(Catalogue 2011) Canalis
(Catalogue 2011) Canalis
from 20 to 800 A
Canalis®
Canalis
Schneider busway
Catalogue 2011
2011
1
19
25
29
31
33
37
39
43
47
50
52
55
59
65
83
87
89
91
94
98
In decentralised distribution,
Schneider Busway hits the high
note!
More than 70,000 km of Schneider busway has been sold Schneider is evolving to better integrate into
around the world.
your environment
They contribute to improving the working environment, whether in industrial buildings
or retail outlets.
Schneider Busway will now quite naturally fit into the Schneider Electric range of
electric power distribution products (Prisma Plus, Kaedra, etc.).
PD202311
3
With Schneider Busway, you play
all the right notes!
Distribution systems Schneider Electric offers different distribution systems to fit your operating needs.
DD221021
Centralised distribution
■ For all continuous processes:
● cement plants
● oil and gas
● petrochemicals
● steel
● paper, etc.
■Centralised distribution offers:
● continuity of service
● combined distribution of power, control and monitoring circuits
● supervision, etc.
Our solutions:
■ Prisma Plus and Okken switchboards.
Decentralised distribution
PD202044
Our solutions:
■ Prisma Plus switchboards
■ Schneider busway.
Combined distribution
PD202155
Our solutions:
■ Prisma Plus and Okken switchboards
■ Schneider busway.
4
With Schneider Busway, you play
all the right notes!
A competitive installation.
Simplicity, upgradeability, safety and continuity of service and operation.
Schneider busway
DD205658
5
For decentralised distribution
in tune with your needs!
Decentralised distribution
DD221022
for small sites
Maximum power available throughout the
installation.
The main busway distributes the full power of the
source.
6
For decentralised distribution
in tune with your needs!
Decentralised distribution
PD202045
for large sites
The simplicity of decentralised distribution
systems
The distribution system can be designed without
detailed knowledge of load locations. Only the source
and load characteristics are needed.
Busway is selected in advance with optimum results.
Easy upgrading
Schneider busway can easily adapt to installation
modifications or extensions. Simply move an existing
tap-off unit or add a new one at the desired location.
Total safety
Tap-units can be connected and disconnected without
de-energising the trunking.
Changes can therefore be made safely on live
installations:
■ Protection against direct contact
■ Mismatch prevention for tap-off units and automatic
compatibility between the performance levels of
tap-units equipped with circuit breakers and the
prospective short-circuit current at the point of
installation.
7
Schneider busway , in total
harmony with the environment!
Safety of life and property With Schneider busway, no toxic emission in case of fire
Schneider busway is halogen-free.
DD205675
Halogen-sensitive applications
■ Public buildings (infrastructures, hospitals, schools, etc.).
■ Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity
buildings.
■ Sensitive processes (production of electronic components, etc.).
Health
Schneider busway reduces the risk of exposure to
DD205674
electromagnetic fields
According to the WHO (World Health Organisation), exposure to electromagnetic
fields can be a health hazard starting at levels as low as 0.2 micro-Teslas and could
represent a long-term risk of cancer. Some countries have created standards that
stipulate limits (e.g. 0.2 µT at 1 metre in Sweden).
8
Schneider busway, in total
harmony with the environment!
■ All Schneider products are designed for safe end-of-life recycling. PVC, on the
other hand, requires neutralisation of the hydrochloric acid produced using lime and
generates dioxins that are extremely toxic.
23 kg 1600 Joules
90 kg 2000 Joules
9
10
Canalis, fortissimo throughout the
range!
PD202217
Run components
Degree of protection IP55 IP55
Number of circuits 1 1
Rating 20 A 25 and 40 A
Tap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 - 3000 mm 500 - 1000 - 1500 mm
Standard lengths 24 and 192 meters 2 and 3 meters
Finish - Galvanised steel
Maximum distance between fixing points 0.7 meter 3 meters
Tap-off units
PD202225
PD202225
11
Canalis, fortissimo throughout the
range!
Canalis KBB
PD202219
IP55
1 or 2
25 and 40 A
500 and 1000 mm
2 and 3 meters
Galvanised steel
5 meters
PD202225
10 and 16 A
12
Canalis, fortissimo throughout the
range!
Panorama of Canalis
medium power solutions
Power distribution
Range Canalis KS
PD202222
Run components
Degree of protection IP52/IP54
Polarity 3L + N + PE
Rating 100, 160, 250, 400, 500, 630,
800A
Tap-off intervals 1000 mm on each face
Standard lengths 1.5/2/3 meters
Finish
Maximum distance between fixing points 3 meters
Tap-off units
PD202089
13
Canalis, fortissimo throughout the
range!
IP52/IP54
3L + N + PE
100, 250, 400, 500, 630, 800A
500 mm
Defined by the floor pitch
25 to 400 A
-
14
Canalis, an installation that
matches your inspiration!
In a garage
PD202017
Characteristics of the garage:
■ Area 300 m2 (20 x 15 m)
■ Loads:
● 3 car lifts
● 1 compressor
● 1 wheel balancing machine
● portable tools
● fluorescent lighting.
DD210512
In a plastics factory
PD202018
15
Canalis, an installation that
matches your inspiration!
Canalis in warehouses
DD210515
Canalis products installed:
■ For power distribution:
● (1) 1 KS 160 A run, 15 m long, to supply the battery chargers
● (2) 1 KS 63 A run, 75 m long, to supply the automatic doors Prisma Plus System G electrical distribution switchboard
■ For lighting:
● (3) 1 KS run, 57 m long, to supply the lighting circuits
● (4) 9 KBA 25 A runs, 6 x 75 m long, 1 x 42 m long and 2 x 29 m long, to supply
ith few
● (5) 90 T5 2 x 80 W luminaires. Even w oints,
gp
lightin s is
C ali
a n
titive.
compe
16
Canalis, an installation that
matches your inspiration!
Canalis in a greenhouse
PD202021
■ Area 15000 m2 (150 x 100 m)
■ Loads:
● lighting by 600 W horticultural lamps
● rolling shutters.
DD210517
Canalis in a supermarket
17
Canalis, an installation that
matches your inspiration!
Canalis in offices
In a partitioned office
PD202023
DD210519
Canalis products installed: Prisma Plus System G electrical distribution switchboard
■ For power distribution:
(1) 2 KS 100 A runs, 21 m long, installed as feeders to supply the lighting circuits
■ For lighting:
asy
● (2) 4 KDP runs, 21 m long, to supply the 180 3 x 36 W luminaires s for e
● 7 KBC single-switch units for the offices Canali ut
layo s.
