MCB Current Calculation
MCB Current Calculation
on -
November 21, 2018
Instagram Pinterest
YouTube Whatsapp
Rss
POPULAR POSTS
MCB Current Calculation, OLR, Fuses and Cable size Calculations for 20 Hp Three
phase (TP) Induction Motor. You can use this formula for any load, to choose MCB How to Make a Low-Cost Water Filter
(Miniature circuit breaker), Fuses and Over Load Relay (OLR) calculation. For Home
May 31, 2020
Type of Load : Three Phase Induction Motor 20 Hp, LL- 400V, 0.88 PF as shown in
Automatic Transfer Switch (ATS)
Motor name plate
working
August 14, 2018
Full Load Current (FLC) Calculation
FLC = 19.1Amps
MCB Current Calculation
Also read : Over load Relay Operating Principles | Types and Connections of OLR
Circuit Breaker (MCB) Instantaneous Trip Current = 800% x 19.1 = 152.8 Amps
Circuit Breaker (MCB) Invers Trip Current = 250% x 19.1 = 47.75 Amps
Starting Current : 6 or 7 times x FLC (IL) = 7 x 19.1 = 133.7 Amp
Contactor Value as per NEC:150% of FLC = 1.5 x 19.1 = 28.65 Amps (Available 40 Amps)
powerstarelectric.in OPEN
REACTIONS
Defferance between On Delay What is an IP Rating in Electrical Difference between VFD and Soft
Timer and Off Delay Timer January 18, 2021 Starter
March 07, 2021 October 28, 2020
POST A COMMENT
3
Comments
www.essay-editor.net/blog/paper-editing-website-get-necessary-help said…
When I was at school, I always hated Math. Even now, these tasks are very difficult for me, though, I
understand, that knowledge of Math is very useful.
13/5/20 16:46
ModernSupplies said…
Best and Famous Rockfon Industrial Products in Australia
31/8/21 10:49
Post a Comment
Solar System 3
Copyright © 2021 Created by EEETECHS4U | Designed by AKR Technical Home About Us Contact Privacy-Policy Disclaimer