Renewable and Sustainable Energy Reviews: Namrata Bordoloi, Aashish Sharma, Himanshu Nautiyal, Varun Goel
Renewable and Sustainable Energy Reviews: Namrata Bordoloi, Aashish Sharma, Himanshu Nautiyal, Varun Goel
A R T I C LE I N FO A B S T R A C T
Keywords: Energy saving is a vital element in today's scenario. Earth Air Heat Exchangers (EAHE) is a technique that
Earth Air Heat Exchanger promotes energy savings. EAHE is a non-conventional technique that uses the earth's underground heat for space
Energy saving cooling/heating. In this article, review of different combinations of EAHEs is presented. The review presents an
Geothermal energy apprehensible summary of the previous works on EAHE. The review addresses an elaborated description of the
Sustainable building
analytical and experimental studies on the different combination of EAHE and analyses the results from the
Renewable energy sources
thermal performance. It also consider the environmental aspect in the field of energy saving. It is concluded from
the summary that the design parameters directly or inversely affect the outlet temperature. The result also shows
that the pipe materials does not have much influence on the outlet temperature. In the case of energy saving,
EAHE technology saves more energy that can replace the conventional air conditioning systems. Thus, this
technology can effectively reduce the greenhouse gases and improve the environment.
⁎
Corresponding author.
E-mail address: [email protected] (A. Sharma).
https://doi.org/10.1016/j.rser.2018.03.056
Received 9 June 2017; Received in revised form 15 March 2018; Accepted 17 March 2018
Available online 06 April 2018
1364-0321/ © 2018 Elsevier Ltd. All rights reserved.
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
262
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
concentric cylindrical meshes were used for each pipe to study the in- flow at different inlet temperature. The experiment was concluded that
teraction between several parallel pipes laid at the same depth. One at a depth of 3.7 m and length of 34 m, optimum outlet temperature can
year later Tittelein et al. [24] developed a new numerical method for be achieved. Sikarwar et al. [31] made a conjunction of the EAHE
EAHE. It showed that heat flux entering the pipe is functions of the system with the air conditioner to reduce the energy consumption and
temperature of air flowing through the pipe. To find the outlet tem- to improve the COP. Results showed that under extreme summer and
perature, a heat balance equation is applied. The problem faced using winter seasons, a ground coupled condenser is seen feasible with air
the above-mentioned model was that it took a long time to calculate the conditioner. Chlela et al. [32] has made a conjunction of EAHE with
behaviour of the heat exchanger accurately due to the type of mesh heat recovery balanced ventilation system to investigate the energy
required. Bisoniya et al. [18] has examined the EAHE system in dif- consumption and thermal comfort. It was found that the EAHE system
ferent seasons and found that at lower air velocities there is high reduces the energy consumption and control the CO2 emissions and to
temperature drop irrespective of the seasons. The same was validated ensure good thermal comfort. Nowadays, hybrid EAHE has become one
using a simulation model developed on Computational Fluid Dynamics of the prominent technologies to increase the efficiency of the system.
(CFD). Ralegaonkar et al. [25] has compared EAHE system with con- The EAHE are also classified on the basis of pipe layout in the
ventional system and concluded that EAHE system saves energy up to ground and according to the mode of arrangement [9] as shown in
90% as compared to conventional systems in Nagpur (India). Figs. 4 and 5.
Choudhury et al. [26] has used bamboo and a plaster of soil-cement On the basis of pipe layout, the EAHE classified as:
mixture in place of PVC pipes or mild steel pipe. It was seen that it
reduced the humidity by 30–40% and reduced outlet temperature by ▪ Horizontal/straight Loop
30–35%. Thus, all design parameters (pipe material, the diameter of the ▪ Vertical Looped
pipe, length of pipe, soil characteristics, moisture content, the tem- ▪ Slinky/spiral Looped
perature difference between earth and ambient air etc.) contributes to ▪ Pond/Helical Looped
the performance and to save energy.
This paper considers a subjective approach that aims in under- On the basis of mode of arrangement, EAHE is classified as:
standing the advancements of EAHE technology in different aspects
such as design parameter, boundary conditions, surface conditions etc. ▪ One tube system
for providing thermal comfort. In this article substantial literature of ▪ Parallel tube system
the recent years, reviewed and analysed to understand the effect of
parameters on the performance of these systems. This paper also re- One tube system is not appropriate to meet the requirements of an
views different hybrid systems found in the literature to analyse the air conditioning system in a building. This is because the tube is too
efficiency of these systems with respect to the hybrid systems. This large for the use in generation. Parallel tube systems are used as it re-
paper also attempts to feature the significant data collected from the duces the pressure drop and increases the thermal performance of the
literature of the recent years explicitly. Thus, the paper is structured system.
and designed for providing a systematic information about the ad-
vancements of EAHE technology and providing room for the future
researchers and designers for systematic designing and productive in- 2.1. Advantages and disadvantages of EAHE
stallations in the near future.
The EAHE systems have several advantages over the conventional
2. Classification of EAHE system. They are [8]:
The EAHE systems are designed on the basis of three configurations: 1. Air is used as working fluid.
open loop system and closed loop system and Hybrid system [27,28] 2. It consumes less energy as compared to prevailing conventional
Open loop system: The ambient air is passed through the buried systems.
pipes for pre-heating or pre-cooling of air as shown in Fig. 2. Then the 3. The design is simple hence requires less maintenance and low cost.
air passes through a conventional system to cool down or get warm up 4. Pollution is minimized as no refrigerant or compressors are used in
before entering the space. The air is then passed away through the this system.
ventilation. Woodson et al. [29] has used open loop EAHE design with
PVC pipes having a length of 25 m, diameter 125 mm buried at a depth The disadvantages are:
of 1.5 m. The pipes were laid in the serpentine pattern. It was seen the
air drawn from outside reduces temperature by more than 7.5 °C. The
outdoor temperature varied from 25 °C to 43 °C and the soil tempera-
ture of 30.4 °C remained the same at a depth of 1.5 m.
Closed loop system: Closed loop systems are also known as earth
coupled system as shown in Fig. 3. Air sucked from inlet travels through
a loop of pipes buried underground and extracts the heat from the
ground [25]. The ground loops are arranged either vertically or hor-
izontally. The vertical loops are more expensive than the horizontal
loop. Closed loop is efficient than open loop system. Closed loop system
reduces the problem of humidity.
Hybrid systems: The EAHE is coupled with other heating/cooling
devices such as air conditioner, heaters, solar chimney, solar air heaters
etc. These devices improve the comfort and efficiency of the EAHE
systems. Researchers like Jakhar et al. [30] coupled the Earth to air
heat exchanger with a solar air heating duct. The aim was to evaluate
the heating potential of EAHE with or without solar air heating duct.
TRNSYS 17 was used as the simulation tool. Results were validated with
an experimental setup in Ajmer, India. An evaluation was done for inlet Fig. 2. Open loop system.
263
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
Fig. 3. Closed loop system. 3.1. Research conducted in different parts of the world
264
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
that saturated temperature decreases due to the dew point temperature. The result shows that with increase in depth there was a decrease in
The results also indicate that maximum COP was obtained during temperature amplitude variation as the temperature remains constant
summers in comparison with other two seasons. at 3 m depth. Thus, this configuration causes a decrease of 8 °C in
Goswami et al. [39] has used corrugated plastic pipe for his ex- summers and increase by 2 °C in winters.
perimental setup conducted in Florida. The experiment was conducted Su et al. [42] has developed a computational 1D implicit transient
considering the soil having high moisture content. The operating time convection-diffusion model for air temperature and humidity. The mass
for the EAHE system was 8–12 h/day. A heat pump circulates the air at transfer coefficient is large hd = 1–5 × 10−4 kg/m2 s. On studying the
the outlet. It was observed that if air was spread uniformly throughout results, it was found that the difference of outer temperature and hu-
the tunnel COP was improved by 8%. The open loop tunnel used midity between 2 simulations is very small.
14 kWh of electricity during cooling period and 52 kWh during the Benhammou et al. [43] has studied the thermal performance in the
heating period. Thus, indicate that the EAHE consumes less energy than steady-state and transient condition in Algerian Sahara during July. The
conventional AC. The author also recommends the EAHE for agri- experimental setup is shown in Fig. 7. A new term DF was introduced
cultural buildings. It was also seen that the payback period was ap- by the author which is a function of the length of the buried pipe. The
proximately 20 years. Thus, the use of a multi-pipe system that instead results indicate that as the length increases, DF decreases thus tem-
of using single pipe is more cost-effective. perature at the outlet increases. The study states that the outlet tem-
Vaz et al. [40] has considered an experimental and numerical si- perature is a function of the diameter of the buried pipe. Again, as the
mulation to reduce the consumption of conventional energy. The ex- length is increased, the mean efficiency also increases but COP is de-
periment was set up in Viamas, Brazil. The numerical solution was creased. Also on studying the influence of pipe diameter, as the pipe
solved based on FVM and turbulence was addressed with Reynolds diameter increases, COP decreases. This increase in pipe diameter re-
stress model. The computational modelling was done using GAMBIT duces the pressure losses, in turn, increases the thermal potential but
and FLUENT. The numerical solutions were validated against experi- the cooling potential was reduced resulting in a decrease of COP. DF is
mental results. The temperature variation of three ducts show that proportional to the pipe diameter. Thus, EAHE with larger pipe dia-
while moving along the length, the magnitude of air temperature in the meter has more heat transfer than smaller diameter pipes.table
same soil temperature decreases. There was a difference of 15% with Yang et al. [44] predicted the performance EAHE subjected to
the numerical model proposed during validation. Also, it was found that harmonic thermal environments. The experiment was conducted in
if the depth is more than 2 m, the operating potential for heating and Changqing, China considering the cylindrical coordinate system. Total
cooling was higher by than 8 °C and 4 °C respectively. time for the numerical simulation was t = 1000 s. It was found that
Bojic et al. [35] has investigated the performance of ATEHE for with an increase in depth the outlet temperature decreases. It was ob-
summer and winter season in Athens, Greece. Space was heated by served that the annual fluctuating amplitude decreases with depth and
using a heater during winters and cooled by using an air conditioning attains a certain value when depth exceeds 7 m. Results show that the
system during summers. At ambient temperature of 20 °C result in- outlet temperature initially decreases then increases with increase in
dicates that with an increase in the length of pipe, the energy use ratio radius. The cooling and heating capacity are a function of outlet tem-
for building increases. It was also observed that the energy use ratio in perature and air flow rate. As the flow rate increases the cooling/
summer days was higher than winters. In summers the expenditure for heating capacity increases.
