current output
Points 8

Compatible Modules
This table describes the analog output module compatible with 9860-610F.

Table 200 Module Compatible with 9860-610F


Module Model Points per
Module Description
Number Module
2870H 8 HART analog output interface
3805E/H 8 4–20 mA, commoned-return, DC-coupled, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 333

Field Wiring Diagrams


This figure illustrates how to connect a 3805E or 3805H analog output module, or a HART
analog output interface module, and a 9860-610F to the field (1 of 8 module points shown).

'21276(3$5$7(:+(1(1(5*,=('
L18 C24
J1
EXT TERM TRICON TRICONEX
L17 C22
$7(;(0&$2
7400270 C17

C20

C19
REV B
L12
ƒ&”7$”ƒ&

C14

C15
SN L15 /

/

L11
L13 L14
L5 C12

L9 L10
L4 C10

L7 L8
C5

L3

C8

C7
C2

C3

L1

L2
!

C35

&

&
C37

C38

C39

C40

C41

C42

C43

TB7 TB8
C44

R2

R1
TB1—TB4

J4
/
C27
C25

C45

L-
J5 P1 P2

Typical unused point


PS2
-
DC
Power
Typical point + Supply
(1 of 8 points shown)

PS1
- DC
Load
Power
+ Supply

Energy limited Not energy limited

Figure 256 Field Wiring for 9860-610F with a 3805E or 3805H AO Module or a 2870H HART AO
Interface Module

Unused points must be shorted together to avoid module diagnostic errors.


For additional instructions on installing HART Interface Modules, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
334 Chapter 7 RG 1.180 Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 8-point commoned-return analog output module with
an analog output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE CABLE TERMINATION


PANEL

A Loop power
PWRA

Selector
Logic
Current
loopback PWRB

DAC
RTN

B RTN

Selector
Logic Current
loopback

DAC
OUT2

Typical point

C RTN2

Selector
Logic
Current
loopback

DAC

Figure 257 Simplified Schematic of a 3805E or 3805H Analog Output Module with a 9860-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Analog Output Term Panels 335

This is a simplified schematic of a Model 2870H HART Analog Output Interface Module with
an analog output panel (1 of 8 module points shown).

8-POINT ANALOG OUTPUT MODULE BACKPLANE 2870H H A R T FIELD TERMINATION


AO INTERFACE MODULE CABLE PANEL

A Loop power
PWRA

Selector
Logic
Current
loopback PWRB

DAC
RTN

B RTN

Selector
Logic OUT2
Current
loopback
Typical point

DAC

RTN2
Selector
Logic
Current
loopback

VX1
DAC
VX2 2071 HART HART
MUX MODULE CONTROLLER

RS-485 HART
CABLE CONTROLLER

Figure 258 Simplified Schematic of a 2870H HART AO Interface Module with a 3805E or 3805H AO
Module and a 9860-610F Panel

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
336 Chapter 7 RG 1.180 Termination Panels

Pulse Input Term Panels


This section describes pulse input term panel 9794-110F (pulse input, 8 pts.), which you can use
in applications that need to meet RG 1.180 requirements.

9794-110F (pulse input, 8 pts.)


Termination panel 9794-110F is designed for use in applications that need to meet RG 1.180
requirements, and is compatible with pulse input modules. Each panel has:
• Two, sixteen-position field terminals; support for 8 points
• Two terminals per point for differential analog input: I+, I–
• Two, one-position terminals for protective earth connection

Specifications
This table describes specifications for 9794-110F.

Table 201 Specifications for Term Panel 9794-110F


Feature Description
Panel type Pulse input
Points 8

Compatible Modules
This table describes pulse input modules compatible with 9794-110F.

Table 202 Modules Compatible with 9794-110F


Module Model Points per
Module Description
Number Module
3511 8 20 Hz to 20 kHz pulse input, non-commoned, AC-coupled,
25 ms typical input update rate

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Pulse Input Term Panels 337

Field Wiring Diagrams


This figure illustrates how to connect a 3511 pulse input module and a 9794-110F to the field.

ƒ&”7$”ƒ&
TRICONEX
$:*

'21276(3$5$7(
WHEN ENERGIZED
as short as possible

J1

!
TB2
TB1
EXT TERM TRICON

REV B
$7(;(0&$,7&

J2
/

7400272
SN
J3
L-

IN1 – Typical passive Typical


speed sensor unused point
IN1 

F
Typical point
F– (1 of 8 points shoZn 
RT

**

*
* )XQFWLRQDOHDUWKJURXQG TXLHWJURXQG LVUHFRPPHQGHGIRUVKLHOGFRQQHFWLRQV)RUVKLHOGJURXQGLQJLQVWUXFWLRQVVHH$SSHQGL[(
* * :KHQSRVVLEOHLQVWDOODWHUPLQDWLQJUHVLVWRUDVVKRZQ)RUIXUWKHULQIRUPDWLRQVHH7HFKQLFDO$SSOLFDWLRQ1RWH 7$1 RQWKH
*OREDO&XVWRPHU6XSSRUW *&6 FHQWHUZHEVLWH

Figure 259 Field Wiring for 9794-110F with a 3511 PI Module

Unused points must be shorted together to avoid module diagnostic errors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
338 Chapter 7 RG 1.180 Termination Panels

Simplified Schematics
This is a simplified schematic of a typical 8-point non-commoned pulse input module with a
pulse input panel (1 of 8 module points shown).

TERMINATION CABLE BACKPLANE 8-POINT PULSE INPUT MODULES


PANEL

to
spare Comparator
AC coupled A
Counter/ Micro-
Timer Processor

to
other
points
IN1

IN1

Comparator
AC coupled B
Counter/ Micro-
Timer Processor

to
other
points

Comparator
AC coupled
C
Counter/ Micro-
Timer Processor

to
other
points

Figure 260 Simplified Schematic of a 3511 PI Module with a 9794-110F Panel

RTD/TC/AI Input Term Panels


Termination panel 9764-310F can be used in applications that are required to meet RG 1.180
guidelines. For more information, including a description, specifications, compatible modules,
field wiring diagrams, and simplified schematics, see 9764-310F (RTD/TC/AI input, 0–5 VDC,
16 pts.) on page 224.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
8
Fanned-Out Cables

Overview 340
Description of Fanned-Out Cables (9101-010F) 340
Fanned-Out Cables with Digital Input Modules 341
Fanned-Out Cables with Digital Output Modules 346

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
340 Chapter 8 Fanned-Out Cables

Overview
This chapter describes fanned-out cables and how to use them with digital I/O modules.

Description of Fanned-Out Cables (9101-010F)


Fanned-out cables are a low-cost alternative to using basic termination panels. Fanned-out
cables allow you to marshal field signals in a separate enclosure up to 90 feet (27.4 meters) from
a Tricon chassis. One end of a fanned-out cable has a female connector that connects to a Tricon
chassis backplane. The other end of the cable contains 50 fanned-out leads, each individually
labeled with its corresponding connector pin number.
Each fanned-out cable has the following characteristics:
• PVC outer covering
• 56-pin connector at one end
• 50 stranded, stripped, tinned and labeled 22-gauge leads at opposite end
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.
Fanned-out cables should only be used with digital input and digital output modules. They are
not certified for use with analog signals. Contact the Global Customer Support (GCS) center if
you need a fanned-out cable for handling analog signals.
The part number for a fanned-out cable is 9101-010F. The last two digits of the part number
represent the standard cable length of 10 feet (3 meters). You may specify a different cable length
for any product by replacing the last two digits of the model number with the desired length in
10-foot increments up to 90 feet (27.4 meters). For example, to order a 50-foot fanned-out cable,
specify 9101-050F.

If you need a fanned-out cable longer than 10 feet, contact the Global Customer Support (GCS)
center, and read Technical Application Note (TAN) number 002, Crosstalk on Digital Circuits.
Note that access to the Global Customer Support (GCS) center website requires registration.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 341

Fanned-Out Cables with Digital Input Modules


This section contains simplified schematics and wiring diagrams for connecting digital input
modules to fanned-out cables.
Topics include:
• Connecting 32-Point Digital Input Modules to Fanned-Out Cables on page 341
• Connecting 64-Point Digital Input Modules to Fanned-Out Cables on page 345

Connecting 32-Point Digital Input Modules to Fanned-Out Cables


This table describes 32-point digital input modules that are compatible with a fanned-out cable.

Table 203 32-point Digital Input Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3501E 115 VAC/VDC, non-commoned, isolated, TMR
3501T 115 VAC/VDC, non-commoned, isolated, TMR
3502E 48 VAC/VDC, commoned in groups of 8, TMR with self-test
3503E 24 VAC/VDC, commoned in groups of 8, TMR with self-test
3505E 24 VAC/VDC, low-threshold, commoned in groups of 8, TMR.with self-test

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
342 Chapter 8 Fanned-Out Cables

Field Wiring Diagrams


This figure illustrates how to connect field wiring to a 32-point digital input module (with or
without self-test) using a fanned-out cable.

FANNED-OUT CABLE * FIELD WIRING

AC HOT/+DC

1A, slow

Terminal Field
Contact
Block

2A (IN1 + )
to
2E (IN1 – )
backplane

AC NEUTRAL/RETURN

* Two cables are required for 32 points. Each point must be independently wired.
3501E supports commoned and uncommoned configurations.
3502E, 3503E and 3505E support commoned configurations only.

Figure 261 Field Wiring for 9101-010F with a 3501E, 3501T, 3502E, 3503E, or 3505E Module

You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 343

Simplified Schematics
This is a simplified schematic of a typical 32-point digital input module without self test
connected to a fanned-out cable (1 of 32 module points shown).

FANNED-OUT BACKPLANE 32-POINT DIGITAL INPUT MODULE


CABLE

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

IN

IN

Threshold to
Detect Input
Opto-Isolator Mux B

Threshold to
to Detect Input
spare Opto-Isolator Mux C
module

Figure 262 Simplified Schematic of a 3501E or 3501T DI Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
344 Chapter 8 Fanned-Out Cables

This is a simplified schematic of a typical 32-point digital input module with self test connected
to a fanned-out cable (1 of 32 module points shown).

FANNED-OUT BACKPLANE 32-POINT DIGITAL INPUT MODULE WITH SELF-TEST


CABLE

AC/DC Input Circuit

Leg-to-Leg Bridge AC
Isolation Rectifier Smoothing
Threshold to
Detect Input
Opto-Isolator Mux A

opto-
IN isolated

IN Test A

Threshold to
Detect Input
Opto-Isolator Mux B

Test B

Threshold to
Detect Input
to
spare Opto-Isolator Mux C
module

Test C

Figure 263 Simplified Schematic of a 3502E, 3503E, or 3505E DI Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Input Modules 345

Connecting 64-Point Digital Input Modules to Fanned-Out Cables


This table describes the 64-point digital input module that is compatible with a fanned-out
cable.

Table 204 64-point Digital Input Module Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3564 24 VDC, commoned, single

Field Wiring Diagrams


This figure illustrates how to connect field wiring to a 64-point digital input module using a
fanned-out cable.

FANNED-OUT BACKPLANE 64-POINT DIGITAL INPUT MODULE


CABLE
to
spare
Test ON Relays
(opto-isolated)
PWR to other
points &
sensors
IN

Threshold Detect
Opto-Isolator B

C
RTN
Test OFF Relays
to
(opto-isolated)
other
points

Figure 264 Field Wiring for 9101-010F with a 3564 Module

You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
346 Chapter 8 Fanned-Out Cables

Simplified Schematics
This is a simplified schematic of a typical 64-point digital input module connected to a fanned-
out cable (1 of 64 module points shown).

FANNED-OUT CABLE * FIELD WIRING

+ DC

Terminal 1A, slow


Block

1A, slow
2A (IN1)
Field
to 14C-32C (RTN)
Contact
backplane
2E (IN2)

RETURN
**
* Two cables are required for 64 points.
** Only one RTN connection is required for proper operation of a 64-point digital input module.

