Robinair 34800 Operation Manual
Robinair 34800 Operation Manual
Operating Manual
WARNING
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. OVERFILLING OF THE TANK MAY CAUSE VIOLENT
EXPLOSION AND POSSIBLE INJURY OR DEATH. Refer to the instruction manual for tank specifications and ordering
information. Do not recover refrigerants into a non-refillable storage container! Federal regulations require refrigerant to
be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA.
ALL HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury.
Wear proper protective equipment, including safety goggles. Disconnect hoses with extreme caution.
HIGH VOLTAGE ELECTRICITY INSIDE PANELS. RISK OF ELECTRICAL SHOCK. Disconnect power before servicing
unit. Refer to the instruction manual.
TO REDUCE THE RISK OF FIRE, avoid the use of an extension cord because the
extension cord may overheat. However, if you must use an extension cord, use No. 14 AWG at the minimum and as
short as possible. Do not use this equipment in the vicinity of spilled or open containers of gasoline or other flammable
substances.
Use this equipment in locations with mechanical ventilation that provides at least four air changes per hour or locate the
equipment at least 18 inches above the floor.
Make certain all safety devices are functioning properly before operating the unit. Before operating, read and follow the
instructions and warnings in this manual.
CAUTION: SHOULD BE OPERATED BY QUALIFIED PERSONNEL. Operator must be familiar with air conditioning
and refrigeration systems, refrigerants and the dangers of pressurized components.
Use only with R-12 or R-134a. This equipment is not designed for any other purpose than recovering, recycling
or recharging refrigerants! Do not mix refrigerant types!
ATTENTION!
Ce réservoir sous pression contient du frigorigène liquide. S’il est surchargé, ce réservoir peut exploser et causer des
blessures ou la mort.
ATTENTION. Débrancher avant la maintenance.
ATTENTION. Pour réduire les risques d’incendie, ne pas utiliser de cordon prolongateur de section inférieure à 14 AWG
de facon à éviter la surchauffe du cordon.
ATTENTION. Utiliser seulement du frigorigène R-134a.
OPERATING NOTES
At temperatures exceeding 120oF / 49oC, wait 10 minutes between recovery jobs.
Introduction ............................................................................................ 2
Glossary of Terms ............................................................................... 2
Set-Up Instructions ................................................................................... 4
Initial Set-Up ........................................................................................ 4
Operating Guidelines .............................................................................. 6
Using the Selection Menu ..................................................................... 6
Change Filter ....................................................................................... 6
Recycle ................................................................................................ 6
External Storage Vessel (ESV) Refill R-12 ............................................... 7
External Storage Vessel (ESV) Refill R-134a ........................................... 8
Vacuum Oil Time ................................................................................. 8
Filter Capacity. .................................................................................... 8
Basic/Advanced Prompts ..................................................................... 9
Selecting a Unit (Metric/English) ........................................................... 9
Language Select ................................................................................... 9
Using the Control Panel ...................................................................... 10
Keypad Functions .............................................................................. 11
Operating Instructions ........................................................................... 12
Operating Tips ................................................................................... 12
Recovering Refrigerant ....................................................................... 13
Evacuating the A/C System ................................................................ 15
Replenishing A/C System Oil .............................................................. 17
Recharging the A/C System ................................................................ 18
Maintenance Instructions ....................................................................... 20
Replacing the Filter-Drier .................................................................... 20
Changing the Vacuum Pump Oil ......................................................... 21
Checking for Leaks ............................................................................. 22
Electrical Protection ............................................................................ 23
General Maintenance ......................................................................... 23
Replacement Parts List (34800-2K) ......................................................... 24
Replacement Parts List (34801-2K) ......................................................... 26
Flow Diagram ....................................................................................... 27
Wiring Schematic .................................................................................. 28
Limited Warranty .................................................................................. 29
U.S. Patents: 4,523,897; 4,688,388 Re 33,212; 4,768,347; 4,805,416; 4,809,520; 4,878,356; 4,938,031;
5,005,369; 5,005,375; 5,038,578; 5,042,271; 5,209,653; 5,248,125 Australian Patent: 613,058 Canadian
Patents: 1,311,621; 1,311,622; 2,012,620; 2,026,348 European Patent: 0 315 296 Bl German Patent: 031296
Mexican Patent: 16208 OTHER U.S. AND FOREIGN PATENTS PENDING.
