0% found this document useful (0 votes)
82 views

Engineering Estimate MEP

The document summarizes the area calculations, cooling load estimations, speaker estimations, and equipment estimations for the sound system of Mall KaliMalang. It includes calculations of the total area, cooling load needed, number and power load of speakers required, and power load of equipment for each floor of the 5-story mall. The priority load is the hypermarket and food court on the semi basement floor.

Uploaded by

Eka Agus Riyani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views

Engineering Estimate MEP

The document summarizes the area calculations, cooling load estimations, speaker estimations, and equipment estimations for the sound system of Mall KaliMalang. It includes calculations of the total area, cooling load needed, number and power load of speakers required, and power load of equipment for each floor of the 5-story mall. The priority load is the hypermarket and food court on the semi basement floor.

Uploaded by

Eka Agus Riyani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 24

Mall KaliMalang

Pekerjaan AC Chiller

1 Area calculation : Tinggi Lantai Floor Area Floor Area Total Area Total Area / Floor
Length Width Length Width
Jumlah lantai 5 : Zone 1 Zone 2 Zone 1 Zone 2

Lantai Basement 3.2 M2 Parking 112 M2 72 M2 0 M2 0 M2 - - - m2


Semi Basement 6 M2 Hypermart 72 M2 72 M2 Food Court 40 M2 72 M2 5,184 2,880 8,064 m2
1st Floor 6 M2 Ruko 223 M2 32 M2 0 M2 0 M2 7,136 - 7,136 m2
2nd Floor 5 M2 Ruko 223 M2 32 M2 0 M2 0 M2 7,136 - 7,136 m2
3rd floor 4 M2 Ruko 223 M2 32 M2 0 M2 0 M2 7,136 - 7,136 m2
4th Floor 4 M2 Ruko 183 M2 32 M2 0 M2 0 M2 5,856 - 5,856 m2

Total Area +/- 35,328 m2

2 Cooling Load Estimation : Asumsi 1 TR = 20 ~ 25 M2 Jumlah Cooling Load Jumlah Cooling Load Jumlah Cooling Load/Floor
Zone 1 Zone 2 Zone 1 Zone 2
Lantai Basement 20 M2 0 M2 0 TR 0 TR 0 TR
Semi Basement 20 M2 18 M2 259.2 TR 160 TR 419.2 TR
1st Floor 25 M2 0 M2 285.44 TR 0 TR 285.44 TR
2nd Floor 25 M2 0 M2 285.44 TR 0 TR 285.44 TR
3rd floor 25 M2 0 M2 285.44 TR 0 TR 285.44 TR
4th Floor 25 M2 0 M2 234.24 TR 0 TR 234.24 TR

Total 1,349.76 TR 160.00 TR 1,509.76 TR

3 Priority Load 1,509.76 TR

Hypermart 259.2 TR 61.83%


Food Court 160 TR
Remarks

Tenant
Parking
HyperMart & Food Court
Ruko/Kios & Void
Ruko/Kios & Void
Ruko/Kios, Cinema & Void
Ruko/Kios, Cinema & Void
Mall KaliMalang
Pekerjaan Tata Suara

Tinggi Lantai Floor Area Total Area / Floor


1 Area calculation : Remarks
Vol. Sat. Zone Length Sat. Width Sat. Vol. Sat.

Jumlah lantai 5 :
Lantai Basement 3.2 M2 Parking 112 M2 72 M2 8,064 m2 Parking
Semi Basement 6 M2 Hypermart 72 M2 72 M2 5,184 m2 HyperMart
Food Court 40 M2 72 M2 2,880 m2 Food Court
1st Floor 6 M2 Kios 223 M2 32 M2 7,136 m2 Kios & Void
2nd Floor 5 M2 Kios 223 M2 32 M2 7,136 m2 Kios & Void
3rd floor 4 M2 Kios 183 M2 32 M2 5,856 m2 Kios, Cinema & Void
4th Floor 4 M2 Kios 183 M2 32 M2 5,856 m2 Kios, Cinema & Void