Figure 265 Simplified Schematic of a 3564 DI Module with a Fanned-Out Cable

Fanned-Out Cables with Digital Output Modules


This section contains simplified schematics and wiring diagrams for connecting digital output
modules to fanned-out cables.
Topics include:
• Connecting 16-Point Digital Output Modules to Fanned-Out Cables on page 346
• Connecting 32-Point Digital Output Modules to Fanned-Out Cables on page 352
• Connecting 32-Point Relay Output Modules to Fanned-Out Cables on page 356

Connecting 16-Point Digital Output Modules to Fanned-Out Cables


This table describes 16-point digital output modules that are compatible with a fanned-out
cable.

Table 205 16-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3601E 115 VAC, non-commoned, opto-isolated, TMR
3603E 120 VDC, commoned, opto-isolated, TMR
3604E 24 VDC, non-commoned, opto-isolated, TMR

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 347

Table 205 16-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3607E 48 VDC, non-commoned, TMR
3623 120 VDC, commoned, supervised, opto-isolated, TMR
3624 24 VDC, commoned, supervised, opto-isolated, self-protected, TMR

You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.

Field Wiring Diagrams


This figure illustrates how to connect field wiring to a 16-point digital output module using a
fanned-out cable.

FANNED-OUT CABLE FIELD WIRING

AC HOT/+DC

Terminal
block
2A (PWR1) * Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)
**

***
AC NEUTRAL/RETURN
*
*For all unused points, PWR and RTN must be connected.
**For all modules, one RTN per point is required.
***To prevent missing-load alarm, install a load at each unused point.

Figure 266 Field Wiring for 9101-010F with a 3601E, 3603E, 3604E, 3607E, or 3623 Module

For proper operation, one PWR connection per point is required.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
348 Chapter 8 Fanned-Out Cables

This figure illustrates how to connect field wiring to a 16-point commoned digital output
module with self-protection using a fanned-out cable.

FANNED-OUT CABLE FIELD WIRING

+DC

Terminal
block
2A (PWR1) Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)

**
*
RETURN

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470-Ohm, 10-W resistor.
** One RTN connection per point is required.

Figure 267 Field Wiring for 9101-010F with a 3624 Module

For proper operation, one RTN connection and one PWR connection per point are required.
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 349

Simplified Schematics
This is a simplified schematic of a typical 16-point commoned digital output module connected
to a fanned-out cable (1 of 16 module points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE FANNED-OUT


CABLE

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

to other
B points
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 268 Simplified Schematic of a 3603E DO Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
350 Chapter 8 Fanned-Out Cables

This is a simplified schematic of a typical 16-point non-commoned digital output module


connected to a fanned-out cable (1 of 16 module points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE FANNED-OUT


CABLE

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

B
Output
Switch
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 269 Simplified Schematic of a 3601E, 3604E, or 3607E DO Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 351

This is a simplified schematic of a typical 16-point commoned supervised digital output module
connected to a fanned-out cable (1 of 16 module points shown).

16-POINT DIGITAL OUTPUT MODULE BACKPLANE FANNED-OUT


CABLE

A Voltage
B Loopback to other
C Detector points

A
Output PWR1 (2A)
Switch
Drive
Circuitry A B
LOAD1 (2C)
A "B
Output
Switch
Drive RTN1 (2E)
Circuitry

B
Output
to other
Switch points
Drive
Circuitry
C A B
C
Output
to
Switch hot
Drive spare
Circuitry
A Voltage
B Loopback
C Detector

Figure 270 Simplified Schematic of a 3623 or 3624 DO Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
352 Chapter 8 Fanned-Out Cables

Connecting 32-Point Digital Output Modules to Fanned-Out Cables


This table describes 32-point digital output modules that are compatible with a fanned-out
cable.

Table 206 32-point Digital Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3625/Aa 24 VDC, commoned, supervised/non-supervised, self-protected, TMR
3664 24 VDC, commoned, opto-isolated, self-protected, dual
3674 24 VDC, commoned, opto-isolated, self-protected, dual

a. The 3625A module may be powered from four independent field power sources, but only if the
voltage from those sources is within 5% of the highest voltage supplied. If this restriction is not
followed, the module will still operate but may experience voter faults and generate an alarm.

You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 353

Field Wiring Diagrams


This figure illustrates how to connect field wiring to a 32-point commoned digital output
module with self-protection using a fanned-out cable.

FANNED-OUT CABLE FIELD WIRING

+DC

Terminal
block
2A (PWR1) Solenoid,
relay, etc.
to 2C (LOAD1)
backplane
2E (RTN1)

**
*
RETURN

* To prevent missing-load alarm, install a load at each unused point.


If a field load is not available, install a 470-Ohm, 10-W resistor.
** One RTN connection per point is required.

Figure 271 Field Wiring for 9101-010F with a 3625 or 3625A Module

For proper operation, one RTN connection and one PWR connection per point are required.
You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
354 Chapter 8 Fanned-Out Cables

This figure illustrates how to connect field wiring to a 32-point dual digital output module using
a fanned-out cable.

FANNED-OUT CABLE FIELD WIRING

+DC

Terminal Solenoid,
block relay, etc.
2A (PWR1)

to 2C (LOAD1)
backplane
2E (RTN1)

RETURN

Figure 272 Field Wiring for 9101-010F with a 3664 or 3674 Module

You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 355

Simplified Schematics
This is a simplified schematic of a typical 32-point digital output module connected to a fanned-
out cable (1 of 32 module points shown).

32-POINT DIGITAL OUTPUT MODULE BACKPLANE FANNED-OUT


A CABLE
Output
Switch
Drive
Circuitry PWR1 (2A)
*to
other
A or C
points
A B
Output LOAD1 (2C)
Switch
Drive
Circuitry

RTN1 (2E)
B
Output
Switch
Drive
Circuitry

C A or C

C
Current
Output Loopback
Switch Detector
Drive Analog/
Circuitry Digital
Mux
to
A hot
Voltage spare
B Loopback
C Detector

* For the 3625 module, field power is commoned to all points, so that if power is present on one point, it is present on all points. For the 3625A
module, field power is commoned in groups of 16 points and is separated by fanned-out cables.

Figure 273 Simplified Schematic of a 3625 or 3625A DO Module with a Fanned-Out Cable

This is a simplified schematic of a typical 32-point dual digital output module connected to a
fanned-out cable (1 of 32 module points shown).

32-POINT DUAL DIGITAL OUTPUT MODULE BACKPLANE FANNED-OUT


CABLE

A Voted PWR1 (2A)


Output
B
Drive
C Circuitry
LOAD1 (2C)

RTN1 (2E)
A Voted
Drive
B
Output
C Circuitry

A Loopback
B Detector/
C Isolator
to
hot
spare

to other points

Figure 274 Simplified Schematic of a 3664 or 3674 DO Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
356 Chapter 8 Fanned-Out Cables

Connecting 32-Point Relay Output Modules to Fanned-Out Cables


This table describes 32-point relay output modules that are compatible with a fanned-out cable.

Table 207 32-point Relay Output Modules Compatible with a Fanned-Out Cable
Module Model
Module Description
Number
3636R Non- commoned, simplex, galvanically-isolated, normally open
3636T Non- commoned, simplex, galvanically-isolated, normally open

You must re-key the female connector on each fanned-out cable to match the corresponding
male connector on the Tricon chassis backplane. Male connectors are mounted on the backplane
directly above their respective I/O slots. For instructions on re-keying connectors, see
Appendix A, Re-Keying Connectors.

Field Wiring Diagrams


This figure illustrates how to connect field wiring to a 32-point relay output module using a
fanned-out cable.

FANNED-OUT CABLE FIELD WIRING

Terminal
block
2A (C1)
to
2E (C1) Contact #1
backplane

Figure 275 Field Wiring for 9101-010F with a 3636R or 3636T Module

You must re-key the female connector to match its corresponding male connector on the Tricon
chassis. For instructions on re-keying connectors, see Appendix A, Re-Keying Connectors.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Fanned-Out Cables with Digital Output Modules 357

Simplified Schematics
This is a simplified schematic of a typical 32-point relay output module connected to a fanned-
out cable (1 of 32 module points shown).

32-POINT RELAY OUTPUT MODULE BACKPLANE FANNED-OUT


CABLE

A to
spare
module
Point
Register

+V +V
2A (C1)

Voted
B Output
Drive
Point Circuitry
Register

Loopback
Detector/
Isolator
2E (C1)
C

Point
Register

Figure 276 Simplified Schematic of a 3636R or 3636T Relay Output Module with a Fanned-Out Cable

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
358 Chapter 8 Fanned-Out Cables

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
A
Re-Keying Connectors

Re-Configuring a System 360


I/O Connector Key Positions 361
Re-Keying a Connector 367
Re-Keying a Fanned-Out Cable 368

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
360 Appendix A Re-Keying Connectors

Re-Configuring a System
The purpose of keying connectors by module type and voltage is to protect modules from
inadvertent connection to inappropriate voltages. Termination panels are also keyed. If you use
a fanned-out cable, you must key its connector according to this appendix to ensure module
protection. This appendix provides instructions for re-keying the field interface connectors and
fanned-out cables only. For instructions on repositioning slot keys, see the Planning and
Installation Guide for Tricon 11.5 and Later 11.x Systems.
To re-configure an existing system:

Procedure
1 Reposition the slot’s top and bottom keys.
2 Re-key the corresponding male connector on the backplane.
3 Install a replacement for the termination assembly, or re-key the female connector on the
fanned-out cable.
To re-configure an existing system without rear access:

Procedure
1 Reposition the slot’s top and bottom keys.
2 Re-key the female connector on the cable to match the backplane connector. All unused
slots are delivered from the factory keyed Small=1, Large=1.
3 Mark cable as being modified.
4 Install new or replacement termination assembly.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 361

I/O Connector Key Positions


Each male and female connector has two keys: a large key, and a small key. Each key has a total
of six possible positions. These tables show the key positions required by each module and
termination assembly combination.

Table 208 Digital Input Panel Key Positions


Termination Small Large
Rating Module
panel key key
9141-010F 115 VA /120 VDC 9670-110F
9670-610F 1 1
9673-810F
9142-010F 48 VDC 9672-810F 1 2
9143-010F 24 VDC 9671-810F 1 3
9551-110F 115 VAC 3501E
1 1
3501T
9552-610F 48 VAC/VDC 3502E 1 2
9553-610F 24 VAC/VDC 3503E
1 3
3505E
9553-610F 24 VDC 3564 1 3
9561-110F 115 VAC 3501E
1 1
3501T
9561-810F 115 VAC 3501E
1 1
3501T
9562-810F 48 VAC/VDC 3502E 1 2
9563-810F 24 VAC/VDC 3503E
1 3
3505E
9565-810F 48 VDC 3504E 1 2
9566-710F 24 VDC 3564 1 3
9566-810F 24 VDC 3504E 1 3
9570-610F 24 VDC 3504E 1 3
9571-610F 24 VDC 3564 1 3
9572-610F 24 VDC 3503E
3505E 1 3
3515
9750-310F 24 VDC non-isolated 3504E 1 3
9750-410F 48 VDC non-isolated 3504E 1 2

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
362 Appendix A Re-Keying Connectors

Table 209 Digital Output Panel Key Positions


Termination Small Large
Rating Module
panel key key
9251-210F 120 VDC 3603B see
1
note
9651-110F 115 VAC 3601E
3601T
3623
3 1
3623T
3603E
3603T
9652-610F 48 VDC 3607E 3 2
9653-610F 24 VDC 3604E
3624
3625 3 3
3625A
3664
9661-110F 115 VAC 3601E
3 1
3601T
9661-510F 115 VAC 3611E 3 1
9661-610F 115 VAC 3601E
3 1
3601T
9661-810F 120 VDC 3613E 3 1
9661-910F 120 VDC 3603E
3623 3 1
3623T
9662-110F 24 VDC 3604E 3 3
9662-610F 24 VDC 3624
3625
3625A 3 3
3664
3674
9662-710F 24 VDC 3615E 3 3
9662-810F 24 VDC 3604E 3 3
9662-910F 24 VDC 3614E 3 3
9667-110F 48 VDC 3607E 3 2
9667-810F 48 VDC 3607E 3 2
9667-910F 48 VDC 3617E 3 2

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 363

Table 209 Digital Output Panel Key Positions (continued)


Termination Small Large
Rating Module
panel key key
9671-610F 24 VDC 3604E
3624
3625
3 3
3625A
3664
3674

Regarding termination panel 9251-210F: for the termination panel and the end of the cable that
connects to the termination panel, the keying is Large=1, Small=1. For the chassis and the end
of the cable that connects to the chassis, the keying is Large =1, Small=3.

