Protection and Switchgear
Protection and Switchgear
After knowing the basic principles of circuit breakers, it is necessary to know the variou s
types of circuit breakers and applications . The Chapter 2
uses a very systematic metho d
of explaining working of various types of circuit breakers . The discussion of selection o
Wholesale Distributio n f
circuit breaker is also included in the chapter .
Pan e
Pragati Books Pvt . Ltd. Mumba i The Chapter 3 explains the concept of fuse, various types of
119, Budhwar Peth, Jogeshwari Mandir lane, Pragati Books Pvt . Ltd . .fuse, characteristics of
Pune -411 002, Indi a 385, S .V.P. Road, Rasdhara, Co-op . Society, Girgaum , fuse, fuse law and various applications of fuses .
Phone : (020) 24452044 Mumbai - 400 004 India .
Phone : (022) 23869976, 2385633 9 The Chapter 4 gives the introduction of protective relaying
Bangalore
Chennai . The chapter starts wit h
Pragati Book House explaining what is protective relaying . The various characteristics of protective relaying
1676-14th, Main Road, PrakashNagar ,
Pragati Book s ,
# 911, Montieth Road, Behind Teas Mahal , overlapped zones and various technologies used in protective relaying are included in thi s
Bangalore - 560021, Indi a Egmore, Chennai - 600 008
Phone : (080) 23324037, Telefax : 2332 4437 , India . Ph. - (044) 6518 3535 Mobile - 94440 01782, chapter .
Mobile : 98805 8233 1
Chennai The Chapter 5 includes variety of protective relays used in the practical power syste
Technical Books Distributo r Hyderabad m
B - Ground floor, 'QUANTAANNAM' 24th Street, H-965/966, Nirali Book Hous e protection . The relay includes attracted armature type, solenoid and plunger type, inductio
Opp . U C MAS'Anna Nagar (W) Chennai -600040, 22,Shivam Enclave, 4-5 . 947, Badi Chavadi , n
Phone :(044)26161903 Mobile : 9840324419 Hyderabad - 5000 type and thermal relays .
India . Mobile : 9440030606 Phone : (040) 655453/35
The Chapter 6 is devoted to differential protection including types of differential relay
s
and busbar protection .
The Chapter 7 includes distance protection including various distance relays and thei r
use in protection of transmission lines .
The Chapter 8 includes generator protection including generator faults, differentia l ******l******* *8** **l**}**** 4*
***********v* **v*w**** ******* * *'
protection, Merz-Price protection, earth fault protection, rotor earth fault protection an d
protection against loss of excitation .
We wish to express our profound thanks to all those who ,helped in .ng this book a
The Chapter 9 explains induction motor protection against single p hdsi ng , reality . Much needed moral support and encouragement is provided on numerou s
overloading, phase fault, ground fault, and phase reversal . occasions by our whole families .
The Chapter 10 includes protection of transformers including discussion of possibl e We are specially grateful to the great teacher Prof. A . V . Bakshi for his time to time ,
transformer faults, differential protection, Merz-Price protection and Buchholz protection . very much needed valuable guidance . We are also thankful to Mr . Sachin S he|orfor hi s
help while preparing this book . Without full support and cheerful encouragement o f
The Chapter 11 includes the discussion of carrier aided protection, static relays an d
Mrs . Varsha U . 8okuhi the book would not have been completed in time .
microprocessor based relays .
Finally we wish to thank Mr . Avinash VVoni, Mr . Bovindro Wani and the entire
. The book not only covers the entire syllabus of the subject but explains the philosoph y
team of Technical Publications who have taken immense pain to get this book in tim e
of the subject . This makes the understanding of this subject more clear and makes th e
subject more interesting . The book will be very useful not only to the students but also t o ` with quality printing .
the subject teachers . The students have to omit nothing and possibly, have to cover nothing Any suggestions for the improvement of the book will be acknowledged and wel l
appreciated .
°
\-4 .13 Interruption of Capacitive Current
s
/1
71.14l5 Resistance
Current Chopping (Interruption of Low Magnetizing Current)
N Switching 25
1 .16 Arc Extinction 27
;
Table of Content s 1 .16 .1 High Resistance Interruption . . . . 31
1 .16 .2 Low Resistance or Current Zero Interruption ''''' .• 31
Chapter-1 Principles of Circuit Breaker s 1 .16 .3 Artificial Current Zero Interruption " 31
1 .1 Introduction 1 1 .17 Ionization of Gases 31
""'
1
1 .2 Formation of an Arc 1 .17.1 Thermal Ionization „, ' ,, , 32
1 .2.1 Initiation of Arc 2 1 .17 .2 Ionization by Collision 32
1 .2 .1 .1 By High Voltage Gradient 2 1 .17 .3 Thermal Emission from Surface of Contacts
2 • 32
1 .2 .1 .2 By Increase of Temperature 1 .17 .4 Secondary Emission at Contact Surface • •
1 .2 .2 Maintenance of an Arc 2 „ • • • • • • , • • . . 32
1 .17.5 Field Emission
1 .2.3 Arc Extinction 3
1 .17 .6 Phofoemission 32
1 .2 .3 .1 High Resistance Method 3
32
1 .18 D eionization
1 .2.3 .2 Low Resistance Method 3
3 1 .18 .1 Recombination •••••,•••••,, , 32
1 .3 D.C . Circuit Breaking
5 1 .18 .2 Diffusion 33
1 .4 A.C. Circuit Breaking
5 1 .18 .3 Conduction of Heat " "" 33
1 .5 Short Circuit in R- L Series Circuit 1ij " „" „
1 .19 Arc Formation 33
1 .6 Current Interruption in A .C . Circuit Breakers 9 . .. . . . . . . . . . .. .. .
. . . . . . . . . . .. . . . . .... .. . ... . .
1 .20 33
1 .7 Transient Rec Voltage 11 High Resistance Arc Interruption Methods
1 .20 .1 Lengthening the Arc 33
1 .8 Effect of Different Parameters on Transient Recovery Voltage (TRV) 12
1 .20 .2 Splitting of Arc 34
1 .8 .1 Effect of Natural Frequency on TRV 13
1.20 .3 Cooling of Arc,, 34
1 .8 .2 Effect of Power Factor on TRV 13
1 .21 Low 34
11 .9,Recovery Voltage 14 Resistance or Zero Point Extinction
V 1 .9.1 Effect of Reactance Drop on Recovery Voltage 1 .22 Arc I nterruption Theories - . . .3 5
15
15 1 .22 .1SIepian'sTheory 35
1 .9 .2 Effect of Armature Reaction on Recovery Voltage
15 1,22,2 Lassie's Theory 35
1 .10 Single Frequency Transient
Examples with Solutions 36
.1 .11 Double Frequency Transient 16
16 Review Questions . .. . .. . . . . . . . . . . . . .. . . . .. . . . . . . . . . .. . . . . . . . . . . . . . . """ ' • . 37
1 .12 Derivation of Rate of Rise of TRV . .. .. . . . . . .
University Questions """""""• .38
1 .12 .1 Expression for Maximum Value of Restriking Voltage E m and Corresponding Time t m 18 .. . . .. . . .
1 .12.2 Expression for RRRV and Maximum RRRV 19 5ter 2
1 .12 .3 Frequency of Oscillation of Restriking Voltage (Transient) 19 40
2 .1 Introduction . . . . . . ... . . .. . . . . . . . ... . . .
1 .12 .4 Restriking Voltage Under Various Conditions 19
2 .2 Requirements of Circuit Breaker
1 .12.5 First Pole to Clear Factor 20 40
2 .3 Basic Action of a
Circuit Breaker
40
62
2 .9 .1 .1 Single Break Oil Circuit Breaker
41 63
2.4 Classification of Circuit Breakers 2 .9 .1 .2 Double Break Oil Circuit Breaker
/ 42 65
35'
*/J***[
- Blast Circuit Breakers 2 .9 .1 .3 Factors Affecting Performance of Plane Break Oil Circuit Breaker
42 65
2.5.1 Construction of an Air Blast Circuit Breaker 2 .9 .1 .4 Advantages of Plain Break Oil Circuit Breaker
' ' . ' 44 66
2.5.2 VVo rkin -q 2 .9 .1 .5 Disadvantages of Plain Break Oil Circuit Breaker
44 66
2.5.2 .1 Cross Blast Type 2 .9 .1 .6 Applications
45 66
2122 Axial Blast Type 2.9 .2 Self Generated Pressure Oil Circuit Breaker
47 66
2.5 .3 Compressed Air System for Air Blast Circuit Breaker 2 .9 .2 .1 Plain Explosion Pot
48 67
2.5.4 Advantages 2 .9 .2 .2 Cross Jet Explosion Pot
48 67
2.5 .5 Disadvantages 2.9 .2 .3 Self Compensated Explosion Pot
48 68
2.5 .6 Applications Blast Explosion Pot
2 .9 .2 .4 Oil 68
.' 48 2 .9 .3 Forced Blast Oil Circuit Breakers
2Air Break Circuit Breaker - '6
49 / 2 .10 Low {}ii or Minimum (}i\ Circuit *}[88k8[---~
211 Cons ruobon 70
' .' ' . . . .' .' ' 50 .10 .1 Construction 92
2.6.2 Working ' 72
' ' 50 ' 2.10 .2 Operation
2.6.3 Applications 72
51 2.10 .3 Maintenance of Oil Circuit Breakers
2 .7/Sulphur Hexafluoride (SF 6) Circuit Beaker 72
" 2.10 .4 Advantages
2.7 .1 Properties of SFo Gas ' 72
51
- 2.10 .5 Disadvantages
2 .7 .1 .1 Physical Properties *
52 72
2.7 .1 .2 Chemical Properties 2.10 .6 Applications
52 . 73
2 .7 .1 .3 Dielectric Properties ** l H\/D C Circuit B no@ k B[
^^ \*- * 73
2I2 Construction of Non-puffer TvoeGF 6 Breaker 2 .12 Selection of Circuit Breaker
' " 51 75
2 .7 .2 .1 Working ' '
55 2 .13 Circuit Breake r Ratings
2.7 .3 Single Pressure Puffer Type 8F6 Circuit Breaker 75
56 , 2.13 .1 Rated Volta g e
2.7 .4 Double Pressure Type SFoC ircV it Breaker 75
"" 2 .13 .2 Rated Insulation Level
2.7 .5 Advantages of SFs Circuit Breaker ' .' 76
` _ 2.13 .3 Rated Current
2.7 .6 Disadvantages 1 * 76
' .' . . .' . . . .' ` ' ' . . . ." 2.13 .4 Rated Frequency
2 .7 .7 Applications 76
---' 57, 2 .13 .5 Rated Duration of Short Circuit
Breakers ~24/8VacumCirt 76
58 2131 Rated Short Circuit Breaking Current
2. 8. 1 High Vacuum 77
1 "7 7 " . ; ` "!-" - 2.13 T R atndGho d Circuit Making (Current
2.8 .2 Construction ' 77
' ` .' .' . .' .' .' 59 2.13 .8 Rated Peak Withstand Current
2.8 .3 Working 78
60 2 .13.9 Rated TRV for Terminal Faults
2.8.4 Advantages ' 7
60 2.13 .10 Rated Operating Sequence
2.8 .5 Disadvantages ` Dov*oa 7
? :0061
.G1 .13 .11 Rated Supply Vobooo*nC*a* g and Opening 82
2.8 .6 Recovery
^--Strength Characteristics
- 79
" . ' .' 61 .13 .12 Rated Pressure of Compressed Gas 82
2.8 .7 Applications .__ _ __-** O
82 2 .14 Type Tests
210111 Circuit Breakers -'
' ` 82
2.9 .1 Plain Break Oil Circuit Breaker
85
2.15 Routine T e St3 . . . . . . . . . . . . . . . . . .. . . . . . . . . . .. . . . . . . . . . .. . . . . . . . . . . . . . . . . .. . . . .. . . . . . . . . . 80 3.4 .4 Fusing Current
85
2.16 Dôv8|Opnl e Ot Tests 81 3 .4 .5 Fusing Factor
7: 96
2.17 Reliability T e StG . .81 3.4 .6 Prospective Current
I I 96
2 .18 Commissioning Te GtS-- 81 847Cu t-ot Current I
^.. 97
2 .19 Short Circuit Test Layout--- 3.4 .8 Pre-arcing Time : I
82 98
2.19 .1 Short Circuit Testing Plants 82 3 .4 .9 Arcing Time
98
2.19 .2 Layout of a Short Circuit Testing Station 82 3.4 .10 Total Operating Time
98
2.19.3 Short Circuit Generator and Drive Motor 83 3.4 .11 Breaking Capacity
98
21 SA Short Circuit Transformers 84 3/A2 Pre-arcing It
98
Z 1 15 Reactors 84 3.4 .13 Arcing Pt
98
2.19 .6 Master Circuit Breaker 84 3 .4.14 Clearing It I
98
2.19 .7 Making Device 85 3 .4 .15 Voltage Rating of Fuse
'
2.19 .8 Capacitor 85 /` ~? , 5 Fuse Element **8t e [8]
99
2 .19 .9 Rosistum 85 / '- 3 .6 Tinl8- Current Characteristic of Fuse
10 1
2.19 .10 Test Cubicles I 85 3 .7 Fuse [8VV
10 3
2.19 .11 Sequence Switch I . . .1 85 \/3'.8 /\ d V8Otage S of Fuse ---- .
. . 103
2.19 .12 Different Measurements 85 3.Q Disadvantages Of Fuse
. 103
2.20 Indirect Testing G0 FU 8---- . . ..
*//*- . 1 OH R**
s
103
2201 Unit Testing 86 ^^ 3.10 .1 Construction
~
104
2.20 .2 Synthetic Testing : I 87 1/3 .10 .2 Operation
.
104
2 .21 Types of Synthetic Test Circuits 87 105
~. /3 .1031 Qd'uff Characteristics
2.21 .1 Parallel Current Injection Method 87 *
' 10
2212 Series Current Injection Method 89 Al O32 Time - Current Characteristics I
106
2.21 .3 Bm wnBovoh s Synthetic Testing Circuit 90 .10 .3 .3 pL Characteristics . . ` '* 5V3
'
' ' .' 107
3.10 .4 Fuse Element of HRCFuoe '
Review Questions ': -A0 107
3 .10 .5 Advantages of oHRC Fuse
University Questions . . . . . . .. . . . . . . . .. . . . . . . . . . . .. . . . . . . .. . . . . . . . . .. . . . 9 1 * ^ . .' 107
8.1O.O ,Disadvantages of eHRO J ueo,
91. 108
3.1D .7 Selection of MRC Fuse
108
.10.8 Application s3
10 8
3 .2Introduction of Fuse . . . . . . . . . . .. . ... . . . .. . . . . . . . .. . . .. . . . . . . . . . .. . . . . . . . . . - ' 92 3 .11 HRC Fuse With Tripping [}8ViQS----
.. . 10 9
3.3 Types of Fuses ' 03 3.11 .1 Advantages
._`--- 109
3.4 Definitions 95 -+/3 .12 Liquid Fuse .
1* *
. ~~
u^3 .4.1 Fuse S5 ~/^ 3 1 3 []iGC[FOiO8t**O ^~ ^
,..---'3 UFuse Element 95 114 Difference Between Fuse and Circuit Breaker 1 -1 -1
1 .2 Formation of an Ar c
Now let's see the formation of an arc . Under fault condition heav current flow s
through the contacts of the circuit breaker before they are o erred . As soon as the contact s
start separating, the area of contact decreases which will increase the current density and
VTU -Switchgear and Protection 3 Principles of Circuit Breaker s
VTU -Switchgear and Protection Principles of Circuit Breaker s
conse uentl T The medium between the contacts of circuit breake r iii) The separation of contacts of circuit breaker increases the length of path which wil l
may be air or oil . The heat which is produced in the medium is sufficient - . . . to i .* . .- increase number of neutral molecules . This will decrease the density of gas whic h
will increase free path movement of the electrons .
air Or of which will act as conductor . Zus an arc is struck between the contacts The p .d .
ettween the contacts is su icient to maintain the arc. So long as the arc is remaining between, 1 .2 .3 Arc Extinctio n
the contacts the circuit is said to be uninterru .te .
It is essential that arc should be extinguished as early as possible . There are two method s
The current flowing between t e contacts depends on the arc resistance . With increase in of extinguishing the arc in circuit breakers which are namely ,
arc resistance the current flowing will be smaller . The arc resistance depends on following a) High resistance metho d
factors, b) Low resistance or current zero metho d
a) Degree of ionisation : If there are less number of ionised particles 'between the 1 .2.3.1 High Resistance Metho d
contacts then the arc resistance increases .
In high resistance method the arc resistance is increased with time . This will reduce th e
b) Length of arc : The arc resistance is a function of length of arc which is nothin g current to such a value which will be insufficient to maintain the arc . Thus the current is
btdseparation between the contacts . More the length, more is the arc resistance .
interrupted and the arc is extinguished . This method is employed in only d .c. circuit
*c)'Cross-section .of arc : If the area of cross-section of the arc is .less then arc breakers . The resistance of the arc may be increased by lengthening the arc, cooling the arc ,
{ resistance is large . reducing the cross-section of the arc and splitting the arc . These methods will be discussed i n
detail later in .this chapter.
1 .2.1 Initiation of Arc
There must be some electrons for initiation of an arc when fault occurs circuit breake r 1 .2.3 .2 Low Resistance Metho d
contacts start separating from each other and the electrons are emitted which are produce d The low resistance or current zero method is employed for arc extinction in a .c. circuits.
by following méthods . In this method arc resistance is kept low until current zero where extinction of arc take s
e
i) . : high voltage gradient at the catho . -, resulting in place naturally and is prevented from restriking . This method is employed in many of th
modern a .c . circuit breakers .
ii) By increase oftemperature resultin
1 .1 .1 By High Voltage Gradien t .3 D.C. Circuit Breakin g
.2
As the moving contacts start separating form each other, the area of contact and pressur e The breaking in case of d .c . circuits can be explained as follows . For this, we will
between the separating contacts decreases . A high fault current causes potential drop (of th e consider a circuit which will consist of generator with voltageE, resistance R, inductor L
order of 106 V/crri)between the contacts which will remove the electrons from cathod e and the circuit breaker as shown in the Fig . 1 .1 (a) .
surface . This process is called field emission.
1,2 .1 .2 By Increase of Temperatur e
With :the separation of contacts there is decrease in contact area which will increase th e
current density and consequently the temperature of the surface as seen before, which wil l
cause emission of electrons which is called thermal electron emission .
In most of the circuit breakers the contacts are made up of copper which :is having les s
thermionic emission .
1 .2 .2 Maintenance of an Arc
In the previous section we have seen the initiation of the arc by field emission an d
thermionic emission . The electrons while travelling towards anode collide with anothe r
electrons to dislodge them and thus the arc is maintained . The ionizing is facilated by, Fig . 1 .1 (a )
i) High temperature of the medium around the contacts due to high current densities . The voltage-current relationship can be represented as shown in the Fig . 1 .1 (b) .
Thus the kinetic energy gained by moving electrons is increased.
From the Fig . 1 .1 (b), it could be seen that curve AB represents the voltage E - iR, i i s
ii) The increase in kinetic energy of moving electrons due to the voltage gradient which
nothing but current' at any instant . The curve XY represents the voltage-curren t
dislodge more electrons from neutral molecules .
characteristics of the arc for decreasing currents .
VTU - Switchgear and Protection 4 Principles of Circuit Breaker s VTU - Switchgear and Protection 5 Principles of Circuit Breakers
It can be seen that arc voltage is greater than E -iR and the balance between the voltage s
is supplied by the voltage across the inductance eL which is proportional to rate of change o f
di
current
dt
Thus .the function of the circuit breaker is to raise the arc characteristics without affectin g
its stability . This is done by reducing the arcing time which is the time from contac t
separation to final extinction of arc . But it will increase extinction voltage . Henc
e
compromise between arcing time and arc extinction voltage is made .
1 .4 A.C . Circuit Breakin g
There is . a difference between breaking in case of d .c. and a .c. circuits. In a.c . circuits the
current passes through zero twice in one complete cycle . When the currents are reduced to
zero the beakers are operated to cut-off the current . This will avoid the striking of the arc . But
Fig . 1 .1 (b) Voltage-current relationship this conditions is difficult to achieve and very much expensive .
When the circuit breaker starts opening it carries the load current I =R In the grap h The restriking of arc when current is interrupted is dependent on the voltage betwee n
the contact gap at that instant which will inturn depend on power factor . Higher the power
shown the current is shown to be reduced to il , iZ and i3 respectively. Section pr represents factor, lesser is the voltage appearing across the gap than its peak value .
voltage drop i3R whereas qs represents arc voltage which is greater than available voltage . Now before studying the actual current interruption in a .c. circuits we will see som e
The arc becomes unstable and the difference in voltage is supplied by inductance L acros s theory which will help us in understanding this concept .
which the voltage is eL = L 1 . For decreasing values of currents this voltage is negative an d 1y5''hort Circuit in R- L Series Circuit
dt
according to Lenz's law it tries to maintain the arc . Consider a series R-L circuit as shown in the Fig . 1 .3 in which switch S is suddenl y
The voltage across inductance L is seen to be positive in the region of currents i t and i 2 closed at time t = O .
since the arc characteristics lies below the curve AB . The arc current in this region tries t o
increase so interruption of current is not possible in this region . Afterwards the arc i s
lengthened with increase in contact separation which will raise the arc voltage above th e
curve AB .
The operation in case of d .c . circuitbreakers is said to be ideal if the characteristics of th e
arc voltage are above the curve AB even in the region of currents i t and i 2 . This is shown in
the Fig. 1.2.
This equation can be solved to get the expression for current i . This is a
non-homogeneous differential equation whose solution consists of two parts vi z
complementary solution and particular solution i .e. i = is + ip.
Fig . 1 .5 No D .C . componen t
The analysis of three phase short circuit of an alternator is done by similar way as w e
have done the analysis of short circuit of series R-L circuit . The current flowing through th e
.c . component
phases of alternator during short circuit has similar waveform to that of R-L circuit as show n Fig . 1 .6 Oscillogram of current in the phase having zero d
instantaneous value of current during short circuit . This instantaneous peak value of firs t
current loop is called making current which is expressed as kA peak .
Now the circuit breaker contacts will separate after few cycles which are taken by rela y
and other operating mechanism . At time say t = Tl the contacts of circuit breaker separate .
3 ph The r,m .s . value of short circuit current at that instant of contact separation is called breakin g
short current.
circuit
As seen earlier an arc is struck between the contact when they start separating . The ar c
IB current varies sinusoidally for few cycles . At t = T2 the arc is interrupted as the dielectri c
strength of arc space builds sufficiently . This will avoid the continuation of arc . Thus the ar c
will be extinguished .
The voltage waveform is shown in the Fig . 1.8 . Before the instant t = 0, the contacts ar e
closed so the voltage between them is zero . At the instant t = Tl , the contacts begin t o
Fig . 1 .7 Sudden 3 phase short circuit of an alternato r
separate and voltage across them starts increasing . This voltage is nothing but the dro p
When the voltage of phase B w .r .t neutral is zero, the circuit breaker is closed . Under this across the arc . The current and the voltage across arc are in phase as the arc is resistive . Due
condition the B phase current will have maximum d .c . component and its current waveform to increased arc resistance the voltage across contacts increases in the next cycles . Finally a t
will be uns ymmetrical about normal zero axis . This is shown in the Fig. 1 .8.
t = T2 the arc is extinguished . A high frequency transient voltage appears across the contacts
which is superimposed on power frequency voltage . This high frequency voltage tries t o
restrike the arc . Hence it is called Restriking Voltage or Transient Recovery Voltage . This i s
the voltage which appears across circuit breaker contact which is responsible'for restrikin g
of arc . The power frequency system voltage between the circuit breaker contacts after ar c
extinction is called Recovery Voltage . The prospective current shown in the waveform ma y
be defined as the current that would flow in the circuit if circuit breakers were replaced b y
solid conductor .
If the breakdown occurs after one fourth of a cycle, the phenomenon is called Restrike . I n = 1 Hz
restriking, high voltage appear across the circuit breaker contacts during capacitive curren t 2i.fL C
breaking. In successive restrikes, voltage will go on increasing which may lead to damage of
where f„ = Frequency of transient recovery voltage
circuit breaker . Thus the circuit breakers used for capacitors should be free from Restrike i .e .
they should have adequate rating . L = Equivalent inductanc e
C = Equivalent capacitanc e
1 .8 Effect of Different Parameters on Transient Recovery Voltage (TRV )
1 .8 .1 Effect of Natural Frequency on TRV
As seen from the previous section, after the final current, zero high frequency transien t With increase in the natural frequency the rate of rise of TRV at current zero increases .
voltage appears across the circuit breaker poles which is superimposed on power frequenc y This is shown in the Fig . 1 .11 . The rate of rise of transient recovery voltage is represented b y
system voltage and tries to restrike the arc . This voltage may last for a few tens or hundred s slopes of tangents to the three waveforms drawn at different frequencies .
of microseconds . If the shape of this TRV is seen on the oscilloscope then it can be seen that i t
may be oscillatory, non-oscillatory or a combination of two depending upon th e
characteristics of the circuit and the circuit breaker . The waveform is as shown in the Fig . 1.9 . A,B,C -► Tangents indicat e
slope of TRV at t = 0
Power frequenc y
Recovery voltag e
Arc
voltag e
10
t -► n
.-Transien t
voltage
wt -'*
Fig . 1 .9 Shape of transient recovery voltag e
This voltage has a power frequency component and an oscillatory transient component .
The oscillatory component is due to inductance and capacitance in the circuit . Thepowe r
frequency component is due to the system voltage . Thisis shown in the Fig . 1 .10 .
.,SWaveform s
showing TRV
V V
decreases . To regain the original value this e .m.f. takes some time . Thus the power
frequency component of recovery voltage is less than the normal value of system voltage .
1 .10 Single Frequency Transient
Consider the circuit
shown in the Fig . 1 .14. This
circuit produces the single
Fig . 1 .12 Unity power facto r
frequency restriking voltag e
transient .
TRV
The natural frequency o f
Recovery
/ voltage oscillation is given by,
Arc 1
/curren t fn .=
1 ti 1
Fig . 1 .1 4
1 1
where L Inductance in henr y
i V#rjX/
f C = Capacitance in farads
Depending upon the values of L and C, the frequency ranges from 10 Hz to 10 kHz . The
circuit configuration in actual power system is complicated and it has distribute d
I capacitance and inductances . In such circuits the TRV has several components o f
1 Arc frequencies which is shown in the Fig : 1.15 .
voltage
Fig . 1 .1 5
VTU -Switchgear and Protection 16 Principles of Circuit Breakers VTU-Switchgear and Protection 17 Principlesof Circuit Breaker s
The transient shown in the Fig . 1 .15 is obtained by operating the terminal fault wher e With the given
reactance between the fault and circuit breaker is negligible . specifications of TRV the
circuit breaker must b e
1 .11 Double Frequency Transien t able to interrupt th e
short circuit breaking
In last section we have considered inductance L and capacitance C on only one side o f current . The peak valu e
circuit breaker . But it may be on both sides of circuit breaker . This is shown in the Fig . 1.16. of TRV, time to reach th e
peak frequency of TR V
L*
and initial rate of rise ar e
000 0
Circuit some of the importan t
breake r properties of TRV whic h
are significant .
e = Em sinwt Cl CZ `
Faul t Fig . 1 .1 8
The solution of 'e' will thus depend on the current and if interruption takes place a t tm =n .,JL C
current zero i.e . when t = 0 then, And peak value of restrikin
i= E m sin co t
wL where Em is equal to active recovery voltage (i .e. instantaneous value of recovery voltag e
and after opening of circuit breaker , at current zero) .
di E m co cos w t 1 .12 .2 Expression for RRRV and Maximum RRRV
dt wL r
E cos co t Now RRRV = d ee = d E m cos t
= m att= 0 dt dt .J LC
L i_
Substituting this in (2),
z RRRV = E "' sin t
Em coswt = e+C d e .JLC ,JL C
L L dt 2
and maximum RRRV = E
This is standard equation and solution of this equation is, .,JL C
t . . . (A)
e=Em 1 - cos when sin t = 1
LC D
V LC
This is an expression fo r i.e. t E7
m restriking voltage in which, LC 2
ma x
Restrikin g E, = Peak value of recover y
e voltag e
voltage phase to neutral i n for maximum RRRV
volts.
t = time in sec . 1 .12 .3 Frequency of Oscillation of Restriking Voltage (Transient )
1
L = inductance in henries fn = 2rz•JL C
C = capacitance in farad s
t m H- tinpse c e = restriking voltag e JLC =
2rzf"
Fig . 1 .1 9
Maximum RRV = E", = 2 7c fn Em
1 .12 .1 Expression for Maximum Value of Restriking Voltage E m .JL C
and Corresponding Time t m Maximum RRV = 2 lt Em fn
Now
1 .12 .4 Restriking Voltage Under Various Condition s
t
e=Em 1 - co s The restriking voltage 'e' under various conditions will be,
LC D - -
t
if 'e' is to be maximum e = Var 1-COS
.JLC
tm
cos 1 where t = tm where Var active recovery voltage i .e . the instantaneous value of recovery voltage a t
.J LC i current zero and Var can be written a s
t m = Var = Kl K2 K3 Em
.J LC Here Em is the peak value of system voltage where ,
Time at which maximum restriking voltage occurs is, Kl is factor which takes into accounts effect of circuit p .f. and K1 = sin 4
VTU - Switchgear and Protection 20 Principles of Circuit Breakers VTU - Switchgear and Protection 21 Principles of Circtiit Breaker s
So if ¢ = 90°, K1 = 1 fn = 1
21c,/ L C
K 2 is factor which accounts effect of armature reaction on recovery voltage .
1
K3 is phase factor or first pole to clear factor . = 21c fn
.J LC
1 .12 .5 First Pole to Clear Facto r
= 21cx16x10 3
The first pole to clear factor is given by ,
RMS voltage between healthy phas e = 1x105
and faulty phase Time to reach maximum restriking voltag e
Factor pole to clear factor =
Phase to neutral voltage with faul t Maximum tn, = lc .j L C =
1x105
remove d
Maximum restriking voltage,
In three phase systems if fault does not involve the earth, the voltage across the circui t = 2 Var
breaker pole first to clear is 1 .5 times the phase voltage . The arc .extinction in the three pole s
of three phase circuit breakers is not simultaneous as currents are 120° out of phase. I n = 2K1 K2 K3 E m
practical systems the recovery voltage of the pole first to extinguish the arc is of the order o f = 2 x 0 .9165 x 0 .9 x 1 .5 x 107 .77 x 10 3
1.2 to 1.5 times of the phase voltage . = 2.66682 x 10 5 V
If fault involves earth and the neutral is grounded through reactor, the recovery voltag e Average RRRV,
is influenced by the equivalent system reactances . Maximum restriking voltage 2 .66682 x 105
Thus in 3 phase circuits K3 = 1 if neutral is earthed and fault is also earthed. While Time to reach maximum restriking voltage lc / 1 x 10 5
K3 = 1 .5 if neutral is earthed and fault is insulated or neutral is insulated and fault is earthed . = 8.48 x 10 9 V/sec
Ex. 1.1 : In short circuit test on a 3 pole, 132 kV circuit breaker, the following observations ar e = 8 .48 x 10° kV/sec = 8 .48 kV/µsec
made pf of fault 0 .4, recovery voltage 0 .9 times full line value, the breaking curren t Ex. 1.2 : In a short circuit test on a 130 kV, 3 phase system, the breaker gave the following results :
symmetrical, frequency of oscillations of restriking voltage 16 kHz . Assume neutral i s pf of fault 0 .45, recovery voltage 0 .95 times full line voltage, breaker current
grounded and fault is iaot grounded. Determine average,R-RRV.
symmetrical, andrestriking transienr7f a natural frequency 16 kHz . Determin e
t average RRRV . Assume fault is grounded .
Sol. : e= V. 1- cos
,jLC _ (V.T.U. Aug .2002 )
where
Vac
= Kl K2 K3 Em Sol. : x130
= 106 .144 kV
Kl takes into account p .f. effect
= sin ck. K l K, K3 E m where K 1 = sin = 0.893 0
K2 = takes into account armature reaction effect 0 .9 Er/"= 0.8930 x 0 .95 x 1 x 106 .144 K2 = 0 .9 5
K3 = Phase factor or 1 St pole to clear factor = 90.047262 kV K3 = 1
1 for both neutral and fault grounded : Maximum e = 2 Var = 180:09452 kV
1 .5 for any one of the two not grounded . Maximum time 1
= 7t .\/ L C and f=
In the problem, n 27t .\/ L C
K l = sin = sin [cos-1 0 .4] = 0.9165 1
Maximum t = 1 =
K2 = 0.9 K3 =1 .5 2fn 2x16x10 3
Peak value of voltage i.e. line to ground
= 132 Average RRRV = Maximum e = 180 .0945 2
Em x.\/ =107 .77 kV Maximum t 1/2x16x10 3
3
= 5.76302 kV/µsec
Principles of Circuit Breakers VTU -Switchgear and Protection 23 Principles of Circuit Breakers
VTU -Switchgear and Protection 22
Maximum voltag e
Ex. 1 .3 : Calculate the RRRV of 132 kV circuit breaker with neutral earthed . S .C . data as follows : Average RRRV =
Broken current is symmetrical, restriking voltage has frequency 20 kHz, p f 0.15. tm
Assume fault is also earthed. 21 .212
Sol. : K = sin= sin (cos 0 .15)
4 [1/(2x14 .1227x103 ) ]
= 0 .988 6 = 0 .599 kV/ µ sec
K, = 1 In a system having 220 kV, the line to ground capacitance 0 .015µF, inductance 3 .5 H.
Ex. 1.5 :
K3 = 1 both grounded Determine voltage appearing across pole of circuit breaker if a magnetising current o f
x132 6 .5 A instantaneous, is interrupted . Determine also the value of resistance to be use d
Em = = 107.77755 kV across the contacts to eliminate the restriking voltage .
,l 3 (
t
Var = K1 Kz K 3 Em Sol . : e = E. 1- cos
.JLC J
= 106.54889 kV
Maximum e = 2 Va r 1Li' = 1 CeZ
= 213.09778 kV 2 2
tm =it .JLC
Energy stored in 'L' = energy given to capacito r
e = i .J L / C where i = instantaneous valu e
and f„ = 1 Tti j LC = tm = 1sec
2n.JLC 2fr, 3 .5
= 6.5
(0 .015x10-6)
Maximum tm = 1 sec
2x20x10 3 = 99.3 kV
213 .09778
RRRV -= emax To eliminate restriking voltage and critical damping condition ,
t max [1 / (20 x 10 3 x 2)] R = 0.5,JL/ C
8 .52 kV/ µsec 3 .5
= 0.5 = 7 .635 kS2
Ex.1.4 : A50Hzgenerator hase•m f toneiitral7.5kV(r•m•s•)•Thereactance ofgenerator andthe ( 0 .015x10 -6 )
connected system is 4 St and distributed capacitance to neutral is 0 .01 µF with resistance
negligible . Find, Ex . 1.6 : A 50 Hz, 3 ph alternator, has rated voltage 13 .5 kV, connected to circuit breaker,
inductive reactance 4 S1/ph, C = 2 µF .
i) maximum voltage across the circuit breaker contact s
Determine maximum RRRV, peak restriking voltage, frequency of oscillations .
ii) frequency of oscillation s
J2x13 . 5
iii) RRRV average upto first peak of oscillations . Sol . : E. = = 11.0227 k V
Sol. : X=2TCfL=4S2
L = 4/2TCx50=0 .0127H. X = 27cfL .•L=0 .0127323 H and C=2µ F
Em = .,G x 7.5=10 .606k V fn = 1 = 0.997 kH z
1) Maximum voltage = 2 x Em 2 Tc.J L C
= 2x10 .606=21 .212 kV Maximum restriking voltage = 2 E m
_ 1 _ 1 = 22.0454 kV
2 fn
2 11,f LC 2tc*0 .0127x0 .01x10-6 t
e=Em 1-cos
= 14.1227 kHz j--'C )
3) Maximum time to reach maximum voltage is , de -
E1 sin t This is the expression of RRRV
tm = Tc . J LC = 1 = 1 sec dt m l/ Lc .JL C
2 fr , 2x14 .1227x10 3
VTU -Switchgear and Protection 24 Principles of Circuit Breakers 25 Principles of Circuit Breaker s
VTU -Switchgear and Protection
Em 1
Maximum RRRV = and fnn =
JLC 2n.\/ L C
Maximum RRRV = 2 nfn Em
= n x 0.997 x 10 3 x 22 .0454 kV/sec
= 0 .06907 kV/ pse c
current rating of the breaker . Interrupting such current causes severe duty on the circui t While interrupting low inductive currents the rapid deionization of contact space an d
breaker. This phenomenon is called current chopping . blast effect may cause the current to reduce abru .tl to zerowell before tHe natura current
Consider the circuit shown in the Fig . 1 .22.(a) . zero. 't'his currén c sopping causes very serious volt e oscr ations .
L the arc current be i when it is chopped down to zero value . The stored energy in the
inductor which 1 L i 2 will be discharged in to the capacitanc that the capacitor is charge d
to a prospective voltage V such that ,
e = E m sinwt Load 1 Li2
= 1 CV2
✓2 2
-= i,f L / C volts
Fig . 1 .22 (a) Circuit diagram showing interruption of inductive currents This prospective voltage is extremely high as compared to the normal system voltage .
The frequency of natural oscillations is given by ,
1
Current finall y fn =
suppressed before - 27c.,JL C
natural zer o
To understand this point let us consider a small example of 220 kV circuit breake r
interrupting a magnetizing current of 10 A r .m.s . of transformer . Let the current be choppe d
at the instantaneous value of 7A . Let the value of inductance and capacitance be 35 H an d
0.0020µF
Assuming that all the inductive energy is transferred to capacitance and using the abov e
formula,
e=7
e = 926 kV
This voltage will appear across the circuit breaker contacts . Such a transient voltag e
having high RRRV appears across the contacts . There will be restriking of arc at some point .
If the arc restrikes further, chop may occur . Thus before final interruption of current ther e
will be many chops and the circuit breaker will fail to clear the fault . Alternately if th e
restrike does not occur, the severe voltage stress will appear across circuit breaker contacts .
The rise of voltage before restriking is an important factor . The lower is the rate of rise,
more is the time required for deionization and high voltage will be reached .
After first chopping the deionising force which is still in action acts and second chop o f
current takes place . But the arc current is now smaller than the previous one and arc curren t
collapses and restriking voltage is again build . Thus a sequence of chops will occur and ar c
will continuously decrease until a final chop brings arc current to zero . There will not be any
further restriking as the gap is almost deionise . This is represented in the Fig . 1 .22 (b) .
I2(S) 2 2
R s (s + x)2 + ( 5) (s + x) 2 + 1/*)
Fig . 1 .2 5 It can be seen that with the value of the resistance R equal to or less than L / C, th e
2
Applying KVL to loop (I) oscillatory nature of the transient will not be there and RRRV will be within the permissibl e
V 1 limits of circuit breaker .
I1 (s) (s)
s sC 1 s C 12
VTU -Switchgear and Protection 30 Principles of Circuit Breakers VTU-Switchgear and Protection 31 Principles of Circuit Breaker s
R = 12 .24kS .
R> 2 1 .16 Arc Extinctio n
I The electric discharge which is taking place between the electrodes is nothing but th e
electric arc . We have seen that when contacts of circuit breakers are separated, an arc i s
established between the contacts which will last for some period . The circuit breaker shoul d
be capable of extinguishing this arc without damaging . The behavior of circuit breaker i s
greatly influènced by the arc .
R< 2
Interrup ti on of arc in case of d .c . circuits is much more difficult than that in case of a .c,
Fig . 1 .2 6 circûits . In a .c. currents the natural current zero point is available where the arc vanishes an d
prevented from restriking .
In air blast circuit breakers it is observed that the rate at which dielectric strength of ga p
increases is lower than in oil breakers . Since air has a much lower dielectric strength than th e The arc extinction in case of circuit breakers is not taking place frequently but still i t
gases at same temperature and pressure in oil circuit breaker . The dielectric strength of a ga s produces 10t of stress on the breaker . The different methods adopted for the arc extinctio n
increases with pressure . Thus the air blast circuit breaker is more sensetive to restrikin g can be grouped into following three categories ,
voltage transient . In low or medium voltage air blast circuit breaker the rate or rise o f
restriking voltage is higher . Thus shunt resistors are used for low and medium voltage ai r 1 .16 .1 High Resistance Interruptio n
blast circuit breakers . Also in case of oil circuit breakers the resistance switching is no t In this technique the resistance of current path is increased rapidly so that voltage dro p
employed as it is not sensitive to RRRV. is increased . The arc gets 'Extinguished when the system voltage is insufficient to maintai n
Ex .1.7 : In 132 kV transmission system, the phase to ground capacitance is 0 .01 µF. The 1 arc ue to high voltage drop . This is normally used in d .c. circuit breakers and air brea k
inductance being 6 H . Calculate the voltage appearing across the pole of a circuit breake r type a .c circuit breakers having low capacity . The system inductance stores the energ y
if a magnetizing current of 10 A is interrupted . Find the value of resistance to be use d which is dissipated in the arc .
across contact space to eliminate the striking voltage transient .