Total Area +/- 42,112 m2

Asumsi 1 Speaker = 60 M2 Jumlah Speaker Power Load Total Load


2 Speakers Estimation : Remarks
Vol Sat. Vol. Sat. Load Sat. Total Load Sat.

Site Plant (Car Call) Conditional 15.00 Bh 15 Watt 225.00 Watt Horn Speaker
Lantai Basement 60 M2 135.00 Bh 10 Watt 1,350.00 Watt Coulumn Speaker
Semi Basement
- Hypermart 60 M2 87.00 Bh 3 Watt 261.00 Watt By Hypermart
- Food Court 60 M2 48.00 Bh 3 Watt 144.00 Watt Ceilling Speaker
1st Floor 60 M2 119.00 Bh 3 Watt 357.00 Watt Ceilling Speaker
2nd Floor 60 M2 119.00 Bh 3 Watt 357.00 Watt Ceilling Speaker
3rd floor 60 M2 98.00 Bh 3 Watt 294.00 Watt Ceilling Speaker
4th Floor 60 M2 98.00 Bh 3 Watt 294.00 Watt Ceilling Speaker
Tangga Kebakaran Conditional 22.00 Bh 3 Watt 66.00 Watt Wall Speaker

Total 741.00 Bh 3,348.00 Watt

Quantity Power Load Total Load


3 Equipment Estimation : Remarks
Vol. Sat. Load Sat. Load Sat.

Central SS
Peging Microphone 1 Buah
w/RU-2001
Emergency Microphone 1 Buah
Mixer Apmlifier 1 Buah
w/Modul
Power Amplifier 16 Buah 240 Watt 3,840 Watt
9 Buah 400 Watt 3,600 Watt
6 Buah 600 Watt 3,600 Watt

Proyek Apart. Puri Mas - Surabaya


Semi Basement 444 Watt
Lantai Ground 204 Watt
Lantai 2 s/d 14 (Typical) 234 Watt
Wall Speaker (Tangga) 30 Watt
Tower C Watt
Tower D Watt
Tower E Watt
Tower F Watt
Tower G Watt
TOTAL 912 Watt Amplifier 240 Watt

Kebutuhan Amplifier 3.80 Bh


Dibulatkan 4.00 Bh
Mall KaliMalang
Pekerjaan Fire Alarm

Tinggi Lantai Floor Area Total Area / Floor


1 Area calculation : Remarks
Vol. Sat. Zone Length Sat. Width Sat. Vol. Sat.

Jumlah lantai 5 : Tenant

Lantai Basement 3.2 M2 Parking 112 M2 72 M2 8,064 m2 Parking


Semi Basement 6 M2 Hypermart 72 M2 72 M2 5,184 m2 HyperMart
Food Court 40 M2 72 M2 2,880 m2 Food Court
1st Floor 6 M2 Kios 223 M2 32 M2 7,136 m2 Ruko/Kios & Void
2nd Floor 5 M2 Kios 223 M2 32 M2 7,136 m2 Ruko/Kios & Void
3rd floor 4 M2 Kios 183 M2 32 M2 5,856 m2 Ruko/Kios, Cinema & Void
4th Floor 4 M2 Kios 183 M2 32 M2 5,856 m2 Ruko/Kios, Cinema & Void

Total Area +/- 42,112 m2

Asumsi 1 Detector =
Floor Area Total Area Jumlah Detector
2 ROR Detectors Estimation : 30 M2 Remarks
Length Sat. Width Sat. Vol. Sat. Vol Sat. Vol. Sat.

Lantai Basement 112 M2 72 M2 8,064 M2 30 M2 269.00 Bh ROR Detector


Semi Basement
- Hypermart 72 M2 72 M2 5,184 M2 30 M2 173.00 Bh ROR Detector
- Food Court 40 M2 72 M2 2,880 M2 30 M2 96.00 Bh ROR Detector
1st Floor 223 M2 32 M2 7,136 M2 30 M2 238.00 Bh ROR Detector
2nd Floor 223 M2 32 M2 7,136 M2 30 M2 238.00 Bh ROR Detector
3rd floor 183 M2 32 M2 5,856 M2 30 M2 196.00 Bh ROR Detector
4th Floor 183 M2 32 M2 5,856 M2 30 M2 196.00 Bh ROR Detector

Total 1,406.00 Bh

Asumsi 1 Detector =
Floor Area Total Area Jumlah Detector
3 Smoke Detectors Estimation : 30 M2 Remarks
Length Sat. Width Sat. Vol. Sat. Vol Sat. Vol. Sat.