The 34800-2K and 34801-2K models are designed to be used on R-12 and R-134a
vehicles. They are compatible with existing service equipment and standard service
procedures.
The 34800-2K model is UL-listed. The 34801-2K is CE approved. Both are single
pass systems that meet the SAE specifications for recycled refrigerant.
To validate your warranty, complete the warranty card attached to your unit and
return it within ten days from date of purchase.
GLOSSARY OF TERMS
A/C System The air conditioning system being serviced.
Unit The refrigerant recovery/recycling/recharging unit.
External Storage Vessel The refillable refrigerant storage vessel designed
specifically for this unit.
Source Tank A disposable tank of new refrigerant used to refill
the external storage vessel.
START
VAC-CHARGE
STOP
CHARGE
Main Power
Valve MENU
1 2 3
4 5 6
7 8 9
F1
Switch
0
CLEAR ENTER
START STOP
High Side
1 2 3
Valve 4 5 6
MENU F1
7 8 9
Keypad 0
CLEAR ENTER
INST 0931
Diagram of the 34800-2K Control Panel
INST 0941
3
9. Fan
2
9
INST 0942
INITIAL SET-UP
CAUTION! R-134a systems have special fittings (per SAE
specifications) to avoid cross-contamination with R-12 systems. Do
not attempt to adapt your unit for another refrigerant — system
failure will result! Read and follow all warnings at the beginning of
this manual before operating the unit.
1. Lock both front casters of the unit by stepping on the cam brake levers, plug
IMPORTANT!
the power cord into the power cord receptacle (Item 9 in the INST 0941
You must press
drawing on page 3). Turn on the MAIN POWER switch.
the MENU key to
access all the 2. The first time the unit is powered up it will start in the initial setup mode.
functions.
3. The first step is to select a language. Use the UP and DOWN arrow keys to
select desired language. Press START to save the currently displayed language.
4. Next select the operating units. Toggle between UNITS ENGLISH and UNITS
METRIC using the arrow keys. Press START to save the currently displayed
choice.
5. Toggle between BASIC/ADVANCED using the arrow keys. Use the BASIC
PROMPT option to receive step-by-step, on-screen prompting through any
procedure. Use ADVANCED PROMPT once you know the procedure and no
longer need the step-by-step routine. Press START to save the currently
displayed choice.
NOTE: The vacuum pump is shipped without oil in the reservoir. Before starting
the pump, oil must be added to the pump or damage to the pump may occur.
7. Attach the flexible tube and cap to the oil bottle and pour eight ounces of
vacuum pump oil into the fill port.
8. Press the START key. While the vacuum pump is running, slowly add oil until
the level rises to the center of the reservoir's sight glass.
9. Press the STOP key and replace the black plastic plug on the fill port.
10. Use the F1 (Mode) key to select which mode to set up first R12 or R134.
Press START to continue. (After setting up the first mode the unit will prompt
you to set up the other mode.)
10. Connect the service hoses to the side that is being set up, turn both panel IMPORTANT!
Set Up
valves to RECOVER/VACUUM and Instructions
press START. The unit will For maximum
automatically run a five minute vacuum to clear all internal air. performance, be
sure to change
11. After the vacuum is complete connect the low side service hose with adapter to
the vacuum
a source tank. (For R-134a use tank to quick-coupler adapter PN 116121, for
pump oil
R12 use the 6" yellow adapter PN 710778. Both are included with unit)
frequently.
NOTE: If using a refillable tank, install the tank upside down and connect the low
side service hose to the vapor valve.
IMPORTANT!
12. Open the tank valve and invert the tank, press START when finished Be sure the
pump is
14. Press START to begin filling the external storage vessel. running when
adding oil.
15. The unit stops when a sufficient amount of refrigerant has been transferred to
the internal tank or when the source tank is empty. Press the STOP key to
pause the process. Press STOP again to exit or START to resume . This
process takes 15-20 minutes.
