Exercise 1
Exercise 1
COM
Exercise 1
a) FRL Unit.
b) 3/2 Push Button Valve.
c) Single Acting Spring Return Cylinder.
1
WWW.VIDYARTHIPLUS.COM
Fig no:1
Observations:
When the push button is pressed, the spring in the valve is compressed,
allowing air to flow through the valve to the cylinder. Air passes through
the rear port of the cylinder and pushes the piston rod out.
(Thereby opening the gate).
When the push button released, the spring in the valve expands. Air is
exhausted from the cylinder and airflow to the cylinder is blocked. The
spring in the cylinder is able to expand; the piston rod retracts (thereby
closing the gate)
2
WWW.VIDYARTHIPLUS.COM
Exercise 2
Design a pneumatic circuit using a double acting cylinder and 5/2
Air Spring Valve to open the main gate of a factory which can be
controlled by a security personnel from the security room.
Component List:
a) FRL Unit:
b) 5/2 Air Spring Valve.
c) 3/2 Push botton Valve
d) Double Acting Cylinder.
Procedure:
Load the double acting cylinder and place at the top of the screen.
Load 5/2 Air Spring Valve and place below the cylinder. The FRL
Unit will be at the bottom by default. Connect the components as
per the circuit, as show in fig. No.2 Start simulation by clicking
on the simulation icon and observe the following
3
WWW.VIDYARTHIPLUS.COM
Fig no:2
Observations:
When the Push button valve is activated, allowing air to flow through the 5/2air spring
valve to the rear port of the cylinder then piston rod extends. (There by opening the gate).
When the Push Button is released, allowing the air to flow through the valve to the front
port of the cylinder. The cylinder piston rod retracts.
4
WWW.VIDYARTHIPLUS.COM
Exercise3
List of components:
a) FRL Unit
b) 5/2 Air Spring Valve
c) 3/2 Push button Valve.
d) Double Acting Cylinder
e) Flow Control valves -2 Nos.
Procedure:
5
WWW.VIDYARTHIPLUS.COM
Fig.No.3
Observations:
When the Push Button is pressed, allowing air to flow through the
valve to the one port of the cylinder. The air enters from the rear
port of the cylinder and pushes the piston rod out. ( Thereby
opening the gate). When the push-button Valve released, allowing
the air to flow through the valve to the front port of the cylinder.
Then the cylinder piston rod retracted (thereby gate is closed).
Adjust the throttle valve screws and observe the variation in piston
speed.
6
WWW.VIDYARTHIPLUS.COM
Exercise 4
Apparatus:
a) Power Pack
b) 4/2 Hand Operated Valve.
c) Double Acting Cylinder.
Procedure:
Select the components from the component library and place at suitable location.
Connect the component as per the circuit shown in the fig no 4Start the simulation
by pressing the simulation button and observe the following.
Fig.No.4
Observations:
7
WWW.VIDYARTHIPLUS.COM
When the hand lever is pressed, allowing fluid to flow through the valve to rear port of
the cylinder and pushes the piston rod out. (Thereby raise the pallet). When the hand
lever raised up, allowing the fluid to flow through the valve to the second port of the
cylinder. Then the cylinder piston rod retracts. (Thereby lowering the pallet).
8
WWW.VIDYARTHIPLUS.COM
Experiment:5
LAMP
9
WWW.VIDYARTHIPLUS.COM
12. After the programming go to PROJECT and select REBUILT all to verify the
program.
13. If any error on program which is written on the screen. Then it will be
displayed on the Bottom of the Screen.
14. Before down load the program to PLC follow the Instruction given below
❖ If any errors displayed then correct it, after that go to ONLINE.
❖ Connects the mains plug in to the mains board, keep the power switch
in ON position.
❖ Now verify the power and Run LED will be glow
❖ Connect the Interface cable between PLC to PC
❖ Patch the circuit
15. Now go to ONLINE ---- Communication parameters and select the Comport
and baud rate Then again go to ONLINE -----Login
16. If it is shown the Error like PLC does not respond to Login Click OK and verify
the Interface cable between PC to PLC If it is on perfect then select another
Com port.
17. Now Login to PLC and down load the Program to PLC. After that the screen
shows to the program is download successfully. Now the PLC is ready to do
process.
19. In MONO PULSE TRIGGERRING two switches available we use normally open
for START button and normally closed for STOP button. When you press start
button “ON” button closed and input passes through START and STOP button
(it is already closed) to “ON” the “LAMP”. Once the Lamp “ON” this signal
goes also in parallel contact “LAMP_1”. The motor will run if you Release the
start button because the input signal passes through parallel contact of the
stop button. When you press the stop button the NC contact is opened then
no signal passes through it so the Lamp will goes to be “OFF”.