energy was 11 d/MJ s with 10 m long pipe and lowest was 7 d/MJ s on Santamouris et al. [45] performed a parametric analysis performed
the application of 2 pipes for ATEHE. The author suggests that when the on glass greenhouse of 1000 m2 area having 4 buried pipes in Athens,
length of pipe L < 17 m it is better to use 4 pipes instead of 2, thus Greece. TRNSYS software was used simulation tool. A relationship be-
making the ATEHE cheaper. The temperature at the outlet was found 3 tween change in pipe length and the outlet temperature was observed.
times higher in summer than winters. This clearly shows that the The results show that the outlet temperature increases more during July
ATEHE is more energy saving and cheaper in summers than winters. and August but the greenhouse temperature was higher during August
Mihalakakou et al. [20] has predicted the thermal performance in- due to the time lag of the underground temperature at different depths.
side the tube. The model was developed within TRNSYS. The influence Also, due to high convective heat transfer coefficient, an increase in the
of temperature due to a ground surface temperature of the pipe was pipe radius results in high indoor temperature and high outlet tem-
surveyed. The proposed model was validated against the experimental perature. It was observed that the indoor temperature increases with
data and was predicted temperature distribution and the temperature of increase in depth of the pipe but the cooling capacity increases with
the circulated air contributes to the performance of EAHE. increase in depth. The indoor temperature also increases with increase
Silva et al. [41] has modelled a computational model to predict the in velocity of air. Thus, due to increase in mass flow rate, thus the outlet
thermal behaviour of EAHE. The results were checked for every time temperature increases.
step for 2 years. The soil average temperature considered was 29.1 °C Yassine et al. [46] coupled EAHE with a mechanical ventilation
for the entire computation simulation and the temperature variations system for thermal comfort of a typical house conducted in Lebanon.
were checked at every point from 1 to 5 m and were plotted at an outlet. The study aimed at using topical materials such as and Hempcrete and
265
Table 1
Summary of the analytical results held around the world.
Author Place/Year Season Material Length of Diameter of Depth of Temperature range Velocity range Temperature rise/ Variable Others
pipe [m] pipe[m] pipe [m] [°C] [m/s] fall [°C]
N. Bordoloi et al.
Mihalakakou et al. [20] 1994 Summer Plastic 14.8 0.15 1.1 – 10.5 17–33.5 Burial Depth –
Santamouris et al. [45] Athens, Greece, – – 50 0.2 1.5 37–42.3 8 23–36 Diameter of Pipe –
1995
Bojic et al. [35] Athens, Greece, Winter PVC 50 0.15 2.4 8 – 20 Length of pipe –
1996 Summer 16 –
Krarti and Kreider [75] 1995 – – 80 0.20 1.5 19 3.5 – Diameter, velocity of Only mathematical
pipe formulation
Kabashnikov et al. [79] 2000 – – – – – – – – Spacing between the Mathematical model
pipe
Darkwa et al. [80] China, 2010 Summer 50 0.4 1.5–3 – 12 Temperature –
Su et al. [42] 2012 – – 900 – – 19 – 17.6 Error analysis –
Silva et al. [41] 2013 Winter PVC 25.77 0.11 1.0–5.0 – – 2 Burial Depth Increase
Summer 8 Decrease
Vaz et al. [57] Viamas, Brazil, 2014 Summer PVC A:0.11 – 1.6 18.8 – 12 Burial Depth –
Winter B: 0.11 0.6 – –
C: 0.10 0.5 – –
Ahmed et al. [54] Queensland, – PVC 8 0.021 – 21.01 3.4 24.61 Configuration VEPC
Australia, 2014 24.58 Configuration HEPC
23.05 Configuration VEPC
23.85 Configuration HEPC
Ariffin et al. [59] Malaysia, 2014 Summer PVC 30 0.076 1 36.46 0.5 30.345 Material of pipe –
PE 30.231 Material of pipe –
St 30.248 Material of pipe –
Cu 30.25 Material of pipe –
266
Benhammou et al. [61] 2014 Summer PVC – – 2 45 – 44.991 Crossectional area –
44.46 Height of tower –
Xamána et al. [63] Mexico, 2014 Winter – 5 0.15 10 – – 0.5 Configuration Mexico City
5.8 Configuration Merida City
3.3 Configuration Juarez City
Nur et al. [67] Malaysia, 2014 – – – – – 21.9–34.8 – 27.2–30.5 Burial Depth –
Gan et al. [50] UK, 2015 – HDPE – 0.2 1.5 10 2 17.6 – –
Xaman et al. [51] Mexico, 2015 Winter – – – 10 – – 6.3 [Re = 100] Juarez City
12.5 [Re = 100] Merida City
10.2 [Re = 100] Mexico City
Summer – – – – 8.8 [Re = 100] Juarez City
10.2 [Re = 100] Merida City
6.3 [Re = 100] Mexico City
Rodriguez et al. [53] Viamao, Brazil 2015 – PVC 26 – – – – – – –
Niu et al. [68] USA, 2015 – St 57 0.45 3 30 – 16 Soil Temperature –
Niu et al. [69] USA, 2015 – – 57 0.45 3 26–34 – 15 Surface temperature –
13 Diameter of Pipe –
Serageldin et al. [47] 2016 Winter St and Cu 5.5 0.0508 2 14.7 1.0–3.9 18.7 Diameter of Pipe –
19.9 Length of pipe –
19.2 Velocity of pipe –
PVC 19.7 Material of Pipe –
St 19.88 Material of Pipe –
Cu 19.8 Material of Pipe –
(continued on next page)
Renewable and Sustainable Energy Reviews 89 (2018) 261–280
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
energy demand
ASHRAE, the lower limit of air flow rate was 7.5 ACH (air change/hour)
and the upper limit flow rate was 25 ACH. During occupancy, PID
decrease
Others
–
controller was activated during summers when Troom > Tsummer so that
Pressure losses and outer temperature can moderate indoor temperature. The energy and
Diameter of Pipe
Velocity of pipe
Length of pipe
mass balance equation was solved to predict the indoor air temperature
Depth of pipe
Length of pipe
for each zone. The program was developed using MATLAB and was
Variable
Air flow
19.5
7
–
–
developed to predict the temperature profile along the length and time.
Velocity range
ture increases with increase in the outlet temperature. Also as the pipe
1
–
length was increased, the temperature inside the pipe along the length
Temperature range
increases but decreases at the outlet due to heat losses to the sur-
rounding. The CFD simulations indicate that the temperature increases
with depth during winters and vice versa. Also, a parametric study was
conducted to study the design parameters considered in the simulation.
The results of the study show that as the pipe diameter was increased
[°C]
40
40
46
–
for all 3 pipe materials were similar. Thus, the pipe material has less
effect on the performance of EAHE.
7
5
–
Barakat et al. [48] has studied the application of EAHE on the inlet
of a gas turbine as shown in Fig. 8. The thermal performance of EAHE a
Diameter of
0.3
mietta Power Plant, North Carolina. Results showed that the outlet
temperature decreases with the decrease in length. Thus, longer pipe
length provides more heat exchange. It was also seen that as the pipe
Length of
pipe [m]
72
45
76
Thus, longer tube, smaller diameter, placed deep and low inlet air ve-
locity give lower outlet temperature using EAHE increases the power
PVC
PVC
output.
–
Summer
Summer
Season
Winter
periment was conducted in an office for 2 seasons, winter (11 °C, 91%
RH) and summer (34 °C, 77% RH) with an AC of 1 TR was already
Marrakech, 2016
present in the room. A small fan of 30 W was placed to ensure the flow
Algeria, 2016
Place/Year
Italy, 2016
of air through the coil. For the cradle to grave analysis 4 stages were
considered. Stage I: extraction of raw material, Stage II: manufacturing
2016
2017
of heat exchanger material [PVC and MS]. Stage III: installation and use
and Stage IV: disposal at the end of life. The thermal performance was
estimated for both the seasons and results showed that the outlet
Belatrache et al. [77]
Wojtkowiak [83]
Table 1 (continued)
temperature was around 23–24 °C for both seasons. But the outlet hu-
Amanowicz and
PVC = 307 MJ and for MS = 96.4 MJ. Thus, MS pipe can be used as
pipe material from a life cycle energy point of view as MS generated
lesser energy than PVC. In the GHG analysis was it was observed that
267
Table 2
Summary of the experimental results held around the world.
