0% found this document useful (0 votes)
123 views

Emco Eaom 210 Ats Gen Set Module FL

The document is a user manual for an automatic transfer and switching unit for diesel/gas generators. It describes installation, operation, programming and fault finding of the unit. Sections include introduction, installation, front panel operation and programming, commissioning, normal operation, troubleshooting, specifications and a block diagram.

Uploaded by

Building Energy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views

Emco Eaom 210 Ats Gen Set Module FL

The document is a user manual for an automatic transfer and switching unit for diesel/gas generators. It describes installation, operation, programming and fault finding of the unit. Sections include introduction, installation, front panel operation and programming, commissioning, normal operation, troubleshooting, specifications and a block diagram.

Uploaded by

Building Energy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 155

 

EAOM-210 FL
AUTOMATIC TRANSFER & SWITCHING UNIT
FOR DIESEL/GAS GENERATORS
User Manual

EMKO ELEKTRONIK A.S.


Demirtas Org. San. Bolg.
Karanfil Sk. No: 6 TR
16369 Bursa / TURKEY

Phone : +90 224 261 1900


Fax : +90 224 261 1912
Url : www.emkoelektronik.com.tr
e-mail : [email protected]
  [email protected]

EAOM-210 FL.eng / ver 0.7


Pages 1 / 154
 

Section 1 Introduction .............................................................................................. 4

Section 2 Installation................................................................................................ 6

2.1 Unit Configuration....................................................................................................... 6


2.2 Mechanical Installation ................................................................................................ 6
Figure 2.1 Front view Figure 2.2 Panel cut-out ................................................................................. 6
Figure 2.3 Side view. ............................................................................................7
2.3 Electrical Connections.................................................................................................. 7 
Figure 2.4 Rear view.............................................................................................8
Figure 2.5 EAOM-210 FL three phase connections schematic. ............................................................. 9
Table 2.1 Unit wiring ................................................................................................................................. 11
Table 2.2 Unit wiring description ............................................................................................................ 13

Section 3 Definition Of Front Panel And Programming ..................................................... 15

3.1 Front Panel Description...............................................................................................15


3.2 Programming Procedure ..............................................................................................17 
3.3 Accessing to the Operator Parameters............................................................................17 
3.3.1 Changing and Saving Operator Parameter Values .................................................................. 19
3.4 Accessing to the Technician Parameters .........................................................................21
3.4.1 Changing and Saving Technician Parameter Values .............................................................. 30
3.5 Programmable function definitions ................................................................................32
3.6 Pc Interface ..............................................................................................................86
3.6.1 Technical Specifications ............................................................................................................... 86
3.6.2 9 pin D connector/FCC68(4 pin) connection lead ................. Hata! Yer imi tanımlanmamış.
3.6.3 Installation Instruction ............................................................................... 86
3.6.3.1 Minimum system requirements.................................................................. 86
3.6.3.2 Installing EAOM-210 FL V00/SW ................................................................. 86
3.6.3.3 To Run EAOM-210 FL V00/SW communication software .................................... 87
3.6.4 Description ...................................................................................................................................... 89
3.6.4.1 Main Menu........................................................................................... 89
File Menu.................................................................................................................................. 89
Window Menu .......................................................................................................................... 89
Program Menu ......................................................................................................................... 90
Observation Menu ................................................................................................................... 91
Operator Parameters Menu ................................................................................................... 95
Technician Parameters Menu ............................................................................................... 96
Setting Menu............................................................................................................................ 98
Help Menu ................................................................................................................................ 99

Section 4 Commissioning ........................................................................................ 100

4.1 Manual operation..................................................................................................... 100


4.2 Auto Operation........................................................................................................ 101
4.3 Test Mode Operation ................................................................................................ 101

EAOM-210 FL.eng / ver 0.7


Pages 2 / 154
 

Section 5 Operation .............................................................................................. 102

5.1 Controls and Indicators ............................................................................................. 102


5.1.1 LCD Display Description ............................................................................................................... 102
5.1.2 Failure Indicators Description ...................................................................................................... 113
5.2 Mode transition ....................................................................................................... 114
5.3 Manual Start ........................................................................................................... 114
5.4 Manual Stop............................................................................................................ 114
5.5 Auto Operation........................................................................................................ 114
5.6 Test Operation ........................................................................................................ 115
5.6.1 Exercise Function ........................................................................................................................ 115

Section 6 Fault Finding .......................................................................................... 116

6.1 General .................................................................................................................. 116


6.2 Error Messages ........................................................................................................ 116
Table 6.1 Fault finding....................................................................................118

Section 7 Specifications & Ratings ............................................................................ 119

Section 8 Block Diagram ......................................................................................... 122

User Defined Parameter:........................................................................................ 123

List-1:......................................................................................................................... 123

EAOM-210 FL.eng / ver 0.7


Pages 3 / 154
 

Section 1 Introduction

The EAOM-210 FL provides for automatic transfer of a load from mains to generator in the
event of a mains failure. Intended for unattended operation, it is able to detect failure of 
any phase of the mains and to start and switch over to a generator if the mains voltage
goes outside pre-set limits. Both automatic and manual control is possible. A test mode is
also available which allows the generator to be run without taking the load.

The unit monitors generator operation and gives warning of any faults that are detected.
The unit monitors:

•  Engine speed
•  Engine Oil pressure
•  Coolant temperature
•  Fuel Level
•  Battery voltage
•  Charge generator voltage
•  Engine run time
•  Number of starts
•  Next maintenance
•  Mains volts (L1-N, L2-N, L3-N)
•  Mains volts (L1-L2, L2-L3, L3-L1)
•  Mains Hz
•  Generator volts (L1-N, L2-N, L3-N)
•  Generator volts (L1-L2, L2-L3, L3-L1)
•  Generator Hz
•  Generator kVA
•  Generator kW
•  Generator kVAr
•  Generator pf 
•  Generator kVAh
•  Generator kWh
•  Generator kVArh
•  Load Amps
•  Earth current (IEA)

It controls:

•  Engine fuel supply or engine stopping


•  Starter motor
•  Alarm horn
•  Automatic generator start and load transfer on mains failure
•  Mains Open, Mains Close, Generator Open and Generator Close contactors

EAOM-210 FL features a 128x64 Dot-matrix LCD display, including:

•  Mains volts (L1-N, L2-N, L3-N)


•  Mains volts (L1-L2, L2-L3, L3-L1)
•  Mains Hz
•  Generator volts (L1-N, L2-N, L3-N)
•  Generator volts (L1-L2, L2-L3, L3-L1)

EAOM-210 FL.eng / ver 0.7


Pages 4 / 154
 

•  Generator Hz
•  Generator kVA
•  Generator kW
•  Generator kVAr
•  Generator kVAh
•  Generator kWh
•  Generator kVArh
•  Generator pf 
•  Engine Rpm
•  Load Amps (IL1, IL2, IL3, IT)
•  Earth current (IEA)
•  Engine Oil pressure
•  Coolant temperature
•  Fuel Level
•  Battery voltage
•  Charge generator voltage
•  Real Time
•  Engine run time
•  Next maintenance hour
•  Next maintenance month
•  Error messages (if available)
•  Event Logs
•  Program parameters

The unit is extensively programmable through the front panel, with password protection on
two levels. Operational parameters can also be monitored and controlled from a PC via a
built-in RS232 port.

If the engine fails to start on the first attempt, further attempts are made up to a
programmed number of times or until successful.

If a fault is detected, the unit shuts down the engine and indicates the failure by flashing a
relevant fault LED.

Emergency stop input provide for remote control of the engine.

The user configurable inputs 4 and 5 can be programmed to perform 26 different functions.
Other four user configurable inputs can be programmed to perform 25 different functions.

Four user configurable relay outputs can be programmed for 93 different functions.

EAOM-210 FL.eng / ver 0.7


Pages 5 / 154
 

Section 2 Installation

Please read the following information before installing.


A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.

Before beginning installation of this product:


-  Disconnect all electrical power to the machine.
-  Make sure the machine cannot operate during installation.
-  Follow all safety warnings of the machine manufacturer.
-  Read and follow all installation instructions.

2.1 Unit Configuration

The unit can be programmed using the buttons and display on the front panel or EAOM-210
FL software. Refer to Section 3 Definition Of Front Panel And Programming for details.

2.2 Mechanical Installation

The unit is designed for panel mounting. Fixing is by four screw fixings. ( See Figure 2.1)
1. Insert the unit in the panel cut-out from the front.
2. Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws
to secure the unit against the panel.

During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you should be careful.
Installation parts of equipment should be tighten properly. The equipment can be
drop from mounting place reason of vibration if installation parts leave soft.

186mm
EAOM - 210 FL
FAILED TO START

LOW OIL PRESSURE

HIGH TEMPERATURE

RPM SPEED FAILURE

V VOLTAGE FAILURE

CHARGING FAIL

   m
   m    m
   m    8
   4    3
   4    1
   1

START
MAINS

PROG G STOP

ENGINE
RUNNING
LOAD

RESET OFF AUTO TEST MANUAL


TEST

204mm

Figure 2.1 Front view. Figure 2.2 Panel cut-out

EAOM-210 FL.eng / ver 0.7


Pages 6 / 154
 

Figure 2.4 Rear view.

This equipment does not contain any parts and material related to users. Only
qualified personnel and technician trained specially should work on this equipment. This
equipment contains dangerous voltage inner circuits for human life . There is severe
dangerous for human life on the case of unauthorised intervene.

EAOM-210 FL.eng / ver 0.7


Pages 8 / 154
 

  s
  y
  a   b  
   d   t   m  
   R   1   2   3   e  u  .
   O   L   L   L   N    3   s   p  o
  r   m  s
  u  n   f   a  r
   T    i   r   e
  e   l   g  g   t
   A    b   t   n  o  e
  a   i
   R   n   i
   t   r
   E    6   g  c   p  m
  a   i   e   a
   N    4   c   d  e  e  r
   l
  a
   E    t    h
   *
   I   a  s   t   p
   G    5
   4
   4    0
   4    1  l  e
  v
  e
   L
   3
   *
   4    1
   1   e
  r  u
  t  a
  r  e
   p
   m
  e
   T
   2
   4

   *
   2
   1    1   e
  r  u
  s
  s
  e
  r
   P l i   O
   4    4

  5    8
  4
  -
  t  u
   p
  t  u
   O
 .
  f  n
   o
   C
   A    3
   V
   0   5    7
  3
  -
  t  u
   p
  t  u
   O
 .
  f  n
   o
   C
   8    0    3
   3
   A
  ~
  5    6
  2
  -
  t  u
   p
  t  u
   O
 .
  f  n
   o
   C
   7   m    A    3
  u
  6
  -
   E
   S
   U
   F

   4
  1
  -
  t  u
   p
  t  u
   O .
  f  n
   o
   C
  r
   o  n
  r
   o
   H
   6    i
  m   1    3
  x
  5
  -
   E
   S
   U
   F    A
  6
  a    T
  4
  -
   E
   S
   U
   F
   5    M
  r    t  .    6
   1   6
  -
  t  u
   p  n
 I .
  f  n    C   A
   o    B
  o   u
   t   +
  c    O    7
  a  e  y    1
   0
  5
  -
  t  u
   p
  n
 I .
  f  n
   o
   C
  r
   o .   p   m
  e
  t  h   g
 i   H
 .   t
   3    A   n  n  s   a
  o   l    8   4
  e  o   l
  5
  e    1   -
  1
  1
  -
   E
   S
   U
   F

   9
  t  u
   p
  n
 I .
  f  n
   o
   C
  r
   o .  s
  e
  r
   p l i   o   w
   o
   L
   2    G   C   C   R
 .
  r    t    9
  o   u
   t    1   3
  -
  t  u
   p
  n
 I .
  f  n
   o
   C
   k    8   c    O
  c    2    A   a  n  y    0
  o
   l
  5  .   t    2
   G   a
  2
  -
  t  u
   p
  n
 I .
  f  n
   o
   C
  r    k    7   n  n  e   l
  e
   t   c    2   e  o  p  e    1
  n
  o
   l    G   C   O   R    2   1
  -
  t  u
   p
  n
 I .
  f  n
   o
   C
   i   r
  e
   D    l    t
   2
   A   a   n
   i    2
  c    l
   p
   o
  t   S .   E
   O    i   a
   L   n   c
   i   c
  a   r
   t    2    i
   t
   h   c    N
   G
   S
  e  p
  c   e    3
  e
   l
   E    1   n  u
   M   g   k
  c
   M  .    4   D
  a   i
  r    t    M   P    )
  o   u    1    N
   G
   L
   t  .
  c    O    W
   (
   6    A   a  e  y
  s   t    5    R   +
   2   5   n  n  s   l
   i   a    1    O   T
   A
   R
   E
   N
   E
   G
   E
   G
   R
   A
   H
   C    D
  o  e
  a  o   l    E
   G  .
   5    M    C   C   R    R   N
   A   E
   2   r    t  .    H   G
   C
  o   u
  0
  1
  -
   E
   S
   U
   F

   4    t
  c    O
   2   s   t
  a   y
  n  n  n   a   1    1
   A
  5
   3    i   e   l    3
   D
 I   O
   N
   E
   L
   O
   S

   2   a  o  p  e
   A
  6
   M    C   O   R
  1    3
   Y
   A
   L
   E
   R
   3
   T
   R
   A
   T
   S
   A
  6
   V    2
   4    0
   0    3    R
   E
   3    T
  9
  -
   E
   S
   U
   F
   R
   3
  ~    5    A
   T
   3    S
  m
  3
  -
   E
   S
   U
   F   8
  -
   E
   S
   U
   F

  u    0
   2   m    4   +
   i
  7
  -
   E
   S
   U
   F
  x
  2
  -
   E
   S
   U
   F    Y
   R
   E
   T
   T
   A
   B
   9    1
   1   a    3
   S
  1
  -
   E
   S
   U
   F
   M
   N
   I
   A   1   2   3
   M   L   L   L   N

Figure 2.5 EAOM-210 FL three phase connections schematic.


FUSE-1, FUSE-2, FUSE-3, FUSE-4, FUSE-5, FUSE-6, FUSE-7 1 A. T
FUSE-8 should meet the current required by configurable output-2, 3, 4 – 15 A.T max
FUSE-9 should meet the current required by solenoids (Max. 16 A. T)
FUSE-10, FUSE-11 Max. 5A. T

EAOM-210 FL.eng / ver 0.7


Pages 9 / 154
 

1- Connect the unit as shown in the appropriate diagram, Figure 2.5 . Be sure
to connect the battery supply the right way round and battery negative should be
grounded. The connectors can be unplugged from the rear of the unit to facilitate
connection.

2-   Screened cable must be used for connecting the Magnetic Pickup, ensuring that the
screen is grounded at one end ONLY.

EAOM-210 FL.eng / ver 0.7


Pages 10 / 154
 

Table 2.1 shows the connections and recommended cable sizes. Table 2.2 describes
the functions of the connections.

Table 2.1 Unit wiring

Pin Description Cable Size Notes


(mm²)
1 Mains voltage input (L1) 2,5
2 Mains voltage input (L2) 2,5 3 phase applications only.
3 Mains voltage input (L3) 2,5 3 phase applications only.
4 Mains voltage neutral 2,5
5 Alternator voltage input (L1) 2,5
6 Alternator voltage input (L2) 2,5 3 phase applications only.
7 Alternator voltage input (L3) 2,5 3 phase applications only.
8 Alternator voltage neutral 2,5
9 Not connected
Connect to fuel level
10 Fuel level sender 1
sender
Connect to Coolant
11 Coolant temperature sender 1
temperature sender
Connect to Low oil pressure
12 Low oil pressure sender 1
sender
13 Connect to magnetic pick-
Input from magnetic pick-up 1
14 up device
15 Input from charge generator 1 NC to “0” volt.
16 Configurable input-6 1 Switch to “BATTERY +”.
17 High temperature or configurable input-5 1 Switch to “0” volt.
18 Low oil pressure or configurable input-4 1 Switch to “0” volt.
19 Configurable input-3 1 Switch to “0” volt.
20 Configurable input-2 1 Switch to “0” volt.
21 Configurable input-1 1 Switch to “0” volt.
22 Input from emergency stop 1 NC to “0” volt. When the
switch is opened, the
engine is stopped.
23 Mains Contactor Open Relay Output 2,5
24 Mains Contactor Open Relay Output 2,5
25 Mains Contactor Close Relay Output 2,5
26 Mains Contactor Close Relay Output 2,5
27 Gen. Contactor Open Relay Output 2,5
28 Gen. Contactor Open Relay Output 2,5
29 Gen. Contactor Close Relay Output 2,5
30 Gen. Contactor Close Relay Output 2,5
31 Output to fuel / stop solenoid 2,5 16 A. Max.
DC supply from Pin 32
32 +Battery supply input 2,5 Supplies to Pin 31,33,34
33 Output to start 2,5 16 A. Max.
DC supply from Pin 32
34 Horn or configurable relay output-1 2,5 16 A. Max.
DC supply from Pin 32
35 +Battery supply input 2,5 Supplies to Pin 36,37,38
36 Configurable relay output-2 2,5 5 A. Max.
DC supply from Pin 35

EAOM-210 FL.eng / ver 0.7


Pages 11 / 154
 

37 Configurable relay output-3 2,5 5 A. Max.


DC supply from Pin 35
38 Configurable relay output-4 2,5 5 A. Max.
DC supply from Pin 35
39 - Battery supply to EAOM-210 FL 2,5 Supplies to unit
40 + Battery supply to EAOM-210 FL 2,5 Supplies to unit
41 CT Secondary for Earth current 2,5 Connect to secondary of  
Earth current monitoring
CT
42 CT Secondary for Earth current 2,5 Connect to secondary of  
Earth current monitoring
CT
43 CT Secondary for load L3 2,5 Connect to secondary of  
load L3 monitoring CT
44 CT Secondary for load L2 2,5 Connect to secondary of  
load L2 monitoring CT
45 CT Secondary for load L1 2,5 Connect to secondary of  
load L1 monitoring CT
46 Common for load L1, L2, L3 2,5 Connect to secondary of  
load common monitoring
CT

EAOM-210 FL.eng / ver 0.7


Pages 12 / 154
 

Table 2.2 Unit wiring description

Pin Function
1 L1
Mains voltage inputs. Used to detect failure for controlling automatic transfer of load
2 L2
to alternator. Pins 2 and 3 not used on single phase applications.
3 L3
4 Mains voltage neutral
5 L1 Alternator voltage inputs. Unit can be programmed to use frequency of alternator
6 L2 output to detect when engine has started. Pins 6 and 7 not used on single phase
7 L3 applications.
8 Alternator voltage neutral
9 Not connected
10 Fuel level sender
11 Coolant temperature sender
12 Low oil pressure sender
13 Magnetic input +ve. An AC signal from the magnetic pick-up +ve for speed sensing.
14 Magnetic input –ve. An AC signal from the magnetic pick-up -ve for speed sensing.
15 Input from charge generator. Can be used to detect when engine has started.
Configurable input-6. This is a negative switched configurable input, see Digital
16 Configurable Input-6 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
High Temperature or Configurable input-5. This is a negative switched. If Configurable
input-5 is not selected as High Temperature, It is possible to configure input to be a
17
normally closed signal or a normally open signal. See Digital Configurable Input-5 Page
Section for options available.
Low Oil Pressure or Configurable input-4. Normally closed contact. Switch to 0V. If 
Configurable input-4 is not selected as Low Oil Pressure, It is possible to configure input to
18
be a normally closed signal or a normally open signal. See Digital Configurable Input-4 Page
Section for options available.
Configurable input-3. This is a negative switched configurable input, see Digital
19 Configurable Input-3 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
Configurable input-2. This is a negative switched configurable input, see Digital
20 Configurable Input-2 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
Configurable input-1. This is a negative switched configurable input, see Digital
21 Configurable Input-1 Page Section for options available. It is possible to configure input to
be a normally closed signal or a normally open signal.
Input from emergency stop switch. Normally closed contact. Switch to 0V. when the switch
22
is opened, the engine is stopped.
Mains Contactor Open Relay Output. See Breakers Page Section for options available. Volts
23
free contacts to 24.
Mains Contactor Open Relay Output. See Breakers Page Section for options available. Volts
24
free contacts to 24.
Mains Contactor Close Relay Output. See Breakers Page Section for options available. Volts
25
free contacts to 26.
Mains Contactor Close Relay Output. See Breakers Page Section for options available. Volts
26
free contacts to 25.
Gen. Contactor Open Relay Output. See Breakers Page Section for options available. Volts
27
free contacts to 28.
Gen. Contactor Open Relay Output. See Breakers Page Section for options available. Volts
28
free contacts to 27.

EAOM-210 FL.eng / ver 0.7


Pages 13 / 154
 

Gen. Contactor Close Relay Output. See Breakers Page Section for options available. Volts
29
free contacts to 30.
Gen. Contactor Close Relay Output. See Breakers Page Section for options available. Volts
30
free contacts to 29.
Output to fuel / stop relay. DC supply from Pin 32. Controls fuel to engine or controls
31
engine stopping.
32 +Battery supply input. Supplies to Pin 31,33,34
33 Output to start relay. DC supply from Pin 32. Controls starter motor.
Horn or configurable relay output-1. DC supply from Pin 32. See Configurable Output-1 Page
34
Section for options available.
35 +Battery supply input. Supplies to Pin 36,37,38
Configurable relay output-2. DC supply from Pin 35. See Configurable Output-2 Page Section
36
for options available.
Configurable relay output-3. DC supply from Pin 35. See Configurable Output-3 Page Section
37
for options available.
Configurable relay output-4. DC supply from Pin 35. See Configurable Output-4 Page Section
38
for options available.
39 - Battery input supplies EAOM-210 FL
40 + Battery input supplies EAOM-210 FL
41 CT Secondary for Earth current (IEA).
42 CT Secondary for Earth current (IEA).
43 CT Secondary for load L3.
44 CT Secondary for load L2.
45 CT Secondary for load L1.
46 CT Secondary for load common.

EAOM-210 FL.eng / ver 0.7


Pages 14 / 154
 

Section 3 Definition Of Front Panel And Programming


3.1 Front Panel Description

30 31

5 7
1 MAINS
17 3 4 19 21
START

13
PROG
14N 15
P  
16 2 8
18 20 6 22
STOP
LOAD

9 10 11   12
23
TEST
24
  25
RESET
26OFF
27 28
AUTOTEST
29
MANUAL

 Number Comment:
1 The red LED illuminates only when the EAOM-210 FL in the Programming Mode.
The green LED indicates that Mains voltage and frequency is within limits and is ready
2
to take over the load.
3 The LED shows that the load is connected to the mains. It’s colour is green.
4 The LED shows that the load is supplied from the generator. It’s colour is green.
The green LED indicates that Generator Voltage is within limits and is ready to take
5
over the load.
6 The green LED indicates that the engine has started and is running.
In the MAN, AUTO and TEST modes, the green LED indicates that the engine is starting
7
up or is running.
In the MAN, AUTO and TEST modes, the red LED indicates that the engine has stopping
8
or stopped.
9 This red LED shows that the unit is in the OFF mode.
10 This red LED shows that the unit is in the AUTO mode.
11 This red LED shows that the unit is in the TEST mode.
12 This red LED shows that the unit is in the MANUAL mode.
When this button is pressed, the unit goes into its PROGRAMMING Mode and LED (1)
13
illuminates.
This button is used for showing next working screen in normal operation. In
14 Programming mode, it operates as an page changing function or increment function
(increase value).