Lantai Basement 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor


Semi Basement
- Hypermart 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
- Food Court 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
1st Floor 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
2nd Floor 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
3rd floor 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
4th Floor 0 M2 0 M2 - M2 30 M2 - Bh Smoke Detektor
Jmlh T. Kebakaran Conditional 36.00 Bh Smoke Detektor

Total 36.00 Bh
STANDART DESIGN - ME

1 Pekerjaan Plumbing

2 Pekerjaan Fire Figthing

3 Pekerjaan Elektrikal

4 Pekerjaan Elektronik
A Pekerjaan Fire Alarm
Untuk 1 Titik Detektor dapat mengcover dengan luasan 30 M2
Untuk 1 Titik Smoke Detektor dapat mengcover dengan luasan 50 M2

B Pekerjaan Sound System


Untuk 1 Titik Ceilling Speaker dapat mengcover dengan luasan 60 M2
Untuk 1 Titik Wall Speaker dapat mengcover dengan luasan 60 M2
Untuk 1 Titik Horn Speaker dapat mengcover dengan luasan 60 M2
TABEL - ducting
UKURAN DUCTING MENURUT KEBUTUHAN PER STATIC PRESSURE / CFM

STATIC PRESSURE UKURAN DUCTING STATIC PRESSURE UKURAN DUCTING


NO NO
( CFM ) ( INCH ) ( CFM ) ( INCH )

1 100 6" x 5" 18 2.700 s/d 3.000 30" x 14"


2 150 6" x 6" 19 3.100 s/d 3.400 30" x 16"
3 200 8" x 6" 20 3.500 s/d 3.750 32" x 16"
4 250 8" x 8" 21 3.800 s/d 4.000 34" x 16"
5 300 s/d 350 10" x 8" 22 4.100 s/d 4.200 36" x 16"
6 400 s/d 450 10" x 10" 23 4.300 s/d 4.500 38" x 16"
7 500 s/d 600 12" x 10" 24 4.600 s/d 4.800 40" x 16"
8 650 s/d 750 14" x 10" 25 4.900 s/d 5.100 42" x 16"
9 800 s/d 1.000 14" x 12" 26 5.200 s/d 5.500 42" x 18"
10 1.100 s/d 1.250 16" x 12" 27 5.600 s/d 5.800 44" x 18"
11 1.300 s/d 1.500 16" x 14" 28 5.900 s/d 6.100 46" x 18"
12 1.600 s/d 1.700 18" x 14" 29 6.200 s/d 6.400 48" x 18"
13 1.800 s/d 1.900 20" x 14" 30 6.500 s/d 6.700 50" x 18"
14 1950 s/d 2.100 22" x 14" 31 6.800 s/d 7.000 52" x 18"
15 2.150 s/d 2.250 24" x 14" 32 7.100 s/d 7.300 54" x 18"
16 2.300 s/d 2.450 26" x 14" 33 7.400 s/d 7.700 56" x 18"
17 2.500 s/d 2.650 28" x 14" 34 7.800 s/d 8.000 58" x 18"

TABEL - bjls
KEBUTUHAN TEBAL SENG BJLS MENURUT UKURAN VOLUME

UKURAN DUCTING TEBAL SENG BJLS Berat (W)


NO
Inch mm mm GA Kg/ M2

1 0" s/d 12" 0 s/d 300 - BJLS 50 26 4,17


2 13" s/d 30" 325 s/d 750 - BJLS 60 24 5,01
3 31" s/d 54" 775 s/d 1.350 - BJLS 70 / 80 23 5,80 / 6,58
3 55" s/d 84" 1.375 s/d 2.100 - BJLS 100 20 8,15
4 85" s/d ……… 2.125 s/d ……. - BJLS 120 18 9,81
TABEL - KONVERSI

NO DALAM SATUAN KONV. DALAM SATUAN KETERANGAN

1 1 TR = 3,517 kW Cooling Capacity


2 1 TR = 1,25 kW Daya Listrik
3 1 TR = 3,024 K. Cal/h
4 1 TR = 12.000 Btu/h
5 1 TR = 2,4 GPM System Chiller
6 1 TR = 3,4 GPM Cooling Tower
7 1 TR = 400 CFM
8 1 TR = 20 ~ 25 M2 1 TR mengcover 20~25 m2
9 1 PK = 300 CFM
10 1 PK = 9.000 Btu/h
11 1 PK = 0,746 kW
12 1 PK = 746 Watts
13 1 Watt = 3.412 Btu/h