NOTE: Add at least 8 lb. (3.6 kg) of refrigerant before stopping the process
to ensure that enough refrigerant is available for charging.
16. When the fill process is complete you may press STOP
to exit. 1. Oil Fill Port
2. Sight Glass
3. Oil Drain
17. Disconnect the source tank from the low side service
hose .
18. The first mode is now ready to use, you will be prompted 1
to set up the remaining mode. Select the other mode and press 2
START. Follow steps 10 - 17 for the other mode. 3
4. Press START to make a choice from the menu. Press STOP to pause any
process and STOP a second time to exit any process.
CHANGE FILTER
The filter-drier removes acid, particulates, and water from the refrigerant. Change
the filter-drier after 150 pounds (68 kg) of refrigerant has been filtered. See
REPLACING THE FILTER DRIER on page 20 of the maintenance section of this
manual.
RECYCLE
Manual recycling may be necessary if excessive air and/or moisture is recovered from
the A/C system.
1. Press the MENU key. Use the arrow keys to select RECYCLE ONLY and
press START to begin.
2. Press the START button to start recycling. To pause recycling, press the
STOP key. To terminate recycling, press the STOP key again or press
START to resume.
Use the F1 (Mode) key to select R12 mode (Press and hold F1 for several
seconds to change modes)
1. Press the MENU key. Use the arrow keys to select TANK REFILL and press
START to begin.
2. Connect the 6" yellow adapter (PN 710778 included with unit) to the end of
the low side service hose.
4. Connect the low side service hose with adapter to a source tank.
6. Press the START key and the tank automatically refills. The unit stops when a
sufficient amount of refrigerant has been transferred to the ESV or if the source
tank is empty. Press the STOP key to pause the process. Press STOP again
to exit or START to resume before the external storage vessel is full.
R-12
Low Side Source
Service Hose Tank
ESV
INST0710
NOTE: If using a refillable tank invert the tank and connect the hose to the vapor
valve.
5. Press the START key and the tank automatically refills. The unit stops when a
sufficient amount of refrigerant has been transferred to the internal tank or if the
source tank is empty. Press the STOP key to pause the process. Press STOP
again to exit or START to resume before the internal tank is full.
2. The display reads: OIL TIME = XX:XX This shows how long the pump has
ran since the last oil change. The time resets to zero after a VACUUM PUMP
OIL CHANGE. See page 21 of this manual for details.
FILTER CAPACITY
This function is used to show the operator how many pounds of refrigerant have
been recovered since the last filter change.
1. Press the MENU key. Use the arrow keys to select FILTER CAPACITY and
press START to begin
NOTE: The displayed filter amount is for the mode the unit is currently operating in.
2. Toggle between UNITS ENGLISH and UNITS METRIC using the arrow key.
LANGUAGE SELECT
The operator can choose between English, Spanish, French, Italian or German.
1. Press the MENU key. Use the arrow keys to choose SELECT LANGUAGE and press START to
begin
2. Use the UP and DOWN arrows to scroll through the languages and then press
3. Press START to save the current choice. Press STOP to exit without saving.
CHANGE DEFAULTS
For service use only.
VERSION
Displays the current software revision.
3
3 4
4
5
VACUUM VACUUM OIL INJECT VACUUM OIL INJECT
VACUUM
RECOVER RECOVER CHARGE RECOVER CHARGE
RECOVER
6 START STOP
1
123
456 F1
MENU
789
0
CLEAR ENTER
5
2
INST 0932
7
Diagram of Control Panel
1. Main Power Switch 5. High Side Valve
2. Display 6. Low Side Valve
3. Low Side Gauge 7. Keypad
4. High Side Gauge
KEYPAD FUNCTIONS
In addition to the number keys, the keypad contains special keys that accomplish
specific operating functions.
• F1 (Mode) —Press and hold to select the operating mode (R-12 or R-134a)
START STOP
1 2 3
MENU
4 5 6 F1
7 8 9
0
CLEAR ENTER
INST 0933
Diagram of Keypad
OPERATING TIPS
Follow the recommended service procedure for the containment of R-12 and R-134a.