● 1 KBC two-way switch unit for the meeting room cation
● 3 timer switch units for the entrance, washrooms and hall. modifi
In an open-plan office
PD202024
18
Characteristics Canalis KDP, 20 A
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
19
Characteristics Canalis KBA, 25 and 40 A
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
20
Characteristics Canalis KBB, 25 and 40 A
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
21
Characteristics KBC tap-off units,
KDP connections
IP55
Ue = 230...400 V
General characteristics
Compliance with standards IEC/EN 60439-2
Degree of protection: IP 55 55 55
Rated current at an ambient temperature of 35°C Inc A 10 16 16
Rated insulation voltage Ui V 690 690 400
Rated operational voltage Ue V 230...400 230...400 230...400
Rated frequency f Hz 50/60 50/60 50/60
22
Characteristics Canalis KSA, 100 to 800 A
Busbar trunking for medium-power distribution
IP52/IP54
Ue = 230...690 V
Mechanical impacts IK 08 08 08 08 08 08 08
Rated current at an ambient temperature of 35°C Inc A 100 160 250 400 500 630 800
Rated insulation voltage Ui V 690 690 690 690 690 690 690
Rated operational voltage Ue V 690 690 690 690 690 690 690
Average reactance of loop Xb ph PE mΩ/m 0.605 0.292 0.323 0.303 0.295 0.225 0.226
Other characteristics
Short - circuit withstand capacity Icw kA 2.6 4.5 10.0 18.8 27.1 32.1 37.4
Short- circuit rated peak current Ipk kA 3.9 6.8 17.0 39.5 56.9 67.4 78.5
Degree of protection IP52 In normal mounting position, horizontal, edgewiseinstallation. Option IP54
IP50 Other positions: horizontal installation, flat, vertical installation. Option IP50
Voltage drop 3phase50Hz with load distrbuted along the run. If the load is concentrated at the end of the run,
the voltage drop are twice the values the table.
Cos. φ = 1,0 V/100 m/A 0.12081 0.05724 0.02546 0.01645 0.01065 0.00875 0.00528
Cos. φ = 0,9 V/100 m/A 0.12598 0.06031 0.03016 0.01904 0.01397 0.01051 0.00743
Cos. φ = 0,8 V/100 m/A 0.12039 0.05790 0.03034 0.01898 0.01455 0.01063 0.00792
Cos. φ = 0,7 V/100 m/A 0.11283 0.05448 0.02970 0.01844 0.01463 0.01045 0.00805
Derating / uprating factor 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C
Determination of permissible
Lz according to ambient temperature
1.11 1.08 1.06 1.03 1.00 0.97 0.94 0.91 0.87
23
Characteristics Canalis KSC, 100 to 800 A
Busbar trunking for medium-power distribution
IP52/IP54
Ue = 230...690 V
Mechanical impacts IK 08 08 08 08 08 08 08
Rated current at an ambient temperature of 35°C Inc A 100 160 250 400 500 630 800
Rated insulation voltage Ui V 690 690 690 690 690 690 690
Rated operational voltage Ue V 690 690 690 690 690 690 690
Average reactance of loop Xb ph PE mΩ/m 0.605 0.292 0.323 0.303 0.295 0.225 0.226
Other characteristics
Short - circuit withstand capacity Icw kA 2.6 4.1 10 21.5 25 31 34
Short - circuit peak current Ipk kA 3.9 6.2 17.0 45.2 52.5 65.1 71.4
Degree of protection IP52 In normal mounting position, horizontal, edgewiseinstallation. Option IP54
IP50 Other positions: horizontal installation, flat, vertical installation. Option IP50
Voltage drop 3phase50Hz with load distrbuted along the run. If the load is concentrated at the end of the run, the
voltage drop are twice the values the table.
Cos. φ = 1,0 V/100 m/A 0.10600 0.07395 0.02383 0.01331 0.00617 0.00779 0.00334
Cos. φ = 0,9 V/100 m/A 0.11265 0.07535 0.02870 0.01621 0.00993 0.00965 0.00568
Cos. φ = 0,8 V/100 m/A 0.10584 0.07127 0.01904 0.01647 0.01096 0.00987 0.00636
Cos. φ = 0,7 V/100 m/A 0.10246 0.06618 0.02856 0.01624 0.01149 0.00978 0.00673
Derating / uprating factor 15°C 20°C 25°C 30°C 35°C 40°C 45°C 50°C 55°C
Determination of permissible
Lz according to ambient temperature
1.11 1.08 1.06 1.03 1.00 0.97 0.94 0.91 0.87
24
1. Run components 2. Feed units
and end covers
■ Rating: 20 A. ■ The feed units deliv*ered with end covers receive
■ 2 or 4 live conductors. the cables supplying one end of Canalis KDP
■ Available in 24 or 192-metre reels. trunking.
PD202156
PD202157
PD202161
25
Canalis
KDP
3. Fixing system 4. Tap-off units
■ The fixing system is used to attach Canalis KDP to ■ The 10 and 16 A tap-off units, pre-wired or not, single-phase with fixed polarity
the sides of cable trays, metal structures or concrete or multi-phase with phase selection, can be used on the entire lighting range.
slabs.
PD202158
PD202159
26
27
28
Canalis
KDP
Description Canalis KDP, 20 A
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
bromine, etc.) releases dark, toxic and corrosive smoke. The latter can cause panic,
difficulties for rescue teams, intoxication and severe damage to electronic and
computer equipment.
KDP trunking, halogen free, avoids the above risks.
Run components
Carry the current and supply lighting fixtures.
The run components consist of:
1 A flat ribbon cable conforming to standard IEC 60502-1 with 3 or 5 x 2.5 mm2
DD210155
All the insulating and plastic materials have increased fire-retardant capacity:
■incandescent-wire test in compliance with IEC 60695-2:
■960°C for components in contact with live parts,
■650°C for other components.
KDP is certified to be non-flame-propagating in compliance with standard
IEC 60332-3.
The system as a whole complies with standard IEC 60439-2.
Uncoiler kit
DD210154
Makes for easy installation of KDP trunking by allowing the cable to be rolled out from
the reel.
It can be used with all standard roller-type uncoilers.
It clips onto the packing spools and can be removed for re-use.
1 Uncoiler kit (8 parts)
2 Packing spools.
3 Cable uncoiler (not supplied).
29
Description Canalis KDP, 20 A
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
Canalis
KDP
Fixing systems
These systems are used to fix KDP in accordance with recommended installation
methods.
30
Catalogue numbers Canalis KDP, 20 A
Dimensions Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
Run components
DD210087
KDP 20E●●●●●
1000-1300
DD210023
KDP20E●●024● KDP20E●●192●
DD210065
DD210027
31
Catalogue numbers Canalis KDP, 20 A
Dimensions Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
Canalis
KDP
Fixing systems
DD210074
KDP on a mesh tray
DD210090
KDP ZF10 KDP ZF11 KDP ZF12 KDP ZF13 KDP ZF14
DD210028
32
Presentation Canalis KBA 0
PD202164
PD202168
33
Presentation Canalis KBA 0
Canalis
There are also fixings to secure the luminaires to
KBA
Canalis KBA.
PD202165
PD202159
34
Presentation Canalis KBA 0
DD202141
In case of fire, Canalis KBA does not release smoke or
toxic gases.
PD202169
35
Presentation Canalis KBA 0
DD202158
trunking, it is possible to
create up to three levels
of illumination.