Table 210 Pulse Input Panel Key Positions


Termination Small Large
Rating Module
panel key key
9753-110F Pulse 3510
1 5
3511
9793-110F Pulse 3511 1 5
9794-110F Pulse 3511 1 5

Table 211 Relay Output Panel Key Positions


Termination Small Large
Rating Module
panel key key
9651-110F Relay 3636R
3 1
3636T
9668-110F Relay 3636R
3 1
3636T

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
364 Appendix A Re-Keying Connectors

Table 212 Analog Input Panel Key Positions


Termination Small Large
Rating Module
panel key key
9750-210F 4–20 mA (5 VDC) 3704E
1 5
3720
9750-810F 0–5/0–10 VDC 3704E
1 5
3720
9753-110F 0–5/0–10 VDC 3700A
3701 1 5
3703E
9760-210F 4–20 mA (5 VDC) 3704E
1 5
3720
9760-410F 4–20 mA (10 VDC) 3704E 1 5
9761-210F 4–20 mA (5 VDC) 3700
1 5
3721
9761-410F 4–20 mA (10 VDC) 3701
1 5
3721
9762-210F 4–20 mA (5 VDC) 3703E 1 5
9762-410F 4–20 mA (10 VDC) 3703E 1 5
9763-810F 0–5/0–10 VDC 3700
3701 1 5
3703E
9765-210F 4–20 mA (5 VDC) 3704E
1 5
3720
9765-610F Thermocouple 3708E 1 5
9766-210F Thermocouple 3706A 1 5
9766-510F Thermocouple 3706A 1 5
9782-110F Thermocouple 3708E 1 5
9783-110F 0–5 VDC 3700A
3703E 1 5
3721
9784-610F Thermocouple 3706A 1 5
9785-610F Thermocouple 3706A 1 5
9786-110F Thermocouple 3708E 1 5
9787-110F 0–5 VDC 3700A
3703E 1 5
3721
9789-610F 4–20 mA (5 VDC) 3704E
1 5
3720

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I/O Connector Key Positions 365

Table 212 Analog Input Panel Key Positions (continued)


Termination Small Large
Rating Module
panel key key
9790-610F 4–20 mA (5 VDC) 2770H
3700A
1 5
3703E
3721
9791-610F 4–20 mA (5 VDC) 2770H
3700A
1 5
3703E
3721
9792-610F 4–20 mA (5 VDC) 3700
3700A
1 5
3703E
3721
9795-610F 4–20 mA (5 VDC) 3703E
1 5
3721

Table 213 Analog Output Panel Key Positions


Termination Small Large
Rating Module
panel key key
9853-610F 4–20 mA 3805E/H 3 5
9860-610F 4–20 mA 2870H
3 5
3805E/H
9861-610F 4–20 mA 2870H
3 5
3805E/H
9863-710F 4–20 mA 3806E
3 5
20–320 mA
9871-810F –60–60 mA 3807 3 5
9881-810F –60–60 mA 3807 3 5

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
366 Appendix A Re-Keying Connectors

Table 214 Relay Output Panel Key Positions


Termination Small Large
Rating Module
panel key key
9670-110F 115 VAC 3601E
3a 1
3601T
9670-610F 115 VAC 3601E 3a 1
9671-810F 24 VDC 3604E
3625
3625A 3a 3
3664
3674
9672-810F 48 VDC 3607E
3a 2
3607T
9673-810F 120 VDC 3603E
3a 1
3603T
a. Small key is “1” at term panel end of cable.

Table 215 Bypass Panel Key Positions


Termination Small Large
Rating Module
panel key key
BP9228-010F Bypass 3503E
1 3
3505E

Table 216 RTD Panel Key Positions


Termination Small Large
Rating Module
panel key key
9764-310F RTD 3700
1 5
3700A

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Re-Keying a Connector 367

Re-Keying a Connector
This procedure explains how to re-key a connector on the Tricon chassis backplane.

NOTICE
HAZARD OF EQUIPMENT DAMAGE

To avoid shorts that could lead to damage, Schneider Electric recommends removing all power from
the Tricon system before you re-key the backplane connectors.

Failure to follow these instructions can result in equipment damage.

Procedure
1 Remove the eight screws that hold the Tricon chassis backplane cover, then remove the
cover.
2 Insert nut driver (part #2000236-001) through the backplane opening and loosen the nut
on the large male key.
3 While you hold the nut in place with the nut driver, remove the large male key
(cylindrical in shape) and reposition it to the correct number for your new module. See
diagram below.
4 Tighten the nut for the large male key.
5 Insert nut driver through the backplane opening and loosen the nut on the small male
key.
6 While you hold the nut in place with the nut driver, remove the small male key
(cylindrical in shape) and reposition it to the correct number for your new module. See
diagram below.
7 Tighten the nut for the small male key.
8 Replace the backplane cover and eight screws.
1

2
6
2

Large Female Key Large Male Key


5

3
5
3

Female Connector Male Connector


(on cable) (on backplane)
4

key.vsd
4

3
5
3

Small Male Key


Small Female Key
2

2
6

1
1

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
368 Appendix A Re-Keying Connectors

Keys are shown in their default position (1), which is also the position for 115 VAC digital input
terminations.

Re-Keying a Fanned-Out Cable


This procedure explains how to re-key a fanned-out cable.
All fanned-out cables are factory-keyed for position 1. Therefore you must always re-key a
fanned-out cable to match an I/O module in your system when you first install a system.
You must also re-key a fanned-out cable if you add new module types to your system. If you
move an existing I/O module to a different slot, you don’t need to re-key the cable if you move
the same cable with the modules.

Procedure
1 Hold the connector in your hand, and loosen (but do not remove the two screws that
secure the cable clamp).
2 Remove the four screws on the connector that fasten it to the housing.
3 Pull the connector away from the housing and rotate the connector slightly to expose the
keying nuts.
4 Loosen the nut on the large hexagonal key using the nut driver (part #2000236-001).
5 While holding the nut in place with the nut driver, remove the large key and reposition
it to the correct number.
6 Tighten the large key nut.
7 Loosen the nut on the small hexagonal key.
8 While holding the nut in place with the nut driver, remove the small key and reposition
it to the correct number.
9 Tighten the small key nut.
10 Replace the female connector in its housing by lining up the thumbscrew with the
opening in the top of the housing.
11 Replace the four screws that secure the female connector to the housing.
12 Tighten the two screws that secure the housing to the cable.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
B
Fanned-Out Cable Pinouts

Signal Names 370


Connector #1 371
Connector #2 373

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
370 Appendix B Fanned-Out Cable Pinouts

Signal Names
This table provides a list of signal names and pin numbers that you need to know when
connecting fanned-out cables and basic termination panels. The signal names in the table match
the labels on a fanned-out cable. The pin numbers in the table match the pin numbers on the
connector for the fanned-out cable as well as the panel connector on the Tricon chassis
backplane.
The signal names depend on which backplane connector the fanned-out cable is attached to, as
shown next.

Table 217 Pin Number Assignment


Total Connector Connector
points #1 #2
16 1–16 n/a
32 1–16 17–32
64 1–32 33–64

Connector 1
L
N
1
NO
C
NC
L
N
Connector 2
2
NO
RC C
NC

POWER A MP B C COM L 2 R L 3 R L 4 R L 5 R L 6 R L 7 R

REMOTE RUN
1 PROGRAM
A PASS PASS PASS
PASS PASS PASS
PASS PASS PASS

STOP FAULT
FAULT FAULT
FAULT FAULT FAULT
FAULT FAULT FAULT
Ñ LOCAL Ñ ACTIVE ACTIVE ACTIVE
ACTIVE ACTIVE ACTIVE
ACTIVE ACTIVE ACTIVE
LOAD/ LOAD/
MAINT1 MAINT1 FUSE FUSE
MAINT1
1 1
MAINT2 MAINT2 MAINT2
1 1 1TX
115/230 VAC 2 2
1RX
2 2
3 3
NET 1
3 3
PASS 4 4

FAULT 5 5
4 4

ALARM 5 5
6 6
TEMP TX
6 6
RX 7 7
BATT LOW
B 8 8
7 7
2TX
2RX

9 9 8 8

10 10

11 11

12 12

13 13
3TX

NET 2 14 14 3RX

POWER MODULE 15 15
MODEL 8310
16 16

TX 17 17

RX 18 18

19 19
115/230 VAC 4TX
20 20 4RX

21 21
PASS
22 22
FAULT
23 23
ALARM
COM RX COM RX COM RX
TEMP 24 24
COM TX COM TX COM TX COMM 9 9
BATT LOW 25 25
I/O RX I/O RX I/O RX TX 10 10
26 26 PRT
RX
C I/O TX I/O TX I/O TX
27 27
11 11

12 12
28 28
13 13
29 29
14 14
30 30
15 15
31 31
16 16
32 32
POWER MODULE EMP EMP EMP NCM
DIGITAL DIGITAL DIGITAL DIGITAL
EICM
MODEL 8310 3006 3006 3006 4329 INPUT INPUT OUTPUT OUTPUT 4119
3501E 3501E 3603B 3603B

D E F G H I J K L M N O P Q R S

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 371

Connector #1
Table 218 Connector Number 1 Pinouts
Connector #1 I/O Modules
Signal 64 Pt 64 Pt 32 Pt DO/ 8 Pt
Pin # RO AI/TC AO PI
Label SDI AI DI 16 Pt SDO SDO
2A AA IN1 IN1 IN1+ PWR1 PWR1 C1 IN1+ OUT1 IN1+
2C KK * * LOAD1 LOAD1 *
2E LL IN2 IN2 IN1– RTN1 RTN1 C1 IN1– RTN1 IN1–
4A z IN3 IN3 IN2+ PWR2 PWR2 C2 IN2+ OUT2 IN2+
4C DD PWR PWR LOAD2 LOAD2 *
4E EE IN4 IN4 IN2– RTN2 RTN2 C2 IN2– RTN2 IN2–
6A p IN5 IN5 IN3+ PWR3 PWR3 C3 IN3+ OUT3 IN3+
6C u * * LOAD3 LOAD3 *
6E v IN6 IN6 IN3– RTN3 RTN3 C3 IN3– RTN3 IN3–
8A h IN7 IN7 IN4+ PWR4 PWR4 C4 IN4+ OUT4 IN4+
8C k PWR PWR LOAD4 LOAD4 *
8E l IN8 IN8 IN4– RTN4 RTN4 C4 IN4– RTN4 IN4–
10A e IN9 IN9 IN5+ PWR5 PWR5 C5 IN5+ OUT5 IN5+
10C a * * LOAD5 LOAD5 *
10E b IN10 IN10 IN5– RTN5 RTN5 C5 IN5– RTN5 IN5–
12A W IN11 IN11 IN6+ PWR6 PWR6 C6 IN6+ OUT6 IN6+
12C R PWR PWR LOAD6 LOAD6 *
12E S IN12 IN12 IN6– RTN6 RTN6 C6 IN6– RTN6 IN6–
14A L IN13 IN13 IN7+ PWR7 PWR7 C7 IN7+ OUT7 IN7+
14C E RTN RTN LOAD7 LOAD7
14E F IN14 IN14 IN7– RTN7 RTN C7 IN7– RTN7 IN7–
16A M IN15 IN15 IN8+ PWR8 PWR8 C8 IN8+ OUT8 IN8+
16C A RTN RTN LOAD8 LOAD8
16E B IN16 IN16 IN8– RTN8 RTN C8 IN8– RTN8 IN8–
18A BB IN17 IN17 IN9+ PWR9 SEC1 C9 IN9+ *
RTN
18C NN RTN LOAD9 FGNDb *
FGNDa
18E MM IN18 IN18 IN9– RTN9 RTN C9 IN9– *
20A CC IN19 IN19 IN10+ PWR10 SEC2 C10 IN10+ *