14 1 CFM = 35,31 M3/Menit


15 1 CFM = 2,846 Watts
16 1 CFM = 30 Btu/h

17 1 Inch WG = 249 Pascal

18 1 kW = : 0,8 kVA
19 1 K.Cal/H = x 0,001163 kW
20 500 ~ 700 Btuh/m2 = 1 Unit AC

21 1 GPM = 3,785 Liter


22 1 Liter = 0,264 Galon
23 1 M3 = 1.000 Liter

24 1 Bar = 14,5 ~ 14,7 Psi (Lb/M2)


25 1 Bar = 1 Kg/Cm2
26 1 Bar = 10 Meter

27 1 Liter = 1 Kg
28 1 Liter/Second = 3,6 CMH
TABEL ESTIMASI
AIR CHANGES PER HOUR

NO NAMA BANGUNAN AIR CHANGES PER HOURE

1 Assembly Halls 4 - 6
2 Bakeries 15 - 30
3 Banks 2 - 4
3 Bathrooms 6 - 8
4 Bars 6 - 8
5 Boiler Houses 15 - 30
6 Cafes 8 - 12
7 Canteens 8 - 12
8 Churches 1 - 10
9 Cinemas 6 - 10
10 Classrooms 2 - 4
11 Cleaners 15 - 30
12 Dance Halls 8 - 12
13 Domestic Kictens 10 - 15
14 Dyers 15 - 30
15 Engine Rooms 15 - 30
16 Founderies 30 - 60
17 Furnance Rooms 30 - 60
18 Garages 6 - 10
19 Hospital Wards 6 - 8
20 Hospitel Treatment Rooms 6 - 8
21 Kitcen for Restourants 13 - 30
22 Laboratories 4 - 6
23 Loundries 10 - 15
24 Libraries 2 - 4
25 Offices 4 - 6
26 Paint Shops 30 - 60
27 Residances 1 - 2
28 Restaurants 10 - 15
29 Storage Areas 1 - 2
30 Swimming Baths 15 - 30
31 Theaters 6 - 10
32 Workshops 6 - 10
33 Trafo Rooms 40 - 60
34 STP Rooms 50 - 80
TABEL ESTIMASI TABEL ESTIMASI
KEKUATAN CAHAYA SUATU BANGUNAN KEKUATAN CAHAYA SUATU BANGUNAN

NO NAMA BANGUNAN DATA LUXTOLERANSI NO NAMA BANGUNAN DATA LUXTOLERANSI

PARTIAL I PARTIAL II
1 Pabrik Pesawat terbang 700 1 Industri Textil 300 1000
2 Assembling 1000 2 Daerah Tangga / Lorong 200
3 Hanggar Service 1000 3 Gudang Industri 50 100
4 Pabrik Roti 300 500 4 Pabrik Lem, Perhiasan 1000 5000
5 Pabrik Kimia 300 5 Art Galery 300
6 Pabrik Keramik 300 1000 6 Auditorium 100 1000
7 Pabrik Pakaian 300 500 7 Pangkas rambut & Salon 500 1000
8 Pabrik Alat alat Listrik 1000 8 Gereja 150 1000
9 Daerah luar area 50 9 Rumah Sakit
10 Bangunan sekeliling 50 Umum 300 500
11 Daerah Gudang 10 200 Laboratorium 500 1000
12 Service Mobil 200 1000 Ruang Pasien 200 300
13 Parkir Garage 100 500 Ruang Bedah 2000
14 Binatu 300 700 Ruang tunggu & toilet 200
15 Pabrik Kulit 300 1000 10 Hotel & Motel 100 300
16 Ruang Locker 200 11 Perpustakaan & Ruang baca 700
17 Toko Peralatan Mesin 500 1000 12 Kantor
18 Pengangkutan Material 100 500 Umum 300 500
19 Toko Cat 500 1000 Khusus 1000 2000
20 Industri Textil 300 1000 13 Kantor Pos 1000
21 Daerah Tangga / Lorong 200 14 Restoran 200 500
22 Gudang Industri 50 100 15 Bioskop 50 200
23 Pabrik Lem, Perhiasan 1000 5000 16 Sekolah 300 500
17 Toko 300 500
RUMUS - RUMUS LAMPU
RUMUS LAMPU
CU = (Coeffisien of Utilization) 50-65% 65
LLF = (Light Loss Factor) 0.7-0.8% 0.8

CU Tergantung Dari :
P = Persentase pantulan
Pc = Persentase pantulan pada Cealing
Pw = Persentase pantulan pada Wall
Pf = Persentase pantulan pada floor