Canalis
KBA
DD202161
36
Description Canalis KBA, 25 and 40 A 0
Run components
Carry current, support and supply the luminaires.
Straight lengths
DD210476
Straight lengths constitute the basic structure of the line and are made up of:
1 an all-in-one carrier casing, crimp closed, forming a rigid beam made of sheet
steel, hot galvanised on both sides. This casing also acts as the protective earth
conductor (PE).
2 a ribbon cable with two or four copper conductors, protected against corrosion by
tinning,
3 two, three or five tap-off outlets,
4 an electrical jointing unit ensuring automatic and simultaneous connection of all
live conductors,
5 a mechanical joining device made of galvanised sheet steel that makes the
connection of two lengths rigid and resistant to bending.
37
Description Canalis KBA, 25 and 40 A 0
Flexible lengths
Flexible length
For changes in direction or levels and detours around
DD210478
obstacles.
It is mounted in the same way as a straight length.
Canalis
KBA
DD210479
Fixing systems
Busbar trunking
For attachment of the busbar trunking to the structure
DD210480
Luminaires
Attached to the luminaires before mounting, these
fixings ensure fast and direct fixing to Canalis KBA.
■ Same catalogue numbers as the busbar fixings.
DD210481
38
38
Catalogue numbers Canalis KBA, 25 and 40 A 0
Straight lengths
DD210086
KBA ●●ED●●● Type of Trunking Length Number 25 A rating Weight 40 A rating Weight
component polarity (m) of Cat. no. (kg) Cat. no. (kg)
tap-offs
Straight length
Standard 3 2 KBA 25ED2302 2.400 - -
DD210095
Ph + N + PE
3 KBA 25ED2303 2.400 KBA 40ED2303 2.700
5 KBA 25ED2305 2.400 KBA 40ED2305 2.700
2 2 KBA 25ED2202 1.900 - -
3 KBA 40ED2203 1.700 KBA 40ED2203 1.700
Straight length
Standard 3 2 KBA 25ED4302 2.400 - -
DD210096
3Ph + N + PE
3 KBA 25ED4303 2.600 KBA 40ED4303 3.100
5 KBA 25ED4305 2.600 KBA 40ED4305 3.100
2 2 KBA 25ED4202 1.900 - -
3 KBA 40ED4203 1.900 KBA 40ED4203 1.900
DD210026
DD210025
39
Catalogue numbers Canalis KBA, 25 and 40 A 0
Canalis
40 Left 10 PG 21, Ø 19 KBA 40ABG4 0.400
KBA
25 or 40 Right 10 PG 21, Ø 19 KBA 40ABD4 0.500
KBA 25ABG4
DD210034
KBA 40ABD4
Flexible lengths
DD210093
KBA 40DF4●●
KBA 40DF405
DD210032
KBA 40DF420
DD210033
40
Catalogue numbers Canalis KBA, 25 and 40 A 0
Fixing systems
Busbar trunking fixings
Designation Mounting Max. load Cat. no. Weight
(kg) (kg)
Universal fixing bracket(1) Suspended on threaded 60 KBA 40ZFU 0.050
rod or lateral (except wall)
Luminaire fixings
Designation Mounting Max. load Cat. no. Weight
(kg) (kg)
DD210105
KBA 40ZFU
DD210037
41
42
Canalis
KBA
Presentation Canalis KBB 0
PD202171
PD202173
43
Presentation Canalis KBB 0
Canalis
There are also fixings to secure the luminaires to
KBB
Canalis KBB.
PD202172
PD202439
44
Presentation Canalis KBB 0
DD202141
In case of fire, Canalis KBB does not release smoke or
toxic gases.
PD202174
45
Presentation Canalis KBB 0
DD202142
DD202163
■ IP55 guarantees distances of up to 5
trunking protection metres, including the
against splashes and jointing units.
dust.
Canalis
■ Canalis KBB complies
KBB
with sprinkler tests, guaranteering operation under
vertically and horizontally sprayed water for 50
minutes.
The high degree of protection for Canalis KBB
means it can be installed in all types of buildings.
46
Description Canalis KBB, 25 and 40 A 0
Run components
Carry current, support and supply the luminaires.
Particularly strong, Canalis KBB is specially intended for installations with large fixing
distances and/or heavy or numerous luminaires.
Straight lengths
DD210379
Straight lengths constitute the basic structure of the line and are made up of:
1 an all-in-one carrier casing, crimp closed, forming a rigid beam made of sheet
steel, hot galvanised on both sides. This casing also acts as the protective earth
conductor (PE).
2 one or two ribbon cable with two or four copper conductors, protected against
corrosion by tinning, making up one or two independent circuits,
3 three tap-off outlets maxi spaced every metre on the main circuit (front), two
tap-off outlets maxi on the adjacent circuit (rear),
4 an electrical joint unit ensuring automatic and simultaneous connection of all live
conductors,
5 a mechanical joint device in two parts, made of stamped sheet steel, that makes
the connection of two lengths rigid and resistant to bending.
47
Description Canalis KBB, 25 and 40 A 0
DD210381
The end cover for the opposite end of the line is
supplied with each feed unit.
Canalis
KBC
KBB
1 Feed unit, two circuits
2 End cover.
Flexible lengths
Flexible length
For changes in direction or levels and detours around
DD210382
obstacles.
It is mounted in the same way as a straight length.
DD210383
48
Description Canalis KBB, 25 and 40 A 0
Fixing systems
Busbar trunking
For attachment of the busbar trunking to the structure
DD210384
of the building, either directly or via a threaded rod,
chain or steel cable.
■ Designed to relieve the installer of the weight of the
busbar trunking once placed in a bracket.
■ The maximum recommended fixing distance is five
metres.
Luminaires
Attached to the luminaires before mounting, these
fixings ensure fast and direct fixing to Canalis KBB.
■ Fixing systems with automatic locking of moving part
on closing.
DD210385
49
Catalogue numbers Canalis KBB, 25 and 40 A, 2 circuits 0
Canalis
KBC
KBB
Type of Length Number 25 A rating Weight 40 A rating Weight
busbar trunking (m) of Cat. no. (kg) Cat. no. (kg)
tap-offs
KBB ●●ED●●●●●
Standard
straight 3 3+2 KBB 25ED22305 4,600 KBB 40ED22305 5,200
DD210108
length
2 2+1 KBB 40ED22203 3,600 KBB 40ED22203 3,600
DD210048
KBB 40ABD44●
50
Catalogue numbers Canalis KBB, 25 and 40 A 0
Flexible lengths
DD210102
KBB 40DF4●●● Designation Mounting For trunking Length Cat. no. Weight
(m) (kg)
Flexible lengths For elbows, 0.5 KBB 40DF4405 0.800
changing levels,
DD210109
detours around
2 KBB 40DF4420 1.900
obstacles, etc.
