MITSUBISHI GENSET MGS1400B-60Hz-480v
MITSUBISHI GENSET MGS1400B-60Hz-480v
MGS1400B
POWER RATING (0.8 P.F.) MODEL CODE
STAND-BY 1420 kW 6S-7PC
PRIME 1280 kW 6P-7PC
Prime: Code: P
Applicable for supplying emergency power at varying load in the event of normal utility power interruption. 10% overload is
allowed.
Fuel stop power in accordance with ISO15550, ISO3046/1, JISB8002-1, DIN6271 and BS5514.
Overload: 10% allowed
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard
conditions.
Fuel rates: based on ASTM D975, BS2869 and on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg
(18,390 Btu/lb.) when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * For conditions of prime power (P.R.P.) and additional rating requirements, please consult your nearest Mitsubishi
MGS dealer.
Bore mm 170
Stroke mm 180
Displacement L 49
Piston speed m/sec. 10.8
Compression ratio 13.5
Lubricating oil capacity L 180
Coolant capacity without radiator L 125
Coolant pump external resistance m water 5.0
Coolant pump flow rate L/min 1850
Cooling fan airflow rate m3/min 2040
Cooling fan air flow restriction kPa 0.1
Ambient air temperature ℃ 40
Allowable exhaust back pressure kPa 6.0
Exhaust flange size (internal diameter) mm 300
STAND-BY PRIME
1420 kW 1280 kW
Gross Engine Power* kWm 1494 1353
Brake mean effective pressure MPa 2.1 1.9
Regenerative absorption kW 144 144
Noise Level at 1 m dB(A) 111 110
(excluding: intake, exhaust & fan)
Fuel consumption load 100%* L/hr. 394 350
Fuel consumption load 75%* L/hr. 294 267
Combustion air inlet flow rate m3/min 135 120
Exhaust gas flow rate m3/min 356 316
Exhaust gas temperature ℃ 530 520
Heat rejection to coolant kW 981 872
Heat rejection to exhaust kW 1282 1114
Heat rejection to atmosphere from engine kW 118 105
Heat rejection to atmosphere from generator kW 75 66
* WITH FAN basis.
Mounting
Fabricated cubicle mounted on individual bracket with anti-vibration isolator
Electrical Design
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive. The optional
interface can provide real time diagnostic facilities.