LAMPU RMI 2X36 watt


Panjang Lebar
Luas Ruang 2.25 4.5 Mtr 10 Mtr2
Dengan Ketinggia Langit-langit 4.5 Mtr
Lampu memakai Type TL 1 X 18
Ukuran watt 18 Watt
Penerangan Lumen 200 Lux
Koofisien 1.2
Di asumsikan CU = 50 % : LLF = 0.7 % Sehingga Di Butuhkan Lampu =………..?
Lumen Untuk TL 75
Watt TL yang di Minta 18
Q Lampu = 1350 Lumen

Rumus
E x A 200 Lux X 10 Mtr
= =
Q lampu x CU x LLF 1350 x 50 % CU x 0.7 LLF

= 2,025
702
= 2.88 Bh Lampu
Total Lampu 3.00 Bh Lampu
1.00 192.0
RUMUS LAMPU
CU = (Coeffisien of Utilization) 50-65% 65
LLF = (Light Loss Factor) 0.7-0.8% 0.8

CU Tergantung Dari :
P = Persentase pantulan
Pc = Persentase pantulan pada Cealing
Pw = Persentase pantulan pada Wall
Pf = Persentase pantulan pada floor

LAMPU RMI 2X36 watt


Panjang Lebar
Luas Ruang 10 20 Mtr 200 WATT AMP
Jenis lampu RMI 2 X 36 72 Watt 8.00 576.00 2.62
RMI 2 X 18 36 Watt 8.00 288.00 1.31
RMI 1 X 36 36 Watt 3.00 108.00 0.49
RMI 1 X 18 18 Watt 8.00 144.00 0.65
BALK 2 X 36 72 Watt 8.00 576.00 2.62
BALK 2 X 18 36 Watt 8.00 288.00 1.31
BALK 1 X 36 36 Watt 8.00 288.00 1.31
BALK 1 X 18 18 Watt 8.00 144.00 0.65
BARET 1 X 40 40 Watt 8.00 320.00 1.45
BARET 1 X 22 22 Watt 8.00 176.00 0.80
DL 1 X 18 18 Watt 8.00 144.00 0.65
DL 1 X 13 13 Watt 8.00 104.00 0.47
HDK 1 X 400 400 Watt 8.00 3,200.00 14.55
HPIT 1 X 400 400 Watt 8.00 3,200.00 14.55

Lampu memakai Type TL 1 x 36


Ukuran watt 72 Watt
Penerangan Lumen 100 Lux
Koofisien 1.2
Di asumsikan CU = 50 % : LLF = 0.7 % Sehingga Di Butuhkan Lampu =………..?
Lumen Untuk TL 75
Watt TL yang di Minta 72
Q Lampu = 5,400 Lumen

Rumus
E x A 100 Lux X 200 Mtr
= =
Q lampu x CU x LLF 5,400 x 50 % CU x 0.7 LLF

= 20,000
2,808
= 7.12 Bh Lampu
Total Lampu 8.00 Bh Lampu

LAMPU HPIT 400 watt


Panjang Lebar
Luas Ruang 20 25 Mtr 500 Mtr2
Dengan Ketinggian Langit-langit 4 Mtr
Lampu memakai Type TL 1 x 36
Ukuran watt 250 Watt
Penerangan Lumen 350 Lux
Koofisien 1.2
Di asumsikan CU = 50 % : LLF = 0.7 % Sehingga Di Butuhkan Lampu =………..?
Lumen Untuk TL 75
Watt TL yang di Minta 250
Q Lampu = 18,750 Lumen

Rumus
E x A 350 Lux X 500 Mtr
= =
Q lampu x CU x LLF 18,750 x 50 % CU x 0.7 LLF

175,000
=
9,750
= 17.95 Bh Lampu
Total Lampu 18.00 Bh Lampu

RUMUS STOP KONTAK

Untuk stop Kontak 10-20 mtr/segi Di perlukan satu stop Kontak dengan kapasitas
500 watt sehingga jumlah daya stop kontak
1 Bh Stop Kontak Meng Cover 20 Mtr/segi
Panjang Lebar
Luas Ruang 112 72 Mtr 8,064 Mtr
Dengan Ketinggia Langit-langit 4 Mtr

