Bridge - Introduction To LRFD Loads and Load Distribution
Bridge - Introduction To LRFD Loads and Load Distribution
Loads and
Loads Distribution
Evolution of Design
Methodologies
SLD Methodology:
(ft)D + (ft)L ≤ 0.55Fy, or
1.82(ft)D + 1.82(ft)L ≤ Fy
LFD Methodology:
1.3[1.0(ft)D + 5/3(ft)L] ≤ φFy, or
1.3(ft)D + 2.17(ft)L ≤ φFy (φ by judgment)
LRFD Methodology:
1.25(ft)D + 1.75(ft)L ≤ φFy (φ by calibration)
(new live-load model)
Evolution of Design
Methodologies (cont’d)
considerable 4
RELIABILITY INDEX
clustering of
reliability indices
2
Standard 0
0 30 60 90 120 200
Specifications. SPAN LENGTH (Feet)
LFD
LRFD
γi = Load factor
φ = Resistance factor
Qi = Nominal force effect
Rn = Nominal resistance
Rr = Factored resistance = φRn
SERVICE I : normal operational use of the bridge with a 55 mph wind and nominal loads.
Also control cracking of reinforced concrete structures.
FATIGUE : repetitive vehicular live load and dynamic responses under a single truck.
or or
Design Tandem:
Pair of 25.0 KIP axles
spaced 4.0 FT apart 25.0 KIP 25.0 KIP
superimposed on +
0.64 Kip/ft
Design Lane Load 0.64 KLF
uniformly distributed load
0.9 x
> 50’-0”
lane
Resistance Factors
(Article 5.5.4.2)
Resistance factor φ shall be taken as:
TABLE 4.6.2.2.1-1 COMMON DECK SUPERSTRUCTURES COVERED IN ARTICLES 4.6.2.2.2 AND 4.6.2.2.3.
Applicable
Cross-Section
from Table Range of
Type of Beams 4.6.2.2.1-1 Distribution Factors Applicability
Concrete Deck, Filled a, e, k and also One Design Lane Loaded: 3.5 ≤ S ≤ 16.0
Grid, Partially Filled i, j 0.4 0.3 0.1
20 ≤ L ≤ 240
⎛ S ⎞ ⎛ S ⎞ ⎛ Kg ⎞
Grid, or Unfilled Grid if sufficiently 0.06 + ⎜ ⎟ ⎜ ⎟ ⎜ 3 ⎟
Deck Composite with connected to ⎝ 14 ⎠ ⎝ L ⎠ ⎝ 12.0 Lts ⎠ 4.5 ≤ ts ≤ 12.0
Reinforced Concrete Slab act as a unit Two or More Design Lanes Loaded: Nb ≥ 4
on Steel or Concrete 0.6 0.2 0.1
10,000 ≤ Kg ≤
⎛ S ⎞ ⎛ S ⎞ ⎛ Kg ⎞
Beams; Concrete T- 0.075 + ⎜ ⎟ ⎜ ⎟ ⎜ 3 ⎟ 7,000,000
Beams, T- and Double T- ⎝ 9.5 ⎠ ⎝ L ⎠ ⎝ 12.0 Lts ⎠
Sections use lesser of the values obtained from the Nb = 3
equation above with Nb = 3 or the lever rule
Applicable
Cross-Section
Type of from Table One Design Lane Two or More Design Lanes Range of
Superstructure 4.6.2.2.1-1 Loaded Loaded Applicability
Concrete Deck, a, e, k and also S S ⎛ S ⎞
2.0 3.5 ≤ S ≤ 16.0
Filled Grid, i, j if 0.36 + 0.2 + −⎜ ⎟
25.0 12 ⎝ 35 ⎠ 20 ≤ L ≤ 240
Partially Filled sufficiently
Grid, or Unfilled connected to 4.5 ≤ ts ≤ 12.0
Grid Deck act as a unit Nb ≥ 4
Composite with
Reinforced
Concrete Slab on
Steel or Concrete
Beams; Concrete Lever Rule Lever Rule Nb = 3
T-Beams, T-and
Double T-Sections
Calculate Kg:
n=8
eg
N.A. is 39.63 in. from
the top of the steel.