1 .16 .2 Low Resistance or Current Zero Interruptio n
Sol . . L=6 H This method is used only in case of a .c . circuit breakers . At the natural current zero point
C = 0 .01µF=0 .01x10-6 F of a.c . wave the arc is interrupted and is prevented from restrikin g tho n
i=10 A <mp*voltage by increasing the dielectric strength of the contact gap . This metho• i s
Voltage appearing across poles of circuit breaker, is given by , used in high power a .c. circuit breakers .
L 1 .16 .3 Artificial Current Zero Interruptio n
V=i
C In HVDC systems this method is employed for breakin d .c. currents where current is
made zero artificially
`Whir:- Switchgearand Protection 32 VTU - Switchgear and Protection 33 Principlesof Circuit Breaker s
Principles of Circuit Breakers
In circuit breakers the deionization is an important process as it supports ai'c éxtinctiôn . The various methods of high resistance and interruption are ,
This can be discussed in short as follows, 1. Lengthening the ar c
2. Splitting of arc
3. Cooling of arc
VTU -Switchgear and Protection 35 Principles of Circuit Breakers
34 Principles of Circuit Breakers
VTU-- Switch ear and Protection
1 .21 Low Resistance or Zero Point Extinctio n
1 .20.1 Lengthening the Ar c
In this method the arc length is increase d This method is used in a .c . arc interruption . The current becomes zero two times in a
Final position of ar c by using arc runners which are horn lik e cycle . So at each current zero point the arc vanishes for small instant and again it appears .
blades of conducting material . The arc
But in a .c . circuit breakers the arc is interrupted at a current zero point . The space
ri Electromagne ti c runners are connected to arcing contacts an d
force in upward between the contacts is deionized quickly if there is fresh unionized medium such as oil o r
it is in the shape of letter 'V' . The arc i s
direction fresh air or SF 6 gas between the contacts at current zero point . This will make dielectri c
initiated at the bottom and blows upward s
strength of the contact space to increase such that arc will be interrupted and discontinue d
due 'to electromagnetic force . Due to this arc
Arc initiation after current zero . This action produces high voltage across the contacts which is sufficien t
length increases and .consequently .,arc i s
to reestablish the arc . Thus the dielectric strength must be build more than the restrikin g
extinguished .
Fig . 1 .28 Arc lengthenin g voltage for faithful interruption of arc . Then the arc is extinguished at next current zero .
While designing the circuit breakers the care is taken so as to remove the hot gases fro m
1 .20 .2 Splitting of Arc
In this method elongation of arc is done and the arc is split using arc splitters which ar e the contact space immediately after the arc . So that it can be filled by fresh dielectric mediu m
having high dielectric strength .
specially made plates of resin bonded fibre glass . These plates are placed in perpendicula r
path-to-arc so that it will be pulled towards it by . electromagneticforce, When the arc'is In summary we can say that the arc extinction process is divided in thee parts ,
pulled upwards it gets elongated then split and cooled . due to which,it gets extinguished . a) Arcing phas e
This is shown in the Fig .11 .29 . b) Current zero phas e
c) Post arc ; phas e
In arcing phase, the temperature of the contact space is increased due to the arc . The heat
produced must be removed quickly by providing radial and axial flow to g ases . The arc can
not be broken abruptly but its diameter can be reduced -by the passage of gas over the arc .
When a .c. current wave is near its zero, the diameter of'thé'arcis very less and consequentl y
arc is extinguished . This is nothing but current zero phase . Now in order to avoid the
reestablishment of arc, the contact space must be filled with dielectric medium having hig h
dielectric strength . This is post arc phase in which hot gases are removed and fresh dielectri c
medium is'introdûced ,
Cas su„ested that the reestablishment of arc or interruption of an arc bot h Marc
alone roces _ If th ; - •• ' • - - - e■ u m r increase the arc re • . nn f
ot, ge s interru . Fig . 1 .31 Waveform of a .c . arc
The theor makes the following assumptions : Examples with Solution s
consists of a cylindrical column having uniform temperature at its cross section .
The energy distributed in the column is unifor m Ex . 1.8 : A 50 cycles, 3 phase alternator with grounded neutral has inductance of 1
.6 mH per phas e
temperature remains constant . and is connected to busbar through a circuit breaker . The capacitance to earth between th e
cross section of the arc adjusts itself to accomodate the arc current . alternator and circuit breaker is 0 .003 p*F per phase . The circuit breaker opens when rm
s
d wer dissipation is proportional to cross sectional area of arc colum n
value of c urrent is 7500 A . Determine the following :
The energy equation as expressed by Cassie is given by , i) Maximum rate of rise of restriking voltage .
ii) Time for maximum rate of rise of restriking voltage .
dQ = EI- N
dt iii) Frequency of oscillation s
where Q = Energy content / length of arc in c m Neglect first pole to clear factor . (V .T.U. Feb .2003, Aug .2003 )
E = volts / c m Sol. : i= 7500 A, L = 1 .6 mH, C = 0.003 }IF
I Total curren t XL = 27c f L = 2 7c x 50 x 1 .6 x 1 0-3 = 0.5026552
N = Total power loss / cm Peak value of active recovery voltage (Phase to neutral) i .e.
Breakdown occurs if power fed to the arc is more than power loss . The theory is true fo r Em = (i x XL) x = (7500 x 0.50265) x
high currents. = 5331.4083 V
Irnr rately after current zero, contact space contains ionised gas and therefore has a fn = frequency of oscillations = 1
fipost zero resistance . 27c-‘/LC
Now there is risin : restriking volta • e . This risin• restrikin• volta : e causes a current to 1
flow tween the contacts . Due to this current flow, over .• ets dissi p ated as heat in the 27E11 .6 x 10 -3 x 0 .003 x 10" 6
ntact space of circuit breaker. IE * *
•
Initially when restriking voltage is zero, automatically current and hence power is zero . = 72643 .96 Hz
It is again zero when the space has become fully deionise and resistance between th e Maximum RRRV = 27c fnEm = 27c x 72643 .96 x 5331 .4083
.ev\.`E-a-&.,h e/t
A '. t h AG .m H
P- ?I,.
VTU -Switchgear and Protection 38 Principles of Circuit Breaker s VTU -Switchgear and Protection 39 Principle s o f Circui t Breaker s
-m
= 2433443822 V/se c 3 . In a short circuit test the breaking current is symmetrical and the restriking transient had a natura l
= 2433 .4438 V/µsec frequency of 16 kHz . Determine the rate of rise of restriking voltage, if the power factor is 0 .45 and th e
system is 132 kV, 3 phase grounded one . Recovery voltage is 0.95 of full line value.
Time for maximum RRRV = = 3 .4414 sec
(Aug.2002, 10 Marks )
Review Question s 4. Explain how current interruption takes place in an AC circuit breaker . (Feb .-2003, 10 Marks)
1 . Define a circuit breaker ? Describe its operation in brief. 5. What is resistance switching ? Derive an expression for 'R' critical. (Feb .-2003, 10 Marks)
2 . Discuss the arc phenomenon in a circuit breaker . 6. A 50 cycles 3 ph alternator with grounded natural has inductances of 1 .6 mH per phase and i s
3 . What are different arc interruption methods ? Explain any one. in detai l connected to bus bar through a circuit breaker . The capacitance to earth between the alternator an d
circuit breaker is 0.003 µF per phase . The circuit breaker opens when rms value of current is 7500 Amp.
4 . Explain the following terms related to circuit breaker.
Determine the following :
i) Arc voltag e
Frequency of oscillatio n
ii) Restriking voltage
Maximum rate of rise of restriking voltage (Feb .-2003, 10 Marks)
iii) Recovery voltage
7. Write a short note on Slepian's theory of arc interruption (Feb : 2003, 5 Marks )
5 . Explain the fault clearing process by giving oscillographs of short circuit current .
8. Derive an expression for short circuit current in an R-L series circuit with an alternating current source .
6 . Discuss the effect of various parameters on TRV . Show that the current has a d .c . component and a .c. component. (Aug.2003, 10 Marks )
7. Obtain an expression for rate of rise of restriking voltage . 9. Explain in detail the theories which explain arc extinction phenomenon . (Aug .2003, 10 Marks )
8 . Explain resistance switching as applied to circuit breakers . 10. A 50-cycles, 3-phase alternator with grounded neutral has inductance of 1 .6 mH per phase and is
9 . Explain in detail the theories which explain the arc extinction phenomenon . connected to busbar through a circuit braker . The capacitance to earth between the alternator and th e
circuit-breaker is 0 .003 F per phase . The circuit breaker opens when r. m.s. value of current is 7500 A.
10 . Write a note on interruption of capacitive currents.
Determine analytically the followin g
11 . Write a note on current chopping phenomenon . i) Maximum rate of rise of restriking voltage . .
12 . Explain in detail d .c. current breakin g ii) Time for maximum rate of rise of restriking voltage .
13 . A 3 ph alternator has line voltage of 11 kV . The generator is connected to . a circuit breaker. Th e iii) Frequency of oscillations.
inductive reactance upto circuit breaker is 5 4 per phase . The distributed capacitance upto circuit
breaker between phase and neutral is 0 .01 .iF. Determin e Neglect first pole to clear factor . (Aug .2003, 10 Marks )
a) Peak restriking voltage across circuit breake r
b) Frequency of restriking voltage transien t
c) Average rate of restriking voltage upto peak restriking voltage
d) Maximum RRRV (Ans . : 18 kV; 12637 c/s ; 0.456 kV I µ seem 714 v / µsec)
14 . In a short circuit test on a 3 pole circuit breaker of fault was 0 .4, the recovery voltage was 0 .95 times full
line voltage . The breaking current was symmetrical . The frequency of oscillations of restriking voltage
was 15000 c/s. Estimate the average rate of rise of restriking voltage . The neutral is grounded and fau n
involves earth . Neglect first pole to clear factor. (Ans. 4.8 kV I µsec)
15. In a system of 132 kV the circuit phase to ground capacitance is 0 .01 mF, the series inductance is 6 H.
Calculate the voltage appearing across the pole of a circuit breakers if a current of 10 A (instantaneous ,
in interrupted. Calculate value of the resistance to be used across contact space to eliminate th e
restriking voltage transient . (Ans . : 245 kV ; 12.25 Ica
University Question s
1 . Explain the problems involved in interruption of low inductive currents and capacitive circuits .
Mark s
(Aug .2002, 10
2. Explain the arc interruption methods used in . high voltage circuit breakers . (Aug .2002, 10 Marks
41 Circuit Breaker s
VTU - Switchgear and Protection
Tri p
coil
Circuit Breakers Automati c
mechanism fo r
opening and closin g
the circuit breake r
contacts
2.1 Introductio n
As already seen in the last chapter, whenever any fault occurs in the power system the n
that part of the system must be isolated from the remaining healthy part of the system . Thi s Fig . 2 .1 Basic action of circuit breake r
function is accomplished by circuit breakers . Thus a circuit breaker will make or break e
a Under normal working conditions the e .m .f . produced in the secondary winding of th
circuit either manually or automatically under different conditions such as no load, full loa d . Thus th e
or short circuit . Thus it proves to be an effective device for switching and protection o transformer is insufficient to energize the trip coil completely for its operation
e
different parts of a power system . f contacts remain in closed position carrying the normal working current . The contacts can b
opened manually also by the handle .
In earlier days fuse was included in the protective system . But due to some limitation
Under abnormal or faulty conditions high current in the primary winding of the curren t
they are not used in practice now a days . The main difference between a fuse and circuis s
t transformer induces sufficiently high e .m .f . in the secondary winding so that the trip coil i e
breaker is that under fault condition the fuse melts and it is to be replaced whereas the circui t . This action will not b
breaker can close or break the circuit without replacement . energized . This will start opening motion of the contacts
instantaneous as there is always a time lag between the energization of the trip circuit an d
d
2 .2 Requirements of Circuit Breake r the actual opening of the contacts . The contacts are moved towards right away from fixe
contact .
The power associated with the circuit breakers is large and it forms the link between th As we have seen already the separation of contacts will not lead to breaking o r
consumers and suppliers . The necessary requirements of circuit breakers are as follows e s
, interruption of circuit as an arc is struck between the contacts . The production of arc delay
1. The normal working current and the short circuit current must be safely interrupte y
the current interruption and in addition to this it produces large amount of heat which ma
by the circuit breaker . d y
damage the system or the breaker . Thus it becomes necessary to extinguish the arc as earl
as possible in minimum time, so that heat produced will lie within the allowable limit . Thi s
2. The faulty section of the system must be isolated by circuit breaker as quickly a
possible keeping minimum delay . s will also ensure that the mechanical stresses produced on the parts of circuit breaker are less .
3. It should not operate with flow of overcurrent during healthy conditions The time interval which is passed in between the energization of the trip coil to th e
. It is dependent on fault curren t
4. The faulty circuit only must be isolated without affecting the healthy one instant of contact separation is called the opening time .
. level .
\/ 2 .3 Basic Action of a Circuit Breake r The time interval from the contact separation to the extinction of arc is called arcin g
e
The Fig. 2 .1 shows the elementary diagram of a circuit breaker time . It depends not only on fault current but also on availability of voltage for maintenanc
. It consists of two contact s of arc and mechanism used for extinction of arc .
a fixed contact and a moving contact
. A handle is attached at the end of the moving contact .
It can be operated manually or automatically . The automatic operation needs a separat 2 .4 Classification of Circuit Breakers
mechanism which consists of a trip coil . The trip coil is energized by secondary of the currene
transformer . The terminals of circuit breaker are brought to power supply t v The circuit breakers are classified by various ways . The different criteria for
.
classification of circuit breakers are as follows ,
i) Interrupting mediu m
ii) According to servic e
iii) Way of operation
(40)
VTU -Switchgear and Protection 42 Circuit Breakers Circuit Breaker s
VTUSwitchgear and Protection 43
iv) Action
13
v) Method of contro l
vi) Way of mounting
L
A
vii) Tank constructio n
viii) Contacts p 111N!1 MID PIIIIIS
•'J)I L
According to the interrupting medium the circuit breakers-are classified as air circui t L
breaker, air blast circuit breaker, oil circuit breaker and magnetic blast circuit breaker . 12
According to service there are two types of circuit breakers viz indoor circuit breake r
and outdoor circuit breaker .
Depending on the operation, the types of circuit breakers are gravity opened, gravit y
closed and horizontal break circuit breaker . r 7
On the basis of action, the circuit breakers are classified as automatic and non-automati c
circuit breaker .
According to method of control, the circuit breaker may be controlled directly or it ma y
be operated remotely . The remote control may be manual, pneumatic or electrical .
END-VIEW
'ELEVATION
The way of mounting classifies the circuit breakers into panel mounted, rear of panel o r
remote from panel type . One pole of an extra high voltage air blast circuit-breake r
' Depending on the tank construction, the circuit breakers are classified as separate tan k
for each pole type or one tank for all poles type .
13
On the basis of contacts, the different types of circuit breakers are Butt, Wedge ,
Laminated flat contact, Explosion chamber etc .
Out of the various ways of classification of circuit breakers the general way o f
10 10
classification is on the basis of medium used for arc extinction which is normally oil, air , 15
Sulphur Hexa Flouride (SF 6) or vacuum . I b b. % Er
Each type of circuit breaker is associated with its own advnatages and disadvantages .
We will now consider some types of circuit breakers in detail .
The double arc extinction chamber is shown separately in the Fig . 2.2 (b) . It can be seen The flow 'r is across the arc. The moving contact is near to the arc splitter assembly .
that for each circuit breaker pole there are six breaks as there are three double arc extinctio n The a; ast forces the arc on to the arc splitterplates . These plates will lengthen the arc .
poles in series . Each arc extinction chamber consists of two fixed and two moving contacts . Depen itng upoh 'the breaking capacity of thé breaker, the size and number of plates ar e
These contacts can move axially so as to open or close . The position depends on air pressur e decided. The fixed contact is mounted at the base between the two insulating blocks . It
and spring pressure . The opening rod is operated by the opening mechanism when it get s consists of a number of silver surfaced spring loaded copper fingers . The arcing portion is
control signal (may be electrical or pneumatic) . This will lead to flow of high pressure air by surfaced with a silver tungsten alloy. The moving contact consists of flat copper silver faced
opening the valve . The high pressure air enters the double arc extinction chamber rapidly . blade . Resistancé switching is not required as sufficient resistance is automaticall y
Due to the flow of air the pressure on moving contacts increases than spring pressure an d not ced in the ,arc to control the restriking transient . The cross blast breakers are
contacts open . The contacts travel through a small distance against the spring pressure . Due y used -in indoor circuit breakers of medium high voltage class .
to the motion of moving contacts the port for outgoing air is closed and the whole ar c Axial Blast Typ e
extinction chamber is filled with high pressure air . But during the arcing period the ai r
passes through the openings shown and takes away ionized air of arc . In case of makin g this type the flow of 1 ast of air is along t his is sl-,Lown in the Fig . 2.4.
operation the valve is turned which connects hollow column of insulator and the reservoir .
The air is passed to the atmosphere due to which pressure of air in the chamber is dropped t o
atmospheric pressure and closing of moving contacts is achieved against spring pressure .
2 .5 .2 Workin g
An auxiliary compressed air system is required by this type of circuit breaker . This will
supply air to the air reservior of the breaker . During the opening operation, the air is allowe d
to enter in the extinction chamber which pushes away moving contacts . The contacts are
separated and the blast of air will take ionized gases with it and helps in extinguishing th e
arc . This will require only one or two cycles . There are two major types - cross blast and axia l
blast.
In cross blast type, the blast of air cuts across the arc . It is less frequently used in th e
prac ice . In axial blast type, the blast of air is along the arc . This type of design is common i n
u
.5 .2 .1 Cross Blast Typ e
The Fig. 2 .3 shows the schematic arrangement of a cross blast
There are two subtypes which are shown in the Fig . 2.4 (a) and (b) viz single blast typ e
and double blast type . The double blast arrangement is also called radial blast type due t o
the fact that the blast flows radially into the space between the contacts .
In this type air flows from high pressure eservio to the atmosphere through a nozzle .
Whose design makes air tb expand in the lowp zone . It`will ttain high ve ocr
ty l - e
high speed air flowing axially along the arc will cause removal rom the periphery of
the arc . The diameter of arc reduces to a low value at current ze. t this instant of the ar c
interruption the contact space is filled with the fresh air . This will make possible to remove
Fig. 2 .3 Cross blast type circuit breaker the hot gases and fast building up of the dielectric strength of the medium .
VTU -Switchgear and Protection 47 Circuit Breaker s
VTU -Switchgear and Protection 46 -Circuit Breaker s
After the arc extinction the pressure on either side of auxiliary contacts is adjusted i n
As already seen during the contact closing, the air from the extinction chamber i s
allowed to pass to the atmosphere . This will reduce the pressure on the moving contacts an d such away that auxiliary contacts open and resistor circuit is interrupted . Cerami c
will assist the closing operation . The total operation is represented in the Fig . 2.5 .. resistances of non=linear characteristics are used for resistance switching .
The size of compressor depends upon the number of circuit breakers, the number o f This type of circuit breaker is employed in both a .c . and d.c . type of circuits upto 12 kV .
makes and breaks expected and amount of air to be used in each make and break . The These are normally indoor type and installed on vertical panels . The lengthening of arc is
compressor feeds the air at high pressure into the main receiver through oilfiltérs and wate r done with the help of mangetic fields . Some typical ratings of this type of circuit breaker ar e
460V - 3 .3 kV with current range 400 - 3500 A or 6 .6 kV with current range 400-2400 A etc .
filters.
2.6.1 Constructiô n
2.5.4 Advantage s
The various advantages of air blast circuit breakers are, The Fig. 2 .7 shows the constructional details of air break circuit breaker .
o fire hazards are possible with this type of circuit breaker .
ze high speed operation is achieved .
r
he time for which arc persists is short . Thus the arc gets extinguished early . tit *P1
sarc duration is short and consistent, the amount of heat released is less and th e r f)
contact points are burnt to a less extent . So life of circuit breaker is increased .
v) The extinguishing medium in this type of circuit breaker is compressed air which i s
supplied :fresh at each operation . The arc energy at each operation is less than tha t
compared with oil circuit breaker . So air blast circuit breaker is most suitable where
frequent operation is required .
is type of circuit breaker is almost maintenance free .
provides facility of high speed reclosure .
',The stability of the system can be well maintained .
2 .5.5 Disadvantage s
The various disadvantages of air blast circuit breakers are,
air blast circuit breaker is to be used for frequent operation it-is necessary to have a
scompressor with sufficient capacity of high pressure air .
he maintenance of compressor and other related equipments is required .
There'is possibility of air leakages at the pipe fittings .
(I) Contact closed (II) Contacts ope n
is-very sensitive to restriking voltage . Thus current chopping may occur which
may be avoided by employing resistance switching . Principle of air-break circuit-breake r
1. Main contacts 5 . Arc splitter plate s
2.5.6 Application s 2.Arcing contacts 6 . Current carrying terminal s
The air blast circuit breakers are preferred for arc furnace duty and traction syste m 3. Arc rising in the direction of the arrow 7 . Arc runner s
4.Arc getting spli t
because they are suitable for repeated-duty. Thesetypeof circuit=breakers .arefinding their
best application stems operating in range of 132kV~to 400 kV with breaking capacitie s
Fig . 2.7 Construction of air break circuit breaker
upto 7000M
It consists of two sets of contacts .
1)Main contacts
In air circuit breaker the ressure air is used as an arc extinguishing 2) Arcing contacts
medium. The principle o f employed for such type ofbreakers . During the normal operation the main contacts are . closed . They are having lo w
The length of the arc is increase . usm runner hich will increase its resistance in s uc h resistance with silver plating . The arcing contacts are very hard, heat resistant . They are
a way that the voltage drop across the d o comes more than the supply vo lta g e and the arc made up of copper alloy . Arc runners are provided at the one end of arcing contact . On the
will be extinguished . upper side arc splitter plates are provided .
Circuit Breakers VTU -Switchgear and Protection 51
VTU -Switchgear and Protection 50 Circuit Breaker s
27Iphur Hexafluoride (SF6) Circuit Breake r
2.6 .2 Workin g .
As seen from the Fig . 2 .8 the contacts remain in closed position during normal condition
. The Pure sulphur hexafluoride gas is inert and thermally stable. It is having good dielectri
Whenever fault occurs, the tripping signal makes the circuit breaker contacts to open and arc extin uishin ro erties . It is ô an electronegativegas and has strông tendency t c
absor ree electrons . SF6 gas remains in gaseous state upto â temperature of 9°C o
arc is drawn in between the contacts . Its density
is a out five times that of air and the free heat convection is 1 .6 times as much as that of air .
Also being inert it is non-inflamable, non-piisonous and odourless .
Contact
The contacts of the breaker are opened in a high pressure flow of SF, gas and an arc i
struck between them The conducting electrons from the arc are captu - . 0 . he as to forms
Current r$ unmo Ile neative ions . The loss of this conducting electrons developes enou
(a) Contact close d
strength of insulation which--wrl extinguish tl ° a,'c. Thus SF6 circuit breakers are found toghen
very effective for high power and high voltage service and widely used inelectrica l
e•'••
Current
L in y t e care o e to en is that some by-products are produced due t o
b ea down of gas which are hazard to the health of the personnel and it should be properl y
disposed .
(b)Contacts separate d
Several types of S F6 circuit breakers are designed by various manufacturers in the worl
d
during the recent years which are rated for voltages from 3 .6 to 760 kV.
The property of this gas is that the gas liquifies at certain low temperatures . The
Fig . 2.8 Working of air break circuit breake r liquification temperature can be increased with pressure This gas is commerciall y
Whenever the arc is struck between the contacts, the surrounding air gets ionised . The manufactured in many countries and now used extensively in electrical industry .
arc is then cooled to reduce the diameter of arc core . While separating, the main contacts ar e
. Later on the arcing contact s The gas is prepared by burning coarsely crushed roll sulphur in fluorine gas in a stee
separated first. The current is then shifted to arcing contains box. . The box must be provided with staggered horizontal shelves each containing about l
also start separating and arc between them is forced upwards by the electromagnetic force s kg of sulphur . The steel box is gas tight . After the chemical reaction taking place in the box4
. Further it moves upwards an d ,
and thermal action . The arc travels through the arc runners f the.SF6 ,gas obtained contains impurities in the form of fluorides such as S, Fio F4
, S etc. Thus it
plit by arc splitter plates . Due to all this finally the arc gets extinguished as the resistance o must be,purified before it is supplied . The manufacturing of this gas at large scale reduces it s
the arc is increased . .cost.
Due to lengthening and . cooling, arc resistance increases which will reduce the faul t The dielectric strength of S F6 gas at any pressure is more than that of air . When the ga s
.c. wave will
current and will not allow to reach at' high value . The current zero points in the a n comes in contact with the electric arc for long period, the decomposition effects are smal l
help the arc extinction. With increase in arc resistance the drop across it will go o and dielectric strength is not considerably reduced and the metallic fluorides that ar e
increasing . formed are good insulators and are not harmful to the breaker.
Whenever arc leaves the contacts it is passed through arc runners with the help of blo w 2 .7 .1 Properties of SF 6 Gas
out coils which provide a .magnetic field due to which it will experience a force as given by
. Th e The properties of SF6 gas are divided as,
electromagnetic theory (F = BI1) . This force will assist in moving the arc upwards
w
magnetic field produced is insufficient to extinguish the arc . For systems having lo g 1. Physical propertie s
inductances arc gets extinguished before reaching extremity of runners because lengthenin 2. Chemical propertie s
of arc will increase the voltage drop which is insufficient to maintain the arc .
3.Dielectric propertie s
For high inductance circuits if it is not extinguished while travelling through arc runner s
e
then it is passed through arc splitters where it is cooled . This will make the effectiv 2.7.1 .1 Physical Propertie s
deionization by removing the heat from arc . i) The gas is colourless, odourless, non-toxic and nonharmful to health .
ii) The gas is non-inflammable .
2.6 .3 Application s iii)It is heavy gas having high density .
This type of circuit breakers are commonly employed for industrialswitchgea r, iv)Liquification starts at low temperatures which depends on pressure .
auxiliary swithgear in generating stations . v) The heat transferability is high as compared to air at same pressure .
VTU -SwitchgearandProtection 53 Circuit Breaker s
Circuit Breaker s
52 After 2 .5 kgf/c m 2, the voltage starts reducing and then again increases . This pressure is
Protectio n r current called critical pressure . The dielectric strength at pressure between 2-3 kgf/c m 2 is high so i t
Switch ear and
VTU is much more which will assist cooling of arc afte is preferred in this type of circuit breakers . However pressure of 5 kgf/cm 2 may also b e
vi) The heat content proper ty selected for arc quenching purpose .
zero . v) With rough electrode surface, breakdown voltage reduces as ionisation starts earlie r
vii)The gas is electroneg ative . metallic part, contacts is near the sharp points . Hence the surface must be smooth .
Chemical Properti es . The life o . Hence the mainten anc e vi) The breakdown can occur at low values provided that the insulator supports ar e
2.7 .1 .2 The inert stable upto 500 C covered by moisture and conducting dust, as flashover may take place along th e
i)
6g The
gas is chemically components do not get deteriorated
flongeriSF of decom p ositio
n surface of support insulators . Hence insulators must be extremely clean .
requirements are reduced : decomposed to S F 4, SF2 . The products vii) The breakdown is initiated at sharp edges of conducting parts having maximu m
6i p os
al. stress concentration.Good dielectric stress distribution is important.
ii) During
are arc extinction, SF s are toxic and hence proper care mus t
l
C e ar e safe for electrica
al.
viii) The breakdown value depends on the wave shape charac t e ris ed by peak value,
. di electri c materials1He wave front, polarity in case of impulse wave etc . The breakdown voltages reduce s
iii)The metallic fluorides are good
times that of air and with increase in steepness and increase in duration of wave .
equip ment.
Properti e s as at atmospheric pressure is 2 ix) Even with dilution of SF 6 with air, its dielectric strength is not much affected . As
2 ;7,1 .3 Dielectric already seen the gas is electronegative so arc time constant is lower which is nothin g
dielectric strenght ofSFb,g the
30% less than that of dielectric oil .
he ii) At higher pressure, gas but the time required to regain dielectric strength by medium after final curren t
s strength o
dielec tric f ,very ma uch zero . This time is of the order of few microseconds in this type of circuit breaker .
Increases. This as smalle Thi r
advantage ou s Construction of Non-puffer Type SF 6 Breaker
clearances and small size o f
components are required for hows the constructional details of SF6 circu reaker . It consists o )
The variation i s herein fixed and moving contacts are nclose• . The chamber is filled
same kV-: - e c amber is connecte• to a reservoir containing 6 gas.
shown in the Fig . 2 .9
The breakdown voltage i n
iii) gas is a 'function of
SF6 e
pressure :The gas follows th
paschen`slaw Which giv eend
Insulated rods 1
for operatin g
' *
t co-
;,,-c?
ct.
°r, ,-
a
SF 6 Ga s
Inle t
as " In uniformly distribut isi moving member ,2 y1
Ni.
the breakdow n a\
electric
voltage in a gas ers
Fig 2.9 Qa . The
pressure and ,electrode, distribution gap" paramet c
of electri Arcin g
are normally consta nt .
proportional to the product of gas ation
prop e
support electro de configur horn
breakdown voltag curve doe s
field, vic sm oe against pressure*
o f sn voltage
t field, obey i Pfield
iv) If electric fie isnnit
Them thee breakdown
isasshown in the Fi
b• r
Fixe d
no aschen s o law . n membe r
Movin g
member
re
.10 The breakdown voltage increases with pressu
Fig . 2
55 Circuit Breaker s
VTU -Switchgear and Protection
reaker s
(pc** Co c 0 }p' f ,ê PC tr y S(--6CircuitB
The single flow pattern has limited quenching ability and is used for breaking currents .
547 I a,....*.
* Switch ear and Protectio n high The four stages of puffer action explains a trenching process in single flow puffer typ e
* -
7
Fixe d
contact Eg. j/%////U//
(a) Breaker fully closed (b) Contacts separated
2 .7.7 Application s
. Each unit is capable o f
circuit breake r A typical SF6 circuit breaker consists of interrupter units . A number of units ar e
.14 Double pressure type SF
I P2 .through
6
a converg ents interrupting currents upto 60 kA and voltages in the range 50-80 kV
Fig . •2
made to flow from zon covers the a . Gas flow attain t connected in series according to system voltage . SF6 breakers are developed for voltag e
gas is e as P g
In this circuit breaker is located such tha oflow thereby
gas takes away the hea ranges from 115 to 500 kV and power of 10 MVA to 20 MVA ratings an d, with interruptin
.
es
divergent nozzle, The nozlne divergent portion gFinally arc diameter becom
h
time of 3 cycles and less .
aalmos o ersonicarc ca*ngreduction in diameter of the arc . is filled with fresh SF s
s ee d 6 ga
r gcurrent zero and arc gets extinguished . Arc spac
m at tspa
fro ce .8 Vacuum Circuit Breaker s
almost tlmostzero
rr e t .
ao ewhicnrasdlteghofcna acuum type of circuit breake , vacuum s used as the arc quenching medium. It is
Circuit Breake r edium than any other arc quenc rig medium as vacuum off erg ug e
.5 Advantages of SF 6 .
2 .7 r ucircuit breakerthan are, conventional circuit breaker of same rating t
The advantages SF
smaller
ake products are no If we consider that the contacts of circuit breakers are opened in vacuum, th e
`*u11 he sizeo f ni6 n fl ker
breake
; 66 gas is noninflammable and chemically stable, decompositio interruption occurs at first current zero . The dielectric strength of the contact space builds up
very rapidly at a rate which is very much higher than that with other circuit breakers .
Say 2 e fire . isn f $assmall is small .
✓ ve d ce no dan m carrying .plosi ability o f When the contacts of the breaker are opened in vacuurr*, n arc roduced between th e
curren
f a
Same as is : ger Fo r of.5th times same size of conductors, t S a m e i s r
t breaker because o
c u l d n t h e f contacts due to ionisation of metal va ours of contacts, which can be explained b f* ield
la r overloa i than that of air blast tree i
ht. 4 breake r s is about 1 1
F 6ci rcc u ci r c ui t t
more heat transfera bility .
59 Circuit Breakers
VTU -Switchgear and Protection
s
CircuitB reaker
58
VTU - Switch ear and Protection contact rationbecaus e
hot spot is created at the instanl °e epa electrons an d
pours, o
emission theory n intensely quickly extinuished a of the breaker*cu** lead t
igh odue d Burin the arc are condensed on tl
surfacesButhearci as an to
t f teat ure • of
i
ions y overy Bunn . This is an importan , tfea r
re
re c over of dielectric
w is wi
strength
assist arc extinction + •' t s inter up ter e units e pole .
f brem vacuu dielectr ic
quen b u tle upbreake hon
yconsite e e sever al merits such a eh rate per ppl
prise mechani sm,
vacuum eav e oP of
The vacuum switching device e y for epeated operations, simpl
reration, suitabi lit d to b e
t silent o . mstrengh,ciu contacts are require
free from explosion and long life
. Many repeated operatio ns
The unique qualit of vacuum of breker interrupters of moving is that th ts
contac
d
travelled by small distances typ e
can be performed with thi m lvacu Th e
Electrical Breakdown in nigh of Vacuu
mercury are considered to be high vwaacc re unot m. caus e
2 8,1 '5 mm o towards other at such a pressu pparticles is les s
The pressure below about 10 de smogin g. Henceionizationby collision of
chargedpai*tict from one electro ga
e s molecules of residual the vacuum and voltage is.
collision with th .
in vacuum as compared to in theis gas e between th n electrodes i s nrapidly
1 (say 0.5 m m) kept th gap e breaks dow n andec raining emainin g nessta eaco the
If a smal gap at, a certain voltage With pressu r atai al r
increasned called vacuum breakdo wn . Fig . 2 .15 Construction of vacuum circuit breake r
Thduheyomeno d materi des. The possibility of leak is eliminated due to permanent sealing of vacuum chamber . The
The phenomenon is
breakdown chracener are
ec
influenced by surface, condition
emission takes p
an
lace from surface of the electrohigh
Few spots having hig outer insulator is made up of glass or ceramics
Due to high arci arced an
l ll be
a be at very high temperature
takes . plac ewfrom surfa ce
d,
an d core wil o n 2.8.3 Workin g
. Thus thermal emissi rs eHighatproduc e
rausefor arc formation in case of these breake When the contacts are separated due to some abnormal conditions, an arc is struc k
ent denies ac between the contacts . The arc is produced due to ionisation of metal ions and depends ver y
e leectrodes
uc which f much on material of contacts .
showsn the schematic representation showing the constructional details o The arc interruption process in vacuum interrupters is different from other types o f
2.8 .2 C onstructio
The Fig. 2 .15 : contact bn'stainless stee l
field a circuit breakers . The separation of contacts causes release of vapour which is filled in th e
fixed contact movie . nis rvacumitbek• contact space . It contains positive ions liberated from contact material . The vapour density
as .er • w11 'the contro l
by ar vas stee l depends on the current in the arc . When current decreases, the rate of vapour releas e
If to d a1 sin e a b l m r i s c o n t e c decreases and after current zero, the medium regains its dielectric strength if vapour densit y
•T The v cotonstruction of the interrupter disc sho m shaped
p faces .The dis g
belpowsTh e
The below s permit the r l sealed of large stem with f ea . contacts are not alon is reduced .
bellows . . The
T y mnricas are made eves -such that segments ô two eal of ra is are stable at When current to be interrupted is very small (of the order of few hundred amps) i n
s
d hie w wi i mef ac li gro w
protective
same
llo s remains ciinatf therapidemovement
tth . The o oarc in u ump ermeable vacuum, the arc has several parallel paths . The total current is divided into many paralle l
is .rovided. Thisgeo p enclosure sm e capabili
one line in diffused state re i s anodde p o f should hav e arcs which repel each other and spreads over contact surface . This is called diffused arc
same p agnetic metal .
one point and rr remains lass . . The material she . should gouge
p o f non m
the hey
which can be interrupted easily.
end flanges are made u
to retain materialt vacuum like glass At high values of currents, the arc gets concentrated on a small region . It causes rapid
.The s The supportin g shields are supported on insulating housing suchgthatt t t g y
to in high contact surface sur durin vapourisation of the contact surface . The interruption of arc is possible if arc remains i n
or vapour i enclosure .
The arc ct region . The metal vapour released from nsing the on t h e face diffused state . If it is quickly removed from the contact surface, the arc will be restriked .
cover the contac d on these shields and is prevented from conde
condense
VTU-'Switchgear and Protection 61 Circuit Breaker s
Circuit Breaker s
60
VTU - Switch a ear and
Protection The gases are liberated from the electrode material in the following ways ,
c material i) Evolution of gas from metal evaporated by anode and the cathode spots which ar e
vacuum breakers is greatly influenc edob ty he ar is kept shape moving soof
Arc e nd te c h in omet l 1 ' T he pa formed when arcing takes place .
contacts and technique of llontswill n a t be high . s ii)From the surface exposed to radiations from the arc, the gases are released .
that temperature at any p of dielectric str e1,rg th which ie iii)The gases are also released from the inactive portion of the electrodes due to the hea t
c upken. They
therey rapid
are suitable for capacitor switching ascurren it willt will givzero conduction from the portion of the electrodes which are arcing .
After final arc
vacuum breaker p t before naturaal Experiments are carried out on copper and oxygen free high conductivity copper . But it
e . releases more amount of gas . In contrast to that single crystal of copper was grown fro m
restrike
w a e of performa nce . Th
fre level depends on material contact
of
which may caus e molten metal which releases small quantity of gas . But, the process is very slow, costly and
the commercially not feasible . The another possible solution to this problem is to us e
The The
chopping
vapour levels are affected
pressure by, material with increase in vapour pressure
of cathode zone-refined copper which is gas free .
a) , leve
chopping level is lowered . 1 The metals like aluminium, copper, silver, tin etc were tested for electrode erosion . A t
The thermal conductivity, if thermal conductivity is low and the
some materials is given in the Table 2choppin . high currents the cathode spots formed shows a high vapour pressure that is supplied by
b) la
. Current chopping level for son galsow vapourisation . The loss from cathode, causes gain in weight for anode due to th e
condensation of cathode vapour on the anode when it is cold .
Another important thing that must be considered is that the electrodes should not wel d
with each other and dielectric strength of the gap must be recovered very rapidly .
Thus the requirements to be satisfied by a vacuum circuit breakers are complicated .
Hence no single metal is suitable for the electrodes . Thus the compromise is made and i t
shows that use of dicopper magnesium (Cu2Mg), dicesium copper (CuCe2 ), copper bismuth
(CuBi) gives the satisfactory performance .
2.8 .6 Recovery Strength Characteristic s
The satisfactory working of vacuum circuit breaker is possible if the electrical strengt h
after arcing is properly recovered . In this type of the breaker, the conducting medium of th e
arc is supplied by contact erosion and recovery of electric strength mostly depends o n
2 .8 .4 Advantag e s condensation of electrode vapour .
The advantages of vacuu A reduction in number of vapour ions lead to improvement in recovery strength .
t in m sze and have longer life . When pressure is reduced to such a value that the breakdown voltage is independent o f
i) They are compac
. pressure then under this case, the factors affecting breakdown voltage are the type o f
ii) There are no fire hazards aafter ult operation . contacts, contact surface etc . Highly polished electrodes has good breakdown strength .
iii) There is no generation of gas during of f .
cu
iv) There is no restriction on interruption 2 .8.7 Application s
This is outstanding quality of vacuum circuit In countries like India, the installation of such breakers proves to be effective as i t
nce operation . requires little maintenance . They are employed for outdoor installations ranging from 22 k V
v) They require less maintena
lly lightning surges . to 66 kV . With limited rating ranging from 60 to 100 MVA they are suitable in man y
vi) They can successfu applications .
vii) They have low arc energy . m.
have low inertia and hence smaller power is required for control mechamis Recently installed capacitor of such breakers are 11 kV, 25 kV and 33 kV .
viii)They Thus for voltages upto 36 kV, vacuum circuit breakers with single interrupter i s
t . erosio becoming extremely popular for metal enclosed switchgear, arc furnace installations ,
A major problem that occurs with this type of circuit breaker s electrode s isduring
tha arcing n iorr f auxiliary switchgear in generating stations and other industrial applications .
m .
material
actorfrom electrodes
materials and evolution
may result of current
into severe gases fro chopping because of low pressure
refi y
VTU -Switchgear and Protection 62 CircuitBreakers VTU-Switchgear and Protection 63 Circuit Breaker s
during normal operating condition . The lever containing the moving contacts can b Let a capacitor of 50 pF be connected as shown in the Fig . 2.19 .
operated with the help of crank .
When the contacts are separated, two arcs are drawn . Thus there are two breaks in . '
series . This can achieve rapid arc lengthening which eliminates the need for a specially fas t
moving contact speed . But this introduces unequal voltage distribution across the break s C I =10pp F
with uneven sharing of total interrupting duty . One break may take 70 to 80 percent of th e
interrupting duty .