Luas Bangunan 8,064 M2


= X 200 Watt
Luas satu stop kontak 20
Watt Stop
80,640 Kontak

= 403 Bh Stop Kontak


RUMUS - RUMUS AC & FAN
RUMUS AC

Untuk AC mtr/segi Di perlukan dengan kapasitas: 9,000 Btuh


Sehingga jumlah daya perBTUH 746 Watt
Factor Daya (Cos Ø) 0.70
* Penghuni Ruangan Sedikit 650
** Penghuni Ruangan Sedang 750
*** Penghuni Ruangan Banyak 800

Luas Bangunan x Penghuni 6,336 M2 X 650 BTUH


=
Kapasitas BTUh 9,000
= 457.60 PK
Total Kap. = 460.00 PK

Total Daya = 490,229 Watt

Total Arus = 745.03 Amp

Total Arus (Dibulatkan) = 750.00 Amp

RUMUS FAN

Untuk Menentukan Kap. Exhaust Fan dalam suatu ruangan


Dimana:
H = Tinggi Ruangan
L = Panjang Ruangan
W = Lebar Ruangan
AC = Air Change /Houre
Note: Untuk AC ditentukan berdasarkan kebutuhan suatu ruangan.
( Lihat Tabel - AC)

CFM = H x L x W x AC (Air Change) x 35,31


60
= 1,092.00 M3 x 6.00 Kali x 35.31
60

= 3,855.85 CFM

3,900.00 CFM

6 650 Cfm
2,650
500.00
5.30

S.P = Panjang Ducting (BJLS/PVC) yang akan dihisap/dibuang


= M
= Inch WG
RUMUS - RUMUS PANEL
RUMUS PANEL
Daya Hantar CU = (y) ( 50 x 106 ) (ohm.m)-1
Factor Kerja = (Cos Ø) 0.8%-0.9% 0.8

Dimana:
P = Load Beban yang dibutuhkan (Watt)
I = Arus dalam penghantar (Ampere)
E1 = Tegangan Antar Fasa (Volt)
Cos Ø = Faktor kerja
√3 = 1.732

Untuk tegangan:
1 Phase = 220 Volt
3 Phase = 380 Volt

MENETUKAN BESARNYA ARUS (3 Phase)

P = 2,700 Watt
E1 = 380 Volt
Cos Ø = 0.8 %
√3 = 1.732

Rumus:
P 50,000 Watt
I= =
√3 x E1 x cos Ø 1.732 x 380 Volt x 0.8

= 50,000
527

= 94.96 Ampere
Total Arus 95.00 Ampere
MENETUKAN BESARNYA ARUS (1 Phase)

Σ Lampu = 8 Bh
P Lampu = 25 Watt

P = 200 Watt
E1 = 220 Volt
Cos Ø = 0.8 %

Rumus:
P 1,300 Watt
I= =
E1 x cos Ø 220 Volt x 0.8

= 1,300
176

= 7.39 Ampere
Total Arus 8.00 Ampere

MENETUKAN BESARNYA PENAMPANG

Σ Lampu = 10 Bh
P Lampu = 36 Watt

P = 360 Watt
E1 = 220 Volt
Cos Ø = 0.8 %

Rumus:
P 360
I= =
E1 x cos Ø 220 x 0.8

= 360
176

= 2.05 mm2
Total Luas Penampang 3.00 mm2
RUMUS - RUMUS AC & FAN
I Lantai Semi Basement

A KALKULASI UNIT AC

1 Lobby Lift (Lantai Ground Floor)

Untuk AC mtr/segi Di perlukan dengan kapasitas: 9,000 Btuh


Sehingga jumlah daya perBTUH 746 Watt
Factor Daya (Cos Ø) 0.70
* Penghuni Ruangan Sedikit 650
** Penghuni Ruangan Sedang 750
*** Penghuni Ruangan Banyak 800

Luas Bangunan x Penghuni 39.50 M2 X 650 BTUH


=
Kapasitas BTUh 9,000
= 2.85 PK
Total Kap. = 3.00 PK

Total Unit AC 2 = 1.50 PK

Total Daya = 3,197 Watt

Total Arus = 4.86 Amp

Total Arus (Dibulatkan) = 10.00 Amp

2 Ruang Kontrol (Ground Floor)

Untuk AC mtr/segi Di perlukan dengan kapasitas: 9,000 Btuh


Sehingga jumlah daya perBTUH 746 Watt
Factor Daya (Cos Ø) 0.70
* Penghuni Ruangan Sedikit 650
** Penghuni Ruangan Sedang 750
*** Penghuni Ruangan Banyak 800