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
372 Appendix B Fanned-Out Cable Pinouts

Table 218 Connector Number 1 Pinouts (continued)


Connector #1 I/O Modules
Signal 64 Pt 64 Pt 32 Pt DO/ 8 Pt
Pin # RO AI/TC AO PI
Label SDI AI DI 16 Pt SDO SDO
RTN
20C JJ RTN LOAD10 FGNDb *
FGNDa
20E HH IN20 IN20 IN10– RTN10 RTN C10 IN10– *
22A t IN21 IN21 IN11+ PWR11 SEC3 C11 IN11+ PWRA *
RTN
22C y RTN LOAD11 FGNDb *
FGNDa
22E x IN22 IN22 IN11– RTN11 RTN C11 IN11– RTN *
24A j IN23 IN23 IN12+ PWR12 SEC4 C12 IN12+ PWRB *
RTN
24C n RTN LOAD12 FGNDb *
FGNDa
24E m IN24 IN24 IN12– RTN12 RTN C12 IN12– RTN *
26A f IN25 IN25 IN13+ PWR13 SEC5 C13 IN13+ *
RTN
26C d RTN LOAD13 FGNDb *
FGNDa
26E c IN26 IN26 IN13– RTN13 RTN C13 IN13– *
28A Z IN27 IN27 IN14+ PWR14 SEC6 C14 IN14+ *
RTN
28C V RTN LOAD14 FGNDb *
FGNDa
28E U IN28 IN28 IN14– RTN14 RTN C14 IN14– *
30A P IN29 IN29 IN15+ PWR15 SEC7 C15 IN15+ *
RTN
30C K RTN LOAD15 FGNDb *
FGNDa
30E J IN30 IN30 IN15– RTN15 RTN C15 IN15– *
32A N IN31 IN31 IN16+ PWR16 SEC8 C16 IN16+ *
RTN
32C D RTN LOAD16 FGNDb *
FGNDa
32E C IN32 IN32 IN16– RTN16 RTN C16 IN16– *
34A T CGND CGND CGND CGND CGND CGND CGND CGND CGND
34C H CGND CGND CGND CGND CGND CGND CGND CGND CGND
34E w CGND CGND CGND CGND CGND CGND CGND CGND CGND
36A FF CGND CGND CGND CGND CGND CGND CGND CGND CGND

a. Only on Model 3720

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 373

b. Only on Model 3721

* Reserved for Tricon controller internal use. Do not connect for any purpose.

Note CGND is the Tricon chassis ground (protective earth). Pins r, s, X and Y on the panel
connector are not used.

Connector #2
Table 219 Connector Number 2 Pinouts
Connector #2 I/O Modules
Signal 64 Pt 64 Pt 32 Pt
Pin # DO RO
Label SDI AI AI/DI
2A AA IN33 IN33 IN17+ PWR17 C17
2C KK RTN LOAD17
2E LL IN34 IN34 IN17– RTN17 C17
4A z IN35 IN35 IN18+ PWR18 C18
4C DD PWR RTN LOAD18
4E EE IN36 IN36 IN18– RTN18 C18
6A p IN37 IN37 IN19+ PWR19 C19
6C u RTN LOAD19
6E v IN38 IN38 IN19– RTN19 C19
8A h IN39 IN39 IN20+ PWR20 C20
8C k PWR RTN LOAD20
8E l IN40 IN40 IN20– RTN20 C20
10A e IN41 IN41 IN21+ PWR21 C21
10C a RTN LOAD21
10E b IN42 IN42 IN21– RTN21 C21
12A W IN43 IN43 IN22+ PWR22 C22
12C R PWR RTN LOAD22
12E S IN44 IN44 IN22– RTN22 C22
14A L IN45 IN45 IN23+ PWR23 C23
RTN
14C E RTN LOAD23
FGNDa
14E F IN46 IN46 IN23– RTN23 C23
16A M IN47 IN47 IN24+ PWR24 C24
RTN
16C A RTN LOAD24
FGNDa

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
374 Appendix B Fanned-Out Cable Pinouts

Table 219 Connector Number 2 Pinouts (continued)


Connector #2 I/O Modules
Signal 64 Pt 64 Pt 32 Pt
Pin # DO RO
Label SDI AI AI/DI
16E B IN48 IN48 IN24– RTN24 C24
18A BB IN49 IN49 IN25+ PWR25 C25
RTN
18C NN RTN FGNDb LOAD25
FGNDa
18E MM IN50 IN50 IN25– RTN25 C25
20A CC IN51 IN51 IN26+ PWR26 C26
RTN
20C JJ RTN FGNDb LOAD26
FGNDa
20E HH IN52 IN52 IN26– RTN26 C26
22A t IN53 IN53 IN27+ PWR27 C27
RTN
22C y RTN FGNDb LOAD27
FGNDa
22E x IN54 IN54 IN27– RTN27 C27
24A j IN55 IN55 IN28+ PWR28 C28
RTN
24C n RTN FGNDb LOAD28
FGNDa
24E m IN56 IN56 IN28– RTN28 C28
26A f IN57 IN57 IN29+ PWR29 C29
RTN
26C d RTN FGNDb LOAD29
FGNDa
26E c IN58 IN58 IN29– RTN29 C29
28A Z IN59 IN59 IN30+ PWR30 C30
RTN
28C V RTN FGNDb LOAD30
FGNDa
28E U IN60 IN60 IN30– RTN30 C30
30A P IN61 IN61 IN31+ PWR31 C31
RTN
30C K RTN FGNDb LOAD31
FGNDa
30E J IN62 IN62 IN31– RTN31 C31
32A N IN63 IN63 IN32+ PWR32 C32
RTN
32C D RTN FGNDb LOAD32
FGNDa
32E C IN64 IN64 IN32– RTN32 C32

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Signal Names 375

Table 219 Connector Number 2 Pinouts (continued)


Connector #2 I/O Modules
Signal 64 Pt 64 Pt 32 Pt
Pin # DO RO
Label SDI AI AI/DI
34A T CGND CGND CGND CGND CGND
34C H CGND CGND CGND CGND CGND
34E w CGND CGND CGND CGND CGND
36A FF CGND CGND CGND CGND CGND
a. Only on Model 3720
b. Only on Model 3721

Note CGND is the Tricon chassis ground (protective earth). Pins r, s, X and Y on the panel
connector are not used.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
376 Appendix B Fanned-Out Cable Pinouts

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
C
Recommended Replacement Parts

This table contains recommended parts that can be used to replace existing Tricon system parts,
or customize a Tricon system.

Table 220 Recommended Replacement Parts


Manufacturer Schneider
Part Description Manufacturer Triconex Models
Part No. Electric Part No.
Lithium battery, C-size, 1400010-001 Schneider 1400010-001 Main chassis
3.6 VDCa Electric
Lithium battery, AA- 3000785-001 Schneider 3000785-001 Main chassis
size packaged as C-size, Electric
3.6 VDCa
15-amp time-delay 326015 Littlefuse 24 VDC power
fuse, 1/4 in x 1-1/4 in MDA-15 Bussman 1410015-001 supplies

3W015 Bel Fuse


5-amp time-delay fuse, 326 005 Littlefuse 115 VAC/VDC
1/4 in x 1-1/4 in MDA-5 Bussman 1410039-001 power supplies

3S350 Bel Fuse


2.5-amp time-delay 326 02.5 Littlefuse 230 VAC power
fuse, 1/4 in x 1-1/4 in MDA-2 1/2 Bussman 1410040-001 supplies

3SB2.5 Bel Fuse


3-amp fast-acting fuse, 235003 Littlefuse Digital output
5 mm x 20 mm GMA-3A Bussman 1410003-001 termination
panels
5MF3 Bel Fuse
2.5-amp fast-acting 23502.5 Littlefuse Digital output
fuse, 5 mm x 20 mm GMA-2.5A Bussman and relay output
1410022-001
termination
5MF 2.5 Bel Fuse panels
2-amp fast-acting fuse, 235002 Littlefuse Relay output
5 mm x 20 mm GMA-2A Bussman 1410009-001 termination
panels
5MF2 Bel Fuse

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
378 Appendix C Recommended Replacement Parts

Table 220 Recommended Replacement Parts (continued)


Manufacturer Schneider
Part Description Manufacturer Triconex Models
Part No. Electric Part No.
2-amp fuse, 312002 Littlefuse Bypass panel
1/4 in x 1-1/4 in 1410020-001
3AG2 Bel Fuse
1.25-amp fast-acting 2351.25 Littlefuse Digital output
fuse, 5 mm x 20 mm GMA-1.25A Bussman 1410023-001 termination
panels
5MF1.25 Bel Fuse
1-amp fast-acting fuse, 235001 Littlefuse Digital output,
5 mm x 20 mm GMA-1A Bussman relay and analog
1410006-001 input
5MF1 Bel Fuse termination
panels
50 mA fast-acting fuse, 216.050 Littlefuse 1410019-001 Analog input
5 mm x 20 mm terminations
50 mA fuse 273.050 Littlefuse 1410037-001 3-wire analog
input
500 mA fuse 273.500 Littlefuse 1410038-001 3-wire analog
input
1.0-amp time-delay 239001 Littlefuse Digital and
fuse, 5 mm x 20 mm GMC-1A Bussman analog input
1410011-001
termination
5TT1 Bel Fuse panels
IC Extractor M125B002 OK 1580009-001 All modules
Fuse Extractor Tool M45B001 Jensen Tools Terminations
1580000-001
34-015 Ideal
Load Resistor, CP-10-2200-10 Dale Supervised
2200 ohm, 10 W, 10% PW-10-2200-10 IRC, RCD digital output
1100280-001
termination
SQP-10-2200-10 RF panels
Load Resistor, 470 ohm, CP-10-470-10 Dale Supervised
10 W, 10% PW-10-470-10 IRC, RCD digital output
1100281-001
termination
SQP-10-470-10 RF panels
Load Resistor, 120 ohm, CP-10-120-10 Dale Supervised
10 W, 10% PW-10-120-10 IRC, RCD digital output
1100282-001
termination
SQP-10-120-10 RF panels
I-to-V Resistor, Y0007250R000T9 Vishay Analog
250 ohm, 0.6 W, 0.01% PF2260H 250 ohm Riedon termination
.01% panels
1100375-001
WAC250R00T Wilbrecht
Electronics
Inc.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
379

Table 220 Recommended Replacement Parts (continued)


Manufacturer Schneider
Part Description Manufacturer Triconex Models
Part No. Electric Part No.
I-to-V Resistor, S102CT 500R00 Vishay Analog
500 ohm, 0.6 W, 0.01% 0.01% Vishay termination
Y0007500R000T9L panels
Riedon
USR 2-0710 500 Riedon 1100425-001
USR 2-0710 500 Riedon
.01%
USR 2-0808
500 ohm 0.01%
Re-keying tool 2000236-001 Schneider 2000236-001 56-pin
Electric connectors on
termination
cables, panels,
backplane and
main chassis
Spring-loaded terminal, 18 73 34 6 Phoenix 1420045-016 All applicable
16-position termination
panels except
basic, bypass,
and interposing
relay
Spring-loaded terminal, 18 73 30 4 Phoenix 1420045-012 All applicable
12-position termination
panels except
basic, bypass,
and interposing
relay
Spring-loaded terminal, 18 73 26 5 Phoenix 1420045-008 All applicable
8-position termination
panels except
basic, bypass,
and interposing
relay
ELCO connector gasket 3000793-001 Schneider 3000793-001 The male side of
These gaskets must be (kit of 25 gaskets) Electric (kit of 25 gaskets) all ELCO
replaced before the end connectors used
of their 5-year lifespan. in hazardous
locations (those
requiring
nonincendive
circuits).

a. To purchase, contact EVS Supply by phone (972-231-5351) or email ([email protected]) and


reference the Schneider Electric part number.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
380 Appendix C Recommended Replacement Parts

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
D
Panel Dimensions

This figure illustrates the dimensions described in Table 221 Panel Dimensions (page 382).