Author Place/Year Season Material Length of Diameter of Depth of Temperature Velocity Temperature Variable Others COP
pipe [m] pipe [m] pipe [m] range [°C] range [m/s] variation [°C]
N. Bordoloi et al.
Goswami et al. Florida, 1993 – – 30.48 0.3048 3.6576 23.89–33.05 – 26.67–28.33 Inlet Temperature – 5.8
[39]
Serres et al. [82] France, 1996 Summer – – – 1.7 – – – – Sensitivity factor –
Winter – analysis
Popiel et al. [74] Poznan, 2001 Summer – – – – – – 15–17 Ground Parking Lawn –
Winter 4 Temperature –
Li et al. [73] Harbin, China, Summer HDPE – 0.0325 47.6 – – 0.75 Ground – –
2006 Temperature
Derbel and Sfax, Tunisia, – PVC 30 0.05 4–6 19–23 6 4–10 Depth of pipe – –
Kanoun [70] 2006
Darkwa et al. [80] China, 2010 Summer 50 0.4 1.5–3 – 12 Temperature – 3.53
Winter – – 10 – 3.2
Ford et al. [38] North east of Iran, Winter PVC and 20 – 4 35–43 0.4–30 – Material of Pipe – 3.5
2011 Summer galvanised mild Soil Temperature – 5.5
steel
Vaz et al. [40] Viamas, Brazil, Summer PVC Duct A: 0.11 – 2 30 – 25 – – –
2011 Winter – Duct B: 0.11 – 2 12.8 – 19 – – –
– – Duct C: 0.10 – 5 – – – – – –
Ozegener et al. [8] Turkey, 2011 – – 47 – 3 18.67 – 21.5 – greenhouse –
temperature
Mongkon et al. Thailand, 2013 Winter Iron 38.5 0.08 1 24.5 9 20.88 – – 2.04
[33] Summer 28.8 21.37 – – 3.56
Monsoon 28.6 26.8 – – 0.77
Benhammou et al. Algerian Sahara, Summer PVC 23.42 0.10–0.30 – 29 2.0–5.0 22.3–23 Diameter of pipe – 0.98–0.67
268
[61] 2013 24 Length of pipe
– – – 27.8 Velocity of pipe – –
Yassine et al. [46] Lebanon, 2013 summer – – – – 28 – 26.88 Mass flow rate – –
winter – – – – 16 – 16.64 – –
Hepbasli et al. Turkey, 2013 Gavanised 47 0.56 – – – – – Exergy analysis
[81]
Chiesa et al. [55] Imola, Italy, 2014 Summer PE 2240 0.25 – – – – – – 19.7
Nur et al. [56] Malaysia, 2014 – – – – – – – 21.5–34.1 Soil type – –
Vaz et al. [57] Viamas, Brazil, Summer PVC A:0.11 – 1.6 18.8 – 12 Burial Depth – –
2014 Winter B: 0.11 0.6 – – – –
C: 0.10 0.5 – – – –
Yu et al. [58] Omaha, USA Winter Culvert Steel 57 0.45 3 12.78 – 21–24 Configuration Passive –
2014 – 20–27.5 Configuration Active –
Hatraf et al. [60] 2014 Summer PVC 60 0.11 – – – – Mass flow rate – –
Li et al. [65] 2014 – Culvert steel 57 0.45 3 – – 14.6 Burial Depth – –
Yang et al. [44] Changqing, – – – – 20 0.5 1.4 Diameter of pipe small change –
China, 2015 15 Length of pipe diameter from 0.05 –
– 13 Mass flow rate to 1 m –
Mohamed et al. Marrakech, 2015 Winter PVC 72 0.15 2.2–3.2 4.2–11 – 16.7–21.2 Time – –
[52] Summer 44.6 24.8 Time – –
Jassim et al. [72] Baghdad, Iraq, Summer – – – – – – 25.3–28.2 Burial Depth 3.43–5.24
2015
(continued on next page)
Renewable and Sustainable Energy Reviews 89 (2018) 261–280
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
Table 3
Thermo-physical properties of materials used.
COP
–
(kg/m3) capacity conductivity
(J/kg K) (W/m K)
La Rochella
Coppera 8933 385 401
decrease
Aluminiuma 2702 903 237
Others
Nancy
–
–
–
–
Galvanised steel [76] – – –
Exergy Analysis Mild Steel [MS]a
Velocity of pipe
(HDPE)b
Irona
–
7
–
a
Thermo-physical properties of Materials at 300 K [77].
range [m/s]
b
Thermo-physical properties of Material at 296 K.
Velocity
1–3.9
1
–
–
Temperature
range [°C]
14.7
11
34
10
46
5
8
–
–
pipe [m]
Depth of
2.43884
2
5
–
–
Diameter of
pipe [m]
0.0381
0.80
–
–
Length of
pipe [m]
14.3256
5.5
45
–
–
Material
PVC
PVC
PVC
–
–
Summer
Summer
summer
Season
Winter
Winter
Winter
Algeria, 2016
Turkey, 2017
France, 2016
Place/Year
up to 288 kWh per month during both seasons. Thus, using AC with
Uddin et al. [49]
Belatrache et al.
Serageldin et al.
[77]
Author
269
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
considered. The simulation of the present study was run on FLUENT for
2 modes continuous and intermittent modes. In continuous mode, the
heat is transferred from the soil to air at any given time. In intermittent
mode, this occurs for a specific time period when the air is preheated Fig. 9. Schematic diagram of VEAHE and HEAHE [54].
only then heat transfer takes place. Simulations were done at different
lengths (10–40 m). There was a rise in temperature from 5 to 6.6 °C for value. Installation 5 shows the superior performance in heating and
ambient air. It was seen that the heat transfer rate decreases day by day cooling. Thus, by increasing the no of ducts and reducing the duct
with a decrease in soil temperature. Thus, with the increase in length diameter constant air volume fraction can be maintained.
rate of heat transfer and temperature rise decreases but overall heat Ahmed et al. [54] has investigated the thermal potential of EAHE by
gain increases. Also, the author found that the thermal and moisture conducting an experiment in Rockhampton, Australia. Using two
interaction between heat exchanger atmosphere and soil has a sig- shipping containers, one connected with Vertical EAHE [VEAHE] and
nificant effect on the rate of heat transfer. other with horizontal EAHE [HEAHE] as shown in Fig. 9. Fans were
Xaman et al. [51] aims to study the transient thermal behaviour of installed to suck the air inside the pipe inlet. 20 PVC corrugated pipes
EAHE in 3 cities of Mexico. A mathematical model was formulated for each configuration. To increase the cooling effect and to cover the
considering conduction heat transfer in the soil, between pipe and soil underground pipes small trees were planted. The schematic diagram of
and flow is laminar in the pipe. The governing equations were solved the setup is given in Fig. 9. A CFD model was formulated considering
using finite volume method. The convective terms were discritised by the flow inside the corrugated pipe to be turbulent. The discretization
the hybrid scheme and diffusive terms were discritised by central dif- was done using PRESTO scheme. The soil temperature analysis was
ference scheme for the mathematical model. For the analysis 3 cities of done for different depths and showed that on a summer day the soil
Mexico are considered (Juarez City, Mexico City and Merida) and four temperature increases with the decrease in depth. For the measure of
Reynolds number are considered (100, 500, 1000 and 1500). It was the performance of HEAHE, the VEAHE was turned off and vice versa.
concluded that the EAHE has a high heating potential for all the Rey- Simulation results show the average room temperature for HEAHE was
nolds number in the cities, Juarez and Merida, as the cities exhibit very slightly larger than VEAHE. Thus, concluded that VEAHE provides more
low temperature during winters. Whereas, EAHE system for Mexico reduction in temperature drop than the HEAHE. So VEAHE is preferable
shows a good heating as well as the cooling potential for only Reynolds to use for Australian weather.
number value at 100. Chiesa et al. [55] aim of the study the results of EAHE in a school
Mohamed et al. [52] has investigated the thermal performance of building of Imola, Italy during winter and summer seasons. A solar wall
EAHE in Marrakech. The EAHE consist of 3 parallel pipes each is con- air collector made of Polyethylene was connected to the EAHE. The
nected with a fan of 44–90 W. The spacing between the pipes was 14 cm energy performance of EAHE system was evaluated by using GAEA
and the vertical parts of the pipe were insulated with 4 cm thick poly- software (Graphische Auslegung von Erdwärme Austauschern). The
styrene. During the operation, only one pipe was monitored and fans of effectiveness of EAHE was found by using Parson and Koehler's ex-
non-monitored pipes were kept off. A numerical model was developed pression. The above expression was used to validate the collected data.
using TRNSYS, which was validated against the data obtained from the A psychometric analysis was performed to predict the inlet, outlet
experimental setup. Results were estimated by taking time as a variable. temperature and relative and absolute humidity. It was seen that during
During the summer season, the temperature drop was nearly 19.8 °C summer there was a significant decrease in the temperature with in-
which was more than the winter season. Thus, EAHE system is more crease in the relative humidity. The absolute humidity increases when
efficient during the summer season. the dew point temperature is reached in the tubes. During winters,
Rodrigues et al. [53] employed constructional design for EAHE to there was a remarkable increase in temperature, so outlet air requires
obtain the highest thermal potential. The numerical simulation was treatment to reach it to indoor conditions. An energy balance was
performed using Ansys FLUENT. The computational domains were de- considered to calculate the rate of heat transfer. The COP of the EAHE
veloped in FLUENT and discretized in Gambit. The numerical simula- was also calculated by considering the pressure loss of the system. The
tion was done as a function of time. The validation was done against an monitored results were compared with the results already present in the
experimental setup constructed in 2007. The constructional design was literature. It was found that EAHE is an effective system which depends
created by Adrian Bejan in 1997. In this experiment, 5 different con- on the design parameters.
figurations of EAHE were evaluated. This design is applied by means of Nur et al. [56] has studied the capacity of Malaysian soil for the
volume fraction parameters to find the optimal installation. For in- application of EAHE. This research aims to predict the soil temperature
stallation I, the high thermal potential was reached during December. for different soil surface condition. The experiment was set up at
In Installation 2, a stable behaviour of thermal potential was seen. In Gombak campus of International Islamic University, Malaysia. Three
this installation, the horizontal spacing of pipe was increased so the different soil surface conditions were considered. The soil condition
thermal potential was also increased. In installation 3, the concept of were: Bare and short grass, Sheltered by layers of recycled timber
volume fraction was considered. The highest value of thermal potential palette and Insulated layers of used tyres. A parametric analysis esti-
was seen in May, June, July, October, November and December. There mates the soil temperature at an optimum depth was done to find the
was no significant change in thermal potential seen during January and appropriate soil surface condition. The simulation for the present study
February. In installation 4, Thermal potential has an intermediate was conducted in Energy Plus software. The soil temperature was
270
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
271
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
the efficiency but also the sustainability of EAHE system and has lower
emission in comparison to conventional systems.
Nur et al. [67] investigated the soil temperature at a different depth
up to 5 m to estimate the potential of EAHE in Malaysia. The site lo-
cation for the experiment was International Islamic University campus
in Malaysia which was generally exposed to solar radiation. The soil
type is sandy and covered with short grass. The study was carried out in
2 phases: in the first phase temperature measured up to 5 m and other
the second phase focuses more on a temperature at shallow depths. It
was seen that there was a little change in temperature for shallow
depths. The results indicate that on the application of EAHE in a
building is possible only if the air temperature increases beyond 34 °C.