EAOM-210 FL.eng / ver 0.7


Pages 15 / 154
 

Number Comment:
This button is used for showing previous working screen in normal operation. In
15 Programming mode, it operates as an page changing function or decrement function
(decrease value).
This button is used for rotating between Event Log screens in normal operation, and
16
between programming parameters in programming mode.
17 This button closes the mains contactor, only operative when manual mode is selected.
18 This button opens the mains contactor, only operative when manual mode is selected.
This button closes the alternator contactor, only operative when manual mode is
19
selected.
This button opens the alternator contactor, only operative when manual mode is
20
selected.
21 The START button is used for starting the engine when the unit is in the Manual Mode.
22 The STOP button is used for stopping the engine when the unit is in the Manual Mode.
23 The LAMP TEST button illuminates all LED indicators.
24 This button will silence the alarm horn after a failure has been detected.
25 This button will reset the controller after a failure has been detected.
26 The OFF button is used for changing operating mode of the unit to the OFF Mode.
27 The AUTO button is used for changing operating mode of the unit to the AUTO Mode.
28 The TEST button is used for changing operating mode of the unit to the TEST Mode.
29 The MAN button is used for changing operating mode of the unit to the MANUAL Mode.
128x64 Dot matrix LCD Display. This is used for displaying the electrical measurements
30 during normal operation (features explained in section 5.1.1.), and editing/inspecting
programming parameters in program mode.
31 Failure Indicators. Detailed information available in section 5.1.2.

EAOM-210 FL.eng / ver 0.7


Pages 16 / 154
 

3.2 Programming Procedure


Many of the unit functions can be set by programming. Programming can be
carried out only while the unit is in OFF   mode. Press the OFF (26) button. If the engine
is running, it will stop and the LED (9) lights on.
The parameters have been divided into groups according to their functions. Every group
has a title and firstly user must determine the title (page) for accessing to the parameters.
Refer to the parameters section for detailed information about parameters.

3.3 Accessing to the Operator Parameters

Operation Screen
 MAINS & LOAD OPERATOR SECTION OPERATOR SECTION
L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A    PASSWORD
IEA: 63A 
 AUTO CRANKNG ATTEMP   0
OVER SPEED PREALARM!

PROG PROG PROG

When the prog button is


pressed, password is User can access to operator parameters by Enter
asked for accessing to entering operator or technician password. password with
parameters. This selection is done with increment and increment and
decrement buttons. decrement
buttons.

OPERATOR SECTION OPERATOR PASSWORD

  PASSWORD
  161
Note1:  If Enter button is
pressed and the operator Press the Enter button to
password is zero, Password confirm password. If the
screen is ignored.
PROG password is incorrect, the
unit will drop out of
program mode.

Operator and technician OPERATOR SECTION MAINS LEVELS Page


can access to this page.  MAINS LEVELS PAGE

PROG

Operator or technician can access


to the following page by pressing
increment button

Operator and technician OPERATOR SECTION GENERATOR VOLTAGE


can access to this page.  GEN.VOLT.LEVELS PAGE LEVELS Page

Note2:  When Password PROG

message is shown, parameters


can be seen by pressing Enter
button without entering operator
Operator or technician can access
password. But user can not
to the following page by pressing
change the parameters.
increment button

EAOM-210 FL.eng / ver 0.7


Pages 17 / 154
 

Operator and technician can access to this OPERATOR SECTION GENERATOR FEQUENCY
page  GEN.FREQ.LEVELS PAGE LEVELS Page

If the sensing options generator


frequency parameter(Gen1) in
Miscellaneous page(Gen) is disable,
this page is ignored.
PROG Operator or technician can access to the
Operator or technician can access to the former page by pressing decrement button
following page by pressing increment button

Operator and technician can access to this OPERATOR SECTION GENERATOR CURRENT/POWER
page  GEN.CUR/POW.LVL PAGE LEVELS Page

PROG Operator or technician can access to the


former page by pressing decrement button

Press prog button to exit Continue to press increment and By pressing ENTER button,
from Program Mode and decrement buttons to change the user can access to all
turn to operation screen. page. parameters in related page.
pera
O tor nd te
h ci a
n inna
c c s e  A to
si E
h O
R
TO
PIC
S

O
T
E
 NRE
FeG
N
O
T
a
 P
S
LgV
AEU
EQ
CNY
p
fIg
rte ahe
e
qc
ensi o
u
y g
a
irpn te
mon
tee
s
g
n rG(n
1tin
)eroa  N G
 
F
.
 V 
EE.
L
 A 
Q

P
G
ES
h issce
tM agn
p
el iea
s
o
p
u
n ig
e rdeG.()en is d
able , P
G
R
O te
a
 hp
Oo
c
r nia
inna
c ce
ssto
th
e
poerg
lO
fo a
toirnag
w
p rth
np e
ic b
yires
n
a
g ic c e
s
mia
rn
tot nth
bu
e
o pa fo
e
m
yg
rbpre
sgde
in rc
e
meto
n
bun
O
p
g
aeera
to r ndh
n te
c i iac
nna c s e s  A 
 N
i E
to
h O
R
TO
G
C
.
 W 
 VL
PIC
O
S
/

.
 A 
T
E
P
L
 G
UP
ENR
Ee G
N
O
T
C
a
 P
S
L
gV
AUR E
N
T/PW
O
ER
PGR
O p
te
a
 y
O
fh
m o
c
g
rbpr
nie
s
c de
a
g
in narce
s
msteto
n
b
h
u
en
s
P e
p
rogo b
ut ntioetx Contiu
eo e
s
p
n
ir cre
m
nt p a
y
rBndessin
E g NE T
butto
R n
,
o
m
n
frPpe
tu grn
am
tiM
ro od
c
e s
n
r.a dec
pag
re
n
.tm nb
su
tot h
a
o
n
c ge
ea ru
p
m
thces
s c a
te
in
r ss
to
de
a
lrl .pa
g
e

EAOM-210 FL.eng / ver 0.7


Pages 18 / 154
 

3.3.1 Changing and Saving Operator Parameter Values


Example-1 : To change Mains Under Voltage parameter in ”MAINS LEVELS PAGE”, user must
access to “MAINS LEVELS PAGE” page firstly.

Operation Screen
 MAINS & LOAD OPERATOR SECTION OPERATOR SECTION
L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A    PASSWORD
IEA: 63A 
 AUTO CRANKNG ATTEMP   0
OVER SPEED PREALARM!

PROG PROG PROG

When the prog button is


pressed, password is User can access to operator parameters by Enter
asked for accessing to entering operator or technician password. password with
parameters. This selection is done with increment and increment and
decrement buttons. decrement
buttons.

OPERATOR SECTION OPERATOR PASSWORD

  PASSWORD
  161
Note1:  If Enter button is
pressed and the operator Press the Enter button to
password is zero, Password confirm password. If the
screen is ignored.
PROG password is incorrect, the
unit will drop out of
program mode.

Operator and technician OPERATOR SECTION MAINS LEVELS Page


can access to this page.  MAINS LEVELS PAGE

PROG

Press Enter button to access


to first parameter in Mains
Levels page.

OPERATOR SECTION Mains Under Voltage parameter


 MAINS LEVELS PAGE
  MAINS UNDER VOLTAGE
   320 Vac

PROG

Parameter can be changed with


increment and decrement buttons
OPERATOR SECTION
 MAINS LEVELS PAGE
  MAINS UNDER VOLTAGE
   322 Vac

PROG

Press Enter button to confirm the


changed value and access to the
following parameter.

EAOM-210 FL.eng / ver 0.7


Pages 19 / 154
 

OPERATOR SECTION Mains Under Voltage Return


 MAINS LEVELS PAGE parameter
  MAINS UNDER V.RET.
   340 Vac

PROG

When Prog button is pressed,


related page can be accessed.

OPERATOR SECTION MAINS LEVELS Page


 MAINS LEVELS PAGE

PROG

If Prog button is pressed


again, operation screen is Continue to press increment and decrement
shown. buttons to change the page.

 MAINS & LOAD Operation Screen


L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

PROG

EAOM-210 FL.eng / ver 0.7


Pages 20 / 154
 

3.4 Accessing to the Technician Parameters


Operation Screen
 MAINS & LOAD OPERATOR SECTION TECHNICIAN SECTION
L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

PROG PROG PROG

When the prog button is


pressed, password is User can access to technician parameters
asked for accessing to by entering technician password. This
parameters. selection is done with increment and
decrement buttons.

Press the Enter button.

TECHNICIAN SECTION TECHNICIAN SECTION TECHNICIAN PASSWORD

  PASSWORD   PASSWORD
  0   162

Press the Enter button to


confirm password. If the
PROG PROG password is incorrect, the
unit will drop out of
program mode.
Enter password with
increment and
decrement buttons. TECHNICIAN SECTION GENERATOR CURRENT/POWER
 GEN.CUR/POW.ACT.PAGE ACTIONS Page

Note1:  If Enter button is pressed Operator can not


and the technician password is access to this page.
zero, Password screen is ignored.
PROG

Technician can access to the


following page by pressing
increment button

TECHNICIAN SECTION MISCELLANEOUS Page


 MISCELLANEOUS PAGE

Operator can not


access to this page.

PROG
Note2:  When Password
message is shown, parameters
can be seen by pressing Enter
button without entering technician Technician can access to the
password. But user can not following page by pressing
change the parameters. increment button

EAOM-210 FL.eng / ver 0.7


Pages 21 / 154
 

Operator can not access to this page. TECHNICIAN SECTION ENGINE STARTING OPTIONS Page
 ENGINE STAR.OPT PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION ENGINE CRANK DISCONNECT Page
 ENG.CRANK DISCN.PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION GENERATOR SPEED SETTINGS Page
 GEN.SPED SETING PAGE
If the sensing options pick up
parameter(Gen2) in Miscellaneous
page(Gen) is disable, this page is
ignored.

Technician can access to the following


PROG
Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION ENGINE PLANT BATTERY Page
 ENG.PLANT BATTR PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION ANALOGUE INPUTS Page
 ANALOGUE INPUTS PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION ANALOGUE SENDER
 ANALG.SENDR LIN.PAGE LINEARISATIONS Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 22 / 154
 

Operator can not access to this page. TECHNICIAN SECTION CANBUS CONFIGURATION Page
 CAN BUS CONFIG. PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-1 PAGE INPUT-1 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-2 PAGE INPUT-2 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-3 PAGE INPUT-3 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-4 PAGE INPUT-4 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-5 PAGE INPUT-5 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 23 / 154
 

Operator can not access to this page. TECHNICIAN SECTION DIGITAL CONFIGURABLE
 DIG.CNF.INPUT-6 PAGE INPUT-6 Page

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-1 PAGE INPUT-1 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-2 PAGE INPUT-2 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-3 PAGE INPUT-3 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-4 PAGE INPUT-4 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-5 PAGE INPUT-5 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 24 / 154
 

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.INPUT-6 PAGE INPUT-6 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.IN PUT-7 PAGE INPUT-7 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CNF.IN PUT-8 PAGE INPUT-8 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION CONFIGURABLE OUTPUT-1 Page
 CONFIG.OUTPUT-1 PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION CONFIGURABLE OUTPUT-2 Page
 CONFIG.OUTPUT-2 PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION CONFIGURABLE OUTPUT-3 Page
 CONFIG.OUTPUT-3 PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 25 / 154
 

Operator can not access to this page. TECHNICIAN SECTION CONFIGURABLE OUTPUT-4 Page
 CONFIG.OUTPUT-4 PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT -1 PAGE OUTPUT-1 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT -2 PAGE OUTPUT-2 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT-3 PAGE OUTPUT-3 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT-4 PAGE OUTPUT-4 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT-5 PAGE OUTPUT-5 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 26 / 154
 

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT-6 PAGE OUTPUT-6 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT -7 PAGE OUTPUT-7 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXPANSION CONFIGURABLE
 EXP.CONFG.OUT -8 PAGE OUTPUT-8 Page
If the Expansion Module Selection
parameter in CanBus Configuration
page is disable, this page is ignored.

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION START TIMERS Page
 START TIMERS PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION LOAD/STOPPING TIMERS Page
 LOAD/STP.TIMERS PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

EAOM-210 FL.eng / ver 0.7


Pages 27 / 154
 

Operator can not access to this page. TECHNICIAN SECTION BREAKERS Page
 BREAKERS PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION LCD CONFIGURATION Page
 LCD CONFIG.PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION ENGINE MAIN TENANCE ALARM Page
 ENG.MAINT.ALARM PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION COMMUNICATION Page
 COMMUNICATION PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION EXERCISE Page
 EXERCISE PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

p
Oera
to
c
r an
c
n
o
tace
s
to s
th
a . A 
i ge
p  NI
C
 N
D
T
H
EP
O
T
 N
S
U
IO
ET
G
I
EA 
CT
D
 S
E
U
Ae
P a
P
g
e
c
T
p
a
ghn
eb
c
a
p
n
ry
i es
a
s
n
g
ic
ecr
ss
e
m
h
to
nef
t ln
w
b
o
u
t .in
g P
G
R
O  n
b
iy
e
c
T
a
p
s
g
rhina
c
s
n
g
e
drsttb
h
o
e
m
fnoutrm
e
to
n
.
p
Oera
to
c
r an
c
n
o
tace
s
to s
th
a  NI
. A 
i ge
p C
T
 N
P
S
 A 
H
EP
O
T
S
 N
GE
D
I
E
RW 
O
T
I
CO
 S
P
D
W
R
APe
a
g
e
s
r ro
P
p tg
o b
untx
oei C
o
t ntn
ue
tP
iR
GOoe
s
p
irncre
m
nt B
a
yndpre
singE R E
Tn
N b
u
to,
o
n
fu
tm
rPop
ro
a
tM
o
im
g
e
n
r oc
e
d
s
n
ra.dg
d
p
e
a
cre.em
nt n
s
bu
tot h
a
n
o
c ge
u
e
rp
tham
s
a rc
a
n re
t scc
e
s
o
tin
la
r dp
ale
a
gl.

EAOM-210 FL.eng / ver 0.7


Pages 28 / 154
 

Operator can not access to this page. TECHNICIAN SECTION DATE SETUP Page
 DATE SETUP PAGE

Technician can access to the following PROG


Technician can access to the former
page by pressing increment button. page by pressing decrement button.

Operator can not access to this page. TECHNICIAN SECTION PASSWORD Page
 PASSWORD PAGE

PROG

Press prog button to exit Continue to press increment and By pressing ENTER button,
from Program Mode and decrement buttons to change the user can access to all
turn to operation screen. page. parameters in related page.

EAOM-210 FL.eng / ver 0.7


Pages 29 / 154
 

3.4.1 Changing and Saving Technician Parameter Values


Example-1 : To change CT Primary parameter in ”GENERATOR CURRENT/POWER ACTIONS
PAGE”, user must access to “GEN.CUR/PW.ACT.PAGE” firstly.

Operation Screen
 MAINS & LOAD OPERATOR SECTION TECHNICIAN SECTION
L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

PROG PROG PROG

When the prog button is


pressed, password is User can access to technician parameters
asked for accessing to by entering technician password. This
parameters. selection is done with increment and
decrement buttons.

Press the Enter button.

TECHNICIAN SECTION TECHNICIAN SECTION TECHNICIAN PASSWORD

  PASSWORD   PASSWORD
  0   162

Press the Enter button to


confirm password. If the
PROG PROG password is incorrect, the
unit will drop out of
program mode.
Enter password with
increment and
decrement buttons. TECHNICIAN SECTION GENERATOR CURRENT/POWER
 GEN.CUR POW.ACT.PAGE ACTIONS Page

Note1:  If Enter button is pressed Operator can not


and the technician password is access to this page.
zero, Password screen is i gnored.
PROG

Press Enter button to access to


first parameter in Generator
Current/Power Actions page.

TECHNICIAN SECTION CT Primary parameter


 GEN.CUR/POW.ACT.PAGE
  CT PRIMARY
   100Vac

PROG

Parameter can be changed with


increment and decrement buttons
TECHNICIAN SECTION
 GEN.CUR POW.ACT.PAGE
  CT PRIMARY
   500Vac

PROG

Press Enter button to confirm the


changed value and access to the
following parameter.

EAOM-210 FL.eng / ver 0.7


Pages 30 / 154
 

TECHNICIAN SECTION CT Primary (Earth Fault) parameter


 GEN.CUR/POW.ACT.PAGE
  EARTH FAULT CT PRIM 
   100Vac

PROG

When Prog button is pressed,


related page can be accessed.

TECHNICIAN SECTION GENERATOR CURRENT/POWER


 GEN.CUR/POW.ACT.PAGE ACTIONS Page

PROG

If Prog button is pressed


again, operation screen is Continue to press increment and decrement
shown. buttons to change the page.

 MAINS & LOAD Operation Screen


L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

PROG

EAOM-210 FL.eng / ver 0.7


Pages 31 / 154
 

3.5 Programmable function definitions

Operator parameters

(MAINS LEVELS PAGE) MAINS LEVELS page


MAINS UNDER VOLTAGE  Mains Under Voltage  VAC 60 – 600 320
MAINS UNDER V.RET. Mains Under Voltage Return  VAC 60 – 600 340
MAINS OVER VOLTAGE  Mains Over Voltage  VAC 60 – 600 440
MAINS OVER V.RETURN  Mains Over Voltage Return  VAC 60 – 600 420
MAINS UNDER FREQ. Mains Under Frequency  Hz 20.0 – 75.0 45.0
MAINS UNDER F.RET. Mains Under Frequency Return  Hz 20.0 – 75.0 48.0
MAINS OVER FREQ. Mains Over Frequency  Hz 20.0 – 75.0 55.0
MAINS OVER F.RETURN  Mains Over Frequency Return  Hz 20.0 – 75.0 52.0

The unit uses these parameters to decide when to lit the “Mains Okey LED”.
In Automatic mode, the unit uses these parameters to switch the load between the mains
supply and the alternator.

(GEN.VOLT.LEVELS PAGE) GENERATOR VOLTAGE LEVELS page


GEN.UNDER VOLTAGE  Generator Under Voltage  VAC (dis)60 – 600 320
GEN.UNDER V.PRE-ALR  Generator Under Voltage Pre-Alarm  VAC (dis)60 – 600 340
GEN.LOADING VOLTAGE  Generator Loading Voltage  VAC 60 – 600 345
GEN.OVER V.PRE-ALR  Generator Over Voltage Pre-Alarm  VAC (dis)60 – 600 420
GEN.OVER V.PR-A.RET  Generator Over Voltage Pre-Alarm Return  VAC 60 – 600 400
GEN.OVER VO.SHUTDWN  Generator Over Voltage Shutdown  VAC 60 – 600 440

The unit uses these parameters to decide when to display Voltage Failure and Voltage Error
Messages. Also, the unit uses Generator Loading Voltage parameter to decide when to take
the load.

(GEN.FREQ.LEVELS PAGE) GENERATOR FREQUENCY LEVELS page


GEN.UNDER FREQUENCY  Generator Under Frequency  Hz (dis)30.0 – 75.0 43.0
GEN.UNDER F.PRE-ALR  Generator Under Frequency Pre-Alarm  Hz (dis)30.0 – 75.0 45.0
GEN.LOADING FREQ. Generator Loading Frequency  Hz 30.0 – 75.0 46.0
GEN.OVER F.PRE-ALR  Generator Over Frequency Pre-Alarm  Hz (dis)30.0 – 75.0 55.0
GEN.OVER F.PR-A.RET  Generator Over Frq Pre-Alarm Return  Hz 30.0 – 75.0 54.0
GEN.OVER FR.SHUTDWN  Generator Over Frequency Shutdown  Hz (dis)30.0 – 75.0 58.0

The unit uses these parameters to decide when to display Speed Failure and Frequency
Error Messages. Also, the unit uses Generator Loading Frequency parameter to decide
when to take the load.

(GEN.CUR/POW.LVL.PAGE) GENERATOR CURRENT/POWER LEVELS page


GEN.OVER CURRENT  Generator Over Current  A AC 0 – 9999 9999
GEN.SHORT CIRCUIT  Generator Short Circuit  A AC 0 – 9999 9999
GEN.EARTH FAULT  Generator Earth Fault  A AC 0 – 9999 100

EAOM-210 FL.eng / ver 0.7


Pages 32 / 154
 

Technician parameters

(GEN.CUR/POW.ACT.PAGE) GENERATOR CURRENT/POWER ACTIONS page


CT PRIMARY  CT Primary  A AC 0 – 9999 500
EARTH FAULT CT PRIM  CT Primary (Earth Fault) A AC 0 – 9999 500
Over Current Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
OVER CUR.ACTIONS  - 0-3 dis
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
OVER CUR.ALARM TIME  Over Current Alarm Time  Sec 0 - 99 0
Short Circuit Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
SHORT CIR.ACTIONS  - 0-3 dis
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
SHORT CIR.ALRM TIME  Short Circuit Alarm Time  Sec 0 - 99 0
Earth Fault Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
EARTH FAULT ACTIONS  - 0-3 dis
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
EARTH FAU.ALRM TIME  Earth Fault Alarm Time  Sec 0 - 99 0
TOTAL ENERGY CLEAR  Total Energy Clear  - No-YES no
ACTIVE ENERGY CLEAR  Active Energy Clear  - No-YES no
REACTIVE ENERGY CLR  Reactive Energy Clear  - No-YES no

(MISCELLANEOUS PAGE) MISCELLANEOUS page


SENS.OPT.GEN.F.ENAB  Sensing Options Generator Frq En/Dis  - ENAB DIS ENAB
SNS.OP.PICKP ENA&FW  Sensing Opt Pickup En/Dis & Flywheel  - (dis)0-1000 DIS
Ac System 0 =1phase 2wire, 1= 3phase 
AC SYSTEM  - 0-2 1
4wire 2= 3phase 4wire Series Delta 
FAST LOAD.FEAT.ENAB  Fast Loading Feature En/Dis  - ENAB DIS DIS
ALL WRN.ARE LTCH.EN  All Warnings Are Latched En/Dis  - ENAB DIS DIS
MAINS FAIL.DETEC.EN  Mains Failure Detection En/Dis  - ENAB DIS ENAB
Look Mains Failure For Mains Cont.
LK.MA.FA.FO.MA.CN.E  - ENAB DIS DIS
En/Dis 
GAS/DIESEL SELECT  Engine Fuel (Gas/ Diesel) Selection  - GAS/ DIESEL DIESEL
STOP/FUEL SELECTION  Stop / Fuel Selection  - STOP/FUEL FUEL
STOP SOLENOID TIME  Stop Solenoid Time  Sec 5 - 99 20
IGNITION DELAY  Ignition Delay  Sec 1 - 99 5
GAS VALVE DELAY  Gas Valve Delay  Sec 1 - 99 5
MIN.IGNITION SPEED  Min Ignition Speed  RPM 10 - 1500 200
NOMINAL FREQUENCY  Nominal Alternator Frequency  Hz 30.0 – 75.0 50.0
NOMINAL SPEED  Nominal Speed  RPM 500 - 5000 3000

SENSING OPTIONS GENERATOR FRQ EN/DIS:


ENABLE: Speed sensing will be derived from the generator output frequency.
DISABLE: Speed sensing not will be derived from the generator output frequency.