When such a breaker interrupts an earth fault, the recovery voltage is not equall y c3 ± cl 1 C2= 40pp F
divided between the two breaks . This statement can be very well understood by considerin 50pp F
. 2 .18, where C1 represents capacitancegthequivalncr tshowineFg :
between fixed and moving contacts whereas C 2 represents capacitance between movin
. gcontaderh
2.9 .1 .5 Disadvantages of Plain Break Oil Circuit Breaker The major drawback with this type is that it cannot be used for very high or very lo w
-'aultcurrents . At low fault current values, the pressure developed is small thus arcing time
The various disadvantages of plain break oil circuit breaker are, . On the other hand at high fault currents due to very high pressure develope d
i) There is no special control over the arc other than the increase in length by separatins increased
the moving contacts . Hence large arc length is required for faithful interruption the explosion pot or chamber . Therefore it is suitable fo r
. here erate short circuit ur sting only.
ii)These breakers have long and inconsistent arcing times .
iii)These breakers do not permit high speed interruption . ;.9.2 .2 Cross Jet Explosion Po t
2.9 .1 .6 Applications It is the modification of plain explosion pot which is shown in the Fig . 2 .21 . The Fig. 2.21
Such types of circuit breakers are suitable upto 150 MVA capacity and hence installed ows the four stages of operation . It consists of cylinder made up of insulating material .
there are channels on one side which act as arc splitters . The use of arc splitters is to increase
low capacity applications having voltages not more than 11 kV. he arc length which will assist arc extinction by -lengthening the arc.
2 .9.2 Self Generated Pressure Oil Circuit Breaker In stage 1 shown in Fig . 2 .21 the moving contact has separated from the fixed contact an d
This type of circuit breakers are also called self blast oil circuit breakers where arfarc is formed while in stage 4 final arc extinction is shown where the moving contact i s
control is provided by internal means . The pressure developed by the arc is used in speeding t of the throat.
up the movement of oil in the contact space at the instant after the current zero . This ii,
achieved by surrounding the contact by a pressure chamber . This will make it possible tc
increase the breaking capacity of such circuit breaker while the arcing time is reduced .
The action of arc will itself set up pressure which is dependent on magnitude o f
currents . Thus proper design of pressure chamber must be done in order to ensure th a Oil
pressure developed is sufficient to extinguish the arc at low currents, while it should not br .
excessive which may break the chamber at heavy currents . Thus a wide variety of design ;,
are possible . Some of them are discussed below .
2.9.2.1 Plain Explosion Pot
This is shown in the Fig. 2 .20. Ij
consists of a rigid cylinder made up of ti Throat Movin g
contact
insulating material . The cylinder contain;:
the fixed and moving contacts . Tht (a) (b) (c) (d)
moving contact is a cylindrical rod which:
can pass through a small opening called
throat. The motion of moving contact i Fig. 2.21 Cross jet explosion po t
vertical . When an fault occurs, the moving contacts begin to separate . An arc is struck initially a t
e
Whenever fault occurs in the systerd top of pot. The gas formed exerts pressure on the oil when the moving contact move s
the contacts will start separating with thayfrom the arc splitter ducts, fresh oil is forced across the path of arc . The arc , is then
formation of arc in between them . Thelssedthrough the arc splitters due to which its length increases which causes the arc
heat contained in the arc causes thé tincti on.
Fig. 2 .20 Plain explosion pot decomposition of the oil into a gas at very This type of circuit breaker gives satisfactory performance at heavy fault currents .
high pressure in the pot . This high pressure forces the oil and gas around the arc t âowever for small fault current, pressure developed by gas which is function of faul t
extinguish it . arrent is less and the performance is not satisfactory.
It can be seen that if the final arc interruption does not take place while the moving9 .2 .3 Self Compensated Explosion Pot
contact is inside the pressure chamber then it occurs immediately after the moving contact This type is essentially a combination of plain explosion and cross jet explosion type
leaves the pot as emergence of moving contact from the pot allows a high velocity axial blast .
of gas to release through the throat producing rapid arc extinction . As the arc extinction ence it can interrupt low as well as heavy short circuit currents effectively . It is represente d
; the Fig . 2.22.
takes place axially of the arc, it is also called axial explosion type .
C
VTU -SwitchgearandProtection 68 CircuitBreak; ,, TU Switchgear and Protection 69 Circuit Breaker s
It consists of two chambers, the upl This- can be achieved by piston cylinder arrangement . The movement of piston is
chamber is the cross jet explosion pot ticoupled mechanically to moving contacts or spring released by tripping mechanism . This
Fixed contact arc splitter ducts, while the loa'rrangement enables high speed interruption .
rlw#i chamber is the plain explosion pot . When a fault occurs, the contacts get separated and an arc is struck . The piston forces a
When fault current is heavy, the let of oil towards the contact gap which will extinguish the arc . The typical scheme is show n
of generation of gas is very high and itthe Fig. 2.24 .
riAlreA Lateral act similar to cross jet explosion I :
®2 orifices When the moving contact moves av
from the arc splitter duct, th e
Cross je t extinction takes place .
explosion po t
When fault current is low the rat( '
gas generation is low and the tip
.wA' moving contact takes some time to r è
lower chamber . By this time the gas bû`
Moving contac t up sufficient pressure as there is no n i
leakage . When the moving contact cor
out of throat the arc is extinguished Fig. 2 .24 Externally generated pressure breake r
Fig. 2 .22 Self compensated explosion pot plain pot action . The performance of the breaker is constant even at low currents as pressure developed i s
With increase in fault current level, the operation will tend more and more similandependent of fault current to be interrupted . This can be seen from follownlg grap h
cross jet explosion pot . Thus interruption of fault current is possible in the wide rangepresented in the Fig . 2.25 .
2 .9.2 .4 Oil Blast Explosion Pot
It is shown schematical l 6
the Fig. 2 .23 . It consists oi-
intermediate contact alon g i N Self pressure
moving contact . Initially 4
intermediate contact and k
moving contact move down ' Externa l
together . An arc is struck bets ô 2 pressure
1 and 2 . The arc causes oil in u
chamber to be subjected t o
pressure . When the interme ( o
Breaking current
contact has reached its maxia.
travel, the lower contact s
Fig. 2.25 Operating time-breaking current characteristic s
moving away from it and a's
Fig . 2.23 Oil blast explosion pot struck between 2 and 3 . Since Another advantage is that quantity of oil required is reduced considerably. If curren t
lower contact is hollow rod it is shut down by pressure which was developed by first arcopping is there while interrupting small inductive currents then damping by resistanc e
this type has a disadvantage of long arcing time . witching is required .
t
VTU -Switchgear and Protection 70 Circuit Breaker; VTU -Switchgear and Protection 71 Circuit Breakers
percentage (about 10%) of oil is used for arc extinction process and major part is used f( .
insulation purposes .
A low or minimum oil circuit breaker uses a small container having oil which is jur
enough for arc extinction. The container of oil is supported on porcelain insulators, so t h
required insulation can be obtained for live parts from earth . Thus low oil circuit breaker h
added advantage that it requires less space than the bulk oil type . This is an importa i
consideration in large installations .
With respect to quenching of arc, the oil behaves identically in bulk as well as low (
circuit breaker. By using suitable arc control devices the arc extinction can be furth i
facilitated in low oil circuit breaker.
2.10.1 Constructio n
The Fig . 2 .26 shows the constructional details of a singlé phase minimum oil circ a
breaker.
It consists of two separate compartments which are separated from each other . B6f
these compartments are filled with the oil . The upper chamber is called the circuit breakir l
chamber while the lower chamber is called the supporting chamber . The two chambers a'1
separated by a partition and oil from both the chambers are prevented from mixing w i,
each other . This type of arrangement has two advantages . Firstly the circuit breaki''
chamber requires a small volume of oil which is just sufficient for arc extinction . Second
small amount of oil is to be replaced as the oil in the supporting chamber does not g
contaminated by the arc .
1) Supporting Chamber : This is a bottom chamber which is made up of procel a
and mounted on metal chamber . It is filled with oil which is physically separated fr o
the oil in circuit breaking chamber . The oil inside the supporting chamber and t l
annular space formed between the porcelain insulation and backelised pape r
employed for insulation.
2) Circuit Breaking Chamber : It is a porcelain enclosure which is mounted on fl';
top of the supporting compartment . It is also filled with oil and consists of follow i
parts
i) Upper and lower fixed contact s
ii) Moving contact
iii) Turbulato r
The moving contact is hollow . It consists of a cylinder which moves down over a fix +
pistion . The turbulator forms an arc control device and it has both axial and radial vents . T
axial venting ensures the interruption of low currents whereas radial venting ensur ;4
interruption of heavy currents .
3) Top Chamber : It is a metal chamber mounted on the top of circuit breaki i
chamber . It provides expansion space for the oil present . in circuit breaking chamber .
also contains a separator which avoids loss of oil by centrifugal action caused ,1
circuit breaker operation during fault conditions .
2.10 .2 Operatio n
2 .11=HVDC Circuit Breaker
Under normal operating conditions, the moving contact and fixed contacts are i n
engaged position . During abnormal conditions the moving contact is pulled down by th e In a .c . circuit breakers, arc extinction is achieved at the natural current zero of the a .c.t
tripping springs . With the separation of contacts, an arc is struck between them . The energ y waveform used . But in d .c, circuit b ers, natural zero of voltage and current is no
in the arc causes vapourisation of oil . This will produce gases at high pressure . This action ! ' available as both are contil s • able . Thus for extinction of an arc, artificial r„rren t
zero is required to be introduced . Such an artificial current zero is • ossible b connecting L C
prevents the oil to pass through central hole in the moving contact and results in forcin
Circuit in s arallel with the circuit •reaker . The C circuit is resp onsib e to pro. ucet
. The process-of turbulation is one i gserioflthupasgeoftrbul
nwhicsetofarucsivelyqnhd,btfcosepar mlfi oscillatory arc currents having many art icia current zeros . At one of the artificial curren
moving across each section . zero arc gets extinguished .
em Th e Fi . 2 .2 showstllYprinciple of HVDC circuit breaker . The HVDC circuit breaker i s
2 .10.3 Maintenance of Oil Circuit Breaker s nothing but a vacuum circuit breake r The(4LC circuit along with a switc h 's connected in
The maintenance of oil circuit breakers consists of checking of contacts and dielectric " parallel with this circuit Brea
strength of the oil . After fault has been interrupted by circuit breaker, fault current flows fo r The capacito used is
short time or load currents for several times, its contacts may be burnt due to arcing . Also Circuit breake r
precharged capacito ith th e
there may be some loss of dielectric strength of oil due to carbonisation . This will reduce High To polarities asshown in the Fig . 2.27 .
rupturing capacity of the breaker . Thus periodic checking of circuit breakers is essential after voDIt e / load When the circuit breaker start s
. r e g u
. Following points should be kept in mind while checking , l a i n t v o f 3 6 m h s C opening, the switch in the L C
i) Check the current carrying parts . It they are burnt replace them circuit ets closed . Due to the
, J e re arged ca âci , the dischargin g
ii) Check the dielectric strength of oil. If its colour is changed then it should be changed ,
or reconditioned . The oil in good condition withstands 30 kV for one minute with oooo--of f current starts flowing i it e *2
,° L Switc h direction to that of load current
4mm gap between electrodes .
iii) Check the insulation for any damage . Clean the surface with removal of carbon bl(a carr* cie*vthe circuit brea er. ue
*\l Parallel LC circuit to this, arcing current starts
deposites with strong and dry fibric to introduce artificia l oscillating - producing many
. .iv)Theolsudbcke current zer o
ri fIi l zeros . Thus artific a
v) The closing and tripping mechanism should be checked . commutation results and ar c
Fig . 2 .27 HVDC circuit breake r inctton is achi e yed . T
2.10.4 Advantage s
The advantages of minimum oil circuit breaker are , The large transient recovery voltage is the main constraint in .HVDC circuit breaker and
i) The quantity of oil required is small . circuit breaker must able to withstand it . For successful operation of such a circuit breaker ,
the switch in LC circuit must be a high speed switch with a very fast response . Such system s
ii) The space requirement is reduced . are complex and very costly as they require costly protection and control systems .
iii) The risk of fire is reduced .
2 Selection of Circuit Breake r
2.10 .5 Disadvantage s
The following parameters are required to be known for selecting proper rating circuit
The disadvantages of minimum oil circuit breaker are , breaker at a given location on a power syste m
i) Due to smaller quantity of oil, the degree of carbonisation is increased . e maximum fault current which is to be interrupted by the breaker .
ii) The gases are difficult to remove from the contact space in time .
iii)The dielectric strength of the oil deterorates rapidly as degree of carbonisation i he maximum current to be carried momentaril y
high. s As it is discussed previously the fault current consists of both a .c. and d .c . components
and its correct calculation is very complex . A simplified method is recommended by IEE E
2.10 .6 Application s committee is given below :
Minimum oil circuit breakers are now available for all voltages and for the highes t 1 . To determine firstl the re• uired interrupting capacity of circuit breaker the highes t
; of fa lt . It can bé
breaking capacity hence preferred in most-of the protection schemes . value of initial rms alternating current , or an t ,.:e and lo-ca-ti-c
considere • as t ree p' ase au t as it carries maximum fault current except in som e
C
VTU - Switchgear and Protection 74 Circuit Breakers VTU -Switchgear and Protection 75 Circuit Breaker s
cases . This current can be obtained b using su ..-transient reactance fore-Tie-1779. .13 Circuit Breaker Rating s
and transient reactance for sync ono_us motor while nduction motors are
nt lected . ollowing multiplying factors can be applied to to e mto account t e •c . , A circuit breaker is a mechanical switching device capable of making, carrying an d
components of currents and decrements of botl .(a.c• a=. com onénts breaking current under normal circuit conditions and also making, carrying for specifie d
1fycle or slow breaker 1 .0 time and breaking current under specified abnormal conditions .
5ycle breaker 1 .1 The circuit breaker is also required to perform some additional functions as th e
)-cycle breaker 1 .2 application demands such as ,
-ycle breaker 1 .4 i) to provide selectivity with breakers
Before applying multiplying factor, all the given factors are increased by 0 .1 for the ii) to provide facility for remote closing and trippin g
breakers on the generator bus where 3 phase short circuit kVA exceed 500,000 . iii) to provide facility for interlocking '
2. To determine the required .ted momentar curr e * . - 1 sec or less of a ' iv) to provide facility for indicatio n
breaker . The calculation of hest value of in' -- lao done a s Some of the important characteristics or ratings that must be possessed by every hig h
given in the step (1) except using-sub-transient reactances of of all the machines voltage a .c. circuit breaker arc as follows ,
including induction motors . Multiply
V 1.Rated voltage
Momentary rated rms current of a circuit breaker = 1 .5 x
✓ X'â 2. Rated insulation leve l
Ex. 2.1 : A generator connected through 5 cycle CB to a transformer is rated 8000 kVA with the ; 3.Rated normal curren t
reactances of X d = 10 %, X d = 16 % and X d = 100 %. It'is operating at no load an d 4. Rated frequency
rated voltage when 3 phase short circuit occurs between breaker and transformer . Find : 5. Rated duration of short circuit
i) sustained short circuit in breake r 6. Rated short circuit breaking curren t
ii) the initial symmetrical rms current in breake r 7.Rated short circuit making curren t
iii) maximum possible d .c• component of short circuit in breaker 8. Rated peak withstand curren t
iv) the momentary current rating of the breake r 9. Rated TRV for terminal fault
v) current to be interrupted by breaker vi) the interrupting kVA
10.Rated operating sequenc e
Sol. : Let the base be 8000 kVA .
11.'Rated supply voltage for opening and closing devices and auxiliary circuits
Sustained short circuit kVA = 8000 x 100 = 8000 1KVA• as X d =100 %
100 12.Rated pressure of compressed gas for interruption
kVA
Sustained short circuit current 2.13 .1 Rated Voltag e
x VL
u
It is a voltage of a circuit breaker which refers to higher system voltage for which it i s
Let VL = 13.8 kV designed . It is expressed in kV and the value is r•m,s . value. In case of three phase circuits it i s
Sustained short circuit current = 8000 = 334 .70 A nothing but phase to phase voltage . A circuit breaker must be assigned two voltage ratings
*x 13 . 8 one corresponding to maximum nominal system voltage and other maximum desig n
8000 x voltage which indicated the maximum operating voltage which should not be exceeded .
Sub-transient short circuit kVA = 100 = 8000 0
10
8000x100 2/13.2 Rated Insulation Level
Sub-transient or initial symmetrical curren t .8 = 3347 .05 A
10x/x 13 The different circuit breakers connected in power system are subjected to powe r
Maximum possible d .c. component = Jx 3347.05 = 4732 .73 A frequency over voltages due to various effects such as regulation, Ferranti effect etc . The
circuit breaker must withstand this overvoltage . This can be tested by carrying out differen t
Momentary current ratin g = 1.6 x 3347.05 = 5355 .28 A 4 tests . During some single phase to ground faults voltage of healthy line to earth increases . So
Current to be interrupte d = 1 .1 x 3347.05 = 3681 .75 A higher values of insulation are suggested . The insulation is provided for each pole externa l
Interrupting kVA = -I§ x 3681.75 x 13.8 = 87999 .836 kVA
Circuit Breakers VTU - Switchgear and Protection 77 Circuit Breakers
VTU - Switchgearand Protection 76
and internal between live parts and earth . It is also provided between poles and betwee n
terminals of same pole internal and external .
2.13 .10 Rated Operating Sequenc e vi) Rated small inductive breaking curren t
It represents the sequ ce of opening and closing operations which circuit breaker ca n vii) Rated time quantitie s
e
perform under specified onditions . As per specifications the circuit breaker should be abl viii) Repeated operating duty .In actual design of circuit breakers following parameters ar
to perform the operating sequence as per one of the way s e
considered :
i) O-t-CO-T-CO ii) CO-t'-CO 1 Current rating
where 0 = Operation of openin g
2 Breaking capacit y
t = 3 minutes for circuit breaker not to be used for rapi d
3 Making capacity
auto-reclosure
CO = Closing followed by openin g 4 Type of protective mechanis m
T = 3 minute s 5 Short time ratin g
t' = 15 sec for circuit breaker not to be used for rapi d 6 Type of mechanis m
auto-reclosur e 7 Accessorie s
8 Indication s
2.13.11 Rated Supply Voltage for Clo 'ng and Opening Device s 9 Locks and interlocks
The performance of auxilary supply ci cuits and operating mechanisms is important i n
y 10 Operational lif e
addition to ratings of or main circuit and oles . The supply voltage is provided by auxiliar
circuits to the trip coil and closing coil which are having certain minimum voltage belo w 11 Ease of maintenanc e
. The
which it will not operate . For correct operation the frequency must be properly chosen 12 Volume / weigh t
rated supply voltage and supply frequency of closing and opening devices and auxiliar y
13 Control voltage
circuits is important .
1
80 Circuit Breakers VTU - Switchgear and Protection 81
VTU -Switchgear and Protection
c) Power frequency voltage test s
14 Availability of spare s
d) Voltage tests on auxiliary circuits, control circuits ,
15 Cos t The quality of the circuit breaker can be very well checked by these tests . Also any
Depending upon the above parameters the different circuit breakers are designed, fo r defects in the materials and construction is detected .
their efficient operation . In the next chapter we will study different types of circuit breaker s
in detail. 2 .16 Development Tests
2 .14 Type Tests These tests, are very much essential to observe the effect of different parameters on th e
circuit breakers performance . Variety of tests are performed on individual items as well a s
As mentioned earlier these tests are carried out on first few circuit breakers to prove th e on complete assemblies .
rated characteristics of the breakers . The necessary information which includes assigne d
ratings, drawings, reference standards, rated operating pressure and voltage, suppor t If a circuit breaker is tested frequently with-change in its contact speed, then we can se e
the effect of contact speed on breaking capacity . The different parameters and their effect s
structure etc must be supplied to the testing authorities before conductingthese tests . These
are theoretically predicted . Full scale prototypes are manufactured after testing an d
details are included in the type tests report . After certifying the breaker by carrying out thes e measurement. The data available in the company is used by the designers for example fo r
tests, there should not be any change in design . the design of contacts, the configuratio n canoe derived from available designs of contac t
Type tests are classified as follows , assemblies .
a) Mechanical tests Each subassembly has certain functional requirement e .g . the contacts should give lo w
b) Tests of temperature rise, millivolt drop tes t resistance in closed position . Therefore to verify the capability of contact configurations,
c) High voltage tes t development tests are conducted, depending on functional requirements . The modifications
d) Basic short circuit test are done on the basis of these test results .
i) Making tes t 2 .17 Reliability Test s
ii) Breaking test
The newly manufactured circuit breakers are tested by type tests and routine tests . Bu t
iii) Operating sequence tests at 10%, 30%, 60%, 100% of rated breaking current wit h
the conditions during these tests are not the conditions that exist at the field . At site the
specified TRV conditions .
circuit breaker is subjected to various stresses due to ,
e) Critical current test s a) Variation in ambient temperature s
f) Single phase short circuit tes t b) Extremely low and high temperature s
g) Short time current tes t c) Rain moisture
In addition to above tests some more tests are recommended on circuit breakers to b e d) Vibrations on account of earthquakes.
used in specific applications, which are , e) Dust and chemical fume s
a) Short line fault tests f) Overloads and over v6ltage s
b) Out of phase switching tests Also the maintainance-of the ;breakermay :notbe done by skilled persons . Thus the
c) Cable charging current switching tes t performance of the breaker is tested under these adverse conditions by reliability tests . The
d) Capacitive current switching test s circuit breaker is subjected to extremely high temperature created in test chambers . The
various parts are critically examined after testing .
e) Small inductive current breaking test s
f) Reactor current switching test s 2.18 Commissioning Tests
2.15 Routine Test s These test are performed after the proper installation of the breaker at the site . The
operational readiness and proper assembly is verified . High accuracy is not generally
Before dispatch of circuit breakers, these tests are performed . Routine test is defined as a expected in such tests . The test facilities available at site is also important factor .
test of every circuit breaker made to the same specifications . They include the followin g
tests. These include following tests ,
a) Mechanical operation test s a) Mechanical operation tests
b) Millivolt drop test, Measurement of resistance b) Measurement of travel, simultaneous touching of contacts
82 Circuit Breakers VTU -Switchgear and Protection 83
VTU -Switchgear and Protection Circuit Breaker s
type tests . By carrying out experimentation and problems r lated to circuit breaking,ih e
modern EHV (Extra High Voltage) breakers are developed .
Due to short circuits, e stresses:'re produced on circuit breakers . The circui t
breake ust be capable ' mg the stresses . The short circuit current duration is
b 1 sec or 3 sec . The short time current test verify the capability of breaker .
Due sort circu i re produced on contacts and current carrying
:s he stress is also pr o aced on insulation . The poles and terminals experienc e
fro-dynamic forces .
The making . .acit checks th. 0 • n close on short circuit . The breaker
should be capable of closin; e fectrv e w:tn contact welding . The breaking capac i
verifv the a . - tm mechanism and e m err . shoul d
able to perform these functio n
The stresses developed during short circuit depend on magnitu It current and
design of breaker . After current zero, the contact space is subject : d to TRV. herefore fo r 1 ° Links
reliable o eration and performance of circuit breaker on short circuit, short circuit testing
MM. shor t
circuit
a
plants are specially built . transforme r
r== =
'-- Z* U== =
2.19 .1 Short Circuit Testing Plant s I.I
There are three types of testing stations which are as follows, 2 i t
a) Field type testing station where power required for testing is taken directly fro m I I u
II
I
large power system and the breaker under tests is connected . II
I II i
b) Laboratory type testing station where the short circuit generators provide the powe r
for testing . The breaker may be tested directly or indirectly . Fig . 2 .30 Layout of short circuit tes t
c) Composite testing station which is a combination of field type testing station an d The test voltages are obtained by transformers . These single phase units are connected i
laboratory type testing station . n
various ways to get different test voltages . This also includes some equipments necessar
y
for measurement, record and control, and auxiliary equipments with a sequence switch t o
2 .19 .2 Layout of a Short Circuit Testing Statio n obtain sequential operation .
It is represented in the Fig . 2.30. The short circuit generators provide the power required .
There may be two or more generators though in the figure shown it is only one . Three phas e 2 .19 .3 Short Circuit Generator and Drive Moto
r
induction motor drives the generator and impulse excitation is provided . The circuit breakers under test are supplied power with this generator . The generator
For adjusting magnitude of short circuit current, variable series resistors and reactor s must withstand high reactive power surges for short duration . Their design is therefor e
are provided . The master circuit breaker has higher capacity than the breaker under test . If somewhat different from conventional alternators .
breaker under test fails to operate, then master breaker operates to protect the circuit . The generator is driven by a three phase induction motor mounted on same shaft . The
Making switch is a closing device specially designed which can close at desired moment an d impulse excitation is provided by separate d .c . converter . The short circuit current at laggin
g
carries the making currents . power factor have a demagnetizing effect which reduces e .m.f . So the voltage before th
short circuit will be less . Thus the generator field current is boosted by impulse excitation e
.
VTU-Switchgear and Protection 85 Circuit Breaker s
Circuit Breaker s
VTU -Switchgear and Protectio n
2 .19 .7 Making Device
.imes its normal value at the time of short circuit .
c)Measurement of ins u The short circuit currents are applied correctly at desired moment by this switch. It
d) Checking iithe o r le Fig . 2 .31 . should have high making capacity while breaking capacity is negligible . It must be air blas t
e)Checking making switch with air pressure 14-16 kgf/cm 2.
2 .19 .8 Capacito r
Capacitor banks provide leading current for verifying the performance of breaker fo r
interruption of charging currents . The frequency of the transient recovery voltag e
(f = Z 1LC is regulated. In synthetic testing it is an important element .
n J
2 .19.9 Resistors
The short circuit p .f. varied by using resistors in series with reactors . It can be increase d
from 0.1 to 0 .3 .
2.19.10 Test Cubicle s
These are constructions of reinforced cement concrete or strong brick work . In,the
cubicles the breakers are tested . Separate cubicles are provided for testing L.V., H.V . and
EHV equipments .
2 .19.11 Sequence Switc h
During short circuit testing, many operations are performed in a sequence and total tim e
X* Y l Z* 1 Part 1 of generator windin g is very less to perform manual operation . A sequence switch performs the sequentia l
Ul VI WI f operations as it is a drum switch with several contacts which is rotated by a motor . Due to
rotation of drum, control circuits are opened or closed as per specific sequence . The
X 2 Y 2 Z2 Part 2 of generator windin g
sequences for breaking capacity test in one test are as follows which takes nearly 0 .2 seconds,
U 2 V 2 W2 i)Drive motor of short circuit generator .made off
t ii)Impulse excitation switched o n
.31 Circuit arrangement in short circuit test layou
Fig, 2
iii)Master circuit breaker close d
Transformers than r
2 .19 .4 Short Circuit v volt iv)Oscillogram circuit connecte d
The transformers are used for testing the breaker the a ltageswhereas single phas e . v) Make switch close d
withs
voltage . Three phase transformer is used to. step d
The transformer vi)Circuit breaker under test opene d
s r a rs ds es to Extra transfomeiudpthvtur olage d vii)Master circuit breaker opene d
. The leakage reactance of these . Coolin g severs
repeated short circuit viii)Excitor switched off and its field supresse d
phasaaee uniteinsulatoprvdhemcanilystrogwd proob l em
. single tes
as transformer is not there in a circuit for a long time 2 .19 .12 Different Measurement s
big it is not normally used . Since the test events takes very short time, all measurements must be recorded by
e are ai d oscillographs . Light beam oscillograph which are easily operated are used for slow varyin g
2 .19 .5 Reactors .
r c o n e t d i r o l h e s t c i u n
e T three
e s phase core quantities like current, voltage, contact travel or trip signal etc . TRV phenomenon require s
Reactors ar e only 1 msec . For recording such fast quantities, CR0 is used .
and air cooled . Iron of withstanding tstresses, be single phas
The reactors must be capable The following quantities are recorded during the test ,
r i) Short circuit current in each phas e
test. It
2 .19 .6 Master Circuit Breake ii)Voltage across each pole before, after and during short circuit
This is a air blast type of breaker having capacitynafter every test itksolatesspecime 1 iii)Fluid pressur e
operates if breakers under . In additio
. Ittest
mustfailbetoable
operate
to carry full short circuit current .
under test from supply
VTU - Switchgear and Protection 86 Circuit Breakers VTU- :SwitchgearandProtection 87 Circuit Breaker s
1 voltage and recovery voltage . The test conditions are given by L, r, C . The short circuit
a where m = number of units per pole and one unit is teste d current Io is supplied by closing switch Sr . At final current zero, switch S2 is closed an d
m
voltage contains transient as it contains L and C .
a = n where n units are teste d The advantages of this method are as follows ,
m
i) The breaker can be tested for desired TRV and RRR V
Let us consider the examples of a 3 pole, 220 kV breaker with 3 units per pol e
ii) The short circuit generator has to supply currents at less voltag e
Voltage across one pole = 220 =127 k V
*l 3 iii) The flexibility can be obtained by independent control of test current and tes t
voltage
1 1
a =- ; m=3 a= - iv) As method is simple it can be applied to unit testing als o
m 3
v) A breaker having capacity five times that of plant can be tested .
Voltage required for testing one unit = a x voltage per pole = 127 x 1= 42.33 kV
3
2.21 Types of Synthetic Test Circuits
L and C of the test circuit is also reduced to get same natural frequency as that of direc t
testing. There are two types of synthetic test circuit s
In direct test , i) Parallel current injectio n
1 ii) Series current injectio n
Natural frequency, fn
2n -"LC 2 .21 .1 Parallel Current Injection Metho d
This method is used for testing breakers as it gives high frequency transient voltages a s
required by standards . It is shown in the Fig . 2.33 .
l
VTU Switchgear and Protection 88 Circuit Breakers VTU - Switchgear and Protection 89 Circuit Breakers
Make Aux .
2 .21 .2 Series Current Injection Metho d
Master
breaker switch breaker The Fig. 2 .34 represents series current injection method . The voltage circuit (2) i s
o LH
f 6000 L O S 2 0 - connected to current circuit in series before main current zero . Due to this IC and Ili are in
LG St +
Gen CH e
Aux .
breake r
Curren t Voltag e
circuit circui t
opposition . The stresses produced in the synthetic test and those in actual network must b e 10. Explain the construction and working of SF6 circuit breaker.
same but it is not the actual case because of several factors like high current, high voltage , .11 . What are advantages and disadvantages of SF6 breaker.
instant of applying voltage etc .
12. Explain the construction, working, advantages and the disadvantages of vacuum circuit breakers .
2 .21 .3 Brown Boveri's Synthetic Testing Circuit 13. Explain the arc interruption taking place in vacuum .
This circuit is shown in the Fig . 2.35 . The short circuit current is supplied from lo w 14. What are the possible applications of vacuum circuit breakers .
voltage circuit. The restriking and recovery voltage is supplied by different high voltag e 15. Explain the process of arc extinction in vacuum .
circuit . 16. Write a note o n
i) Unit testing ii) Synthetic testin g
17. Describe short circuit test layout for a circuit breaker .
18. What are the different ratings of circuit breakers . Explain any one in detail .
19. Wrie a note on HVDC circuit breaker .
University Question s
1. Define 'circuit breaker as applied to. electrical power circuits . With a neat sketch explain the working of a
vacuum circuit breaker. (Aug .-2002, 10 Marks )
2. Describe the short circuit tests to be carried out on circuit breaker . (Aug .-2002, 10 Marks )
3. Enumerate the properties of SF6 gas which render its use in high voltage circuit breakers . With the help
of a neat sketch explain briefly . working of any one type of SF6 breaker. (Aug.-2002, 10 Marks)
Fig . 2 .35 Brown-Boveri's synthetic testing circuit
4. Write a short note on arc quenching in air blast circuit breakers . (Aug.-2002, 5 Marks)
The high current circuit on left side consists of short circuit generator G, short circuit
5. Write a short-note on minimum oil .circuit breaker. . (Aug: 2002, 5 Marks )
transformer with resistor Ro and capacitor C 0 -which controls natural frequency of current .
The short circuit power is supplied at voltages Vs which corresponds to about 30 kV which i s 6. Explain the working of air blast circuit breaker with-reference to i) Axial blast ii) Cross blast .
smaller than recovery voltage required for testing . The recovery voltage is supplied by hig h (Feb .-2003, 10 Marks )
voltage circuit on right side . 7. Explain the construction and working of a Vacuum circuit breaker . Mention two advantages .
The test breaker and auxiliary breaker Sr are opened together . Before the curren t (Feb .-2003, 10 Marks )
interruption takes place in breaker B, the spark gap is triggered by control S t and voltage V is
8. Discuss the properties and advantages of SF 6 gas as a dielectric over air medium .
applied to breaker B . During final current zero-onlycurrent iH flows through breaker B .
Previously is = io + iH which is interrupted by S i and breaker B . But now breaker B has t o (Feb .-2003,10 Marks )
interrupt only iH . Hence restriking voltage across breaker B is given by HV circuit. 9. Write a short note on testing of circuit breaker s (Feb .-2003, 5 Marks)
10. Explain the working of airblast circuit breaker with .relevance to
Review Question s
i) Axial.blast ii) Cross blast . (Aug .-2003, 10 Marks )
1. State the requirements of a circuit breaker and explain the basic action of circuit breaker . 11, Explain the construction, working, advantages and the disadvantages of vacuum circuit breakers .
2. State the classification of circuit breaker based on different factors. (Aug .-2003, 10 Marks)
3. Explain the construction and working of air break circuit breaker .
12. With the help of .a neat layout diagram of a short circuit testing laboratory explain the procedure of
4. Write a note on air blast circuit breaker . testing of circuit breakers (Aug .-2003, 10 Marks)
5. Explain plain break oil circuit breaker. 13. Write a short note on SFb circuit breaker (Aug .-2003, 5 Marks)
6. Explain with the help of neat sketch the construction and working of minimum oil circuit breaker. 14 . Write a short note on synthetic testing (Aug .-2003, 5 .Marks)
What are its advantages and disadvantages . compared to bulk oil circuit breaker .
❑❑ ❑
7. Explain in brief cross jet and plain jet explosion pot.
8. Why SF6 gas is preferred in circuit breakers.
9. Write a note on dielectric properties of SF6 gas.
VTU -SwitchgearandProtection 93 Fuse s
equipment from excessive current. The fusing element melts due to the heat produced b y
the excessive .current . So the melting point of the fusing element plays an important role i n
the design of the fuse .
The Table 3 .1 gives various metals which can be used as fusing elements, with th e
corresponding melting point and specific resistance values.
Fuses
Metal Melting point in Specific resistance i n
S2-cm
°F °C
Fp
3 .4,6'Prospective Current 21
The Fig. 3 .1 shows how the a .c . current is cut off using a fuse . This is called cut-of f
characteristics of a fuse . 20
19
" 60 0
18
Current
r\ IAGLt.A-*b m 6Q ( pct 17
au c c)A Ce
l
K t
c
Asy mmetncal 16
15
Cut-offcurrent a . *,
current . Cho CJlcQ
0
occurs ' lb
Final
current zero
(Arc finishes)
o - emp`m *{ ,2
tim e
\Cl*f
t Q
Y
14
13
12
0 â
Y
11
10
AA i d 300
m
m
9
,*' I**,. *.
8 i* ,.*
200
Fig . 3.1 Cut-off characteristics 7
When the fault occurs, the current starts increasing . This fault current is asymmetrica l
and very large first loop. But before achieving maximum value, it generates sufficien t
energy to melt the fuse element . The-r .m .s . va l
B
5
4 . ► MI
e.iÔ
*" *.
IN
..
10 0
ut-off Current
2
1 ® ***•*
3 .4
e current value at which the-fuse me s, before fault current achieves its peak value is 1 1 .5 2 3 4 6 8 10 15 30 50 6 0
called cut-offcurrent . It can also be defined asp the maximum value attained by the faul t Prospective current kA (r.m .s .)
cu ren )us when the fuse melts .
It is the current corresponding to the point 'a' shown in the Fig . 3.1 . The cut-off valu e Fig . 3 .2 Typical cut-off characteristics for a cartridge fuse
depends on, 3 .4 .8-•-Pre-arcing . Time -
1. Current rating of fus e The time between the commencement Of the fault current and the instant when the fus e
2. Value of prospective current melts and the arc starts is called pre-arcing time .
3. Asymmetry of the fault current waveform In the Fig . 3.1, the pre-arcing time is in between the point o and a . The point o i
The cut-off value is very important as it does not allow prospective current to reach its s
corresponding to start of fault current while the point a is when fuse melts and arc starts .
peak . So it avoids the circuit, to get subjected to electrodynamic stresses . This is also called melting time . The pre-arcing time is generally very small and its typica l
value is 0 .001 sec .
98 ., .fuses VTU -Switchgear and Protection 99 Fuses
VTU - Switchgea ahd Protection
No metal can posses all these characteristics .
3.4 .9 A,rc`ing Tim e
le time between the end of the prearcing time and the instant when the arc get s It is seen earlier that the various metals which are used as fuse elements are lead, zinc
tin, copper, aluminium and sliver. The melting points and specific resistance values of thes e,
completed extinguished is called arcing time . metals are given in the Table . 3.1 . Low melting point is available with high specifi
In the Fig. 3 .1, it is the time between the points a and point b . resistance metal . c
3 .4 .10 T Operating Tim e For small value of currents lead-tin alloy is used for making the fuse element . The most
ne sum of the pre-arcing time and the arcing time is called total operating time of th e preferred lead-tin alloy consists of 37 percent of lead and 63 percent of tin . Such an alloy i s
called eutectic alloy . It is preferred because ,
fuse . 1 . It has less tendency to spread over . 2 . It is quite homogeneous
In the Fig. 3 .1, it is time between the points o and b . In rupturing small values of currents such an alloy is used because the fusing current for
The operating time of a fuse is generally very small as compared to the .circuit breaker . such a type of fuse wire is about 50 percent over load . Such an alloy is used upto curren t
So a fuse in series with a circuit breaker gives a useful, simple and economical way t o capacity of 10 A .
provide sufficient short circuit protection . This is because fuse melts when there is a:fault For large values of current copper or silver is used for making fuse element . The lead-ti n
before the circuit breaker has time to operate . It must be noted that the circuit breaker in alloy is not used because after fusing there is excessive metal released in case of alloys a s
series with fuse should have low breaking capacity . diameters of such wires are large .
âking Capacit y The zinc in a strip form is also a good choice when a considerable time lag is required i n
he breaking capacity is the fuse rating corresponding to the r .m.s . value of the a .c. the operation. This is because zinc has tendency to sustain small overloads for long time an d
component of maximum prospective current at its rated service voltage . not to melt very quickly.
The present trend is to use silver though it is costly because of following reasons ,
3 .4.12 Pre-arcing 1 2t 1. The silver has low coefficient of expansion such that no critical fatigue occurs . The ful l
It is the time integral of the square of the current passing through the fuse during th e capacity of normal rated ,current` can be passed through silver continuously, for a
pre-arcing time . It gives the heating effect in the pre-arcing time . long time.
2. The conductivity of silver is-very high and not affected by the continuous operatio n
3 .4.13 Arcin g 1 2t and surges of current .
It is the time integral of the square of the current through the fuse during the arcing time . 3. Due to high conductivity, the mass of silver required for a given rating of fuse is les s
than other materials . So the problems of clearing after the fusion are less whic h
3.4 .14 Clearing 1 2 t increases the operating speed .
The sum of the pre- -arcing fit and the arcing 12t is called clearing 12 t or total 1 2t. 4. The conductivity of silver does not deteriorate with oxidation.
5. Because of its low specific heat, silver elements can be raised from normal operatin g
3.4 .15 Voltage Rating of Fus e
temperature to vapourization much quicker than other elements .
The voltage rating of the fuse is specified by the manufacturer . The rated voltage of th e 6. Silver resistance increases abruptly as melting temperature is achieved . Due to this ,
fuse must be equal or greater than , transition from melting to vapourization is almost instantaneous . Hence the
1.Voltage of a single..phase circuit operation of silver fuse element becomes very fast at higher currents .
2.Line voltage is case of three phase circuit 7. Vapourization temperature of silver is low than that at which vapour readily ionises .
Hence when an arc is formed through the vapourized portion of silver then arc pat h
3. Voltage between two outer wires in three wire d .c. circuits. has much higher resistance . Hence short circuit current gets interrupted very fast .
3 .5 F e Element Material 3 .6 e - Current Characteristic of Fus e
The desirable characteristics of any fuse element are,
The fuse ha . inverse time - current' characteristics-This means as the magnitude of faul t
1. Low melting poin t current is higher, smal er is t e time taken by the fuse to melt . When fault current is low, the
2. High conductivity time taken by the fuse is more .
3. Free from deterioration due to oxidatio n The time - current characteristic of a fuse is shown in the Fig . 3 .3. Such characteristic is
4. Low cost generally shown on the logarithmic scale .
VTU - Switchgearand Protection 101 Fuses
3 .7 Fuse La w
When the fuse achieves the steady state condition then we can write ,
Heat generated = Heat lost due to conduction, convection and radiatio n
Now Heat generated = I2R watts
where I = Current through fuse element = fusing curren t
R = resistance of fuse elemen t
Assuming circular shape of fuse element, .
pI pl
R = -= (3)
a d2
4
where p = specific resistance of fuse elemen t
1 = length of fuse elemen t
d = diameter of fuse element
Now for a fuse wire of diameter d, the heat lost can be obtained as ,
Heat lost = effective surface area x constan t
= dl x constan t . . . (4)
Substituting (2), (3), (4) in (1) we get ,
I2 x p1 = dl x constant
"4 d
I2 p 1 d3 1 x constant
=4
I2 =K'd3
where K' =constant = another constan t
P
I = K*d3 =Kd 312 (5)
This equation (5) is called fuse law and K is called fuse constant . The value of fus e
constant depends on the fuse element material. ,Sir W. H . Preec has given the values of
constant K for various fuse element materials . The Table 3 .2 shows the values of K fo r
various materials
Material Value of K
dincm d in mm
Aluminium 1873 59
Copper 2530 80
Lead 340 .5 10.8
Tin 405 .5 12.8
Iron 777 24.6
Table 3 .2
10 2 Fuses
VTU -Switchgear and Protection
f
Ex. 3 .1 : A current of 6 A fuses a lead fuse of diameter 0,0195 inch . What current will fuse a wire o semienclosed fuses is overcome in HRC fuses .