Experiment: 6
Using PLC, Write and simulate a program to move the forward stroke of a pneumatic double acting
cylinder in 15seconds and to return after 10seconds.
10
WWW.VIDYARTHIPLUS.COM
Components Required:
1. PLC trainer kit
2. FRL unit.
3.5/2 Double solenoid valve
4. Double acting cylinder
Procedure:
20. After the connection, go to PROJECT menu and select REBUILT all to
Verify the program.
21. Now go to ONLINE menu and Login.
22. Click down load menu to transfer the Program to PLC CPU.
23. Finally, by clicking the Run menu, the required operation is performed.
11
WWW.VIDYARTHIPLUS.COM
Fig no: 7
Result:
By using the PLC, the required operation is performed.
12
WWW.VIDYARTHIPLUS.COM
Experiment :7
Write and simulate a program in PLC to repeat 15 times the to and fro motion of a pneumatic
Double acting cylinder.
Components Required:
1. PLC trainer kit
2. FRL unit.
3.5/2 Double solenoid valve
4. Double acting cylinder
Procedure:
13
WWW.VIDYARTHIPLUS.COM
Fig no: 8
Result:
By using the PLC, the required operation is performed.
14
WWW.VIDYARTHIPLUS.COM
Exercise 8
Aim :
To study the closed loop operation of the Flow Process control using PID controller with
LABVIEW. Also To find the Kc and Ti value of the PID controller for a particular set point.
Apparatus :
FRONT PANEL
BLOCK DIAGRAM
15
WWW.VIDYARTHIPLUS.COM
Procedure :
1. To interconnect the Flow Process Station Trainer as per the patching diagram.
2. Ensure all the precautions and follow as per the previous experiment.
3. Ensure the connection of the process variable to ADC and DAC output to the V to I converter.
16
WWW.VIDYARTHIPLUS.COM
7. Set the value of set flow rate of process (say for example 1200LPH) using numeric Indicator
named SET FLOW in the front panel of experiment 5.3.
8. To find the final value of P gain Kc and Ti for that increase the Kc value first from minimum to
final value keep other values are zero. After getting P gain increase Ti from step-by-step from
minimum to final value with P gain & keep Td as zero. For a constant input-output process .Td is
not necessary. -Td is mainly used at the rapid change of process variable.
9. At the initial state set the PID GAIN parameters, Proportional gain (Kc) = 1
Integral Time (Ti) =0
Derivative Time (Td) = 0
RUN
Don’t stop the program until to find the final value of Kc and Ti are found.
11. Check the front panel actual flow meter indicates zero and I to P input current and the output
pressure. And also observe the control valve, which is also open.
12. After opening the valve switch ON the motor using START switch.
13. Now the process (Actual flow) is increasing slowly and try to reach the predefined set flow with
the applied P gain. To find the final value of proportional gain will includes the following three
steps.
14. After some time interval the screen looks like below
STEP 1:
1200 LPH
17
WWW.VIDYARTHIPLUS.COM
Steady state
error
The above diagram gives the larger value of steady state error this is due to
smaller value of P gain. To reduce this increase the proportional gain slowly in
steps of 0.1 or 0.2
This is the final value of P gain because further increment of the P value the process variable will begin to oscillate that
condition is indicated in the figure (12002 LPH).
STEP 2:
18
WWW.VIDYARTHIPLUS.COM
12001 LPH
Steady state
error
290 580
In this condition also we have a steady state error to reduce this further increase the P gain.
STEP 3:
1200 2LPH
19
WWW.VIDYARTHIPLUS.COM
Steady state
error
Note : The final value of P I D gains are also depends on the percentage of Bypass
valve opening. It may vary under the input flow variation.
20
WWW.VIDYARTHIPLUS.COM
The integral response will continuously increase overtime, unless the error is zero. So the effect is
to drive the steady state error is zero. The following diagrams identify this.
Without stop the experiment add the integral time Ti = 0.001 with Kc = 2.5
1200 i
1200 i1
Further increment of Ti from 0.001 min to 0.01 with Kc = 2.5 gives the following result. The increased
value of Ti shows the reduced amplitude of the oscillation and also indicates the further increment of
Ti.
21
WWW.VIDYARTHIPLUS.COM
1200 i2
22
WWW.VIDYARTHIPLUS.COM
16. After the experimentation stop the program by clicking the Red button on the tool bar or go to
menu
OPERATE
STOP.