SENSING OPT. PICKUP EN/DIS & FLYWHEEL


DISABLE: Speed sensing will not be derived from the magnetic pickup.
1-1000: Speed sensing will be derived from the magnetic pickup and the number is flywheel
teeth on the engine.

EAOM-210 FL.eng / ver 0.7


Pages 33 / 154
 

AC SYSTEM 3 PHASE 4 WIRE OR 1 PHASE 2 WIRE


0: AC system is 1 phase 2 wire.
1: AC system is 3 phase 4 wire.
2: AC system is 3 phase 4 wire series delta.

FAST LOADING FEATURE EN/DIS


ENABLE: The module will terminate the safety on timer once all monitored parameters have
reached their normal settings. This feature is useful if the module is to be used as a standby
controller as it allows the generator to start and go on load in the shortest possible time.
DISABLE: Normal operation, the safety on timer will be observed in full. This feature is useful
if the module is to be used with some small engines where pre-mature termination of the
delay timer can lead to overspeed alarms on start up.

ALL WARNINGS ARE LATCHED EN/DIS


Disable: Normal operation, the warnings and pre-alarms (except spare inputs, because they
have their latching or non-latching selections) will automatically reset once the triggering
condition has cleared.
Enable: Warnings and pre-alarms will latched when triggered. To reset the alarm either an
external reset must be applied to one of the inputs or the ‘Reset’ pushbutton operated, once
the triggering condition has cleared.

MAINS FAILURE DETECTION EN/DIS


Disable: The module will not monitor the AC mains supply for failure. The AC mains
instrumentation will still be active however.
Enable: The module will monitor the incoming AC mains supply. Should the supply go out
side of limits the module will initiate its automatic mains failure sequence.

LOOK MAINS FAILURE FOR MAINS CONTACTOR EN/DIS


Disable: In the event of a mains failure the EAOM-210 FL will attempt to maintain the supply
to the load for the incoming AC mains supply until the generator is available to go on load. In
the event of a generator failure the module will default back to the incoming AC mains
supply. This provides a ‘fail-safe system’, ensuring that in the event of a system failure the
load will still be fed from the AC mains supply.
Enable: As soon as the module detects a mains failure the mains contactor or breaker relay
will be opened to remove the supply from the load. This is to prevent damage to the load in
case of single-phase failure, especially useful if the load is a 3-phase motor or pump. The
supply to the load will then be fed from the gen-set once it is available. In the event of
generator failure the module will open the generator relay and remove the supply to the load
until either the mains supply is restored or the generator is restarted.

ENGINE FUEL (DIESEL /GAS) SELECTION


Diesel or Gas engine can be selected.

If diesel engine selected:


STOP/FUEL SELECTION
Selection for the engine has Fuel or Stop selenoid.

STOP SOLEONID TIME


This timer is used if the unit is configured to operate an Energise to stop engine. It dictates
the duration that the Stop Solenoid output will remain active after the module has detected
the engine has come to rest. If the Stop Solenoid output is not configured, this timer will still
operate, preventing an immediate restart.

EAOM-210 FL.eng / ver 0.7


Pages 34 / 154
 

Example: Start/stop diagram for Diesel Engine.

The formula signs and indices mean:


TPT Preheating time [s]
TCT Engagement time [s]
TRT Interval between 2 start attempts [s]
TDT Engine delayed monitoring [s]

EAOM-210 FL.eng / ver 0.7


Pages 35 / 154
 

  g
  n
   i
   ]    ]    ]    ]    ]    ]   p
  s
   [   s
   [   s
   [   s
   [   s
   [   s
   [   p
   t    t    t    t    t    t   o
   t
   S

   ]    T
   D
   M    t
   P
   R
  ;
  n
   i    l
  m
   /   u
   f
   1
   [   s
  s
  e
  c
  c
  u
   S
   T
   C
   t

   T
   R
   t

   T
   C    l
   t   u
   f
  s
  s
  e
  c
  c
  s   u
  s
   2   n
   T    U
   P
   t

   ]
   M    d
  e    d
   P   e
  p
  e
  e
   R   s   p
   [    d   s    N
  e
   t    t
  c  p    t
  a   e   u   s    O
  -
  n   k   e   g
   R   n  c   u   y   n
  o   i   q    t   a
   l    i
  r
  c   p   e   a   r   e   e   t
  o   g
  s  c   r   e   e   r   n   i   n
   i
   i    t    h    t    i    t
   d   i
   t   r
  a   -
  e   r
  a
   l
  e   n
  g   o   r
  a
   k  e
  n    t
   S
  r
   P
   t
   S
  u
   F
  n
   E  m
   t
   S
  n
  a   g
  r  a
   C  m

EAOM-210 FL.eng / ver 0.7


Pages 36 / 154
 

If gas engine selected:

IGNITION DELAY
With gas engines often a purging operation is desired before starting. With the engaging of
the starter the ignition delay is started. If the ‘min ignition speed’ is reached after expiry of
this time, the configurable relay output ‘ignition’ is set.

GAS VALVE DELAY


By setting the ignition relay the gas valve delay is started. After the expiry of the set time as
long as the number of revolutions is higher than the minimum ignition speed, the gas valve is
set. When the necessary engine shutdown process, gas valve is de-energised.

MIN IGNITION SPEED


After expiry of the ignition delay the number of revolutions set must be reached, so that the
configurable relay output ‘ignition’ will be set.

Example: Start/stop diagram for Gas Engine.

The formula signs and indices mean:


TRT Interval between 2 start attempts [s]
TIT Ignition delay [s]
TGT Gas valve delay [s]
TDT Engine delayed monitoring [s]

EAOM-210 FL.eng / ver 0.7


Pages 37 / 154
 

  g
  n
   i
   ]    ]    ]    ]    ]    ]   p
  s
   [   s
   [   s
   [   s
   [   s
   [   s
   [   p
   t    t    t    t    t    t   o
   t
   S

  s
 
   5

   T
   D
   t

   ]
   M
   P
   R
  ;
  n
   i
  m
   /
   1    l
   [   u
   f
  s
  s
  e
  c
  c
  u
   S

   T
   G
   t

   T
   I
   t
   d
  e
  e   d
  p   e
  s   h
  n   c
  o   a
   i   e
   t
   i   r
  n   e
  g   b
   i    t
  m  o
  n
  u   l
   l
  m   i
   i    T
  n   w
   i    R
   t
   M

   l
  u
   f
  s
  s
   T   e
  c
   I   c
   t   u
  s
  n
   U

   ]
   M    d
  e    d    d
   P   e
  p
  e
  e   e
  e
   R
   [
  s   p
  s   p
  s
   d    t    N
  e
   t   c  p   n    t    O
  a   u
  e  -   o
   i   s
   R   n   k    t
   i   e   e   g
  n   i
  c   n   u   n
   i
  o  p   g   q   n   v
   l   r   g
  c    i   e
  r   o   r   a   e   t
  o   n
  s  c
   i    t    i
   t   e
   t   v   n   i
   i    i
   t
   d   i
   t   m
  u   r
  a
   i
  n   r
  a   s   n
  g   o   r
  a
   k  e
  n   m
   t
   S   g
   I
   t
   S
  a
   G
  n
   E  m
   t
   S
  n
  a   g    i
  r   a   n
   i
   C  m    M

EAOM-210 FL.eng / ver 0.7


Pages 38 / 154
 

(ENGINE STAR.OPT PAGE) ENGINE STARTING OPTIONS page


AU.ALR.PRIOR STRT.E  Audible Alarm Prior To Starting En/Dis  - ENAB DIS DIS
NUMBR OF STR.ATTEMP  Number Of Start Attempts  - 1 – 10 3
CRANKING TIME  Cranking Time  SEC 5 – 99 5
CRANK REST TIME  Crank Rest Time  SEC 5 – 99 10
MUL.STR.ENG.ATEMP.E  Multiple Start Engage Attempts E/D (Pick) - ENAB DIS DIS
ENGAGE ATTEMPT TIME  Engage Attempt Time  (Pickup) SEC 0.1 – 10.0 1.0
ENG.ATEMP.REST TIME  Engage Attempt Rest Time (Pickup) SEC 0.1 – 10.0 1.0
PICK.SNSR FAIL DELY  Pickup Sensor Fail Delay(Pickup) SEC 0.1 – 10.0 1.0

AUDIBLE ALARM PRIOR TO STARTING EN/DIS


ENABLE: The audible alarm will sound before the engine starts. The sounder will become
active once the start delay is initialised, it will remain active until either the engine reaches
crank disconnect speed or pre-heat timers are cancelled.

NUMBER OF START ATTEMPTS


This value is the number of times the module will attempt to start the generator. Should the
generator start the module will not attempt further starts. If the generator does not start after
the final attempt, the module will give a ‘Fail to start’ alarm.

CRANKING TIME
This is the maximum amount of time that the module will energise the starter motor for during
starting attempts once the starter has engaged.

CRANK REST TIME


This is the amount of time the module will wait for between start attempts. This is to allow the
starter motor to cool and the starter batteries to recover.

MULTIPLE START ENGAGE ATTEMPTS E/D


(Only available if using Magnetic pickup)
ENABLE: The module will monitor the flywheel to ensure that the starter motor has engaged.
If it detects the starter has not meshed, it will de-energise the start relay and after a short
delay it will attempt to re-engage the starter. This will be repeated until either the starter
motor engages correctly or the number of engage attempts expires. Each start attempt can
have a maximum number of attempts to engage the starter, this value is entered the box.
DISABLE: Normal operation, starter engagement with flywheel will not monitored.

ENGAGE ATTEMPT TIME


(Only available if using Magnetic pickup and multiple engage attempts)
This timer dictates the duration that the module will attempt to engage the starter motor
during each engage attempt. If the magnetic pickup is not detecting movement of the
flywheel when this timer expires the engage attempt will terminate. Once all engage attempts
have been made the module will generate ‘Fail to engage’ alarm.

ENGAGE ATTEMPT REST TIME


(Only available if using Magnetic pickup and multiple engage attempts)
This timer dictates the duration that the module will wait between attempts to engage the
starter.

PICKUP SENSOR FAIL DELAY


(Only available if using Magnetic pickup without multiple engage attempts)
This is only used if magnetic pickup speed sensing is selected. When cranking, the module
must receive a speed signal within this time. If no signal is present the generator will be
shutdown and Loss of Speed Sensing alarm given.

EAOM-210 FL.eng / ver 0.7


Pages 39 / 154
 

(ENG.CRANK DISCN.PAGE) ENGINE CRANK DISCONNECT page


CRNK DISCN.ON GEN.F  Crank Disconnect On Gen. Frequency  Hz 25.0 – 75.0 30.0
CRNK DISCN.ON MAG.P  Crank Disconnect On Magnetic Pickup  RPM 500-6000 500
CRNK DISCN.ON GEN.V  Crank Disconnect On Gen. Voltage  VAC (dis)60 – 600 300
CRNK DISC.ON CH.G.V  Crank Disconnect On Charge Alt. Voltage  VDC (dis)6.0 – 30.0 6.1
CRNK DISCN.ON OIL P  Crank Disconnect On Oil Pressure  BAR (dis)1.0-90.0 dis

(GEN.SPED SETING PAGE) GENERATOR SPEED SETTINGS page


GEN.UNDER SPEED  Generator Under Speed  RPM (dis)500 – 5000 500
GEN.UNDR SPED PRE-A Generator Under Speed Prealarm  RPM (dis) 500 – 5000 500
GEN.UNDR SP.PR-A.RT  Generator Under Speed Prealarm Return  RPM 500 – 5000 500
GEN.OVER SPED PRE-A Generator Over Speed Prealarm  RPM (dis) 500 – 5000 500
GEN.OVER SP.PR-A.RT  Generator Over Speed Prealarm Return  RPM 500 – 5000 500
GEN.OVER SP.SHUTDWN  Generator Over Speed Shutdown  RPM (dis) 500 – 5000 500

(ENG.PLANT BATTR PAGE) ENGINE PLANT BATTERY page


BAT.UNDER V.WARNING  Battery Undervolts Warning  VDC (dis)6.0 – 30.0 10.0
BAT.UNDR V.WARN.RET  Battery Undervolts Warning Return  VDC 6.0 – 30.0 10.5
BAT.UNDER VOL.DELAY  Batt Undervolts Volts Delay  Sec 0 – 9.9 1.0
BAT.OVER V.WARNING  Battery Overvolts Warning  VDC (dis)6.0 – 30.0 30.0
BAT.OVER V.WARN.RET  Battery Overvolts Warning Return  VDC 6.0 – 30.0 29.5
BAT.OVER VOL.DELAY  Batt Overvolts Delay  sec 0 – 9.9 1.0
CHARGE ALT.WARNING  Charge Alternator Warning  VDC (dis)6.0 – 30.0 6.1

(ANALOGUE INPUTS PAGE) ANALOGUE INPUTS page


OIL PRES.INPUT TYPE  Oil Pressure Input Type  Dis,nc,no,anlg ANLG
OIL PRES.PRE-ALARM  Oil Pressure Pre-Alarm  BAR (dis)0.0 – 99.9 1.2
OIL PRES.PRE-AL.RET  Oil Pressure Pre-Alarm Return  BAR 0.0 – 99.9 1.4
OIL PRES.SHUTDOWN  Oil Pressure Shutdown  BAR 0.0 – 99.9 1.0
TEMP.INPUT TYPE  Temperature Input Type  Dis,nc,no,anlg ANLG
TEMP.PRE-ALARM  Temperature Pre-Alarm  C (dis)0 - 300 90
TEMP.PRE-ALARM RET  Temperature Pre-Alarm Return  C 0 - 300 88
TEMP.SHUTDDOWN  Temperature Shutdown  C 0 - 300 95
LEVEL PRE-ALARM  Level Pre-Alarm  % (dis)0 - 300 80
LEVEL PRE-ALARM RET  Level Pre-Alarm Return  % 0 - 300 90
LEVEL SHUTDOWN  Level Shutdown  % (dis)0 - 300 70

OIL PRESSURE INPUT TYPE


This section is used to configure the Oil Pressure sender input.
dıS: The Oil Pressure input will not be monitored.
1: digital & closed for low oil pressure : The Oil pressure input is fed from an engine
mounted digital pressure switch. This switch returns a closed signal during low oil pressure
conditions (and engine at rest), once oil pressure is established the switch will open.
2: digital & open for low oil pressure : The Oil pressure input is fed from an engine
mounted digital pressure switch. This switch returns an open signal during low oil pressure
conditions (and engine at rest), once oil pressure is established the switch will close.
3: analog : The Oil pressure input is connected to a resistive type engine mounted oil
pressure transducer.

TEMPERATURE INPUT TYPE


This section is used to configure the Coolant Temperature sender input.
dıS: The Coolant Temperature input will not be monitored.
1: digital & normally closed : The Coolant Temperature input is fed from an engine
mounted digital temperature switch. This switch returns a closed signal during low
temperature, should the temperature rise above the switch manifacturers trip point the switch
contact will open.
2: digital & normally open : The Coolant Temperature input is fed from an engine mounted
digital temperature switch. This switch returns an open signal during low temperature, should
the temperature rise above the switch manifacturers trip point the switch contact will close.

EAOM-210 FL.eng / ver 0.7


Pages 40 / 154
 

3: analog : The Oil pressure input is connected to a resistive type engine mounted
temperature transducer.

Note: If the Level Pre-alarm and Level Shutdown parameters are selected as disable, the
Level showing is ignored.

(ANALG.SENDR LIN.PAGE) ANALOGUE SENDER LINEARISATIONS page


OIL PRESS.SENDER 0  Oil Pressure Sender 0  R 0 -650 10
OIL PRESSURE 0  Oil Pressure 0  BAR 0 – 99.9 0.0
OIL PRESS.SENDER 1 Oil Pressure Sender 1 R 0 -650 62
OIL PRESSURE 1 Oil Pressure 1 BAR 0 –99.9 2.0
OIL PRESS.SENDER 2  Oil Pressure Sender 2  R 0 -650 111
OIL PRESSURE 2  Oil Pressure 2  BAR 0 –99.9 4.0
OIL PRESS.SENDER 3  Oil Pressure Sender 3  R 0 -650 156
OIL PRESSURE 3  Oil Pressure 3  BAR 0 –99.9 6.0
OIL PRESS.SENDER 4  Oil Pressure Sender 4  R 0 -650 205
OIL PRESSURE 4  Oil Pressure 4  BAR 0 –99.9 10.0
TEMP.SENDER 0  Temperature Sender 0  R 0 -650 360
TEMPERATURE 0  Temperature 0  C 0 -300 34
TEMP.SENDER 1 Temperature Sender 1 R 0 -650 145
TEMPERATURE 1 Temperature 1 C 0 -300 54
TEMP.SENDER 2  Temperature Sender 2  R 0 -650 50
TEMPERATURE 2  Temperature 2  C 0 -300 84
TEMP.SENDER 3  Temperature Sender 3  R 0 -650 43
TEMPERATURE 3  Temperature 3  C 0 -300 100
TEMP.SENDER 4  Temperature Sender 4  R 0 -650 10
TEMPERATURE 4  Temperature 4  C 0 -300 150
LEVEL SENDER 0  Level Sender 0  R 0 -650 10
LEVEL 0  Level 0  - 0 -300 0
LEVEL SENDER 1 Level Sender 1 R 0 -650 40
LEVEL 1 Level 1 - 0 -300 25
LEVEL SENDER 2  Level Sender 2  R 0 -650 80
LEVEL 2  Level 2  - 0 -300 50
LEVEL SENDER 3  Level Sender 3  R 0 -650 140
LEVEL 3  Level 3  - 0 -300 75
LEVEL SENDER 4  Level Sender 4  R 0 -650 185
LEVEL 4  Level 4  - 0 -300 100

(CANBUS CONFIG. PAGE) CANBUS CONFIGURATION page


EXPANS. MODUL SELECT  Expansion Module Selection  Disable,Enable Disable

EAOM-210 FL.eng / ver 0.7


Pages 41 / 154
 

(DIG.CNF.INPUT-1 PAGE) DIGITAL CONFIGURABLE INPUT (1) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION  0–4 0
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  0 – 24 2
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 42 / 154
 

(DIG.CNF.INPUT-2 PAGE) DIGITAL CONFIGURABLE INPUT (2) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION  0–4 0
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  0 – 24 3
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 43 / 154
 

(DIG.CNF.INPUT-3 PAGE) DIGITAL CONFIGURABLE INPUT (3) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION  0–4 0
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  0 – 24 4
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 44 / 154
 

(DIG.CNF.INPUT-4 PAGE) DIGITAL CONFIGURABLE INPUT (4) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 2
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  12 Generator Load Inhibit 0 – 25 25
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
25 Low Oil Pressure
INPUT TIME DELAY  Input time delay  SEC 0 - 250 0

EAOM-210 FL.eng / ver 0.7


Pages 45 / 154
 

(DIG.CNF.INPUT-5 PAGE) DIGITAL CONFIGURABLE INPUT (5) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 2
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  12 Generator Load Inhibit 0 – 25 25
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
25 High Temperature
INPUT TIME DELAY  Input time delay  SEC 0 - 250 0

EAOM-210 FL.eng / ver 0.7


Pages 46 / 154
 

(DIG.CNF.INPUT-6 PAGE) DIGITAL CONFIGURABLE INPUT (6) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  0 – 24 7
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 47 / 154
 

(EXP.CNF.INPUT-1 PAGE) EXPANSION CONFIGURABLE INPUT (1) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 48 / 154
 

(EXP.CNF.INPUT-2 PAGE) EXPANSION CONFIGURABLE INPUT (2) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 49 / 154
 

(EXP.CNF.INPUT-3 PAGE) EXPANSION CONFIGURABLE INPUT (3) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 50 / 154
 

(EXP.CNF.INPUT-4 PAGE) EXPANSION CONFIGURABLE INPUT (4) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 51 / 154
 

(EXP.CNF.INPUT-5 PAGE) EXPANSION CONFIGURABLE INPUT (5) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 52 / 154
 

(EXP.CNF.INPUT-6 PAGE) EXPANSION CONFIGURABLE INPUT (6) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 53 / 154
 

(EXP.CNF.INPUT-7 PAGE) EXPANSION CONFIGURABLE INPUT (7) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

EAOM-210 FL.eng / ver 0.7


Pages 54 / 154
 

(EXP.CNF.INPUT-8 PAGE) EXPANSION CONFIGURABLE INPUT (8) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST  (dis)0 - 2 1
List 
-Hardware type 
HARDWARE TYPE  0-1 0
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To  0-1 0
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION  1–4 1
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active  0–2 2
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button 1 – 21 2
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay  SEC 0 - 250 5

CONFIGURABLE INPUTS SELECTIONS

0 REMOTE START/STOP
In AUTO mode, if one of the configurable inputs are selected as 0 (Remote Start), the
module doesn’t perform the mains failure control in order to start the generator. In AUTO
mode, if one of the configurable inputs are selected as 0 (Remote Start) and this input is
active, then the module will perform the start sequence. If the input is passive module will
perform the stop sequence.

1 AUXILIARY MAINS FAIL


The Eaom-210 Fl module will monitor the incoming single or three phase supply for Over
Voltage, Under Voltage, Over Frequency or Under Frequency. It may be required to monitor
a different mains supply or some aspect of the incoming mains not monitored by the Eaom-
210 Fl. If the devices providing this additional monitoring are connected to operate this input,
the Eaom-210 Fl will operate as if the incoming mains supply has fallen outside of limits, the
generator will be instructed to start and take load. Removal of the input signal will cause the
module to act if the mains has returned to within limits.

EAOM-210 FL.eng / ver 0.7


Pages 55 / 154
 

2 SIMULATE LAMP TEST BUTTON


This input mimic’s the operation of the ‘Lamp Test’ button and is used to provide a remotely
located Lamp Test push button.

3 SIMULATE HORN RESET BUTTON


This input mimic’s the operation of the ‘Horn Reset’ button and is used to provide a remotely
located Horn Reset push button.
4 SIMULATE ALARM RESET BUTTON
This input mimic’s the operation of the ‘Alarm Reset’ button and is used to provide a remotely
located Alarm Reset push button.