Length (along DIN rail)


FRONT VIEW

SN
Width (across DIN rail)

1
2
3
4
5
6
7
8
L+

L+
L–

L–
PS1

PS2

BOTTOM VIEW
Height (out from DIN rail)

1 2 3 4 5 6 7 8

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
382 Appendix D Panel Dimensions

This table describes the dimensions of each external termination panel (ETP).

Table 221 Panel Dimensions


Width Length Height
Panel Model
(across DIN rail) (along DIN rail) (out from DIN rail)
9251-210F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9551-110F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9552-610F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9553-610F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9561-110F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9561-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9562-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9563-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9563-910F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9565-810F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9566-710F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9566-810F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9570-610F 4.42 in (11.23 cm) 9.88in (25.08 cm) 4.25 in (10.795 cm)
9571-610F 4.42 in (11.23 cm) 9.88 in (25.08 cm) 4.25 in (10.795 cm)
9572-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9651-110F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9652-610F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9653-610F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9661-110F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9661-510F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9661-610F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9661-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9661-910F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9662-110F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9662-610F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9662-710F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9662-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9662-910F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9663-610F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9664-110F 4.5 in (11.43 cm) 9.88 in (25.08 cm) 4.25 in (10.795 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
383

Table 221 Panel Dimensions (continued)


Width Length Height
Panel Model
(across DIN rail) (along DIN rail) (out from DIN rail)
9664-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9667-110F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9667-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9667-910F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9668-110F 4.5 in (11.43 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9670-110F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9670-610F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9671-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9671-810F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9672-810F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9673-810F 7 in (17.78 cm) 19 in (48.26 cm) 4.75 in (12.065 cm)
9750-210F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9750-310F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9750-410F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9750-810F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9753-110F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9760-210F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9760-410F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9761-210F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9761-410F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9762-210F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9762-410F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9763-810F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9764-310F 5.22 in (13.26 cm) 19 in (48.26 cm) 3.24 in (8.23 cm)
9765-210F 4.5 in (11.43 cm) 10 in (25.4 cm) 4.25 in (10.795 cm)
9765-610F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9766-210F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9766-510F 4.5 in (11.43 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9771-210F 4.5 in (11.43 cm) 5.729 in (14.552 cm) 4.25 in (10.795 cm)
9782-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9783-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9784-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
384 Appendix D Panel Dimensions

Table 221 Panel Dimensions (continued)


Width Length Height
Panel Model
(across DIN rail) (along DIN rail) (out from DIN rail)
9785-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9786-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9787-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9789-610F 4.42 in (11.23 cm) 9.88 in (25.08 cm) 4.25 in (10.795 cm)
9790-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9791-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9792-610F 4.42 in (11.23 cm) 7.75 in (19.685 cm) 4.25 in (10.795 cm)
9793-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9794-110F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9795-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9853-610F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9860-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9861-610F 4.42 in (11.23 cm) 5.02 in (12.75 cm) 4.25 in (10.795 cm)
9863-710F 3 in (7.62 cm) 6.66 in (16.9164 cm) 4.25 in (10.795 cm)
9871-810F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
9881-810F 3 in (7.62 cm) 5 in (12.7 cm) 4.25 in (10.795 cm)
BP9228-010F 3.5 in (8.89 cm) 19 in (48.26 cm) 8 in (20.32 cm)
BP9229-010F 3.5 in (8.89 cm) 19 in (48.26 cm) 8 in (20.32 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
E
Shield Ground

This appendix shows how to connect a shield to earth. The typical parts shown are available
from Phoenix Contact. See additional installation guidelines in the Planning and Installation
Guide for Tricon 11.5 and Later 11.x Systems.
J1

J1

One typical thermocouple


point shown.
3
2
1

7 mm

19.4 mm
23.4 mm

23.5 mm

Dedicated Bus Bar


or Cabinet

Safety Ground
Bus Bar
26 mm
35.5 mm

Plant Safety Ground System


or ZRSG

Ref. # Type Description Phoenix Order #


1 NLS-MS 3/10 Neutral busbar 04 04 18 5
2 AB/SS Support 04 04 42 8
3 AKG 4 Black N/PE terminal block 04 21 03 2

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
386 Appendix E Shield Ground

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
F
Panel Labels

16-Point Non-Commoned DI/DO/RO Panels 388


16-Point Non-Commoned AI/TI Panels 389
16-Point Commoned AI/DI/DO Panels 390
32-Point Commoned AI/DI Panels 391
16-Point Commoned AI ATEX/RG 1.180 Panels 392
16-Point RTD/TC/AI Panels 393

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
388 Appendix F Panel Labels

Overview
This appendix shows how to apply termination panel labels. Because some modules (32- and
64-point input modules and 32-point output modules) require a two-panel arrangement to
accommodate all points, each standard panel must have a set of labels that indicate the correct
range of points. For instance, a 64-point module requires two 32-point panels: the first panel
connects points 1–32; the second panel connects points 33–64. Panels that are not used in a two-
panel arrangement are labeled at the factory.
Standard panels that require labels include the appropriate labels as loose-piece parts. Since a
panel can be connected as the first or second panel, a set of labels appropriate for either range is
provided with every panel, with a duplicate label for each row of terminals on each terminal
block. Any unused labels can be stored or discarded.
Attach the appropriate labels to each panel as shown in these illustrations.

16-Point Non-Commoned DI/DO/RO Panels


This figure illustrates placement of labels for 16-point digital input, digital output, and relay
output termination panels.

SN REV A 7400168-
Panel Type
9561-110F DI
9661-110F DO
9662-110F DO
9667-110F DO
F13

F14

F15

F16
F5

F6

F7

F8

9667-310F DO
J1

9668-110F RO
F10

F12
F11
F1

F2

F3

F4

F9
CONTACT
PWR

Labels (for front and back row) Labels (for front and back row)
+1 – +2 – +3 – +4 – +5 – +6 – +7 – +8 – +9 – + 10 – +11 – + 12 – +13 – + 14 – + 15 – + 16 –
First Panel

Labels (for front and back row) Labels (for front and back row)
+ 17 – + 18 – + 19 – + 20 – + 21 – +22 – + 23 – +24 – + 25 – + 26 – +27 – + 28 – +29 – + 30 – + 31 – + 32 –
Second Panel

Figure 277 16-Point Non-Commoned DI/DO/RO Panel Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point Non-Commoned AI/TI Panels 389

16-Point Non-Commoned AI/TI Panels


This figure illustrates placement of labels for 16-point non-commoned analog input and
thermocouple input termination panels.

SN REV A 7400171-
Panel Type
9763-810F AI
9765-610F TI
9766-210F TI
9766-510F TI

J1
+

+
ñ

ñ
Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

First Panel

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Second Panel

Figure 278 16-Point Non-Commoned AI/TI Panel Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
390 Appendix F Panel Labels

16-Point Commoned AI/DI/DO Panels


This figure illustrates placement of labels for 16-point commoned analog input, digital input,
and digital output termination panels.

Panel Type SN REV A 7400166-

9561-810F DI
9562-810F DI
9563-810F DI
9661-610F DO

CR
1
F2 F4 F6 F8 F10 F12 F14 F16
9661-710F DO

J1
9661-910F DO CR
2
9662-610F DO
9662-810F DO
9667-610F DO
F1 F3 F5 F7 F9 F11 F13 F15
9667-710F DO
9667-810F DO L+

L+
9761-210F AI
9761-410F AI


9762-210F AI
PS1

PS2

9762-410F AI

Labels (for front and back row)


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

First Panel

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Second Panel

Figure 279 16-Point Commoned AI/DI/DO Panel Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
32-Point Commoned AI/DI Panels 391

32-Point Commoned AI/DI Panels


This figure illustrates placement of labels for 32-point commoned analog input and digital input
termination panels.

SN REV A 7400150-
Panel Type
9565-710F DI
9565-810F DI
9566-710F DI

R10

R12

R14

R16

R18

R20

R22

R24

R26

R28

R30

R32
R2

R4

R6

R8
9566-810F DI

J1
9567-810F DI

CR1

CR2
9760-210F AI
9760-410F AI

R13

R15

R17

R19

R21

R23

R25

R27

R29

R31
R11
R1

R3

R5

R7

R9
PS1

PS2

Labels (for front and back row) Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
First Panel

Labels (for front and back row) Labels (for front and back row)
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Second Panel

Figure 280 32-Point Commoned AI/DI Panel Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
392 Appendix F Panel Labels

16-Point Commoned AI ATEX/RG 1.180 Panels


This figure illustrates placement of labels for 32-point commoned analog input ATEX and RG
1.180 termination panels.

TRICONEX
Panel Type EXT TERM TRICON
$7(;(0&$,',

9783-110F AI 7400275 REV B ƒ&”7$”ƒ&

17
R
SN
AI

R25
9787-110F

18
R1

R
9
R
TB1 TB4

'21276(3$5$7(

5
9790-610F AI

:+(1(1(5*,=('
19
R2

R
10
R

R27
9791-610F AI

20
R3

R
11
R

R28
9795-610F AI

3
21
R4

R
12
R

R29
22
R5

R
13
R

R30
23
5

R
14

!
R

R31
24
R7

R
15
R

R32
R8


J1

5
TB2 TB3 TB5 7%

J2
/
J3

L- P1 P2

Labels (for front and back row)


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

First Panel

Labels (for front and back row)


17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Second Panel

Figure 281 16-Point Commoned AI ATEX/RG 1.180 Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
16-Point RTD/TC/AI Panels 393

16-Point RTD/TC/AI Panels


This figure illustrates placement of labels for 16-point RTD/TC/AI termination panels.

TRICONEX 7B 16 MODULE BASEPLATE 7400225- REV E SN


J1

7B47

7B47

7B47

7B47

7B32

7B32

7B32

7B32

7B34

7B34

7B34

7B34

7B34

7B34

7B34

7B34
DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES CURRENT INPUT


ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG

DEVICES
ANALOG
RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT

RTD INPUT
ISOLATED

ISOLATED

ISOLATED

ISOLATED

PROCESS

PROCESS

PROCESS

PROCESS
ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED

ISOLATED
TC INPUT

TC INPUT

TC INPUT

TC INPUT
U1 U2 U3 U4 U5 U6 U7 U8 U9 U10 U11 U12 U13 U14 U15 U16

R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R14 R15 R16


1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16

10

12
13
14
15
16
J2
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16
1
2
3
4
5
6
7
8
9

11

1
2
3
4
5
6
7
8
9

11
10

12
13
14
15
16

10

12
13
14
15
16
J3 J4 J5 J6

First Panel

Labels (for front and back row) Labels (for front and back row) Labels (for front and back row) Labels (for front and back row)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Second Panel

Labels (for front and back row) Labels (for front and back row) Labels (for front and back row) Labels (for front and back row)
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Figure 282 16-Point RTD/TC/AI Panel Label Placement

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
394 Appendix F Panel Labels

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
G
Part Number Cross-Reference

Table 222 identifies the termination panel part number and the cable part number included in
each external termination panel (ETP) kit.
The table includes these types of cables:
• FT4: Ninety-degree cables that meet FT4 flame test ratings. Add “F” at the end of the
ETP kit base model number to obtain the complete model number. For example, 9551-
110F.
• FT4 Z: Zero-degree cables, designed to be used with G-Series Enclosures for Tricon
systems that have front access. Add “F-Z” at the end of the ETP kit base model number
to obtain the complete model number. For example, 9551-110F-Z.
• LSZH: Low Smoke Zero Halogen ninety-degree cables. Kits are not available for these
configurations, the Termination Panel Base Part Number and LSZH Cable must be
ordered separately.
For more information about these cables, see Interface Cables on page 6.