0.0392 inch ?
3 .10.1 Construction
Sol. : According to Fuse law,
I a d312
(d 1) 31 2
(d 2J-
Now I 6A
dl = 0 .0195 inch
d2 = 0 .0392 inch
3/ 2
6 ( 0 .0195
I2 0 .0392 j
12 = 6x2.8502
= 17.101 A
Fig . 3 .4 Construction of HRC fuse
VTU - Switchgear and Protection 1 04 Fuses VTU -Switchgear and Protection 105 Fuses
The bod of this fuse is of h-at resistin_ cerami . with metal endcaps . The metal used fo r 3 .10 .3 .1 Cut - off Characteristic s
end caps is generallybrass . Between the end caps, the fixedelementsare mounted, vihic h When excessive current flows through the fuse, fuse element starts melting at one o r
are welded to the endcaps. The fuse element whi ;- ►- . • , ► - r . • en
more points, depending upon the design . When the fuse melts the arc is struck . The fault
the fixed elements . ' 1'he construction of HRC fuse is shown in the Fig . 3 .4. current has a large positive peak but before reaching to its peak, the fuse blows . This current
The body of the fuse is cylindrical in shape . The bodysurK _ :*:y *=r=ang the fus e is called prospective current which is actually r .m.s. value of the first loop of*the faul t
element is completely filled with a filling powder . The filling powder is generally auartz current . The current at which fuse melts and arc starts is called cut - off current .
sand` plastter of oari or marble dust. The filling powdè"r material is selected such that it s When the fault occurs the voltage momentarily reduces and when fuse n Its with ar c
chemical reac ' . ► . ' ► . ourforms ver hi_ h re i . ► This helps in arc formation, the arc voltage reaches to a value which is several times more th n the suppl y
quen and acts as cooling medium., The filling powder can absorb the heat at very hig h voltage . This depends on the fuse length and the cross-section . When arc completel y
rate and it does not evolve appreciable gas . . vanishes, recovery voltage becomes normal .
3.1 peratio n The Fig . 3 .5 shows the HRC fuse cut - off characteristics showing the waveforms o f
Under normal condition! the n,rre i flowinng-through the-fuse Plenae t is rated or below current as well as voltage . As mentioned earlier; the cut-off value depends n the norma l
rated. Hence the temperature of the element is well belowits rmeltng point Hence fus e current rating of the fuse, the value of prospective current and the asymmetr of the curren t
continues t rr€nt saf ithn ,t overheating . When a t drc "waveform . The breaking capacity of the HRC fuse is represented by its ormal servic e
current increases . ver hi . , e increasing the temperature ofIhe "element upto it s voltage and the r .m.s. value of the prospective current .
melting si . - u • , e . Hence r - •• melts before fault c-**rrentreachesto its
eak v lue• The silver vapourises after melting . The chemical reaction between silver
p•* Current
vapour and the filling powder forms a high resistance substance which helpsinuenchin
fhe arc very q-- uickLy_
The various steps; in the operation of the HRC fuse can bEy,ummarized as , Arc starts Prospective current
The Fig. 3 .6 shows the typical time-current characteristic of a HRC fuse . 3 .10 .4 Fuse Element of HRC Fus e
The fuse element of the HRC fuse is enclosed in a fuse link . The fuse link is replaced
when it blows out .
Curren t
The fuse element is of silver or copper with a special shape . Generally the fuse elemen t
-has two or more sections joined by means of tin joint . The various .shapes . of fuse elements
1000 -
which are used in HRC fuse are shown in the Fig . 3.8.
Fuse elemen t
100 Minimu m
fusing current
I I I - tim e
0 .01 0.1 1 10 100 o
o
o o
o o
3.10.3.3 1 2 t Characteristic s
The information about heating effect due to the pre-arcing current and at the time of ar c
quenching can be obtained from 12t characteristics . The Fig. 3 .7 shows 12t characteristic s
showing curves of pre-arcing 1 2t and total I2t against fusing current. Time delay center insert
2
I tin `Fig . 3 .8 Various types of fuse elements of HRC fus e
Amp-S
2 The fuse element governs the various characteristics of a HRC fuse .
10 6 Total I 2t . f .5 Advantages of a HRC Fus e
5
10 The rious advantages of a•HRC fuse are ,
. It can clear high values of short circuit current .
104
2 . It does not deteriorate with-high speed .
10 3 Pre-ar mg I 2t
2
t,3!'5 e operation is very fast . -
10 4. It has inverse current - time characteristics .
10 5. Thy performance is very much consistent .
provides reliable discrimination .
4 60 100 150 300 400 50 0 cost is less as compared to other protecting device of same breaking capacity .
Fusin g maintenance is required .
current
The j peration is reliable.
Fig . 3 .7 1 2t characteristics
.6 Disadvantages of a HRC fus e
The ft characteristics indicate the amount of energy released which will be passed to th e The jsadvantages of a HRC fuse are,
equipment being protected, at the time of fault current interruption .
must be replaced after each operation .
VTU -Switchgear and Protection 109 Fuses
VTU - Switchgear and Protection 1 08 .:Fuses
e replacement of fuse takes time . The fuse body is made up of ceramic having a cap rigidly fixed at both ends . Through th e
3 u .jected to high temperature rises and hence heat produced can affect the adjacen t cap at one end, the plunger is inserted which acts as a tripping device for the associate d
contacts, associated switches etc . circuit breaker . Between the caps at two ends, number of silver fuse elements are connected .
The plunger is electrically connected to a tungsten shunt wire with a weak link, connected t o
4. er-locking is not possible .
the cap at other end . Behind the plunger, a small chemical charge is placed .
3 .10 .7 Selection of HRC Fus e Operation : When a fault occur, the silver fuse elements melt first . Due to this th e
The following points must be considered while selecting the HRC fuse for a particula r current gets transferred to the tungsten shunt-wire due to which the weak link get s
application, .. fused . The chemical charge gets detonated . This forces the plunger upwards . The
1. The level of the overcurrent protection required. upward movement of the plunger is controlled so that it should not eject ou t
2. The normal current of the circuit . completely from the body of the fuse and at the same time it gets trapped so that i t
3. The voltage appearing across the fuse after its operation which should not be greate r can not be reset . This operates the trip circuit of the breaker to open it .
than its rating .
3 .11 .1 Advantage s
4. The rupturing capacity must not be less than the current to be interrupted .
The HRC fuse with a tripping device has the following advantages over the normal HR C
5. The discrimination needed when used with other fuses .
fuse without tripping device ,
3.10.8 Applications of HRC Fus e 1. In a three phase system if one phase fuse blows off then .the supply to the moto r
The main applications of HRC fuse are , continues but single phasing occurs . This causes overheating of the motor windin g
1 . To protect the low voltage distribution'system against the overload and short circui t due to tremendous overloading . The HRC fuse with a tripping device operates the
conditions . circuit breaker disconnecting all the three phases . So it is ensured that one fuse blow s
off, the entire three phase supply gets disconnected due to the operation of circui t
2. For the backup protection to circuit breakers . breaker .
3 . Protection of meshed feeders with the steady load. The plunger gives the visual indication when a fuse blows .
2.
.11 HRC Fuse With Tripping Device 3. The effects of full short circuit .current are not required to be considered for th e
selection of the circuit breaker . Hence inexpensive circuit breaker can be used .
When the fuse is used along with the circuit breaker then fuse must blow first and the n 4. Low voltage HRC fuses may be built with breaking capacity of 16500 to 33000 A a t
circuit breaker should operate . This is ensured by using the HRC fuse with a tripping device . 440 V.
The construction of HRC fuse with a tripping device is shown in the Fig 3 .9. So it is always advantageous to use a fuse with a tripping device .
Plunge r
}12 Liquid Fuse
n
A_ fuse which uses a li uid instead of a powder for the ar extinction is called a liquid
Cap
fuse. The oil is enerally use as a iquid to extinguish the arc . The 'qui us 's very
popularlused in:iigh voltage sys e iqur• use aving breaking capacity of th e
Chemical charg e order of 6000 A is used for the systems upto 132 kV .
Weak link . , , The Fig. 3 .10 shows the constructional details liquid fuse .
Silve r The fuse basical>sr consists of a glass tube . The glass tube is filled with carbo n
d
fus e tetr iae sQlut ^n . The glass tube is sealed with the caps at both the ends . The caps use
elements are made , up of brass, ._. .
A B
Feeder
*o Majo r Minor Fault F
fuse fus e
,I-Kit detects and interrupts the faul t 1 . It only interrupts the fault current . The
current . detection is done by relay system .
'Fig . 3 .10 Construction A:A liquid fus e fter every operation, the replacemen t 6 . No need of replacement afte r
is necessary . operation.
3 .13 Discrimination
i
s
J/. Replacement takes time . 7. No question of replacement.
When there are two or more than two protective devices used for the protection of th e
same circuit then there must be co-ordination between the two . This co-ordination wit h . Simple to design hence cheap . 8 . Complicated to design henc e
which the correct operation of correct device takes place, the others remaining . unaffected is expensive .
called discrimination .
VTU -Switchgear and Protection 1 12 Fuses
VTU -Switchgear and Protection 113 Fuses
Review Question s
University Questions
1 . What is switch gear ? What is its function ?
1. With a neat sketch explain the time current and 'cut-off' characteristics of HRC fuse . Explain the use of these
2 . What is fuse ? State and explain the various types offuses . characteristics in electrical power system . (Aug .-2002, 10 Marks )
3 . What are the disadvantages of semienclosed fuse ? 2 . What is a liquid fuse ? Explain the time current and cut off characteristics of HRC fuse .
4. Define and explain the following terms related to a fuse,
(Feb .-2003, 10 Marks )
i) Current rating offus e
3 ._ Explain with a neat sketch the construction and working of a HRC fuse. Also explain its properties and
ii) Fusing curren t characteristics . (Aug.-2003, 10 Marks )
iii) Fusing factor
iv) Prospective curren t ❑❑❑
v) Cut-off curren t
vi) Pre-arcing tim e
vii) Arcing tim e
viii) Total operating time
ix) Breaking capacity
5 . Write a note on fuse element material .
6 . Why in modern days silver is preferred as a fuse element ?
7. Draw and explain the typical time - current characteristics of a fuse .
8 . State and derive the fuse law for a circular fuse element .
9 . How fusing current is calculated for strip type fuse element made up of,
i) Coppe r
ii) Zinc
iii) Aluminiu m
1
1 .0. State advantages and disadvantages offuse .
1.1 . Explain the construction and working principle of HRC fuse.
12 . Explain the various . characteristics of HRC fuse .
13 . Write a note on shapes offuse elements used for HRC fuse .
14 . State the advantages, disadvantages and applications of HRC fuse .
15 . Draw and explain the working of HRC fuse with tripping device .
16 . State the advantages of HRC fuse with tripping device.
17 . Draw and explain the working of a-liquid fuse .
18. What is discrimination ? Explain the discrimination between,
i) Fuse and fus e
ii) Fuse and circuit breaker
19. What is the difference between fuse and a circuit breaker ?
20. A current of 4 amperes fuses a lead fuse wire of diameter 0 .0203 inches . What current will fuse a wire of
diameter 0 .0491 inch ? (Ans . ;15 .04 A)
VTU -Switchgear and Protection 115 Protective Relayin g
4. To disconnect the faulty part as quickly as possible so as to minimise the damage t
the faulty part itself . For example, if there is a winding fault in a machine and if i o
t
persists for a long time then there is a possibility of the damage of the entire winding .
As against this, if it is disconnected quickly then only few coils may get damage d
instead of the entire winding .
Protective Relayin g 5. To restrict the spreading of the effect of fault causing least interference to the rest o
the healthy system. Thus by disconnecting the faulty part, the fault effects ge f
t
localised.
6. To improve the system performance, system reliability, system stability and servic
e
continuity .
The faults can not be completely avoided but can be minimised . Thus the protectiv e
4.1 Introductio n relaying plays an important role in sensing the faults, minimizing the effects of fault s
and minimizing the damage due to the faults .
Protective relaying is one of the several features of the power system design . Every part
of the power system is protected . The factors affecting the choice of protection are type an d 4 .3 P tective Zone s
rating of equipment, location of the equipment, types of faults, abnormal conditions an d
In a protective relaying scheme, the circuit breakers are placed at the
cost . appropriate points
such that anylement of the entire power system can be disconnected
The protective relaying is used to give an alarm or to cause prompt removal of an y repairing wor -,
element of power system from service when that element behaves abnormally . . The
abnormal `behaviour of an element might cause damage or interference within effectiv e
operation of rest of the system . The protéctive relaying minimises the damage to th e
equipment and interruptions to the service when electrical failure occurs . Along with som e Generator protectiv e
zon e
other equipments the relays help to minimise damage and improve the service .
The relays are compact and self contained devices which can sense the abnorma l Generator transforme r
conditions . Whenever an abnormal condition exists, the relay contacts get closed . Thi s protective zone
inturn closes the trip circuit of a circuit breaker . The circuit breakers are capable o f
disconnecting a faulty element, when they are called upon to do so by the relays . Thus entir e
process includes the operations like occurrence of fault, operation of relay, opening of a
circuit breaker and removal of faulty element . This entire process is automatic and fast ,
which is possible due to effective protective relaying scheme . Bus bar protective zon e
The protective relaying scheme includes protective current transformers, voltag e Circuit
breaker
transformers, protective relays, time delay relays, auxiliary relays, secondary circuits, tri p
circuits etc . Each component plays its own role, which is very important in the overall
operation of the scheme . The protective relaying is the team work of all these components .
The pr ective relaying also provides the indication of location and type of the fault .
(114)
Fig . 4.1 Protective zones
*! V
VTU - Switchgear and Protection 117 Protective Relayin g
11 6
ear and Protectio n It can be seen from the Fig. 4.2 that the circuit breakers are located in the connections to
VTU - Switch .
and maintenance requirements and also under e al c n di ion emike each power system element . This provision makes it possible to disconnect only the fault y
usual element from the system . Ocassionally for economy in the number of circuit breakers, a
a protective covering is provided around
ea ch element en . breaker between the two adjacent sections may be omitted but in that case both the powe r
shor t t circuits . Thusa
shhus ate zone which is blishe
establis h ed g aroundeac
as given zone will
A protective zone is the se ag d occurrin n system sections are required to be disconnected for the failure in either of the two .
ificance of such a rotective zone is that any e circus * • Each protective zone has certain protective scheme and each scheme has number o f
The si ; of relays which causes opening o alca , with ctNo
iv pones ar
cause the tri• in protective syste
, les thei rsote evariouscmpntwhareos part
c . ecap
that zone . The transformers, transmission lines, bus bars d
beors, .1 shows the various protective zones, use 4.4 P ary and Backup Protectio n
. The Fig .4 s of t a system
system is left unprotected The protection provided by the protective relaying equipment can be categorised int o
The boundaries of protective zones are decided by the location
e two types as :
transformers. . - - . . - . The overla in of rotectiv e zone 1.Primary protection
In practice, va_rous.: . . - of each and ever elemen ed and hence there is n o 2.Backup protection 3
zones is done to ensure complete saf e ot . The zones are overla The primary protection is the first line of defence and is responsible to protect all th e
. ec e . is ca es dea CC
d n e•
,. *' ro . For the failures withi ` pe e . power system elements from all the types of faults . The backup protection comes into play
chance o existence of a dead sot in, s stem ' n spot may only when the primary protection fails .
e rotective zones area -
. If there are no overlaps , then an dead mithe faultt
faul
, acent s e f s t clam t t even thoughh The backup protection is providèd as the main protection can fail due to many reason s
scary to sec ircwt breaker within the zone may not trip eventhoug
. The exten like,
exist p means th cy cause
e damag
dammage eeytoing the healthy system regrol s
o overlap ed region ; -1 a lure in circuit breaker
occurs .. Thisones
occuurs may ir
is relatively small
. The probability of the failure s in willn be als infrequents.
s breaker
protective z consequently y g. 'ilurein protective relay
is very low, the tripping of too man
.2 shows the overlapping of protective zones in the primary relayin .lure in tripping circuit
T Fig . 4
The Tlure in d .c. tripping voltag e
s of voltage or current supply to the rela y
Thus if the backup protection is absent and the main protection _ fails then there is a
possibility of severe damage to the system . `
When the primary protection is made inoperative for the maintenance purpose, th e
backup protection acts like a main protection . The arrangement of backup protectiv e
scheme should be such that the failure in main protection should not cause the failure i n
back up protection as well . This is satisfied if back up relaying and primary relaying do not
have-anything common . Hence generally backup protection is located at different stations
from the primary protection. From the cost and economy point . of view, the backup
protection is employed only for the protection against short circuit and not for any othe r
abnormal conditions .
4 .4 .1 Co pt of Backup Relayin g
seder the backup relaying employed for the transmission line section EF as shown i n
the Fig. 4.3.
The relays C,-D, G and H are primary relays while A, B, I and J are the backup relays .
Normally backup relays are tripped if primary relay fails . So if the primary relay E fails
to trip, then backup relays A and B get tripped . The backup relays and associated backup
relaying equipments are physically apart from the faulty equipment .
in primary relaying
Fig . 4 .2 Overlapping zones
Protective Relaying VTU -Switchgear and Protection 119
VTU -Switchgear and Protection 118 Protective Relayin g
4.5 Ess 'al Qualities of Protective Relayin g
Station K
protective relaying scheme should have certain important qualities . Such an essential
qualities of protective relaying are ,
f1, Reliability
✓2'Selectivity and Discriminatio n
2. Speed and Tim e
C Sensitivity
Transmissio n . Stability
lin e
v,-6, Adequatenes s
Fig . 4 .3 Backup relaying . \„,,.7, Simplicity and Econom y
e
The backup relays A and B provide backup protection for fault at station K . Also th
backup relays at A and F provide the backup protection for the faults in line DB . 54Reliability
The backup relaying often provides primary protection when the primary relays are ou t A protective relaying should be reliable is its basic quality . It indicates the ability
of the
relay system to operate under the predétemdconditions . There are various component s
of service for repairs . w i icl1 go into the o a eration before a rel .
s e . - rate . Therefore every component and circui t
It is obvious that when the backup relay operates, the larger part of the system i w i is involved in the operation of a relay
plays ah important role . The reliability of a
disconnected . p5 Etion system depends on the reliability of various components like circuit brew cers,
The important requirement of backup relaying is that it must operate with sufficien t relays, current trans. ,• • _ . .' , ,, - fs - f .
h rcuitsetc.
time delay so that the primary relaying is given a chance to operate . When fault occurs, bot The proper maintenance also plays an important role in improving the reliable operation f
p o
the type of relays starts relaying operation but primary is expected to trip first and backu the system . The reliability can not be expressed in the mathematical
expression s but can be
will then reset without having had time to complete its relaying operation . judged from the statistical data . The statistical survey and-records-give good idea about th
e
When the given set of relays provides the backup protection for several adjacent syste m reliability of the protective system . The inherent reliability is based on the de
i gn which is
s
elements then the slowest primary relaying of any of those will determine the necessar y based on the long experience . This can be achieved by the factors like ,
time delay of the given backup relays . i) Simplicity ii) Robustnes s
iii) High contact pressure iv) Dust free enclosur e
4.4 .2 Methods of Backup Protec tio n iv) Good contact material vi) Good workmanship an d
protection ate classified as ,
The various . methods used for the backup , vii) Careful maintenanc e
In this scheme, a single breaker is used by both primary a s
1 e ay Backup Protection ;
well as backup protection but the two protective systems are different . 4. Selectivity and Discriminatio n
In this method, separate breakers are provided fo r
eaker Backup Protection : .
The selective is the a i ' 've s stem to identif the faulty part correctl y
primary and backup protection. Both the types of,breakers are at the same station and to disconnect that part without affecting the rest
of the healthy part of system. The
r
ote Backup Protection : In this method, separate breakers are provided fo t discrimination me ans to distinguis The discrimination ' . e .
primary and backup protection . . The two types of breakers are at the, differen sys e ne a ity to • istin• uish between norma condition and
abnormal condition an d
stations and are completely isolated and independent of each other . so •e ween a .norma condition within protective zone and elsewhere
In this method, primary protection is a t . Theprotectiv e
4 . entratly Co-ordinated Backup Protection : e
system should o erate - *, . .
various stations . There is a central control room and backup protection for all`th con . i ion . ence it must clearly discriminate between normal and abnormal condition
e loa d .
stations is at central control room . Central control continuously inspects th : d T Zul tfe protective
- system should select the faulty part and disconnect only the faulty par t
flow and frequency in the system . If any element of any part of the system fails, loa f without disturbing the healthy part of the system .
flow gets affected which is sensed by the control room . The control sourèe consists o
o
a digital computers which decides the proper switching action . The method is als The protective system should not operate for the faults beyond its protective zone . For
example, consider the portion of a typical power system shown in the Fig . 4.4.
called centrally controlled backup protection .
1 20 Protective Relaying VTU -Switchgear and Protection 121
VTU - Switchgear and Protection Protective Relayin g
4.5 ensitivity
Therotective system should be sufficiently sensitive so that it can o erate reliabl y
when required . The sensitivity of the system is the ability of the relay system to operate w t h
low value of actuatfn
` antity .
It indicates the smallest value of the actuating quantity at which the protection start s
operating in relation with the minimum value of the fault current in the protected zone .
The relay sensitivity is the function of the volt-amperes input to the relay coil necessar y
to cause its operation . Smaller the value of volt-ampere input, more sensitive is the relay .
Thus 1VA input relay is more sensitive than the 5VA input relay .
Mathematically the sensitivity is expressed by a factor called sensitivity factor K s. It is
Fig . 4 .4
t the ratio of minimum short circuit current in the protected zone to the minimum operatin g
It is clear from the Fig . 4 .4 that if fault F 2 occurs on transmission line then the circui
. The current required for the protection to start .
breakers 2 and 3 should operate and disconnect the line from the remaining system
protective system should be selective in selecting faulty transmission line only for the faul t
and it should isolate it without tripping the adjacent transmission line breakers or th e
F2
transformer. where sensitivity facto r
If the protective system is not selective then it operates for the faults beyond it s Is = minimum short circuit current in the zone t
protective zones and unnecessary the large part of the system gets isolated . This causes a lo t Io = minimum operating current for the protection r -
'of inconvenience to the supplier and users . 4.5.5 ability
4.5 .3 peed and Tim e The stability is the quality of the protective system due to which the system remains
A protective system must disconnect the fault s stem a nscible .1f thefaulty inoperative and stable under certain s•ecified conditions such as transients, disturbance ,
isconnected for a long time then, t ou au s etc . For providing the stability, certain mo i ications are require . n the
evices carrying a t currents may get damaged . system design . In most of the cases time delays, filter circuits, mechanical and electrical bia s
. Such low voltage may affect th e are provided to achieve stable operation during the disturbances .
2 . The failure leads to the reduction in system voltage .
motors and generators running on the consumer side
. 4.5 .6 dequateness
,f fault persists for long time, then subsequently other faults may get generated
The high speed protective system avoids the • ossibility of such undesirable effects. ✓✓There are variety of faults and disturbances those may practically exists in a powe r
system . It is impossible to provide protection against each and every abnormal conditio n
The total time required which may exist in practice, due to economical reasons . But the protective system mus t
i'hter- tô*?in in the circuit breaker is calle e . It is the sum of rela*time*an d
aril provide adequate protection for any element of the system . The adequateness of the syste m
circus •reaker time . The relay time is the time ewe r. he instant of aunt occurrence can be assessed by considering following factors ,
byeth
the instant :o closure ofrela contacts . The circuit breaker time is tha time±akanThe faul t 1. Ratings of various equipment s
circuit reak • • o • . • walk- e 2. Cost of the equipment s
operation of the protectiv e
clearing time should be as---small as possible to have high-speed - 3. Locations of the equipment s
system. 4. Probability of abnormal condition due to internal and external causes .
Though the small fault clearing time is preferred, in practice certain time lag is provided .
5. Discontinuity of supply due to the failure of the equipmen t
This is because ,
1.To have clear discrimination between primary and backup protection 4.5 .7iiplicity and .Econom y
,
2. To prevent unnecessary operation of relays under the conditions such as transients n addition to .all the important qualities it is necessary that the cost of the system shoul d
starting inrush of current etc . be well within limits . In practice sometimes it is not necessary to use ideal protection schem e
Thus fast protective system is an important quality which minimises the damage and i t which is economically unjustified . In such cases compromise is done . As a rule, th e
improves the overall stabilit of the sower s stem . protection cost should not be more than 5% of the total cost . But if the equipments to b e
protected are very important, the economic constraints can be relaxed .
VTU -Switchgear and Protection 1 22 Protective Relaying VTU - Switchgear and Protection 123 Protective Relayin g
The protective system should be as simple as possible so that it can be easily maintained . 4.6.4 Relays Based on Timin g
The complex system are difficult from the maintenance point of view . The simplicity and - In relays the time between instant of relay operation and instant at which tripping o f
reliability are closely related to each other . The simpler systems are always more reliable . contacts takes place, can be controlled . This time is called operation time . Based on this, th e
time relays are classified as ,
4 .6 Classification of Protective Relay s 1. Instantaneous Type : In this type no time is lost between operation of relay an d
All the relays consist of one or more elements which get energised and actuated by th e tripping of contacts . No intentional time delay is provided .
electrical quantities of the circuit . Most of the relays used now a days are electro-mechanica l 2. Definite Time Lag Type :'In this type intentionally a definite time lag is provide d
type which work on the principles of electromagnetic attraction and electromagneti c between operation of relay and tripping of contact .
induction . 3. Inverse Time Lag type : In this type, the operating time is approximately inversel y
proportional to the magnitude of the actuating quantity .
4.6 .1 Electromagnetic Attraction Type Relay s
4.6 .5 Distance Type Relay s
The electromagnetic attraction type relays operate on the principle of attraction of a n
armature by the magnetic force produced by undesirable current or movement of plunger i n These relays work on the principle of measurement of voltage to current ratio . In this
a solenoid . These relays can be actuated by a .c . or d .c. quantities . The various types of thes e type, there are two coils . One coil is energised by current while other by voltage . The, torque
relays are, produced is proportional to the ratio of the two quantities . When the ratio reduces below a
1. Solenoid Type : In this relay, the plunger or iron core moves into a solenoid and th e set value, the relay operates . The various types of these relays are ,
operation of the relay depends on the movement of the plunger . 1. Impedance Type : In this type, the ratio of voltage to current is nothing but a n
2.Attracted Armature Type : This relay operates on the current setting . When current i n impedance which is proportional to the distance of the relay form the fault point .
the circuit exceeds beyond the limit, the armature gets attracted by the magnetic forc e 2. Reactance Type : The operating time is proportional to the reactance which i s
produced by the undesirable current . The current rating of the circuit in which rela y proportional to the distance of the relay from the fault point .
is connected plays an important role in the operation of the relay. 3. Admittance Type : This is also called mho type . In this type, the operating time i s
3.Balanced Beam Type : In this relay, the armature is fastened to a balanced beam . For proportional to the admittance .
normal current, the beam remains horizontal but when current exceeds, the armatur e 4.6 .6 Differential Type Relay s
gets attracted and beam gets tilted causing the required operation .
A differential relay operates when the vector difference of two or more electrica l
4.6 .2 Induction Type Relays quantities in the circuit in which .relay is connected, exceeds a set value . These are classifie d
These relays work on the principle of an electromagnetic induction . The use of these as,
relays is limited to a .c. quantities. The various types of these relays are , 1. Current Differential Type : In this type, the relay compares the current entering a
1.Induction Disc Type : In this relay, a metal disc is allowed tO rotate between the tw o section of the system and the current leaving the section . Under fault condition, thes e
electromagnets . The electromagnets are energised by alternating currents . The two currents are different .
types of constructions used for this type are shaded pole type and watthour meter 2. Voltage Differential Type : In this type, two transformers are used . The secondaries
type. of the transformers are connected in series with the relay in such a way that th e
2. Induction Cup Type : In this relay, electromagnets act as a stator and energised b y induced e .m.f .s are in opposition under normal conditions . Under fault condition,
relay coils . The rotor is metallic cylindrical cup type . primaries carry different currents due to which induced e .m .f.s no longer remain i n
opposition and the relay operates .
4.6 .3 Directional Type Relay s
4.6 .7 Other Types of Relay s
These relays work on the direction of current or power flow in the circuit . The various
types of these relays are , Various other types of relays which are used in practice are,
1.Under voltage, current, power relay : This relay operates when the voltage, current o r
1 . Reverse Current Type : The relay is actuated when the direction of the curren t power in a circuit falls below a set value .
is reversed or the phase of the current becomes more than the predetermined value .
2. Over voltage, current, power relay : This relay actuates when the voltage, current o r
2 . Reverse Power Type : The relay is actuated when the phase displacemen t power in a circuit rises above a set value.
between applied voltage and current attains a specified value .
3. Thermal Relay : This relay actuates due to the heat produced by the current in th e
relay coil.
VTU -Switchgear and Protection 12 5
124 Protective Relayin g
VTU - Switchgear and Protection
4.Rectifier Relay : In this relay, the quantities to be sensed are rectified and then give n
to the moving coil unit of the relay .
5. Permanent Magnet Moving Coil Relay : In this relay, the coil carrying current is fre e
to rotate in the magnetic field of a permanent magnet . This is used for d.c . only .
6. Static Relay : This relay uses some electronic method for sensing the actuatin g
quantity. It uses a stationary circuit .
7. Gas Operated Relay : The gas pressure is adjusted according to the variations in thne
actuating quantity . This gas pressure is used to actuate the relay . Buchholz relay is a
example of such type of relay .
Primary
Moulde d
insulation
The insulation on the bar type primary is bakelized paper tube or a resin directly Primary winding consists of large number of turns while secondary has less number of turn s
moulded on the bar . Such bar type primary is the integral part of the current transformer . and usually rated for 110 V, irrespective of the primary voltage rating . The primary i s
The core and the secondary windings are same in bar type transformer . connected across the high voltage line while secondary is connected to the low rang e
voltmeter coil . One end of the secondary is always grounded for safety purpose . Th e
The stampings used for the laminations in current transformers must have hig h
connections are shown in the Fig . 4.12.
cross-sectional area than the ordinary transformers . Due to this, the reluctance of th e
interleaved corners remains as low as possible . Hence the corresponding magnetizin g As a normal transformer, its r_a_tio
current is also small . The windings are placed very close to each other so as to reduce th e N
N*
*J=
leakage reactance . To avoid the corona effect, in bar type transformer, the external diamete r V2
of the tube is kept large . So if voltage ratio of P .T. is-known and the voltmeter reading is known then the hig h
The windings are so designed that without damage, they can withstand short circuit voltage to be measured, can be determined .
forces which may be caused due to short circuit in the circuit in which the current A 11000 : 110, potential transformer is used along with a voltmeter reading 87 .5V.
Ex . 4.2 :
transformer is inserted . Estimate the value of line voltage .
For small line voltages,-the tape and varnish are used for insulation . For line voltage s Sol . : For a P .T .
above 7 kV the oil immersed or compound filled current transformers are used . V I _ 11000
V2 .110
4.11 Why Secondary of C .T. Should not be Open ?
and V2 = 87 .5 V
It is very important that the secondary of C .T . should not be kept open . Either it shoul d V I _ 11000
be shorted or must be connected in series with a low resistance coil such as current coils of 87 .5 11 0
wattmeter, coil of ammeter etc . If it is left open, then current through secondary becomes VI = 8750 V
zero hence the ampere turns produced by secondary which generally oppose primar y
ampere turns becomes zero . As there is no counter m .m .f., unopposed primary m.m.f. This is the value of high voltage to be measured .
(ampere turns) produce high flux in the core . This produces excessive core losses, heatin g
4.12 .1 Constructio n
the core beyond limits . Similarly heavy e .m .fs will be induced on the primary and secondar y
The potential transformer use larger core and conductor sizes compared to conventiona l
side . This may damage the insulation of the winding . This is danger from the operator poin t
of view as well . It is usual to ground the C .T . on the secondary side to avoid a danger of power transformer . In potential transformer, economy of material is not an importan t
shock to .the operator . consideration at the time of design . The accuracy is an important consideration .
Hence never open the secondary winding circuit of a current transformer while it s The shell type or core type construction is preferred for potential transformer . The shell
type is used for low voltage while core type for high voltage transformers . At the time o f
primary winding is energised .
assembly special core is required to reduce the effect of air gap at the joints .
Thus most of the current transformers have a short circuit link or a switch at secondar y
The coaxial primary and secondary windings are used, to reduce the leakage reactance .
terminals . When the primary is to be energised, the short circuit link must be closed so tha t
The secondary winding which is a low voltage winding is always next to the core . Th e
there is no danger of open circuit secondary .
primary winding is a single coil in low voltage transformers . For high voltages, insulation i s
4.12 Potential Transformers (P .T.) the main problem . Hence in high voltage potential transformers, primary is divided int o
number of small sections of short coils to reduce the need of insulation between coil layers .
The basic ' principle of these The cotton tape and varnished cambric are used as the insulations for windings . Hard
transformers is same as curren t
fiber separators are used in between the coils . The oil immersed potential transformers ar e
transformers . The high alternating voltage
used for the voltage levels above 7 kV .
are reduced in a fixed proportion for the
measurement purpose with the help of For oil filled potential transformers, oil filled bushings are used . Two bushings are
potential transformers . The construction of required when no side of the line is at earth potential .
these transformers is similar to the norma l The overall construction of single phase, two winding potential transformer is shown i n
transformer . These are extremely accurat e the Fig . 4.13 .
ratio step down transformers . Th e
windings are low power rating windings .
Fig . 4 .12 Potential transformer
Protective Relaying VTUSwitchgear and Protection 133 Protective Relayin g
VTU -Switchgear and Protection 1 32
6 = angle between secondary winging induced voltage where = no load power factor angle
and secondary winding curren t XI, = equivalent reactance of transformer referred t o
5 is positive for lagging p .f. and negative for leading p.f. primary
= X1 +X2=X 1 +n22 X2
4 .14.2 Phase Angle Erro r Rle = equivalent resistance of transformer referred t o
In the power measurements, it is must that the phase of secondary current is to b e primary
displaced by exactly 180° from that of primary current for C .T. While the phase of secondar y = R1 +R2 =R 1 +n2R2
voltage is to be displaced by exactly 180° from that of primary voltage, for P .T. But actually it VI
is not so . The error introduced due to this fact is called phase angle error . It denoted by angle and n= = N l for potential transforme r
V2 N2
e by which the phase difference between primary and secondary is different from 180° .
The precise expression to calculate the angle e is, 4.14 .3 Reduction of Ratio and Phase Angle Error s
180 Im cosh-I c sin 5 degree The ratio and phase angle errors can be minimized by using following methods . :
e 1 . As the errors depend on components of exciting current, reduce th e
n nI2
magnetizing and loss components of exciting current . This requires to provid e
While the approximate formula to calculate e is, smaller magnetic path, good core material and low flux density in core .
0= 180[1m 180 1m 2 Reduction of resistance and leakage reactance . The values decide the secondar y
7t nI 2JJ It n x 1In circuit power factor which affects the errors . This can be achieved by providin g
thick conductors and smaller length of mean turn .
= 180[I m 'degree 3 . Providing turns compensation at no load the actual ratio exceeds the turn s
1t Il ratio thus the solution to this is to reduce primary turns or increasin g
Similar to ratio error, this error also. depends on the components of exciting current ( I° ), secondary turns and to make actual ratio equal to nominal ration for on e
load current i.e. secondary current and power factor . This error does not affect the particular value of load .
measurements of only current or voltage but do affect at the time of power and energ y Ex. 4.3 : The no load current components of a current transformer are ,
measurements . magnetizing 'component =102 A
The phase angle error for P .T. is defined as, core loss component = 38A
The current transformation ratio is 1000 /5 A . Calculate the approximate ratio error a t
- In [Xle cosy -Rle'sin5]+IcXi -Im RI rad
full load.
e -
nV2 Sol. : Im = 102A, lc = 38A
12
2
(X2e cos5-R2e sin6]+ IXln mRi
2
V 1000
I(,, = nominal ratio = 5=200
where 6 = secondary p,f . angle At full load, IZ = 5A
R2e = equivalent resistance of transformer referred to 38
R = n+ -I` = 200+
secondary = R2 + Ri = R2 + Rz I2 5
n = 207 .6
VTU - Switchgear and Protection 136 Protective Relaying Protective Relayin g
VTU -Switchgearand Protection 137
Ratio error = K" -R x100= 2002-072.607'6 x100 K„ - R 400-398 .52
R /° Ratio error = * R 100 x 100
= 398 .52
_ -3 .66%
= 0.3713%
Ex. 4.4 : A current transformer has a single turn primary and 400 secondary turns . The
'magnetizing current is 90A while core loss cu r rent is 40A . Secondary circuit phase angle 180 I,,, cosh-Icsin 5
And e
is 28° . Calculate the actual primary current and ratio error when secondary carries 5 A rc [ n l2
current .
180[8x0 .8-3x(-0 .6)
Sol. : Im = 90A, I, = 40A, S = 28°, I, = 5 A
7c 399x5 J
n = 400 =40 0 = 0.2355°
1
= n = 400
4 .15 Advantages and Disadvantages of Instrument Transformer s
Now actual ratio R = ri + I"` Sind+I ` cosh
12 The advantages of instrument transformers can be listed as ,
400+ 90 x sin 28 + 40 x cos 28
1.The normal range voltmeter and ammeter can be used along with these transformer s
= to measure high voltage and currents .
5 The rating of low range meter can be fixed irrespective of the value of high voltage o r
2.
= 415 .514. current to be measured .
Actual primary current = actual ratio x 1 2 '3 . These transformers isolate the measurement from high voltage and current circuits .
= 415 .514 x 5 = 2077 .5703 This ensures safety of the operator and makes the handling of the equipments ver y
easy and safe .
Ratio error = K" Rx100= 400 415 .514 x 100 . These can be used for operating many types of protecting devices such as relays or
R 415 .51 4 4
pilot lights .
= -3 .733%
Ex. 4.5 : A current transformer has turns ratio 1 :399 and is rated as 2000/5A . The core loss ,5 . Several instruments can be fed economically by single transformer .
Disadvantage :
component is 3A and magnetizing component is 8A, under full load conditions . Find the
phase angle and ratio errors under full load condition if secondary circuit power factor i s The only disadvantage of these instrument transformers is that they can be used only fo r
0.8 leading . a .c. circuits and not for d .c . circuits .
Sol. : lc = 3A, lm = 8A, cos 5 = 0 .8 leadin g Applications of C.T.s and P .T.s :
n = 399 = 39 9 The C.T.s and P .T .s are used for,
1 1. Circulating current differential protection .
Nominal ratio = Kn = 2000 = 400 2. Over current phase fault protection .
5
m ' 3. Distance protection .
Actual ratio = R = n + I sin 5 +I cos d
I2 4. Intermediate CTs for feeding protective devices, measuring systems, relays etc .
Rated I 2 = 5 A Review Questions
d = cos-1 0 .8 = - 36 .86° . .. negative as leading 1. What is protective relaying ? What is a relay ?
sin d = sin (-36 .86°) = - 0.6 2. Explain the various functions of protective relaying .
8x(-0 .6)+3x0 . 8
R = 399+ 3. What is a protective zone ? With a simple diagram, show the various zones in a typical power system .
5 4. Why the protective zones are arranged in overlap fashion ? With the help of simple diagram, show how th e
= 398 . 52 zones are overlapped .
5. Explain what is meant by primary protection and backup protection .
6. State the various methods used to provide backup protection .
VTU -Switchgear and Protection 138 Protective Relaying
(139 )
Electromagnetic Relays VTU - Switch ear and Protection 141 Electromagnetic Relay s
VTU - Switchgear and Protection 140
Relay contacts
C . T. o
C .T.
-Relay coi l o o
Relays
.- Fault
Breake r
A - auxiliary C1 C2 C3
Circuit to be switch
protected
Circuit
breaker i
Fig . 5 .1 Typical relay circui t
ô Trip coi l
a
5 .1 .2 Auxiliary Switch
Another important device in the trip circuit is an auxiliary switch. It is a multipoint
switch generally 4 point, 6 point, 12 point or 24 point . This switch is mechanically coupled
Fus e
with operating mechanism of the circuit breaker . Thus when circuit breaker opens, th e
switch also gets opened . The switch is in the trip circuit and hence when it opens, it breaks
the current through the trip circuit . Once the current in the trip circuit is interrupted th e
Equipment to b e
1 Battery
relay contacts come to normal position . The advantage of an auxiliary switch is that the protected suppl y
breaking of trip circuit takes place only across the switch and hence possible arcing due t o
current interruption across the relay contacts gets avoided . Such arcing is harmful for rela y Fig . 5 .2 Relay with make type contac t
contacts as relay contacts are delicate and light. To interrupt a current through the inductiv e As mentioned earlier, a separate supply is necessary for the relay operation. The relays
circuit like trip circuit a .robust mechanical switch is necessary. This purpose is served by an are connected in star while the relay contacts are connected in parallel . The entire rela y
auxiliary switch, protecting delicate relay contacts . In addition to this, indication circuit s conta ct unit is connected in series with the auxiliary switch,-trip coil and the battery . Relay
showing whether circuit breaker is open or close and some other control circuits also ge t contacts are open in normal position .
connected or disconnected by an auxiliary switch .