Result :
The closed loop operation of the Flow Process control using PID controller with LABVIEW was
studied. And also the value of Kc and Ti of the PID controller were found for a set point 1200 LPH.
23
WWW.VIDYARTHIPLUS.COM
Exercise 9
Aim:
To study the auto tuning PID controller using virtual instrumentation (LABVIEW) based DAQ.
Apparatus:
1. Level Process Station Trainer
2. Patch chords
Procedure :
1. To interconnect the Level Process Station circuits as per the patching diagram.
3. Switch ON the key lock and change the selector switch to auto mode.
6. Given the pressure signal to the input of air regulator and observes the I to P input pressure which
should in 1.2 kg per cm2 otherwise adjust the air regulator.
7. Enter the set level of the tank in the front panel of the software program.
8. Switch ON the MCB and start the motor using start switch.
10.Execute the software and view the current level of the tank
11. The PID controller gains and outputs are displayed in the front panel of
the software program.
24
WWW.VIDYARTHIPLUS.COM
25
WWW.VIDYARTHIPLUS.COM
Result :
The Auto tuning PID controller using virtual instrumentation (LABVIEW) based DAQ was studied.
Exercise 10
Aim:
To maintain the constant pressure of a process (Pressure) tank using Auto PID in LABVIEW.
Apparatus:
2. Patch chords
Procedure:
1. To interconnect the Pressure Process Station Trainer as per the patching diagram
26
WWW.VIDYARTHIPLUS.COM
2. Ensure all the precautions in the pneumatic (Pressure) section and follow as per the previous
experiment.
3. Ensure the connection of the process variable to ADC and DAC output to the V to I converter.
4. In the Pressure process station, Switch ON the key and start switch change the selector switch to
Auto mode.
6. Set the value of set Pressure of process (say for example 2Kg/cm2) in the numeric Indicator named
SET PRESSURE in the front panel screen.
RUN
8. We will get a Auto PID tuning Wizard in that select the tuning parameters in four steps such us
Controller type - PID
#Of cycle of Average – 1
Relay amplitude - 0.5
Control design – Fast
10. Another screen will appear in that select accept current value of noise provided in the screen then
click NEXT.
11. After completion of four steps we will get PID gain values, this automatically generated PID gain
values will control and maintain the process corresponding to the set value.
12. The graph indicator displays the set point, process variable PID output status.
27
WWW.VIDYARTHIPLUS.COM
Front panel
BLOCK DIAGRAM
28
WWW.VIDYARTHIPLUS.COM
Experimentation Results :
Pr 2 a
Pr.auto
Note : The final value of P I D gains are also depends on the percentage of Outlet
valve opening. It may also vary under the input Pressure variation. So always keep
the constant input pressure to the process tank.
Result :
The process (Pressure) tank pressure was maintained constantly corresponding to the set value
using Auto PID in LABVIEW and the output was verified with the PC and the Process tank.
29
WWW.VIDYARTHIPLUS.COM
Exercise 11
Aim :
To study the closed loop operation of the Temperature Process control using Auto PID controller
with LABVIEW. Also To find the Kc and Ti value of the PID controller for a particular set point.
Apparatus :
Procedure :
1. To interconnect the Temperature Process Station Trainer as per the patching diagram.
2. Ensure all the precautions and follow as per the previous experiment.
3. Ensure the connection of the process variable to ADC and DAC output to the V to I converter.
7. Set the value of set Temperature rate of process (say for example 100C) using numeric Indicator
named SET TEMPERATURE in the front panel of experiment.
8. To find the final value of P gain Kc and Ti for that increase the Kc value first from minimum to
final value keep other values are zero. After getting P gain increase Ti from step-by-step from
minimum to final value with P gain & keep Td as zero. For a constant input-output process .Td is
not necessary. -Td is mainly used at the rapid change of process variable.
9. At the initial state set the PID GAIN parameters, Proportional gain (Kc) = 1
Integral Time (Ti) =0
Derivative Time (Td) =
0
30
WWW.VIDYARTHIPLUS.COM
FRONT PANEL
EX.NO: 5.3
FRONT PANEL
BLOCK DIAGRAM
31
WWW.VIDYARTHIPLUS.COM
OUTPUT
32
WWW.VIDYARTHIPLUS.COM
Experimentation Result :
33
WWW.VIDYARTHIPLUS.COM
Note : The final value of P I D gains are also depends on the percentage of Outlet
valve opening. It may also vary under the input Cold water variation. So always
keep the constant input Cold water to the Heat Exchanger.
RESULT :
The Process (Temperature) was maintained constantly corresponding to the set value using Auto PID
in LABVIEW and the output was verified with the PC.
34