Table 222 Part Number Cross-Reference—Tricon ETPs


ETP Kit Termination Panel FT4 Cable FT4 Z Cable
LSZH Cable
Base Model # Base Part # Part # Part #
9551-110 3000400-160 4000187-110 4000192-110 4000140-110

9552-610 3000400-260 4000187-210 4000192-210 4000140-210

9553-610 3000400-360 4000187-310 4000192-310 4000140-310

9561-110 3000560-110 4000187-110 4000192-110 4000140-110

9561-810 3000510-180 4000187-110 4000192-110 4000140-110

9562-810 3000510-280 4000187-210 4000192-210 4000140-210

9563-810 3000510-380 4000187-310 4000192-310 4000140-310

9563-910 3000510-390 4000187-310 4000192-310 4000140-310

9565-810 3000540-280 4000187-210 4000192-210 4000140-210

9566-710 3000530-380 4000187-310 4000192-310 4000140-310

9566-810 3000540-380 4000187-310 4000192-310 4000140-310

9570-610 3000768-370 4000195-310 4000199-310 n/a

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
396 Appendix G Part Number Cross-Reference

Table 222 Part Number Cross-Reference—Tricon ETPs (continued)


ETP Kit Termination Panel FT4 Cable FT4 Z Cable
LSZH Cable
Base Model # Base Part # Part # Part #
9571-610 3000768-390 4000195-310 4000199-310 n/a

9572-610 3000771-380 4000195-310 4000199-310 n/a

9651-110 3000410-160 4000188-110 4000193-110 4000141-110

9652-610 3000410-260 4000188-210 4000193-210 4000141-210

9653-610 3000410-360 4000188-310 4000193-310 4000141-310

9661-110 3000570-110 4000188-110 4000193-110 4000141-110

9661-510 3000550-160 4000188-110 4000193-110 4000141-110

9661-610 3000520-160 4000188-110 4000193-110 4000141-110

9661-810 3000550-180 4000188-110 4000193-110 4000141-110

9661-910 3000520-180 4000188-110 4000193-110 4000141-110

9662-110 3000570-310 4000188-310 4000193-310 4000141-310

9662-610 3000520-390 4000188-310 4000193-310 4000141-310

9662-710 3000550-390 4000188-310 4000193-310 4000141-310

9662-810 3000520-380 4000188-310 4000193-310 4000141-310

9662-910 3000550-380 4000188-310 4000193-310 4000141-310

9663-610 3000725-160 4000188-110 4000193-110 4000141-110

9664-110 3000726-110 4000188-110 4000193-110 4000141-110

9664-810 3000520-170 4000188-110 4000193-110 4000141-110

9667-110 3000570-710 4000188-210 4000193-210 4000141-210

9667-810 3000520-280 4000188-210 4000193-210 4000141-210

9667-910 3000550-280 4000188-210 4000193-210 4000141-210

9668-110 3000590-110 4000188-110 4000193-110 4000141-110

9670-110 3000290-110 4000203-110 4000204-110 n/a

9670-610 3000290-160 4000203-110 4000204-110 n/a

9671-610 3000769-390 4000196-310 4000200-310 n/a

9671-810 3000290-380 4000203-310 4000204-310 n/a

9672-810 3000290-280 4000203-210 4000204-210 n/a

9673-810 3000290-181 4000203-110 4000204-110 n/a

9750-210 3000420-120 4000206-510 4000207-510 n/a

9750-310 3000420-310 4000187-310 4000192-310 4000140-310

9750-410 3000420-410 4000187-210 4000192-210 4000140-210

9750-810 3000420-180 4000206-510 4000207-510 n/a

9753-110 3000400-510 4000189-510 4000191-510 4000142-510

9760-210 3000470-510 4000206-510 4000207-510 n/a

Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
397

Table 222 Part Number Cross-Reference—Tricon ETPs (continued)


ETP Kit Termination Panel FT4 Cable FT4 Z Cable
LSZH Cable
Base Model # Base Part # Part # Part #
9760-410 3000470-530 4000206-510 4000207-510 n/a

9761-210 3000510-510 4000189-510 4000191-510 4000142-510

9761-410 3000510-530 4000189-510 4000191-510 4000142-510

9762-210 3000510-560 4000189-510 4000191-510 4000142-510

9762-410 3000510-580 4000189-510 4000191-510 4000142-510

9763-810 3000580-110 4000189-510 4000191-510 4000142-510

9764-310 3000712-200 4000189-510 4000191-510 4000142-510

9765-210 3000475-520 4000206-510 4000207-510 n/a

9765-610 3000580-230 4000189-510 4000191-510 4000142-510

9766-210 3000580-210 4000189-510 4000191-510 4000142-510

9766-510 3000580-220 4000189-510 4000191-510 4000142-510

9771-210 3000656-210 4000189-510 4000191-510 4000142-510

9782-110 3000767-280 4000189-510 4000191-510 4000142-510

9783-110 3000767-160 4000189-510 4000191-510 4000142-510

9784-610 3000767-220 4000197-510 4000201-510 n/a

9785-610 3000767-210 4000197-510 4000201-510 n/a

9786-110 3000767-230 4000197-510 4000201-510 n/a

9787-110 3000767-110 4000197-510 4000201-510 n/a

9789-610 3000768-510 4000209-510 4000208-510 n/a

9790-610 3000771-560 4000189-510 4000191-510 4000142-510

9791-610 3000771-510 4000197-510 4000201-510 n/a

9792-610 3000772-660 4000189-510 4000191-510 4000142-510

9793-110 3000767-115 4000197-510 4000201-510 n/a

9794-110 3000767-165 4000189-510 4000191-510 4000142-510

9795-610 3000771-460 4000189-510 4000191-510 4000142-510

9853-610 3000400-530 4000190-510 4000194-510 4000157-510

9860-610 3000770-610 4000190-510 4000194-510 4000157-510

9861-610 3000770-560 4000198-510 4000202-510 n/a

9863-710 1600049-010 4000190-510 4000194-510 4000157-510


1600049-100

9871-810 3000818-560 4000198-510 4000202-510 n/a

9881-810 3000818-660 4000190-510 4000194-510 4000157-510

Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
398 Appendix G Part Number Cross-Reference

Field Terminations Guide for Tricon, 11.5 and Later 11.x Systems
H
Minimum Bend Radiuses of Cables

This table identifies the minimum bend radiuses of cables.

Table 223 Minimum Bend Radiuses of Cables


Triconex Cable Assembly Number Minimum Bend Radius of Cable
4000002-006 4 in (10.16 cm)
4000004-0xx 1.75 in (4.445 cm)
4000006-0xx 2.12 in (5.3848 cm)
4000007-0xx 2.12 in (5.3848 cm)
4000008-0xx 2.12 in (5.3848 cm)
4000009-0xx 2.12 in (5.3848 cm)
4000010-00x 3 in (7.62 cm)
4000015-0xx 2.12 in (5.3848 cm)
4000016-0xx 2.12 in (5.3848 cm)
4000017-0xx 2.12 in (5.3848 cm)
4000027-006 2.5 in (6.35 cm)
4000028-006 1.75 in (4.445 cm)
4000029-0xx 5.5 in (13.97 cm)
4000030-025 1.75 in (4.445 cm)
4000041-0xx 2.125 in (5.3975 cm)
4000042-xxx 5 in (12.7 cm)
4000043-1xx 4.6 in (11.684 cm)
4000050-00x 3.25 in (8.255 cm)
4000052-006 2.5 in (6.35 cm)
4000054-x10 4.6 in (11.684 cm)
4000055-x10 5 in (12.7 cm)
4000056-00x 3 in (7.62 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
400 Appendix H Minimum Bend Radiuses of Cables

Table 223 Minimum Bend Radiuses of Cables (continued)


Triconex Cable Assembly Number Minimum Bend Radius of Cable
4000058-x10 5 in (12.7 cm)
4000059-510 6.2 in (15.748 cm)
4000060-510 4.4 in (11.176 cm)
4000061-x10 3.5 in (8.89 cm)
4000062-x10 4.6 in (11.684 cm)
4000063-510 6.2 in (15.748 cm)
4000064-510 5.4 in (13.716 cm)
4000065-510 4.4 in (11.176 cm)
4000066-025 1.75 in (4.445 cm)
4000068-x10 5 in (12.7 cm)
4000069-x10 6.2 in (15.748 cm)
4000070-0x0 4.4 in (11.176 cm)
4000071-0x0 3.5 in (8.89 cm)
4000072-x10 4.6 in(11.684 cm)
4000073-x10 6.2 in (15.748 cm)
4000074-0x0 5.4 in (13.716 cm)
4000075-0x0 4.4 in (11.176 cm)
4000076-510 6.2 in (15.748 cm)
4000078-x10 5 in (12.7 cm)
4000079-510 6.2 in (15.748 cm)
4000085-x10 4.6 in (11.684 cm)
4000086-510 5.4 in (13.716 cm)
4000089-025 1.75 in (4.445 cm)
4000090-025 2.12 in (5.3848 cm)
4000091-0xx 2.12 in (5.3848 cm)
4000092-x10 5 in (12.7 cm)
4000093-x10 5 in (12.7 cm)
4000094-x10 5 in (12.7 cm)
4000096-x01 3.5 in (8.89 cm)
4000098-510 6.20 in (15.748 cm)
4000100-310 5 in (12.7 cm)
4000101-310 4.5 in (11.43 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
401

Table 223 Minimum Bend Radiuses of Cables (continued)


Triconex Cable Assembly Number Minimum Bend Radius of Cable
4000102-x10 5 in (12.7 cm)
4000103-510 6.25 in (15.875 cm)
4000107-x0x 3.5 in (8.89 cm)
4000109-x10 5.6 in (14.224 cm)
4000110-x10 4.6 in (11.684 cm)
4000111-x10 5.6 in (14.224 cm)
4000112-x10 5 in (12.7 cm)
4000113-x10 5 in (12.7 cm)
4000114-510 6 in (15.24 cm)
4000120-510 6 in (15.24 cm)
4000121-010 5.5 in (13.97 cm)
4000122-x10 5.6 in (14.224 cm)
4000123-x10 5.6 in (14.224 cm)
4000126-x10 5.6 in (14.224 cm)
4000127-510 5.5 in (13.97 cm)
4000128-510 5.5 in (13.97 cm)
4000129-510 5.5 in (13.97 cm)
4000139-010 7.4 in (18.796 cm)
4000140-x10 3.62 in (9.1948 cm)
4000141-x10 3.62 in (9.1948 cm)
4000142-510 4.05 in (10.287 cm)
4000143-x10 5.5 in (13.97 cm)
4000144-x10 3.62 in (9.1948 cm)
4000147-510 7.4 in (18.796 cm)
4000150-510 7.4 in (18.796 cm)
4000151-510 7.4 in (18.796 cm)
4000153-xxx 1.62 in (4.1148 cm)
4000154-x10 2.1 in (5.334 cm)
4000155-x10 3.62 in (9.1948 cm)
4000157-510 4.05 in (10.287 cm)
4000161-002 3 in (7.62 cm)
4000163-xxx 6.25 in (15.875 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
402 Appendix H Minimum Bend Radiuses of Cables

Table 223 Minimum Bend Radiuses of Cables (continued)