5 SIMULATE OFF BUTTON


This input mimic’s the operation of the ‘Off’ button and is used to provide a remotely located
Off mode push button.

6 SIMULATE AUTO BUTTON


This input mimic’s the operation of the ‘Auto’ button and is used to provide a remotely located
Auto mode push button.

7 SIMULATE TEST BUTTON


This input mimic’s the operation of the ‘Test’ button and is used to provide a remotely located
Test mode push button.

8 SIMULATE MANUAL BUTTON


This input mimic’s the operation of the ‘Manual’ button and is used to provide a remotely
located Manual mode push button.

9 SIMULATE START BUTTON


This input mimic’s the operation of the ‘Start’ button and is used to provide a remotely
located start push button.

10 SIMULATE STOP BUTTON


This input mimic’s the operation of the ‘Stop’ button and is used to provide a remotely located
Stop push button.

11 GENERATOR CLOSED AUXILIARY


This input is used to provide feedback to allow the Eaom-210 Fl to give true indication of the
contactor or circuit breaker switching status. It should be connected to the generator load
switching device auxiliary contact.

12 GENERATOR LOAD INHIBIT


This input is used to prevent the Eaom-210 Fl from loading the generator. If the generator is
already on load, activating this input will cause the Eaom-210 Fl to unload the generator.
Removing the input will allow the generator to be loaded again.
NOTE: This input only operates to control the generator-switching device if the Eaom-210 Fl
load switching logic is attempting load the generator. It will not control the generator-
switching device when the mains is on load.

13 MAINS CLOSED AUXILIARY


This input is used to provide feedback to allow the Eaom-210 Fl to give true indication of the
contactor or circuit breaker switching status. It should be connected to the generator load
switching device auxiliary contact.

EAOM-210 FL.eng / ver 0.7


Pages 56 / 154
 

14 MAINS LOAD INHIBIT


This input is used to prevent the Eaom-210 Fl from loading the mains supply. If the manis
supply is already on load, activating this input will cause the Eaom-210 Fl to unload the
mains supply. Removing the input will allow the mains to be loaded again.
NOTE: This input only operates to control the mains-switching device if the Eaom-210 Fl load
switching logic is attempting to load the mains. It will not control the mains-switching device
when the generator is on load.

15 AUTO RESTORE INHIBIT


When module in the AUTO mode. In the event of a remote start / mains failure the generator
will be instructed to start and take load. On removal of the remote start signal / mains return
the module will continue to run the generator on load until this AUTO RESTORE INHIBIT
input is removed. Once the input is removed the module will transfer the load back to the
mains supply and follow a normal generator stop sequence. This input allows the module to
be fitted as part of a system where the manual restoration to mains is controlled remotely or
by an automated system.

16 AUTO START INHIBIT


This input is used to provide an over-ride function to prevent the Eaom-210 Fl from starting
the generator in the event of a remote start / mains out of limits condition occurring. If this
input is active and a remote start signal / mains failure occurs the Eaom-210 Fl will not give a
start command to the generator. If this input signal is then removed, the Eaom-210 Fl will
operate as if a remote start / mains failure has occurred, starting and loading the generator.
This function can be used to give an ‘AND’ function so that a generator will only be called to
start if the mains fails and another condition exists whish requires the generator to run. If the
‘Auto Start Inhibit’ signal become active once more it will be ignored until the module has
returned the mains supply on load and shutdown.

17 PANEL LOCK
This input is used to provide security to the installation. If the panel lock input is active, the
module will not respond to operation of the mode select or start buttons. This allows the
module to be placed into a spesific mode (such as Auto) and than secured. The operation of
the module is not affected and the operator will still be able to view the various
instrumentation pages etc.
NOTE: External control sources (i.e. Simulate Start Button) are not affected by the panel lock
input and will continue to operate normally.

18 SCHEDULED RUNS INHIBITED


This input is used to prevent the generator for starting in the event of a programmed
scheduled run occurring. While the input is active no scheduled runs will occur. If the input is
active when a schedule run is called for, and is removed during the running period the gen-
set will start and complete any remaining scheduled running time.

19 RESET MAINTENANCE ALARM


This input used to reset the maintenance alarm. When activated it will reset the maintenance
counter to the pre-configured value (i.e. 250 hours). If the maintenance alarm is configured to
monitor the monthly service interval this will also be reset to the pre-configured period. (i.e. 6
months).

20 TRANSFER TO GENERATOR/OPEN MAINS


This input is used to transfer the load to the generator when running in Manual mode.

21 TRANSFER TO MAINS/OPEN GENERATOR


This input is used to transfer the load to the mains supply when running in Manual mode.

EAOM-210 FL.eng / ver 0.7


Pages 57 / 154
 

22 REMOTE INHIBIT
In automatic mode, if any of the configurable inputs is congigured as ’16 Auto Start Inhibit’
and this input is active, unit inhibits to work of the generator. In addition to this, if this input is
active while the generator is working, unit stops the generator.

23 TEST ON LOAD
If this input is active when the unit is in test mode, load is transferred to the generator to do
the test on load. If the input is not active, test is done without load.

24 GENERATOR IS SUPPLYING THE LOAD IN OFF MODE


If this input is active when the unit is in OFF mode, the power is calculated. If the input is not
active, the power is not calculated.

25 LOW OIL PRESSURE (FOR CONFIGURABLE INPUT-4)


This input is used as the oil pressure failure input.

25 HIGH TEMPERATURE (FOR CONFIGURABLE INPUT-5)


This input is used as the temperature failure input.

EAOM-210 FL.eng / ver 0.7


Pages 58 / 154
 

(CONFIG.OUTPUT-1 PAGE) CONFIGURABLE OUTPUT (1) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 55
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 59 / 154
 

(CONFIG.OUTPUT-2 PAGE) CONFIGURABLE OUTPUT (2) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 60 / 154
 

(CONFIG.OUTPUT-3 PAGE) CONFIGURABLE OUTPUT (3) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 61 / 154
 

(CONFIG.OUTPUT-4 PAGE) CONFIGURABLE OUTPUT (4) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 32
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 62 / 154
 

(EXP.CONFG.OUT-1 PAGE) EXPANSION CONFIGURABLE OUTPUT (1) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 63 / 154
 

(EXP.CONFG.OUT-2 PAGE) EXPANSION CONFIGURABLE OUTPUT (2) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 64 / 154
 

(EXP.CONFG.OUT-3 PAGE) EXPANSION CONFIGURABLE OUTPUT (3) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 65 / 154
 

(EXP.CONFG.OUT-4 PAGE) EXPANSION CONFIGURABLE OUTPUT (4) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 66 / 154
 

(EXP.CONFG.OUT-5 PAGE) EXPANSION CONFIGURABLE OUTPUT (5) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 67 / 154
 

(EXP.CONFG.OUT-6 PAGE) EXPANSION CONFIGURABLE OUTPUT (6) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 68 / 154
 

(EXP.CONFG.OUT-7 PAGE) EXPANSION CONFIGURABLE OUTPUT (7) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 69 / 154
 

(EXP.CONFG.OUT-8 PAGE) EXPANSION CONFIGURABLE OUTPUT (8) page


POLARITY  Polarity (Normally Open, Normally Closed) 0-1 0
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTER START
33 ELECTRIC COOLING FAN AFTER STOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN 0 - 93 9
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 70 / 154
 

CONFIGURABLE OUTPUTS SELECTIONS


0 NOT USED
Output is not used

1 AUDIBLE ALARM
The output indicates that the internal sounder is operating. It may be use for external
sounder.

2 ALARM RESET
The output indicates that an alarm reset being performed. Once the alarm reset has been
completed, the output become inactive again. The output could be used to give an external
reset signal to external systems.

3 AUTO START INHIBIT


This output indicates that a digital input that has been configured as ‘auto start inhibit’ is
active.

4 AUXILIARY MAINS FAILURE


This output indicates that a digital input that has been configured as ‘auxiliary mains failure’
is active.

5 BATTERY HIGH VOLTAGE


This output indicates that a battery high voltage alarm has occurred.

6 BATTERY LOW VOLTAGE


This output indicates that a battery low voltage alarm has occurred.

7 CALLING FOR SCHEDULED RUN


This output indicates that a scheduled run has been called for. If the module is in the ‘auto’
and mains okey, the module will change mode to ‘test’ and the generator will run if no
shutdown alarms are present.

8 CHARGE ALTERNATOR FAILURE


This output indicates that a charging alternator failure has occurred

9 COMMON ALARM
This output indicates that a warning, electrical trip or shutdown alarm has been activated.

10 COMMON ELECTRICAL TRIP ALARM


This output indicates that an electrical trip alarm has been activated. This output can only be
reset by removal of the fault and by then pressing the RESET button.

11 COMMON SHUTDOWN ALARM


This output indicates that a shutdown alarm has been activated. This output can only be
reset by removal of the fault and by then pressing the RESET button or by using an external
‘alarm reset’ input.

12 COMMON WARNING ALARM


This output indicates that a warning alarm has been activated. This output is normally self-
resetting on removal of the fault.

13 COOLANT TEMPERATURE HIGH PRE-ALARM


This output indicates that a high engine coolant temperature warning (pre-alarm) has
occurred.

EAOM-210 FL.eng / ver 0.7


Pages 71 / 154
 

14 COOLANT TEMPERATURE HIGH SHUTDOWN


This output indicates that a high engine coolant temperature shutdown has occurred.

15 COOLING DOWN TIMER IN PROGRESS


This output source will be active when the cooling off-load timer is running.

16 DELAYED ALARMS ACTIVE


The output indicates that the delayed alarms now enabled. Can be used to control external
logic circuitry.

17 DIGITAL INPUT1 ACTIVE


This output indicates that digital input 1 is active.

18 DIGITAL INPUT2 ACTIVE


This output indicates that digital input 2 is active.

19 DIGITAL INPUT3 ACTIVE


This output indicates that digital input 3 is active.

20 DIGITAL INPUT4 ACTIVE


This output indicates that digital input 4 is active.

21 DIGITAL INPUT5 ACTIVE


This output indicates that digital input 5 is active.

22 DIGITAL INPUT6 ACTIVE


This output indicates that digital input 6 is active.

23 EXPNSION CONFIGURABLE INPUT1 ACTIVE


This output indicates that expansion configurable input 1 is active.

24 EXPNSION CONFIGURABLE INPUT2 ACTIVE


This output indicates that expansion configurable input 2 is active.

25 EXPNSION CONFIGURABLE INPUT3 ACTIVE


This output indicates that expansion configurable input 3 is active.

26 EXPNSION CONFIGURABLE INPUT4 ACTIVE


This output indicates that expansion configurable input 4 is active.

27 EXPNSION CONFIGURABLE INPUT5 ACTIVE


This output indicates that expansion configurable input 5 is active.

28 EXPNSION CONFIGURABLE INPUT6 ACTIVE


This output indicates that expansion configurable input 6 is active.

29 EXPNSION CONFIGURABLE INPUT7 ACTIVE


This output indicates that expansion configurable input 7 is active.

30 EXPNSION CONFIGURABLE INPUT8 ACTIVE


This output indicates that expansion configurable input 8 is active.

31 EARTH FAULT
This output indicates that the module has detected that an earth fault exists on the generator
output.

EAOM-210 FL.eng / ver 0.7


Pages 72 / 154
 

32 ELECTRIC COOLING FAN AFTER START


This output should energise as soon as engine has started so the fan should be running
when the engine is running. This output should continue to operate for Cooling Fan Time
parameter after engine has stopped.

33 ELECTRIC COOLING FAN AFTER STOP


This output indicates that can be made to energise for Cooling Fan Time parameter after the
engine shuts down (to run an electric cooling fan on the radiator).

34 EMERGENCY STOP
This output indicates that an emergency stop alarm has occurred.

35 FAIL TO START ALARM


This output indicates that the engine has not started after the specified number of attempts.

36 FAIL TO STOP ALARM


This output indicates that the generator has failed to stop within the selected time

37 FUEL RELAY ENERGISED


The output mimics the operation of the fuel relay. It can be used to control external logic
circuitry.

38 GAS ENGINE IGNITION OUTPUT


With the engaging of the starter the ignition delay is started. If the ‘minimum ignition speed’ is
reached after expiry of this time, the configurable relay output ‘ignition’ is set. When the
necessary engine shutdown process, firstly gas valve is de-energised. Then ignition output is
de-energised that after 5 seconds when the engine speed become lower than ‘minimum
ignition speed’.

39 GENERATOR AT REST
The output indicates that the generator is not running.

40 GENERATOR AVAILABLE
This output indicates when the generator is ready to accept load, i.e. after safety on and
warm up timers have timed out.

41 GENERATOR CLOSED AUXILIARY


This output indicates that a digital input that has been configured as ‘generator closed
auxiliary’ is active.

42 GENERATOR FAILED TO CLOSE


This output source has intended to be used to indicate a failure of the generator contactor or
breaker. It can only be used if the module is configured to use ‘generator closed auxiliary’
feedback.

43 GENERATOR FAILED TO OPEN


This output source has intended to be used to indicate a failure of the generator contactor or
breaker. It can only be used if the module is configured to use ‘generator closed auxiliary’
feedback.

44 GENERATOR HIGH FREQUENCY PRE-ALARM


This output indicates that a generator high frequency warning (pre-alarm) has occurred.

EAOM-210 FL.eng / ver 0.7


Pages 73 / 154
 

45 GENERATOR HIGH FREQUENCY SHUTDOWN


This output indicates that a generator high frequency shutdown has occurred.

46 GENERATOR HIGH VOLTAGE PRE-ALARM


This output indicates that a generator high voltage warning (pre-alarm) has occurred.

47 GENERATOR HIGH VOLTAGE SHUTDOWN


This output indicates that a generator high voltage shutdown has occurred.

48 GENERATOR LOAD INHIBIT


This output indicates that a digital input has been configured as ‘generator load inhibit’ is
active.

49 GENERATOR LOW FREQUENCY PRE-ALARM


This output indicates that a generator low frequency warning (pre-alarm) has occurred.

50 GENERATOR LOW FREQUENCY SHUTDOWN


This output indicates that a generator low frequency shutdown has occurred.

51 GENERATOR LOW VOLTAGE PRE-ALARM


This output indicates that a generator low voltage warning (pre-alarm) has occurred.

52 GENERATOR LOW VOLTAGE SHUTDOWN


This output indicates that a generator low voltage shutdown has occurred.

53 RESERVED

54 GENERATOR STOPPING
This output source indicates that the engine has been instructed to stop but has not come to
rest.

55 HORN OUTPUT
This output indicates that the horn alarm has occurred.

56 LAMP TEST
This output indicates that the module is performing a lamp test. Once the lamp test
completed, the output will become inactive again. The output can be used to feed a lamp test
on external modules or panel lamps.

57 LEVEL PREALARM
This output indicates that a level warning (pre-alarm) has occurred.

58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL


This output indicates that the magnetic pick up signal is not sufficient to be used by the
module for speed monitoring. The alarm can only operate if the speed signal fails to appear
during cranking. It is disabled if ‘multiple attempts to engage’ is selected. If the MPU fails
during engine running this would result in an underspeed alarm.

59 MAINTENANCE DUE ALARM


This output indicates that the generator is now due for maintenance either because it has
used all the available running hours or the periodic maintenance time has expired. To clear
the output a maintenance reset must be performed.

EAOM-210 FL.eng / ver 0.7


Pages 74 / 154
 

60 MAINS CLOSED AUXILIARY


This output indicates that a digital input that has been configured as ‘mains closed auxiliary’
is active.

61 MAINS FAILED TO CLOSE


This output source has intended to be used to indicate a failure of the mains contactor or
breaker. It can only be used if the module is configured to use ‘mains closed auxiliary’
feedback.

62 MAINS FAILED TO OPEN


This output source has intended to be used to indicate a failure of the mains contactor or
breaker. It can only be used if the module is configured to use ‘mains closed auxiliary’
feedback.

63 MAINS FAILURE
This output indicates that the module has sensed that a failure of the incoming AC mains
supply. This output will become active whenever the mains voltage or frequency goes out of
limits, or if the auxiliary mains failure input active (if used) and the mains transient timer has
expired.

64 MAINS HIGH FREQUENCY


This output indicates that the module has sensed that the incoming AC mains supply
frequency has exceeded the frequency limit setting.

65 MAINS HIGH VOLTAGE


This output indicates that the module has sensed that the incoming AC mains supply voltage
has exceeded the voltage limit setting.

66 MAINS LOAD INHIBIT


This output indicates that a digital input has been configured as ‘mains load inhibit’ is active.

67 MAINS LOW FREQUENCY


This output indicates that the module has sensed that the incoming AC mains supply
frequency has fallen below the frequency setting.

68 MAINS LOW VOLTAGE


This output indicates that the module has sensed that the incoming AC mains supply voltage
has fallen below the voltage limit setting.

69 NO LOADING COMMAND
This output indicates that the module is not calling of the generator contactor or breaker to be
closed. Should the module close the generator contactor this output will become inactive.

70 OIL PRESSURE LOW PRE-ALARM


This output indicates that a low oil pressure warning (pre-alarm) has occurred.

71 OIL PRESSURE LOW SHUTDOWN


This output indicates that a low oil pressure shutdown has occurred.

72 OVER CURRENT ALARM


This output indicates that the over current trip level has been reached.

73 OVERSPEED PRE-ALARM
This output indicates that the over speed warning (pre-alarm) has occurred.

EAOM-210 FL.eng / ver 0.7


Pages 75 / 154
 

74 OVERSPEED SHUTDOWN
This output indicates that the over speed shutdown has occurred.

75 PANEL LOCK
This output indicates that the module ‘panel lock’ is active. If the panel lock input is active,
the modul will not respond to operation of the Mode select or start buttons. This allows the
module to be placed into a spesific mode (such as auto) and then secured.

76 PRE-HEAT(during preheat timer)


The output controls the pre-heater. Pre-heat output is available for the duration of pre-heat
timer, which terminates prior to cranking.

77 PRE-HEAT(until end of cranking)


The output controls the pre-heater. As ‘ Pre-heat (during pre-heat timer)’ mode but pre-heat
is also available during cranking.

78 PRE-HEAT(until end of warming)


The output controls the pre-heater. As ‘ Pre-heat (until safety on)’ but pre-heat continues to
be available until the warm-up timer has elapsed.

79 PRE-HEAT(until end safety on)


The output controls the pre-heater. As ‘ Pre-heat (until end of cranking)’ but pre-heat is also
available while waiting for the delayed alarms to become active.

80 REMOTE START PRESENT


This output indicates that a digital input that has been configured as ‘remote start’ is active.
This output could be used to pass the remote start signal on to elsewhere in the control
system.

81 REMOTE STOP DELAY IN PROGRESS


This output source will be active to indicate that the return timer is running.

82 SHORT CIRCUIT
This output indicates that the module has detected a short circuit on the generator output.

83 START RELAY ENERGISED


The output mimics the operation of the start relay. Can be used to control external logic
circuitry.

84 STARTING ALARM
This output is used to supply an external sounder with a signal that the engine is about to
start. The output will be active during the start delay and pre-heat timer (if used).

85 STARTING ALARMS ARMED


The output indicates that the starting alarms are now enabled. It can be used to control
external logic circuitry. Starting alarms are armed as soon as module commences starting of
the engine and remain armed until the engine at rest.

86 STOP BUTTON PRESSED


This output indicates that the stop pushbutton being operated. Once the button is released
the output will become inactive.

87 SYSTEM IN AUTO MODE


The output indicates that the module is in the Auto mode.

EAOM-210 FL.eng / ver 0.7


Pages 76 / 154
 

88 SYSTEM IN MANUAL MODE


The output indicates that the module is in the Manual mode.

89 SYSTEM IN OFF MODE


The output indicates that the module is in the Stop mode.

90 SYSTEM IN TEST MODE


The output indicates that the module is in the Test mode.

91 UNDERSPEED SHUTDOWN
This output indicates that an underspeed shutdown has occurred.

92 UNDERSPEED PRE-ALARM
This output indicates that an underspeed warning (pre-alarm) has occurred.

93 WAITING FOR GENERATOR


This output indicates that the engine has been instructed to start but has not yet become
available. Once the generator becomes available this output will be in-active. (Available =
generator frequency and voltage levels are above the ‘loading’ levels set in the
configuration.)

(START TIMERS PAGE) START TIMERS page


MAINS TRANS.DELAY  Mains Transient Delay  sec 0 - 9999 0
REMOTE START DELAY  Remote Start Delay  sec 0 - 3600 4
REMOTE STOP DELAY  Remote Stop Delay  sec 0 - 250 4
PRE-HEAT  Pre-Heat  Sec 0 – 250 3
PRE-HEAT BYPASS  Pre-Heat Bypass  Min 0 – 250 0
SAFETY ON DELAY  Safety On Delay  sec 0 - 99 8
HORN DURATION  Horn Duration  sec (dis)0 - 999 60
CHRG.EXCITATION TIM  Charge Excitation Time  sec 0 – 99(cont.) 15
ELECTR.COOL.FAN TIM  Cooling Fan Time  sec 0 - 250 180
MAINS FAIL DELAY  Mains Fail Delay  sec 0.0 – 20.0 2.0

MAINS TRANSIENT DELAY


This timer dictates how long a mains anomaly must be present before the module will
respond to it. This can be used to prevent nuisance tripping when switching loads etc.

REMOTE START DELAY


This timer dictates how long the module will wait after it has received a remote start signal
before it will attempt to start. This prevent un-necessary starting on a fluctuating mains
supply etc.

REMOTE STOP DELAY


This timer dictates how long the module will wait after it has received a remote stop signal
before it will attempt to stop. This prevent un-necessary stopping on a fluctuating mains
supply etc.

PRE-HEAT
This timer dictates the duration that the pre-heat output will be active before an attempt is
made to start the engine. Once this timer is expired cranking will commence.

PRE-HEAT BYPASS
This feature allows the module to start a hot engine without performing an un-necessary pre-
heat delay. The bypass timer is triggered by the generator starting and actually being loaded.
If the generator started but does not achieve loading then the timer will not be triggered. The

EAOM-210 FL.eng / ver 0.7


Pages 77 / 154
 

bypass timer is initiated once the engine has come to rest. If any attempts to start are
requested within the duration of the bypass timer the start sequence will bypass the pre-heat
timer.

SAFETY ON DELAY
This timer dictates how long the module will ignore the Low Oil Pressure, High Engine
Temperature, Underspeed, Undervolts and any other inputs configured as active from safety
on. It allows the values such as oil pressure to rise to their operating values on starting
without triggering an alarm. Once the timer has expired all alarm conditions are monitored
again. If configured to use ‘fast loading’, should all the monitored conditions, such as oil
pressure, come to expected state prior to the end of the safety on timer, the timer will be
terminated prematurely ensuring maximum protection as soon as possible.

HORN DURATION
This timer dictates how long the horn will work after the last error detected. Once after this
timer ended module will do horn reset.