Also, the optimum temperature for the undisturbed soil temperature
was at a depth of 1 m.
Niu et al. [68] used the transient control volume method to study
2D heat transfer mechanism. The computational domain was divided
Fig. 11. Schematic of EAHE with thermal insulation [63]. into control units and the thermal balance was applied. A self-recovery
temperature analysis was done using continuous and intermittent
modes. The data was validated against an experimental set up already
to the inside of the tower and other end was connected to conveyor box.
present in Omaha, USA. The measurements were done to record the
A planned monitoring system was also installed to monitor the results
cooling capacity of the system. The simulations were done using MA-
whether the non-zero objective is reached or not. In this study only the
TLAB 8. Results indicate that the outlet temperature increases when soil
systems were installed, the results were not monitored. Three types of
air temperature was increased. It was observed that there was a good
soil have been used to cover the pipes: scoriaceous lava, a mixture of
agreement with the experimental results during validation. It was ob-
fine sand and clay and topsoil.
served that the soil temperature near the tube fluctuated more the far
Li et al. [65] studied a Hybrid EAHE coupled with solar chimney.
one. Thus, the temperature difference between soil and air is higher
The schematic diagram for the experimental set up is shown in Fig. 12.
than the outlet. To recover the lost energy, night time is the time for
The solar collector is used to connect the solar chimney to the building.
recovery. Two modes were considered to analyse the recovery analysis:
The system consists of an EAHE pipe with one end exposed to the
continuous modes and intermittent mode. In intermittent mode, the soil
outside and the other end to inner side. The experimental setup was
temperature was recovered during non-working time. The recovery
made on a testing facility of the University of Nebraska. The solar
ability decreases with time and distance. In continuous mode as the
chimney was designed in such a way that the pressure losses from EAHE
supply air temperature increases the recovery temperature varies be-
were compensated. The schematic diagram of the setup is given in
tween 19.5 and 21.7 °C.
Fig. 12. The parameters examined are time and date, relative humidity
Niu et al. [69] predicted the cooling capacity of EAHE using re-
(%),supply air, supply airflow rate (m3/s), the indoor relative humidity
gression analysis. The study considers both heat and mass transfer be-
(%), outdoor relative humidity (%), solar collector airflow rate (m3/s),
tween tube and air. A mathematical model was formulated to estimate
supply air temperature (°C), average indoor temperature (°C) and out-
the underground soil temperature. The results were validated with re-
door air temperature (°C). The underground soil temperature was
sults already present in a test facility. For the heat transfer analysis,
monitored at different depths. It was seen that fewer temperature
sensible and latent heat transfer were considered. A simulation model
fluctuations were observed for deeper depth. The maximum tempera-
was developed in MATLAB 8. The data was validated with the experi-
ture difference was observed at 2.9 m depth.
mental data already present in a test facility in Omaha, USA. The results
Mendez et al. [66] studied the uses of PID controller, which is
when compared show a good agreement with the present data. Thus,
generally used for thermal processes. This study shows the usage of PID
the formulated equation for soil temperature can be used. For the
in improving the performance of EAHE than conventional heat ex-
EAHE, there was a rise in outlet temperature. To predict the soil tem-
change. Simulation of PID was created in LabVIEW. The results show
perature, temperature profiles were checked along the length. The re-
that PID controllers show better control of temperature in comparison
sults indicate that as the surface temperature increases, the outlet
with the conventional controller. The PID controller reduces energy
temperature increases. Also as the tube diameter increases, there is a
consumptions after a steady temperature is achieved. The average en-
decrease in the outlet temperature. Cooling capacity for the system was
ergy consumption on energy consumption was 0.017 kWh. There was
also investigated. The cooling capacity increases with increase in the
about 87% energy saved in comparison to conventional controllers. A
inlet air temperature. On calculating the cooling capacity sensible
simulation runs on PID controller, results show that energy consump-
cooling capacity was 0.31 kW/°C and latent cooling capacity was
tion can be reduced if a PID controller is applied. It not only increases
0.7 kW/°C. Thus, the total cooling capacity was 1.1 kW/°C.
Derbel and Kanoun [70] investigated the ground temperature at
different depths in Tunisia. A thermal model was developed considering
all the properties of the soil and other meteorological factors. In this
study different thermal conductivities of the soil were tested to un-
derstand the physical properties of the soil. A model of EAHE system
was developed for estimating the heating and cooling loads. It was
observed that as the burial length as increases the energy load of the
system also increases. Further, it was also observed that as the pipe
length of the system increases, the thermal efficiency of the system also
increases. The results of the model were validated against an experi-
mental setup [71]. Thus it was concluded that at a certain burial depth
the ground temperature becomes stable.
Jassim et al. [72] investigated the performance of wind catcher in
Fig. 12. Schematic diagram of EAHE coupled to solar chimney [65]. EAHE to reduce the energy consumption in hot dry areas like Iraq. Wind
272
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
Catcher is a device designed for pulling and expelling the air. Generally, Krarti and Kreider [75] studied the energy performance of EATHEs
wind catcher towers are connected to a building to cool the building. by developing a simplified analytical model. It was assumed after some
The thermal performance was studied in two phases. Phase 1: The days of operation that the system reaches periodic and quasi-steady
temperature was measured using data loggers. Phase 2: Simulation is state behaviour. Also, the model was valid when condensation occur-
done using CFD. The model was a 2-storied building with a wind ring inside the tunnel. The heating and cooling effect of the system were
catcher of 2 m2 area. A CFD model was formulated and was validated also studied. For the study of hydraulic diameter and air flow rate, a
against the experimental setup. Results indicate that a higher fluctua- parametric model was developed. It was found that increase in pipe
tion in temperature was seen in August. But these fluctuations were diameter is preferable for obtaining a suitable air flow rate.
decreased in June, but the relative humidity was increased. The results Khabbaz et al. [76] in Marrakech (Morocco) introduced EATHE
also indicate that the soil temperature also depends on the soil type and system for the cooling of a residential building located. The system was
water table. It was observed that if the wind catcher space was in- made of three parallel PVC pipes of length 72 m each and a diameter
creased in phase 1, the thermal comfort was not achieved. But in phase 15 cm which were buried at a depth of 2.2–3.2 m. It was assumed that
2 if space is increased the temperature is reduced by 18 °C. It was also the system produces an air temperature of 25 °C with an outside tem-
observed that when the velocity was increased, the COP was increased perature of 40 °C. It was found that there was an exponential drop in the
to 5.24. Thus, this new design for self-cooling reduces energy con- reduction of annual and daily air temperature amplitudes which was a
sumption. function of pipe length and the characteristic length. Again, simulations
Li et al. [73] constructed an experiment in Harbin area of an air- for this system were also run for EAHE system in TRNSYS. There was
conditioning system for cold areas which directly supplies the cold good agreement between the experimental and simulated results. The
energy stored in the ground. The operation time was in summer in simulated results indicate that there was a maximum temperature drop
2006. Performance parameters such as the average heat rejection rate of 19.5 °C. Thus it was concluded that he EAHE system is beneficial to
unit depth of borehole and cooling seasonal performance factor (CSPF) use in Marrakech (Morocco) climatic conditions.
were investigated. The system consists of a ground heat exchanger and Belatrache et al. [77] studied the feasibility of EAHE in the climate
indoor fan coil. The circulating fluid considered was water. To reduce conditions of Algeria using a numerical simulation model. In this ana-
the thermal influence of the building on the ground, the borehole was lysis, the author calculated the appropriate depth of the buried depth of
made 7 m exterior to the walls. The heat rejection rate per unit depth of the tubes by taking considering the physical properties of the soil. The
borehole ranged between 40 and 100 W/m. The cooling characteristics analysis was done on the basis of air flow rate, length and radius of the
are divided daily cooling characteristics and into seasonal cooling pipe. It was observed from the analysis that the maximum cooling ca-
characteristics. On daily basis, maximum cooling capacity occurred on pacity of the system was 1.755 kWh. Thus it was concluded from the
the 2nd day. The ground temperature rises rapidly initially but becomes results that this EAHE system is quite feasible for small-scale residential
stable at a later stage. There was an increase of cooling 0.75 °C on last buildings.
45 days. On an hourly basis, maximum cooling capacity occurred on the Raczkowski et al. [78] investigated the EAHE system for a ventila-
first hour and minimum cooling capacity occurred on the tenth hour tion system in Poland using CFD simulations. The work focuses on the
having a ratio 0.81. Thus, the increase in ground temperature in in- investigation of temperature outlet dependency on fresh air after deli-
itially low at different depth and gradually becomes faster. vering to the mechanical system. The main focus of the work was to
Chlela et al. [32] carried out a numerical study to evaluate the evaluate an efficient passive technique to enhance the energy perfor-
energy performance of two different ventilation system and earth air mance and to maintain the standard with Polish National Energy
heat exchanger for three French climates. The building considered is a Conservation Agency (NAPE). The boundary condition for the analysis
dwelling called "Mozart" having floor area 101 m2. The simulations was considered with respect to the climatic condition. For simulations,
were carried out for three French cities: Nancy (5 °C), La Rochelle (8 °C) control volume method was used. The results were observed for dif-
and Nice (10 °C). Two ventilation systems were considered: mechanical ferent outlet temperature. It was observed that when Tin = − 24 °C the
extract ventilation system and balanced ventilation system. The soil simulated Tout = − 3.58 °C and the standard set by NAPE was
type proposed was clay. The thermal behaviour of the building was − 3.58 °C, almost similar variation were observed for different tem-
carried out using SIMBAD. Yearly simulations were done to evaluate peratures. A regression analysis of the inlet and outlet temperature was
the thermal performance of EAHE and balanced ventilation system for considered. On analysing the results a higher slope for CFD simulation
all three cities. The heating demands of the ventilation system for the was observed with respect to the NAPE standard. Thus confirming its
three cities were evaluated and there was a reduction in heating de- inferiority with respect to other conditions.
mand. The heating demand for the house in Nice was 13.2 kWh/m2, Kalashnikov et al. [79] studied the efficiency of EAHE system con-
which was almost equal to the annual heating demand. There was a sidering the spacing of the tubes as a variable. The other variables such
decrease in heating demand for EAHE with the mechanical extract as length, diameter, burial depth and air flow rate were also studied.
ventilation system. Thus, the balanced ventilation with heat recovery The thermal power was calculated for the only winter season. The re-
unit is more efficient than EAHE. During the summer season, the heat sults were independent of the tube diameter but the reduction of the
exchanger of the balanced system was bypassed. The cooling potential spacing between the tubes causes a loss of power by 5–15% depending
for the 3 cities was evaluated on 3 modes. Thus, EAHE has a good on the air flow rate, while the reduction of the spacing to 1 m resulted
potential for cooling. in a loss of 10–25% as compared to the case of an infinite spacing be-
Popiel et al. [74] in Poznan, studied the ground temperature by tween the tubes. Thus it was concluded that the efficiency of the system
considering two different ground surfaces i.e. car park and lawn, at two greatly depends on the orientation and spacing between the tubes along
different soil depths. It was found that the subsoil temperature below with other variables.