Operation : When the fault occurs, the current through relay coils increases to a
The auxiliary switch is generally placed in the control cabinet of the circuit breaker . very -high value . Due to this, the normally open relay contacts C,, C 2 and C 3 get
closed . This activates the trip coil of a circuit breaker . The auxiliary switch is initiall y
5.2 Tripping Schemes in Circuit Breake r closed along with the circuit breaker . So when contacts C 1, C2 and C3 are closed, th e
Two schemes are very popularly used for tripping in circuit breakers which are , current flows through trip coil of circuit breaker . This activates the trip coil which
opens the circuit breaker . As auxiliary switch is mechanically coupled with the circui t
1. Relay with make type contac t
breaker, it also gets opened . This interrupts the current through trip coil . Thus supply
2. Relay with break type contac t to faulty part gets interrupted and trip coil also gets de-energized . This brings the
The relay with make type contact requires auxiliary d .c. supply for its operation whil e relay contacts back to normal position . Due to auxiliary switch, arcing across rela y
the relay with break type contact uses the energy from the main supply source for it s contacts gets avoided . As relay contacts are normally open and they 'make' the circui t
operation . Let us see the details of these two types of schemes . to open the circuit breaker hence called make type contact relay .
142 Electromagnetic Relays VTU -Switch ear and Protection 143 Electromagnetic Relay s
VTUSwitchgear and Protection
R Y B
5.2 .2 Relay with Break Type Contac t
The schematic arrangement of various elements in a relay with break type contact i s
shown in the Fig . 5.3 . P.T.
Fus e
I
Relays' g
I ô I â. I
o
C .T. ô
Relay o
contact s -ih o I II o I o
ô I oo I o Relay s
* *
C1 C3
* *1 I
Circui t I lI i
breaker
C* C2
Unde r
L
a Circui t o voltag e Relay
o o
0 0
j °r breake r
trip coi l
trip coil contacts
5 .3 Electromagnetic Attraction Relay s The minimum current at which the armature gets attracted to close the trip circuit i s
called pickup current.
In these relays, there is a coil which enerzises an electromagnet . When the operatin g
Generally the number of tappings are provided on the relay coil with which its turns ca n
current becomes large, the magnetic field produced by an electromagnet is so high that i t
be selected as per the requirement . This is used to adjust the set value of an operatin g
attracts the armature or plunger, making contact with the trip circuit contacts . These ar e
simplest type of relays . The various types of electromagnetic attraction type relays are , quantity at which relay should operate .
1. Attracted armature rela y An important advantage of such relays is their high operating speed . In modern relays
2. Solenoid and plunger type rela y an operating time as small as 0 .5 msec is possible . The current-time characteristics of suc h
relays is hyperbolic, as shown in the Fig . 5 .6.
5.3 .1 Attracted Armature Type Rela y
There are two types of structures available for attracted armature type relay which are ,
i) Hinged armature type
ii) Polarised moving iron typ e
The two types of attracted armature type relays are shown in the Fig . 5.5 (a) and (b) .
Current-timé',Icharacteristic s
Fig . 5 .6
Input 5.3.2 Solenoid and Plunger Type Rela y
Vor 1
The Fig . 5 .7 shows the schematic arrangement of solenoid and plunger type relay whic h
(a) Hinged armature type relay (b) Polarised moving iron type relay works on the principle of electromagnetic attraction.
It consists of a solenoid which is nothing but an electromagnet . It also consists a movable
Fig . 5 . 5
iron plunger . Under normal working conditions, the spring holds the plunger in th e
In attracted armature type, there exists a laminated electromagnet which carries a coil . position such that it cannot make contact with trip circuit contacts .
The coil is energized by the operating quantity which is proportional to the circuit voltage o r Under fault conditions when current through relay coil increases, the solenoid draw s
current . The armature or a moving iron is subjected to the magnetic force produced by th e
the plunger upwards . Due to this, it makes contact with the trip circuit contacts, whic h
operating quantity . The force produced is proportional to the square of current hence thes e
results in an opening of a circuit breaker .
relays can be used for a .c. as well as d .c. The spring is used to produce restraining force .
When the current through coil increases beyond the limit under fault conditions, armatur e
gets attracted . Due to this it makes contact with contacts of a trip circuit, which results in a n
opening of a circuit breaker .
146 Electromagnetic Relays VTUSwitchgear and Protection 147 Electromagnetic Relays
VTU •Switchgear and Protection
I = I K' = constant
Input - Ki
Vor l
This is the current at which relay operates in case of d .c. operation .
For a.c. operation : In a.c . electromagnetic relays, the electromagnetic force i s
proportional to square of the current but it is not constant . It is given by,
Electroma gnet Fe =KI2
Coil
= 2 KIm- 1 KI*cos2m t
where = Maximum value of the operating curren t
K = constant
It shows that the electromagnetic force consists of two components ,
o
i) Constant, independent of time .
To trip circuit ii) Pulsating at double the frequency of applied voltage .
Movable _ _-ro P---, The total force thus pulsates at double the frequency .
iron plunger
If the restraining force Fr which is produced by the spring is constant then the armature
of relay will be picked up at time tl and it drops off at time t2 as shown in the Fig. 5.8.
â•--Sprin g
r
Fig. 5 .7 Solenoid and plunger type relay
Principle of Electromagnetic Attraction Relay s
5 .3 .3 Operatin g
The electromagnetic force produced due to operating quantity which is exerted o n
armature, moving iron or plunger is proportional to the square of the flux in the air gap .
Thus neglecting the saturation effect, the force is proportional to the square of the operatin g
. both.
current. Hence such relays are useful for a .c. and d .c
. operation, the electromagnetic force is constant . When
For d .c . operation : In d.c
this force exceeds the restraining force, the relay operates .
K112
Now Fe =
where Fe = Electromagnetic forc e
K, = constan t Fig. 5 .8 Electromagnetic force and current curve s
I = Operating current in a coi l Thus relay armature .pulsates at double frequency . This causes the relay to hum an d
produces a noise . It may cause damage to the relay contacts .
And Fr = K 2
where Fr = Restraining force due to spring including frictio n To overcome this difficulty, the air gap flux producing an electromagnetic force i s
K2 = Constant divided into two fluxes acting simultaneously but differing in time phase . This causes
resulting electromagnetic force to be always positive . If this is always greater tha n
On the verge of relay operating, electromagnetic force is just equal to the restrainin g restraining force F then armature will not vibrate . The phase lag between the tw o
force . components of fluxrcan be easily produced using shading in a relay . The flux through th e
K112 = K 2 shaded pole lags behind the flux through the unshaded part .
12 = K2
Kl
148 VTUSwitchgear and Protection 149 Electromagnetic Relay s
n
VTU - Switch . ear and Protectio
s Before studying these types in detail, let us derive the torque equation for the inductio n
5.3 .4 Advantages of Electromagnetic Relay type relays, which is same for all the three types of relays . .
The various advantages of electromagnetic relays are ,
. and d .c. 5.4.1 Torque Equation for Induction Type Relay s
1. Can be used for both a .c As mentioned earlier, the alternating currents supp lied to two electromagnets produce
2. They have fast operation and fast reset . s
arrangements
instantaneous . instantaneous, the o perating tim e the two alternating fluxes $and 4 2 . These two .- ,.
These are almo s W . slow peratin g
3.
with current ., W th ar in etc phase difference of a in betweenkernsuch that 2 l ads
mathematical) ex s,
Thus the two fl„xP* **n he
and resetting times can be obtained . .
High operating speed with operating time in few milliseconds also can be achieved sinm t
1 = Cm (1)
4. .c, operation and 60 to 90% for the d .c .
The pickup can be as high as 90-95% for d 4 = d'2m sin (co t+a) . . . (2 )
5.
operation. These alternating fluxes caus e
Modern relays are compact, simple, reliable and robust . the induced e.m.f.s in the rotor .
6.
Due to the induced e .m .f.s, the
.5 Disadvantages of Electromagnetic Relay s
5 .3 eddy currents i1 and i2 re
The few disadvantages of these relays are , circulated in the disc . The two
.
1. The directional feature is absent eddy currents react with eac h
as the working can be affected by the
2. Due fast ell pulsating component ,
value less than se t other to produce sforce w11 c
acts on therotor.
contain d .c: as as w s
value, the relay . can operate during, transient The Fig . 5.9 shows how th e
.6 Applications of Electromagnetic Relay s forces are produced in a section o f
5 .3 rotor due to the . alternating fluxes .
The various application s of these relays are , The instant considered to sho w
.c . and d .c . equipments .
1. The protection of various a .over/under voltage, protection of various a .c. and d .c. Fig . 5 .9 Torque productio n the various quantities is whe n
2. The over/under current and both the fluxes are directe d
equipments . e downwards and are increasing in magnitude . The induced eddy currents lag behind th e
In the definite time lag over current and earth fault protection along with definite tim respective fluxes by -90°.
3.
lag over current relay . Assumption : The parts of rotor in which rotor currents flow have negligible sel f
4. For the differential protection . inductance and hence the rotor currents are in phase with the respective induce d
Used as a iliary relays in the contact systems of protective relaying schemes voltages.
5.
.9z .4 The induced voltages are proportional to the rate of change of fluxes and hence the edd y
ction Type Relays( ,
5 .4 I currents also are proportional to the rate of change of fluxes . Hence we can write,
relays. These relays work on th e
The induction type relays are also called magnitude . In these rela s a metallic disc is allowe d it
do t
(3)
principle of the induction motor or an ever . meter dt
to rotate between t Zem two e l -aroma n
torque is p roduced in these relays due to the interactio 12
)
a .dql 2 , . . (4 )
thé he of alternatin •-** * * aced m the rotor byailofher terns ng flux; dt
of one alternatin
e_fregiiency but are displaced in time and ^spâce• As the interactio n Substituting
e two and from (1) and (2) we get ,
ernating fluxes is the base of operation of these relays, these are not used for the d .c.
fluxesl1av_e_sam C
sincot)
ofalt . These are widely used for protective relaying involving only a .c . quantities. i « d1m a Cm cos co t (5)
j quantities dt
e re ays are ,
Based on the constructio n , the various types of the induction typ d[c 2m sin(cot+a))
1. Shaded pole type dt cc 2m COS (cot+a) ., (6)
2. Watt hour meter type
3. Induction cup type
150 Electromagnetic Relays VTU -Switchgear and Protection
VTU -Switchgear and Protection 151 Electromagnetic Relay s
The forces are produced due to the interaction of 11 with i2 and ¢ 2 with il . It consists of an aluminium disc which is free to rotate in an air gap of an electromagnet .
(7) The . art of . • ' - - .••
Fl a (1)1 i 2 1ng . This is
e
(8) ca ed shading ring . The total flux roduced due to the alternating current split ;nta_too
and , F2 cc (1)2 it fluxes displaced in time and space due to the shading ring .
The directions of F l and F, can be obtained by Flemings left hand rule . It can be seen from Due to the alternating flux, e .m .f. gets induced in the shading ring . This e .m .f . drives th e
the Fig . 5 .9 that the two forces are acting in the opposite directions and hence the net forc e
currents causing the flux to exist in shaded portion . This flux lags behind the flux in th e
acting on the disc is proportional to the difference between the two forces .
unshaded portion by angel a .
F a F 2 - Fl
Let = Flux in shaded portio n
F oC 11)2 in - (1) 1 12 .(9)
from (1), (2), (5) and (6) in th e = Flux in unshaded portio n
Substituting the proportional expressions of (1o1,
E S = E .M .F . induced in the disc due to (k 5
equation (9) we get,
F x [4) 2 ,1 sin (cot+a)* 1m cosc)t-`) i mSmcot4)2m c oS (O)t+a ) ] E u = E .M .F . induced in the disc due to (1) u
IS = Induced current due to E S
a 4 im cl)2m [sin ((1.) t + a) cos (cot) - sin (cot) cos (co t + a) ]
] I,, = Induced current due to E, ,
klm k2m [sin ((At+a-cot)
o`
E„ lags behind C, by 90° while E S lags behind cli 5 by 90°. The current I S lags ES by small
F cc cklm(k2m sin a angle p while Iu lags E„ small angle f3 . This angle is generally neglected and I S and Iu are
The equation (10) gives the : het force acting on the disc which is proportional to sin a . assumed to be in phase with E S and Eu respectively, in practice . The phasor diagram i s
Substituting the r .m .s . values e fluxes instead of maximum values we get , shown in the Fig . 5.11 .
. . . (11 )
F a (P I 13' 2 sin a
I important to note that the net force or torque acting on the disc is same at ever y
stant . The action of relay under such force is free from vibrations .
It can be observed from the equation (10) that if a is zero then the net force is zero an d
disc cannot rotate . Hence there must exist a phase difference -between the two fluxes . The
torque is maximum when the phase difference a is 90° .
The direction of the net force which decides the direction of rotation of disc depends o n
which flux is leading the other . In practice various constructions are used to produce phas e
displacement between the two fluxes .
* 2 * *
2'
o o Coi l
Stationary 1
core
Fig . 5 .1 3
T to • i is of two fo @s diles . These are energized by the rely coils . The
.
In all, the induction relays are widely used for protective relays involving a .c. quantities . With the help of this bridge, number of turns of primary winding can be adjusted . Thus
High, low and ad*ju table speeds are possible in these relays . Various shapes of time agains t the de--S-ire current setting for the relay can be obtained . There are usually seven sections o f
operating qua tffcurves can be obtained . tappings to have the overcurrent range from 50% to 200% in steps of 25% . These values are
percentages of the current rating of the relay . Thus a relay current rating may be 10A i .e. it
5.5*N9tfdirectional Induction Type Overcurrent Rela y can be connected to C .T . with secondary current rating of 10A but with 50% setting the rela y
t/ Thiss r v is also called earth leakage induction type relay . will start operating at 5A. So adjustment of the urrent setting is made by inserting a pin ,
between spring loaded jaw of the ri e socket, at the proper tap value required . When the
' The overcurrent relay operates whe n pin is withdrrawi fa-the purpose of chap;' • ; • • _ ' • ; . • • ice then relay
value . The induction type riondirectional overcurrent relay has a construction simi a r a igher current if C.T. is not o en circuited . So
automatically ac opts • ; • • s . s .
watthour meter, with slight modification . The Fig . 5 .15 shows the constructional details o f regy remin erative or It oc - ; • •. the •rocess of changing t e se ng.
riondirectional induction type over current relay .
To
The secondary winding on the central limb of upper magnet is connected in series wit h
trip circuit ° winding on the lower magnet . This winding is energized by the induction from primary . By
this arrangement of secondary winding, the leakage fluxes of upper and lower magnets ar e
Upper electromagne t sufficiently displaced in space and time to produce a rotational torque on the aluminiu m
°
° disc. The control torque is provided by the spiral spring .
Primary
winding When current exceeds its preset value, disc rotates and moving contacts on spindl e
make connection with trip circuit terminals . Angle through which the disc rotates i s
between 0° to 360° . The travel of the moving contacts can be adjusted by adjusting angle o f
rotation of disc . This gives the relay any desired time setting which is indicated by a pointe r
on a time setting dial . The dial is calibrated from 0 to 1 . This does not give direct operating
time but it gives multiplier which can be used along with the time-plug setting multiplie r
curve to obtain actual operating time of the relay . The time-plug setting multiplier curve i s
Aluminum disc provided by the manufacturer .
Secondar y Disc Movin g 5.5 .1 Time-Current characteristic s
winding - spindle contact
Time required to rotate the disc depends on a torque . The torque varies as current in the
primary circuit . More the torque, lesser is the time required hence relay has inverse tim e
Plu g characteristics . The Fig. 5 .16 (see on next page) shows the time-current characteristics for th e
setting
bridg e
overcurrent relay . Such characteristics are called Inverse Definite Minimum Type (I .D.M.T. )
characteristics . This is because, the characteristics shows inverse relation between time an d
current for small values ofcurrents . . But . as current increases, some definite time is require d
Lower
electromagnè t
P by the relay . So the characteristics becomes straight line for higher values of currents . Such
'I.D.M.T. characteristics can be obtained by saturating the iron in the upper magnet so tha t
there cannot be increase in the flux once current achieves certain high value .
Curren t
o The P.S.M . can be obtained as,
terminal s Fault current in relay coi l
from C . T. Rated secondary C .T. current x Current setting
Fig . 5 .15 Nondirectional induction over current rela y
Fault current in relay coil = Line fault current x C .T. ratio
It consists of two electromagnets . The upper is E shaped while the lower is U shaped .
The aluminium disc is free to rotate between the two magnets . Thpindle of the lisc carries '5 .5 .2 Operation
moving contacts and when the disc rotates the moving contacts come in contact with fixe d The torque is produced due to induction principle, as explained in the section 5 .4.1 . This
contacts which are the termin g s of a trip circuit. torque is opposed by restraining force produced by spiral springs . Under normal conditions
The upper magnet has two windings, primary and secondary . The rimaryis connected the restraining force is more than driving force hence disc remains stationary . Under fault
to the secondary of C . T. on the line to be protected . This winding is tappe at in e r
`tappings are connected to plug setting bridge . conditions when current becomes high, the disc rotates through the preset angle and make s
VTU - Switchgear and Protection 156 Electromagnetic Relays VTU -Switchgear and Protection 157 Electromagnetic Relay s
Fig. 5.17
VTU -Switchgear and Protection 158 Electromagnetic Relay s VTU -Switchgear and Protection 159 Electromagnetic Relay s
from secondary., . of C .T. while in directional ow -r -I . the tor q ue is roduced due to . ,,,-T a V I cos 4) oc power in circuit
- au . s
,interaction of the fluxes •ro 09 ;ii . .. . ii6i7.li*T3*TiTi urren o e e Under normal working conditions, the driving torque acts in the same direction as tha t
two windings, one acts as voltage coil while other as current coil, similar to a wattmeter . The of restraining torque . This moves the moving contacts away from the fixed tripping circui t
upper magnet carries a voltage coil or potential coil which is,energized from P .T . while th e contacts . Thus relay remaii inoperative as long as power flow is in one particular direction .
lower magnet carries a current coil which is energized fromC Tin the line to be protected . But when there is a current reversal and' hence the power reversal then the driving
The construction is shown in the Fig. 5.19. torque acts in opposite direction to the restraining torque in such a manner that the moving
contacts close the tripping circuit contacts . This opens the circiit breaker to isolate the fault y
part .
This relay is used for providing the reverse power protection to synchronous machines .
The relay e single phase or three phase .
Due to this, the correct operation of relay at all the types of faults under all syste m Thus the directional element operates, provided that the current phasor lies within ±90 °
of the maximum torque line . If it is displaced more than 90° then the element will restrain .
condition is ensured . Both operating as well as nonoperating regions are shown in the Fig . 5.22.
So current I leads voltage V by angle 0 . Maximum torque angle : The angle by which the current supplied to the rela y
*>v = Flux produced by voltage V leads the voltage supplied to the relay so as to obtain the maximum torque is calle d
This flux 4)v lags voltage V by an angle 4) . maximum torque angle (M .T.A.) . It is denoted as T in the Fig . 5.22.
= Flux produced by current I From the Fig . 5 .22, we can write,
The flux 4)is in phase with the current I . 4) = 90°- T
.
The phasor diagram is shown in the Fig . 5 .22 . The voltage V is taken as reference Substituting in the torque equation ,
T = KV I sin (0 + 90°-T )
T = KV I cos (0 - T )
I for maximum torque .
This is the torque equation interms of maximum torque angle T . The typical values of the
maximum torque angle are 0°, 30°, 45° etc .
5 . Derive the torque equating for electromagnetic attraction relays when used for,
5.9 Universal Relay Torque Equatio n i) A. C. operatio n
Most of the protection relays consist of some arrangement of electromagnets wit h ii) D . C. operation
armature or induction disc, which carry contacts . The relays also carry the closing o r 6. State the advantages, disadvantages and applications of electromagnetic relay s
opening of contacts control devices like trip coils of circuit breaker . The electromagnets hav e 7. Derive the torque equation for the induction type relay s
current, voltage or both the types of windings . Currents through windings produc e
magnetic fluxes and torque is developed by the interaction between the fluxes of sam e 8 . Describe the operation of following relays with neat sketches ,
windings or between the fluxes of both the windings . In general the torque produced b y i) Shaded pole type induction relay
current winding is proportional to square of the current the torque produced by voltag e ii) Watthour meter type induction rela y
winding is proportional to square of the voltage, and the torque produced by both th e iii) Induction cup type rela y
windings is proportional to product of voltage and the current . Mathematically we ca n 9. Explain with the help of a neat diagram, the construction and working of a nondirectional induction t)p
write, e
overcurrent relay. Draw and explain its time-current characteristics .
Torque produced by current coil, = K I 2 10 . What is I .D .M.T characteristics of a relay ?
K2V2
Torque produced by voltage coil = 11 . Explain the working principle of directional power relay.
Torque produced by both the coils = K 3VI cos (0 - r) 12. What is the procedure of setting I .D.M .T . relay ? What initial data is required ? How
is the directiona l
relay different than simple I .D .M.T relay ?
where K1, K, and K3 = constant 0 = angle between V and I
13 . Explain with the help of neat sketch, the construction and working of directional inductier typ
= maximum torque angl e e
overcurrent relay .
Torque produced by control spring = K 4 14. State the conditions to be satisfied by a directional relay before its operatio n
The control springs are used as restraining element s 15 . Draw the directional characteristics and explain what is maximum torque angl e
If all the elements are present in a relay then total torque produced by all the causes ca n 16 . What . is universal relay torque equation ? What is its use ?
be expressed by a general equation as , 17. An I.D .M.T. ouercurrent relay has a current setting of 150% and has a time multiplier setting of
+ K4 9 .5 .
T = K1I 2 + K7V2 + K 3VI cos (0 The relay is connected in the circuit with the help of C .T. having ratio 500 : 5 A . Calculate the tim e
This equation is called universal relay torque equation the term K4 can be a restraining of operation of the relay if circuit carries a fault current of 6000 A . The relay characteristics are give
n
in the Fig . 5 .24.
torque due to springs or gravity .
By assigning positive and negative signs to certain constants and lets other constants t o
be zero and sometimes by adding similar other terms, the operating characteristics equatio n
of all the types of protective relays can be obtained from universal equation .
For example, for overcurrent relay K 2 = K3 = 0 and the spring torque is negative so w e Tim e
in secs
get,
T = K1I 2 -K4
For the directional relay K 1 = K, = 0 and the spring torque is negative .
So we get,
T = K3 VI cos (0-T) -K4
Review Question s
1 . Explain the operation of basic trip circuit
2. Explain the following schemes used in circuit breakers , P.S .M .
16 6 Electromagnetic Relay s
VTUSwitchgear and . Protection
18. For a particular transmission line, relays are used as shown in the Fig. 5 .25 .
200/1 200/ 1
C.B . C.B . li
Fault 2000 A
Differential Protectio n
I Relay 2 1 [Relay 1
125 % 100 %
Plug setting Plug setting
Fig. 5.25 6 .1 Introductio n
For discrimination, the time grading margin is 0 .5 sec . In the overcurrent relays, a current is sensed but such relays are not very sensitive a s
Determine the time of operation of the two relays assuming that both the relays have characteristic s these relays cannot distinguish between heavy loads and minor fault conditions . In such
as shown in the Fig . 5.24 . The relay 1 has time setting multiplier of 0 .2 . Find the time settin g cases, differential relays can be used.
multiplier of relay 2 . (Ans . : 0.56 sec, 1 .06 sec, 0.3364 )
A differential relay is defined as the rela that operates when the hasor diffe r
19. Write a note on thermal relays. tw o or more similar elect alue.
University Questions Thus a current differential relay operates on the result of comparison between the phas e
1. With a neat sketch explain the working principle of induction disc relay . (Aug.-2002, 10 Marks ) angle and magnitudes of the currents entering and leaving the system to be protected .
Under normal conditions, the two currents Ore equal in phase and magnitude hence relay i s
2. Explain the working principle of an induction disc type relay with a neat sketch . inoperative . But under fault conditions, this condition no longer exists. The relay is
(Feb.-2003, 10 Marks ) connected in such a manner that the difference between current entering and current
3. Explain with the help of neat sketch, the construction and working of directional induction type ove r leaving flows through the operating coil . If this difference current exceeds a preset valu e
current relay . (Aug.-2003, 10 Marks) then the relay operates and opens the circuit breaker .
❑ 0❑ Almost any type of relay when connected in a certain way can be made to operate as a
differential relay .
6.2 Types of Differential Relay s
The various types of differential relays are,
d . Current differential rela y
2.Biased beam relay or percentage differential rela y
3.Voltage b nice differential relay
6.2 .1 Cur t Differential Relay c i \/\C t̀ p 1
(I
st of the differential relays are of current differential type . Consider an over curren t
relay connected in the circuit so as to operate as the current differential relay . This is shown
in the Fig. 6.1 .
Two current transformers are used having same ratio are connected on the either side o f
the section to be protected . The secondaries of current transformers are connected in series ,
so they carry induced currents in the same direction . Let current I is flowing through th e
primary of current transformers towards the external fault . As the current transformers ar e
identical, the secondaries of current transformers will c . âl ts . Due to the
co re ay, no curren wi ow . ug le operating coil for the relay . Hence relay
will remain inoperative . So relay cannot operate if there is an external fault .
(167 )
VTU - Switchgear and Protection 168 Differential Protection VTU - Switchgear and Protection 169 Differential Protectio n
3. Under sever through fault conditions, the current transformers may saturate an d
cause unequal secondary currents . The difference between the currents ma y
approach the pick value to cause the inaccurate operation for the relay .
4. Under heavy current flows, pilot cable capacitances may cause inaccurate operatio n
of the relay .
All these disadvantages are overcome in biased beam relay .
Generato r
C . T. winding C. T.
niuui r
Interna l
fault
-Differentia l
relay
The current flows through the fault from both sides . The two secondary currents Fig . 6.3 Biased beam rela y
through C .T.s are not equal . The current flowing through the relay coil is now I l + I, . This The simple circuit connection of this type of relay is shown in the Fig . 6.4 .
high current causes the relay to operate .
Alternator windin g
It should be noted that the fault current need not always flow to the fault from bot h
C . T. to be protected C . T.
sides . A flow on one side only . or even. some current flowing out of one side while a larg e
current entering the other side can cause' differential relay tooperaté . Thus the amount o f 1
current flowing through a relay coil : depends upon the way the fault is being ,fed . Operatin g
\ coil
This relay suffers from the following disadvantages ,
1. The current transformers are connected through cables called pilot cables . Th e
impedance of such pilot cables generally causes a slight difference between th e
currents at the ends of the section to be protected . A sensitive relay can operate to a 1 1 2-
very small difference in the two currents, though there is no fault existing . , mmtl
2. The relay is likely to operate inaccurately with heavy through current flows . This is I
- R- - - `* Percentage differential relay
because the assumed identical current transformers may not have identica l
secondary currents due to the constructional errors and pilot cable impedances . Restraining coi l
Thus it can be assumed that the current Il2I2l flows through the entire N turns of the
Relay
restraining coil . oo
o
Under normal and through load conditions, the bias force produced due to th e '0000'
restraining coil is greater than the operating force produced by operating coil hence relay i s
inoperative . When internal fault occurs, the operating force becomes more than the bia s
force . Due to this, beam moves and the trip contacts are closed to open then circuit breaker . Fig. 6 .7 Voltage balance differential rela y
The operating characteristics of Under normal conditions, the current at the two ends of the section to be protected i s
this type of relay is shown in th e same . Hence there is no voltage drop across the relay to cause the current to flow .
Fig. 6.5. Under fault conditions, the currents in the two secondaries of current transformers ar e
It can be seen that except at lo w different. This causes a large vo lttiage drop across the relay . Thus the voltage balance of th e
currents, the characteristics is a circuit gets disturbed . Hence large current flows through the relay due to which the rela y
straight line . operates to open the circuit breaker .
Thus the ratio of the differentia l .3 Busbar Protectio n
operating current to the average
restraining current is a fixe d The busbar plays an important role in the supply system . The busbar faults are rare but i f
percentage . Hence the relay name is occurs there can be interruption of supply, considerable damage and loss . Hence busba r
percentage differential relay . protection is must and it must be fast, stable and reliable . The busbar protection needs t o
The relays with constant slop e protect not only the busbar but the apparatus associated with it such as circuit breakers ,
Fig. 6 .5 Operating characteristic s characteristics are called constant isolating switches, instrument transformers etc .
slope percentage differential relays .
6.3 .1 Bus Bar Fault s
Operating In some relays, the slope of the
Relay i characteristic s The various busbar faults can be classified as ,
current characteristics increases as the shor t
circuit current increases . Such 1.Failure of insulation due to material deterioration .
characteristics is shown in th e 2. Failure of circuit breaker .
Fig. 6.6. 3. Earth fault due to failure of support insulator .
Such relays are called increasin g 4. Flashover due to sustained excessive over voltages .
slope percentage differential relays .
5. Errors in the operation and maintenance of switchgear .
The important fact about
increasing slope type relays is tha t 6. Earthquake and mechanical damage .
their cost is more but require les s 7. Accidents due to foreign bodies falling across the busbars .
accuracy in the performance of their 8. Flashover due to heavily polluted insulator .
Short circuit current
All bus bar protection schemes are mostly designed for earth faults . Each conductor i s This is nothing but the differential scheme of the protection of bus bar . The circulating
surrounded by the earthed metal barrier . All the metal frameworks are bonded together an d current principle states that under normal working conditions or external fault conditions ,
. sum of the currents entering the bus equals sum of the currents leaving the bus . Under any
insulated from earth . The switchgear framework is also insulated from lead cable sheaths
abnormal conditions in the protected zone i.e . short circuit or phase to phase faults, th e
The arrangement of frame leakage protection to a single busbar substation with a
current condition gets disturbed and sensing this the relay can be operated .
switchgear unit is shown in the Fig . 6.8 .
The Fig . 6 .9 shows the principle of circulating current protection of bus bar .
--------------------------- -
B C i Bus ba r
sectio n
Switchgea r
frame work
o+
Fram e
leakag e
relay
Incomin g o
transformer ! o
0
-
CT Chec k
relay Fig .
Circulating current protection of bus ba r
6 .9
The linear coupler has a property that it s measuring unit is connected to the secondary of this transformer which measures this dro p
secondary voltage is proportional to the primar y and trips the relay accordingly . Main advantage is that as voltage drop is sensed, saturation
current and the secondary windings of all th e of core of one of the current transformers has no effect on the protection scheme .
linear couplers are connected in series to the
relay . This is shown in the Fig . 6.10 . 6 .7 Difficulties in Bus Bar Protectio n
The sum of the voltage outputs of linea r The various difficulties in the bus bar protection are ,
couplers is equal to the vector sum of the voltage s 1. Current levels for different circuits are , different.
in the circuits connected to the bus bars . Hence 2. Large number of circuits to be protected .
under normal conditions overall voltage in the 3. Saturation of cores of current transformers due to d .c. component in short crrctit
secondary circuit is zero and relay is inoperative . current is possible which produces ratio error .
Under fault conditions, there is resultant voltag e
Fig . 6 .10 4. Due to various bus sections, the scheme becomes complicated .
in the secondary and the relay operates .
5. With large load changes, relay settings need to be changed .
A high impedance relay can differentiate properly the internal and external fault s
Review Question s
compared to normal low impedance relay . Hence in circulating current protection, hig h
impedance relays are used . A high resistance is connected in series with relay operating coi l 1 . What are differential relays ? How they are classified ?
to get high impedance relay . This resistance is called stabilising resistance . 2 . Explain the working of following differential relays ,
i) Current differential rela y
6.6 High Impedance Differential Protection of Bus Bar
ii) Percentage differential relay
Another method to provide differential protection to bus bar is based on sensing a iii) Voltage balance differential rela y
voltage drop across a high impedance, under fault conditions . The scheme is shown in the
3 . Explain the need of bus bar protection and difficulties in'bus bar protection .
Fig . 6.11 .
4 . Explain frame leakage protection of bus bar .
5. Explain current circulating protection of bus bar .
6. Explain high impedance differential protection of bus bar.
University Question s
1. Write a short note on frame leakage protection . (March-2003,5 M xl<s)
2. What are the problems encountered in differential protection of bus bars ? (Aug .-2003,10 Marks )
-CO
Distance Protectio n
For a particular fault position, the ratio V/I i.e. impedance is constant. It changes if the Mathematically x 2 + y2 = 1.2 represents an equation of circle where x and y are vertical and
fault position changes . If fault is nearer to relay, this ratio will be low and as fault positio n horizo co-ordinates while r is the radius . Similarly the equation (1) represents circl e
moves away from the relay the ratio becomes higher and higher . So it can be installed t o re R and X are vertical and horizontal co-ordinates and magnitude of impedance Z is I
operate for the section to be protected and once installed and adjusted for a particula r the radius of the circle . The centre of this circle is at point where R and X axes intersect each
section, it is inoperative beyond that section . other i.e. origin.
The operating characteristics of the relay is shown in the Fig . 7.2. From equation (1) we can write,
tan ) = -
X .L
7`
P \ X (-\v-e-)
'v,`.
✓ * = tan-1 - XR ,A*(s V x. .z*
The numerical values of ratio V and I determine the length of the radius vector Z whil e
the phase angle between V and I determines the exact position of the vector Z .
i
If I is in phase with V then th e
Z vector lies along R-axis . If 1 lags
vector V then X is negative whil e
if 1 leads vector V then X i s
positive .
The operation of the relay is
V independent of phase angle and
hence the operating characteristi c
Fig . 7 .2 Operating characteristic s is a circle with radius equal t o
As the effect of spring is dominating for the lower values of currents, the characteristic s magnitude of Z which i s
predetermined set value .
shows a noticiable bend at lower currents .
But for all practical purposes, the dotted line, which represents a constant value of Z At any value of Mess tha the
radius of the circle the vel a
may be considered as an operating characteristics .
Hence the entire
The impedance Z which is predetermined set value is given by , portion inside the circle is
1 positive torque region i.e.
slope of characteristic s operating region of the rela y
The relay will pickup for any combination of V and I represented by any point above th e while the portion exterior to th e
line in the positive torque region . In other words for any value of Z less than the constan t circle is negative torque regio n
value represented by the line, the relay will operate . i .e . nonoperative region, a s
Fig . 7 .3 Characteristic on R-X diagra m
shown in the Fig . 7 .3 .
By adjustments, the slope of the characteristics can be changed so that the relay wil l
alues of impedance less than any : desired upper limit . If Z f = Impedance between relay and fault poin t
respond to all tl
Z = Set value for impedance = Radius of circl e
7.2 .3 perating Characteristics on R-X Diagra m Then for, Zf < Z . . . relay operates
The operating characteristics of an impedance relay can be more easily represented by a Z f > Z . . . relay is inoperativ e
diagram called R-X diagram . The diagram is shown in a plane having X-axis as R (resistance ) Such a relay is nondirectional and can operate for faults on either side of a point wher e
while the Y-axis as X (reactance) . This plane is called R-X plane . The impedance Z can b e relay is installed.
expressed as,
.,!Z = R+jX
f I Z = ,R2 + X 2
I
Z22=R 2 +X 2
VTU - Switchgear and Protection 180 Distance Protectio n VTU - Switchgear and Protection 181 Distance Protectio n
The relay is connected at point A . The fault occurs at point X . The voltage coil of rela y
receives voltage V F and current coil receives current i F, when fault occurs . The setting of th e
relay is selected such that it protects the transmission line upto point B . Thus for any faul t
between A-B similar to that shown at point X, the impedance under fault condition will b e
less than the predetermined value of impedance Z L and the relay will operate .
Fig . 7 .8
VTU - Switchgear and Protection 184 Distance Protectio n
. It is a four pol e
If the impedance relay used is nondirectional, it can protect the line from faults for al The structure used for the reactance rel . can be of induction cup; type
fault positions within the section AC too . So nondirectional relay provides protection o nl coi The schemati c
structure . It has eratm : coil y.o arizin; coi nd es ramm
either side of the point where relay is located . But if the portion of line AB only is to b e arrangement of coi s or the reactance relay is shown in the Fig . 7 .9 .
protected, then the directional impedance relay can be used . As directional unit permit s The current I flows from pole 1, through iron core stacking to lower pole 3 . The windin g
tripping only in one direction, the section AB will be protected but relay will hot.operate fo r of fluxe s
any fault positions between section AC . on pole 4 is fed from voltage V . The oeratin for ue is produced by interaction
due to the windings carrying current cor s i .e . interaction of fluxes • • . • s • • '
7
Whether the relay is directional or nondirectional, if its setting is such that fo and 3 . While the restra a . . • •- develope d ue to interaction of fluxes dice to the poles
impedance less than Z L defined upto point B, the relay should operate then for any faul r ratin tor . ue . . square o the current I while
t 1,3 d4 . cethe
positions to the right of point B like point Y the relay will not operate . ro or ona l t The desired maximu m
the aming torqu
The characteristics of the directional distance scheme discussed above can be shown o n torque ang e is obtained wit t e e p of RC circuit, shown in the Fig . 7.9 .
1 R-X diagram . It is shown in the Fig . 7 .8 (See Fig . on previous page)
. The various sections o f
the line are represented by straight lines on the R-X diagram . 7 .3 .2 Torque Equatio n
The driving torque is proportional to the square of the current while the restrainin g
For fault at X, Zf < ZL hence point X is in the operating region and relay will trip
. So for torque is proportional to the product of V and I .
any fault position along line AB, relay will trip as the entire section AB is in the protecte d
zone . For fault at Y, it can be seen that the impedance Zf > ZL hence point lies outside th Hence the net torque neglecting the effect of spring is given by ,
e
circle hence in the negative torque region and relay remains inoperative . T = Kl 12 -K2 VIcos (0-r)
7.3 R ctance Rela y At the balance point net torque is zero ,
0 ='K l 12 - K2 V I cos (0 -t)
In this relay the operatin tor ue is obtained hile th• estraining torq e du e Ki 12 = K2 V I cos (0 - i)
to current-voltages irectional rela he overcurrent element develops e posi ' e torqu e
and directional unit produces negative torque . Ki = K2 cos (e-ti )
I
Thus the reactance rela is an overcurrent relay with the directional restraint . Ki = K2 Z cos (0 - i )
The directional element is so designed that the maximum torque ang e i s Adding capacitor, the torque angle is adjusted as 90° ,
7 Ki = K2 Zcos(e-90°)
.3 .1 Construction
Ki = K2 Zsin e
K
Zsine = i
2
Consider an impedance triangle shown in the Fig . 7.10.
Z sin 0 = X = reactanc e
Z cos 0 = R = resistance
X= K, constant
K2
Thus the relay operates on the reactanc e
only . The constant X means a straight lin e
parallel to X-axis on R-X diagram . For the
operation of the relay, the reactance seen b y
the relay should 'be smaller than th e
reactance for which the relay is designed .
Fig . 7 .10
Fig . 7 .9 Schematic arrangement of reactance relay
187 Distance Protectio n
VTU - Switchgear and Protection 186 Distance Protection VTU -Switchgear and Protection
7 .3 .3 Operating Characteristic s
The operating characteristics of such relay is a straight line parallel to the x-axis i .e R-axi s
on R-X diagram . All the impedance vectors have their tips lying on the straight lin e
representing constant reactance . The resistance component of the impedance has no effec t
on the operation of the relay . It responds only to the reactance component of the impedance .
The characteristics is shown in the Fig. 7.11 .
2
K1
+ve torqu e zsinO = X = -
region K2
+R
-X
Kl cos (0 -T) = K, V The angle r can be adjusted to be 45°, 60°, 75° and so on . This angle is maximum torqu e
I angle . The setting of 45°is used for high voltage (33 or 11 kV) distribution lines, the setting o f
Z =
K21
K
cos (0-r)
60° is used for 66 or 132 kV lines while the setting of 75° is used for 275 and 400 kV lines .
On a R-X diagram show a line having an impedance of 3 + j 4 On the same diagra m
Ex . 7 .1 :
show the operating characteristics of,
This is the equation of a circle having diameter K 1 /K2 passing through origin . And thi s
constant K1/K2 is the ohmic setting of this relay . 1. Impedance rela y
2. Reactance relay
7 .4 .3 Operating Characteristic s
3. Mho rela y
As seen from the torque equation, the characteristics of this relay is a circle passin g Assume that these relays are adjusted to just operate for a zero impedance shor t
1 through origin with diameter as K 1 /K 2.
circuit at the end of the line section .
L et K = ZR = ohmic setting of relay = diameter If an arcing short circuit fault having an arc impedance of 1 + j0 E2 occurs any-
z1 where on the line, find for each type of distance relay, the maximum portion of th e
The circle is shown in the Fig . 7.13. line that can be protected .
Sol .. : The line OA is the impedance vector with impedance 3 + j 4 S2
OB= 3
BA=4 .
The circle with 0 as a centre and OA as radius represents the characteristics of a n
impedance relay.
The line parallel to the resistance axis at a distance of 4, passing through point A ,
corresponding to reactance o&tfie impedance given, represents the characteristics of a
reactance relay .