CHARGE EXCITATION TIME


Charge excitation was selectable as momentary / continuous operation.This timer dictates
how long the Charge excitation will active.

COOLING FAN TIME


This timer dictates how long the Cooling Fan will continue to operate.

MAINS FAIL DELAY


The unit uses this parameter to decide the mains fail.

(LOAD/STP.TIMERS PAGE) LOAD/STOPPING TIMERS page


WARM UP TIME  Warmup Timer  Sec 0 - 250 3
RETURN DELAY  Return Delay  Sec 0 – 3600 5
COOLING TIME  Cooling Timer  Sec 0 – 9999 60
GEN.FR.ERR.CNT.TIME  Generator Frequency Error Control Time  Sec 0.0 – 10.0 1.0
GEN.VL.ERR.CNT.TIME  Generator Voltage Error Control Time  Sec 0.0 – 10.0 1.0
FAIL TO STOP TIME  Fail To Stop Time  Sec 15 – 99 30

WARMUP TIMER
This timer is initiated once the engine is up and running. It delays loading the generator until
it has stabilised. Once this timer is expired the ‘Close generator’ signal will be given and the
generator is available to be loaded.

RETURN DELAY
This timer dictates how long the module will wait before it will un-load the generator (back to
the mains supply if AMF) and initialise it’s run-on and shutdown cycle. This is ensure that the
mains supply has stabilised before transferring the load back to mains.

COOLING TIMER
This is the time the generator is to run off-load once the load transfer signal has ceased. This
gives the engine time to cool down before shutdown.

GENERATOR FREQUENCY ERROR CONTROL TIME


If firstly generator frequency is out of under and over set points this timer is initiated. If
generator frequency is out of under and over set points when this timer expires a ‘generator
frequency error’ alarm signal is generated.

EAOM-210 FL.eng / ver 0.7


Pages 78 / 154
 

GENERATOR VOLTAGE ERROR CONTROL TIME


If firstly generator voltage is out of under and over set points this timer is initiated. If
generator voltage is out of under and over set points when this timer expires a ‘generator
voltage error’ alarm signal is generated.

FAIL TO STOP TIME


Once the module has given a shutdown signal to the engine it expects the engine to come to
rest. It monitors the Oil pressure and speed sensing sources and if they still indicate engine
movement when this timer expires a ‘Fail To Stop’ alarm signal is generated.

(BREAKERS PAGE) BREAKERS page


HARDW.BREAKER SELCT  Hardware Breaker Selection  0–2 0
GEN.CLOS.BREK.C.TYP  Gen Close Breaker Contact Type  NO/NC 0–1 0
GEN.CLOS.BREK.R.TYP  Gen Close Breaker Relay Type  NOR/PULS 0–1 0
GEN.CLOSE TIMER  Gen Close Timer  Sec 1 – 250 5
GEN.OPEN.BREK.C.TYP  Gen Open Breaker Contact Type  NO/NC 0–1 0
GEN.OPEN.BREK.R.TYP  Gen Open Breaker Relay Type  NOR/PULS 0–1 0
GEN.OPEN TIMER  Gen Open Timer  Sec 1 – 250 5
MAIN CLS.BREK.C.TYP  Main Close Breaker Contact Type  NO/NC 0–1 0
MAIN CLS.BREK.R.TYP  Main Close Breaker Relay Type  NOR/PULS 0–1 0
MAINS CLOSE TIMER  Mains Close Timer  Sec 1 – 250 5
MAIN OPN.BREK.C.TYP  Main Open Breaker Contact Type  NO/NC 0–1 0
MAIN OPN.BREK.R.TYP  Main Open Breaker Relay Type  NOR/PULS 0–1 0
MAINS OPEN TIMER  Mains Open Timer  Sec 1 – 250 5
BREKR.CLOS.PULS.TIM  Breaker Close Pulse Time  Sec 0.0 – 10.0 0.5
BREKR.OPEN.PULS.TIM  Breaker Open Pulse Time  Sec 0.0 – 10.0 0.5
TRANSFER TIME  Transfer Time  Sec 0 - 250 2

HARDWARE BREAKER SELECTION


0- Mains and Gen schalters have only close drives and if close drive off schalter will open.
Parameters; GEN CLOSE BREAKER CONTACT TYPE, GEN CLOSE TIMER(if gen closed 
input selected), GEN OPEN TIMER(if gen closed input selected), MAIN CLOSE BREAKER 
CONTACT TYPE, MAINS CLOSE TIMER(if mains closed input selected), MAINS OPEN 
TIMER(if mains closed input selected), TRANSFER TIME.

Example: If Hardware Breaker Selection parameter is selected as 0;


For closing For opening
Gen. Shalter Gen. Shalter

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]

Gen. Shalter Closed Opened

1- Mains and Gen schalters have only close drives, when want to schalter close, close
breaker output on and after 1 sec. open breaker output on and after breaker close pulse time
open breaker output will off. When want to schalter open close breaker output and open
breaker output will off.
Parameters; GEN CLOSE BREAKER CONTACT TYPE, GEN CLOSE TIMER(if gen closed 
input selected), GEN OPEN BREAKER CONTACT TYPE, GEN OPEN TIMER(if gen closed 
input selected), MAIN CLOSE BREAKER CONTACT TYPE, MAINS CLOSE TIMER(if mains 
closed input selected), MAIN OPEN BREAKER CONTACT TYPE, MAINS OPEN TIMER(if 
mains closed input selected),BREAKER CLOSE PULSE TIME, TRANSFER TIME.

EAOM-210 FL.eng / ver 0.7


Pages 79 / 154
 

Example: If Hardware Breaker Selection parameter is selected as 1;


For closing For opening
Gen. Shalter Gen. Shalter

Breaker close
pulse time

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]

1s
Gen. Open Out.
(NO)
t[s]

Gen. Open Out.


(NC)
t[s]

Gen. Shalter Closed Opened

2- USER CONFIGURED: User can select all the schalter types.


Parameters; GEN CLOSE BREAKER CONTACT TYPE, GEN CLOSE BREAKER RELAY 
TYPE, GEN CLOSE TIMER(if gen closed input selected), GEN OPEN BREAKER CONTACT 
TYPE, GEN OPEN BREAKER RELAY TYPE, GEN OPEN TIMER(if gen closed input 
selected), MAIN CLOSE BREAKER CONTACT TYPE, MAIN CLOSE BREAKER RELAY 
TYPE, MAINS CLOSE TIMER(if mains closed input selected), MAIN OPEN BREAKER 
CONTACT TYPE, MAIN OPEN BREAKER RELAY TYPE, MAINS OPEN TIMER(if mains 
closed input selected), BREAKER CLOSE PULSE TIME(if Gen Close Breaker Relay Type or 
Main Close Breaker Relay Type parameter is selected as 1), BREAKER OPEN PULSE 
TIME(if Gen Open Breaker Relay Type or Main Open Breaker Relay Type parameter is 
selected as 1), TRANSFER TIME.

Example-1: If Hardware Breaker Selection parameter is selected as 2 (user configured),


Gen. Close Breaker Relay Type parameter is selected as 0 (NOR) and Gen. Open Breaker
Relay Type parameter is selected as 0 (NOR);
For closing For opening For closing For opening
Gen. Shalter Gen. Shalter Gen. Shalter Gen. Shalter

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]

Gen. Open Out.


(NO) t[s]

Gen. Open Out.


(NC) t[s]

Gen. Shalter Closed Opened Closed Opened

EAOM-210 FL.eng / ver 0.7


Pages 80 / 154
 

Example-2: If Hardware Breaker Selection parameter is selected as 2 (user configured),


Gen. Close Breaker Relay Type parameter is selected as 1 (PULSE) and Gen. Open
Breaker Relay Type parameter is selected as 0 (NOR);
For closing For opening For closing For opening
Gen. Shalter Gen. Shalter Gen. Shalter Gen. Shalter

Breaker close Breaker close


pulse time pulse time

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]

Gen. Open Out.


(NO) t[s]

Gen. Open Out.


(NC) t[s]

Gen. Shalter Closed Opened Closed Opened

Example-3: If Hardware Breaker Selection parameter is selected as 2 (user configured),


Gen. Close Breaker Relay Type parameter is selected as 0 (NOR) and Gen. Open Breaker
Relay Type parameter is selected as 1 (PULSE);
For closing For opening For closing For opening
Gen. Shalter Gen. Shalter Gen. Shalter Gen. Shalter

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]
Breaker open Breaker open
pulse time pulse time

Gen. Open Out.


(NO) t[s]

Gen. Open Out.


(NC) t[s]

Gen. Shalter Closed Opened Closed Opened

EAOM-210 FL.eng / ver 0.7


Pages 81 / 154
 

Example-4: If Hardware Breaker Selection parameter is selected as 2 (user configured),


Gen. Close Breaker Relay Type parameter is selected as 1 (PULSE) and Gen. Open
Breaker Relay Type parameter is selected as 1 (PULSE);
For closing For opening For closing For opening
Gen. Shalter Gen. Shalter Gen. Shalter Gen. Shalter

Breaker close Breaker close


pulse time pulse time

Gen. Closed Out.


(NO) t[s]

Gen. Closed Out.


(NC) t[s]
Breaker open Breaker open
pulse time pulse time

Gen. Open Out.


(NO) t[s]

Gen. Open Out.


(NC) t[s]

Gen. Shalter Closed Opened Closed Opened

GEN. CLOSE TIMER


This is used to monitor the closure of the generator contactor or breaker. It will only operate if
an auxiliary input is configured as ‘Generator Closed Auxiliary’ and connected to the auxiliary
on the generator contactor or breaker. Once a generator closed signal is issued the ‘gen
close timer’ is initiated. Should the ‘Generator Closed Auxiliary’ input become active the timer
the ‘gen close timer’ is cancelled. If the timer expires and the ‘Generator Closed Auxiliary’
has not become active the module will issue a ‘generator failed to close’ alarm.

GEN. OPEN TIMER


This is used to monitor the opening of the generator contactor or breaker. It will only operate
if an auxiliary input is configured as ‘Generator Closed Auxiliary’ and connected to the
auxiliary on the generator contactor or breaker. Once a generator open signal is issued the
‘gen open timer’ is initiated. Should the ‘Generator Closed Auxiliary’ input become in-active
the timer ‘gen open timer’ is cancelled. If the timer expires and the ‘Generator Closed
Auxiliary’ has not become in-active the module will issue a ‘generator failed to open’ alarm.

MAINS CLOSE TIMER


This is used to monitor the closure of the mains contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Mains Closed Auxiliary’ and connected to the auxiliary on the
mains contactor or breaker. Once a mains closed signal is issued the ‘mains close timer’ is
initiated. Should the ‘Mains Closed Auxiliary’ input become active the timer the ‘mains close
timer’ is cancelled. If the timer expires and the ‘Mains Closed Auxiliary’ has not become
active the module will issue a ‘mains failed to close’ alarm.

MAINS OPEN TIMER


This is used to monitor the opening of the mains contactor or breaker. It will only operate if
an auxiliary input is configured as ‘Mains Closed Auxiliary’ and connected to the auxiliary on
the mains contactor or breaker. Once a mains open signal is issued the ‘mains open timer’ is
initiated. Should the ‘Mains Closed Auxiliary’ input become in-active the timer the ‘mains
open timer’ is cancelled. If the timer expires and the ‘Mains closed auxiliary’ has not become
in-active the module will issue a ‘mains failed to open’ alarm.

EAOM-210 FL.eng / ver 0.7


Pages 82 / 154
 

BREAKER CLOSE PULSE TIME


This is used to determine the duration of the Mains and Generator close signals. This timer is
only used if Pulsed outputs are configured to be used.

BREAKER OPEN PULSE TIME


This is used to determine the duration of the Mains and Generator close signals. This timer is
only used if Pulsed outputs are configured to be used.

TRANSFER TIME
This is used to allow for fixed duration transfer breaks when switching from mains to
generator and back. It can be used to ensure that the supply is removed from the load for
fixed period of time to allow pumps/motors to come to rest etc.

(LCD CONFIG.PAGE) LCD CONFIGURATION page


ERR.MESS SCROLL TIM  Scroll Time For Error Messages Sec 0 - 99 4
DIGITAL CONTRAST  Digital Contrast 0 – 15 8
BACKLIGHT ON/OFF  Backlight On/Off 0-1 0

AUTO SCROLL TIMER


Error messages are displayed eighth line of LCD Display. If more than one error condition is
present, each of them is displayed during time defined by Auto Scroll Timer parameter.

DIGITAL CONTRAST
It is used to change contrast of LCD Display.

BACKLIGHT ON/OFF
0- Backlight on. 1- Backlight off.

(ENG.MAINT.ALARM PAGE) ENGINE MAINTENANCE ALARM page


RUNN.HOURS INTERVAL Running Hours Interval  HOUR (dis)0 - 9999 5000
MAINT.DATE INTERVAL Maintenance Date Interval  MONTH (dis)0 - 12 6
Force Engine Shutdown When 
ENG.STP.WH.MANT.E/D  - ENAB DIS DIS
Maintenance Is Due En/Dis 
ENGIN.RUN.HOUR(LSB)  Engine Running Hour (Lsb) - 0 - 255 0
ENGINE RUNNING HOUR  Engine Running Hour  - 0 – 255 0
ENGIN.RUN.HOUR(MSB)  Engine Running Hour(Msb) - 0 - 14 0

(COMMUNICATION PAGE) COMMUNICATION page


SLAVE ADDRESS  Slave Address  1 - 247 1
Baud Rate 
0=1200 
1=2400 
BAUD RATE  0-4 3
2=4800 
3=9600 
4=19200 
PARITY  Parity; 0= NONE, 1= ODD, 2= EVEN  0-2 0
STOP BIT  Stop Bit  0–1 0

EAOM-210 FL.eng / ver 0.7


Pages 83 / 154
 

(WR.CALENDR&EXER.PAGE) WORKING CALENDAR & EXERCISE page


Working calendar working time on 
WORK.PERIOD ON MON. min (dis)0 - 1440 1440
Monday 
Working calendar work start time on 
WORK.START TIME MON  hour-min 0.0 – 23.59 0.0
Monday 
Working calendar working time on 
WORK.PERIOD ON TUE. min (dis)0 - 1440 1440
Tuesday 
Working calendar work start time on 
WORK.START TIME TUE  hour-min 0.0 – 23.59 0.0
Tuesday 
Working calendar working time on 
WORK.PERIOD ON WED. min (dis)0 - 1440 1440
Wednesday 
Working calendar work start time on 
WORK.START TIME WED  hour-min 0.0 – 23.59 0.0
Wednesday 
Working calendar working time on 
WORK.PERIOD ON THU. min (dis)0 - 1440 1440
Thursday 
Working calendar work start time on 
WORK.START TIME THU  hour-min 0.0 – 23.59 0.0
Thursday 
WORK.PERIOD ON FRI. Working calendar working time on Friday  min (dis)0 - 1440 1440
Working calendar work start time on 
WORK.START TIME FRI  hour-min 0.0 – 23.59 0.0
Friday 
Working calendar working time on 
WORK.PERIOD ON SAT. min (dis)0 - 1440 1440
Saturday 
Working calendar work start time on 
WORK.START TIME SAT  hour-min 0.0 – 23.59 0.0
Saturday 
WORK.PERIOD ON SUN. Working calendar working time on Sunday  min (dis)0 - 1440 1440
Working calendar work start time on 
WORK.START TIME SUN  Hour-min 0.0 – 23.59 0.0
Sunday 
Generator exercise working time on 
EXER.WORKING PERIOD  min (dis)0 - 99 DIS
related day 
EXER.WR.DAY OF WEEK  Generator exercise working day of week  1–7 1
Generator exercise work start time on 
EXER.WORK.START TIM  hour-min 0.0 – 23.59 0.0
related day 

Please enter the days of the weekly workdays for Working Function. Example:
WORK.PERIOD ON MON. (dis)0 The working function is Mondays disabled.
(1440) The working function is enabled whole day.
(120) The working function is every Monday enabled for 120
 minutes.
WORK.START TIME MON 12.20 The working function is every Monday started
 at 12.20 o'clock (if it is enabled)

WORK.PERIOD ON TUE. (dis)0 The working function is Tuesdays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Tuesday enabled for 120
minutes.
WORK.START TIME TUE 12.20 The working function is every Tuesday started
at 12.20 o'clock (if it is enabled)

WORK.PERIOD ON WED. (dis)0 The working function is Wednesdays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Wednesday enabled for
 120 minutes.
WORK.START TIME WED 12.20 The working function is every Wednesday started
 at 12.20 o'clock (if it is enabled)

WORK.PERIOD ON THU. (dis)0 The working function is Thursdays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Thursday enabled for 120
 minutes.

EAOM-210 FL.eng / ver 0.7


Pages 84 / 154
 

WORK.START TIME THU 12.20 The working function is every Thursday started
at 12.20 o'clock (if it is enabled)

WORK.PERIOD ON FRI. (dis)0 The working function is Fridays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Friday enabled for 120
 minutes.
WORK.START TIME FRI 12.20 The working function is every Friday started
at 12.20 o'clock (if it is enabled)

WORK.PERIOD ON SAT. (dis)0 The working function is Saturdays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Saturday enabled for 120
 minutes.
WORK.START TIME SAT 12.20 The working function is every Saturday started
at 12.20 o'clock (If it is enabled)

WORK.PERIOD ON SUN. (dis)0 The working function is Sundays disabled.


(1440) The working function is enabled whole day.
(120) The working function is every Sunday enabled for 120
minutes.
WORK.START TIME SUN 12.20 The working function is every Sunday started
at 12.20 o'clock (If it is enabled)

Please enter the day of the week for Exercise Function. Example:
EXER.WORKING PERIOD (dis)0 The exercise function is disabled.
(10) The exercise function is enabled for 10 minutes.
EXER.WR.DAY OF WEEK 1=Monday, 2=Tuesday, 3=Wednesday, 4=Thursday,
5=Friday, 6=Saturday, 7=Sunday.
EXER.WORK.START TIM 12.20 The exercise function is started at 12.20 o'clock
 (If it is enabled)

(DATE SETUP PAGE) DATE SETUP page


YEAR  YEAR  0 - 99
MONTH  MONTH  1 - 12
DATE  DATE  1 - 31
DAY  DAY  1-7
HOUR  HOUR  0 - 23
MINUTE  MIN  0 - 59
SECOND  SEC  0 - 59

(PASSWORD PAGE) PASSWORD page


OPERATOR PASSWORD  OPERATOR PASSWORD  0 - 9999 0
TECHNICIAN PASSWORD  TECHNICIAN PASSWORD  0 - 9999 0

OPERATOR PASSWORD
Use this option to change the Operator password. This password allows access to operator
parameters section.
TECHNICIAN PASSWORD
Use this option to change the Technician password. It allows access to both operator and
technician parameters section.

To prevent to changing unit program parameters by unauthorised personnel don’t


allow to the learning operator and technician passwords by the others. In case of this
situation, change passwords immediately.

EAOM-210 FL.eng / ver 0.7


Pages 85 / 154
 

3.6 Pc Interface
The PC interface kit ( EAOM-210 FL/PCIK ) comprises the following:
9 pin D connector/FCC68(4 pin) connection lead with 2 meters cable
EAOM-210 FL V00/SW Communication software (CD)

3.6.1 Technical Specifications


RS-232 serial communication with Modbus RTU protocol
Baud Rate from 1200 to 19200
8 data bits, Parity; None, Odd or Even, Stop Bit; 0 or 1
Maximum allowable cable length is 10 meters

3.6.2 RS-232 Serial Interface, Programming The Device Over PC or Modem

3.6.2.1 Cable Connection Between RS-232 Terminal of the Device and PC

EAOM-210 FL PC
9 pin D connector 9 pin D connector
female male

White

Brown

Green

3.6.2.2 Cable Connection Between RS-232 Terminal of the Device and Modem

EAOM-210 FL MODEM
9 pin D connector 9 pin D connector
male female
Green

Yellow
White

Brown

3.6.3 Installation Instruction


3.6.3.1 Minimum system requirements
Processor :486 66MHz
Operating Systems :Windows95/98, Windows NT
Ram :16 Mbyte
Monitor :14” SVGA (640x480 resolution)
Fixed Disk Free Space :1 Mbyte
Disk Drive :CD-ROM
Communication :An RS232 communication port is needed to
communicate with the EAOM-210 FL Unit

3.6.3.2 Installing EAOM-210 FL V00/SW


Insert the software CD into the CD-ROM drive on the PC
Double click on MyComputer
Then double click on CD-ROM drive

EAOM-210 FL.eng / ver 0.7


Pages 86 / 154
 

There will be a short delay while the CD-ROM is accessed, then the disk contents will be
displayed.
Double click on “Install.exe”.
EAOM-210 FL V00/SW will be installed automatically on to your PC in its own
folder(directory). It will also create “START MENU” items.

3.6.3.3 To Run EAOM-210 FL V00/SW communication software


Press the START icon
Then select Programs  EAOM-210 FL V00 SW(Folder)  EAOM-210 FL V00
Then click on EAOM-210 FL V00

When the program runs firstly, a window is shown to determine how the connection will be
established: over modem or RS-232 communication port. This selection is made with the
‘Connect with Modem’ check box. If the comport settings are correct, when ‘Connect’
button is pressed, connection is established. With ‘Add New Phone Number’ button, user
can access to the window below and save the location name and phone number for using to
connect with modem.

EAOM-210 FL.eng / ver 0.7


Pages 87 / 154
 

 Firstly, enter phone number and location name (It is used to remember where the phone
number belongs) and press ‘Ok’ button for saving these values.

When the connection is established, main screen is shown;

EAOM-210 FL.eng / ver 0.7


Pages 88 / 154
 

3.6.4 Description
EAOM-210 FL unit communicates with PC by means of EAOM-210 FL/PCIK. With EAOM-210
FL V00/SW ,the EAOM-210 FL unit’s parameters and status information can be reached over
PC easily. Operator and Technician parameters can be viewed. Parameters are password
protected.

3.6.4.1 Main Menu

File Menu
This menu allows the user to save configuration files to the disc, read from disc and write
to disc.

Open :This menu allows the user to load the registered configuration files to PC.
For example: Click 'Open' in File menu. Choose configuration file which includes operator
or technician parameters on Open Dialog Box. When user clickss 'Open' button on Open
Dialog Box parameters will be transferred to PC window.
Save :This menu allows the user to save the parameters with a name defined by user.
For example: Click 'Save' in File menu. After choosing where to save the file, enter the file
name. When user clicks 'Save' button on Save Dialog Box, all parameters will be saved to
the file that user determine.
Preview : This menu allows the user to preview the operator parameters, when the user to
come into the Operator Parameters section. It allows the user to preview the technician
parameters, when the user to come into the Technician Parameters section. It allows the
user to preview the Event Logs, when the user to come into the Events section.
Print :This menu allows the user to print the parameters.
Exit :With this menu user can exit from the EAOM-210 FL V00/SW.