1 m for the lawn was about 4 °C lower than the car park. Again, when Darkwa et al. [80] installed an EAHE system in the Center for
the subsoil temperature for the conditions was not in the desirable Sustainable Energy Technologies (CSET) at the University of Not-
range (18–30 °C) for thermal comfort, the conditions were improved to tingham to investigate the effectiveness of this system. The study also
bring the temperature into the desirable heating/cooling temperature examined the other factors that might affect the performance of the
range. A short variation in temperature was observed for a depth of system in hot and humid climate. It was concluded from the results that
0–1 m. It was also observed that during summers the ground tempera- this system was effectively used in building for energy savings. It was
ture in the car park was 4 °C higher than the lawn. Also, similar var- also observed that during the month of March and July there was a COP
iations were observed in winters. Thus the author concludes that a of 3.2 and 3.53 respectively. Thus, the EAHE system can be used ef-
temperature variation is necessary for heat loss calculations. fectively in such a climate during both the seasons.
273
N. Bordoloi et al.
Table 4
Summary of analytical results conducted in India.
Author Place/Year Season Material Length of pipe Diameter of pipe Depth of pipe Temperature range Velocity range Temperature rise/fall Variable Others
[m] [m] [m] [°C] [m/s] [°C]
Kumar et al. [90] Mathura, India, – – 80 – – 23.8–27.9 4.9 20.2 Length of pipe –
2003 2.15 Mass flow rate –
25.3 Radius of Pipe –
Ghosal et al. [11] New Delhi, India, Summer PVC 39 0.06 ≤4 39–45 – 34–39 Length of pipe –
2003 Winter 4.0–9.0 7.0–8.0 Length of pipe –
Bansal et al. [86] Ajmer, India, 2009 Winter MS 23.42 0.15 2.7 8.0–12.7 2.0–5.0 12.8 Velocity of pipe –
PVC 12.5 Velocity of pipe –
Bansal et al. [17] Ajmer, India, 2009 Summer MS 23.42 0.15 2.7 8.0–12.7 2.0–5.0 12.7 Velocity of pipe –
PVC 10.3 Velocity of pipe –
Bisoniya et al. [18] Bhopal, India, 2014 Summer PVC 9.114 0.1016 2 25–40 0.4–25 12.9–11.3 Velocity of pipe –
Bisoniya et al. [101] Bhopal, India, 2014 Summer – – – – – – – No results –
monitored
Mathur et al. [102] Jaipur, India, 2014 HDPE 40 0.1 27 5 46.7–28.8 Soil Type Soil J
46.2–28.8 Soil Type Soil F
46.2–28.8 Soil Type Soil A
274
Chaturvedi et al. Bhopal, India, 2015 Summer GI 9 0.05 2.0–3.0 – – – Material of Pipe –
[28]
Thakur et al. [92] India, 2015 Summer Al 60 0.1 – 46 3.0–9.0 25.5 Configuration Finned
Summer 28.3 Configuration Unfinned
Singh et al. [91] Punjab, India 2015 Winter GI – 0.1524 3.048 – 16.7 29.3 Crossectional area –
Summer – – –
Khandelwal et al. Jaipur, India, 2015 – PVC – 0.1524 4 – 4 11.5 – mathematical model
[98]
Mathur et al. [97] Jaipur, India, 2015 – HDPE – – – 26.39 – 27.27 Burial Depth –
Singh et al. [13] Chandigarh, India, – – – – – – – – – –
2015
Kaushal et al. [99] India, 2015 – – 3 0.1 – 7 1.0–3.0 21–24 Configuration Hybrid EAHE
12 Configuration EAHE
Jakhar et al. [95] Rajasthan, India, – HDPE 90 0.025 – 90 – ± 1.61 Material of pipe –
2016 GI Material of pipe –
St Material of pipe –
HDPE 22.5–27.7 Burial Depth –
31.9 Length of pipe –
31.8 Diameter of Pipe –
Renewable and Sustainable Energy Reviews 89 (2018) 261–280
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
6.4–3.6
2.8–3.1
COP
1.54
4.57
pled with a PV system. The coupled system was installed at the Solar
7.9
2.1
2.9
1.8
–
–
–
–
–
–
Energy Institute, Ege University, Izmir, Turkey; the PV system powered
the fan connected to the EATHE system. In this study, an exergy ana-
Mode III
Mode II
Others
Mode I
ciency decreased when the reference point was changed from 0 to 18 °C.
rooms
Again, the sustainability index value was decreased from 1.24 to 1.01
–
–
–
–
–
–
with the increase in its reference temperature. Thus it was concluded
Velocity of pipe
Velocity of pipe
Velocity of pipe
Velocity of pipe
Configuration that both the energy as well as exergy efficiency of the system is of
Configuration
Configuration
Burial Depth
equal importance. The author also suggests for further work on the cost
Variable
Time
17.7–21.1
17.5–22.3
17.6–24.1
24.3–24.7
24.3–32.5
8.3–12.4
25–26
20–22
different diameters. During winters, air coming from the ventilated roof
25.8
cause to flow through the EATHE before being blown into the building.
–
–
While in summer, the air was directly extracted from the ventilated roof
range [m/s]
2.5,3.5,5
4.1–11.6
13
5
–
The pressure losses and airflow for each pipe were examined. It was
Temperature range
observed that the airflow for each pipe was not equal. This study uses 5
parallel pipes which were connected to the main inlet and outlet pipe at
its ends. On comparing the simulated results with the experimental
13.9–20.4
results there was a deviation of less than 10% in case of pressure losses
37.5–46
35–42
34–44
15–18
and a discrepancy of 15% for smaller air flow rates. It was concluded
[°C]
45
that air flow division for the pipes may not be equal thus non-uni-
4
–
–
formity of air flow within the pipes can be taken into account for es-
pipe [m]
Depth of
1.5
3.7
3.7
4
2
–
data was collected for last 7 years on hourly basis at Solar Energy In-
pipe [m]
0.05
0.1
–
was observed that during the heating period the inlet temperature
varied between 3 and 17.1 °C and outlet temperature between 7 and
Length of
pipe [m]
24 °C. It was also observed that the mean exergy efficiency of EAHE was
55% with an exergy rate 5.82 kW.
76.5
78
17
60
11
60
Ascione et al. [85] studies the Net Zero Energy buildings [NZEB],
–
galvanised steel
PVC
PVC
PVC
PVC
Summer
Summer
Summer
Summer
Season
Winter
Winter
Rainy
Bhopal, India,
India, 2013
India, 2014
Delhi 2001
Arunachal
2013
2016
ergy use per floor (PE) for summer (PEc) and for winter (PEh). Thus,
during summers PEc reduces the increase in airflow and vice-versa in
Misra et al. [100]
Thanu et al. [71]
winters. The annual electricity demand for MVS was 35,455 kWh and
for EAHE+MVS, the demand was 31,200 kWh. But the PV panels
[26]
Author
275
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
higher number of PV must be sued to compensate the demand than the experimental data and simulated data at different velocities; there was
other case. a deviation of 0–8.86% of the experimental results. It was observed that
the maximum hourly cooling energy gain was 1.8 MWh at 5 m/s. Thus,
3.2. Research conducted in India it was concluded that for effective reduction in cooling load EAHE can
be used in buildings during summer season.
The climate of India ranges from tropical south to the temperate Dubey et al. [89] considered an open loop EAHE having 3 horizontal
north. The climate of India is influenced by The Himalaya and the Thar pipes connected in parallel to the find cooling rate during the summer
Desert. With the help of geothermal energy, about 6.5% of electricity season. The pipes were in parallel connection with a common intake
generation is achieved [36], but India is at the nascent stage for power and exhaust manifold of the air passage. Results indicate that there was
generation using geothermal energy. The Geological Survey of India a decrease in the temperature and COP of the system as the velocity was
reported that there are about 340 geothermal hot springs [36] that increased. Thus, the velocity of air flow affects the performance of the
conserve geothermal energy in India. The Indian market has not been system.
much influenced by EAHE. Chaturvedi et al. [28] studied the performance of EAHE in Bhopal
In India, many types of research have been initiated to study the having multiple pipes in parallel during the summer season. It was seen
potential of buried pipes. The parameters for the studies are given in that material of the pipe has no effect on the output. The result shows
Tables 4, 5. Ghosal et al. [11] conducted an analytical study in New that if the length of the pipe is small and blower voltage is high, the
Delhi, India. The pipes were arranged in a serpentine manner with mass temperature difference at inlet and outlet can be low. Thus, it can be
flow rate 100 kg/h. The performance was evaluated on the basis length concluded that material of pipe does not affect the performance of the
of pipe and air temperature inside the greenhouse for both the seasons. system.