KBB 40DF4●●●
DD210043
Fixing systems
Busbar trunking fixings
Designation Mounting Max. load Cat. no. Weight
(kg) (kg)
Universal fixing bracket(1) Suspended on threaded 60 KBB 40ZFU 0.050
rod or lateral (except wall)
Luminaire fixings
Designation Mounting Max. load Cat. no. Weight
(kg) (kg)
DD210105
KBB 40ZFU
DD210037
51
Description Canalis KDP, KBA and KBB
Busbar trunking for lighting and
IP55 power socket distribution
Ue = 230...400 V
Tap-off units
Canalis
systems,
KBC
■selection is visible via a transparent window,
■a coloured lock holds them in the tap-off outlet,
■all the insulating and plastic materials have a high fire-retardant capacity:
□incandescent-wire test in compliance with IEC 60695-2:
- 960°C for components in contact with live parts,
- 650°C for other components.
■To be wired for connection of luminaires using a cable of specific type, size or
length.
■Fast connection for 3 x 0.75 to 1.5 mm2 cable. If prefabricated leads are used, the
line must have 16 A protection (see possibilities of dispensing with protection in the
simplified design guide for lighting distribution, in the section on protection against
overloads).
Accessories
Specific to KBC 16DCF tap-off units
DD210191
52
Catalogue numbers Canalis KDP, KBA and KBB tap-off
Dimensions units 0
L2 + N
DD210118
DD210126
DD210121
or
L3 + N
15 A gG
maximum
(not supplied)
KBC 16DC●40
53
54
Canalis
KBC
Presentation Canalis KS 0
PD202205
PD202208
55
Presentation Canalis KS 0
■The fixing system ensures that Canalis KS is well ■ The tap-off units (with and without isolators) have ratings of 25 to 400 A
secured, whatever the type of building structure. ■ Protection is ensured with modular or Compact NS circuit breakers or fuses.
PD202206
PD202207
Canalis
KS
56
Presentation Canalis KS 0
Joint-Pack
PD202209
DD202171
57
Presentation Canalis KS 0
Canalis
KS
58
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
Canalis KS is designed for medium-power distribution with high tap-off densities in industrial and commercial buildings (factories, exhibition
halls, supermarkets, etc.).
The range is available in eight ratings: 100, 160, 250, 400, 500, 630, 800 A.
Canalis KS provides an IP54 degree of protection, whatever the installation method. Consequently it can be installed in virtually any type
of building.
Tap-offs are implemented by tap-off units from 25 to 400 A that may be removed in complete safety under energised conditions,
from 25 to 400 A.
Busbar trunking rated 100 to 250 A may be equipped with tap-off units up to 160 A.
Busbar trunking with higher ratings may be equipped with the entire range of tap-off units.
All the insulating and plastic materials are halogen-free and have enhanced fire-withstand capabilities
■ incandescent wire test as per standard IEC 60695-2 :
□ 960°C for components in contact with live parts,
□ 650°C for other components.
Straight lengths
Distribution components
DD210264
Straight lengths are designed to carry current and feed loads with low or medium power. the straight lengths form the
structure of the run. They comprise:
1 A casing of galvanized sheet steel, which is crimped closed.
This casing, shaped and ribbed by rolling, provides excellent resistance to bending and twisting.
Three casing widths cover the whole range. Casings are available in two finishes:
-52.4 mm wide sheet steel with white finished for 100, 160 and 250A ratings
-73 mm wide sheet steel with white finished for 400 and 500 A ratings.
-109 mm wide sheet steel with white finished for 630 and 800 A ratings.
2 4 live conductors of the same cross-section:
-High purity electrical copper bar for KSC 100 to 800 ratings.
-High purtiy electrical aluminum bar for KSA 100 to 800 ratings with silver-plated copper contact.
3 Fibreglass reinforced polyester isolators, at 250 mm intervals.These hold the conductors securely within the casing.
4 A special protected earth (PE) conductor with a cross-section 1/2 of three phase cross-section. It is connected to the casing at each
junction.
5 Tap-off outlets on both sides of the trucking, at 0.5 or 1 m intervals.
They have a shuttered outlet which is opened and closed automatically when connectors or tap-off units are plugged in or removed.
6 A mechanical and electrical jointing device.
Electrical connection is via a block with spring and silver graphite contacts. This block absorbs the differential conductor/casing expansion
of each length equally.
For 100,160 and 250 A ratings, it automatically and simultaneously connects all the live conductors, ensures continuity of the protective
earth conductor and its connection with the casing. For higher ratings(400 to 800A), the electrical connection is made by a 1/4 screw turn for
each conductor.
Special components
1 Custom-length run components
Used to adjust the length of a line (e.g. between
DD210265
2 Fire barrier
This type of length is used to transit a fire-proof wall
(e.g. between two rooms in a building).
It has been tested in a certified laboratory and
complies with standard EN 1363-1.
The laboratory report lists the following results:
□ thermal insulation:≥120 minutes,
□ resistance to flames:≥120 minutes,
□ stability: ≥120 minutes.
59
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
DD210267
busbars in a switchboard. They can be mounted at the
end of a line (end feed, left or right) or in the middle
(central feed).
Canalis
is supplied with an end cover.
KS
5 End cover
DD210268
1 Edgewise elbow
One model for turning right or left.
2 Flat elbows
Two models, one for turning up and the other for
turning down.
3 Edgewise tee
To create branches perpendicular to the main line.
Sprinkler kit
To comply with the sprinkler tests (guaranteeing
operation under vertically and horizontally sprayed
water for 50 minutes), each electrical jointing system
should be fitted with a reinforced protection kit (the
jointing sleeve).
60
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
Fixing systems
The maximum recommended fixing distance is three
metres.
DD210273
1 Universal fixing bracket
For attachment of the busbar trunking to the
structure of the building, either directly or via a
threaded rod M8, brackets, etc.
Suspension using chains or steel cables is not
advised.
Tap-off units
61
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
DD210277
up to 100 A are made of plastic:
■ Colour: RAL 9001 white for the casing and the grip
zones and transparent green for the cover (design
based on Kaedra enclosures),The fixing mechanisms
are in RAL 7016
■ Material: self-extinguishing, halogen free insulating
plastic (fire resistant and very high temperature
withstand).
DD210279
■ Other characteristics: cable gland drilling zone,
stainless steel screws and the door can be lead sealed.
Canalis
25 mm and designed for maximum access.
KS
Disconnection principle:
62
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
DD210282
devices (18 mm wide) of the Multi 9 type:
■ rated current: 32 A,
■ capacity: 5 modules,
■ with a window in front for visual and physical access
to the devices. A transparent cover seals the window.
63
Description Canalis KS, 100 to 800 A 0
Medium-power distribution
IP54
Ue = 230...690 V
DD210302
household or industrial plugs in a garage, maintenance
workshop, laboratory, battery charging room, etc
For installation on trunking mounted on a wall for better
access.
For easy access, install on trunking mounted at an
appropriate height on the wall.
Flexibility, upgradeability: positioned as close as
possible to the loads, extension leads are not required
, earth-leakage protection.
Rated current: 32 A
Capacity: 8 modules in multiples of 18 mm wide
DD210459
Canalis
KS
Tap-off units for fuses (not equipped)
For protection of the tap-off by fuses (not supplied).