Triconex Cable Assembly Number Minimum Bend Radius of Cable
4000164-xxx 6.25 in (15.875 cm)
4000165-xxx 5.6 in (14.224 cm)
4000166-xxx 5.6 in (14.224 cm)
4000172-3xx 5 in (12.7 cm)
4000173-3xx 4 in (10.16 cm)
4000174-3xx 4 in (10.16 cm)
4000175-510 6.25 in (15.875 cm)
4000176-510 6.25 in (15.875 cm)
4000177-510 8.1 in (20.574 cm)
4000178-510 6.25 in (15.875 cm)
4000179-310 5.6 in (14.224 cm)
4000179-510 5.6 in (14.224 cm)
4000180-310 5.6 in (14.224 cm)
4000182-5xx 6.25 in (15.875 cm)
4000183-5xx 5 in (12.7 cm)
4000184-5xx 5.5 in (13.97 cm)
4000185-3xx 5 in (12.7 cm)
4000186-3xx 5 in (12.7 cm)
4000187-x10 5 in (12.7 cm)
4000188-x10 5 in (12.7 cm)
4000189-510 6.2 in (15.748 cm)
4000190-510 6.2 in (15.748 cm)
4000191-510 6.2 in (15.748 cm)
4000192-x10 5 in (12.7 cm)
4000193-x10 5 in (12.7 cm)
4000194-510 6.2 in (15.748 cm)
4000195-x10 5 in (12.7 cm)
4000196-x10 5 in (12.7 cm)
4000197-510 6.2 in (15.748 cm)
4000198-510 6.2 in (15.748 cm)
4000199-x10 5 in (12.7 cm)
4000200-x10 5 in (12.7 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
403

Table 223 Minimum Bend Radiuses of Cables (continued)


Triconex Cable Assembly Number Minimum Bend Radius of Cable
4000201-510 6.2 in (15.748 cm)
4000202-510 6.2 in (15.748 cm)
4000203-x10 5 in (12.7 cm)
4000204-x10 5 in (12.7 cm)
4000206-510 5.5 in (13.97 cm)
4000207-510 5.5 in (13.97 cm)
4000208-510 5.5 in (13.97 cm)
4000209-510 5.5 in (13.97 cm)
4000210-010 2.12 in (5.3848 cm)
4000211-006 2.7 in (6.858 cm)
4000212-010 2.4 in (6.096 cm)
4000213-x10 5 in (12.7 cm)
4000214-x10 4.6 in (11.684 cm)
4000215-x10 5.6 in (14.224 cm)
4000216-510 5.5 in (13.97 cm)
4000217-110 5.6 in (14.224 cm)
4000218-510 5.5 in (13.97 cm)
4000219-510 6.2 in (15.748 cm)
4100002-001 3.5 in (8.89 cm)
4100005-xx0 2 in (5.08 cm)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
404 Appendix H Minimum Bend Radiuses of Cables

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
I
Low-Density Chassis I/O Module
Compatibility

Overview 406
Module Upgrades 406
ETP Upgrades for Compatibility with I/O Modules 407
Model 3807 BPAO Compatibility 416

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
406 Appendix I Low-Density Chassis I/O Module Compatibility

Overview
This appendix describes the compatibility of Model 3720, 3721, 3625, and 3625A I/O Modules
with low-density Tricon systems that have been upgraded to v10.2.x or later. This appendix also
describes the external termination kit that you can use to install the Model 3807 Bipolar AO
module in low-density systems that have been upgraded to v10.2.x or later.
To install Model 3720, 3721, 3625, or 3625A I/O Modules in low-density Tricon systems, in most
cases, you must upgrade the termination panels and interface cables, and install a new chassis
interface module. In most instances, you have the option of using RETMA-rail-mount
termination panels or equivalent DIN-rail-mount termination panels.
Upgrade ETP kits are available that include ETPs, cables, and new chassis interface modules.
Some existing ETPs used in low-density systems are compatible with Model 3720, 3721, 3625,
and 3625A I/O Modules. The existing ETP models that are compatible with these I/O modules
are identified in this appendix.

Module Upgrades
This table lists existing I/O modules and identifies the newer I/O modules that they can be
upgraded with in low-density Tricon systems that have been upgraded to v10.2.x or later.

Table 224 Module Upgrades


Module Type Existing I/O Module Upgrade I/O Module
AI 3700 3721
32 points 32 points
3700A 3721
32 points 32 points
3704Ea 3720a
64 points 64 points
DO 3604E 3625/A
16 points 32 points
3614E 3625/A
8 points 32 points
3615E 3625/A
8 points 32 points
3624 3625/A
16 points 32 points

a. The upgrade from the Model 3704E AI Module to the Model


3720 AI Module is only available for 0–5 V applications.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 407

ETP Upgrades for Compatibility with I/O Modules


This section identifies External Termination Panel kits that existing ETPs should be replaced
with to provide compatibility with Model 3720, 3721, 3625, and 3625A I/O Modules in low-
density Tricon systems that have been upgraded to v10.2.x or later. Also, Existing ETP models
that are already compatible with these I/O modules are identified.
Topics include:
• 3700 and 3700A AI Module ETP Upgrade on page 408
• 3704E AI Module ETP Upgrade on page 409
• 3604E DO Module ETP Upgrade on page 410
• 3614E DO Module ETP Upgrade on page 412
• 3615E DO Module ETP Upgrade on page 414
• 3624 DO Module ETP Upgrade on page 416

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
408 Appendix I Low-Density Chassis I/O Module Compatibility

3700 and 3700A AI Module ETP Upgrade


This table lists ETPs used with Model 3700 and Model 3700A AI Modules in low-density
systems and identifies upgrade RETMA-rail-mount ETP kits that you can replace them with
when you are upgrading to the Model 3721 AI Module.

Table 225 3700 and 3700A AI Module—Upgrade to 3721 with RETMA-Rail ETP Kits
RETMA-Rail RETMA-Rail ETP Upgrade RETMA-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
2750-2a Current input, 2750-210L 2 x 4000184-510 (cable)
0–5 VDC, 32 pts. 1 x 3000280-500 (interface module)
1 x 3000142-220 (ETP)
2750-8b Voltage input, 2750-810L 2 x 4000184-510 (cable)
0–5 VDC, 32 pts. 1 x 3000280-500 (interface module)
1 x 3000142-280 (ETP)

a. This ETP does not require an upgrade kit for compatibility with Model 3721 AI Modules in low-
density systems; however, if you want to add additional AI points, use the 2750-2L.
b. This ETP does not require an upgrade kit for compatibility with Model 3721 AI Modules in low-
density systems; however, if you want to add additional AI points, use the 2750-8L.

This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3700 and Model 3700A AI Modules in low-density systems
when you are upgrading to the Model 3721 AI Module.

Table 226 3700 and 3700A AI Module—Upgrade to 3721 with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9761-210F Current input, 9761-210FL 2 x 4000182-510 (cable)
0–5 VDC, 1 x 3000280-500 (interface module)
-5–5 VDC, 16 pts.
2 x 3000510-510 (ETP)
9763-810F Voltage input, 9763-810FL 2 x 4000182-510 (cable)
0–5 VDC, 1 x 3000280-500 (interface module)
-5–5 VDC,
0–10 VDC, 16 pts. 2 x 3000580-110 (ETP)

9771-210F Current input, 9771-210FL 2 x 4000182-510 (cable)


0–5 VDC, 1 x 3000280-500 (interface module)
user configurable,
32 pts. 2 x 3000656-210 (ETP)

9764-310F RTD/TC/AI, 9764-310FLa 2 x 4000182-510 (cable)


0–5 VDC, 1 x 3000280-500 (interface module)
-5–5 VDC, 16 pts.
2 x 3000712-200 (ETP)

a. The 9764-310FL also is the only upgrade ETP kit available for these obsolete RETMA-rail ETP kit
models: 2790-1, 2790-11, 2790-12, 2790-13, 2790-14, 2790-15, 2790-16, 2790-17, 2790-2, 2790-21, 2790-22,
2790-23, 2790-24, 2790-25, 2790-26, 2790-27, 2790-3T, 2790-4T.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 409

3704E AI Module ETP Upgrade


The upgrade from the Model 3704E AI Module to the Model 3720 AI Module is only available
for 0–5 V applications.
This table lists ETPs used with Model 3704E AI Modules in low-density systems and identifies
upgrade RETMA-rail-mount ETP kits that you can replace them with when you are upgrading
to the Model 3720 AI Module.

Table 227 3704E AI Module—Upgrade to 3720 with RETMA-Rail ETP Kits


RETMA-Rail Upgrade RETMA-Rail
Upgrade ETP Kit Includes...
ETP Model ETP Kit Model
2760-2a n/a n/a
Current input,
0–5 VDC, 64 pts.
2760-8a n/a n/a
Voltage input,
0–5 VDC, 64 pts.

a. This ETP does not require a new kit for compatibility with Model 3720 AI Modules in low-density
systems.

This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3704E AI Modules in low-density systems when you are
upgrading to the Model 3720 AI Module.

Table 228 3704E AI Module—Upgrade to 3720 with DIN-Rail ETP Kits


DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9765-210F 3-wire current 9765-210FL 2 x 4000183-510 (cable)
input, 1 x 3000280-500 (interface module)
0–5 VDC, 32 pts.
2 x 3000475-520 (ETP)
9760-210F Current input, 9760-210FL 2 x 4000183-510 (cable)
0–5 VDC, 32 pts. 1 x 3000280-500 (interface module)
2 x 3000470-510 (ETP)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
410 Appendix I Low-Density Chassis I/O Module Compatibility

3604E DO Module ETP Upgrade


This table lists ETPs used with Model 3604E DO Modules in low-density systems and identifies
upgrade RETMA-rail-mount ETP kits that you can replace them with when you are upgrading
to the Model 3625 or 3625A DO Modules.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.

Table 229 3604E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA-Rail RETMA-Rail ETP Upgrade RETMA-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
2652-1 24 VDC, 2652-110L 2 x 4000172-310 (cable)
non-commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000120-310 (ETP)
2652-6 24 VDC, 2652-610L 2 x 4000172-310 (cable)
1x8 commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000120-360 (ETP)
2652-8 24 VDC, 2652-810L 2 x 4000172-310 (cable)
redundant, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000120-380 (ETP)
2661-1 24 VDC, 2661-110L 2 x 4000172-310 (cable)
external relay, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000290-310 (ETP)
2661-8 24 VDC, commoned, 9671-810FLa 2 x 4000186-310 (cable)
interposing relay, 1 x 3000280-300 (interface module)
fused, 16 pts.
1 x 3000290-380 (ETP)

a. This high-density upgrade ETP kit is the only option for compatibility with Model 3625 or 3625A DO
Modules in low-density systems.

When you use the supervisory function of the Model 3625 or 3625A DO Module with the 9671-
810FL or the 2661-110L ETPs, only the ELCO termination cable and the relay coil will be
monitored for field fault detection.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 411

This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3604E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.

Table 230 3604E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9662-110F 24 VDC, 9662-110FL 2 x 4000185-310 (cable)
non-commoned, 1 x 3000280-300 (interface module)
fused, 16 pts.
1 x 3000570-310 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)
9671-810F 24 VDC, 9671-810FL 2 x 4000186-310 (cable)
commoned, 1 x 3000280-300 (interface module)
interposing relay,
fused, 16 pts. 1 x 3000290-380 (ETP)

When you use the supervisory function of the Model 3625 or 3625A DO Module with the 9671-
810F or the 9671-810FL ETPs, only the ELCO termination cable and the relay coil will be
monitored for field fault detection.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
412 Appendix I Low-Density Chassis I/O Module Compatibility

3614E DO Module ETP Upgrade


This table lists ETPs used with Model 3614E DO Modules in low-density systems and identifies
upgrade RETMA-rail-mount ETP kits that you can replace them with when you are upgrading
to the Model 3625 or 3625A DO Module.

Table 231 3614E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA- Upgrade
RETMA-Rail ETP
Rail ETP RETMA-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
2652-5 24 VDC, 2652-510L0 2 x 4000174-310 (cable) Use this kit if
1x16 1 x 3000280-300 (interface module) you have four
commoned, eight-point ETPs
8 pts.
2652-510L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-350 (ETP)
2652-510L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-350 (ETP)
2652-510L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-350 (ETP)
2652-510L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-350 (ETP)
2652-9 24 VDC, 2652-910L0 2 x 4000174-310 (cable) Use this kit if
redundant, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-910L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-390 (ETP)
2652-910L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-390 (ETP)
2652-910L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-390 (ETP)
2652-910L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-390 (ETP)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 413

This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3614E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.