The recovery compressor is not a vacuum pump. The compressor pulls the A/C
system to a partial vacuum only. You must use the unit’s vacuum cycle to remove
moisture from the A/C system. We recommend a minimum 15-minute vacuum with
more time as required by the system manufacturer.
This unit is designed to be used with the manifold gauge set built into the control
panel.
It includes a 6 cfm (142 l/m) vacuum pump for fast, thorough evacuation. Be sure to
change the vacuum pump oil after 10 hours of vacuum pump use.
R-12 and R-134a systems require special oils. Refer to the A/C system
manufacturer’s service manuals for oil specifications.
Pressing the START and STOP keys together for several seconds will exit any mode
and reset the control
NOTE: The following operating instructions are written to be used with the
BASIC PROMPTS mode of operation. It is recommended that the BASIC
PROMPTS mode is used until the operator becomes very familiar with the
operation of the unit. See the OPERATING GUIDELINES section of this manual
for instructions on how to select between BASIC PROMPTS and ADVANCED
PROMPTS.
RECOVERING REFRIGERANT
WARNING
Always wear safety goggles when working with refrigerant. Read and
follow all warnings at the beginning of this manual before operating
the unit.
1. Connect the power cord to the back of the unit and plug into the proper voltage
outlet.
2. Turn on the MAIN POWER and if necessary empty the oil drain bottle located on
the right hand side of the unit.
3. Ensure the unit is in the proper refrigerant mode. Use the F1 (Mode) key to
select the correct refrigerant mode.
4. Press the RECOVER button.
5. If 150 pounds (68 kg) or more of refrigerant has been recovered since the last
filter-drier change, the display reads FILTER WEIGHT XXX lb (XX kg).
Press START to continue STOP to exit.
NOTE: See the filter change procedure on page 20 of this manual for details on
replacing the filter.
6. Connect the high and low side hoses to the A/C system and on R-134a systems
open the coupler valves.
7. Put Low Side Valve in the Recover/Vacuum position. Put High Side Valve in
the Recover/Vacuum position. Press START to continue.
9. If the system pressure is below 25 psi, the display reads: LOW SYSTEM
PRESSURE until the pressure increases or the START button is pressed. You
may press STOP to exit at this point.
9. If the unit has refrigerant in the low-side plumbing, it begins the clearing
process and displays CLEARING IN PROGRESS. If you wish to skip the
clearing operation or stop the clearing prematurely, press the START key.
START STOP
123
456 F1
MENU
789
0
CLEAR ENTER
Valves
Open INST 0934
Recover
10. When the system has recovered to a vacuum level of approximately 13 in. Hg., the compressor
automatically shuts off.
11. The unit then goes into automatic oil drain and the display reads: OIL DRAINING. Oil draining can
require up to 90 seconds to complete.
12. After the oil drain is complete, the display alternates between:
RECOVERY COMPLETE CHECK OIL BOTTLE.
RECOVERED XX.XX lbs. (X.XXkg) RECOVERED XX.XX lbs. (X.XXkg)
NOTE: The displayed recovered weight can vary depending on ambient conditions and should not be
used as an indicator of scale accuracy.
13. Check the oil drain bottle and note the amount of oil that was removed from the A/C system. This is
the amount of oil that must be charged into the A/C system after evacuation is complete.
14. To ensure complete recovery of refrigerant, wait 5 minutes and watch the manifold gauges for a rise
in pressure above 0 in. Hg. A pressure rise may occur if there was freezing in the A/C system during
recovery. If a rise occurs, press the START button to resume the recovery process. Repeat as needed
until the system pressure holds for two minutes, then press STOP to exit.
Recovery is now complete. You are now ready to make any repairs to the A/C system, if necessary, or
advance to the Evacuation Process.
Diagram of the Oil Injection System
INST 0713
WARNING
Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Read and follow all warnings at the
beginning of this manual before operating the unit. In addition to the
number keys, the keypad contains special keys that accomplish specific
operating functions.
NOTE: If any oil was drained from the system during recovery, DO NOT use the
IMPORTANT! VAC-CHARGE feature. The oil must be replenished into the A/C system,
which is not possible when the VAC-CHARGE function is used.