The results indicate that with an increase in the length of the buried Kumar et al. [90] studied the numerical techniques of finite differ-
pipes the air temperature inside greenhouse increases in winters and ence method and FFT (MATLAB) model. The results were validated
decreases in summers. Thus, concluded that performance of the EAHE is against the experimental data of a similar tunnel in Mathura (India). It
a function of length and temperature of the greenhouse. was observed that when the length and flow rate was decreased the
Bansal et al. [86] developed a model in FLUENT to reduce heating outlet temperature increases and decreases respectively. Also, when the
loads in a building. A transient and implicit model based on CFD was radius of the pipe was increased, the outlet temperature was increased
developed and was validated against a setup in Ajmer (winters). Two but convective heat transfer coefficient is lowered. Thus, can be con-
types of materials were considered Mild steel and PVC. CFD simulations cluded that longer tunnel length is efficient for more cooling energy
were performed in FLUENT 6.3. Result shows that as the air velocity saving. Results indicate that the cooling potential of the setup was
increases the outlet temperature decreases due to increase in heat 456kWh. By increasing the pipe radius above a critical value, the outlet
transfer coefficient of the materials. On keeping the same input con- temperature can be increased which affects the heating/cooling po-
ditions for both the materials it was seen that there was a small tem- tential. Thus, it was concluded that by using larger diameter pipe large
perature difference at the outlet of the pipe due to a high coefficient of outlet temperature can be achieved.
friction. It can be concluded that convective heat transfer plays an Singh et al. [91] designed a metallic EAHE to determine the heating
important role than conductive heat transfer. It can also be concluded and cooling loads of a classroom. The ducts were laid in a zigzag pattern
that the performance of EAHE does not depend on the material of the having a combination of PVC and Iron, a square cross-section for the
pipe. Results show that EAHE saves 38% of electricity in comparison to metallic pipe and round cross section for PVC. The cooling load was
an electric heater having an efficiency of 95%. Thus, the material of the found using CLTD method. The main duct was divided into 3 parts; inlet
pipe is not of much concern so a cheaper material can be used. and outlet were made of PVC and remaining sections were made of
Bansal et al. [87] conducted the same experiment for summer galvanised iron. The simulations were run in ANSYS. The result shows
season considering the same input parameters. When comparison was that there was a change in the temperature profile at the outlet of the
made, there was a variation of 0–11.4% with the experimental results. metallic section. The air in the central portion is warmer than the air
It was seen that as the air velocity increases the outlet temperature near the boundary layer by 2 °C as the inner part gets less convected.
increases. For both the materials a very small temperature difference at After all the variables were taken into account, final layout of the earth-
the outlet of the pipe. The maximum hourly energy gain was 3.1 MWh, air tunnel was made through CATIA software. The prototype was run in
observed at 5 m/s, in the same velocity range the COP obtained was different seasons. The prototype showed a maximum C.O.P of 3.9 in the
1.9–2.9. Thus, the material of pipe does not influence the performance summer season which was more than COP of 2.1 in the winter season. It
of EAHE. was seen that the maximum cooling effect of the prototype was 2.6 kW.
Chel et al. [88] formulated a thermal model of vault roof building Thus, it can be concluded that the EAHE is more useful during summer
coupled with EAHE solved by Ranga Kutta approach. The adobe house season than in winter season for the climate of Punjab.
has a room air temperature higher than ambient air in winters and Thakur et al. [92] developed a model in Pro–e to study the effect of
lowers than ambient temperature in summers by 5–15 °C which in- a finned model of EAHE. This was compared with a finless model of
creases the energy-saving potential. The analysis of the adobe house EAHE. Meshing tool used was ANSYS Workbench, complex heat
was done under 3 conditions (Before the renovation, after renovation, transfer and air flow process studied using FLUENT. The computational
with EAHE for 6 rooms). The total energy saving potential obtained model validated against an experimental study conducted by Misra
between 4183 and 10,321 kWh/year for all three cases and the CO2 [93]. The simulations were run at different pipe inlet velocities. On
emission ranged from 7 to 16 t/year. The average seasonal energy ef- comparing the data with the existing experimental data, it was seen that
ficient ratio for heating was 1.8 and for winters were 2.9. Thus, it can be there was a variation of 7.64%. The simulation results for finned and
concluded that EAHE is more efficient for heating than for cooling. finless EAHE system were studied. From the results, it was concluded
Bisoniya et al. [18] investigated the cooling demand in a building that on an addition of fins, the system to work efficiently even if the soil
for a hot and dry climate of Bhopal considering quasi-steady state has poor thermal conductivity. Also, concluded that smaller length of
model, developed in CFX 12.0. The simulated results were validated pipes can perform satisfactorily thus lowering the initial cost.
against an experimental set up in Bhopal. The observations were made Soni et al. [94] conducted an experiment to reduce the power
for different flow velocities assuming Tsurface = Tambient = Tinlet to consumption of a 1.5 TR air conditioner coupled to EAHE. For the ex-
evaluate the total hourly energy gain. Results indicate that the tem- periment, three different arrangements were considered. The economic
perature drop was faster at the initial length of the pipe and became analysis techniques such as discounted payback period, simple payback
moderate for rest of the length. Also, a comparison was made with period, etc. were also evaluated. From the arrangements, it was
276
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
observed that in arrangement II, the condenser tube temperature was The heating capacity and COP for mode II was 665.52 kW and 1.54, for
reduced by 10% than the arrangement III condenser tube temperature. mode III heating capacity was increased to 1976.02 kW and COP 4.57.
The power consumption in all 3 arrangements was also calculated and a Thus, it was concluded that for same power consumption the solar
comparison was with the base mode. The results indicate that the ar- heating duct increases the heating capacity as well as the COP of the
rangement III was useful in terms of power reduction during summer system.
days. At a velocity range between 5 and 7 m/s, EAHE arrangement gave Singh et al. [13] studied Chandigarh city for the installation of
optimum results. For the energy matrices, the EPBT for arrangement II EAHE. Chandigarh is situated at latitude 30.74°N, longitude 76.79°E
is 604.3 days and arrangement III is 362.6 days and the CO2 emissions and at an altitude of 321 m. It receives a rainfall of 1110.7 mm. The
for arrangement II are 5425.92 kg and arrangement III is 9043.2 kg. cooling period is from April to October and heating period is from
Thus, arrangement II is profitable to use in order to reduce the CO2 November to March. The soil type is sandy soil type in Chandigarh up to
emissions. a depth of 3 m with a water table of 5–15 m. The electricity demand in
Jakhar et al. [95] estimated the performance of EAHE with and summers and winters is 350 MW but available is only 324 MW. The soil
without Solar air heating duct (SAHD) during the winter season and diffusivity varies from 0.084 to 0.14 m2/day. Thus, Chandigarh city is
was formulated using TRNSYS 17. The results were validated against an suitable for the installation of EAHE.
experimental setup in Ajmer, India. For the solar air heating purpose, Khandelwal et al. [98] studied heating and cooling load of a Library
galvanised iron ducts were used. In the study, three cases were con- of MNIT, Jaipur. A simple excel model was developed. The library
sidered to investigate the performance of EAHE. The results show that consists of 4 rooms conditioned with split AC to which EAHE was
EAHE coupled with SAHD increases the outlet by 6–9 °C when the air connected. In the cooling load estimation, totally sensible and latent
velocity was varied. Also, it was observed that the heating capacity of heat was considered including infiltration load. During a survey, the
EAHE was refined when coupled with solar air heating duct. In the error comfort temperature was found to be 28.6 °C. Results show the max-
analysis, it was observed that there was an error of 3.9%. imum temperature drop was 11.5 °C and length of the pipe was 72 m. In
Jakhar et al. [96] investigated the operating temperature of Pho- a cost analysis result, Rs. 1,149,380 was estimated for its installation.
tovoltaic panels (PV) which was responsible for lifespan and perfor- The cooling load was 77 kW including ventilation load and the cooling
mance using TRNSYS v17.0. Water was used as operating fluid. The capacity of EAHE was 60,781 kW.
simulated system was compared with the prevailing ones in the lit- Kaushal et al. [99] used FVM to investigate the thermal potential of
erature for a given cooling setup of Concentrating Photovoltaic (CPV). hybrid EAHE. This study also used response surface method is used to
In the study three types of pipes material considered for the study. The optimise the process parameters using Ansys Fluent. The numerical
temperatures along the depth for all 3 pipes were evaluated keeping the results are compared to individual EAHE. The EAHE was coupled with a
pipe length, flow rate, diameter constant. On taking the pipe material solar air heater. The schematic diagram of the setup is given in Fig. 13.
into consideration it was observed that there was a temperature var- The temperature contours along the length were studied which shows
iation 1.61 °C. For the analysis, HDPE was considered as it cheaper. It that temperature increases with increase in length. The results of only
was observed that as the depth increases the average temperature also EAHE were validated against the data reported by Bansal [86]. The
increases. Thus, it was concluded that at 3.5 m was considered as op- results of HEAHE were validated against the experiment set up. Re-
timum depth for further simulation. Again, it can also be concluded that sponse surface methodology uses f test and ANOVA technique to esti-
the pipe material does not affect the performance of EAHE. But when mate the factors affecting the input variables. Results show that the
the mass flow rate was increased the outlet temperature, Reynolds potential or solar heat gain decreases with increase in temperature.
number and Nusselt number was increased. Thus, mass flow rate affects Results show that for hybrid EAHE shows maximum temperature drop.
the outlet temperature. Thus, HEAHE shows good performance than EAHE.
