P&B Relays and Services Test Report For Motor Relay: 33/6.6Kv Ippl Plant

The document is a test report for a motor relay (model AFV2-1A, serial 153323) used in a 33/6.6kV IPPL plant. It summarizes the motor details, settings and results of tests of the relay's over voltage, earth fault, and over current protection functions. All protection functions were tested within their set parameters and time delays. The relay was found to be in good working condition based on the input, output, and protection function checks performed.

Uploaded by

8085ro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
271 views2 pages

P&B Relays and Services Test Report For Motor Relay: 33/6.6Kv Ippl Plant

The document is a test report for a motor relay (model AFV2-1A, serial 153323) used in a 33/6.6kV IPPL plant. It summarizes the motor details, settings and results of tests of the relay's over voltage, earth fault, and over current protection functions. All protection functions were tested within their set parameters and time delays. The relay was found to be in good working condition based on the input, output, and protection function checks performed.

Uploaded by

8085ro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

33/6.

6KV IPPL PLANT


P&B Relays and Services
TEST REPORT FOR MOTOR RELAY

TEST REPORT FOR EFV2 -1A


Customer : 33/6.6kv IPPL
Date : 14-02-2022

Model No : AFV2-1A Aux. Voltage : 110 VDC


Serial No : 153323 Frequency : 50 Hz

MOTOR DETAILS:

CT PRI RATIO 100 A / 1A

VT PRI 415 V

VT SEC 100 V

VOLTAGE REF Ph-N

EF CT 100 A

OVER VOLTAGE PROTECTION:


V< Set : 110%
OPERATING SET TIME OPERATING OPEARTING
S.NO Phase
Volts ( Sec ) Volts TIME ( Sec )
R-N 63.5 64.4
2 1.764 s
1. Y-N 63.5 64.4

B-N 63.5 64.4

EARTH FAULT 1 : D T
IE> Set : 10%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 1.1 1.13
1. Y-N 1 0.5 1 527.0 m
B-N 1 1

1
33/6.6KV IPPL PLANT
P&B Relays and Services
TEST REPORT FOR MOTOR RELAY

OVER CURRENT 1: D T
I> Set : 300%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 3 3.1
1. Y-N 3 2 3.1 2.065 s
B-N 3 3.1

TEST RESULTS:

MEASUREMENT CHECKS FOUND OK


PROTECTION FUNCTION CHECKS FOUND OK
OUTPUT RELAY CHECKS FOUND OK
INPUT CHECKS FOUND OK
RELAY FOUND HEALTHY ON ALL ASPECTS