You should
evacuate for at NOTE: If the vacuum pump has been run more than 10 hours since the last oil
least 15 minutes change, the display reads: VACUUM OIL TIME XX:XX. Press the STOP key
to ensure to change the vacuum pump oil or press the START key to continue.
adequate moisture Instructions for changing the vacuum pump oil are located in the maintenance
and contaminant section of this manual. NOTE: Vacuum Pump oil should be changed after 10
removal. hours of use to maintain maximum performance and endurance levels.
NOTE: If the system being evacuated contains a pressure over 25 psi at any point
during the evacuation, the display reads PRESSURE EXISTS. This message
indicates that the A/C system contains refrigerant, press any key to continue.
Press the RECOVERY key to recover any refrigerant in the system. (See
IMPORTANT! RECOVERING REFRIGERANT page 13) After recovery is complete, return to
Evacuating the A/C System.
If the vacuum
pump has run for
10 or more hours
without an oil
change, the
message
VACUUM OIL
TIME = Xhr. Xmin
Xsec appears on
the display.
Change the CLOSED CLOSED CLOSED CLOSED
procedures in the
START STOP
123
456
MAINTENANCE MENU
789
F1
0
CLEAR ENTER
INSTRUCTIONS.
Valves Open
Vacuum Vac-Charge
2. Ensure the service hoses are connected and panel valves are in the
VACUUM/RECOVER position. Press START
IMPORTANT!
3. Press the START key to charge the default amount of refrigerant or use the
number keys to enter the desired charge weight. Then press the START key.
You should
4. If the weight entered will leave less than 3 lbs (1.36 kg). of refrigerant in the evacuate the A/C
external storage vessel, the VAC-CHARGE process does not begin and the system for at
display reads INSUFFICIENT REFRIG. At this point, refrigerant must be least 15 minutes
added to the external storage vessel. See pages 7 and 8 of this manual for
external storage vessel refill instructions and then return to Step 1 of to ensure
EVACUATING the A/C system. adequate
moisture and
5. If the external storage vessel contains a sufficient amount of refrigerant, press contaminant
the START key to accept the default evacuation time of 15:00 minutes or enter removal.
the desired vacuum time by using the number keys. Then press the START key.
6. The unit automatically charges the A/C system 10 seconds after the specified
vacuum time has elapsed.
NOTE: It is not necessary to change the High side panel valve from vacuum to charge
when performing the VAC-CHARGE function
VACUUM
NOTE: Ensure the unit is in the proper refrigerant mode. Use the F1 (Mode)
key to select the correct refrigerant mode.
1. Press the VACUUM key.
2. Ensure the service hoses are connected and panel valves are in the
VACUUM/RECOVER position. Press START
3. Press the START key to accept the default evacuation time of 15:00 minutes
or enter the desired vacuum time by using the number keys and press the
START key.
4. The unit evacuates the A/C system and stops when the specified time has
elapsed. Pressing the STOP key will pause the process. Press START to
resume or STOP again to exit.
5. You are now ready to replenish the A/C system oil (if necessary) or advance to
Recharging the A/C System.
1. Select the correct oil for the A/C system being serviced. Refer to the vehicle
manufacturer's service manual.
CAUTION! To prevent air from entering the A/C system, never let the oil
level drop below the pick-up tube while charging or replenishing.
2. Adjust the O-ring around the oil injector bottle to the required oil charge level.
For example, if the bottle's oil level is at 4 ounces and you need 1/2 ounce of
oil to replenish the A/C system, place the o-ring at the 3 1/2 ounce level.
3. Install the bottle on the oil injection assembly on the back of the unit.
CAUTION! Never open the oil injection valve while there is positive
pressure in the A/C system. This action could blow oil back through the
bottle vent.
4. Place the Low Side valve in the Closed position. Place the High Side valve in the
Oil Inject/Charge position.
5. Turn the oil injection valve at the top of the bottle and watch the level of oil being
drawn into the A/C system. This process takes only seconds—watch carefully!
6. Turn OFF the valve when the required oil charge has been pulled into the system.
CAUTION! Always perform a charge after any oil inject to insure all of the
oil is delivered to the A/C system.