DD210287
64
Catalogue numbers Canalis KSA, 100 to 250 A 0
Standard lengths
Rating Length Number of Cat. no. Order Generic Weight
Polarity (A) (mm) tap-off outlets (kg)
3L + N + PE or 3 L + PEN 100 3000 6 KSA10EA430 KSA10PG 11.90
2000 8 KSA25ED420 KSA25PG 10.65
1500 6 KSA25ED415 KSA25PG 8.35
160 3000 6 KSA16EA430 KSA16PG 13.20
2000 8 KSA25ED420 KSA25PG 10.65
1500 6 KSA25ED415 KSA25PG 8.35
250 3000 6 KSA25EA430 KSA25PG 15.50
2000 8 KSA25ED420 KSA25PG 10.65
1500 6 KSA25ED415 KSA25PG 8.35
KSA**EA430 KSA25ED420
KSA25ED415
Standard lengths
Rating Length Cat. no. Order Generic Weight
Polarity (A) (mm) (kg)
3L + N + PE or 3 L + PEN 100 3000 KSA10ET430 KSA10FG 11.90
2000 KSA25ET420 KSA25FG 10.65
1500 KSA25ET415 KSA25FG 8.35
160 3000 KSA16ET430 KSA16FG 13.20
2000 KSA25ET420 KSA25FG 10.65
1500 KSA25ET415 KSA25FG 8.35
250 3000 KSA25ET430 KSA25FG 15.50
2000 KSA25ET420 KSA25FG 10.65
1500 KSA25ET415 KSA25FG 8.35
KSA**ET430 KSA25ET420
KSA25ET415
65
Catalogue numbers Canalis KSA, 100 to 250 A 0
Feed units
End feed unit 100 to 250 Right or left 6.35 X 38.1 KSA25AB42 KSA25PG+KSA25ETB 7.20
Canalis
KS
KSA25AB42
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
Flange feed unit 100 to 250 Right or left 6.35 X 38.1 KSA25ER4 KSA25PG+KSA25FE 1.70
KSA25ER4
Fixing system
KSA25EZ1
66
Catalogue numbers Canalis KSA, 100 to 250 A 0
Elbow
KSA25LP4*
DD210309
KSA25LC40
KSA25TC40
DD210310
KSA25TC40
Accessaries
Spare parts
Designation Rating For Cat. no. Weight
(A) (kg)
Joint Pack 100 to 250 KSB25YA4 1.41
DD202019
KSB25YA4
Ip54 accessory
DD202021
KSE80YA2
67
Catalogue numbers Canalis KSA, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Standard lengths
Rating Length Number of tap-off Cat. no. Order Generic Weight
Polarity (A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 400 3000 6 KSA40ED430 KSA40PG 25.00
2000 6 KSA40ED420 KSA40PG 13.90
DD210638
KSA**ED430 KSA**ED420
KSA**ED415
Canalis
KS
Straight lengths without tap-off outlets
Standard lengths
Rating Length Cat. no. Order Generic Weight
Polarity (A) (mm) (kg)
3L + N + PE or 3L + PEN 400 3000 KSA40ET430 KSA40FG 25.00
2000 KSA40ET420 KSA40FG 13.90
1500 KSA40ET415 KSA40FG 10.85
500 3000 KSA50ET430 KSA50FG 28.00
2000 KSA50ET420 KSA50FG 20.00
1500 KSA50ET415 KSA50FG 15.90
KSA**ET430 KSA**ET420
KSA**ET415
68
Catalogue numbers Canalis KSA, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Special lengths
Rating Length15 Option Cat. no. Order Generic Weight
Polarity (A) (kg)
3L + N + PE or 3L + PEN 400 to 500 515 to 2300 - KSA50ES4AG KSA50PG 15.00
900 to 2300 With Smoke barrier KSA50EF4AG KSA50PG 15.67
Feed units
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
DD202027
KSA50AB452 KSA50AB462
KSA50AB4*2
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
Flange feed unit 400 to 500 Right or Left 8.0X41 KSA50ER4 KSA50PG KSA50FE 4.10
KSA50ER4
Fixing system
KSA50EZ3
69
Catalogue numbers Canalis KSA, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Elbow
KSA50LC40
DD202057
KSA50TC40
Canalis
KS
KSA50TC40
Accessaries
Spare parts
Designation Rating For Order in Cat. no. Weight
(A) muitples of (kg)
Electrical and mechanical 400 to 500 1 KSB50YA4 3.26
DD202019
jointing unit
KSB50YA4
IP54 accessory
Designation Rating For Order in Cat. no. Weight
DD202021
KSE50YA2
70
Catalogue numbers Canalis KSA, 630 to 800 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Standard lengths
Polarity Rating Length Number of tap-off Cat. no. Order Generic Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 630 3000 6 KSA63ED430 KSA63PG 36.20
2000 6 KSA63ED420 KSA63PG 26.00
DD210638
KSA**ED430 KSA**ED420
KSA**ED415
Standard lengths
Polarity Rating Length Cat. no. Order Generic Weight
(A) (mm) (kg)
3L + N + PE or 3L + PEN 630 3000 KSA63ET430 KSA63FG 36.20
2000 KSA63ET420 KSA63FG 26.00
1500 KSA63ET415 KSA63FG 20.50
800 3000 KSA80ET430 KSA80FG 43.50
2000 KSA80ET420 KSA80FG 30.60
1500 KSA80ET415 KSA80FG 24.00
KSA**ET430 KSA**ET420
KSA**ET415
71
Catalogue numbers Canalis KSA, 630 to 800 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Special lengths
Rating Length Option Cat. no. Order Generic Weight
Polarity (A) (mm) (kg)
3L + N + PE or 3L + PEN 630 to 800 515 to 2300 - KSA80ES4AG KSA80PG 19.6
900 to 2300 With Smoke barrier KSA80EF4AG KSA80PG 20.2
Feed units
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
DD202071
KSA80AB452 KSA80AB462
Canalis
KS
KSA80AB4*2
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
Flange feed unit 630 to 800 Right or Left 8.0X71 KSA80ER4 KSA80PG KSA80FE 6.15
KSA80ER4
Fixing system
KSA80EZ3
72
Catalogue numbers Canalis KSA, 630 to 800 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Elbow
KSA80LP4*
DD202056
KSA80LC40 KSA80TC40
DD202057
KSA80TC40
Accessaries
Spare parts
Designation Rating For Order in Cat. no. Weight
(A) muitples of (kg)
Joint Pack 630 to 800 1 KSB80YA4 4.523
DD202019
KSB80YA4
Ip54 accessory
Designation Rating For Order in Cat. no. Weight
DD202021
KSE80YA2
73
Catalogue numbers Canalis KSC, 100 to 250 A 0
Standard lengths
Rating Length Number of Cat. no. Order Generic Weight
Polarity (A) (mm) tap-off outlets (kg)
3L + N + PE or 3 L + PEN 100 3000 6 KSC10EA430 KSC10PG 12.96
2000 8 KSC25ED420 KSC25PG 13.50
1500 6 KSC25ED415 KSC25PG 10.45
160 3000 6 KSC16EA430 KSC16PG 13.99
2000 8 KSC25ED420 KSC25PG 13.50
1500 6 KSC25ED415 KSC25PG 10.45
250 3000 6 KSC25EA430 KSC25PG 20.11
