Grasso System Control
Grasso System Control
Operating Instructions
_805011_om_gsc_sp2_gbr_1_.doc 1
OPERATING INSTRUCTIONS
COPYRIGHT
All Rights reserved. No part of this publication may be copied or published by means of printing, photocopying,
microfilm or otherwise without prior written consent of Grasso. This restriction also applies to the corresponding
drawings and diagrams.
LEGAL NOTICE
This publication has been written in good faith. However, Grasso cannot be held responsible, neither for any
errors occurring in this publication nor for their consequences.
2 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
Warning!
Attention! Caution! Important!
Hint!
Tip! Note!
_805011_om_gsc_sp2_gbr_1_.doc 3
OPERATING INSTRUCTIONS
TABLE OF CONTENTS
1 Start-up / Operation of GSC .................................................................................................................. 8
1.1 General Information ................................................................................................................. 8
1.2 Description of the Grasso System Control................................................................................ 8
1.2.1 View............................................................................................................................... 8
1.2.2 Lamps/ Push buttons .................................................................................................. 10
1.2.3 Operator terminal....................................................................................................... 11
1.2.3.1 Key assignment............................................................................................ 12
1.2.3.2 Call up table of contents ............................................................................. 14
1.2.4 Status displays ............................................................................................................. 15
1.3 System description GSC........................................................................................................... 18
1.3.1 Explanation of the system LED................................................................................... 18
1.4 Alarms ..................................................................................................................................... 19
1.4.1 View active alarms and warnings............................................................................... 19
1.4.2 No alarm signal and the compressor will not start.................................................... 19
1.4.3 Restart following Alarms ............................................................................................ 20
_805011_om_gsc_sp2_gbr_1_.doc 5
OPERATING INSTRUCTIONS
TABLE OF FIGURES
fig. 1: View of outside of switchgear cabinet................................................................................................ 8
fig. 2: View of inside of switchgear cabinet .................................................................................................. 9
fig. 3: GSC operator terminal ....................................................................................................................... 11
fig. 4: "Status messages" display................................................................................................................... 15
fig. 5: Restart following Alarms ................................................................................................................... 20
_805011_om_gsc_sp2_gbr_1_.doc 7
OPERATING INSTRUCTIONS
For more specific information see GSC User Manual or press the key to obtain more
information about the selected parameter.
The GSC is supplied with text in native language.
1.2.1 View
[Chapter 1.1.1. in user manual]
A HP
B LP
C Warning
D Failure
8 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
1 Profibus DP/DP-coppler
2 Bus Terminal
3 Type of Power Supply
4 Emergency stop relay
5 Relays
6 Socket-outlet for service
_805011_om_gsc_sp2_gbr_1_.doc 9
OPERATING INSTRUCTIONS
10 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
A System LED’s
B Function keys
C soft keys
D CPU operating mode setting
E digital keybord
F cursor keys
G System keys
H System keys LED‘s
_805011_om_gsc_sp2_gbr_1_.doc 11
OPERATING INSTRUCTIONS
Key Function
without function
+
Lamp test
without function
+
12 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
Key Function
Confirm input
Cursor keys
_805011_om_gsc_sp2_gbr_1_.doc 13
OPERATING INSTRUCTIONS
To get to the table of contents, press the key. A list of the available menus is then displayed.
14 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
50 Configuration Enter:
— Refrigerants
— SC-Type
— Code
— - with/ without economiser
— - scaling of the sensors
To get to these menus, position the cursor on the menu name (using the or key) and confirm with the
key.
Danger!
Parameter changes in menu 20, 30, 35, 50 can cause serious damage to the screw compressor
unit or chiller!
To get to the "status display" views, press the key several times, or press the key and then .
This display shows all of the information shown in the first actual values screen plus the status of the compressor
unit.
Hint!
See menu 05 actual values
_805011_om_gsc_sp2_gbr_1_.doc 15
OPERATING INSTRUCTIONS
Initialisation Initialisation of the control after switching on the power supply or after saving the
settings (RAM → ROM)
Start to start HP A switch on frequency limitation of the HP compressor drive motor is still active
Oil drain A switch on block period is active, the oil pump has run too long by itself
(Minimum position was not reached during start or stop procedure)
Standby Compressor unit/ chiller ready for switching on, but one or more starting conditions
are still not fulfilled e.g. process variable still below set point
No start release The controller is waiting for an external signal to enable the start of the unit
Force to Min HP Starting procedure issued, slide moves to minimum position (HP)
Starting HP Compressor motor has been started, but the switchover to "Delta" has not yet taken
place or the startup has not yet been completed.