Draw the circle with OA as the diameter, passing through 0 and A represent s
characteristics of mho relay .
The characteristics are shown in the Fig . 7.14 . (See on next page )
The impedance of arcing fault is 1 + j 0, is represented by OD .
The line parallel to the OA is drawn from point D, cutting the mho circle at point F an d
cutting the impedance circle at pont E .
Draw line FN parallel to R-axis to cut OA at N and draw EM parallel to R-axis to cut O A
at M .
Then the ratio ON/OA represents the line protected by mho relay .
ON x 100 = % of line protected by mho rela y
OA
= 4 x10 0
5
Fig . 7 .13 Operating characteristics of mho relay
= 80%
The relay operates when the impedance seen by the relay falls within this circle . While the ratio OM/OA represents the line protected by impedance relay .
Consider two lines AB and AC with mho relay located at the point A . The relay will operat e OM x
for the faults occurring in the section AB only and not for the faults occurring in the sectio n 100 = % of line protected by impedance rela y
AC . This shows that this relay is inherently directional without any additional directiona OA
l
unit required . = 4 .25 x10 0
5
= 85 %
VTU - Switchgear and Protection 1 90 Distance Protection BTU - Switchgear and Protection 191 Distance Protectio n
Characteristics o f
mho relay
-R +R
The Fig . 7 .17 shows the schematic arrangement of distance time impedance relay .
I Kl
To trip circuit
z < IK?
VK i Fixed contacts
`o
So for impedance value less than JK 2 /K1 , the relay operates. Moving contact s
TI
The constants K1 and K2 are dependent on the ampere turns of the two electromagne t Fro m V
P.T.
By providing tappings on the coils, Kl and K2 can be changed and hence any preset value f c
To
the impedance can be adjusted as per the requirement .
1 Characteristics : The Fig . 7.16 shows the characteristics of the definite distant
type impedance relay . The Y-axis represents time for operation while the X-ax
Spiral spring couplin g
represents distance which is measured interms of impedance between fault positio: Voltage restrainin g
and the point where relay is installed . magnet and armature
Tim e I to
From o
C .T.
t
-- Induction typ e
over current rela y
Inductio n
disc
B S
Distance
P
Fig . 7 .16 Characteristics of definite distance impedance rela y
For the entire length AB of the line, the time of operation remains constant, irrespecti v Fig . 7 .17 Distance time impedance rela y
of distance . But if fault occurs in the section of line which is not protected, the operating tini " It consists of an induction type over current relay unit which is _a current driven element .
becomes suddenly infinite as shown in the Fig . 7.45 . Towards end of the protected zone, th i The spindle which is carrying the disc of the element is connected to â second spindle wit h
curve rises gradually . the help of spiral spring coupling . This second spindle carries moving contacts which i s
Its advantages are, nothing but a bridging piece which can bridge the trip contacts when relay operates . The trip
1. Superior to the time graded over current rela y contacts are normally open and spindle is held in this position by an armature held agains t
2. Number of feeders in series which can be protected is unlimited as the relay time i the pole face of an electromagnet . This electromagnet is energized by the voltage of th e
constant . circuit to be protected .
The one limitation of these relays is the absencé of back up protection . Operation : Under normal conditions, the force exerted by voltage restrainin g
magnet is more than that produced by an overcurrent induction element . Thus the trip
7 .5.2 Distance Time Impedance Rela y contacts remain open and the relay is inoperative .
This relay adjusts automatically, its time or operation corresponding to the distance â When :the fault occurs, the induction disc starts rotating . The speed of the disc is
the fault from the relay . proportional to the operating current, neglecting the spring effect . Hence the time which th e
Operating time cc Z cc distance disc requires to turn through the given angle varies inversely with current . As the dis c
rotates, spiral spring is wound . this exerts a force on armature so as to pull it away from th e
voltage restrained magnet . The disc continues to rotate till the tension of the spring i s
VTU - Switchgear and Protection 194 Distance Protectio n
VTU - Switchgear and Protection 195 Distance Protectio n
sufficient to overcome the restraining force produced by voltage restraining magnet on th e
armature . Immediately the moving contacts bridge the fixed contacts of tripping circuit . Review Question s
This open the circuit breaker to isolate the faulty section . 1 . Explain fully how an impedance relay is used for distance protection obtain its operating characteristic . Dra w
The angle through which the disc must rotate to close the trip contacts depends on th e its operating characteristics on R-X diagram .
pull required by armature which is restrained by voltage restraining magnet . This pull i s 2 . State the disadvantages of basic impedance rela y
thus proportional to the voltage of system . Greater this pull, greater will be travel of the disc . . 3 . Explain the operation of directional impedance relay . Draw its characteristics on R-X diagram . How thes e
So travel for the disc is proportional to the voltage V . But the time which disc takes to rotate characteristics can be modified, similar to that of mho relay ?
through certain required angle varies inversely with current (1/I) . Thus effectively , ,
4 . Draw and explain the full scheme of protecting a transmission line using an impedance rela y
I or Z or distanc e
Time of operation of relay or 5 . Explain the construction, working, torque equation and characteristics offollowing distance relays
1 i) Reactance relay
In actual practice the pull on armature is proportional to the V2 while the torque on dis c ii) Mho relay
is proportional to the 12 . Hence the time distance characteristics of this relay is nonlinear in .
6 . Explain the construction and working of,
nature, as shown in the Fig. 7.18 . The exact curve is shown dotted while the assumed line i s
shown thick . The minimum operating time for the relay is generally 0 .2 seconds . i) Definite distance type impedance relay
ii) Distance time impedance relay
7. State the advantages and applications of distance relays
8 . A line section has an impedance of 2 .8 + j 5 Sd. Show this on R-X diagram, as impedance vector . If f the relay i s
adjusted to operate for a zero impedance short circuit .at the end of the line section, show on the same R- X
diagram the characteristics of,
1. Impedance rela y
2. Reactance relay
3. Mho rela y
Assume that centre of mho relay characteristics lies on an impedance .vector . If the arching fault occurs wit h
an impedance of 1 .5 + j 0 (2 anywhere along the line, find for each type of distance relay the maximum portio n
of the line that can be protected . (Ans . : 82%, 100% and 85% )
University Question s
1. Write a short note on operating principle of distance relay . (Aug .-2002, 5 Marks )
Fig . 7 .18 Time-distance characteristics of distance time impedance rela y 2. What is a distance relay ? Explain the different types with relevant diagrams . (Feb .2003, 10 Marks )
7.5 .3 Applications and Advantages of Distance Relay s 3. Explain fully how an impedance relay is used for distance protection . Obtain it's operating characteristic .
The various advantages of the distance relays are . Draw its operating characteristics on R-X diagram . (Aug .-2003, 10 Marks )
The unbalanced loading on the generator is responsible to produce the negativ e rated load causes tremendous heating which is dominant incase of cylindrical rotor o f
sequence currents . These currents produce a rotating magnetic field which rotates i n truboalternators .
opposite direction to that of rotor magnetic field . Due to this field, there is induced e .m.f. in
the rotor winding . This causes overheating of the rotor . The reasons for the unbalanced load conditions are ,
1. Occurrence of unsymmetrical faults near the generating station .
Rotor earth fault protection and rotor temperature indicators are the essential and ar e 2. The failure of circuit breaker near the generating station in clearing all the thre e
provided to large rating generators .
phases.
8 .2.3 Abnormal Running Condition s Negative sequence protection is important to prevent dangerous situations due t o
negative sequence currents which are because of unbalanced load conditions .
In practice there are number of situations in which generator is subjected to som e
abnormal running conditions . The protection must be provided against the abnorma l 8.2 .3 .4 Overvoltag e
conditions . These abnormal conditions include , The overvoltages are basically due to the overspeeding of generators . Another reaso n
1. Overloadin g for the overvoltages is the faulty operation of voltage regulators . Not only the interna l
overvoltages are dangerous but atmospheric surge voltages can also reach to the generators .
2. Overspeeding ' Such atmospheric surge voltages are generated by direct lighting strokes to the aerial lines o f
3. Unbalanced loading high voltage system . Inductively and capacitively, these surges can get transferred to th e
4. Overvoltag e generator . To protect the generators from surge voltages, the surge arresters and surg e
5. Failure of prime mover capacitors are often used .
At the time of restriking across .the contacts of circuit , breakers, the transient ove r
6. Loss of excitation (Field failure )
voltages get generated . Such surges are called switching surges and can be limited by th e
7. Cooling system failur e uses of modern circuit breakers . R-C surge suppressors also help in reducing switchin g
8 .2.3 .1 Overloadin g surges . Another situation, when the transient overvoltages are generated, is when the arc s
are grounded . During arcing grounds, the transient voltages having amplitudes five time s
Due to the continuous overloading, the overheating of the stator results . This may more than the normal line to neutral peak amplitude are generated . Such transient voltages
increase the winding temperature . If this temperature rise exceeds certain th e
are dangerous and can be reduced by using resistance earthing .
insulation of the winding may get damaged . The degree of overloading decides the effect s
and temperature rise . The overcurrent protection is generally set to very high value henc e 8.2.3 .5 Failure of Prime Move r
continuous overloads of less value than the setting cannot be sensed by overcurren t The failure of prime mover results in motoring operation of synchronous generator . The
protection. generator draws active power from the network and continues to run at synchronous spee d
8 .2.3.2 Overspeedin g as a synchronous motor . This may lead to dangerous mechanical conditions if allowed t o
persist for more than twenty seconds . The serious overheating of the steam turbine blade s
In case of hydraulic generators a sudden loss of load results in overspeeding of th e
generator . This is because the water flow to the turbine cannot be stopped or reduce may result . To prevent this the reverse power protection achieved by directional powe r
d relays is used.
instantly . Generally a turbogovernor is provided to prevent the ovespèéd`ing
. But if there is
any fault in the turbine governor then the dangerous overspeeding may take place . Hence it 8 .2.3 .6 Loss of Excitatio n
is necessary to supervise the working of turbine governor and-Lake some correctiv e The loss of excitation orreduced excitation is possible due to the field failure i .e. opening
measures if there is some fault in the governor . of field winding or due to short circuit in field or due to some fault in exciter system .
8.2 .3 .3 Unbalanced Loadin g Such loss of excitation results in loss of synchronism within a second and this causes th e
The unbalanced loading of the generator results in the circulation of negative sequence increase in speed of the generator : Since power input to the machine remains same, th e
currents . These currents produce the rotating `magnetic field : This ' rotating magnetic field generator starts working as an induction generator, drawing the reactive power from th e
rotates at the synchronous speed with respect to rotor . The direction of rotation of this bus . The machine starts drawing an exciting current from the system, which is equal to th e
magnetic field is opposite to that of rotor . Hence effectivélythe relative speed between th e full load rated value . This leads to the overheating of the stator winding and the rotor bod y
two is double the synchronous speed . due to induced currents . The loss of excitation may also lead to the pole slipping conditio n
which results in the voltage reduction for the output above half the rated load .
Thus the e .m.f . gets induced, having double the normal frequency, the rotor winding .
The circulating currents due to the induced .e.m.f. are responsible toinoverheat the roto r Loss of excitation should not persist for long and corrective measures like disconnectio n
winding as well as rotor stampings . Continuous unbalanced load more than 10% of the of alternator should be taken immediately . For this a tripping scheme can be used which ca n
trip the generator circuit breaker immediately when there is a field failure .
VTUSwitchgear and Protection 200 Generator Protectio n
Generator Protectio n 201
VTU -Switchgear and Protection
8 .2 .3 .7 Cooling System Failur e 1 i, . Even some +
currents are t and i, . So the current flowing through the relay will be
i
i
The failure of cooling system also causes severe overheating to rise the temperatur e current flowing out of one side while a large current entering the other side will cause th e
above safe limit. This may lead to insulation failure, causing some other faults to occur .
. The differential current . Such a current is responsible to operate the relay
thermocouples or resistance thermometers are used in large machines to sense th
e Thus the relay current is proportional to the phasor difference between the current s
temperature
. The corrective measures are taken whenever the temperature exceeds th e entering and leaving the protected circuit and if the differential current exceeds the picku p
limit.
value, the relay operates .
Apart from the above dominant abnormal conditions, some conditions may exist whic This basic differential scheme has following disadvantages :
are rare in practice . Such conditions are, wrong synchronization, local overheating, leakagh .
e 1. This circuit operates inaccurately with heavy external faults
in hydrogen circuit, moisture in the generator winding, oxygen in pure water circuit , f
vibrations, bearing currents, excessive bearing temperature etc . 2. The C .T.s may saturate and cause unequal secondary currents and the difference oy
secondary currents may approach the pickup value to operate the rela
8 .3 Basic Differential Protection Scheme unnecessarily .
for Generator s These disadvantages are overcome in the percentage differential relay .
A basic differential protection scheme used for the generators is shown in the Fig . 8.1
. It Protection Scheme for Generator s
is known that the differential relay operates when the phasor difference of two or mor
e 8 .4 Basic Percentage Differential
similar electrical quantities exceeds a predetermined value .
This protection scheme is also called biased differential protection scheme . The Fig . 8 .3
Generato r shows the connections of the percentage differential relay, in such a protection scheme .
C . T. winding
IV;
C . T.
I,ilui l
1 A
!} r
Externa l
fault
i
Differential rela y
Fig . 8 . 1
Suppose the current I flows through the primary of C .T.s to the external fault
C .T .s have same ratio, then no current will flow through . If the tw o
the relay and it remain
inoperative . s
But now if an internal fault occurs at point X as shown in the Fig . 8 Fig . 8 .3 Percentage differential protection schem e
through the fault from both the sides . The primary currents are .2,, the,current flow s
Il and 12 while the secondary The fault occurs at point X and the primary currents in the circuit are Il and 12 . The C .T .
The current flowing through the operating coil of the relay is
secondary currents are 1 and 2 :
i i
12 +
.
1 This i s
i t - i 2 . While the current flowing through the restraining coil of the relay is 2
because the operating coil is connected to the midpoint of the restraining coil .
flows through
2 and
i1 i2
Thus if the number of turns of the restraining coil is N then
11 N + 1 ' N
This is a s
flows through remaining . The total ampere turns are - i.e. N (11 +12
2 2 2 2
X1 1 +1 2 *
good as the flow of current through the entire restraining coil .
2 i
Generator Protectio n
20 3
VTU -Switchgear and Protection VTU -Switchgear and Protection
202 Generator Protectio n
Star connecte d C .T.
The operating characteristics of such a biased differential relay is shown in the Fig . 8 .4. alternator stato r - neutral
windin g earthing
The characteristics shows that except at low currents, ratio of differential operating curren t C . T.
Alternator
to average restraining current is a fixed percentage . Hence the relay is called the percentag e neutral
differential relay . earthin g
II
r
Fig . 8 .5 Merz-Price protection for star connected alternato
f
The differential relay gives protection against short circuit fault in the stator winding o
d
.s are connected in star and are provided on both, the outgoing side an
a generator . The C .T . The restraining coils are energized from th e
Fig . 8 . 4
machine winding connEctions to earth side . The operating coils ar e
This basic percentage differential protection scheme forms the basis of the practicall y secondary connection of C .T .s in each phase, through pilot wires
. neutral earthing connection .
very commonly used percentage differentiah protection scheme for alternator stato r energized by the tappings from restraining coils and the C .T
windings . This popular scheme is known as Biased differential protection or Merz-Pric s
e The similar arrangement is used for the delta connected alternator stator winding, a
protection .
shown in the Fig . 8.6 .
Let us discuss the details of Merz-Price protection scheme for the three phase alternato r Delta connected alternato r neutral
stator windings . stator winding earthin g
C . T. R
8 .5 Merz-Price Protection of Alternator Stator Winding s 11,111,1
This is most commonly used protection scheme for the alternator stator windings . The
scheme is also called biased differential protection and percentage differential protection .
In this method, the currents at the two ends of the protected section are sensed usin g
current transformers . The wires connecting relay coils to the current transforme
r
secondaries are called pilot wires . B
I11$11,1
Under normal conditions, when there is no fault in the windings, the currents in the pilo t
wires fed from C .T . secondaries are equal . The differential current i t i2 through the
operating coils of the relay is zero . Hence the relay is inoperative and system is said to b e Pilot wir e ---------------- -
balanced .
When fault occurs inside the protected section of the stator windings, the differentia l 0 .c . etô Q .C . O .C .
current it - i2 flows through the operating coils of the relay . Due to this current, the rela
y WW I
operates . This trips the generator circuit breaker to isolate the faulty section
. The field is als o O .C .-► Operating coil
R .C .
disconnected and is discharged through a suitable impedance . R .C . -► Restraining coil 0001100 0
C .B . - - Circuit breaker RR .C
C. /ooa ooo,
The Fig . 8 .5 shows a schematic arrangement of Merz-Price protection scheme for a sta R .C .
r
connected alternator . Percentag e
differential rela y
r
Fig . 8 .6 Merz-Price protection for delta connected alternato
VTU -Switchgear and Protection 205 Generator Protectio n
204 Generator Protectio n VTU -Switchgear and Protection
d
The C .T .s on the delta connected machine winding side are connected in delta while th e windings get partly protected against earth faults . The percentage of winding protecte
C .T .s at outgoing ends are connected in star . The restraining coils are placed in each phase depends on the value of earthing resistance and the relay setting .
,
energized by the secondary connections of C .T .s while the operating coils are energize d In this scheme, the value of earth resistance, relay setting, current rating of eart h
from the restraining coil tappings and the C .T . neutral earthing. e
resistance must be carefully selected . The earth faults are rare near the neutral point as th r
. But when earth fault occurs nea
If there is a fault due to a short circuit in the protected zone of the windings, it produces a voltage of neutral point with respect to earth is very less
difference between the currents in the primary windings of C .T .s on both sides of th e the neutral point then the insufficient voltage across the fault drives very low fault curren t
generator winding of the same phase . This results in a difference between the secondar y . Thus 15 to
than the pick up current of relay coil . Hence the relay coil remains inoperative d
currents of the two current transformers . Thus, under fault conditions, a differential curren t 20% winding from the neutral side remains unprotected in this scheme . Hence it is calle
.
flows through the operating coils which is responsible to trip the relay and open the circui t restricted earth fault protection . It is usual practice to protect 85% of the winding
breaker . The differential relay operation depends on the relation between the current in th e
The restricted earth fault protection scheme is shown in the Fig . 8 .7 .
operating coil and that in the restraining coil .
stato r
In addition to the tripping of circuit breaker, the percentage differential relay trip a han d
reset multicontact auxiliary relay . This auxiliary relay simultaneously initiates the followin g C . T.
$,11111 1 V
operations,
Neutra l
1. Tripping of the main circuit breaker of generato r
point I.1
2. Tripping of the field circuit breake r b
arm 11111111
3. Tripping of the neutral circuit breaker if it is presen t V i If
4. Shut down of the prime mover Earth faul t
5. Turn on of CO, gas if provided for safety of generator under faulty conditions . Operating coi l
6. Operation of alarm and /or annunciator to indicate the occurrence of the fault and th e '0000000) '
operation of the relay the field must be opened immediately otherwise it start s 00000010 '
feeding the fault .
00000010
When differential relaying is used for the protection, C .T .s at both the ends of generator o
must be of -equal ratio and equal accuracy otherwise if the error-is-excessive, -wron g Earthing
operation of the relay may result . The causes of unequal currents on both•the .sides of C .T.s resistance
Is Restricted earth fault relay
without any fault are ratio errors, unequal lengths of the leads, unequa l. secondary burdens
etc.
Fig . 8.7 Restricted earth fault protectio n
This scheme provides very fast protection to the stator winding against phase to phas e
faults and phase to ground faults . If the neutral is not grounded or grounded throug h Consider that earth fault occurs on phase B due to breakdown of its insulation to earth ,
o
resistance then additional sensitive earth fault relay should be provided . as shown in the Fig. 8.7 . The fault current If will flow through the core, frame of machine t S
. secondary current I
earth and complete the path through the earthing resistance . The C .T
The advantages of this scheme are ,
flows through the operating coil and the restricted earth fault relay coil of the differential
1. Very high speed operation with operating time of about 15 msec . e
2. It allows low fault setting which ensures maximum protection of machine windings . protection . The setting of restricted earth fault relay and setting of overcurrent relay ar e
5 , the relay operates to trip th
independent of each other . Under this secondary current I
3. It ensures complete stability under the most severe through and external faults . f when the
circuit breaker . The voltage V bX is sufficient to drive the enough fault current I
4. It does not require current transformers with air gaps or special balancing features . fault point x is away from the neutra l point .
, If the fault point x is nearer to the neutral point then the voltage V bX is small and no t
8.6 Restricted Earth Fault Protection of Generator . Thus part o f
sufficient to drive enough fault current I f . And for this If, relay cannot operate
s
Generally Merz-Price protection based on circulating current principle provides th e the winding from the neutral point remains unprotected . To overcome this, if relay setting i
protection against internal earth faults . Butfôr large generators, asthese are costly, a n chosen very low to make it sensitive to low fault currents, then wrong operation of relay ma y
.T .s,
additional protection scheme called restricted earth fault . protection is provided . result . The relay can operate under the conditions of heavy through faults, inaccurate C t
When the neutral is solidly grounded then the generator gets completely protecte d saturation of C .T .s etc . Hence practically 15% of winding from the neutral point is kep
unprotected, protecting the remaining 85% of the winding against phase to earth faults .
against earth faults . But when neutral is grounded through earth resistance, then the stator
VTU - Switchgear and Protection 20 7 Generator Protectio n
206 Generator Protection VTU - Switchgear and Protection
. The generator ratings ar e
8.6 .1 Effect of Earth Resistance on % of Winding Unprotecte d Ex . 8.1 : A generator is protected by restricted earth fault protection
to ground fault i s
Let us see the effect of earth resistance on the % of the winding which remain 13 .2 kV, 10 MVA . The percentage of winding protected against. phaseCalculate the resistanc e
s 85% . The relay setting is such that it trips for 20% out of balance
unprotected .
to be added in the neutral to ground connection .
Consider the earth Sol. : The given values ,
resistance R used to limit VL = 13.2 kV Rating = 10 MV A
earth fault current as shown
V b
in the Fig. 8 .8. From rating, calculate the full load current ,
------------- - I _ Rating in VA 10x10 6
% of winding The value of the
x13 .2x10 3
N J which is unprotected resistance R limits the earth VL
fault current . = 437 .386 A
.
Alternato r If the resistance R is ver y Relay setting is 20% out of balance i .e . 20% of the rated current activates the realy
small i.e. the neutral i s 20
almost solidly grounded, I ° = 4387 .386x 100 87 .477 A
B then the fault current is very = Minimum operating curren t
high . But high fault current s
are not desirable hence V = Line to neutral voltage =
small R is not preferred fo r
Fig. 8.8 the large machines . 13,2x103 =7621 .02 V
For low resistance R, the value of R is selected such that full load current passes throug h
the neutral, for a full line to neutral voltage V .
of winding unprotected =15% as 85% is protecte d
In medium resistance R, the earth fault current is limited to about 200A for "full line t o
neutral voltage V, for a 60 MW machine . 15 = .R2 x10 0
V
In high resistance R, the earth fault current is limited to about 10 A . This is used for Rx 87 .477
distribution transformers and generator-transformer units . 15 = x10 0
7621 .02
Now higher the value of earth resistance R, less is the earth fault current and les s
percentage of winding gets protected . Large percentage of winding remains unprotected . R = 13 .068 S 2
kV alternator has a phase reactance of 10% . It is
Let V = Full line to neutral voltage Ex. 8.2 : A star connected 3 phase, 12 MVA, 11 t
protected by Merz-Price circulating current scheme which is set to operate for faul
I = Full load current of largest capacity generato Calculate the value of earthing resistance to be provided i n
r current not less than 200 A .
R = Earth resistanc e order to ensure that only 15% of the alternator winding remains unprotected .
Then the value of the resistance R is , The given values are,
Sol. :
V V L = 11 kV Rating =12 MVA
R=
I Rating = - VL I L
And the percentage of winding unprotected is given by,
12x10 6 = ,x11x10 3 xI L
% of winding unprotected = R V x 100
IL
12x10 6
where I° = Minimum operating current in the primary of C .T. ,f§xl1x10 3
If relay setting used is 15 %, then l o is 15% of the full load current of the largest machin e = 629 .8366 A = I = rated curren t
and so on.
Greater percentage of windings of small capacity machines running parallel ge t
v VL 11 x 103
= 6350 .8529 V
protected .
VTU -Switchgear and Protection 208 Generator Protectio n VTU -Switchgear and Protection 209 Generator Protectio n
Earthin g 00000000L -
resistance
F2
LT - 1
o
g i Relay
The scheme uses cross differential principle . Each phase of the generator is doubl y
8 .10 Stator Protection Against Interturn Fault s wound and split into two parts S 1 and S2 as shown in the Fig . 8.12 . The current transformer s
The Merz-Price protection system gives protection against phase to phase faults an d are connected in the two parallel paths of the each phase winding . The secondaries of th e
earth faults . It does not give protection against interturn faults . The interturn fault is a shor t current transformers are cross connected . The current transformers work on circulatin g
circuit between the turns of the same phase winding . Thus the current produced due to suc h current principle . The relay is connected across the cross connected secondaries of th e
fault is a local circuit current and it does not affect the currents entering and leaving th e current transformers .
winding at the two ends, where C .T .s are located . Hence Merz-Price protection cannot giv e Under normal operating conditions, when the two paths are sound then currents in th e
protection against interturn faults . two parallel paths S 1 and S2 are equal . Hence currents in the secondaries of the curren t
In single turn generator, there is no question of interturn faults but in multitur n transformers are also equal . The secondary current flows round the loop and is same at al l
generators, the interturn fault protection is necessary . So such interturn protection i s the points . Hence no current flows through the relay and the relay is inoperative .
provided for multiturn generators such as hydroelectric generators . These generators hav e If the short circuit is developed between the adjacent turns of the part S I of the windin g
double winding armatures . This means, each phase winding is divided into two halves, du e say then currents through S 1 and S 2 no longer remain same . Thus unequal currents will b e
to the very heavy currents which they have to carry . This splitting of single phase windin g induced in the secondaries of the current transformers . The difference of these current s
into two is advantageous in providing interturn fault protection to such hydroelectri c flows through the relay R . Relay then closes its contacts to trip the circuit breaker whic h
generators . isolates the generator from the system .
The Fig . 8 .12 shows the interturn fault protection scheme used for the generator wit h Such an interturn fault protection system is extremely sensitive but it can be applied t o
double winding armatures . the generators having doubly wound armatures .
1111111 1 Method 1 : In this method a high resistance is connected across the rotor circuit . It is
S 2 provided with centre tap and the centre tap point is connected to the ground throug h
C .T. a sensitive earth fault relay as shown in the Fig . 8.13 .
C .T.
o tllh 1111111 1
. Phase B
1111111 1
111■1
■
C .T.
Fig . 8 .12 Interturn fault protection Fig . 8 .13 Rotor earth fault protectio n
VTU -Switchgear and Protection 214 Generator Protection VTU -Switchgear and Protection 215 Generator Protectio n
Except the centre point, the earth fault relay detects the earth faults for most of the roto r 8 .12 Protection Against Loss of Excitatio n
circuit . Thus most of the rotor winding part is protected against the earth faults .
The loss of excitation of the generator may result in the loss of synchronism and slightl y
Method 2 : The modern method of providing earth fault protection includes d .c. increase in the generator speed . The machine starts behaving as an induction generator . It
injection or a .c. injection . The scheme is shown in the Fig . 8 .14. drawn reactive power from the system which is undesirable . The loss of excitation may lea d
to the pole slipping condition . Hence protection against loss of excitation must be provided .
The protection is provided using directional distance type relay with the generato r
terminals .
When there is loss of excitation, the equivalent generator impedance varies and traces a
curve as shown in the Fig . 8 .15. This Fig . 8 .15 shows the loss of excitation characteristic s
alongwith the relay operating characteristics, on R-X diagram .
+X
Normal operating point
+R
Auxiliary
supply
Relay
Locus of equivalent
characteristics
generator impedance
during loss of excitation
+v e
-ve torque torque
C .T. OB= R
2
Now in triangle OAB,
OB
cos 30 =
C .T. OA
/ IR
IY 13- 2 )
2 I
I= =I 1 =I2 (1 )
13-
Now I1 leads IR by 30° while I2 lags IR by 30° .
Similarly the current I B gets divided into two equal parts 13 and 14. The current 13 lags 14
by 60° . From equation (1) we can write,
IB
r = I3 = I4 . . . (2 )
NJ
Fig„8 .1 8
It can be seen from the Fig . 8 .18 that,
3 = -Ty
I1 +1-
.. I l +1 3 +Iy = 0
Fig . 8 .20 Zero sequence currents
Thus the current entering the relay at point B is zero . Similarly the resultant current at
I R = I 1 +I 2
junction D is also zero . Thus the relay is inoperative for a balanced system .
Ig I 3 +I 4
Now consider that there is unbalanced load on generator or motor due to whic h
negative sequence currents exist . The phase sequence of C .T. secondary currents is as show n These sums are shown in the Fig . 8 .20 (b) and (c) . It can be seen from the Fig . 8.20 (d) that,
in the Fig. 8.19 (a) . The vector diagram of I1, 13 and Iy is shown in the Fig . 8.19 (b) under this I 1 +I 3 = I Y in phase with I y
condition . _The total current through relay is I 1 +I 3
+I . . Thus under zero sequence currents th e
total current of twice the zero sequence
current flows through the relay . Hence th e
relay operates to open the circuit breaker .
To make the relay sensitive to only
negative sequence currents by making it
inoperative under the influence of zer o
sequence currents is possible by connectin g
the current transformers in delta as shown in
the Fig . 8.21 . Under delta connection o f
current transformers, no zero sequenc e
current can flow in the network .
Fig . 8 .21 Delta connection of C .T. s
VTU - Switchgear and Protection 22 0 Generator Protection VTU -Switchgear and Protection 221 Generator Protectio n
Auxiliary
transformer
Upper magnet
(Primary ) 30°
r1 120 °
IY IR
(a) C.T. secondary current s (b) Current I RI
-(Y
Ds-itTo-Dis
trip circuit
■ c
Lower magnet
(secondary)
I R1
Induction type negative sequence rela y
Fig . 8 .22 (c) Relay current
The central limb of upper magnet carries the primary which has a centre tap . Due to this,
the primary winding has three terminal 1, 2, and 3 . The section 1-2 is energized from the Positive sequence current s
Fig . 8 .23
secondary of an auxiliary transformer to R-phase . The section 2-3 is directly energized from
the Y-phase current . Negative sequence currents : The C .T . secondary currents are shown in the
Fig. 8.24 (a) . The Fig . 8 .24 (b) shows the position of IRI lagging IR by 120°. The
The auxiliary transformer is a special device having an air gap in its magnetic circuit. Fig. 8 .24 (c) shows the vector difference of I RI and IY which is the relay current .
With the help of this, the phase angle between its primary and secondary can be easil y
Under negative sequence currents, the vector difference of I RI and I y results into a
adjusted . In practice it is adjusted such that output current lags by 120°rather than usual 180 °
from the input . current I as shown in the Fig . 8 .24 (c) . This current I flows through the primary coil of the
relay . (See Fig . on next page .)
IR = Input current of auxiliary transforme r
Under the influence of current I, the relay operates . The disc rotates to close the tri p
IRI = Output current of auxiliary transformer contacts and it opens the circuit breaker .
IR1.lags IR by 120 °
This relay is inoperative for zero phase sequence currents . But the relay can be mad e
Hence the relay primary carries the current which is phase difference of I RI and I . operative for the flow of zero sequence currents also by providing an additional winding o n
Positive Sequence Currents : The C .T . secondary currents are shown in th e the central limb of the upper magnet cif the relay . This winding is connected in the residual
Fig . 8.23 (a). The Fig. 8 .23 (b) shows the position of vector IRI lagging IR by 120°. Th e circuit of the three line C .T.s . This relay is called induction type negative and zero sequenc e
Fig . 8.23 (c) shows the vector sum of IRI and - Ix, . relay .
The phase difference of IRI and IY is the vector sum of IRI and - I . It can seen from the The schematic arrangement of induction type negative and zero sequence relay i s
Fig. 8.23 (c) that the resultant is zero . Thus the relay primary current is zero and relay i s shown in the Fig . 8.25 . (See Fig . on next page .)
inoperative for positive sequence currents .
VTU - Switchgear and Protection 222 Generator Protection VTU - Switchgear and Protection 223 Generator Protectio n
Generato r
stator windin g
C .T
-4J 00000000'- : -
Fig . 8 .24 Negative sequence currents C .T
N (00000000 `
T C .B .
- C .T
Auxiliary -(00000000'
transformer
Upper magne t
(Primary)
Additiona l
windin g
To trip
circui t
T
Disc O
Relay
Lower magnet
-4
(secondary)
A negative phase sequence filter is connected to the secondaries of the curren t Ex. 8.4 : A 50 MVA, 3 phase, 33 kV synchronous generator is protected by the Merz-Pric e
transformers . A negative phase sequence filter consists of resistors and inductors . These are protection using 1000/5 ratio C .T.s . It is provided with restricted earth fault protectio n
so arranged that under normal operating conditions, the relay is inoperative . The filter with the earthing resistance of 7.5E2 . Calculate the percentage of winding unprotected i n
circuit is stable for the symmetrical overloads up to about three times the rated full load . each phase against earth faults if the minimum operating current of the relay is 0.5 A .
When unbalanced load occurs, the negative phase sequence filter circuit produces a n Sol. : The given values are,
output proportional to the negative phase sequence components . This is directed through L
V = 33 kV C . T. ratio =1000/5 R = 7.5 E2
the relay coil . Hence the relay operates to open the circuit breaker to isolate the generator . °
i = 0 .5 A = relay current
Examples with Solution s °
I = minimum operating current (primary )
1000 0 .5x100 0
Ex. 8.3 : The neutral point of a 11 kV alternator'is earthed through a resistance of 12 SQ, the relay i s
=1 x °
5 5
set to operate wizen there is out of balance current of 0 .8 A . The C .T .s have a ratio of 200/5 .
What percentage of the winding is protected against earth faults . What must be th e = 100 A
minimum value of earthing resistance required to give 90% of protection to each phase ? V =
L
V - 33x10 3
Sol. : The given values are,
11 kV R =1252 C.T. ratio = 2000/5 = 19052.55 V
relay current = 0.8 A RI°
Winding unprotected = x10 0
minimum operating lin e current (C .T. primary) V
2000 .= 0 .8x 200 0 7.5x100
ix x100
° 5 5 19052 .55
= 320 A 3.936%
V = line to neutral voltage =
V L Ex. 8.5 : A 13 .2 kV, 3 phase, 100 MW at 0 .8 pf lag, alternator has reactance of 0 .2 p .u . If it is
equipped with a circulating current differential protection set to operate at least at 500 A
fault current, determine the magnitude of the neutral grounding resistance that leaves th e
11 x 10 3
= 6350 .8529 V 10% of the winding unprotected ,
Sol . : The given values are,
12x 320x
% Winding unprotected = RIx 100 =
V
100 L
V = 13.2 kV cosh=0.8 P = 100 MW X = 0 .2 p.u.
6350 .852 9
Now P = N*V I cos,1■ LL
60 .46 100x106 = Jx13 .2x 103 xI x 0. 8 L
% Winding protected = 100 - 60 .46 = 39.53 %
Thus with R =1252 only 39 .53 % winding is protected .
L
I = 5467 .33 A = I = full load curren t
= 0 .02787E2 i1 = (300 + j 0) x 5= 3 A
Voltage induced in 10% of unprotected winding 500
10 x13.2x103 and i 2 = (340 + j 0) x 5 = 3.4 A
xV= 10 =762 .1023 V 500
100 100
The directions of currents are shown in the Fig . 8 .28.
Let this voltage be v = 762 .1023 V
Z = .\/r 2. +x 2
where Z = Impedance offered to the faul t
r = Resistance in neutral
x= Reactance of 10% of winding
Now Z = v
where V Voltage induced in 10% winding
Fig . 8 .2 8
762 .1023 V
i Fault current = 500 A The current flowing through the relay coil is i 1 - i 2.
'jr +X 2 762 .1023 i 1 -i2 = 3-3 .4=-0 .4 A
500 i 1 +i2 3+3 . 4
While =3,2 A
vIr2 + (0 .02787) 2 1 .5242 2 2
r2 + (0 .02787) 2 2.3232 From the characteristics of 15 % slope, corresponding to 11 + 12 the out of balance curren t
r2 2.3224 2
r 1 .524 S2 required is,
i 1 +i 2
This is the required resistance in neutral earthing . 11 i2 = Slopex
2 l
Ex. 8.6 : An alternator stator winding protected by a percentage differential relay is shown in th e
Fig. 8.27. The relay has 15% slope of characteristics (I 1 - I2) against (l + I2/2). The high = 0 .15x3 . 2
resistance ground fault has occurred near the grounded neutral end of the generato r = 0 .48 A
winding while the generator is carrying load . The currents flowing at each end of th e
generator winding are also shown . Assuming C .T. ratio to be 500/5 A, will the relay This is shown in the
+ve 15% Slop e
operate to trip the circuit breaker ? Fig. 8.29.
-ve Thus it - i, must b e
0 .48 A
more than 0.48 A i.e.
i1 - i2
above the line to operate
0 .4A
Q Actual poin t the relay but actual poin t
is located below the line
h in negative torque region.
Hence the relay will
2 not operate .
Fig . 8 .2 9
Ex. 8 .7 : A 6.6 kV, star connected alternator has a transient reactance of 2 S2 per phase an d
negligible winding resistance . It is protected by circulating current Merz-Pric e
protection . The alternator neutral is earthed through the resistance of 7 .5 S2 . The relay s
Fig . 8 .2 7 are set to operate when there is out of balance current of 1 A in secondary of 500/5 A
Sol. : From the given current at two ends, let us calculate C .T . secondary currents current transformers . How much % of winding is protected against earth fault ?
at two ends, (V.T.U August-2003 )
Generator Protection VTU -Switchgear and Protection 229 Generator Protectio n
VTU -Switchgear and Protection 228
i) I ° = minimum line operating current (C .T. primary)
Sol. : The given values,
. 1000 3x100 0
V L = 6 .6 kV X = 2n/phase r = 7 .552 C.T. = 500/ 5 = r° x
5 5
Let the x % of winding is unprotected .
= 600 A
Reactance of unprotected winding =100 x 2 = 0 .02 x S2 V20x10 3
v ._ =
1/J 3
V L - 66x10 3 =3810.511 V . . . full voltage
V= =11547 V
X = % of winding unprotecte d
V = Voltage across unprotected windin g
x x 3810 .511=38 .10511 x V - RI,, x100= 15x600 x100
= V 11547
10 0
= 77.94%
r = 7.551
Z = Impedance offered to the faul t ii) We want 75% protection .
= r + j (0.02x) %X = 100-75=25 %
= 7.5 +j (0 .02x) S 2 Remaining conditions are same except R .
1Z = (7 .5) 2 +(0 .02x) 2 25 = RRI°x10 0
V
i = fault current Rx600
= out of balanés--secondary current x C.T. ratio 25 = x10 0
= 1x 500
11547
25 x 11547
5 R-
= 100 A 60N 10 0
V = 4 .811 S
Z=
This is the required earth resistance .
38 .10511 x
V(7 .5) 2 +(0 .02x)2 = Ex. 8.9 : The Fig. 8.30 shows the percentage differential relay used for the protection of a n
100 alternator winding . The relay has minimum pickup current of 0 .25 A and has a % slope of
(7 .5)2 + (0.02 x) 2 = 0 .1452 x2 10%.. A high resistance ground fault occurs near the grounded neutral end of th e
56 .25 +4 x 10 -4 x2= 0.1452 x 2 generator winding with the current distribution as shown in the Fig . 8,30 . Assume a C .T.
0 .1448 x2 = 56.25 ratio of 400 : 5, determine if relay will operate .
x2 = 388.4668
x = 19.7%
This is % of winding unprotected .
of winding protected = 100 - 19 .7
= 80 .29' %
i Fig . 8 .3 0
Ex . 8.8 : A synchronous generator rated at 20 kV protected by circulating current system having '
neutral grounded through a resistance of 1552 . The differential protection relay is set t o "Sol. : For the given current at the two ends, the C .T. secondary currents can be
operate when there is an out of balance current of 3 A . The C .T .s have ratio of 1000/5 A . ? obtained using C .T. ratio as,
Determine,
il = (380 + j 0) x 4 .75 A
i) The % of winding remains unprotecte d 400
ii) Value of earth resistance to achieve 75% protection of winding i2 = (340 + j 0) 40
x-- 4.25 A
Sol. : The given values are ,
VL = 20 kV, i° = 3 A, R = 15 S2, C .T. ratio = 1000/5 ii -i2 = 4.75-4.25=0 .5 A
VTU - Switchgear and Protection 230 Generator Protectio n VTU -Switchgear and Protection 231 Generator Protectio n
i1 + iz = 4 .75+4 .2 5 Ex. 8.10 : An alternator rated 10 kV protected by balanced circulating current system has it s
2 2 neutral grounded through a resistance of 10 ohms . The protective relay is set to operat e
when there is an out of balance current of 1 .8 amperes in the pilot wires which ar e
= 4 .5 A connected to the secondary of current transformers with ratio 1000/5 .
So i t - i, current flows through operating coil while 4 .5 A flows through the restrainin g Determin e
coil . i) The percentage winding which remains unprotected .