2000 8 KSC25ED420 KSC25PG 13.50
1500 6 KSC25ED415 KSC25PG 10.45
KSC**EA430 KSC25ED420
KSC25ED415
Canalis
KS
74
Catalogue numbers Canalis KSC, 100 to 250 A 0
Feed units
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
DD210295
End feed unit 100 to 250 Right or left 6.35 X 38.1 KSC25AB42 KSC25PG KSC25ETB 8.83
KSC25AB42
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
Flange feed unit 100 to 250 Right or left 6.35 X 38.1 KSC25ER4 KSC25PG KSC25FE 3.33
KSC25ER4
Fixing system
KSA25EZ1
75
Catalogue numbers Canalis KSC, 100 to 250 A 0
Elbow
KSC25LP4*
DD210309
KSC25LC40
KSC25TC40
Canalis
DD210310
KS
KSC25TC40
Accessaries
Spare parts
Designation Rating For Order in Cat. no. Weight
(A) muitples of (kg)
Joint Pack 100 to 250 1 KSB25YA4 1.41
DD202019
KSB25YA4
DD202021
IP54 accessory
Designation Rating For Order in Cat. no. Weight
KSE80YB2
(A) muitples of (kg)
PIO Cover 100 to 800 1 KSE80YB2 0.8
KSE25YA3
76
Catalogue numbers Canalis KSC, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Standard lengths
Rating Length Number of tap-off Cat. no. Order Generic Weight
Polarity (A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 400 3000 6 KSC40ED430 KSC40PG 33.86
2000 6 KSC40ED420 KSC40PG 19.76
DD210638
KSC**ED430 KSC**ED420
KSC**ED415
77
Catalogue numbers Canalis KSC, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Special lengths
Rating Length Option Cat. no. Order Generic Weight
Polarity (A) (mm) (kg)
3L + N + PE or 3L + PEN 400 515 to 2300 - KSC40ES4AG KSC40PG 15.16
900 to 2300 With Smoke barrier KSC40EF41AG KSC40PG 15.76
500 515 to 2300 - KSC50ES4AG KSC50PG 17.52
900 to 2300 With Smoke barrier KSC50EF41AG KSC50PG 18.12
Feed units
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
DD202027
Canalis
KSC50AB452 KSC50AB462
KS
KSC50AB4*2
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
Flange feed unit 400 to 500 Right or Left 8.0X41 KSC50ER4 KSC50PG + KSC50FE 6.77
KSC50ER4
Fixing system
KSA50EZ3
78
Catalogue numbers Canalis KSC, 400 to 500 A
Dimensions Busbar trunking for medium-power distribution
IP54
Ue = 230...690 V
Elbow
KSC50LC40
DD202057
KSC50TC40
KSC50TC40
Accessories
Spare parts
Designation Rating For Order in Cat. no. Weight
(A) muitples of (kg)
Electrical and mechanical 400 to 500 1 KSB50YA4 3.26
DD202019
jointing unit
KSB50YA4
IP54 accessory
DD202021
KSE50YA2
79
Catalogue numbers Canalis KSC, 630 to 800 A
Dimensions Busbar trunking medium-power distribution
IP54
Ue = 230...690 V
Standard lengths
Polarity Rating Length Number of tap-off Cat. no. Order Generic Weight
(A) (mm) outlets (kg)
3L + N + PE or 3L + PEN 630 3000 6 KSC63ED430 KSC63PG 50.95
2000 6 KSC63ED420 KSC63PG 35.76
DD210638
KSC**ED430 KSC**ED420
KSC**ED415
Canalis
KS
80
Catalogue numbers Canalis KSC, 630 to 800 A
Dimensions Busbar trunking medium-power distribution
IP54
Ue = 230...690 V
Special lengths
Rating Length Option Cat. no. Order Generic Weight
Polarity (A) (mm) (kg)
3L + N + PE or 3L + PEN 630 515 to 2300 - KSC63ES4AG KSC63PG 19.64
900 to 2300 With Smoke barrier KSC63EF41AG KSC63PG 20.24
800 515 to 2300 - KSC80ES4AG KSC80PG 24.27
900 to 2300 With Smoke barrier KSC80EF41AG KSC80PG 24.87
Feed units
Designation Rating Mounting Max. size Cat. no. Order Generic Weight
(A) (mm2) (kg)
DD202071
End feed unit 630 to 800 Right 8.0 x 71 KSC80AB452 KSC80PG + KSC80ETB 47.91
Left 8.0 x 71 KSC80AB462 KSC80PG + KSC80ETB 47.91
KSC80AB452 KSC80AB462
KSC80AB4*2
KSC80ER4
Fixing system
KSA80EZ3
81
Catalogue numbers Canalis KSC, 630 to 800 A
Dimensions Busbar trunking medium-power distribution
IP54 Complementary products
Ue = 230...690 V
Elbow
KSC80LP4*
DD202056
KSC80LC40 KSC80TC40
Canalis
KS
DD202057
KSC80TC40
Accessories
Spare parts
Designation Rating For Order in Cat. no. Weight
(A) muitples of (kg)
Joint Pack 630 to 800 1 KSB80YA4 4.523
DD202019
KSB80YA4
Ip54 accessory
DD202021
KSE80YA2
82
Presentation Canalis KSA, 100 to 800 A 0
83
Presentation Canalis KSA, 100 to 800 A 0
PD202212
Canalis
KS
3. Fixing system 4. Tap-off units
■The fixing system is made up of ■The tap-off units (with and without isolators) are used to supply loads from 25 to
□floor supports for the riser. 400 A.
■Protection using modular or Compact NS circuit breakers or fuses.
PD202213
PD202214
84
Presentation Canalis KSA, 100 to 800 A 0
85
Presentation Canalis KSA, 100 to 800 A 0
Canalis
Floor-distribution components are designed to facilitate:
KS
■access to the straight lengths on floors given the narrowness of lift shafts and
stairways,
■installation of the straight lengths given the height of doors and the size of shafts
and technical ducts.
Because the available space in technical ducts is limited, Canalis KS gives the
advantage to use significantly less room compared to a centralised distribution
system using cables.
Installation is made easy due to the design of the jointing units that facilitate
alignment of the straight lengths.
components in the no maintenance is required on the line. All sliding jointing contacts are lubricated
Canalis KS range offer 3 for the life of the product.
or 4 tap-off outlets per
floor, enough to have
reserve outlets for future
upgrades.
86
Description Canalis KSA, 100 to 800 A 0
General
Canalis KS risers distribute power to each floor in multi-level buildings (office
buildings, hotels, hospitals, car parks and ships).