Oil
Injector
Bottle
START STOP
123
MENU
456 F1
789
0
CLEAR ENTER
Oil
Oil Inject/Charge Drain
Bottle
WARNING
Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Disconnect hoses with extreme
caution!
All hoses may contain liquid refrigerant under pressure. Read and IMPORTANT!
follow all warnings at the beginning of this manual before operating the You should
unit. evacuate the A/C
system for at
NOTE: Ensure the unit is in the proper refrigerant mode. Use the F1 (Mode) key
least 15 minutes
to select the correct refrigerant mode.
for adequate
1. Press the CHARGE button. moisture and
contaminant
2. Put the Low Side Valve in the Closed position. Put the High Side Valve in removal.
the Oil Inject/Charge position. Press START to continue
3. Accept either the default weight by pressing START or type in a weight with
the number keys and press START.
4. If the weight entered will leave less than 3 lbs (1.36 kg) of refrigerant
in the external storage vessel, the charge function will not start and
the display reads:
INSUFFICIENT REFRIG.
Closed CLOSED CLOSED CLOSED CLOSED
START STOP
123
456
See the Operating Guidelines section of the manual for MENU
789
0
CLEAR ENTER
F1
refill instructions.
5. Upon entering a valid charge weight, the display reads: Oil Inject/Charge
INST 0936
CHARGE IN PROGRESS
6. If, during the charge cycle, the weight fails to charge 0.05 lbs (0.02 kg) in 30
seconds, the unit intermittently beeps while the display alternates between:
7. Pressing the START button when the charging is slowed causes the charge to
resume. If charging does not complete see the SLOW CHARGE PROCEDURE
below.
CHARGE COMPLETE
X.XXlb (kg) CHARGED
9. For a R-134a System close the high and low side coupler valves. Remove the
service hoses from the A/C system.
WARNING
Before starting the vehicle's engine, check to see that it is in PARK or
NEUTRAL, with the emergency brake ON. Never run a vehicle without
adequate ventilation in the work area.
1. Close the High Side Valve. Put the Low Side Valve in the
Recover/Vacuum position.
2. Start the vehicle and set the AC system to its maximum setting.
3. Press START. The unit charges out of the low side inlet only,
allowing the vehicle's compressor to pull the refrigerant into the
A/C system.
CHARGE COMPLETE.
X.XX lb (kg) CHARGED
7. For a R-134a System close the high and low side coupler valves. Remove the
service hoses from the A/C system.
6. Open the unit door and replace the old filter with the new
Filter filter.
7. Close the unit door, plug in the machine, and turn on the
Main Power.
Filter
9. Attach the flexible tube and cap to the oil bottle and pour eight ounces of vacuum
pump oil into the fill port.
10. Press the START key. While the vacuum pump is running, slowly add oil until
the level rises to the center of the reservoir's sight glass.
11. Press the STOP key and replace the black plastic plug on
the fill port.
2 6 3
4
5
OPEN
CLOSE
1
2
INST 00709
Diagram of Vacuum Pump
4. Close door.
ELECTRICAL PROTECTION
If the circuit breaker trips, all power to the unit is lost. Press the circuit breaker
button to reset. The circuit breaker is located near the fuse on the back of the unit.
GENERAL MAINTENANCE
1. On a regular basis, wipe off the unit with a clean cloth to remove grease, dust
or other dirt.
2. Periodically check the internal components for leaks—over time, fittings can
loosen as the unit is moved. Open the unit door panel and trace lines with a
leak detector. Also, check connections on the back of the unit. Tighten any
loose fittings or connections you may find.
The following is a list of replacement parts and accessories you may need to service
or maintain your unit.
We suggest you keep several filter-driers on hand so you will always be able to
change them and complete any recycling job that is in progress.