Mathur et al. [97] focuses on the thermal saturation of soil and the Thanu et al. [71] investigated the thermal performance of the
self-recovery ability of the soil between different (continuous and in- EATHEs in Gulmohar farmhouse, Gurgaon, India. The results were
termittent) modes of EAHE system which was set up in MNIT Jaipur, taken a single pass that was used to condition 3 rooms in the house. The
India. The numerical simulations were performed using Ansys FLUENT performance of the system was evaluated before and after the con-
v14.5. It was observed that there was a good acceptance between the struction. After the construction was complete the performance of
measured and simulated results. After the validation of the CFD model, EAHE in one room as evaluated. The COP for the summer, monsoon and
a comprehensive analysis was done to analyse the impact the soil winter seasons is 7.9, 1.9 and 2.1 respectively. It was concluded that
temperature on EAHE. Results indicate that the soil temperature along EATHE can installed for achieving thermal comfort.
the length decreases. Thus, ambient air temperature is also an im- Misra et al. [100] emphasis on the use of low-cost material like PVC
portant factor in soil temperature. In the study of heat penetrating the to the cooling potential. This focuses on the design of the duct system.
soil, the temperature profile in the radial direction was simulated. The The experimental setup was made as a prototype model where the base
result shows that the soil temperature decreases as it moves away from of the model was a metal tray. It was observed that the minimum EER
the EAHE surface but the soil temperature around the pipe varies with for the system was 3.78 which were almost equal to an energy star 5
ambient air temperature. This effect is analysed by considering the rating. Thus, EAHE also consumes less energy than convention systems.
continuous and intermittent operation modes. In continuous operation, This study suggests that the prototype model can be used in small
ambient temperature goes down and cools the heated subsoil which
helps to revive its cooling ability. In intermittent operation mode
through the heat conduction among the soil layers, the soil temp can be
recovered during non-working hours. The self-recovery temperature for
continuous operation was more than intermittent operation mode.
Jakhar et al. [30] predicted the thermal performance of EAHE when
coupled with solar air heating duct in Ajmer where the temperature
ranges from 15 to 18 °C in winters. The inlet of solar air heating duct is
connected to the outlet of the EAHE. In this study, three modes were
considered to estimate the thermal performance. The 3 modes were
evaluated in four periods 14–16 January, 26–28 January, 1–3 February
and 13–15 February. The results show that by using EAHE with the
solar heating duct increases temperature 1.1–3.5 °C inside the room. Fig. 13. Schematic diagram of EAHE with SAHD [99].
277
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
houses which can maintain the room temperature lower than outside 4. Discussions
temperature during the summer season. The author recommends the
EAHE to use domestically in houses to achieve thermal comfort. Thus, The results of various studies conducted are shown in Tables 1, 5. It
EAHE is an energy efficient system when compared with an energy star has been analysed from the tables that results mainly focus on the
rating system. variation of outlet temperature. It should be noted that according to the
Bisoniya et al. [101] developed a model to study the different design working principle of EAHE the outlet temperature depends on the lo-
parameters pipe radius, length, depth of burial and air flow rate to cation, depth, length, diameter of the pipe, season and ambient tem-
estimate the thermal potential of EAHE. In one dimensional model, a perature, the thermal conductivity of the pipe, air flow velocity and
relation was derived between inlet and outlet temperature by giving a configuration. This has been varied from the results of various studies in
description of a pipe. This shows that performance of EAHE as the the literature. Following are parameters that influence the performance
steady-state 1D model. 2D models are used to calculate the ground of EAHE with summarized suggestions.
temperature at 5 different depths. Finite element methods are used to
solve the conduction problems. 3-D models are developed to analyse 1. Underground Soil temperature: The underground soil temperature
the performance analysis also provides room for all types of grid geo- depends on the aboveground temperature. The soil characteristics
metry. For solving 3D heat transfer and energy equation CFD is used. also influence the underground soil temperature. The temperature
For complex fluid flow and heat transfer process in any heat exchanger of the soil increases with increase in depth [47] but soil temperature
CFD software alike Ansys FLUENT, STAR-CD, CFX, FIDAP, CFD2000, should be lower than the surface temperature. The decrease in soil
PHOENICS, ADINA can be used. temperature decreases the heat transfer rate [50]. At a certain
Choudhury et al. [26] investigated an experimental study of EAHE depth, the temperature becomes stable.
design using low-cost material like Bamboos and hydra form to reduce 2. The depth of pipe and pipe orientation: Burial depth is directly
energy consumption. An open loop EAHE system was set up to predict proportional to soil temperature. As the depth of the pipe goes
the potential of EAHE. The experiment was conducted in Arunachal deeper the soil temperature increases. But the burial depth is in-
Pradesh. The study mainly focuses on the use of locally available ma- versely proportional to the outlet temperature. The depth of pipe
terials. Out of all locally available materials, bamboo was selected for affects the thermal potential. It was seen in the literature that
the pipe material. The thermal conductivity of bamboo was increased temperature increases with depth in winters and decreases in sum-
by using hydra form plaster. PVC pipes were used to install sensors for mers [48]. Hatraf et al. suggest that depth of pipe depends on the
the measurement of the temperature gradient. The inlet and outlet were diffusivity of the pipe. The cooling capacity increases as depth in-
formed using PVC pipes and bricks. Results show the maximum hu- creases. Generally, the burial depth considered for the studies varies
midity recorded was 98%. Irrespective of the inlet temperature, outlet between 2 and 5 m. The pipe orientations used in the literature are
temperature range between 25 and 26 °C. Results also show a variation open loop, closed loop. The pipes were also laid in parallel and in a
of outlet temperature with airflow velocity. It was seen that using of serpentine manner. These configurations have not much effect on
bamboo with hydra form plaster in the tunnel, reduces the outlet the thermal performance.
temperature by 10–15 °C which reduces the electricity consumption. 3. The diameter of pipe: The diameter of the pipe is directly propor-
Thus, this type of tunnel configuration is very effective for agricultural tional to the outlet temperature. As the diameter of the pipe is in-
and residential buildings. EAHE supplies fresh air ventilation and is safe creased the outlet temperature also increases. But increase in the
for environment. It also reduces the CO2 emission which helps in en- pipe diameter reduces the convective heat transfer coefficient which
vironmental management. in turn reduced the heating capacity of the system. Generally, dia-
Mathur et al. [102] studied the thermo -physical properties of soil meters vary between 0.1 and 0.6 m as suggested in the studies.
on the performance of EAHE. The study was validated using 3D tran- 4. Length of the pipe: The length of the pipe is directly proportional to
sient numerical model for 3 different soil types. A CFD model was outlet temperature. As length increases the temperature at the
formulated and solved using Ansys FLUENT 6.3. For the creation of outlet also increases. This enhances the heating potential of the
geometry Gambit 3.3 was used. The model was validated against the system. The optimal length depends on the climatic conditions.
numerical model developed by Mishra, 2013 [93]. The three soil types 5. Pipe Material: The pipe material does not affect much of the per-
selected for the study are: Soil J, F and A. The results also imply that formance. Thus, a cheaper pipe material such as PVC can also be
there was more heat penetration in the surrounding soil for J and F soil used. This makes the system more economical.
type as they have high thermal conductivity than soil type A. Thus, the 6. Airflow velocity: Air flow velocity is directly proportional to outlet
performance of soil type J and F were similar because soil with high temperature. Any small change in the air flow velocity causes a
thermal conductivity have high rate of heat transfer small decrease in the outlet temperature. High air flow velocities are
From the literature survey, it can be concluded that the performance not considered as it is not energy efficient. Generally, the air flow
of EAHE system depends on the material type of the pipe, length of the velocity varied between 2 and 5 m/s as suggested by the studies.
pipe, diameter of the pipe, pattern of the pipes laid on the ground, 7. COP: As suggested in the literature the COP in winters is lower than
underground soil temperature, soil properties, soil thermal con- COP in summers. Thus, EAHE systems can be used in both the
ductivity, inlet flow velocity, geographical and climatic conditions. For season for space heating and cooling.
the computational formulation selection of suitable software like 8. As noted from the literature survey, EAHE saves up to 50% energy
FLUENT, TRNSYS, EnergyPlus, REHAU. The performance parameter than conventional systems. Depending on the current scenario EAHE
that are affected are the pressure drop, temperature drop at the inlet is the perfect alternative to conventional systems that can employ in
and outlet, convective heat transfer coefficient, Reynolds Number, commercial, residential and agricultural buildings to achieve
Friction factor, overall heat transfer coefficient, heat capacity and total thermal comfort.
heat generated by the system. In case of coupled EAHE system the
coefficient of performance is considerably affected. The significance of 5. Conclusion
Boundary layer formation inside the pipes has not been brought into
focus. An attempt can be made by comparing different duct geometries Minimization of high-grade energy and to recommend the use of
with different duct material considering the boundary layer formation renewable energy to protect the earth from hazardous effects has be-
inside the pipes. Computational software such as ANSYS FLUENT, come an important aspect of today's world. Heating/cooling of air with
STAR-CD can be used as the simulation tool to evaluate the perfor- EAHE is a passive way to reduce the heat losses due to ventilation and
mance parameters mentioned above. thermal comfort in buildings. EAHE is an emerging technique which
278
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
can be efficiently used for pre-heating in winters and vice versa in renene.2006.03.004.
summers. Computational software like FLUENT, EnergyPlus, TRANSYS [16] Jamil Ahmad M, Tiwari GN, Singh Anil Kumar, Sharma Manisha, S HN. Heating/
cooling potential and carbon credit. Int J Energy Environ 2010;1:133–48.
etc. are used in the studies to predict the thermal performance of EAHE [17] Bansal V, Misra R, Das G, Mathur J. Transient effect of soil thermal conductivity
system. From the literature, it is concluded that after a certain depth the and duration of operation on performance of earth air tunnel heat exchanger. Appl
Energy 2013;103:1–11. http://dx.doi.org/10.1016/j.apenergy.2012.10.014.
soil temperature is lower in summers and higher than outside air in [18] Bisoniya TS, Kumar A, Baredar P. Cooling potential evaluation of earth-air heat
winters. Generally, a depth of 2.5–3 m is recommended for constant soil exchanger system for summer season. Int J Eng Tech Res (IJETR) 2014;2:309–16.
temperature. While analysing the performance of EAHE, soil properties [19] Sodha MS, Buddhi D, Campus KR. Optimization of pipe parameters of an under-
ground air pipe cooling system. Energy Convers Manag 1993;34:465–70.
such as moisture content, soil type etc. have to be considered. The [20] Mihalakakou G, Santamouris M, Asimakopoulos D. Modelling the thermal per-
design parameters such as the diameter of the pipe, material of pipe, formance of earth-to-air heat exchangers. Sol Energy 1994;53:301–5. http://dx.
doi.org/10.1016/0038-092X(94)90636-X.
length of pipe, velocity of air inside the pipes have found a significant
[21] Ascione F, Bellia L, Minichiello F. Earth-to-air heat exchangers for Italian climates.
effect on its performance. Thus, while designing EAHE consideration of Renew Energy 2011;36:2177–88. http://dx.doi.org/10.1016/j.renene.2011.01.
design parameters and soil properties play an important role in evalu- 013.