DD210675
For more detailed description, see “Canalis 100 to 800 A for power distribution”
When installed vertically, the Canalis KS degree of protection is IP54 with accessory.
B Use floor supports . They are used Rating (A) Max. Max.
to support the riser on each floor of recommended recommended
height weight by
the building, for enhanced flexibility
support
in carrying out the various
100 and 250 40 m 680 kg
installation phases. With this
400 30 m 680 kg
support, riser sections can be
500 70 m 1760 kg
installed even when the lower floors
630 50 m 1760 kg
have not been completed.
800 50 m 1760 kg
C Use custom-length fire barriers to block fire propagation between floors. They
also provide the means to adjust to the distance between floors.
D Use standard straight lengths, 1.5 or 2.0 metres long. Lengths and fire barriers
can be combined to provide:
Solution 1: for a distance of 2900 mm to 4300 mm between floors, with
KS***EV415 straight lengths,
Solution 2 : for a distance of 3400 mm to 4800 mm between floors, with
KS***EV420 straight lengths,
Solution 1: Solution 2:
DD210676
DD210677
87
Description Canalis KSA, 100 to 800 A 0
Riser components
1 Straight lengths for distribution
Specially designed for rising mains, they are available in two lengths (1.5 and
DD210678
2.0 metres).
They have three or four tap-off outlets, all on the same side. The outlets are
positioned to enable connection of up to three 160 A tap-off units for Compact
NS circuit breakers on the 1.5 metre lengths and up to four on the 2.0 metre
lengths.
Canalis
The plate can be removed and is not pre-drilled.
KS
Fixing systems
4 Floor supports
Secured to the floor or wall (via Canalis 200 mm cantilever arms), they attach
to the sides of a special component (with or without fire barrier).
Tap-off units
Standard KS tap-off units are used
Accessories
Sprinkler kit
To comply with the sprinkler tests (guaranteeing operation under vertically and
horizontally sprayed water for 50 minutes), each electrical jointing system should be
fitted with a reinforced protection kit (the jointing sleeve).
88
Catalogue numbers Canalis KSA, 100 to 800 A 0
Fixing system
KS01000ZV3
Designation Rating Max. load Mounting Order in Cat. no. Weight
(A) (kg) multiples (kg)
of
Spring hanger 100 to 400 Vertical application 1 KS01000ZV3 3.50
800
89
Catalogue numbers Canalis KSC, 100 to 800 A 0
Fixing system
KS01000ZV3
Designation Rating Max. load Mounting Order in Cat. no. Weight
(A) (kg) multiples (kg)
Canalis
of
KS
Spring hanger 100 to 400 Vertical application 1 KS01000ZV3 3.50
800
90
Catalogue numbers Canalis KS,32 to 100 A
Dimensions Tap-off units for modular devices
IP54
Ue = 230...690 V
Tap-off units
Disconnection by unplugging the tap-off unit
DD210451
protection)
Rating Number of Connection Max. size Cable gland(4) Cat. no. Weight
KSB 32CM55 (A) 18 mm (mm2) (not supplied) (kg)
modules(3) Flexible Rigid
32 5 Pre wired 6 10 ISO 32 max. KSB 32CM55 0.60
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plate (1x5 divisible).
(4) Maximum diameter for a multipolar cable.
KSB 32CM55
DD210453
Cable exit
Centre line of tap-off outlets
(5) Protruding
DD205034
protection)
Rating Number of Connection Max. size Cable gland(4) Cat. no. Cat. no. Weight
KSB 63SM*8, (A) 18 mm (mm2) (not supplied) (kg)
KSB 100SM*12 modules(3) Flexible Rigid
63 8 Copper cable 16 16 ISO 50 max. KSB 63SM48 KSB 63SM58 2.40
lugs
100 12 Copper cable 35 35 ISO 63 max. KSB 100SM412 KSB 100SM512 5.00
lugs
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Supplied with blanking plates:(1x5 divisible (8 modules) or 2x5 divisible (12 modules)).
(4) Maximum diameter for a multipolar cable.
KSB 63SM*8, KSB 100SM*12
DD210455
A 357 444
B 158 183
C 167 202
D 309 397
E 108 133
F 202 220
X = 432.5 (KSB 63SM*8)
X = 545.5 (KSB 100SM*12)
Cable exit (5) Protruding
Centre line of tap-off outlets
91
Catalogue numbers Canalis KS,32 A
Dimensions Tap-off unit with power sockets protected by modular devices
IP54
Ue = 230...690 V
DD205035
sockets used
NF
1 Industrial socket 16 415 3P+N+T
Canalis
KS
1 Industrial socket 16 415 3P+N+T
KSB 32CP
(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Supplied with blanking plate (1x5 divisible).
DD210459
(3) Quantity
KSB 32CP***
DD210460
KSB 32CP
Power sockets
Designation Rated current Rated voltage Number of poles Dimensions Cat. no. Weight
(A) (V AC) (W x H in mm) (kg)
Industrial sockets 16 200-250 2P + T 65 x 85 PKY16F723 -
Pratika 3P + N + T 90 x 100 PKY16F725 -
380-415 2P + T 65 x 85 PKY16F733 -
3P + N + T 90 x 100 PKY16F735 -
32 200-250 2P + T 90 x 100 PKY32F723 -
3P + N + T 90 x 100 PKY32F725 -
380-415 2P + T 90 x 100 PKY32F733 -
3P + N + T 90 x 100 PKY32F735 -
Household NF sockets 10 to 16 250 2P + T 65 x 85 81140 -
Household Schuko sockets 10 to 16 250 2P + T 65 x 85 81141 -
Screw-on plate For blanking of unused openings 13137 0.10
For adapting 65 x 85 mm power-socket bases 13136 0.09
92
Catalogue numbers Canalis KS, 160 to 400 A
Dimensions Tap-off units for Compact NS circuit breakers
Ue = 230...690 V
DD210451
DD210452
protection)
NSXF breaker 3 NSXF breaker 3 NSXF breaker 4 NSXN breaker 3 NSXN breaker 4P
Rating Scheme Weight Isc Weight Isc Weight Isc Weight Isc Weight Isc
(A) kg KA kg KA kg KA kg KA kg KA
25 KSA02NSD311 KSA02NSXF311 KSA02NSXF411
6.48 25 10.6 25 11.1 25
*For KSA06NSD311 the rated current is 60A, for KSA06NSN311 and KSA06NSH311 the rated current are 63A.
*For IP54 tap-off units with compact NS, follow above catalog numbers and change “KSA” to “KSE”.
KSA25NS●●311/411
93
Canalis
KS
135 500 500 500 500 500 365
865 500 500 500 500 135
3000
135 500 500 500 500 500 365
865 500 500 500 500 135
3000
500
230
KSB80EZDC1 HFDC1 KSB80EZDC1
742
165
KSB80EZDC2 HFDC2 KSB80EZDC2
427
Canalis
KS
1000
KSB80EZDC3
279
95
KSB1000ZV2
25
25
KFB25CD253
Design guide Simplified design guide
Design
for lighting distribution
guide
Installation
Fixing distance
KBA and KBB busbar trunking
DD210206
The fixing distance for KBA and KBB busbar trunking depends on the number and weight of the luminaires, as well as the building structure.