Window Menu

Explorer: This menu allows the user to reach quickly the Observation, Operator
Parameters and Technician Parameters sections.
Toolbar:  Toolbar on/off 

EAOM-210 FL.eng / ver 0.7


Pages 89 / 154
 

Program Menu
This menu is active during the Operator or Technician Parameters Section is open. With
this menu user can load parameters from EAOM-210 FL unit to PC or from PC to EAOM-210
FL unit.

Download :With this menu user can load parameters from PC to EAOM-210 FL.
For loading parameters from PC to EAOM-210 FL follow the steps below.
Download This Page to the Controller:
While the operator parameters window is showing, If user clicks “Download This Page to
the Controller” in Program menu, only parameters in the related page is loaded from PC to
device. While the technician parameters window is showing, If user clicks “Download This
Page to the Controller” in Program menu, only parameters in the related page is loaded
from PC to device.
Download All Parameters to the Controller:
While the operator parameters window is showing, If user clicks “Download All Parameters
to the Controller” in Program menu, all of the operator parameters is loaded from PC to
device. While the technician parameters window is showing, If user clicks “Download All
Parameters to the Controller” in Program menu, all of the technician parameters is loaded
from PC to device.

Upload :User can load the parameters that is stored on EAOM-210 FL unit to PC.
For loading parameters from EAOM-210 FL unit to PC follow the steps below.
Upload This Page from the Controller:
While the operator parameters window is showing, If user clicks “Upload This Page from
the Controller” in Program menu, only parameters in the related page is loaded from
device to PC. While the technician parameters window is showing, If user clicks “Upload
This Page from the Controller” in Program menu, only parameters in the related page is
loaded from device to PC.
Upload All Parameters from the Controller:
While the operator parameters window is showing, If user clicks “Upload All Parameters
from the Controller” in Program menu, all of the operator parameters is loaded from
device to PC. While the technician parameters window is showing, If user clicks “Upload All
Parameters from the Controller” in Program menu, all of the technician parameters is
loaded from device to PC.

Add New Phone Number:


User can be saved the phone number which is used for connecting with the modem.

EAOM-210 FL.eng / ver 0.7


Pages 90 / 154
 

Observation Menu
There are four sub-menus in this menu: Measurement Values, Failures, Events and Output
& Modes.

Measurement Values:

In this window the values listed below can be observed:


Mains volts (L1-N, L2-N, L3-N)
Mains volts (L1-L2, L2-L3, L3-L1)
Mains Hz
Generator volts (L1-N, L2-N, L3-N)
Generator volts (L1-L2, L2-L3, L3-L1)
Generator Hz
Load amps (IL1, IL2, IL3)
Earth current (IEA)
Generator pf 
Generator kVA
Generator kW
Generator kVAr
Generator kVAh
Generator kWh

EAOM-210 FL.eng / ver 0.7


Pages 91 / 154
 

Generator kVArh
Next maintenance
Working time
Real time
Charge generator voltage
Battery Voltage
Level
Pressure
Temperature
Engine speed (Rpm)

Failures:

In this window the failures listed below can be observed:


Failed to start
Low oil pressure
High temperature
Voltage failure
Speed failure
Charging fail
Spare 1
Spare 2
Spare 3
And the 39 different error messages (if Expansion Module is selected as disable) or
the 47 different error messages (if Expansion Module is selected as enable).

EAOM-210 FL.eng / ver 0.7


Pages 92 / 154
 

Events:

In this window the last 32 Event logs can be observed:

EAOM-210 FL.eng / ver 0.7


Pages 93 / 154
 

Outputs & Modes:

In this window the parameters listed below can be observed:

Outputs:
Configurable Output1
Configurable Output2
Configurable Output3
Configurable Output4
Configurable Exp Output1(if Expansion Module is selected as enable).
Configurable Exp Output2(if Expansion Module is selected as enable).
Configurable Exp Output3(if Expansion Module is selected as enable).
Configurable Exp Output4(if Expansion Module is selected as enable).
Configurable Exp Output5(if Expansion Module is selected as enable).
Configurable Exp Output6(if Expansion Module is selected as enable).
Configurable Exp Output7(if Expansion Module is selected as enable).
Configurable Exp Output8(if Expansion Module is selected as enable).
Start
Mains open and button for remote control
Mains close and button for remote control
Generator open and button for remote control
Generator close and button for remote control
Solenoid

EAOM-210 FL.eng / ver 0.7


Pages 94 / 154
 

Modes:
Manual mode and button for remote control
No Load Test mode and button for remote control
Auto mode and button for remote control
Program
Off mode and button for remote control
Engine status:
Start position and button for remote control
Stop position and button for remote control

Failure Reset:
Reset button for remote control

Operator Parameters Menu


Operator can reach the parameters in this menu. Parameters are password protected.
When the operator password is entered, it is compared with operator password that is
registered on EAOM-210 FL unit.

Entering To Operator Parameters Section


Click “Mains Level” in Operator Parameter menu. Then Operator Password is monitored.
Enter the Operator Password and click OK button. If the password is correct, first page of 
the operator parameters (Mains Levels page) will be viewed.

EAOM-210 FL.eng / ver 0.7


Pages 95 / 154
 

Technician Parameters Menu


All parameters can be viewed in this menu. Parameters are password protected. When the
technician password is entered, it is compared with technician password that is registered
on EAOM-210 FL unit.

Entering To Technician Parameters Section


Click “Mains Level” in Technician Parameter menu. Then Technician Password is
monitored. Enter the Technician Password and click OK button. If the password is correct,
first page of the technician parameters (Mains Levels page) will be viewed.

EAOM-210 FL.eng / ver 0.7


Pages 96 / 154
 

Adjusment Page (Calibration) Menu


There is one sub-menu in this menu: Adjusment.

Adjusment (Calibration):
Click “Adjusment” in Adjasment Page menu. Then Technician Password is monitored. Enter
the Technician Password and click OK button. If the password is correct, the ADJUSMENT
section will be viewed.

EAOM-210 FL.eng / ver 0.7


Pages 97 / 154
 

Setting Menu

Click “Comport Setting” in Setting menu. Then Comport Settings window is monitored.And
then change Comport Settings, Slave ID parameters and click OK button.

EAOM-210 FL.eng / ver 0.7


Pages 98 / 154
 

Connect: With this menu, the window below is observed. According to the ‘Connect with
Modem’ check status, connection can be establish over RS-232 port or modem. If the
comport settings are done correctly, when the ‘Connect’ button is pressed, connection is
established.

Disconnect: If the connection is established over modem or RS-232 port, connection can
be cut off with this selection.

Help Menu

Help: This menu allows the user to get information about mention to used the program and
the menus in the program.
About: Click “About” in Help menu. It gives information about the PC software version and
MCU software version to the user.

EAOM-210 FL.eng / ver 0.7


Pages 99 / 154
 

Section 4 Commissioning

These commissioning checks may interfere with the power supply to the load. Therefore
they should not be carried out with a mission-critical load connected to the system.

4.1 Manual operation


1. Check that the unit is correctly wired and that the wiring is of a standard and rating
compatible with the system.

2. Check that the correct fuses are fitted.

3. Program the unit as detailed in Section 3 Definition Of Front Panel And Programming.

4. Take temporary steps to prevent the engine from starting . (for example, disable the
fuel solenoid.)

5. After a visual inspection to ensure it is safe to proceed, connect the battery supply.

6. On the EAOM-210 FL, press the Man (29) button. The associated LED (12) should light.

7. Press the Engine Start (21) button. At this moment the LED (7) lights on.

8. Check that the engine start sequence commences. The starter motor should run for the
programmed time period (cranking time) for the pre-set number of times (number of start
attempts).

9. Check that the Failed to Start LED flashes and the LED (7) lights off.

10. Check the unit will change to the OFF mode and the LED (9) lights on.

11. Restore the engine to operational state (reconnect the fuel solenoid).

12. Press the Man (29) button. The LED (12) will light on.

13. Press the Engine Start (21) button. The LED (7) will light on.

14. Check the start sequence, as follows:


the starter motor runs
the engine starts
the starter motor disengages once the engine is running.

If not, check that the engine is fully operational (fuel available etc.) and check the wiring
and programming of the EAOM-210 FL.

15. Check that the engine runs up to its operating speed. If not and an alarm is present,
check that the alarm is valid and then check the input wiring.

16. Press the Engine Stop (22) button. At this moment the LED (8) will light on. The engine
should stop. Allow time for the engine to come to rest.

EAOM-210 FL.eng / ver 0.7


Pages 100 / 154
 

4.2 Auto Operation

1. Check that the mains is connected to the unit and is present.

2. Check the mains voltage readings on the display.

3. At the EAOM-210 FL, press the Auto (27) button. The LED (10) on the button should
light.

4. Switch off the mains supply to the unit. Check that the generator starts and, after a
delay, the load is transferred to the generator.

5. Restore the mains supply to the unit. Check that, after a delay, the load is transferred
back to the mains and the generator, after a further delay, shuts down.

4.3 Test Mode Operation

1. Check that the mains is connected to the unit.

2. Press the Test (28) button. At this moment the LED (11) will light on.

3. Check that the generator starts and that the load is still connected to the mains.

4. Switch off the mains supply. Check that the contactors change over to connect the load
to the generator. Check also that the Auto (10) LED is lit. The unit changes operating mode
to AUTO Mode automatically.

5. Restore the mains supply. Check that the contactors reconnect the load to the mains
supply.

6. Check that the generator shuts down with cool-down period.

EAOM-210 FL.eng / ver 0.7


Pages 101 / 154
 

Section 5 Operation

5.1 Controls and Indicators


5.1.1 LCD Display Description:

Mains & Load Page


Current page name
 MAINS & LOAD Measurement values
L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A  Engine Status
Working mode IEA: 63A 
 AUTO CRANKNG ATTEMP Error Messages
OVER SPEED PREALARM!

PROG

128x64 Dot-matrix LCD display. It consist of 10 main working pages (screens). Every screen

has got 8 lines. Seventh and eighth lines are common in all pages. Use the and
buttons to select which working page (screen) is to be displayed. For details see Example-
1: Changing page with Next and Previous buttons.

There are 10 working pages in the LCD display, as follows;

1- Mains & Load Page:

 MAINS & LOAD


 A 
L12:380Vac IL1: 126
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

•  L12 - Mains voltage L1-L2


•  L23 - Mains voltage L2-L3
•  L31 - Mains voltage L3-L1
•  Fq - Mains frequency
•  IL1 - Load current
•  IL2 - Load current
•  IL3 - Load current
•  IT - Total current
•  IEA - Earth current
•  AUTO - Working mode
•  CRANKNG ATTEMP - Engine cranking process is executing. (Engine status)

EAOM-210 FL.eng / ver 0.7


Pages 102 / 154
 

  OVER SPEED PREALARM - This message indicates that the over speed warning

(pre-alarm) has occured. (Error message). If more than one error condition is
present, all of them is displayed sequencely in time defined by “Scroll Time For
Error Messages” parameter. Possible error messages are:

BATTERY HIGH ERROR! : Battery High Error.


BATTERY LOW ERROR! : Battery Low Error.
CANBUS ERROR! : Can Bus Error.
EARTH FAULT ERROR! : Earth Fault Error
EARTH FAULT EL.TRIP! : Earth Fault Electrical Trip
EARTH FAULT WARNING! : Earth Fault Warning
EMERGENCY STOP ERR! : Emergency Stop.
EXPAN. SPARE-1 ERROR! : Expansion Spare 1 Error.
EXPAN. SPARE-2 ERROR! : Expansion Spare 2 Error.
EXPAN. SPARE-3 ERROR! : Expansion Spare 3 Error.
EXPAN. SPARE-4 ERROR! : Expansion Spare 4 Error.
EXPAN. SPARE-5 ERROR! : Expansion Spare 5 Error.
EXPAN. SPARE-6 ERROR! : Expansion Spare 6 Error.
EXPAN. SPARE-7 ERROR! : Expansion Spare 7 Error.
EXPAN. SPARE-8 ERROR! : Expansion Spare 8 Error.
GEN BR.NOT CLOS.ALR! : Generator Breaker Not Closed alarm
GEN BR.NOT OPEN.ALR! : Generator Breaker Not Opened alarm
GEN OVER FRQ.PREAL! : Generator Over Frequency Prealarm
GEN OVER VOL.PREAL! : Generator Over Voltage Prealarm
GEN UNDER FRQ.PREAL! : Generator Under Frequency Prealarm
GEN UNDER VOL.PREAL! : Generator Under Voltage Prealarm
GENERATOR STOP ERR! : Generator Stop Error.
LEVEL ERROR! : Fuel Level Error.
LEVEL PREALARM! : Fuel Level Prealarm.
MULTPLE ENGAGE FAIL! : Multiple engage fail
MAINS BR.NOT CL.ALR! : Mains Breaker Not Closed alarm
MAINS BR.NOT OP.ALR! : Mains Breaker Not Opened alarm
MAINTENANCE ERROR! : Maintenance error
OVER CURRNT EL.TRIP! : Over Current Electrical Trip
OVER CURRENT ERROR! : Over Current Error
OVER CURRENT WARNNG! : Over Current Warning
OVER SPEED ERROR! : Over speed error
OVER SPEED PREALARM! : Over speed pre-alarm
PRESSURE PREALARM! : Oil Pressure Prealarm.
SHORT CIRCT EL.TRIP! : Short Circuit Electrical Trip
SHORT CIRCUIT ERROR! : Short Circuit Error
SHORT CIRCUIT WARNN! : Short Circuit Warning
SPARE-4 ERROR! : Spare 4 Error.
SPARE-5 ERROR! : Spare 5 Error.
SPARE-6 ERROR! : Spare 6 Error.
SPEED LOSS ERROR! : Speed loss error
TEMPERAT. PREALARM! : Generator Temperature Prealarm.
UNDER SPEED ERROR! : Under speed error
UNDER SPED PREALARM! : Under speed pre-alarm

EAOM-210 FL.eng / ver 0.7


Pages 103 / 154
 

2- Generator & Load Page:

GENERATOR & LOAD


L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
Sp:2000Rpm IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

•  L12 - Generator voltage L1-L2


•  L23 - Generator voltage L2-L3
•  L31 - Generator voltage L3-L1
•  Fq - Generator frequency (if enabled).
•  Sp - Engine Rpm (if enabled).
•  IL1 - Load current
•  IL2 - Load current
•  IL3 - Load current
•  IT – Total current
•  IEA - Earth current

3- Mains Page:

 MAINS
L1:220Vac L12:380Vac
 L2:220Vac L23:380Vac
L3:220Vac L31:380Vac
Fq:50.0Hz
 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

•  L1 - Mains voltage L1-N


•  L2 - Mains voltage L2-N
•  L3 - Mains voltage L3-N
•  Fq - Mains frequency
•  L12 - Mains voltage L1-L2
•  L23 - Mains voltage L2-L3
•  L31 - Mains voltage L3-L1

EAOM-210 FL.eng / ver 0.7


Pages 104 / 154
 

4- Generator Page:

GENERATOR
L1:220Vac L12:380Vac
 L2:220Vac L23:380Vac
L3:220Vac L31:380Vac
Fq:50.0Hz Sp:2000Rpm 
 AUTO CRANKNG ATTEMP
 
OVER SPEED PREALARM!
•  L1 - Generator voltage L1-N
•  L2 - Generator voltage L2-N
•  L3 - Generator voltage L3-N
•  Fq - Generator frequency (if enabled).
•  L12 - Generator voltage L1-L2
•  L23 - Generator voltage L2-L3
•  L31 - Generator voltage L3-L1
•  Sp - Engine Rpm (if enabled).

5- Power Page:

POWER 
 kVA  : 630
 kW : 510
kVAr : 120
FACTOR:-0.84
 AUTO CRANKNG ATTEMP
 OVER SPEED PREALARM!

•  kVA - Generator power


•  kW - Generator active power
•  kVAr - Generator reactive power
•  FACTOR  - Generator power factor (pf)

6- Meter Page:

 METER 
 kVAh : 37800
 kWh : 30600
kVArh : 7200

 AUTO CRANKNG ATTEMP


 OVER SPEED PREALARM!

•  kVA - Generator energy


•  kW - Generator active energy
•  kVAr - Generator reactive energy

EAOM-210 FL.eng / ver 0.7


Pages 105 / 154
 

7- Load Page:

LOAD
CURRENT L1 : 126A 
 CURRENT L2 : 126A 
CURRENT L3 : 126A 
TOTAL CURRENT: 378A 
 EARTH CURRENT: 63A 
 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

•  CURRENT L1 - Load Current


•  CURRENT L2 - Load Current
•  CURRENT L3 - Load Current
•  TOTAL CURRENT - Total Current
•  EARTH CURRENT - Earth Current

8- Anologue Page:

 ANALOGUE
BATTERY VOL:18.0Vdc
 CHR.GEN.VOL:18.0Vdc
OIL PRESS. : 40.3Bar
 TEMPERATURE: 30ºC
 LEVEL : 16%
 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

•  BATTERY VOL - Battery voltage


•  CHR.GEN.VOL  - Charge generator voltage
•  OIL PRESS. - Engine Oil pressure (if enabled).
•  TEMPERATURE - Coolant temperature (if enabled).
•  LEVEL - Fuel Level

9- Miscellaneous Page:

 DATE: 30/06/ 2005


 TIME: 14:20:58
 WORKING HOUR : 1
 NEXT MAINT.HOUR 
:5000
 NEXT MAINT.MONT: 6
 AUTO CRANKNG ATTEMP
 
OVER SPEED PREALARM!

•  DATE - Real Date: Day, Month, Year.


•  TIME - Real Time: Hour, minute, second.
•  WORKING HOUR  – Engine run time
•  NEXT MAINT.HOUR  - The remaining hour for maintenance
•  NEXT MAINT.MONT - The remaining month for maintenance

EAOM-210 FL.eng / ver 0.7


Pages 106 / 154
 

10- Event Logs Page:

EVENT LOG 1
20/03/2005 15:21:38
 EMERGENCY STOP ERROR 
 
 AUTO CRANKNG ATTEMP
 OVER SPEED PREALARM!

•  EMERGENCY STOP ERROR  - This message indicates that an emergency stop


alarm has occured. (Event history: 20/03/2005 date, 15:21:38 time). Events

(from 1 to 32) can be displayed sequencely with the button. Possible Event
messages are:

BATTERY HIGH ERROR : Battery high voltage alarm


BATTERY LOW ERROR : Battery low voltage alarm
CAN BUS ERROR : Can Bus error
CHANGED MODE TO AUTO: Changed mode to auto
CHANGED MODE TO MAN: Changed mode to manual
CHANGED MODE TO OFF: Changed mode to off 
CHANGED MODE TO TEST: Changed mode to test
CHARGE ALTERNTR FAIL: Charge alternator fail
EARTH FAULT ALARM: Earth fault alarm
EMERGENCY STOP ERROR : Emergency stop error
EXPAN.SPARE-1 ERROR : Expansion Spare-1 error
EXPAN.SPARE-2 ERROR : Expansion Spare-2 error
EXPAN.SPARE-3 ERROR : Expansion Spare-3 error
EXPAN.SPARE-4 ERROR : Expansion Spare-4 error
EXPAN.SPARE-5 ERROR : Expansion Spare-5 error
EXPAN.SPARE-6 ERROR : Expansion Spare-6 error
EXPAN.SPARE-7 ERROR : Expansion Spare-7 error
EXPAN.SPARE-8 ERROR : Expansion Spare-8 error
FAIL TO START ALARM: Generator fail to start
GEN BR.NOT CLOS.ALRM: Gen breaker close error
GEN BR.NOT OPEN.ALRM: Gen breaker open error
GEN UNDER FRQ.PREALR : Generator low frequency pre-alarm
GEN UNDER FRQ.SHTDWN: Generator low frequency shutdown
GEN UNDER VOL.PREALR : Generator low voltage pre-alarm
GEN UNDER VOL.SHTDWN: Generator low voltage shutdown
GEN OVER FRQ.PREALRM: Generator high frequency pre-alarm
GEN OVER FRQ.SHUTDWN: Generator high frequency shutdown
GEN OVER VOL.PREALRM: Generator high voltage pre-alarm
GEN OVER VOL.SHUTDWN: Generator high voltage shutdown
GENERATOR STOP ERROR : Generator fail to stop
LEVEL ERROR : Fuel level alarm
LEVEL PREALARM: Fuel level pre-alarm
MAINS BR.NOT CLS.ALR : Mains breaker close error
MAINS BR.NOT OPN.ALR : Mains breaker open error
MAINTENANCE ERROR : Generator maintenance error

EAOM-210 FL.eng / ver 0.7


Pages 107 / 154
 

MAINTENANCE WARNING: Generator maintenance warning


OIL PRESSURE PREALRM: Oil pressure pre-alarm
OIL PRESSURE SHUTDWN: Oil pressure shutdown
OVER CURRENT ALARM: Over current alarm
OVER SPEED PREALARM: Generator high speed pre-alarm
OVER SPEED SHUTDOWN: Generator high speed shutdown
SHORT CIRCUIT ALARM: Short circuit alarm
SPARE-1 ERROR : Spare 1 error
SPARE-2 ERROR : Spare 2 error
SPARE-3 ERROR : Spare 3 error
SPARE-4 ERROR : Spare 4 error
SPARE-5 ERROR : Spare 5 error
SPARE-6 ERROR : Spare 6 error
SPEED LOSS ERROR : Magnetic pickup loss of speed error
TEMPER.HIGH PREALARM: High temperature pre-alarm
TEMPER.HIGH SHUTDOWN: High temperature shutdown
UNDER SPEED PREALARM: Generator low speed pre-alarm
UNDER SPEED SHUTDOWN: Generator low speed shutdown

EAOM-210 FL.eng / ver 0.7


Pages 108 / 154
 

Example-1: Changing page with Next and Previous buttons.

Mains & Load Page

 MAINS & LOAD


L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A 
L31:380Vac IL3: 126A 
Fq:50.0Hz IT: 378A 
IEA: 63A 
 AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!

PROG
Press the next button Press the previous button
to view the next page. to view the previous page.

Generator & Load Page Event Log Page

GENERATOR & LOAD EVENT LOG 1


L12:380Vac IL1: 126A 
 L23:380Vac IL2: 126A  20/03/2005 15:21:38
L31:380Vac IL3: 126A   EMERGENCY STOP ERROR 
Fq:50.0Hz IT: 378A   
Sp:2000Rpm IEA: 63A 
 AUTO CRANKNG ATTEMP  AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!  OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

Mains Page Mains & Load Page

 MAINS  MAINS & LOAD


L1:220Vac L12:380Vac L12:380Vac IL1: 126A 
 L2:220Vac L23:380Vac  L23:380Vac IL2: 126A 
L3:220Vac L31:380Vac L31:380Vac IL3: 126A 
Fq:50.0Hz Fq:50.0Hz IT: 378A 
  IEA: 63A 
 AUTO CRANKNG ATTEMP  AUTO CRANKNG ATTEMP
OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG

Press the previous button


Press the next button to view the previous page.
to view the next page.