Table 232 3614E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail Upgrade
DIN-Rail ETP
ETP DIN-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
9662-910F 24 VDC, 9662-910FL0 2 x 4000173-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
fused, 8 pts. eight-point ETPs
9662-910FL1 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000550-380 (ETP)
9662-910FL2 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000550-380 (ETP)
9662-910FL3 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000550-380 (ETP)
9662-910FL4 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000550-380 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)

If connected, you must disconnect 5 V shorted-load detection power (PS3) for the ETP to
function correctly.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
414 Appendix I Low-Density Chassis I/O Module Compatibility

3615E DO Module ETP Upgrade


This table lists ETPs used with Model 3615E DO Modules in low-density systems and identifies
upgrade RETMA-rail-mount ETP kits that you can replace them with when you are upgrading
to the Model 3625 or 3625A DO Module.

Table 233 3615E DO Module—Upgrade to 3625 or 3625A with RETMA-Rail ETP Kits
RETMA- Upgrade
RETMA-Rail ETP
Rail ETP RETMA-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
2652-55 24 VDC, 1x16 2652-55L0 2 x 4000174-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-55L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-355 (ETP)
2652-55L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-355 (ETP)
2652-55L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-355 (ETP)
2652-55L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-355 (ETP)
2652-95 24 VDC, 2652-95L0 2 x 4000174-310 (cable) Use this kit if
redundant, 1 x 3000280-300 (interface module) you have four
8 pts. eight-point ETPs
2652-95L1 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000120-395 (ETP)
2652-95L2 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000120-395 (ETP)
2652-95L3 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000120-395 (ETP)
2652-95L4 2 x 4000174-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000120-395 (ETP)

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
ETP Upgrades for Compatibility with I/O Modules 415

This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3615E DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.

Table 234 3615E DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail Upgrade
DIN-Rail ETP
ETP DIN-Rail Upgrade ETP Kit Includes... Comments
Description
Model ETP Kit Model
9662-710F 24 VDC, 9662-710FL0 2 x 4000173-310 (cable) Use this kit if
commoned, 1 x 3000280-300 (interface module) you have four
low-power, eight-point ETPs
fused, 8 pts.
9662-710FL1 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have three
eight-point ETPs
1 x 3000550-390 (ETP)
9662-710FL2 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have two
eight-point ETPs
2 x 3000550-390 (ETP)
9662-710FL3 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have one
eight-point ETP
3 x 3000550-390 (ETP)
9662-710FL4 2 x 4000173-310 (cable) Use this kit if
1 x 3000280-300 (interface module) you have no
eight-point ETPs
4 x 3000550-390 (ETP)
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
2 x 3000410-360 (ETP)

If connected, you must disconnect 5 V shorted-load detection power (PS3) for the ETP to
function correctly.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
416 Appendix I Low-Density Chassis I/O Module Compatibility

3624 DO Module ETP Upgrade


This table lists DIN-rail-mount ETPs and associated upgrade ETP kits that you can use to
replace ETPs connected to Model 3624 DO Modules in low-density systems when you are
upgrading to the Model 3625 or 3625A DO Module.
The 16-point upgrade ETP kits are configured with the assumption that you have one similar
existing ETP per 3625 or 3625A module. To terminate all of the points on the module, which is
recommended, you may wish to purchase additional ETPs separately.

Table 235 3624 DO Module—Upgrade to 3625 or 3625A with DIN-Rail ETP Kits
DIN-Rail DIN-Rail ETP Upgrade DIN-Rail
Upgrade ETP Kit Includes...
ETP Model Description ETP Kit Model
9662-610F 24 VDC, 9662-610FL 2 x 4000185-310 (cable)
commoned, 1 x 3000280-300 (interface module)
16 pts.
1 x 3000520-390 (ETP)
9653-610F 24 VDC, 9653-610FL 2 x 4000185-310 (cable)
basic, 16 pts. 1 x 3000280-300 (interface module)
1 x 3000410-360 (ETP)

Model 3807 BPAO Compatibility


This table describes the external termination kit that you can use to install the Model 3807
Bipolar AO module in low-density systems that have been upgraded to v10.2.x or later.

Upgrade Kit Model Upgrade Kit Includes...


2853-110F 1 x 4000219-510 (cable)
1 x 3000270-510 (interface module)
1 x 3000818-560 (ETP, current output, 4pts.)

This kit contains nonincendive circuits and can be used in hazardous locations. When using the
Model 3807 Bipolar AO module in hazardous locations, you must install ETPs and associated
field wiring according to the requirements of the prevailing local electrical codes and the
instructions in Chapter 3 of the Planning and Installation Guide for Tricon 11.5 and Later 11.x
Systems.
In Europe, the ETP in this kit is in full compliance with the ATEX Directive and is suitable for
use in Zone 2 Group IIB hazardous locations per the requirements of EN 60079-15, Electrical
apparatus for explosive gas atmospheres - Part 15: Type protection “n”.
In North America, the ETP in this kit is suitable for use in Class 1, Division 2 Groups C and D
hazardous locations per the requirements of ANSI/ISA S12.12.01-2000, Nonincendive Electrical
Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous
(Classified) Locations.
This kit can also be used for applications in non-hazardous (non-ATEX) locations.

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
J
Using V8 ETPs with v11 Systems

Selected version 8 “low-density” external termination panels (ETPs) can be used with version
11 systems as identified in Table 236 V8 ETPs Compatible with v11 Systems (page 417). The
cables and ETPs must be ordered separately. In some cases, 2 cables must be ordered per ETP.
Each ETP kit includes 1 or 2 external termination panels on a 19 inch RETMA compatible plate.
The V8 User’s Guide for Field Termination should be used for all ETP application and field
wiring information.

Table 236 V8 ETPs Compatible with v11 Systems


V8 Compatible Compatible V8
Termination Description v11 v11 Interface Termination
Kit Model # I/O Module Cable Panel (ETP)
Digital Input
2551-1 Digital Input, 3501E/T 4000214-1xx, 3000110-110
115 VAC/VDC, 2 required per
Non-commoned ETP
2551-6 Digital Input, 3501E/T 4000214-1xx, 3000110-160
115 VAC/VDC, 2 required per
Commoned ETP
2551-8 Digital Input, 3501E/T 4000214-1xx, 3000110-180
115 VAC/VDC, 2 required per
Commoned, ETP
Redundant
2552-6 Digital Input, 3502E 4000214-2xx, 3000110-260
48 VAC/VDC, 2 required per
Commoned ETP
2552-8 Digital Input, 3502E 4000214-2xx, 3000110-280
48 VAC/VDC, 2 required per
Commoned, ETP
Redundant
2553-6 Digital Input, 24 VDC, 3503E 4000214-3xx, 3000110-360
Commoned 2 required per
ETP

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
418 Appendix J Using V8 ETPs with v11 Systems

Table 236 V8 ETPs Compatible with v11 Systems (continued)


V8 Compatible Compatible V8
Termination Description v11 v11 Interface Termination
Kit Model # I/O Module Cable Panel (ETP)
2553-8 Digital Input, 24 VDC, 3503E 4000214-3xx, 3000110-380
Commoned, 2 required per
Redundant ETP
2555-6 Digital Input, 48 VDC, 3504E 4000187-2xx, 3000352-280
Commoned 2 required per
ETP
2555-8 Digital Input, 48 VDC, 3504E 4000187-2xx, 3000352-280
Commoned, 2 required per
Redundant ETP
2554-6 Digital Input, 24 VDC, 3504E 4000187-3xx, 3000352-380
Commoned 2 required per
ETP
2554-8 Digital Input, 24 VDC, 3504E 4000187-3xx, 3000352-380
Commoned, 2 required per
Redundant ETP
2553-6 Digital Input, 24 VDC, 3505E 4000214-3xx, 3000110-360
Commoned 2 required per
ETP
2553-8 Digital Input, 24 VDC, 3505E 4000214-3xx, 3000110-380
Commoned, 2 required per
Redundant ETP
2560-9 Pulse Input 3510 Not supported Not supported
3511
Digital Output
2651-1 Digital Output, 3601E/T 4000215-1xx 3000120-110
115 VAC,
Non-commoned
2651-6 Digital Output, 3601E/T 4000215-1xx 3000120-160
115 VAC, Commoned
2652-1 Digital Output, 3604E 4000215-3xx 3000120-310
24 VDC,
Non-commoned
2652-6 Digital Output, 3604E 4000215-3xx 3000120-360
24 VDC, Commoned
2652-8 Digital Output, 3604E 4000215-3xx 3000120-380
24 VDC, Commoned,
Redundant

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
419

Table 236 V8 ETPs Compatible with v11 Systems (continued)


V8 Compatible Compatible V8
Termination Description v11 v11 Interface Termination
Kit Model # I/O Module Cable Panel (ETP)
2657-1 Digital Output, 3607E 4000215-2xx 3000120-210
48 VDC,
Non-commoned
2657-6 Digital Output, 3607E 4000215-2xx 3000120-260
48 VDC, Commoned
2657-8 Digital Output, 3607E 4000215-2xx 3000120-280
48 VDC, Commoned,
Redundant
2651-2 Digital Output, 3603B For more
2651-9 120 VDC, information,
All versions see 9251-210F
(120 VDC, non-
commoned, 16
pts., 3603B
module) on
page 124.
2651-7 Digital Output, 3603B 4000203-1xx For more
120 VDC, information,
All versions see 9251-210F
(120 VDC, non-
commoned, 16
pts., 3603B
module) on
page 124.
Supervised, Digital Output
2651-5 Supervised Digital 3611E Not supported Not supported
2651-3 Output, 3613E
2651-8 All versions 3614E
2652-5 3617E
2652-9
2657-5
2657-9
Relay Output
2658-1 Relay Output, 3636R/T 4000217-1xx, 3000250-010
Non-commoned 2 required per
ETP
2658-6 Relay Output, 3636R/T 4000217-1xx, 3000250-060
Commoned 2 required per
ETP

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
420 Appendix J Using V8 ETPs with v11 Systems

Table 236 V8 ETPs Compatible with v11 Systems (continued)


V8 Compatible Compatible V8
Termination Description v11 v11 Interface Termination
Kit Model # I/O Module Cable Panel (ETP)
2658-8 Relay Output, 3636R/T 4000217-1xx, 3000250-080
Commoned, 2 required per
Redundant ETP
Analog Input
2750-2 AI, 0–20 ma/5 V 3700 4000218-5xx, 3000142-220
3700A 2 required per
ETP
2750-4 AI, 0–20 ma/10 V 3701 4000218-5xx, 3000142-240
2 required per
ETP
2750-8 AI, 0–5 V/10 V, 3700 4000218-5xx, 3000142-280
Non-commoned 3700A 2 required per
3701 ETP

2752-2 EIAI, 0–20 ma/5 V 3703E 4000218-5xx 3000142-320


2752-4 EIAI, 0–20 ma/10 V 3703E 4000218-5xx 3000142-340
2752-8 EIAI, 0–5 V/10 V, 3703E 4000218-5xx 3000142-380
Non-commoned
2760-2 Analog Input, 3704E 4000206-5xx, 3000352-120
0-20 mA/5 V 2 required per
ETP
2760-8 Analog Input, 3704E 4000206-5xx, 3000352-180
0–5/0–10 VDC 2 required per
ETP
2756-2 Non-Isolated, 3706A 4000218-5xx, 3000142-900
(upscale) Thermocouple Input 2 required per
2756-5 ETP
(downscale)
2755-6 Isolated, 3708E 4000218-5xx 3000142-600
Thermocouple Input
Analog Output
2852-1 Analog Output 3805E/H 4000216-5xx 3000259-100

Field Terminations Guide for Tricon 11.5 and Later 11.x Systems
Schneider Electric Systems USA, Inc.

38 Neponset Avenue
Foxborough, MA 02035-2037
United States of America
www.schneider-electric.com

As standards, specifications, and designs change from time to time,


please ask for confirmation of the information given in this publication.

© 2004–2021 Schneider Electric. All rights reserved.

You might also like