Running Compressor motor running in "Delta" or startup has been completed. Package/ Chiller
in operation.
Psuc Limitation A capacity limitation is active (suction pressure too low), "reduce output" solenoid
valve is opened.
Pdis Limitation A capacity limitation is active (discharge pressure too high), "reduce output" solenoid
valve is opened.
Imot Limitation HP A capacity limitation is active (HP motor current too high), "reduce output" solenoid
valve is opened.
Text Limitation A capacity limitation is active (external temperature too low), "reduce output"
solenoid valve is opened.
Toil Limitation Oil temperature too high, "refrigerant injection" is enabled (optional)
Stopping HP The compressor unit/ chiller has received a shutdown command, the capacity slide is
moved towards its minimum position (HP)
Pump by itself The minimum position was not reached during switch on or off procedure. The oil
pump continues to try to adjust the control slide in the min direction. After the oil
pump run by itself the oil block period becomes active.
Pull down Pinterm The intermediate pressure is drawn off down to the switch on pressure (release of
the LP compressor)
16 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
Start to start LP A switch on frequency limitation of the LP compressor drive motor is still active
Imot Limitation LP A capacity limitation is active (LP motor current too high), "reduce output" solenoid
valve is opened.
Pdis Limitation LP A capacity limitation as active (LP discharge pressure too high), "reduce output"
solenoid valve is opened
Psuc Limitation HP A capacity limitation as active (HP suction pressure too low), "reduce output" solenoid
valve is opened
Slide to min LP Starting command issued, control slide moves into the minimum position (LP)
Starting LP Compressor motor has been started, and the running feedback signal from the
starter panel has not yet been received (LP)
Stopping LP The compressor unit/ chiller has received a shutdown command, the capacity slide is
moved towards its minimum position (LP)
The overall status of the compressor unit is displayed with the LEDs in and .
_805011_om_gsc_sp2_gbr_1_.doc 17
OPERATING INSTRUCTIONS
DC5V (green) Voltage supply for C7 lights up, if the internal DC 5V supply is OK.
RUN (green) Operating state RUN of the C7- lights up, if the C7 CPU application program is running.
CPU flashes (2Hz) during the C7 CPU start up (the STOP lamps also
lights up; after the STOP lights go off, the outputs are released).
STOP (yellow) Operating state STOP of the C7 lights up, if the C7 is not processing a CPU-application program.
CPU flashes at 1-second intervals, if C7 CPU general reset (MRES) is
required.
SF-IM (red) Switching module - centralised lights up, if the connection between C7 and the extension rack
fault is interrupted.
18 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
Alarm active lights up, if a malfunction has been confirmed, but is still active.
(red)
flashes, if a further malfunction has been activated.
Help (green) Help text available lights up, if a help text is available.
Shift (green) Switch over function active lights up, if the SWITCHOVER function is active.
1.4 Alarms
[Chapter 6. in user manual]
The ´Status mode´ is displayed by pressing the key several times. The most important actual values are
shown in the first three rows and in the 4th row the status message is shown.
By scrolling with the cursor keys and all active alarms and warnings are displayed.
Key “ON” has been pressed and the LED K1 ”ON” is flashing.
Cause Remedy
No ‘start release’ signal The input ´start release´ is not Close input or install a link.
closed.
‘Auto Start dly’ active The time setting ‘Auto start dly’ in Wait until the delay time has
‘control settings menu’ has not yet expired.
expired.
‘Start to start’ delay active The time setting ‘Start to start’ in Wait until the delay time has
‘Timer settings’ menu has not yet expired.
expired.
actual value < (set point + ½ NZ) Check set point and neutral zone
NZ = neutral zone settings in ´Control settings´menu.
In case of suction pressure control
the set point value is entered in
degrees Celsius.
_805011_om_gsc_sp2_gbr_1_.doc 19
OPERATING INSTRUCTIONS
Caution!
It is not possible to restart the compressor as long as the cause of the alarm still exists!
20 _805011_om_gsc_sp2_gbr_1_.doc
OPERATING INSTRUCTIONS
Display of the cause(s) of the alarms after deleting the display on view (press the key) or in the case that
several alarms have occurred simultaneously:
Step Procedure
1
Call up the "Alarms" menu by pressing the key.
2
Select the "View" menu item for the alarms by pressing the key.
The errors that have occurred can be viewed here with the date and time at which
they occur.
Caution!
For more detailed explanations for reading the error messages, see Chapter 1.2.2.2. (GSC User
Manual).
_805011_om_gsc_sp2_gbr_1_.doc 21