Luas Bangunan x Penghuni 15.00 M2 X 650 BTUH


=
Kapasitas BTUh 9,000
= 1.08 PK
Total Kap. = 1.00 PK

Total Unit AC 1 = 1.00 PK

Total Daya = 1,066 Watt

Total Arus = 1.62 Amp

Total Arus (Dibulatkan) = 10.00 Amp

3 Ruang Mesin Lift (Lantai Atap)

Untuk AC mtr/segi Di perlukan dengan kapasitas: 9,000 Btuh


Sehingga jumlah daya perBTUH 746 Watt
Factor Daya (Cos Ø) 0.70
* Penghuni Ruangan Sedikit 650
** Penghuni Ruangan Sedang 750
*** Penghuni Ruangan Banyak 800

Luas Bangunan x Penghuni 27.00 M2 X 650 BTUH


=
Kapasitas BTUh 9,000
= 1.95 PK
Total Kap. = 2.00 PK
Total Unit AC 2 = 1.00 PK

Total Daya = 2,131 Watt

Total Arus = 3.24 Amp

Total Arus (Dibulatkan) = 10.00 Amp

B KALKULASI UNIT FAN

1 Exhaust Fan/Parkir Area (Lantai Semi Basement)

Untuk Menentukan Kap. Intake Fan dalam suatu ruangan


Dimana:
H = Tinggi Ruangan
L = Panjang Ruangan
W = Lebar Ruangan
AC = Air Change /Houre
Note: Untuk AC ditentukan berdasarkan kebutuhan suatu ruangan.
( Lihat Tabel - AC)

CFM = H x L x W x AC (Air Change) x 35,31


60
= 3,287.15 M3 x 60.00 Kali x 35.31
60

= 116,069.27 CFM

116,100.00 CFM

Unit Fan 3 38,700 Cfm


Total CFM 38,700 Cfm Jmlh Grille 2,750 14.073

S.P = Panjang Ducting (BJLS/PVC) yang akan dihisap/dibuang


= M
= Inch WG

2 Intake Fan/Parkir Area (Lantai Semi Basement)

Untuk Menentukan Kap. Exhaust Fan dalam suatu ruangan


Dimana:
H = Tinggi Ruangan
L = Panjang Ruangan
W = Lebar Ruangan
AC = Air Change /Houre
Note: Untuk AC ditentukan berdasarkan kebutuhan suatu ruangan.
( Lihat Tabel - AC)

CFM = H x L x W x AC (Air Change) x 35,31


60
= 3,287.15 M3 x 60.00 Kali x 35.31
60

= 116,069.27 CFM

116,100.00 CFM

Unit Fan 3 38,700 Cfm


Toleransi 2,000 Cfm
Total CFM 3 40,700.00 Cfm Jmlh Grille 2,750 14.8

S.P = Panjang Ducting (BJLS/PVC) yang akan dihisap/dibuang


= M
= Inch WG
3 Exhaust Fan/Ruang Trafo (Lantai Ground Floor)

Untuk Menentukan Kap. Intake Fan dalam suatu ruangan


Dimana:
H = Tinggi Ruangan
L = Panjang Ruangan
W = Lebar Ruangan
AC = Air Change /Houre
Note: Untuk AC ditentukan berdasarkan kebutuhan suatu ruangan.
( Lihat Tabel - AC)

CFM = H x L x W x AC (Air Change) x 35,31


60
= 40.00 M3 x 60.00 Kali x 35.31
60

= 1,412.40 CFM

1,500.00 CFM

Unit Fan 1 1,500 Cfm


Total CFM 1,500 Cfm

4 Intake Fan/Ruang Trafo (Lantai Ground Floor)

Untuk Menentukan Kap. Exhaust Fan dalam suatu ruangan


Dimana:
H = Tinggi Ruangan
L = Panjang Ruangan
W = Lebar Ruangan
AC = Air Change /Houre
Note: Untuk AC ditentukan berdasarkan kebutuhan suatu ruangan.
( Lihat Tabel - AC)