Premium High Vacuum Pump Oil is also available in handy quart containers or in
convenient gallon containers:
26
LS HS
SWITCH DESCRIPTION
1 HIGH PRESSURE SWITCH-MANIFOLD
2 VACUUM PROTECTION SWITCH
2 3 4
UPPER BLOCK FUNCTION
Flow Diagram
TO A/C SYSTEM TO A/C SYSTEM SOLENOID DESCRIPTION RECOVER VACUUM RECYCLE CHARGE
1 RECOVER X O O O
2 VACUUM O X X O
3 CHARGE O O O X
4 RECYCLE O O X O
FROM LIQUID 5 OIL RETURN O * * O
PORT ON
TANK 6 AIR PURGE O * * O
7 OIL DRAIN * O O O
2
VACUUM PUMP
5
TO VAPOR PORT
ON TANK
TO DRAIN
BOTTLE
LOWER BLOCK
CHECK VALVE
LOCATED BETWEEN PORTS E AND F
4 OF LOWER BLOCK 1
RECEPTACLE
GRN/YEL
IEC320 INLET
2 R134 OIL DRAIN
9 RED SW5
P27 3
BLUE THERMAL 3 YELLOW
1 R134 LOW PRESS
PROTECTOR YELLOW SW6
2 BROWN 10
1 ORANGE
WHITE 4
3 R134 VAC PROT
BLACK 11 ORANGE SW7
4
P11 YELLOW PURPLE
5 5 R12 LOW PRESS
1 GRAY
15 AMP PURPLE 5 4 3 12 PURPLE SW8
GRAY BREAKER 6 COMPRESSOR START
2 BLACK
7 START RELAY CAPACITOR 6 R12 VAC PROT
3 WHITE 1 2 BLACK
3 AMP 13 SW9
WHITE BREAKER 8
4 NC
7
R12 COMPRESSOR NC
14
1 3
2 HIGH PRESS THERMAL
P28 3 R12 SW2 PROTECTOR
BROWN 1
1
BROWN
BROWN
2
SHIELD
P20
1
2 HIGH PRESS 5 4 3 1 BLACK
3 R134 SW3 COMPRESSOR START GREEN
START RELAY CAPACITOR 2 R134 SCALE
1 2 3 WHITE ASSY
4 RED G
P24 R134 COMPRESSOR
1 WHITE
R12 RECYCLE
8 WHITE SOL 10
2 ORANGE
R12 CHARGE SHIELD
9 ORANGE SOL 9 P23 P21
Inst0939
27
Limited Warranty
%
Visit our web site at
OZ. LBS.
www.robinair.com
0.5 0.03
1.0 0.06
or call our Toll-Free
1.5 0.09
2.0 0.13
Technical Support Line at
2.5
3.0
0.16
0.19
800-822-5561
3.5 0.22
4.0 0.25
in the continental U.S. or Canada.
4.5 0.28
5.0 0.31
In all other locations, contact your local distributor. To help us serve
5.5 0.34
you better, please be prepared to provide the model number, serial
6.0 0.38
6.5 0.41 number, and date of purchase.
7.0 0.44
7.5 0.47 To validate your warranty, complete the warranty card attached to your
8.0 0.50 unit and return it within ten days from date of purchase.
8.5 0.53
9.0 0.56
9.5 0.59 • NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS
10.0 0.63 If your unit needs repairs or replacement parts, contact the service
10.5 0.69 center in your area. For help in locating a service center, call the toll
11.0 0.69 free technical support line.
11.5 0.72
12.0 0.75
12.5 0.78
Due to ongoing product improvements, we reserve the right to change design,
13.0 0.81 specifications, and materials without notice.
13.5 0.84
14.0 0.88
14.5 0.91 The 34800-2K and 34801-2K are designed to meet all applicable agency certifica-
15.0 0.94 tions including Underwriter's Laboratories, Inc., SAE Standards and CUL. Proper
15.5 0.97 maintenance of this equipment will provide accurate A/C service for many years.
16.0 1 lb.
Certain state and local jurisdictions dictate that using this equipment to sell refrig-
erant by weight may not be permitted. We recommend charging for any A/C service
by the job performed.
This weight scale provides a means of metering the amount of refrigerant needed
for optimum A/C system performance as recommended by OEM manufacturers.
SPX Corporation
655 Eisenhower Drive
Owatonna, MN 55060-0995 USA
Tech Services:1-800-822-5561
Fax: 1-800-822-7805
Customer Service: 1-800-533-6127
Fax: 1-800-322-2890
Web site: www.robinair.com