EAOM-210 FL.eng / ver 0.7


Pages 109 / 154
 

Generator Page Generator & Load Page

GENERATOR GENERATOR & LOAD


L1:220Vac L12:380Vac L12:380Vac IL1: 126A 
 L2:220Vac L23:380Vac  L23:380Vac IL2: 126A 
L3:220Vac L31:380Vac L31:380Vac IL3: 126A 
Fq:50.0Hz Sp:2000Rpm  Fq:50.0Hz IT: 378A 
Sp:2000Rpm IEA: 63A 
 AUTO CRANKNG ATTEMP
   AUTO CRANKNG ATTEMP
OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

Power Page Mains Page

POWER   MAINS
 kVA  : 630 L1:220Vac L12:380Vac
 kW : 510  L2:220Vac L23:380Vac
kVAr : 120 L3:220Vac L31:380Vac
FACTOR:-0.84 Fq:50.0Hz
 
 AUTO CRANKNG ATTEMP  AUTO CRANKNG ATTEMP
 OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

Meter Page Generator Page

 METER  GENERATOR
 kVAh : 37800 L1:220Vac L12:380Vac
 kWh : 30600  L2:220Vac L23:380Vac
kVArh : 7200 L3:220Vac L31:380Vac
Fq:50.0Hz Sp:2000Rpm 
 AUTO CRANKNG ATTEMP  AUTO
  CRANKNG ATTEMP
 OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

EAOM-210 FL.eng / ver 0.7


Pages 110 / 154
 

Load Page Power Page

LOAD POWER 
CURRENT L1 : 126A   kVA  : 630
 CURRENT L2 : 126A   kW : 510
CURRENT L3 : 126A  kVAr : 120
TOTAL CURRENT: 378A  FACTOR:-0.84
 EARTH CURRENT: 63A 
 
 AUTO CRANKNG ATTEMP  AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!  OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

Analog Page Meter Page

 ANALOGUE  METER 
BATTERY VOL:18.0Vdc  kVAh : 37800
 CHR.GEN.VOL:18.0Vdc  kWh : 30600
OIL PRESS. : 40.3Bar kVArh : 7200
 TEMPERATURE: 30ºC
 LEVEL : 16%
 
 AUTO CRANKNG ATTEMP  AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!  OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

Miscellaneous Page Load Page

 DATE: 30/06/2005 LOAD


 TIME: 14:20:58 CURRENT L1 : 126A 
 WORKING HOUR : 1  CURRENT L2 : 126A 
 NEXT MAINT.HOUR 
:5000 CURRENT L3 : 126A 
 NEXT MAINT.MONT: 6 TOTAL CURRENT: 378A 
 EARTH CURRENT: 63A 
 AUTO CRANKNG ATTEMP
   AUTO CRANKNG ATTEMP
OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG
Press the previous button
Press the next button to view the previous page.
to view the next page.

EAOM-210 FL.eng / ver 0.7


Pages 111 / 154
 

Event Log 1 Page Analogue Page

EVENT LOG 1  ANALOGUE


BATTERY VOL:18.0Vdc
20/03/2005 15:21:38  CHR.GEN.VOL:18.0Vdc
 EMERGENCY STOP ERROR  OIL PRESS. : 40.3Bar
   TEMPERATURE: 30ºC
 LEVEL : 16%
 AUTO CRANKNG ATTEMP  
 AUTO CRANKNG ATTEMP
 OVER SPEED PREALARM! OVER SPEED PREALARM!

PROG PROG
Press the page button to view
the following Event Log page.

Event Log 2 Page

EVENT LOG 2
18/03/2005 17:42:53
 SPARE-4 ERROR 
 
 AUTO CRANKNG ATTEMP
 OVER SPEED PREALARM!

PROG

Press the next button to view Press the previous button to Press the page button to view
the Mains & Load page. view the Miscellaneous page. the following Event Log page.

EAOM-210 FL.eng / ver 0.7


Pages 112 / 154
 

5.1.2 Failure Indicators Description:

FAILED TO START

LOW OIL PRESSURE

HIGH TEMPERATURE

RPM SPEED FAILURE

V VOLTAGE FAILURE

CHARGING FAIL

SPARE-1

SPARE-2

SPARE-3

Explanations:

1-  Failed to Start LED : This LED flashes if the engine has not started after the
programmed number of attempts. The unit must be reset, by pressing the Reset
button, before afresh attempt can be made.
2-  Low Oil Pressure Failure LED : This LED flashes if the Oil Pressure Sender and the Low
Oil Pressure Input (if conf. input-4 is selected as Low Oil pressure) on the engine
indicate low oil pressure while the engine is running. If this fault occurs, the unit will
stop the engine without any cool-down period.
3-  High Temperature Failure LED : This LED flashes if the Temperature Sender and the
High Temperature Input (if conf. input-5 is selected as High Temperature) on the
engine indicates high temperature while the engine is running. If this fault occurs, the
unit will stop the engine without any cool-down period.
4-  Over Speed Failure LED : This LED flashes if the Alternator Frequency goes below the
Generator Under Frequency parameter or above theGenerator Over Frequency
parameter. For a fault to be indicated, the speed must be outside these limits for
longer than the period defined by the Generator Frequency Error Control Time
parameter. This failure immediately stops the generating set, without any cool-down
period.
5-  Voltage Failure LED : This LED flashes if the Alternator output voltage is outside of the
limits programmed into Generator Under Voltage parameter, and Generator Over
Voltage parameter, For a time period longer than the Generator Voltage Error Control
Time parameter. This failure immediately releases the generator contactor, and stops
the generating set, without any cool-down period.
6-  Charge Generator Failure LED : This LED flashes if the field current for the battery
charge generator fails to fall to zero after the engine has started. A fault will not be
indicated if the current falls within the period defined by the Safety On Delay
parameter after the engine has started. This failure will not stop the generating set.
7-  Configurable Input-1 LED (SPARE 1): This LED indicate the status of the input Pin 21,
and the controller can be programmed to perform 25 different functions when this
input is asserted.

EAOM-210 FL.eng / ver 0.7


Pages 113 / 154
 

8-  Configurable Input-2 LED (SPARE 2): This LED indicate the status of the input Pin 20,
and the controller can be programmed to perform 25 different functions when this
input is asserted.
9-  Configurable Input-3 LED (SPARE 3): This LED indicate the status of the input Pin 19,
and the controller can be programmed to perform 25 different functions when this
input is asserted.

5.2 Mode transition

The mode can be changed at any time. A change in mode will not effect the current state
of the generator or load connection. For example; if the unit is in Auto mode with the
generator running and the load running on the generator, changing the mode to Manual
will not effect the operating state. Any changes between Auto, Manual and Test modes will
not change the operating state.

5.3 Manual Start

1. Press the Man (29) button. The LED (12) will light on.
2. Press the Engine Start (21) button on the panel the LED (7) will light on. The engine
should start. The sequence is as follows:
•   The starter motor runs
•   The engine starts

Once the engine is running,


  The LED (6) “Engine Running” is lit.

  The “Generator Ready” LED (5) is lit after “safety on delay” time period like as

AUTO mode.
  It is not possible supply to load on the generator unless “Generator Ready” LED

(5) is lit. (The contactor open / close button does not work)

3. Once LEDs have lit, press the Mains contactor open button (18) to disconnect the load
from the mains supply. LED (3) should go off.
4. Press the Generator contactor close button (19) to connect the load to the generator
supply. LED (4) should light.

5.4 Manual Stop

The LED (8) is lit and engine is stopped when the “Engine Stop” (22) button is pressed.
When the “Engine Stop” button is pressed while the load connected to the alternator
output (generator output) first alternator contactor is released then engine is stopped.

5.5 Auto Operation

Press the Auto (27) button to select Auto mode. The LED (10) in the corner of the button
will light to indicate this mode has been selected.

In the event of a mains voltage failure, the unit will start up the generator and, once the
generator is running and alternator voltage available, will transfer the load to the
generator. When the mains is restored and stable, it will transfer the load back to the
mains and, after a cool-down period, shut down the generator.

EAOM-210 FL.eng / ver 0.7


Pages 114 / 154
 

5.6 Test Operation

Press the Test (28) button to select Test mode the LED (11) will light on. This mode allows
for testing of the generator off load. All alarm circuits will operate so that any faults will
be reported. If a mains failure occurs while the unit is in Test mode, the unit will revert to
Auto mode and will switch the load to the generator.

5.6.1 Exercise Function

Please enter the day of the week for Exercise Function. Example:
EXER.WORKING PERIOD (dis)0 The exercise function is disabled.
(10) The exercise function is enabled for 10 minutes.
EXER.WR.DAY OF WEEK 1=Monday.
EXER.WORK.START TIM 12.20 The exercise function is every Monday started at
12.20 o’clock. (if it is enabled)

When the Real-Time clock reached to the Generator Exercise Work Start Time (12.20
o’clock) if the unit is in “AUTO MODE” and Mains is available the unit changes running
mode to the “TEST MODE” automatically and starts the engine. The time period of engine
running is counted and compared with value of Generator Exercise Working Period
parameter (10 minutes). (If the engine does not run time is not counted). If the period is
completed the unit changes run mode to “AUTO” automatically. When the unit is in the
“TEST MODE” if the Mains is gone, the unit will change run mode to “AUTO MODE”
automatically.

EAOM-210 FL.eng / ver 0.7


Pages 115 / 154
 

Section 6 Fault Finding

6.1 General

Indicators on the central section of the panel will flash if a fault is detected. For details
see Section 5.1.2 Failure Indicators Description. Fault conditions latch so that further
operation is prevented. If a failure is indicated, proceed as follows:

1. Find and fix the fault.

2. Press the Failure Reset (25) button to enable a restart.

3.  Select the required mode of operation – Manual, Auto or Test.

6.2 Error Messages

 
OVER SPEED PREALARM!

In addition to the indicators on the centre panel, when a fault is occured, it’s error
message is displayed in the eighth lines of current page. Seventh and eighth lines are
common in all pages. If more than one error condition is present, all of them is displayed
sequencely in time defined by “Scroll Time For Error Messages” parameter. All Error
messages are:

BATTERY HIGH ERROR! : This message indicates that a battery high voltage alarm
has occured.
BATTERY LOW ERROR! : This message indicates that a battery low voltage alarm
has occured.
CAN BUS ERROR! : This message indicates that a Can Bus error has occured.
EARTH FAULT EL.TRIP! : This message indicates that a earth fault electrical trip
has occured.
EARTH FAULT ERROR! : This message indicates that a earth fault shutdown has
occured.
EARTH FAULT WARNING! : This message indicates that a earth fault warning (pre-
alarm) has occured.
EMERGENCY STOP ERR! : This message indicates that an emergency stop alarm has
occured.
EXPAN. SPARE-1 ERROR! : This message indicates that an Expansion
spare 1 alarm has occured.
EXPAN. SPARE-2 ERROR! : This message indicates that an Expansion
spare 2 alarm has occured.
EXPAN. SPARE-3 ERROR! : This message indicates that an Expansion
spare 3 alarm has occured.
EXPAN. SPARE-4 ERROR! : This message indicates that an Expansion
spare 4 alarm has occured.

EAOM-210 FL.eng / ver 0.7


Pages 116 / 154
 

EXPAN. SPARE-5 ERROR! : This message indicates that an Expansion


spare 5 alarm has occured.
EXPAN. SPARE-6 ERROR! : This message indicates that an Expansion
spare 6 alarm has occured.
EXPAN. SPARE-7 ERROR! : This message indicates that an Expansion
spare 7 alarm has occured.
EXPAN. SPARE-8 ERROR! : This message indicates that an Expansion
spare 8 alarm has occured.
GEN BR.NOT CLOS.ALR! : This message indicates that a generator breaker not
closed alarm has occured.
GEN BR.NOT OPEN.ALR! : This message indicates that a generator breaker not
opened alarm has occured.
GEN OVER FRQ.PREAL! : This message indicates that a generator over frequency
warning (pre-alarm) has occured.
GEN OVER VOL.PREAL! : This message indicates that a generator over voltage
warning (pre-alarm) has occured.
GEN UNDER FRQ.PREAL! : This message indicates that a generator under frequency
warning (pre-alarm) has occured.
GEN UNDER VOL.PREAL! : This message indicates that a generator under voltage
warning (pre-alarm) has occured.
GENERATOR STOP ERR! : This message indicates that the generator has failed to
stop within the selected time.
LEVEL ERROR! : This message indicates that the fuel level shutdown has occured.
LEVEL PREALARM! : This message indicates that the fuel level warning (pre-alarm)
has occured.
MAINS BR.NOT CL.ALR! : This message indicates that a mains breaker not closed
alarm has occured.
MAINS BR.NOT OP.ALR! : This message indicates that a mains breaker not opened
alarm has occured.
MAINTENANCE ERROR! : This message indicates that the generator is now due for
maintenance.
MULTPLE ENGAGE FAIL! : This message indicates that the multiple engage fail has
occured.
OVER CURRNT EL.TRIP! : This message indicates that a over current electrical trip
has occured.
OVER CURRENT ERROR! : This message indicates that a over current shutdown has
occured.
OVER CURRENT WARNNG! : This message indicates that a over current warning
(pre-alarm) has occured.
OVER SPEED ERROR! : This message indicates that the over speed shutdown has
occured.
OVER SPEED PREALARM! : This message indicates that the over speed warning (pre-
alarm) has occured.
PRESSURE PREALARM! : This message indicates that a low oil pressure warning
(pre-alarm) has occured.
SHORT CIRCT EL.TRIP! : This message indicates that a short circuit electrical trip
has occured.
SHORT CIRCUIT ERROR! : This message indicates that a short circuit shutdown has
occured.
SHORT CIRCUIT WARNN! : This message indicates that a short circuit warning (pre-
alarm) has occured.
SPARE-4 ERROR! : This message indicates that a spare 4 alarm has occured.
SPARE-5 ERROR! : This message indicates that a spare 5 alarm has occured.
SPARE-6 ERROR! : This message indicates that a spare 6 alarm has occured.

EAOM-210 FL.eng / ver 0.7


Pages 117 / 154
 

SPEED LOSS ERROR! : This message indicates that the magnetic pick-up sensor fail
(speed loss error) has occured.
TEMPERAT. PREALARM! : This message indicates that a high engine coolant
temperature warning (pre-alarm) has occured.
UNDER SPEED ERROR! : This message indicates that the under speed shutdown has
occured.
UNDER SPED PREALARM! : This message indicates that the under speed warning
(pre-alarm) has occured.

Table 6.1 Fault finding

Symptom Possible remedy


Check the battery and wiring to the unit.
Unit is inoperative. Check the DC supply. ( measure voltage between pins 39 and 40 )
Check the DC fuse.
Check engine oil level and pressure..
Low oil pressure fault
operates after engine Check oil pressure switch and sender and wiring.
has started. Check configured polarity (if applicable) is correct (i.e. Normally Open or
Normally Closed) or that sender is compatible with the device.
High engine Check engine temperature.
temperature Check temperature switch and sender and wiring.
Fault operates after
Check configured polarity (if applicable) is correct (i.e. Normally Open or
engine has started.
Normally Closed) or that sender is compatible with the device.
Shutdown fault Check relevant switch and wiring of fault indicated on the panel.
operates. Check configuration of input.
Warning fault Check relevant switch and wiring of fault indicated on the panel.
operates. Check configuration of input.
Failed to Start fault. Check fuel solenoid and wiring, fuel and battery. Reset the
Engine failed to start EAOM-210 FL and restart the engine.
after Pre-set number Check the signals that the EAOM-210 FL is using to determine if the engine
of Attempts. has started. Refer to engine manual.
Check wiring to starter solenoid.
Starter motor Check battery supply.
inoperative.
Check battery supply is present on the Start output pin 33 of the
EAOM-210 FL.

Disconnect the equipment totally from electricity in the best and correct way during
mechanical and electrical maintenance. When this is not possible, the equipment must be in the
“OFF” position for preventing any accident.

EAOM-210 FL.eng / ver 0.7


Pages 118 / 154
 

Section 7 Specifications & Ratings

Specification: Description:
Equipment use Electrical control equipment for generating sets
Housing & Mounting 144 mm x 204 mm x 37 mm. (including connectors) plastic
housing for panel mounting.
Panel Cut-Out 138 mm x 186 mm.
Protection IP54 at front panel, IP20 at rear side.
Weight Approximately 0,76 Kg.
Environmental rating Standard, indoor at an altitude of less then 2000 meters with
non-condensing humidity.
Operating / Storage 0°C to +50°C / -25°C to +70°C
Temperature
Operating / Storage 90 % max. (non-condensing)
Humidity
Installation Over Voltage II Appliances, portable equipment.
Category
Pollution Degree II, Normal office or workplace, non conductive pollution
Mode of Operation Continuous
EMC EN 61000-6-4, EMC Generic Emission Standard for industrial
equipment
EN 61000-6-2, EMC Generic Immunity Standard for industrial
equipment
Electrical Safety EN 61010-1, Safety Requirements for electrical equipment for
measurement, control and laboratory use
DC Battery Supply
Voltage 8 to 32 VDC max. operating current is 360 mA.

Cranking Dropouts Battery voltage can be “0” VDC for max. 100 ms during cranking
(battery voltage should be at least nominal voltage before
cranking).
Battery Voltage 8 to 32 VDC, accuracy: 1 % FS, resolution: 0,1 V
Measurement
Mains Voltage Selectable three phase or single phase, 4 wire connection for
Measurement three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Mains Frequency 15.6 to 99.9 Hz (min. 35 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Generator Voltage Selectable three phase or single phase, 4 wire connection for
Measurement three phase, 2 wire connection for single phase gen-set. 35 to
300 VAC Ph-N, 15.6 to 99.9 Hz. Accuracy: 1 % FS, Resolution: 1 V
Generator Speed From magnetic pick-up: 35 to 10000 Hz (4 to 35 volts peak
continuously.) Accuracy: 0,25 % FS
Generator Frequency From alternator voltage: 15.6 to 99.9 Hz (min. 35 VAC Ph-N)
Accuracy: 0,25 % FS, Resolution: 0,1 Hz.
CT secondary 5A.
Charge Generator 220mA, max 4W.
Excitation

EAOM-210 FL.eng / ver 0.7


Pages 119 / 154
 

Specification: Description:
LCD Display 128x64 Dot-matrix LCD display showin:
Mains volts (L1-N, L2-N, L3-N)
Mains volts (L1-L2, L2-L3, L3-L1)
Mains Hz
Generator volts (L1-N, L2-N, L3-N)
Generator volts (L1-L2, L2-L3, L3-L1)
Generator Hz
Engine Rpm
Generator kVA
Generator kW
Generator kVAr
Generator kVAh
Generator kWh
Generator kVArh
Generator power factor (pf)
Load amps (IL1, IL2, IL3)
Earth current (IEA)
Engine oil pressure
Coolant temperature
Fuel level
Battery voltage
Charge generator voltage
Real time
Engine run time
Next maintenance hour
Next maintenance month
Event logs
Working modes
Engine status
Error messages
Program parameters
Failure Indicators Failed to start
Low oil pressure
High temperature
Speed failure
Voltage failure
Charging fail
Spare 1
Spare 2
Spare 3
Status indicators OFF mode LED
TEST mode LED
AUTOMATIC mode LED
MANUAL mode LED
Engine start LED
Engine stop LED
Engine running
Main voltage available LED
Generator ready LED
Mains contactor LED
Generator contactor LED
Communication RS 232 serial communication with PC.
interface CanBus communication with Expansion module.