[22] Lee KH, Strand RK. The cooling and heating potential of an earth tube system in
ating the performance. This paper provides a detailed analysis of the buildings. Energy Build 2008;40:486–94. http://dx.doi.org/10.1016/j.enbuild.
advancements of EAHE system that will assist the future designers and 2007.04.003.
researchers in designing and installing efficient systems. [23] Peuportier B. Thermal and environmental assessment of a passive building
equipped with an earth-to-air heat exchanger in France. Sol Energy
Literature shows that EAHE is installed in different locations such as 2008;82:820–31. http://dx.doi.org/10.1016/j.solener.2008.02.014.
the hot and humid climate of Sahara, cold climate of Australia, tropical [24] Tittelein P, Achard G, Wurtz E. Modelling earth-to-air heat exchanger behaviour
with the convolutive response factors method. Appl Energy 2009;86:1683–91.
climate of Brazil, Mediterranean climate, moderate climate of India etc. http://dx.doi.org/10.1016/j.apenergy.2009.02.010.
that makes EAHE feasible to use. EAHE systems are also made a con- [25] Ralegaonkar R, Kamath MV, Dakwale VA. Design and development of geothermal
junction with the ventilation system and other cooling technique to cooling system for composite climatic zone in India. J Inst Eng Ser A
2014;95:179–83. http://dx.doi.org/10.1007/s40030-014-0082-y.
obtain the optimal inner room temperature. EAHE enhances the use of [26] Choudhury T, Misra AK. Minimizing changing climate impact on buildings using
low energy cooling techniques that can eliminate the usage of air easily and economically feasible earth to air heat exchanger technique. Mitig
conditioning system in buildings. Using hybrid EAHE other than EAHE Adapt Strat Glob Change 2014:947–54. http://dx.doi.org/10.1007/s11027-013-
9453-3.
has become very prominent in today's research as it promotes more [27] Dhruw HK, Sahu G, Sen PK, Sharma R, Bohidar S. A review paper on earth tube
energy saving. It has to be noted that EAHE saves about 5% more en- heat exchanger. Int J Res Appl Sci Eng Technol 2015;3:415–7.
[28] Chaturvedi AK, Bartaria VN. Performance of earth tube heat exchanger of air – a
ergy than conventional systems. Thus, EAHE is an efficient energy review. Int J Mech Eng Robot Res 2015:4.
technology that can replace the prevailing system to reduce the energy [29] Thomas W, Coulibaly Y, Traoré ES. Earth-air heat exchangers for passive air
crisis today. To understand the real behaviour of EAHE, simulation conditioning: case study Burkina Faso. J Construct Develop Ctries 2012;17:21–32.
[30] Jakhar S, Misra R, Bansal V, Soni MS. Thermal performance investigation of earth
along with data interpretation is very useful. But the important para- air tunnel heat exchanger coupled with a solar air heating duct for northwestern
meters that influence the performance of EAHE have to be investigated India. Energy Build 2015;87:360–9. http://dx.doi.org/10.1016/j.enbuild.2014.11.
070.
and selected with care and understanding to get the optimal tempera-
[31] Sikarwar PS. A review on performance of air conditioner with ground. Int J Emerg
ture difference. Technol 2014;5:79–82.
In spite of the substantial literature review on EAHE system, the [32] Chlela F, Husaunndee A, Riederer P, Inard C. Numerical evaluation of earth to air
heat exchangers and heat recovery ventilation systems. Int J Vent
detailed explanation for negligible temperature drop on considering the 2016;3315:30–42. http://dx.doi.org/10.1080/14733315.2007.11683762.
material of the pipe as a variable is yet to be investigated and is sug- [33] Mongkon S, Thepa S, Namprakai P, Pratinthong N. Cooling performance and
gested to be performed in the future works. condensation evaluation of horizontal earth tube system for the tropical green-
house. Energy Build 2013;66:104–11. http://dx.doi.org/10.1016/j.enbuild.2013.
07.009.
References [34] De Paepe M, Janssens A. Thermo-hydraulic design of earth-air heat exchangers.
Energy Build 2003;35:389–97.
[35] Bojic M. Numerical simulation, technical and economic evaluation of air-to-earth
[1] Panwar NL, Kaushik SC, Kothari S. Role of renewable energy sources in environ- heat exchanger coupled. Energy 1997;22:1151–8.
mental protection: a review. Renew Sustain Energy Rev 2011;15:1513–24. http:// [36] Razdan PN, Agarwal RK, Singh R. Geothermal energy resources and its potential in
dx.doi.org/10.1016/j.rser.2010.11.037. India. Earth Sci India 2013;7:14–8.
[2] UNDP. World energy assessment. Energy and the challenge of sustainability. 2000. [37] Sehli A, Hasni A, Tamali M. The potential of earth-air heat exchangers for low
[3] Gera RK, Parvej Y, Soni H. Renewable energy scenario in India: opportunities and energy cooling of buildings in South Algeria. Energy Procedia 2012;18:496–506.
challenges. Indian J. Electr Biomed Eng 2013:10–6. http://dx.doi.org/10.1016/j.egypro.2012.05.061.
[4] United Nations Development Programme. World energy assessment. Energy and [38] Hossein Abbaspour-Fard M, Gholami A, Khojastehpour M. Evaluation of an earth-
the challenge of sustainability. 2012. 2000. p. 1–49. to-air heat exchanger for the north-east of Iran with semi-arid climate. Int J Green
[5] Industries D. Business situations during the summer in Tokyo. Daikin 21st Surv Energy 2011;8:499–510. http://dx.doi.org/10.1080/15435075.2011.576289.
Attitudes Mod People Towar Air; 2015, p. 1–10. [39] Goswami DY, B KM. Use of underground air tunnels for heating and cooling
[6] Petroleum FOF Functioning of petroleum conservation research association; 2016, agricultural and residential buildings. Analysis 1993:1–4.
1937. [40] Vaz J, Sattler MA, Elizaldo D, Isoldi LA. Experimental and numerical analysis of an
[7] Peretti C, Zarrella A, De Carli M, Zecchin R. The design and environmental eva- earth–air heat exchanger. Energy Build 2011;43:2476–82. http://dx.doi.org/10.
luation of earth-to-air heat exchangers (EAHE). A literature review. Renew Sustain 1016/j.enbuild.2011.06.003.
Energy Rev 2013;28:107–16. http://dx.doi.org/10.1016/j.rser.2013.07.057. [41] Brum S, Vaz J, Alberto L, Rocha O, Domingues E, André L. A new computational
[8] Ozgener L. A review on the experimental and analytical analysis of earth to air heat modeling to predict the behavior of earth-air heat exchangers. Energy Build
exchanger (EAHE) systems in Turkey. Renew Sustain Energy Rev 2013;64:395–402. http://dx.doi.org/10.1016/j.enbuild.2013.05.032.
2011;15:4483–90. http://dx.doi.org/10.1016/j.rser.2011.07.103. [42] Su H, Liu X, Ji L, Mu J. A numerical model of a deeply buried air–earth–tunnel heat
[9] Singh AD Earth air tunnels; n.d. exchanger. Energy Build 2012;48:233–9. http://dx.doi.org/10.1016/j.enbuild.
[10] Kumar S, Pandey M, Nath V. Ground coupled heat exchangers: a review and ap- 2012.01.029.
plications. Renew Sustain Energy Rev 2015;47:83–92. http://dx.doi.org/10.1016/ [43] Benhammou M, Draoui B. Parametric study on thermal performance of earth-to-air
j.rser.2015.03.014. heat exchanger used for cooling of buildings. Renew Sustain Energy Rev
[11] Ghosal MK, Tiwari GN, Srivastava NSL. Thermal modeling of a greenhouse with an 2015;44:348–55. http://dx.doi.org/10.1016/j.rser.2014.12.030.
integrated earth to air heat exchanger: an experimental validation. Energy Build [44] Yang D, Guo Y, Zhang J. Evaluation of the thermal performance of an earth-to-air
2004;36:219–27. http://dx.doi.org/10.1016/j.enbuild.2003.10.006. heat exchanger (EAHE) in a harmonic thermal environment. Energy Convers
[12] Bisoniya TS, Kumar A, Baredar P. Energy metrics of earth–air heat exchanger Manag 2016;109:184–94. http://dx.doi.org/10.1016/j.enconman.2015.11.050.
system for hot and dry climatic conditions of India. Energy Build 2015;86:214–21. [45] Santamouris M, Mihalakakou G, Balaras CA, Argiriou A, A D, V M. Use of buried
http://dx.doi.org/10.1016/j.enbuild.2014.10.012. pipes for energy conservation in cooling of agricultural greenhouses. Sol Energy
[13] Sobti J, Singh SK. Earth-air heat exchanger as a green retrofit for Chandigarh—a 1995;55:111–24.
critical review. Geotherm Energy 2015:1–9. http://dx.doi.org/10.1186/s40517- [46] Yassine B, Ghali K, Ghaddar N, Chehab G, Srour I. Effectiveness of the earth tube
015-0034-4. heat exchanger system coupled to a space model in achieving thermal comfort in
[14] Florides G, Kalogirou S. Ground heat exchangers – a review of systems, models and rural areas. Int J Sustain Energy 2013;33:567–86. http://dx.doi.org/10.1080/
applications. Renew Energy 2007;32:2461–78. http://dx.doi.org/10.1016/j. 14786451.2012.762776.
renene.2006.12.014. [47] Serageldin AA, Abdelrahman AK, Ookawara S. Earth-air heat exchanger thermal
[15] Badescu Viorel. Simple and accurate model for the ground heat exchanger of a performance in Egyptian conditions: experimental results, mathematical model,
passive house. Renew Energy 2007;32:845–55. http://dx.doi.org/10.1016/j. and computational fluid dynamics simulation. Energy Convers Manag
279
N. Bordoloi et al. Renewable and Sustainable Energy Reviews 89 (2018) 261–280
280