With the minimum pickup current of 0 .25 A, and slope 10%, the operatin g ii) The minimum value of the earthing resistance required to protect 80% of the winding .
characteristics is as shown in the Fig . 8.31 . (V .T .U August-2002)
Sol. : VL =10kV, R = 10C .T .ratio =1000/5,=1 .8 A
1° = minimum operating line current (C .T . primary)
1000
.°x15 =1 .8x=360
5 A
3
1o x 10
V = line to neutral voltage = v = = 5773 .5026 V
10 x 360
i) % Winding unprotected = RIx 100 = x 10 0
V 5773 .5026
= 62.3538 %
ii) It is necessary to give 80 % protection .
% Winding unprotected = 100 - 80 = 2 0
Fig . 8 .3 1 Rx360
The equation of the characteristics is, 20 = x10 0
5773 .502 6
y = mx+ c
R = 3 .2075 S2 . . . Minimum earthing resistance require d
At origin, x = 0 but y = 0 .25
Ex . 8.11 : The neutral point of a 10,000 V alternator is earthed through a resistance of 10 Sd, th e
Y = c = 0 .25 relay is said to operate when there is an out of balance current of 1A . The CT's have a rati o
Hence characteristic equation is, of 1000/5 . What % of the winding is protected . What should be the value of resistance t o
get 90% protected . (V .T .U March-2003 )
(il - i2) _
where m = slope = 0 .1
Sol. : VL = 10000 V, R =10E2, i ° = 1 A, C .T . ratio = 1000/ 5
1000
(i 1 - i 2) = 10 = i ° x C .T .ratio =1x =200 A
rl L = 10000
and V=V = 5773 .5026 V
For r2- = 4 .5 we get,
2
10 x 200x
i t -i 2 = (0 .1x4 .5)+0 .2 5 i) % Winding unprotected = x 100 = 100
V 5773 .502 6
=0 .7 A
12 = 34 .64 1
Thus to operate the relay, it - i2 must be greater than 0 .7 A when lr+ is 4 .5 A . Bu t
% Winding protected = 100 - 34 .641 = 65 .3589 %
actually it - i 2 = 0 .5 A as shown . It is located below the line in negative torque region henc e ii) It is necessary to give 90% protection .
relay will not operate . % Winding unprotected = 100 - 90 = 1 0
Rx 200
10 = x10 0
5773 .502 6
R = 2.8867 SI . . . Minimum earthing resistance required
VTU - Switchgear and Protection 232 Generator Protection VTU - Switchgear and Protection 233 Generator Protectio n
Review Question s
1. Which are the various types of faults which can occur in a generator ? Explain in brief.
2. Why the protection of generators is complex ? Explain .
3. Which are the various abnormal running conditions, which may exist in a generator ? What are thei r
effects and how these effects can be minimized ?
4. Explain the basic differential protection scheme . What are its disadvantages ?
5. Explain the basic percentage differential protection scheme . Draw its operating characteristics showin g
positive and negative torque regions .
6. Draw and explain the Merz-Price protection of alternator stator windings . State .its advantages .
7. What is the role of auxiliary relay, in Merz-Price protection ?
8. Explain the restricted earth fault protection of generators.
9. Derive the expression for the percentage of winding unprotected in the restricted earth fault protection .
Fig . 8 .32 (b )
10. Explain the operation of unrestricted earth fault protection scheme .
A high resistance ground fault occurred near the grounded neutral end of the generator winding whil e
11. Draw and explain balanced earth fault protection scheme . generator is carrying load. As a consequence, the currents in amperes flowing at each end of th e
12. Is it possible that 100 % winding of generator is protected against earth faults ? How ? winding are shown in Fig . 8.32 (b) . Assuming C .T. ratio of 400/5 amperes, will the relay operate to tri p
the breaker. (Ans . : Relay will not operate )
13. Suggest the scheme for interturn fault protection for Stator of alternator .
21. A 11 kV, 3 phase alternator has full load rated current of 200 A . Reactance of armature winding i s
14. Explain the negative phase sequence protection for the generators .
15 percent . The differential protection system is set to operate ,on earth fault currents of more than 200
15. What are the methods to provide rotor earth-fault protection ? A. Find the neutral earthing resistance, which gives earth fault protection to 90% of stator winding .
16. How the protection against loss of excitation is provided in generators ? Why it is important ? (Ans . : 3 .145 S2)
17. A generator is provided with restricted earth fault protection . The ratings are 11 kV, 5000 kVA . Th e 22. A star-connected 3-phase 10 MVA, 6 .6 kV alternator has a per phase reactance of 10% . It is protected b y
percentage of winding protected against phase to ground fault is 80% . The relay setting such that it trip s Merz-Price circulating-current principle which is set to operate for fault currents not less than 175 A .
for 25% out of balance. Calculate the resistance to be added in neutral to ground connection . Calculate the value of earthing resistance to be provided in order to ensure that only 10% of th e
(Ans. 1 .94 S2) alternator winding remains unprotected . (Ans . : 2 .171 S2)
18. The neutral point of a 10,000 V alternator is earthed through a resistance of 10 ohms, the relay is .set t o 23. A star connected, 3 phase, 10 MVA, 6 .6 kV alternator is protected by Merz-Price circulating curren t
operate when there is an out of balance current of lA . The C .T.s have a ratio of 1000/5 . Wha t principle using 1000/5 amperes current transformers . The star point of the alternator is earthed through
percentage of the winding is protected against fault to earth and what must be minimum value o f a resistance of 7.5E2 . If the minimum operating current for the relay is 0 .5 A, calculate the percentage of
earthing resistance to give 90% protection to each phase winding ? (Ans . : 62 .5%, 2 .88n) each phase of the stator winding which is unprotected against earth faults when the machine is operatin g
at normal voltage. (Ans . : 19 .69 % )
19. A 3 phase, 2 pole, 11 kV, 10,000 kVA alternator has neutral earthed through a resistance of 7 ohms . Th e
machine has current balance protection which operates upon out of balance current exceed 20% of ful l 24. A 6.600 volt 3-phase turbo-alternator has a maximum continuous rating of 2,000 kW at 0.8 p .f and its
load . Determine % of winding protected against earth fault. (Ans . :88.4% ) reactance is 12 .5% . It is equipped with Merz-Price circulating current protection which is set to operat e
at fault currents not less than 200 amperes. Find what value of the neutral earthing resistance leaves
20. The Fig. 8.32 shows percentage differential relay applied to the protection of an alternator winding. Th e 10% of the windings unprotected ? (Ans . :1.89 S).)
relay has 10% slope of characteristics I, -12 vs (I, + 12)/2.
25. A 50 MVA, 3-phase, 33 kV alternator is being protected by the use of circulating current balance schem e
using 2000/5 ampere current transformer. The neutral of the generator is earthed through a NCR of
Circuit 7,5 ohms, if the pick up current forthe relay is just above 0 .5 ampere, determine what percentage of th e
breaker winding of each phase unprotected against earth when the machine operates at nominal voltage.
320+j 0
'00 (Ans . : 7 .88% )
304 + jO
University Question s
Real coi l 1. With a neat sketch and vector diagrams explain how a negative phase sequence relay is employed fo r
r 000 00 0 protection of electrical power system . (Aug .-2002, 10 Marks )
2 . With a neat diagram explain any one method of protecting large size generator rotor against earth faults .
Fig . 8 .32 (a)
(Aug .-2002, 10 Marks )
VTU -Switchgear and Protection 234 Generator Protectio n
3 . An alternator rated 10 kV protected by balanced circulating current system has its neutral grounde d
through a resistance of 10 ohms . The protective relay is set to operate when there is an out of balanc e
current of 1 .8 amperes in the pilot wires which are connected to the secondary of current transformer s
with ratio 1000/5 .
Determine
i) The percentage winding which remains unprotected. Induction Motor Protection
ii) The minimum value of the earthing resistance required to protect 80% of the winding .
(Aug.-2002, 10 Marks )
4 . Explain the Merz-Price protection given to a generator . (March-2003, 10 Marks )
5 . The neutral point of a 10,000 V alternator is earthed through a resistance of 1052, the relay is said t
o 9 .1 Introductio n
operate when there is an out of balance current of 1 A . The CTs have a ratio of 1000/5 . What % of th e g
winding is protected . What should be the value of resistance to get 90% protected . Based on the control action i .e . starting, stopping or reversal, various controllin
elements known in electrical terms as switchgear are employed for the protection o f
(March-2003, 10 Marks ) d
induction motor . Generally two basic protections viz short circuit protection and overloa
6. With a suitable diagram explain a negative sequence relay and mention its applications . . The switchgear used for protection include s
protection are provided for each motor
.
(Aug .-2003, 10 Marks ) contactors with H .R.C fuse and thermal overload relays along with circuit breakers
7 . Draw and explain the Merz-Price protection of alternator stator windings . State its advantages
. If the rating of the motor is upto 150 kW then contactors and fuses can be used while fo r
(Aug .-2003, 10 Marks ) motors having rating beyond 150 kW, circuit breakers are used . The contactor is a kind o f
8. A 6 .6 kV star connected alternator has a transient reactance of 2U per phase and negligible windin switch through which supply can be given to the motor when its coil is energized . If th e
g e
resistance. It is protected by circulating current Merz-Price protection . The alternator neutral is earthe
d current .to be interrupted is . six times the rated current of the motor then contactors can b
through the resistance of 7 .5 SI . The relays are set to operate when there is out of balance current of 1 used .
A
in secondary of 500/5 A current transformers . How much .% of winding is protected against earth fault
?
(Aug.-2003, 10 Marks ) 9 .2 Abnormal Conditions and Failure in Case of Induction Moto r
The three phase induction motors are used in numerous industrial applications . Henc e
❑❑❑ before studying the protection circuit we have to consider the abnormal conditions an d
failure that may occur in case of induction motor .
If the motor is heavily loaded beyond its capacity then it will be overload condition o f
motor in which case motor draws heavy current from the supply and there will b e
simultaneous rise in temperature of winding and deteroriation of the insulation resulting i n
l
damage of winding . Hence the motor must be protected against this mechanica
. Normally thermal overload relays, ove r
overloading with overload protection circuits
current relays or miniature circuit breaker with built in trip coils may be used .
It might be possible that the rotor is locked or starting lasts for longer duration or roto r
does not move because of excessive load (stalling) at start . In all these cases motor draw s
heavy current from the supply and results in damage to the winding due to overheating a s
.
stated above . In this case thermal relays or instantaneous overcurrent relays are used
If the supply conditions are abnormal such as loss of supply voltage, unbalanced suppl y
voltage, phase sequence reversal of supply voltage, over voltage, under voltage or unde r
frequency then also the performance of the motor is affected . With unbalanced supply
voltage there will be excessive heating while with undervoltage the motor draws mor e
current for the same load . For undervoltage protection, undervoltage relays are used .
(235 )
VTU - Switchgear and Protection 236 InductionMotor Protectio n VTU - Switchgear and Protection 237 Induction Motor Protectio n
With correct phase sequence, the motor runs in one direction . With change in phas e
9 .3 Protection Circuit for Induction Moto r
sequence of supply it runs in other direction which is dangerous in some of the application s
such as cranes, hoists or elevators . In such cases phase reversal relay may be provided whic h The protection circuit along with its single line diagram is shown in the Fig . 9 .1 .
will disconnect the supply to the motor through the circuit breaker .
Ro
Due to excessive temperature rise, the insulation may get damaged which may lead t o
stator earth fault or stator phase to phase fault which are rare in nature . For low ratin g
motors, HRC fuses provide sufficient protection against these faults while for large motors ,
differential protection may be used .
Bo
Due to blowing of fuse in any phase or open circuit in one of the three phases results in
single phasing. In such case motor continues to run and if it is loaded to its rated value then i t
will draw excessive current which will damage the rotor and eventually the motor will b e
damaged due to excessive overheating. Normally thermal overload relays are used agains t Fus e
single phasing . Sometimes special single phase preventer may be provided .
Thermal overload rela y
Summary of abnormal condition and protection circuit to be employed is given in th e ? Suppl y
table . e Switch/
Fuse
ON pushbutton
Abnormal condition Choice of protection circuit to be employe d (normally open )
Overload release, thermal overload relay, over
1 Mechanical overload current relays, miniature circuit breaker (MCB )
with built in trip coil . OF F
(Normally Butto n
2 Stalling or prolonged starting of motor Thermal relays ; Instantaneous overcurrent relay. closed) -*-
Mai n
3 Under voltage Under voltage release, under voltage relay . contacts 0
Table 9 . 1
The motor protection circuit that is designed should be simple in operation an d (a) (b) Single line diagra m
economically feasible . Its cost should be less than 5% of the motor cost . It should also be kept
in mind that during starting and permissible overload conditions, the protection circui t Fig . 9 . 1
should not operate . The choice of motor protecting circuit is based on various factors such as The three phase supply is given to the motor through various elements such as fuse ,
rated voltage, rated kW, size of motor, type of induction motor, type of starter, type o f switch, contactor and thermal overload relay . The control circuit of contactor consists o f
switchgear used, cost of motor, type of load, starting current possibility of occurance o f energizing coil, start and stop buttons . The start (ON) push button is normally open gree n
abnormal conditions etc . switch while the stop (OFF) push button is normally closed red switch .
When the start button is pressed then the contactor coil is energized as it gets suppl y
voltage . The coil attracts the plunger when excited and the main contacts are closed alon g
with the auxiliary contact . Even if the ON push button is relased, the contactor coil remains
energized as it gets supply through auxiliary contacts . Thus motor starts running .
239 Induction Motor Protectio n
VTU - Switchgear and Protection 238 Induction Motor Protection VTU -Switchgear and Protection
The OFF push button which is normally closed when pressed cuts the supply of th e
contactor coil and hence the main as well as auxiliary contacts are open so motor eventuall y
stops . If supply voltage fails, control coil is de-energized which opens the contactor an d
motor stops .
During overload condition, the thermal overload relay operates . Thermal overload relay Contro l
consists of bimetallic strips . Because of bending of one or more bimetallic strip results i n circuit
operation of common lever which operates the trip contacts to deenergize the coil and
disconnects the supply to the motor .
The bimetallic strips are either heated directly by flow of current or with the help o f
special heater coil through which motor current flows . For large motors, these relays ar e Therma l ON
connected in secondary of current transformers . The bimetallic strips can be of self settin g overloa d o--+
type or hand resetting type in which mechanical reset is required as the trip mechanis m %zz relay
locks itself in operated condition . It should be observed that the rating of thermal rela y
should be such that it should not operate during normal starting conditions . A setting range
is provided for adjustment for various load conditions . Protection against short circuit i s OF F
provided with the help of HRC fuses . o
_ -10000-ti =====
9.4 Single Phasing Prevente r
If one of the supply line is disconnected due to open circuit or improper contact in switc h Contacto r Contactor
then still the motor continues to run . The power is then supplied to the remaining windings . coil
The current in the other phases increases to about times its normal value . This is calle d
single phasing which results in unbalanced stator currents . The component which is present
Three phas e
in this unbalanced current called negative sequence component causes magnetic flu x I. M.
rotating in opposite direction to the main flux . This results in double frequency currents t o
induce in the rotor to cause its heating . Thus major damage to motor may take place due t o
single phasing if proper precaution is not taken . As the phase overcurrent relays reac t
slowly, they cannot give the instantaneous protection against single phasing . Fig. 9.2
Consider an example of a person .whose finger sticks into the socket . Even though the
For small motors separate protection against single phasing is normally not provided as
metal enclosure is securely earthened, the person will receive a severe shock . Under such
thermal relays sense the increased current in remaining phases due to single phasing an d
case there must be certain device that will cut the supply . This can be done with the help o f
provides the sufficient protection .
ELCB which will typically trip in around 25 ms if current exceeds its preset value .
A separate single phasing protection circuit is required in case of large induction motor s
as even a small unbalance can cause damage to motor winding and rotor . The single phasing The schematic of ELCB is shown in Fig . 9.3 .
preventer is shown in the Fig . 9.2 . (See Fig. on next page .)
As shown in the figure, it consists of C .Ts connected in each phase . The output of control
circuit is fed to the level detector which sensethe magnitude of unbalance . Depending o n
this output from the control circuit the tripping command to the starter or the circuit breake r
is given when negative sequence current exceeds its preset limit .
Fig. 9 .3
VTU - Switchgear and Protection VTU - Switchgear andProtection 241 Induction Motor Protectio n
240 Induction Motor Protection
As shown in the Fig. 9 .3 ELCB consists of a small current transformer surrounding liv e R Thre e
and neutral wire . The secondary winding of current transformer is connected to relay circui t Y phas e
which can trip the circuit breaker which is connected in the circuit . supply
B
Under normal conditions, the current in line and neutral conductor is same so the ne t
current (I L -IN ) flowing through the core is zero . Eventually there will not be an y
production of flux in the core and no induced emf. So the breaker does not trip .
If there is a fault due to leakage from live wire to earth or a person by mistake touching t o
the live terminal then the net current through the core will no longer remain as zero bu t
equal to I L -IN or It which will set up Rix and emf in C .T. As per the preset value the
unbalance in current is detected by C .T . and relay coil is energized which will give tripping
singal for the circuit breaker . As C.T . operates with low value of current, the core must b e
very permeable at low flux densities .
In case of three phase circuits, single ring shaped core of magnetic material, encircles th e
conductor of all three phases as shown in the Fig . 9.4. A secondary is connected to relay
circuit . Under normal condition, the component of fluxes due to fields of three conductor s
are balanced and secondary carries negligible current .
should be disconnected as quickly as possible when fault occurs . Fast over current relay s
also are used to provide phase fault protection .
As mentioned above to avoid relay functioning during starting, the short circui t
protection current setting must be just above the maximum starting current of the motor .
10.2 .1 Overheatin g
❑❑❑
The overheating of the transformer is basically of sustained overloads and short circuits .
The permissible overload and the corresponding duration is dependent on the type o f
transformer and class of insulation used for the transformer . Higher loads are permissibl e
for very short duration of time . The overloading which continues for longer time i s
dangerous as it causes overheating of the transformer. Similarly the failure of the coolin g
system, though rare, is another possible cause of overheating . Generally the therma l
overload relays and temperature relays, sounding the alarm are used to provide protectio n
against overheating . Similarly temperature indicators are also provided . On th e
transformers, when temperature exceeds the permissible limits, the alarm sounds and th e
(243)
VTU -Switchgear and Protection 245 Transformer Protectio n
VTU - Switchgear and Protection 244 Transformer Protection
result. Higher core flux means more core loss and overheating of the core . The saturation o f
fans are started . The thermocouples or resistance temperature indicators are also provide d magnetic circuit is also the probable cause for the overfluxing operation . The V/f relay
near the winding . These are connected in a bridge circuit . When temperature exceeds th e called volts/hertz relay is provided to give the protection against overfluxing operation .
limiting safe value, the bridge balance gets disturbed and alarm is sounded . If the correctiv e
This relay does not allow exciting current to flow till the generator reaches to a synchronou s
action is not taken within certain period of time then the circuit breaker trips .
speed and runs to produce voltage of proper frequency . The overfluxing relays with enoug h
time lag also can be provided .
10.2 .2 Winding Faults
The winding faults are called internal faults . These faults are, Apart from these faults, some other faults like tap-changer faults, high voltage surge s
due to lightning and switching, incipient faults i .e . slow developing faults may also occur i n
i) Phase to phase faults the transformers . The Buchholz relay is used for oil immersed transformers to give th e
ii) Earth faults protection against incipient faults .
iii) Inter turn fault s
10 .3 Percentage Differential Protection for Transformer s
The overheating or mechanical shocks cause to deteriorate the winding insulation . If th e
winding insulation is weak, there is a possibility of short circuit between the phases o r The percentage differential protection or Merz-Price protection based on the circulatin g
between the phase and ground . Also the possibility of short circuit between the adjacent current principle can also be used for the transformers . This system gives protection agains t
turns of the same phase winding is also possible . phase to phase faults and phase to ground faults to the power transformers .
When such an internal fault occurs, the transformer must be quickly disconnected fro m The principle of such a protection scheme is the comparison of the currents entering an d
the system . If such a fault persists for longer time, there is possibility of oil fire . Th e leaving the ends of a transformer . The vector difference of currents I I - I 2 passes through th e
differential protection is very commonly used to provide protection against such faults . But operating coil while the average current (I I + I2)/2 passes through the restraining coil . In
this protection is not economical for the transformers below 5 MVA for which an ove r normal conditions, the two currents at the two ends of the transformer are equal and balanc e
current protection is used . For the high capacity transformers in addition to mai n is maintained . So no current flows through the operating coil of the relay and relay i s
differential protection, the overcurrent protection is also provided as a backup protection . inoperative . But when there is phase to phase fault or phase'to ground fault, this balance get s
For earth fault protection, the restricted earth fault protection system, neutral current relay s disturbed . The difference current flows through the operating coil due to which rela y
or leakage to frame protection system is used . operates, tripping the circuit breaker .
Compared to the differential protection used in generators, there are certain importan t
10 .2 .3 Open Circuit s
points which must be taken care of while using such protection for the power transformers .
The open circuit in one of the three phases is dangerous as it causes the undesirabl e These points are ,
heating of the transformer . A separate relay protection is not provided for the open circuit s 1. In a power transformer, the voltage rating of the two windings is different . The high
as open circuits are much harmless compared to other faults . In case of such faults, th e voltage winding is low current winding while low voltage winding is high curren t
transformer can be manually disconnected from the system . winding. thus there always exists difference in current on the primary and secondar y
sides of the power transformer . Hence if C .T .s of same ratio are used on two sides,
10 .2 .4 Through Faults .
then relay may get operated through there is no fault existing .
Through faults are the external faults which occur outside the protected zone . Through To compensate for this difficulty, the current ratios of C .T .s on each side ar e
faults are not detected by the differential protection . If the through faults persists for lon g different . These ratios depend on the line currents of the power transformer and th e
period of time, the transformer may get subjected to the thermal and mechanical stresse s connection of C .T.s . Due to the different turns ratio, the currents fed into the pilo t
which can damage the transformer . The overcurrent relays with undervoltage blocking, wires from each end are same under normal conditions so that the relay remain s
zero sequence protection and negative sequence protection are used to give protectio n inoperative . For example if K is the turns ratio of a power transformer then the rati o
against through faults . The setting of the overcurrent protection not only protects th e of C .T.s on low voltage side is made K times greater than that of C .T.s on high voltage
transformer but also covers the station busbar and portion of a transmission line . Such a side .
protection acts as a backup protection for the differential protection . 2. In case of power transformers, there is an inherent phase difference between th e
voltages induced in high voltage winding and low voltage winding . Due to this ,
10 .2.5 Overfluxin g there exists a phase difference between the line currents on primary and secondar y
The flux density in the transformer core is proportional to the ratio of the voltage t o sides of a power transformer . This introduces the phase difference between the C .T .
frequency i .e. V/f . The power transformers are designed to work with certain value of flu x secondary currents, on the two sides of a power transformer . Though the turns rati o
density in the core . In the generator transformer unit, if full excitation is applied befor e of C .T.s are selected to compensate for turns ratio of transformer, a differentia l
generator reaches its synchronous speed then due to high V/f the overfluxing of core may current may result due to the phase difference between the currents on two sides .
VTU - Switchgearand Protection 246 Transformer Protection VTU -Switchgear and Protection 247 Transformer Protectio n
Such a differential current may operate the relay though there is no fault . Hence it i s 10.3 .1 Merz-Price Protection for Star-Delta Transforme r
necessary to correct the phase difference .
To compensate for this, the C .T . connections should be such that the resultan t
currents fed into the pilot wires from either sides are displaced in phase by an angl e
equal to the phase shift between the primary and secondary currents . To achieve this,
secondaries of C .T.s on star connected side of a power transformer are connected i n
delta while the secondaries of C .T .s on delta connected side of a power transforme r
are connected in star. a
The Table 10 .1 gives the way of connecting C .T. secondaries for the various types o f a)
power transformer connections . N
C
m
Power Transformer Connections C. T. Connections
A
Primary Secondary Primary Secondary o
Star Delta Delta Star
m
Delta Delta Star Star Û - --------------- -
For the sake of understanding, the connection of C .T . secondaries in delta for star side of.
-
power transformer and the connection of C .T. secondaries in star for delta side of power -
H t
Û( m
0 0
Fig . 10 .1
VTU -Switchgear and Protection 248 Transformer Protection VTU -Switchgear and Protection 249 Transformer Protectio n
Let us study the Merz-Price protection for the star-delta power transformer . The
primary of the power transformer is star connected while the secondary is delta connected .
Hence to compensate for the phase difference, the C .T . secondaries on primary side must b e
connected in delta while the C .T . secondaries on delta side must be connected in star . Th e m
star point of the power transformer primary as well as the star connected C .T . secondaries
must be grounded . N
a
.2 %a
The circuit diagram of the scheme is shown in the Fig . 10 .2 (See Fig . on previous page) . •
a) -o
N
C C
C o
The restraining coils are connected across the C .T. secondary windings while th e o U
❑ 0)
operating coils are connected between the tapping points on the restraining coils and the ai
N
star point of C .T . secondaries . CO
With the proper selection of turns ratio of C .T .s the coils are under balanced condition a
C
during normal operating conditions . The C .T. secondaries carry equal currents which are i n a
m
O
phase under normal conditions . So no current flows through the relay and the relay i s C
C
inoperative . o O*
0
With an internal fault in power transformer windings, the balance in the C .T .s ge t *a)
N
disturbed . The operating coils of differential relay carry currents proportional to th e
difference of current between the two sides of a power transformer . This causes the rela y - -
operation which trips the main circuit breakers on both the sides of the power transformer .
The basic requirements of the differential relay are ,
-4eo
I o
I
e
e
e b
I ôo ôe o
o ,I
1. The differential relay must not operate on load or externaLfaults . I ô ô 0
°
o
2. It must operate on'severe -internal faults . ----------- -
The relay satisfying these requirements is used in Merz-Price protection . ill e
It is important to note that this scheme gives protection against short circuit fault s °
0,6
III
between the turns i.e. interturn faults also . This is because when there is an interturn fault , e
the turns ratio of power transformer gets affected . Due to this the currents on both sides o f
the power transformer become unbalanced . This causes an enough differential curren t
which flows through the relay and the relay operates . ri°
I
• "
I: 1iii
un
Hence the C .T . ratio on 33 kV side is ,
Primary current _ 12 .1 2
C .T. ratio
Ill Secondary current 5- Z
• . .. .
= 1 .4 : 1
This is the required C .T. ratio on 33 kV side .
4 . Magnetizing current inrush : When the transformer is energized, the conditio n In the latest method, the harmonic content of the magnetizing current flowing in th e
initially is of zero induced e .m .f . and it is similar to the switching of an inductiv e operating circuit is filtered out and passed through a restraining coil . This is called harmoni c
circuit . Due to this the transient inrush of magnetising current flows in to th e current restraint .
transformer . This current is called magnetizing current inrush . This current may b e
as great as 10 times the full load current of the transformer . This decays very slowly 10 .4 .1 Harmonic Restraint and Harmonic Blockin g
and is bound to operate differential protection of the transformer falsely . The high initial inrush of magnetizing currents consist of a high component of even an d
The factors which affect the magnitude and direction of the magnetizing current inrus h odd harmonics .
are, Table 10 .2 gives the typical values of harmonic contents in a magnetizing current .
a. Size of the transforme r
b. Size of the power syste m Order of harmonic content in magnetizing Amplitude as a % of fundamenta l
c. Type of magnetic material used for the core . curren t
d. The amount of residual flux existing before energizing the transformer . 2nd 63. 0
e. The method by which transformer is energized .
If the transformer is energized when the voltage wave is passing through zero, th e 3 rd 26.8
magnetizing current inrush is maximum . At this instant, the current and flux should b e
4 th 5.1
maximum in highly inductive circuit . And in a half wave flux reversal must take place t o
attain maximum value in the other half cycles . If the residual flux exists, the required flu x
5th 4.1
maybe in same or opposite direction . Due to this magnetizing current inrush is less or more .
If it is more, it is responsible to saturate the core which further increases its component . 6 th 3.7
This current decays rapidly for first few cycles and then decays slowly . The tim e
constant L/R of the circuit is variable as inductance of circuit varies due to the change in 7t h 2.4
,
permeability of the core . The losses in the circuit damp the inrush currents . Depending o n Table 10.2
the size of the transformer, the time constant of inrush current varies from 0 .2 sec to 1 sec .
The operating coil carries the fundamental component of the inrush current only . The
The waveforms o f
harmonic contents and fundamental together is passed through the restraining coil .
Phase R magnetizing inrush current i n
three phases is shown in th e Thus more the harmonic contents in the inrush current, more is the restraining torqu e
Fig . 10.5 . and the relay does not operate . .So use of percentage differential protection rather tha n
simple differential protection is preferred . The circuit used to compensate the effect o f
Restrainin g
surges . Firstly the relay may
Phase Y coil s
be given a setting higher tha n
* 1 vU V t
maximum inrush current . X111 1111 o
U
Secondly the time setting ma y
be made long enough for th e
magnetizing current to fall to
Phase B
I lu « a value below the primar y
operating current before th e
relay operates . But thes e
simple remedies are
inconsistent with high spee d
and low primary operating
o
current .
Fig . 10 .5 Typical magnetizing inrush current waveforms Fig . 10 .6 Magnetizing current compensatio n
VTU - Switchgear and Protection 254 Transformer Protection VTU -Switchgear and Protection 255 Transformer Protectio n
The filter F1 is designed to pass the fundamental 50 Hz component which excites th e When there is an earth fault, then fault current leaks from the frame and passes throug h
operating coil Ro . The magnetizing current has large third harmonic component . There is an the earth connection provided . Thus the primary of C .T . senses the current due to whic h
additional restraining coil Rr . The filter F, is designed to pass the third harmonic componen t current passes through the sensitive earth fault relay . This operates the relay .
which energizes the additional restraining coil Rr . The current passing through normal Such a protection is provided only for small transformers . For the large transformers ,
restraining coil and current passing through additional restraining coil Rr produce sufficien t the differential protection is enough to sense and operate for the earth faults .
restraining torque . This compensates for the differential current resulting due to the flow o f
magnetizing current . 10.6 Buchholz Relay
The separate blocking relay in series with the differential relay is used . The operation of The Buchholz relay is a gas operated relay used for the protection of oil immerse d
this relay is based on harmonic component of inrush current . This relay consists of 100 H z transformers against all the types of internal faults . It is named after its inventor, Buchholz .
blocking filter in operating coil while 50 Hz filter in restraining coil . At the time of inrush The slow developing faults called incipient faults in the transformer tank below oil leve l
current, second harmonic component is maximum and thus blocking relay is blocked with operate Buchholz relay which gives an alarm . If the faults are severe it disconnects th e
its contacts remain open . transformer from the supply .
In short circuit case, the harmonic component is negligible and 50 Hz component i s It uses the principle that due to the faults, oil in the tank decomposes, generating th e
dominant . Hence the blocking relay operates to close its contact . This principle is calle d gases . The 70% component of such gases is hydrogen which is light and hence rises upward s
harmonic blocking . towards conservator through the pipe . Buchholz relay is connected in the pipe, as shown i n
the Fig . 10.8 . Due to the gas collected in the upper portion of the Buchholz relay, the rela y
10 .5 Frame Leakage Protectio n
operates and gives an alarm .
This protection is nothing but the method of providing earth fault protection to th e
transformer . This protection can be provided to the metal clad switchgear .
The arrangement is shown in the Fig. 10.7 .
Earthin g
bus Earth faul t
C . T.
relay y
::
lrlrllllllil ' :: 1111 1
Concrete
foundation
Earthing
closed . This energizes the trip circuit which opens the circuit breaker . Thus transformer i s
totally disconnected from the supply .
The connecting pipe between the tank and the conservator should be as straight a s
possible and should slope upwards conservator at a small angle from the horizontal . Thi s
Gas accumulate d angle should be between 10 to 11°.
Float tilting with reduced oil level For the economic considerations, Buchholz relays are not provided for the transformer s
having rating below 500 kVA .
10 .6.2 Advantages
The various advantages of the Buchholz relay are ,
1. Normally a protective relay does not indicate the appearance of the fault . It operates
when fault occurs . But Buchholz relay gives an indication of the fault at very earl y
stage, by anticipating the fault and operating the alarm circuit . Thus the transforme r
can be taken out of service before any type of serious damage occurs .
2. It is the simplest protection in case of transformers .
10.6 :3 Limitation s
The various limitations of the Buchholz relay are ,
1. Can be used only for oil immersed transformers having conservator tanks .
2. Only faults below oil level are detected .
3. Setting of the mercury switches can not be kept too sensitive otherwise the relay ca n
operate due to bubbles, vibration, .earthquakes mechanical shocks etc .
Fig. 10 .9 Construction of Buchholz rela y 4. The relay is slow to operate having minimum operating time of 0 .1 seconds an d
average time of 0 .2 seconds.
10 .6.1 Operatio n
There are many types of internal faults such as insulation fault, core heating, bad switc h 10 .6.4 Application s
contacts, faulty joints etc . which can occur . When the fault occurs the decomposition of oil in The following types of transformer faults can be protected by the Buchholz relay and ar e
the main tank starts due to which the gases are generated . As mentioned earlier, major indicated by alarm, :
component of such gases is hydrogen . The hydrogen tries to rise up towards conservator bu t 1. Local overheating
in its path it gets accumulated in the upper part of the Buchholz relay . Through passage o f 2. Entrance of air bubbles in oil
the gas is prevented by the flap valve . 3. Core bolt insulation failure
When gas gets accumulated in the upper part of housing, The oil level inside the housin g 4. Short circuited lamination s
falls . Due to which the hollow float tilts and close the contacts of the mercury switc h 5. Loss of oil and reduction in oil level due to leakag e
attached to it . This completes the alarm circuit to sound an alarm . Due to this operator
6. Bad and loose electrical contact s
knowsthat there is some incipient fault in the transformer . The transformer is disconnecte d
and the gas sample is tested . The testing results give the indication, what type of fault i s 7. Short circuit between phase s
started developing in the transformer . Hence transformer can be disconnected before faul t 8. Winding short circuit
grows into a serious one . The alarm circuit does not immediately disconnects the 9. Bushing punctur e
transformer but gives only indication to the operator . This is because some times bubbles i n 10. Winding earth faults .
the oil circulating system may operate the alarm circuit through actually there is no fault . Examples with Solution s
However if a serious fault such as internal short circuit between phases, earth faul t
inside the tank etc . occurs then the considerable amount of gas gets generated . Thus due to Ex . 10.2 : A 11 kV/132 kV power transformer is connected in delta-star . The C .T .s on the low
voltage side have turns ratio of 600/5 . Find the suitable turns ratio for the C .T.s on high
fast reduce level of oil, the pressure in the tank increases . Due to this the oil rushes toward s
voltage side.
the conservator . While doing so it passes though the relay where flap valve is present. Th e
flap valve gets deflected due to the rushing oil . Due to this the mercury switch contacts get Sol. : The connections are shown in the Fig . 10 .10.
VTU - Switchgearand Protection 258 Transformer Protection VTU - Switchgearand Protection 259 Transformer Protectio n
50
C.T . ratio on high voltage side =
(5/ 13-)
= 17.32 : 1
Ex. 10.3 : A 3 phase, 200 kVA,11 kV/400 V transformer is connected in delta-star . The C .T.s o n
low voltage side have turns ratio of 500/5 . Determine the C .T. ratio on high voltage side.
Also obtain the circulating current when the fault of 750 A offollowing types occur on th e
low voltage side :
i) Earth fault within the protective zone
ii) Earth fault outside the protective zone
iii) Phase to phase fault within the protective zon e
iv) Phase to phase fault outside the protective zon e
Assume balanced voltage .
Sol. : The connections are shown in the Fig . 10 .11.
Star-
C . T. H . V. Sid e
secondaries
Fig . 10 .1 0
Let the current on the primary i .e . low voltage side of power transformer be 600 A .
This current will flow through each line on primary of transformer .
Hence current in each secondary of star connected C .T. on.primary is the phase current
Ip as shown in the Fig . 10.10.
0
Ip = 600 x 6 0 = 5 A
The same in line current I L which is line current for the C .T.s connected in delta on
secondary of transformer .
Hence current in each secondary of C .T. which is phase current of C .T. is )/ times the
line value .
Ip = - A for C. T. secondary connected in delta
IL1 11000
= 18.18 A
This is current through each primary of C .T .s connected in star .
Current ratio of C .T .s on high voltage side
_ 18 .1 8
5-13- ô
U
= 2 .099 : 1 a
To'
(i) Consider the earth fault within-the protective zone as shown in the Fig . 10.12.
(See Fig . 10.12 on next page . ) Q
Now IL2 = 750 A CD
N
Equating apparent power , a
Q) a
W
VL1 I L1 =N VL2 I L2
ô n
r
x11000xI L1 = fx400x75 0
0 N
ILl = 27 .27 A
a
This is the line current on h .v . side under fault condition . r
N
The C .T . ratio is 2.099 : 1 . Hence corresponding current through C .T. secondary on h.v . N
r
1
side is, = 27 .27 x = 12 .99 A
2 .099
N a
So 12 .99 A current will flow through the relay and relay will operate . m
)
C
(ii) Consider the earth fault outside the protective zone as shown in the Fig . 10.13 . Th e
line current on secondary is 750 A .
Secondary C .T . current = 750 x 500 7.5 A
The currents are shown in the Fig . 10.13. Due to such fault current will flow in two phases of low voltage winding but in all thre e
phases in high voltage winding as shown in the Fig . 10 .14 . This current on high voltage sid e
will flow through the relay and relay will operate .
So on both sides the current is balanced hence no current will flow through the relay an d
relay will not operate .
iii) Phase to phase fault in the protected zone on low voltage side . This is shown in the
Fig. 10.14.
VTU -Switchgear and Protection 264 Transformer Protection VTU -Switchgear and Protection 265 Transformer Protectio n
r
iv) Consider phase to phase fault outside the protected zone as shown in the Fig . 10.15. C .T .s on star connected side are delta connected hence current in secondary is equal t o
The various currents and corresponding distribution is also shown in the Fig . 10.15. current in pilot wires divided by -13- .
Assume 400 A is flowing in the lines on low voltage side i .e. 6.6 kV side .
Now primary apparent power = secondary apparent powe r
VL1 ILl = 3 V L2 I L2
x33x10 3 xIL, = Jx6 .6x103 x40 0
ILI = 80 A
This is primary current of C .T. on high voltage side .
On the delta side of transformers the C .T. secondaries are star connected . Their
secondary current is 5 A . Hence current fed in pilot wires from low voltage side is 5 A . Same
current is fed from C .T . connections on high voltage side which are delta connected .
Hence secondary current of C .T.s on high voltage side is 5/-, A .
Thus C.T . ratio on H .T. side is 80 : 5/' i.e. 27.712 :1 .
The connection diagram is shown in the Fig. 10.16.
C .T. C .T.
Secondarie s
Delt a
Secondaries
in sta r
1
in delta Sta r
0000' -* 0000'
Restraining coils
'0040
Operating coil s
As the currents on both sides are balanced, no current flows through the relay henc e O
relay will not operate .
Ex. 10 .4 : A 3 phase transformer rated for 33 kV/6 .6 kV is connected star/delta and the protectin g
1
current transformers on the low voltage side have a ratio of 400/5 . Determine the ratio of 1
the current transformers on H. V. side . Draw the connection diagram showing how th e
relay operates under fault conditions . Fig . 10 .1 6
Sol. : C,T.s on delta connected side are star connected . Hence the secondary phas e
currents are equal to currents in pilot wires .
VTU - Switchgear and Protection 266 Transformer Protectio n
Review Question s
1 . State and explain the various possible faults in transformer . Why the faults are less in transformers than th e
11
generators .
2. What is overfluxing ? When it occurs ? What are the methods to overcome it ?
Carrier Aided Protectio n
3. Which are the important point to be taken care of while providing differential protection to the transformers ?
4. Draw explain the Merz-Price protection scheme for ,
and Static Relay s
i) Star-Delta transforme r
ii) Star-Star transformer
ii) Delta-Star transforme r 11 .1 Block Schematic of Carrier Aided Protectio n
5. State the problems encountered in a simple differential protection of transformers .
Carrier aided protection is used for the protection of transmission lines . The carrie r
6. Write a notes on , currents with high frequency range are transmitted and received with the help o f
i) Magnetic current in rus h transmission lines for protection . The schematic representation of carrier current protectio n
ii) Harmonic restraint and harmonic blocking is shown in the Fig . 11.1 .
iii) Frame leakage protectio n
7. Draw and explain the construction and working of Buchholz relay . Against which faults Buchholz relay gives Bus ba r
the protection ? State its advantages and disadvantages .
8 . Describe with the help of a neat diagram the connections of differential protection of a transformer . A 3-phas e
33/6 .6 kV star/delta connected transformer is protected by differential system . The C .T.'s on LT side hav e
ratio of 300/5 . Show that the C .T.s on HT side will have a ratio 60 : 53.