EAOM-210 FL.eng / ver 0.7


Pages 120 / 154
 

Specification: Description:
Contact sensing inputs Emergency stop (NC)
Configurable failure input-1 (NO or NC selectable)
Configurable failure input-2 (NO or NC selectable)
Configurable failure input-3 (NO or NC selectable)
Low oil pressure or configurable failure input-4 (NO or NC
selectable)
High temperature or configurable failure input-5 (NO or NC
selectable)
Configurable failure input-6 (NO or NC selectable)
Relay outputs Fuel relay output. 16A at DC supply voltage
Start relay output. 16A at DC supply voltage
Horn or configurable relay output-1. 16A at DC supply voltage
Mains open relay output. 5A at DC supply voltage
Mains close relay output. 5A at DC supply voltage
Generator open relay output. 5A at DC supply voltage
Generator close relay output. 5A at DC supply voltage
Configurable relay output-2. 5A at DC supply voltage
Configurable relay output-3. 5A at DC supply voltage
Configurable relay output-4. 5A at DC supply voltage

EAOM-210 FL.eng / ver 0.7


Pages 121 / 154
 

Section 8 Block Diagram

+BATTERY

POWER
SUPPLY

MICROCONTROLLER
BATTERY
RELAY
VOLTAGE
SENSING OUTPUTS

MAINS N
MAINS L1 MAINS
MAINS L2 &
MAINS L3 GENERATOR
VOLTAGE
GEN. N SENSING
GEN. L1 & ANALOG
CONDITIONING TO
GEN. L2 DIGITAL
GEN. L3 CONVERTOR

LOAD L1 LOAD RS232


LOAD L2 CURRENTS COMM.
LOAD L3 &
EARTH
IEA CURRENT
SENSING

ANALOG
SENDERS

LCD DISPLAY
&
FREQUENCY INDICATORS
SENSING
FROM
GENERATOR
VOLTAGE
COUNTER
&
TIMER
FREQUENCY
SENSING
MAGNETIC
FROM
PICK-UP
MAGNETIC
PICK-UP
FAILURE
&
CONTROL
INPUTS

PUSH
BUTTONS

EAOM-210 FL.eng / ver 0.7


Pages 122 / 154
 

User Defined Parameter:


List-1:

Definition of Parameter User Defined Value

Operator parameters

(MAINS LEVELS PAGE) MAINS LEVELS page


MAINS UNDER VOLTAGE  Mains Under Voltage 
MAINS UNDER V.RET. Mains Under Voltage Return 
MAINS OVER VOLTAGE  Mains Over Voltage 
MAINS OVER V.RETURN  Mains Over Voltage Return 
MAINS UNDER FREQ. Mains Under Frequency 
MAINS UNDER F.RET. Mains Under Frequency Return 
MAINS OVER FREQ. Mains Over Frequency 
MAINS OVER F.RETURN  Mains Over Frequency Return 

(GEN.VOLT.LEVELS PAGE) GENERATOR VOLTAGE LEVELS page


GEN.UNDER VOLTAGE  Generator Under Voltage 
GEN.UNDER V.PRE-ALR  Generator Under Voltage Pre-Alarm 
GEN.LOADING VOLTAGE  Generator Loading Voltage 
GEN.OVER V.PRE-ALR  Generator Over Voltage Pre-Alarm 
GEN.OVER V.PR-A.RET  Generator Over Voltage Pre-Alarm Return 
GEN.OVER VO.SHUTDWN  Generator Over Voltage Shutdown 

(GEN.FREQ.LEVELS PAGE) GENERATOR FREQUENCY LEVELS page


GEN.UNDER FREQUENCY  Generator Under Frequency 
GEN.UNDER F.PRE-ALR  Generator Under Frequency Pre-Alarm 
GEN.LOADING FREQ. Generator Loading Frequency 
GEN.OVER F.PRE-ALR  Generator Over Frequency Pre-Alarm 
GEN.OVER F.PR-A.RET  Generator Over Frq Pre-Alarm Return 
GEN.OVER FR.SHUTDWN  Generator Over Frequency Shutdown 

(GEN.CUR/POW.LVL.PAGE) GENERATOR CURRENT/POWER LEVELS page


GEN.OVER CURRENT  Generator Over Current 
GEN.SHORT CIRCUIT  Generator Short Circuit 
GEN.EARTH FAULT  Generator Earth Fault 

EAOM-210 FL.eng / ver 0.7


Pages 123 / 154
 

Definition of Parameter User Defined Value

Technician parameters

(GEN.CUR/POW.ACT.PAGE) GENERATOR CURRENT/POWER ACTIONS page


CT PRIMARY  CT Primary 
EARTH FAULT CT PRIM  CT Primary (Earth Fault)
Over Current Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
OVER CUR.ACTIONS 
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
OVER CUR.ALARM TIME  Over Current Alarm Time 
Short Circuit Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
SHORT CIR.ACTIONS 
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
SHORT CIR.ALRM TIME  Short Circuit Alarm Time 
Earth Fault Actions 
-Disable 
-Warning (Alarm Only, No Shutdown)
EARTH FAULT ACTIONS 
-Electrical Trip (Alarm/Off Load Generator 
Followed By Shutdown After Cooling)
-Shutdown (Alarm And Shutdown)
EARTH FAU.ALRM TIME  Earth Fault Alarm Time 
TOTAL ENERGY CLEAR  Total Energy Clear 
ACTIVE ENERGY CLEAR  Active Energy Clear 
REACTIVE ENERGY CLR  Reactive Energy Clear 

(MISCELLANEOUS PAGE) MISCELLANEOUS page


SENS.OPT.GEN.F.ENAB  Sensing Options Generator Frq En/Dis 
SNS.OP.PICKP ENA&FW  Sensing Opt Pickup En/Dis & Flywheel 
Ac System 0 =1phase 2wire, 1= 3phase 
AC SYSTEM 
4wire 2= 3phase 4wire Series Delta 
FAST LOAD.FEAT.ENAB  Fast Loading Feature En/Dis 
ALL WRN.ARE LTCH.EN  All Warnings Are Latched En/Dis 
MAINS FAIL.DETEC.EN  Mains Failure Detection En/Dis 
Look Mains Failure For Mains Cont.
LK.MA.FA.FO.MA.CN.E 
En/Dis 
GAS/DIESEL SELECT  Engine Fuel (Gas/ Diesel) Selection 
STOP/FUEL SELECTION  Stop / Fuel Selection 
STOP SOLENOID TIME  Stop Solenoid Time 
IGNITION DELAY  Ignition Delay 
GAS VALVE DELAY  Gas Valve Delay 
MIN.IGNITION SPEED  Min Ignition Speed 
NOMINAL FREQUENCY  Nominal Alternator Frequency 
NOMINAL SPEED  Nominal Speed 

EAOM-210 FL.eng / ver 0.7


Pages 124 / 154
 

Definition of Parameter User Defined Value

(ENGINE STAR.OPT PAGE) ENGINE STARTING OPTIONS page


AU.ALR.PRIOR STRT.E  Audible Alarm Prior To Starting En/Dis 
NUMBR OF STR.ATTEMP  Number Of Start Attempts 
CRANKING TIME  Cranking Time 
CRANK REST TIME  Crank Rest Time 
MUL.STR.ENG.ATEMP.E  Multiple Start Engage Attempts E/D (Pick)
ENGAGE ATTEMPT TIME  Engage Attempt Time  (Pickup)
ENG.ATEMP.REST TIME  Engage Attempt Rest Time (Pickup)
PICK.SNSR FAIL DELY  Pickup Sensor Fail Delay(Pickup)

(ENG.CRANK DISCN.PAGE) ENGINE CRANK DISCONNECT page


CRNK DISCN.ON GEN.F  Crank Disconnect On Gen. Frequency 
CRNK DISCN.ON MAG.P  Crank Disconnect On Magnetic Pickup 
CRNK DISCN.ON GEN.V  Crank Disconnect On Gen. Voltage 
CRNK DISC.ON CH.G.V  Crank Disconnect On Charge Alt. Voltage 
CRNK DISCN.ON OIL P  Crank Disconnect On Oil Pressure 

(GEN.SPED SETING PAGE) GENERATOR SPEED SETTINGS page


GEN.UNDER SPEED  Generator Under Speed 
GEN.UNDR SPED PRE-A Generator Under Speed Prealarm 
GEN.UNDR SP.PR-A.RT  Generator Under Speed Prealarm Return 
GEN.OVER SPED PRE-A Generator Over Speed Prealarm 
GEN.OVER SP.PR-A.RT  Generator Over Speed Prealarm Return 
GEN.OVER SP.SHUTDWN  Generator Over Speed Shutdown 

(ENG.PLANT BATTR PAGE) ENGINE PLANT BATTERY page


BAT.UNDER V.WARNING  Battery Undervolts Warning 
BAT.UNDR V.WARN.RET  Battery Undervolts Warning Return 
BAT.UNDER VOL.DELAY  Batt Undervolts Volts Delay 
BAT.OVER V.WARNING  Battery Overvolts Warning 
BAT.OVER V.WARN.RET  Battery Overvolts Warning Return 
BAT.OVER VOL.DELAY  Batt Overvolts Delay 
CHARGE ALT.WARNING  Charge Alternator Warning 

(ANALOGUE INPUTS PAGE) ANALOGUE INPUTS page


OIL PRES.INPUT TYPE  Oil Pressure Input Type 
OIL PRES.PRE-ALARM  Oil Pressure Pre-Alarm 
OIL PRES.PRE-AL.RET  Oil Pressure Pre-Alarm Return 
OIL PRES.SHUTDOWN  Oil Pressure Shutdown 
TEMP.INPUT TYPE  Temperature Input Type 
TEMP.PRE-ALARM  Temperature Pre-Alarm 
TEMP.PRE-ALARM RET  Temperature Pre-Alarm Return 
TEMP.SHUTDDOWN  Temperature Shutdown 
LEVEL PRE-ALARM  Level Pre-Alarm 
LEVEL PRE-ALARM RET  Level Pre-Alarm Return 
LEVEL SHUTDOWN  Level Shutdown 

EAOM-210 FL.eng / ver 0.7


Pages 125 / 154
 

Definition of Parameter User Defined Value

(ANALG.SENDR LIN.PAGE) ANALOGUE SENDER LINEARISATIONS page


OIL PRESS.SENDER 0  Oil Pressure Sender 0 
OIL PRESSURE 0  Oil Pressure 0 
OIL PRESS.SENDER 1 Oil Pressure Sender 1
OIL PRESSURE 1 Oil Pressure 1
OIL PRESS.SENDER 2  Oil Pressure Sender 2 
OIL PRESSURE 2  Oil Pressure 2 
OIL PRESS.SENDER 3  Oil Pressure Sender 3 
OIL PRESSURE 3  Oil Pressure 3 
OIL PRESS.SENDER 4  Oil Pressure Sender 4 
OIL PRESSURE 4  Oil Pressure 4 
TEMP.SENDER 0  Temperature Sender 0 
TEMPERATURE 0  Temperature 0 
TEMP.SENDER 1 Temperature Sender 1
TEMPERATURE 1 Temperature 1
TEMP.SENDER 2  Temperature Sender 2 
TEMPERATURE 2  Temperature 2 
TEMP.SENDER 3  Temperature Sender 3 
TEMPERATURE 3  Temperature 3 
TEMP.SENDER 4  Temperature Sender 4 
TEMPERATURE 4  Temperature 4 
LEVEL SENDER 0  Level Sender 0 
LEVEL 0  Level 0 
LEVEL SENDER 1 Level Sender 1
LEVEL 1 Level 1
LEVEL SENDER 2  Level Sender 2 
LEVEL 2  Level 2 
LEVEL SENDER 3  Level Sender 3 
LEVEL 3  Level 3 
LEVEL SENDER 4  Level Sender 4 
LEVEL 4  Level 4 

(CAN BUS CONFIG. PAGE) CAN BUS CONFIGURATION page


EXPANS.MODUL SELECT  Expansion module selection 

EAOM-210 FL.eng / ver 0.7


Pages 126 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-1 PAGE) DIGITAL CONFIGURABLE INPUT (1) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST 
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 127 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-2 PAGE) DIGITAL CONFIGURABLE INPUT (2) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST 
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 128 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-3 PAGE) DIGITAL CONFIGURABLE INPUT (3) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Status, Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST 
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 129 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-4 PAGE) DIGITAL CONFIGURABLE INPUT (4) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
25 Low Oil Pressure
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 130 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-5 PAGE) DIGITAL CONFIGURABLE INPUT (5) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST  12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
25 High Temperature
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 131 / 154
 

Definition of Parameter User Defined Value

(DIG.CNF.INPUT-6 PAGE) DIGITAL CONFIGURABLE INPUT (6) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

0 Remote Start
1 Auxiliary Mains Fail
2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
10 Simulate Stop Button
11 Generator Closed Auxiliary
SELECT FROM LIST 
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
22 Remote Inhibit
23 Test on Load
24 Generator is supplying the load in OFF
mode
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 132 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-1 PAGE) EXPANSION CONFIGURABLE INPUT (1) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 133 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-2 PAGE) EXPANSION CONFIGURABLE INPUT (2) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 134 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-3 PAGE) EXPANSION CONFIGURABLE INPUT (3) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 135 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-4 PAGE) EXPANSION CONFIGURABLE INPUT (4) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 136 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-5 PAGE) EXPANSION CONFIGURABLE INPUT (5) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 137 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-6 PAGE) EXPANSION CONFIGURABLE INPUT (6) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 138 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-7 PAGE) EXPANSION CONFIGURABLE INPUT (7) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 139 / 154
 

Definition of Parameter User Defined Value

(EXP.CNF.INPUT-8 PAGE) EXPANSION CONFIGURABLE INPUT (8) page


Disable, User Configured Or Select From 
DIS,USERCNF.OR LIST 
List 
-Hardware type 
HARDWARE TYPE 
(0 = -Ve, 1 = +Ve)
If User Configured 
POLARITY  -Polarity (Close To Activate, Open To 
Activate)
If User Configured 
-Indication(Warning Non-Latching,
INDICATION 
Warning Latching, Electrical Trip,
Shutdown)
If User Configured 
ACTIVATION  -Activation (Active From Starting, Active 
From Safety On, Always Active)
If Select From List 

1 Auxiliary Mains Fail


2 Simulate Lamp Test Button
3 Simulate Horn Reset Button
4 Simulate Alarm Reset Button
5 Simulate Off Button
6 Simulate Auto Button
7 Simulate Test Button
8 Simulate Manual Button
9 Simulate Start Button
SELECT FROM LIST  10 Simulate Stop Button
11 Generator Closed Auxiliary
12 Generator Load Inhibit
13 Mains Closed Auxiliary
14 Mains Load Inhibit
15 Auto Restore Inhibit
16 Auto Start Inhibit
17 Panel Lock
18 Scheduled Runs Inhibited
19 Reset Maintenance Alarm
20 Transfer To Generator/Open Mains
21 Transfer To Mains/Open Generator
INPUT TIME DELAY  Input time delay 

EAOM-210 FL.eng / ver 0.7


Pages 140 / 154
 

Definition of Parameter User Defined Value


(CONFIG.OUTPUT-1 PAGE) CONFIGURABLE OUTPUT (1) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 141 / 154
 

Definition of Parameter User Defined Value


(CONFIG.OUTPUT-2 PAGE) CONFIGURABLE OUTPUT (2) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 142 / 154
 

Definition of Parameter User Defined Value


(CONFIG.OUTPUT-3 PAGE) CONFIGURABLE OUTPUT (3) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 143 / 154
 

Definition of Parameter User Defined Value


(CONFIG.OUTPUT-4 PAGE) CONFIGURABLE OUTPUT (4) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 144 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-1 PAGE) EXPANSION CONFIGURABLE OUTPUT (1) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 145 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-2 PAGE) EXPANSION CONFIGURABLE OUTPUT (2) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 146 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-3 PAGE) EXPANSION CONFIGURABLE OUTPUT (3) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 147 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-4 PAGE) EXPANSION CONFIGURABLE OUTPUT (4) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 148 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-5 PAGE) EXPANSION CONFIGURABLE OUTPUT (5) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 149 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-6 PAGE) EXPANSION CONFIGURABLE OUTPUT (6) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 150 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-7 PAGE) EXPANSION CONFIGURABLE OUTPUT (7) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 151 / 154
 

Definition of Parameter User Defined Value


(EXP.CONFG.OUT-8 PAGE) EXPANSION CONFIGURABLE OUTPUT (8) page
POLARITY  Polarity (Normally Open, Normally Closed)
0 NOT USED
1 AUDIBLE ALARM
2 ALARM RESET
3 AUTO START INHIBIT
4 AUXILIARY MAINS FAILURE
5 BATTERY HIGH VOLTAGE
6 BATTERY LOW VOLTAGE
7 CALLING FOR SCHEDULED RUN
8 CHARGE ALTERNATOR FAILURE
9 COMMON ALARM
10 COMMON ELECTRICAL TRIP ALARM
11 COMMON SHUTDOWN ALARM
12 COMMON WARNING ALARM
13 COOLANT TEMPERATURE HIGH PRE-ALARM
14 COOLANT TEMPERATURE HIGH SHUTDOWN
15 COOLING DOWN TIMER IN PROGRESS
16 DELAYED ALARMS ACTIVE
17 DIGITAL INPUT1 ACTIVE
18 DIGITAL INPUT2 ACTIVE
19 DIGITAL INPUT3 ACTIVE
20 DIGITAL INPUT4 ACTIVE
21 DIGITAL INPUT5 ACTIVE
22 DIGITAL INPUT6 ACTIVE
23 EXPANSION INPUT1 ACTIVE
24 EXPANSION INPUT2 ACTIVE
25 EXPANSION INPUT3 ACTIVE
26 EXPANSION INPUT4 ACTIVE
27 EXPANSION INPUT5 ACTIVE
28 EXPANSION INPUT6 ACTIVE
29 EXPANSION INPUT7 ACTIVE
30 EXPANSION INPUT8 ACTIVE
31 EARTH FAULT
32 ELECTRIC COOLING FAN AFTERSTART
33 ELECTRIC COOLING FAN AFTERSTOP
34 EMERGENCY STOP
35 FAIL TO START ALARM
36 FAIL TO STOP ALARM
37 FUEL RELAY ENERGISED
38 GAS ENGINE IGNITION OUTPUT
39 GENERATOR AT REST
40 GENERATOR AVAILABLE
41 GENERATOR CLOSED AUXILIARY
42 GENERATOR FAILED TO CLOSE
43 GENERATOR FAILED TO OPEN
44 GENERATOR HIGH FREQUENCY PRE-ALARM
45 GENERATOR HIGH FREQUENCY SHUTDOWN
46 GENERATOR HIGH VOLTAGE PRE-ALARM
FUNCTION  47 GENERATOR HIGH VOLTAGE SHUTDOWN
48 GENERATOR LOAD INHIBIT
49 GENERATOR LOW FREQUENCY PRE-ALARM
50 GENERATOR LOW FREQUENCY SHUTDOWN
51 GENERATOR LOW VOLTAGE PRE-ALARM
52 GENERATOR LOW VOLTAGE SHUTDOWN
53 RESERVED
54 GENERATOR STOPPING
55 HORN OUTPUT
56 LAMP TEST
57 LEVEL PREALARM
58 LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
59 MAINTENANCE DUE ALARM
60 MAINS CLOSED AUXILIARY
61 MAINS FAILED TO CLOSE
62 MAINS FAILED TO OPEN
63 MAINS FAILURE
64 MAINS HIGH FREQUENCY
65 MAINS HIGH VOLTAGE
66 MAINS LOAD INHIBIT
67 MAINS LOW FREQUENCY
68 MAINS LOW VOLTAGE
69 NO LOADING COMMAND
70 OIL PRESSURE LOW PRE-ALARM
71 OIL PRESSURE LOW SHUTDOWN
72 OVER CURRENT
73 OVERSPEED PRE-ALARM
74 OVERSPEED SHUTDOWN
75 PANEL LOCK
76 PRE-HEAT(during preheat timer)
77 PRE-HEAT(until end of cranking)
78 PRE-HEAT(until end of warming)
79 PRE-HEAT(until end safety on)
80 REMOTE START PRESENT
81 REMOTE STOP DELAY IN PROGRESS
82 SHORT CIRCUIT
83 START RELAY ENERGISED
84 STARTING ALARM
85 STARTING ALARMS ARMED
86 STOP BUTTON PRESSED
87 SYSTEM IN AUTO MODE
88 SYSTEM IN MANUAL MODE
89 SYSTEM IN OFF MODE
90 SYSTEM IN TEST MODE
91 UNDERSPEED SHUTDOWN
92 UNDERSPEED PRE-ALARM
93 WAITING FOR GENERATOR

EAOM-210 FL.eng / ver 0.7


Pages 152 / 154
 

Definition of Parameter User Defined Value


(START TIMERS PAGE) START TIMERS page
MAINS TRANS.DELAY  Mains Transient Delay 
REMOTE START DELAY  Remote Start Delay 
REMOTE STOP DELAY  Remote Stop Delay 
PRE-HEAT  Pre-Heat 
PRE-HEAT BYPASS  Pre-Heat Bypass 
SAFETY ON DELAY  Safety On Delay 
HORN DURATION  Horn Duration 
CHRG.EXCITATION TIM  Charge Excitation Time 
ELECTR.COOL.FAN TIM  Cooling Fan Time 
MAINS FAIL DELAY  Mains Fail Delay 

(LOAD/STP.TIMERS PAGE) LOAD/STOPPING TIMERS page


WARM UP TIME  Warmup Timer 
RETURN DELAY  Return Delay 
COOLING TIME  Cooling Timer 
GEN.FR.ERR.CNT.TIME  Generator Frequency Error Control Time 
GEN.VL.ERR.CNT.TIME  Generator Voltage Error Control Time 
FAIL TO STOP TIME  Fail To Stop Time 

(BREAKERS PAGE) BREAKERS page


HARDW.BREAKER SELCT  Hardware Breaker Selection 
GEN.CLOS.BREK.C.TYP  Gen Close Breaker Contact Type 
GEN.CLOS.BREK.R.TYP  Gen Close Breaker Relay Type 
GEN.CLOSE TIMER  Gen Close Timer 
GEN.OPEN.BREK.C.TYP  Gen Open Breaker Contact Type 
GEN.OPEN.BREK.R.TYP  Gen Open Breaker Relay Type 
GEN.OPEN TIMER  Gen Open Timer 
MAIN CLS.BREK.C.TYP  Main Close Breaker Contact Type 
MAIN CLS.BREK.R.TYP  Main Close Breaker Relay Type 
MAINS CLOSE TIMER  Mains Close Timer 
MAIN OPN.BREK.C.TYP  Main Open Breaker Contact Type 
MAIN OPN.BREK.R.TYP  Main Open Breaker Relay Type 
MAINS OPEN TIMER  Mains Open Timer 
BREKR.CLOS.PULS.TIM  Breaker Close Pulse Time 
BREKR.OPEN.PULS.TIM  Breaker Open Pulse Time 
TRANSFER TIME  Transfer Time 

(LCD CONFIG.PAGE) LCD CONFIGURATION page


ERR.MESS SCROLL TIM  Scroll Time For Error Messages
DIGITAL CONTRAST  Digital Contrast
BACKLIGHT ON/OFF  Backlight On/Off

(ENG.MAINT.ALARM PAGE) ENGINE MAINTENANCE ALARM page


RUNN.HOURS INTERVAL Running Hours Interval 
MAINT.DATE INTERVAL Maintenance Date Interval 
Force Engine Shutdown When 
ENG.STP.WH.MANT.E/D 
Maintenance Is Due En/Dis 
ENGIN.RUN.HOUR(LSB)  Engine Running Hour (Lsb)
ENGINE RUNNING HOUR  Engine Running Hour 
ENGIN.RUN.HOUR(MSB)  Engine Running Hour(Msb)

(COMMUNICATION PAGE) COMMUNICATION page


SLAVE ADDRESS  Slave Address 
Baud Rate 0=1200 
  1=2400 
BAUD RATE    2=4800 
  3=9600 
  4=19200 
PARITY  Parity; 0= NONE, 1= ODD, 2= EVEN 
STOP BIT  Stop Bit 

EAOM-210 FL.eng / ver 0.7


Pages 153 / 154
 

Definition of Parameter User Defined Value

(WR.CALENDR&EXER.PAGE) WORKING CALENDAR & EXERCISE page


Working calendar working time on 
WORK.PERIOD ON MON.
Monday 
Working calendar work start time on 
WORK.START TIME MON 
Monday 
Working calendar working time on 
WORK.PERIOD ON TUE.
Tuesday 
Working calendar work start time on 
WORK.START TIME TUE 
Tuesday 
Working calendar working time on 
WORK.PERIOD ON WED.
Wednesday 
Working calendar work start time on 
WORK.START TIME WED 
Wednesday 
Working calendar working time on 
WORK.PERIOD ON THU.
Thursday 
Working calendar work start time on 
WORK.START TIME THU 
Thursday 
WORK.PERIOD ON FRI. Working calendar working time on Friday 
Working calendar work start time on 
WORK.START TIME FRI 
Friday 
Working calendar working time on 
WORK.PERIOD ON SAT.
Saturday 
Working calendar work start time on 
WORK.START TIME SAT 
Saturday 
WORK.PERIOD ON SUN. Working calendar working time on Sunday 
Working calendar work start time on 
WORK.START TIME SUN 
Sunday 
Generator exercise working time on 
EXER.WORKING PERIOD 
related day 
EXER.WR.DAY OF WEEK  Generator exercise working day of week 
Generator exercise work start time on 
EXER.WORK.START TIM 
related day 

(DATE SETUP PAGE) DATE SETUP page


YEAR  YEAR 
MONTH  MONTH 
DATE  DATE 
DAY  DAY 
HOUR  HOUR 
MINUTE  MIN 
SECOND  SEC 

(PASSWORD PAGE) PASSWORD page


OPERATOR PASSWORD  OPERATOR PASSWORD 
TECHNICIAN PASSWORD  TECHNICIAN PASSWORD 

Change Date :...../...../.......


Change Technician Name :

EAOM-210 FL.eng / ver 0.7


Pages 154 / 154

You might also like