The table below indicates the maximum permissible load (kg) between two fixing points for a deflection of
1/500. If the load is concentrated between two fixing points (mercury-vapour lamps), apply a coefficient of 0.6 to the values.
Maximum load
(kg)
Type of tap-offs Fixing
busbar distance (m) distance a (m)
trunking
2 2.5 3 3.5 4 4.5 5 5.5 6
KBA 1 34 22 15 no load
0.5 29 19 13 no load
KBB 1 circuit 60 60 48 35 27 21 17 no load
2 circuits 60 51 41 30 23 18 15 no load
The tables below indicate the possible fixing distances in metres for a deflection
of 1/350, depending on the type of luminaire used and the installation method
(trunking installed edgewise). .
Mercury-vapour luminaires
Between two fixing points Next to a fixing point
DD205013
98
Design guide Simplified design guide
for lighting distribution
Check on voltage drop
DD205021
% Un
Canalis KN or KS % Un
% Un
(1) Wherever possible, voltage drops in final lighting circuits must not exceed 3 %. When the main
busbar trunking in the installation is longer than 100 metres, the permissible values may be
increased 0.005 % per metre of trunking over 100 metres, on the condition that the total addition
not exceed 0.5 %.
■ Convert into volts the % of the rated voltage (Un) assigned to each circuit.
■ Using the tables, check that the trunking and/or cables selected in the previous
pages are compatible with the calculated voltage drops.
Otherwise, it is necessary to increase the size of the cables.
Remarks
■ In a mixed circuit, the most economical option is to increase the size of cables and
avoid the use of prefabricated trunking with a higher rated current (Inc).
■ For certain loads, it may be necessary to take into account transient voltage drops.
99
Design guide Simplified design guide
Design
for lighting distribution
guide
Check on voltage drop
Voltage-drop conversion
Operational Voltage drop in volts for a given %
voltage (V) 0.3 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 6 7 8 9 10
230 0.7 1.2 2.3 3.5 4.6 5.8 6.9 8.1 9.2 10 12 14 16 18 21 23
400 1.2 2 4 6 8 10 12 14 16 18 20 24 28 32 36 40
100
Design guide Simplified design guide
Determining the degree of protection
Degree of protection IP
Standard IEC 60529 (February 2001) indicates the degree of protection provided by electrical equipment enclosures against accidental direct
contact with live parts and against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or conditions such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional letter when the actual protection of persons against direct contact
with live parts is better than that indicated by the first numeral.
The first numeral characterises the protection of the equipment against penetration of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against penetration of water with harmful effects.
Meaning of the numerals and letters representing the degree of protection IP.
1st characteristic numeral: corresponds to protection of equipment against 2nd characteristic numeral: corresponds to
penetration of solid objects and protection of persons against direct contact with live protection of equipment against penetration of
parts. water with harmful effects.
Protection of equipment Protection of persons Protection of equipment
Non-protected Non-protected Non-protected
0 0
Protected against the Protected against direct Protected against vertical
penetration of solid objects contact with the back of the dripping water
1 1
DD210014
DD210006
having a diameter greater than hand (accidental contact). (condensation).
or equal to 50 mm.
Protected against the Protected against direct Protected against dripping
penetration of solid objects finger contact. water at an angle of up to
2 2
DD210531
DD210007
having a diameter greater than 15°.
or equal to 12.5 mm.
Protected against the Protected against direct Protected against rain at an
penetration of solid objects contact angle of up to 60°.
3 3
DD210532
DD210008
having a diameter greater than with a 2.5 mm diameter tool.
or equal to 2.5 mm.
Protected against the Protected against direct Protected against splashing
penetration of solid objects contact with a 1 mm diameter water in all directions.
4 4
DD210017
DD210009
having a diameter greater than wire.
1 mm.
Dust protected Protected against direct Protected against water jets
(no harmful deposits). contact with a 1 mm diameter in all directions.
DD210018
DD210010
wire. 5 5
Dust tight. Protected against direct Protected against powerful
contact with a 1 mm diameter jets of water and waves.
DD210019
DD210011
wire. 6 6
Protected against the effects
of temporary immersion.
7
DD210012
101
Recommendations for How Canalis compensate
special applications For thermal expansion
Foreword
Prefabricated electrical trunking components expand and contract due to:
■ changes in ambient temperature (e.g. summer and winter)
■ current flowing in the conductors (e.g. 0 to In).
For example, consider a 30 metre long 800 A Canalis KS line equipped with ten
160 A tap-off units and installed under the roof of a building where the ambient
temperature varies by more than 30 °C between summer and winter:
■ just the change in the ambient temperature results in an expansion of 20 mm for
the conductors and the 10 mm for the casing
■ at a constant ambient temperature, the temperature rise in the conductors every
morning when the installation is started (increase in current from 0 to In = 800 A)
results in an expansion of 55 mm for the conductors and 7 mm for the casing.
The lengths of the sheet steel (1) and the aluminium conductors (2) therefore vary as
a function of the changes in temperature and their specific thermal expansion
coefficients.
PD202309
For this reason, Canalis components are designed so that these phenomena do not
affect their installation or operation.
How Canalis trunking components effectively compensate for the effects of conductor thermal expansion.
Inside a trunking section, the conductors are fixed (1) at a single point in the casing
and, due to the change in temperature, expand (V) on either side of that point. The
zones affected by expansion and considered critical from the electrical standpoint
are the jointing system (2) and tap-off outlets (3).
DD202281
applications
Special
102
Recommendations for How Canalis compensate
Special application For thermal expansion
How Canalis trunking components effectively compensate for the effects of conductor thermal expansion.
■ the Canalis jointing system mechanically and electrically connects components
(e.g. two straight lengths), but allows for the expansion and contraction of the
conductors (4).
The system is made up of springs (1) and an area of sliding contacts (2) that allow
conductor movement ( ) while maintaining outstanding electrical contact.
Contact quality is ensured by two parts made of silver-plated copper (3). Sufficient
pressure between the two parts for good contact is maintained by the springs.
This system is used at each end of the straight lengths, every three metres.
DD202282
1 Spring of clamps.
2 Copper area.
DD202283
Conclusion: at both the jointing system and the tap-off outlets, sliding contacts can
handle the expansion of the conductors.
These maintenance-free silver-plated contacts are guaranteed for life.
Only the expansion of the sheet steel must be taken into account for Canalis
installation, however the problem is minor because both trials and
calculations show that expansion is only approximately 1 mm for every
three-metre length under extreme operating conditions.
103
Recommendations for Measurements and metering
special applications Transparent Ready units
DD205666
DD205668
DD205671
104
Recommendations for Measurements and metering
special applications Transparent Ready units
PowerLogic PM810 Power Meter, a Compact NS circuit breaker and the associated
current transformers, must be installed in the tap-off unit equipped with a mounting
plate and a DIN rail .
105