9. A 3 phase transformer of 220/11,000 line volts is connected in star/delta . The protective transformers on 22 0
V side have a current ratio of 600/5. What should be C .T. ratio on 11,000 V side ? (Ans . : 1 .385 :1 )
10 . A 3-phase, 2 2 0/11 000 V transformer is connected in star-delta and the protective transformers on the 22 0
V sides have a current ratio of 60% . What must be the ratio of the CT. s on the 11,000 V side and ho w
Normally the frequencies with range from 50 to 500 kHz are employed in variou s
can be seen that the carrier current signals are allowed to pass through this capacitor an d
frequency bands with each has specific bandwidth . The oscillator is used for the generatio n
enter in carrier equipment while power frequency currents are blocked . The inductanc e
of carrier frequency and it is tuned for a particular frequency which is chosen for particula r
connected in series with the coupling capacitor reduces the impedance to further low value .
Thus a condition of resonance is achieved at carrier frequency . application . Sometimes a crystal oscillator may also be used which gives particula r
bandwidth after selecting particular type of crystal . Voltage stabilizers are employed fo r
2. Line Trap Uni t maintaining the oscillator output voltage constant . The losses in the transmission pat h
This unit is between the busbar and the connection of coupling capacitor to the line . It between transmitter and receiver at remote end of line are overcome with the help o f
consists of parallel combination of inductance (L) and capacitance (C) acting as tuned circuit . amplifier which increases the level of the signal to be transmitted .
This circuit offers low impedance to power frequency currents while offers very hig h The attenuation in signal is due to losses in coupling equipment which are constant fo r
impedance to carrier frequency currents which prevents the high frequency carrier to enter given frequency range . Depending on length of line, frequency whether conditions and th e
in the neighbouring line and carrier currents flow only in the protected line . size and type of line, the line losses vary .
3. Protection and Earthing of Coupling Equipmen t If weather is fairly reasonable then the attenuation is of the order of 0 .1 dB/kHz a t
Due to lightning, switching transients or faults, overvoltage surges are produced on th e 80 kHz which increases 0 .2 dB/km at 380 kHz . If we consider 250 km line then the output o f
transmission lines . These overvoltages may produce stress on coupling equipment and lin e power amplifier is about 20 W . For a particular bandwidth the amplifier should giv e
trap unit. For protection purpose, the nonlinear resistors are connected across line trap uni t maximum power . Depending on the type of protection required, various methods ar e
in series with a protective gap . These resistors with protective gap is connected acros s adopted for the control of transmitter . The interconnection between oscillator and amplifie r
inductor in the coupling unit . The length of the gap is adjusted in such a way that, spark ove r is done through control circuit . The block diagram representation of transmitting unit i s
takes place at a set value of overvoltage . The earth rod is used is for earthing of coupling uni t shown in the Fig . 11 .3 (b) .
so as to get low resistance earth path . The relay room consists of carrier equipment pane l
which is connected to station earthing system . Contro l
unit
4. Electronic Equipment s
Following electronic equipments are generally used at each end of the line ,
a) Transmitter uni t
Form _ To
b) Receiver unit
c) Relay unit
rela y
unit
Oscillator Amplifier
H lin e
Carrie r
Receiver receiver
Line tuning unit
The signal is reduced to a safe value with the help of attenuator . The undesired signal s The block diagram of the phase comparison method is shown in the Fig . 11 .5 .
which are signals from subsequent sections or spurious signals are prevented by using ban d C6)
pass filter . The matching element matches the impedance of the transmission line an d
Oscillator Modulato r Amplifie r
receiving section . The undesired signals are generated either by short circuits or radi o
interferences . The malfunctioning of this unit is avoided due to the noise signals by using th e
set value above 2 milliwatts which is above noise level . If the carrier signals have power leve l
of 20 W and receiver unit is set at higher level of 5 milliwatts then the operation is unaffecte d
by spurious signals . For avoiding the overloading, the signals should be attenuated befor e Summation
applying - it to the amplifier detector . Starter
Comparato r Receive r
c) Frequency Spacing : The subsequent line sections use various frequencies . The carrier
signals are prevented from entering into next section by wave traps . The filters fro m
receiving unit filters other frequencies . The frequency bands of various sections are properl y
co-ordinated .
Tri p
d) High Frequency Signal Modulatio n relay
For modulation of power frequency signals, the modulator is used . The signal after
modulation is passed to the amplifier and then transmitted through coupling unit . From th e Fig . 11 .5 Block diagram of phase comparison metho d
half cycle line currents, the required blocks of carrier signals are generated with the help o f In this method, the phase relation between the current entering in the protected zon e
oscillator . The level of line current at which .oscillator generates these carrier blocks shoul d and current leaving the protected zone is compared without comparison of magnitudes o f
be theoretically constant but practically there is critical minimum current . The modulation currents . It does not provide back up protection which is to be additionally provided but i t
of line current into high frequency carriers is shown in the Fig . 11 .4. acts as main protection.
In this method the signals are sent from each end of the line while they are received at th e
other end . The signals are obtained from C .T . secondaries and are related to the current flo w
in the main line .
In the absence of any fault on the line, the signal is sent for alternate half cycles from eac h
end resulting in continuous signal on the line . For external fault the same condition hold s
good . If there is an internal fault, the current in one of the lines reverses in phase and remain s
below fault detector setting resulting in sending the carrier only for half the time . The relay i s
arranged to sense the absence of signal in the line . When the phase angle between the tw o
signals reaches to a certain set value, the tripping occurs .
For internal fault condition, the transmitted signals and received signals are almost i n
phase with each other . The comparator compares these signals . For alternate half cycles, the
signal is absent so the comparator gives output which operates to trip=relay . Various signal s
in primary circuit, secondary circuit : transmitter, receiver comparator during external fault
are shown in the Fig . 11 .6 . (See on ne xt page .)
Carrier signals are transmitted to the line from both ends . If fault is external then th e
effect of sum of the two signals is similar to that obtained with continuous high frequenc y
11 .2 Phase Comparison Method of Carrier Current Protectio n carrier available on line . Protection is designed to remain stable under this condition .
If fault is internal then sum of these two signals produces effects similar to periodi c
There are various methods of carrier current protection . Some of them are as give n
suppression of such a continuous carrier . The time span between the each suppression i s
below
proportional to the phase displacement between the primary current at both the ends . .
1. Directional comparison metho d Normal angle for which designed protection operates is about 30° below which th e
2. Phase comparison method protection remains stable . This angle is known as stabilising angle of protection . The high
frequency signals are generated by the process of modulation .
VTU - Switchgear and Protection 272 Carrier Aided Protection & Static Relays VTU -Switchgear and Protection 273 Carrier Aided Protection & Static Relays
End 1 End 2
11 .3 Advantages of Carrier Current Protectio n
With carrier current protection, very fast fault clearing is obtained . The tripping o f
Primary curren t circuit breakers at both ends of the line takes place in about one to three cycles . Due to thi s
stability of power system is improved . The other advantages of this protection are give n
below
1. Simultaneous reclosing of circuit breaker is possible as reclosing signal is sent
Secondary signa l simultaneously .
2. It prevents shock to the systems as faults are cleared rapidly .
3. It gives easy discrimination for simultaneous faults .
Transmitted signa l 4. During synchronizing power surges, tripping does not occur .
5. For operation of circuit breaker to be fast, faster relaying is necessary which is
achieved through carrier aided protection.
Signal fed to receive r
The carrier current equipments are used in other applications apart from protection
which include communication between two stations . The receiving stations and substations
Current in comparato r
are provided with telephones which are connected to carrier current equipment an d
conversion of signals is done with the help of carrier current communication . The remote
control of power station equipment is possible through carrier equipments using carrie r
signals . It is also used in telemetering which consists of various electronic equipments tha t
End 1 End 2 convert the data obtained from transducers into desired form (analog or digital) an d
transmits it to the control room for its processing using computers .
Current i n
comparator
VTU - Switchgear and Protection 274 Carrier Aided Protection & Static Relay s VTU -Switchgear and Protection 275 Carrier Aided Protection & Static Relay s
11 .5 Basic Elements of a Static Rela y The main functions of such devices in the protection are ,
1. To produce final tripping signal to the circuit breaker .
The Fig. 11 .7 shows the block diagram of a static relay indicating its basic elements .
2. To produce signals to perform supplementary functions such as alarming ,
Feed element D .C . powe r suppl y
intertripping etc .
3. To act as intermediate switching stages in a complex protection scheme .
b. Critical Measuring Function :
Output Trippin g This device is a sort of on-off controller . It activates when the input signal reaches t o
Input Measurin g elemen t
element element amplifie r circuit some critical level decided by the protection scheme . Such a device is shown in the Fig .11 .9 .
Relayin g
quantity
Rectifier Comparator Transistor a s
an amplifier Input Instantaneou s Instantaneou s
R critica l noncritica l
Fig. 11 .7 Block diagram of a static rela y
11 .5 .1 Input Elemen t
Fig. 11.9 Instantaneous critical functio n
The relaying quantity can be the output of C .T. or P .T . or it may be the output of a
transducer or it may be combination of various signals . Thus an electronic circuit such a s Thus when input R is greater than some critical value P, it operates . While for reset ,
rectifier is required as an input element to get the input signal in a convenient form befor e input R must be less than kP (k 1) .
applying it to a measuring element . Some mixing circuits such as op-amp adder may also b e It has only one output and switching gain need not be high . The output of such device
required as an input element . then can be connected to instantaneous noncritical to obtain multiple outputs .
The various requirements of critical function devices are ,
11 .5 .2 Measuring Elemen t
This is the heart of the static relay . It compares the output of an input element with a se t 1.High accuracy.
value and decides the signal to be applied to the output element which ultimately drives th e 2. Long term consistency .
tripping circuit . Thus measuring element is a deciding signal generator . 3. Fast and reliable operation .
Measuring element can be classified as , 4. High controllable reset ratio .
1. Single input devic e c. Definite or Fixed Time Function :
2. Two input device This is nothing but a delay function element .
3. Multi-input devic e T Itproduces a define time delay between its inpu t
The single input devices, depending on the protection and control schemes are furthe r and the output . The delay may be provide d
Fixe d between the application of input and activatio n
classified as , time Output
Input delay signa l of output or between removal of input and j
a . Noncritical Repeat Function (All or Nothing Relay) : resetting of output. It is shown in the Fig .
R
As the name suggests, these device s
are completely unenergized or The input is noncritical type i .e . either i?r o
Many energized much higher than the Fig . 11 .10 Definite time functio n or too high than the marginal requirement .
Input Instantaneou s outputs Practically charging time of a capacitor is
R noncritical (contracts) marginal condition. required, to produc e controlled to obtain fixed time delay .
very fast response It can be represente d
as shown in the Fig . 11.8 . The input R is d.Input Dependent Time Function :
Fig. 11 .8 Noncritical repeat function either zero or too higher than th e This function depends on the input characteristics and decides the time accordingly .
marginal operating level . Such devices The common form of input dependent time function characteristics is ,
are instantaneous with response time less than 20 ms . The switching power gain associate d t = f(Rn ) where R = inpu t
with them is generally 10 3 . Such devices have multiple output contacts .
and n = negativ e
Carrier Aided Protection & Static Relay s VTU -Switchgear and Protection 277
VTU - Switchgear and Protection 276 Carrier Aided Protection &Static Relays
The function and its characteristics are shown in the Fig . 11.11 . 11 .6 .1 Advantages of Static Relay s
The various advantages of static relays are ,
t 1. The moving parts are absent . The moving parts are present only in the actua
l
tripping circuit and not in the control circuit .
2. The burden on current transformers gets considerably reduced thus smalle
Inpu t Input r
dependen t C.T.s can be used .
R time functio n i -R 3. The power consumption is very low as most of the circuits are electronic .
4. The response is very quick .
Fig . 11 .11 Input dependent time functio n
5. As moving parts are absent, the minimum maintenance is required
As n is negative, as the input increases the operating time decreases . So operating time i s . No bearing
friction or contact troubles exist .
inversely proportional to some power of the input . The examples of such relays are invers e
definite minimum time lag overcurrent and earth fault relays . 6. The resetting time can be reduced and overshoots can be reduced due t
o
The two input devices are very common such as comparators, level detectors etc . whil e absence of mechanical inertia and thermal storage .
multiple input devices are extension of two input devices to extend the range o f 7. The sensitivity is high as signal amplification can be achieved very easily .
characteristics . 8. The use of printed circuits eliminates the wiring errors and mass production i
s
possible.
11 .5 .3 Output Elemen t
The signals obtained from the measuring element are required to be amplified befor e 9. As electronic circuits can be used to perform number of functions, the wid
e
applying to the tripping circuit . Thus output element is an amplifier . Sometimes this range of operating characteristics can be obtained, which almost approach t o
element not only amplifies the signals but multiplies them or combines them with othe r ideal requirements .
signals to delay them . 10. The low energy levels required in the measuring circuits make the relay
s
smaller and compact in size .
11 .5 .4 Feed Element
The measuring element uses electronic circuits consisting transistors, diodes etc . The 11. The testing aid servicing is simplified .
output element uses transistor as an amplifier . All these components, circuits alongwith th e 11 .6 .2 Limitations of Static Relay s
tripping circuit require d .c . supply for the proper functioning . The feed element provide s
the d .c . voltage required by the various elements . Inspite of various advantages, the static relays suffer from the following limitations ,
1. The characteristics of electronic components such as transistors, diodes etc
s . are
11 .6 Comparison of Static and Electromagnetic Relay temperature dependent. Hence relay characteristics vary with temperature and
ageing.
The conventional electromagnetic relays use the moving parts such as an armature, dis c
e
etc . Thus they are bulky in size . These relays are robust and highly reliable . These ar ' 2. The reliability is unpredictable as it depends on a large number of smal
l
subjected to differential forces under fault conditions and hence required to have delicate components and their electrical connections .
setting of small contact gaps, special bearing arrangements, clutch assemblies etc . Thu s 3. These relays have low short time overload capacity compared t
there are lot of manufacturing difficulties and problems related to mechanical stabilit y electromagnetic relays .
o
associated with electromagnetic relays . The current and potential transformers ar e
subjected to high burdens in case of electromagnetic relays . 4. Additional d .c. supply is required for various transistor circuits .
The static relays are commonly using the transistor circuits and called transistor relays . 5. Susceptable to the voltage fluctuations and transients .
This is because transistor can be used as an amplifying device as well as a switching device . 6. Less robust compared to electromagnetic relays .
Hence any functional characteristics as per the requirement can be obtained by the static i
Now a days effect of temperature on the semiconductor devices can be compensated b y
relays . The transistor circuits can perform functions like summation, integration, compariso n careful design of the circuits .
etc.
278 Carrier Aided Protection & Static Relays VTU -Switchgear and Protection 279 Carrier Aided Protection &Static Relay s
VTU -Switchgear and Protection
11 .8 Static Time Current Rela y
11 .7 Semiconductor Devices used in Static Relay s
The various electronic components, devices and circuits which are commonly used i n This is nothing but instantaneous overcurrent relay . The Fig. 11 .12 shows the bloc k
static relays are , diagram of static time current relay .
1. Semiconductor diodes : This includes the conventional p-n junction diode, zene r
diode, avalanche diode and the circuits using these diodes such as rectifiers, regulators , Fro m
Inpu t
Overloa d
C .T. Rectifie r Timin g
references etc . summation ---►
wit h unit leve l Leve l Amplifie r
C .T. circui t detector filte r
detector
2.Transistors : This includes bipolar junction transistors (BJT) and field effect transistor s filter
(FET) . The transistors are used as amplifiers or as switches in the static relays . The direc t
coupled amplifiers using transistors are also used in the static relays .
3. Unijunction transistor : The device UJT having negative resistance characteristics i s Trippin g
often used to obtain relaxation oscillator, the output of which is used to trigger SCR . circui t
4. Thyristor family : This includes various two and three terminal and four laye r
electronic devices such as silicon controlled rectifier (SCR), triac, diac, silicon controlle d
Fig. 11 .12 Block diagram of time current static relay
switch (SCS) . Such devices are used in static relays to obtain high speed switchin g
characteristics . The secondaries of line C .T .s are connected to the summation circuit. The output of
summation C .T . is given to the input C .T . The input C.T. is called auxiliary C .T. which has
5. Logic circuits : Most of the relays are bistable devices i .e. they are operated in tw o taps on the primary for selecting the required pickup and current range . Then the output o f
stable states either ON or OFF . The logic circuit also has two states high i .e. ON and low i.e. auxiliary C .T . is rectified and smoothened . It is then applied to overload level detector an d
OFF . Hence logic circuits play an important role in the static relays . RC timing circuit . When the voltage across the timing capacitor reaches to a critical valu e
6.Filter circuits : The RC and LC filters are also used in static relays after rectifiers t o then it triggers the level detector . The output of the level detector is amplified as per th e
obtain smoothing of d .c. voltage generated . To obtain fast smoothing instead o f requirement and given to the tripping circuit . This operates the output device . The chargin g
conventional capacitor filter, the phase splitting before the rectification is used in stati c of capacitor in a timing c ircuit is achieved by a voltage derived from CT current. This voltag e
relays. is obtained across a nonlinear resistor by passing rectified current through it . The proper
7. Multivibrators : The various multivibrators using transistors are used to produc e selection of nonlinear resistor and RC timing circuit allows to obtain desired shape of tim e
square waveforms in static relays . The diode clippers also can be used to obtain squar e current characteristics of the static relay .
waveforms.
The current at which the level detector trips is called threshold current denoted a s
8.Time delay circuits : The variety of time delay circuits such as delay lines, RC circuits ,
timer circuits, resonant circuits using transistors, thyristors and ICs are used in static relays . I threshold . Thus for an overcurrent relay ,
Depending upon the requirement of time delay, the particular circuit is chosen . The delay when I;n < 'threshold , level detector does not trip
lines are used for shorter delays while RC charging and discharging circuits are used fo r when Tin 'threshold' level detector trip s
longer delays . The time delays of the order of micro secs to hours can be achieved using suc h
time delay circuits . 11 .8 .1 Static Time-Current Characteristic s
9.Level detectors : In static relays, it is necessary to detect the operating levels of variou s The time-current characteristics is inverse type of characteristics and given by th e
signals and used it to produce the necessary actuating signals . The level detector circuit s expression,
using the diodes, rectifier and RC elements are commonly used in static relays . t = K(TMS)
10.Analog circuits : The op-amp available in IC form is very common in building analo g In -In
circuits such as adder, subtractor, differentiator, integrator, inverting amplifier , where t = Time of operation in second s
noninverting amplifier etc. Op-amp also can be used to obtain the circuits like zero crossin g
detector, Schmitt trigger etc . All such circuits are used in various types of static relays . K = Design constant of relay
TMS = Time multiplier settin g
I = Tap current multiplie r
Ip = Multiple of tap current at which pickup occur s
n = Characteristic index of relay
VTU -Switchgear and Protection 281 Carrier Aided Protection &Static Relays
VTU -Switchgear and Protection 280 Carrier Aided Protection&Static Relays
The shape of the characteristics and degree of inverse nature is standardized . Accordin g
to British standards ,
For standard inverse characteristics (IDMT) , a v).
K x (TMS) = 0.14, n = 0 .02 and I p = 1 A 0
o
o
a) MNVV
m
E E
. g a_ Nei
N
Fig . 11 .13 Inverse time-current characteristics
0.o
It can be seen that the curve is asymptotic about both the axes . Due to this, there exists
minimum pickup current below which relay can not be operated . While there exist s o
o
minimum definite time of operation below which it can not be reduced . 0
1 U
N
11 .8.2 Static Instantaneous Overcurrent Rela y m
U
The detailed circuit diagram of instantaneous static overcurrent relay is shown in th e 4
Fig. 11 .14. (See on next page .)
The auxiliary transformer gives output voltage proportional to the fault current . The
main circuit is protected from the voltage surges by using R1 C 1 circuit at the input . This is
surge protector . The output voltage from the transformer is then rectified and smoothene d -------------- -
m S
m ô
using capacitor filter C 2 . The level of this voltage is compared with the voltage level decide d ma)
by zener diode ZD1 . This zener limits the rectified voltage to a safe value though the faul t Û u7 ) a
ô
current is very high . Part of this voltage, as decided by the potentiometer P is compared with ------------------ -
the breakdown voltage of another zener diode Z D2 . When the rectified voltage is greater
than voltage of Z D2 , the transistor Q 1 conducts . This increases drop across R 2 due to which
Q 2 conducts . This energizes the trip coil Tc of the relay . When the trip coil opens, it develop s
high reverse voltage (back e.m.f.) . To protect Q 2 from such a high back e.m.f., a diode D is
connected across the trip coil . With the help of potentiometer P different pick up values can xw 00000000 ,-I
= N
CII
be obtained . Q *
Under normal conditions, Q l gets biasing from d .c. supply applied through R4 and P2
11 .8 .3 Inverse Time-Current Rela y and conducts . Hence capacitor C is short circuited . When fault current exceeds the pick up
The Fig . 11 .15 shows the circuit diagram of static inverse time-current relay . value set by the potentiometer P2 and selector switch then the transistor Q 1 becomes OFF .
. The capacitor C starts charging through R3 and P1 by the voltage developed across Rl . Thi s
C.) a.
charging time varies as per the severity of the fault . More severe is the fault, more is th e
Cu,
o voltage developed across R1 and less is the time for charging capacitor C to a critical level .
When voltage across the capacitor reaches to a predetermined level set by th e
o
C
0 potentionmenter P3 then the transistor Q 3 conducts . This energizes the trip coil and th e
oooo, circuit breaker opens . The diode D protects the transistor from the high reverse voltage .
o"
Thus more is the fault current, less is the time required to operate relay hence it is invers e
time-current relay.
I-o
11 .9 Directional Static Overcurrent Rela y
The directional relay is nothing but a directional power relay which operates when th e
power in the circuit flows in a particular direction. Thus it requires to sense the syste m
voltage as well as the system current .
The Fig . 11.16 shows block diagram of the directional static overcurrent relay .
Input I
A o-0-
Auxiliary
CT
Directiona l
uni t Tri p
Phas e circuit
go ► shifter
O
Input V
Fig . 11 .15
VTU -Switchgear and Protection 284 Carrier Aided Protection&Static Relay s VTU -Switchgear and Protection 285 Carrier Aided Protection & Static Relay s
The static directional overcurrent relays are very sensitive and directional unit can b e Bridge rectifie r
made reliable down to 1% of the system voltage . comparato r
The various types of derived voltages S l and S, for amplitude and phase comparator s AND function :
to obtain particular characteristics are given in the Table . 11 .1 . The block schematic of AND function and the truth table is shown in the Fig . 11 .21. In the
Distance relay
truth table 1 indicates high while 0 indicates low . AND is nothing but a multiplication .
N . Amplitude comparator Phase comparator
scheme
Operating Restraining Operating Restrainin g A B C=AAND B
L Directional 0 0 0
1 L V V IL V Ao
- -L
ZR
IL +- IL 0 1
ZR ZR AN D C=A• B 0
Bo
1 0 0
2 IIL I VL I L ZR- VL
IL Z R +V L Impedanc e
1 1 1
ZR
Table 11 .1 +V
o
The characteristics of various schemes as obtained from above Table 11 .1 are shown i n
the Fig. 11 .20. o A•B=AAND B
Ao Ia Ao Bo
7
Bo K o C=A•B 1
(a) Diode AND (b) AND with relays
Fig. 11 .22
OR function :
The block schematic of OR function and the truth table is shown in the Fig . 11 .23 . The OR
Fig . 11 .20
function is nothing but an addition.
The static distance relays are used popularly for protection of medium and lon g
transmission lines, parallel feeders and interconnected and T connected lines .
A B C=AOR B
11 .12 Microprocessor Based Relay 0 o 0
Ao
0 1 1
Let us see the relay logic which is very important in understanding the microprocesso r Bo
OR o C=A+ B
based relay . The relay can be ON or OFF i .e . it has two stable states . Similarly output of a 1 0 1
logic function is ON i.e . high or OFF i .e. low. The three basic logic functions are, 1 1 1
1. AND 2 . OR 3. NOT
(a) Block schematic (b) Truth tabl e
The diode OR gate is shown in the Fig . 11 .24 (a) while the OR operation using relays i s All these functions can be achieved using transistors also . It is called .transistor transisto r
shown in the Fig . 11 .24 (b) . logic (TTL) .
The Fig . 11 .26 shows the block diagram of microprocessor based relay .
Ao DI o C=A+B
Circui t
o A+ B breake r
CT
Lin e
Ao a !i ce
c w'
Tripping signa l
ME
D/A converte r
C =A
(2 9 1 )
80 Chemical properties 52 Current bias
Basic short circuit test 181 Diffused ar c 59
139 Chopped current 60 Current chopping
Basic trip circuit operation 26,57 Diffusion 33
200 Chopping level 60 Current curves 147
Bearing currents Digital computers 11 8
58 Circuit breaker ratings 75 Current differential relay
Bellows 167 Directional characteristics 16 1
169 Circuit breaker time 120 Current interruption in A .C . circuit breakers 9
Biased beam relay Directional element 16 0
202 Circuit breaker 1,114 Current interruption
Biased differential protection 92 Directional impedance relay characteristics 18 1
201 Circuit breaking chamber 70
Biased differential protection scheme Current rating of fuse 95 Directional impedance relay 18 0
50 Circulating current principle 213,245 Current setting
Blow out coils 124 Directional induction type overcurrent relay 15 9
118 Classification of circuit breakers 41 Current surges
Breaker backup protection 197 Directional power relay 15 8
124 Classification of distance relays 190 Current transformer
Breaker time 127 Disadvantages of a HRC fuse 10 7
94 Classification of protective relays 122 Current transformers
Breaking capacity cartridge fuse 142 Disadvantages of fuse 10 3
98 Clearing 1 2t 98 Current zero interruption
Breaking capacity 31 Discrimination 110,11 9
11 Coefficient of expansion 99 Current zero method
Breaking current 3 Distance protection 18 1
80 Commissioning tests 81 Current zero phase
Breaking test 35 Distance relays 17 6
155 Complementary solution 6
Bridge socket Current-time characteristics 145 Distance time impedance relay 19 2
90 Complete solution 7
Brown Bover i ' s synthetic testing circuit Cut-off Characteristics 105 Distributors 1
245,255 Composite testing station 82 Cut-off current
Buchholz relay 96,105 Double blast type 45
62 Compressed air circuit breaker 42 Cut-off characteristics
Bulk oil circuit breakers 96 Double break oil circuit breaker 63
257 Compressed air system 47 Cylindrical rotor
Bushing puncture 199 Double frequency transient 16
Conduction of heat 33
Double induction loop structure 15 3
C Conservator 256 D
Double'pressure type S F 6 circuit breaker 56
Constant slope percentage differential relays 17 0
Cable charging current switching test 80 D .C . circuit breaking 3 Double winding structure 15 2
Contact corrosion 57
Cancelling current 17 D .C . component 6 Doubling effect 77
Control cabinet 14 0
Capacitive current switching 25 D .C . converter 83 Doubly wound armatures 21 3
Control signal 44
Capacitive current switching tests 80 Dashpot 148 Driving torque 13 9
Control source 118
Capacitive currents 11 Dead spot 116 Drop-out fuse 94
Control spring 153
Capacitor banks 11 Definite distance type impedance relay 191 Dropout or reset 12 4
Convergent divergent nozzle 54
Capacitor switching 60 Degree of ionisation 2
Cooling of arc 34 E
Capacitor 85 Degree of overloading 198
Cooling system failure 20 0
Carbon tetrachloride solution 109 Deionising force 27 Earth fault protection
19 6 148,24 0
94 Cooling systems Deionization
Cartridge fuse 27,32 Earth fault relays 21 4
Copper band 151
Cassie's theory 36 Demagnetizing armature reaction 15 Earth fault 126,24 4
Core bolt insulation failure 257
Cathode spots 61 Demagnetizing effect 83 Earth leakage induction type relay
256 15 4
2 Core heating Development tests
Cathode 81 Earthing resistance 20 5
Critical current tests 80
Central control 118 Dielectric medium 32 Eddy currents
53 15 3
118 Critical pressure Dielectric properties
Centrally controlled backup protection 52 Edison 92
Cross blast type 44
Centrally co-ordinated backup protection 118 Dielectric strength 11 Effect of armature reaction 15
Cross differential principle 21 3
Characteristics of HRC fuse 104 Dielectric stress 11 Effect of earth resistance 20 6
Cross jet explosion pot 67
Characteristics 106, 155 Differential operating current 202 Electric discharge 31
Cross-section of arc 2
Chemical charge 109 Differential relay 123 Electrical bias
153 12 1
Cup type rotor
(292) (293 )
Electrical breakdown in high vacuum 58 Free path movement 3 I Length of arc 2
Electrode gap 52 Frequency of transient recovery voltage 13 Lengthening the arc 34
Impedance rela y 176
Electrodes 31 Functions of protective relaying 114 Lenz ' s law 4
Impedance Z 176
Electro-dynamic forces 82 Fuse constant 101 Lightning surges 60
Impedanc e 176
Electromagnet 144 Fuse element material 98 Line of defence 11 7
Impulse excitatio n 82
Electromagnetic attraction relays 144 Fuse element of HRC fuse 107 Liquid director 109
Incipient fault s 245,255
Electromagnetic attraction 145 Fuse low 101 Liquid fuse 94,10 9
107 Increasing slope percentag e Liquificotion temperature
Electromagnetic force 146,147 Fuse link 51
95 differential relays 170 Load capacitance
Electronegative gas 51 Fuse wire 24
Indirect testin g 86 Load flow
Electronegativity 54 Fuse 92 11 8
Indoor circuit breake r 42
Element testing 86 Fusing current 95 Loss of excitation characteristics 21 5
Induction cup type rela y 152
Energy balance theory 35,36 Fusing element 92 Loss of excitation 19 9
Induction generato r 199 Loss of oil
Energy meter 148 Fusing factor 95 25 7
Induction moto r 148 Loss of synchronism
Equivalent generator impedance locus 21 5 19 9
G Induction type negative sequence rela y 220 Low oil circuit breaker
Eutectic alloy 99 69
Induction type relay s 148 Low resistance interruption 31
Excitation systems 196 Gas operated relay 124
Initiation of arc 2 Low resistance method
Exponentially decaying component 6 Generating stations 1 3
Instrument transformers 12 7
Expression for restriking voltage 18 Generator faults 196
Insulating housin g 58
Expulsion fuse 93 Generator protective scheme 126
Insulation faul t 256
Externally generated pressure breaker 69 Gravity closed circuit breaker 42 Magnetic blast circuit breaker 42
Inter-locking i s 108
Externally generated pressure oil circuit Gravity opened circuit breaker 42 Magnetising current 23
Internal faults 244
breakers 62 Magnetising currents 57
H Interrupting mediu m 42
Extinction chamber 46 Magnetizing current compensation 25 3
Interruption of capacitive current s 24
Extinction voltage 5 Magnetizing current inrush 25 2
Hand reset multicontact auxiliary relay 204
Interruption of low magnetizing curren t 25
Harmonic blocking 253,25 4 Magnitude relays 14 8
F Inter-turn fault s 197
Harmonic restraint 253 Main contacts 49
Inverse laplace transfor m 29
Failure of prime mover 199 Heat content property 52 Maintenance of an arc 2
Inverse time characteristic s 155
Fault clearing time 120,124 High resistance arc interruption methods 33 Making current 11
Ionization by collisio n 32
Field emission 2,32 High resistance interruption 31,48 Making device 85
Ionization of gases 32
Field type testing station 82 High resistance method 3 Making test 80
Flap valve 255 Horizontal break circuit breaker 42 Maximum torque angle 16 3
L
Flemings left hand rule 150 Hot spo t 58 Measurement of insulation resistance 82
Flow 118 94, 103 Laboratory type testing statio n 82 Measurement of resistance 80
HRC fuse
Force blast oil circuit breakers 62,68 Laplace transform equivalen t 28 Measurement of travel 81
HRC fuse with tripping device 108
Formation of an arc 1 Largest machin e 206 Mechanical operation tests 80
Hum 147
Frame leakage protection 254 198 Layout of a short circuit testing statio n 82 Mechanical stresses 41
Hydraulic generators
Free electrons 32 Leakage reactance 84 Mechanical tests 80
Hydrogen circuit 200
(294) (295)
Melting time 97 Oil immersed transformers 24 5 Photoemissio n 32 Prospective voltage 27
Mercury switch 25 5 Oil-blast fus e 94 Physical properties 51 Protection against interturn faults 21 2
Merl-price protection - star-sta r Oil-break circuit breaker fus e 94 Pickup curren t 14 5 Protection against loss of excitation 21 5
transformer 247, 24 8 Oil-expulsion fus e 94 Pickup torqu e 17 6 Protective covering 11 6
Mea-price protection 20 2 Open circuit s 24 4 Pickup valu e 124,20 1 Protective relay 12 4
Metal clad switchgear 25 4 Open fuse 94 Picku p 124 Protective relaying scheme 11 4
Metal enclosed switchgear 61 Opening tim e 41 Pilot cable capacitance s 16 9 Protective relaying 11 4
Methods of backup protection 11 8 Operating coi l 185,20 1 Pilot cable s 16 8 Protective scheme 1
Mho relay 18 6 Operating sequence tests 80 Pilot wire s 202,25 1 Protective system 12 6
Mho 17 6 Operating time-breaking current Plain break oil circuit breake r 62 Protective zone 115,11 6
Millivolt drop test 80 characteristic s 69 Plain explosion po t 66 Puffer cylinder 55
Minimum oil circuit breaker 62,6 9 Operating torqu e 17 6 Plain impedance rela y 18 0 Puffer principle 55
Modification in air blast circuit breaker 46 Operation tim e 12 3 Plaster of pari s 10 4 Pulsating component 14 8
Moment of inertia 15 3 Opposed voltage metho d 171 Plug bridg e 12 4
Moving iron 14 6 Oscillogra m 9 Plug setting bridg e 15 4
Multipoint switch 14 0 Out of phase switching test s 80 Plug setting multiplie r 12 5 Quartz sand 94
Outdoor circuit breake r 42 Plunge r 109,122,14 4
Overfluxin g 24 4 Pneumatic valve 47 R
Negative phase sequence filter 22 3 Overheatin g 24 3 Polarizing coi l 18 5 Radial blast type 45
Negative sequence currents 198,22 1 Overload margi n 56 Polarizing windin g 18 6
Rate of rise of TRV 16
Negative sequence relays 21 6 Overloadin g 19 8 Pole slipping conditio n 19 9
Rated duration of short circuit 76
Negative torque region 17 9 Over-reach 12 6 Positive sequence currents 22 0 Rated insulation level 75
Negative torque 17 6 Overspeedin g 19 8 Positive torque region 17 9 Rated operating sequence 78
Neutral earthing 16 Overvoltag e 199 Positive torqu e 17 6 Rated peak withstand current 77
Neutral earthing connection 20 3 Possible transformer faults 24 3
P Rated pressure of compressed gas 79
Neutral molecules 3 Post arc phas e 35 Rated short circuit breaking current 76
Non-automatic circuit breaker 42 Panel mounted circuit breake r 42 Post zero resistanc e 36 Rated short circuit making current 77
Nondirectional element 16 1 Parallel arcs 59 Potential transformers 14 2 Rated TRV for terminal faults 78
Nondirectional induction type Parallel current injection metho d 87 Power frequency voltage test s 81 Ratio change 25 1
overcurrent relay 15 4 Particular solutio n 6 Power frequency voltag e 1 1
Ratio relays 17 6
Non-homogeneous differential equation 5 Paschen's la w 52 Power shortag e 19 6 R-C surge suppressors 19 9
Non-ionized gas 32 Peak restriking voltag e 16 Power swing s 18 0 Reach 12 6
Non-puffer type SF6 breaker 53 Percentage differential protectio n 24 5 Pre-arcin g 25 Reactance relay 18 4
Normal service voltage 10 5 Percentage differential rela y 16 9 Pre-arcing let 98 Reactance 123,17 6
Nozzle 45 Permanent magnet moving coil rela y 12 4 Pre-arcing tim e 97 Reactive power surges 83
Phase facto r 20 Primary protectio n 11 7 Reactor current switching tests 80
Phase fault 12 6 Prime movers 19 6
Reactors 84
Phase to earth fault s 194,19 7 Principle of an electromagnetic induction 12 2
Oil blast explosion pot 68 Recombination 33
62 Phase to phase fault s 194,197,24 4 Proper discrimination 11 1
Oil circuit breakers Recovery rate theory 35
Phase unbalance relays 21 6 Properties of S F6 ga s 51
Oil decomposition 65 Recovery strength characteristics 61
Prospective current 96,105
(2 97 )
Small inductive current breaking tests 80 Thermal relay 12 3
Recovery voltag e 11, 14, 64,10 5 s Solenoid and plunger type relay 145 Thermionic emission 2
Rectifier rela y 12 4 Solenoid 122 Three phase faults
Saturation effect 14 6 194
Refractory material s 60 Speed 120 Throat 66
Saturation of C .T .s 20 5
Reigintio n 1 1 Spiral spring 155 Through faults 24 4
Schematic arrangement of admittance relay 18 7
Relay backup protectio n 11 8 Splitting of arc 34 Time - current characteristic 99,10 5
Schematic arrangement of reactance relay 18 4
Relay coi l 13 9 Spring loaded jaw 155 Time delay 12 4
Schwartz and James 10 2
Relay tim e 120,12 4 121 Time lag 14 8
57 Stability
14 2 Sealing problem
Relay with break type contac t Static devices 243 Time setting dial 15 5
Sealing relays 12 4
Rela y 114,13 9 Static relay 124 Time 12 0
Secondary emission at contact surface 32
Relays based on timin g 12 3 Stator core 197 Time/P .S .M . curve 12 5
Selection of HRC fuse 10 8
Relays with make type contact 14 1 Stator faults 196 Time-current characteristics 15 5
Selectivity 11 9
Reliability test s 81 197 Time-setting multiplier 12 6
Self blast oil circuit breakers 62 Stator inter-turn faults
Reliabilit y 11 9 Steady state reactance 9 Top chamber 70
Self compensated explosion pot 67
Remote backup protectio n 11 8 Steady state 9 Torque equation 149,17 7
Self generated pressure oil circui t
Requirements of circuit breake r 40
Steam turbine blades 199 Total operating time 98
breaker 62,6 6
Reset torqu e 17 6 Striker fuse 94 Traction system 48
Semienclosed fuse 93
Reset valu e 12 4 Subtransient reactance 8 Transient reactance 9
Sensitivity 12 1
Residual flu x 25 2 Subtransient state 9 Transient recovery voltage 1 1
Sequence switch 83,8 5
Resistance switchin g 27 Sulphur hexafluoride (S Fb ) circuit breaker 51 Transient state 9
Series current injection method 89
Resistor s 85 70 Transients 120,14 8
Series tuning circuit 18 7 Supporting chamber
Restraining coi l 185,20 1 199 Transmission line protection 18 1
Shaded pole type induction relay 15 0 Surge arresters
Restraining torqu e 139,17 6 Surge capacitors 199 Transmission line 1,17 6
Shading ring 15 1
Restricted earth fault protectio n 20 4 Switch fuse 94 Trial solution 6
Shaft distortion 19 7
Restrik e 12 Switch 92 Trip circuit 126,13 9
Short circuit generator and drive motor 83
Restriking voltag e 1 1 92 Trip coil 40
Short circuit in R- L series circuit 5 Switchgear
Reverse power protectio n 19 9 199 Tripping schemes 14 0
Short circuit test layout 82 Synchronous generator
Rewirable fus e 93 Synthetic test circuits 87 Tripping springs 72
Short circuit testing plants 82
Rotating magnetic fiel d 153,19 8 Synthetic testing 86,87 Truboalternators 19 9
Short circuit transformers 84
Rotational torqu e 15 5 Turbine governor 19 8
Short line fault tests 80
Rotor earth fault protectio n 198,21 3 T Turbogovernor 19 8
Short time current test 80
Rotor faults 19 7 Turbulator 70
Shunt resistance 28 Tap change 251
Rotor stamping s 19 8 Type tests 80
Shunt-wire 10 9 Terminal-bushings 62
Rotor temperature indicators 19 8 Typical relay circuit 14 0
Single blast type 45 Test cubicles 85
Routine tests 80
Single break oil circuit breaker 62 Testing authorities 80
RRRV 16
80
U
Single frequency transient 15 Tests of temperature rise
Rupturing capacity 10 8
Single phase short circuit test 80 Thermal conductivity 60 Unbalanced loading 19 8
Russel l 102
Single phasing 10 9 Thermal electron emission 2 Under-reach 12 6
R-X diagra m 215,178,21 5
Single pressure puffer type SF6 C .B . 55 Thermal emission from surface of contacts 32 Undervoltage trip coil 14 3
R-X plane 178
Sinusoidal 7 Thermal Ionization 32 Unit protection 126
Slepian's theory 35
(299 )
(2 9 8 )
Unit testing 86
Universal relay torque equation 164
Unmatched characteristics 25 1
Unprotected 20 6
Unrestricted earth fault protection 20 8
Unsymmetrical faults 19 9
r-
V
V shaped insulators 46
Vaccum circuit breakers 57
Vacuum chamber 58
Vapourization temperature 99
Voltage balance differential relay .l71
Voltage gradient 2
Voltage rating 98
Voltage regulators 19 6
Voltage restrained directional relay 18 7
Voltage restrained overcurrent 17 6
Voltage stress 27
Voltage tests 81
Voltage-current characteristics 3
w
W . H . Preec 10 1
Watthour meter type induction relay 15 2
Weak link 10 9
Winding faults 24 4
Z
Zero point extinction 35
Zero point interruption technique 9
Zero sequence current transformer 24 0
Zero torque line 16 2
Zone-refined copper 61
(3 0 0 )