9.0
eg = + 3.5 + 39.63 − 1.0 = 46.63 in.
2
( ) ( )
Kg = n I + Ae2g = 8 62,658 + 75.25(46.63)2 = 1.81x 106 in.4
S
L
Article 4.6.2.2.2b:
One lane loaded: 0 .1
⎛ S⎞
0 .4
⎛S⎞
0 .3
⎛ Kg ⎞
0.06 + ⎜ ⎟ ⎜ ⎟ ⎜ ⎟
⎝ 14 ⎠ ⎝L⎠ ⎜ 12 .0Lt 3 ⎟
⎝ S⎠
Table 4.6.2.2.3a-1
One lane loaded:
S
0.36 +
25.0
12.0
0.36 + = 0.840 lanes
25.0
Applicable Cross-
Section from Table One Design Lane Two or More Design Range of
Type of Superstructure 4.6.2.2.1-1 Loaded Lanes Loaded Applicability
Concrete Deck, Filled a, e, k and Lever Rule g = e ginterior -1.0 < de < 5.5
Grid, Partially Filled also i, j d
Grid, or Unfilled Grid if sufficiently connected e = 0.6 + e
10
Deck Composite with to act as a unit
Reinforced Concrete Slab
on Steel or Concrete Lever Rule Nb = 3
Beams; Concrete T-
Number Multiple
Consider multiple of Loaded Presence
presence factors when: Lanes Factors "m"
- # of lanes of traffic 1 1.20
on the deck must be 2 1.00
considered in the 3 0.85
analysis (Art. 3.6.1.1.2) > 3 0.65
= R x 9 / 12
9.0
= 0.750
12.0
de
e = 0 .77 + (Table 4.6.2.2.2d-1)
9.1
2.0
e = 0 .77 + = 0 . 990
9.1
0 . 990 (0.807 ) = 0.799 lanes
NL X ext ∑ NL e
R= + Eq. (C4.6.2.2.2d-1)
Nb ∑ Nb x 2
Special Analysis:
NL X ext ∑ NL e
R= + Eq. (C4.6.2.2.2d-1)
Nb ∑ Nb x 2
R=
1
+
(18.0 )(15.0 ) = 0.625
15’-0”
(
4 2 18.0 2 + 6.0 2 )
m1 R = 1.2(0.625) = 0.750 lanes
Number Multiple
of Loaded Presence
Lanes Factors "m"
1 1.20
18’-0”
2 1.00
3 0.85
> 3 0.65
Number Multiple
of Loaded Presence
Lanes Factors "m"
1 1.20
2 1.00
3 0.85
> 3 0.65
Number Multiple
of Loaded Presence
Lanes Factors "m"
1 1.20
2 1.00
3 0.85
> 3 0.65
Special Analysis:
SUMMARY
Live-Load Distribution Factors
Strength Limit State
AASHTO LRFD - Positive Flexure:
Interior Girder Exterior Girder
Bending Moment 0.807 lanes 0.950 lanes
Shear 1.082 lanes 0.950 lanes
SUMMARY
Live-Load Distribution Factors
Fatigue Limit State - Design Example
Live-Load Deflection
(Article 2.5.2.6.2)
⎛N ⎞
DF = m3 ⎜⎜ L ⎟⎟
⎝ Nb ⎠
⎛3⎞
= 0.85⎜ ⎟ = 0.638 lanes
⎝4⎠
Number Multiple
of Loaded Presence
Lanes Factors "m"
1 1.20
2 1.00
3 0.85
> 3 0.65
Exceptions are:
Deck joints: IM = 75%
Fatigue limit state: IM = 15%