CFM = H x L x W x AC (Air Change) x 35,31


60
= 40.00 M3 x 60.00 Kali x 35.31
60

= 1,412.40 CFM

1,500.00 CFM

Unit Fan 1 1,500 Cfm


Toleransi 2,000 Cfm
Total CFM 1 3,500.00 Cfm

S.P = Panjang Ducting (BJLS/PVC) yang akan dihisap/dibuang


= M
= Inch WG
0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.0 1.5 2.2 3 3.7 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 230
1\12 1\8 1\6 1\6 1\4 1\2 3\4 1 1.5 2 3 4 5 5.5 7 3\4 10 15 20 25 30 40 50 60 75 100 125 150 180 220 270 340
0.5 0.7 0.8 1.2 1.5 2.1 2.7 3.5 4.5 6.1 8.7 11.5 14.5 15 20 26.5 35 50 62 75 100 124 148 182 245 295 350 420 510
C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 11 TP C 16 TP C 16 TP C 11 TP C 35 TP C 50 TP C 50 TP C 80 TP C 100 TP C 100 TP C 150 TP C 150 TP C 220 TP C 300 TP C 300 TP C 401 TP C 600 TP C 600 TP

12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 20 TP 20 TP 20 TP 20 TP 60 TP 60 TP 60 TP 60 TP 120 TP 120 TP 120 TP 220 TP 403 TP 403 TP 403 TP 600 TP 600 TP


0.6 0.6 0.9 1.2 1.7 2.1 3.3 3.3 4.4 6.5 9 11 15 15 21 28 40 54 67 80 105 130 130 200 260 260 350 500 500
*2 *2 *4 *4 *6 *6 8 8 10 16 20 32 32 32 40 63 80 100 125 160 200 250 250 400 500 800 800 800 800
30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 100 S 100 S 100 S 100 S 100 S 100 S 225 S 225 S 225 S 400 S 400 S 400 S 600 S 800 S 1000 S
3 3 3 3 3 3 10 10 10 15 20 30 30 30 50 50 60 100 100 100 150 200 225 300 400 400 600 700 1000
1 1 1 1 1 1 1 1 1 1 1.5 1.5 1.5 1.5 4 6 10 10 16 25 35 50 70 95 120 185 240 300 400
`

0.3 0.4 0.5 0.7 0.85 1.2 1.6 2.0 2.7 3.6 5.1 6.8 8.5 8.8 11.8 16 22 35 37 43 57 72 86 105 140 168 205 245 290 360 475
C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 11TP C 11TP C 11TP C 16 TP C 11TP C 35 TP C 50 TP C 50 TP C 60 TP C 80TP C 100 TP C 100 TP C 150 TP C 220 TP C 220 TP C 300 TP C 300 TP C 401 TP C 600 TP

12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 20 TP 20 TP 20 TP 60 TP 60 TP 60 TP 60 TP 120 TP 120 TP 120 TP 220 HTP 220 HTP 403 HTP 403 HTP 403 HTP 600 HTP

0.25 0.4 0.6 0.6 0.8 1.2 1.7 2.1 3.3 3.3 4.4 6.5 9 9 11 15 21 28 40 40 54 67 80 105 130 160 200 260 260 350 500
*2 *2 *2 *2 *4 *4 *6 *6 8 10 10 16 20 20 32 40 40 63 80 80 100 160 160 200 250 315 400 500 800 800 800
30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 50 SB 50 SB 100 S 100 S 100 S 100 S 100 S 100 S 225 S 225 S 400 S 400 S 400 S 400 S 600 S 600 S
3 3 3 3 3 3 3 5 10 10 10 20 20 20 30 30 50 50 75 100 100 100 100 150 200 300 300 400 400 600 800
1 1 1 1 1 1 1 1 1 1 1 1 1.5 1.5 1.5 2.5 4 6 10 10 16 25 25 35 50 70 95 120 185 240 300

0.3 0.4 0.5 0.65 0.8 1.1 1.5 1.9 2.6 3.5 5..0 6.3 7.5 8.1 11 15 21 28 35 40 54 67 79 98 130 160 190 230 270 328 435
C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 10 TP C 11 TP C 11 TP C 11 TP C 16 TP C 11 TP C 35 TP C 50 TP C 50 TP C 60 TP C 80 TP C 100 TP C 100 TP C 150 TP C 220 TP C 220 TP C 300 TP C 300 TP C 401 TP C 600 TP

12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 12 TP 20 TP 20 TP 20 TP 60 TP 60 TP 60 TP 60 TP 120 TP 120 TP 120 TP 220 HTP 220 HTP 403 HTP 403 HTP 403 HTP 600 HTP

0.25 0.4 0.4 0.6 0.9 1.2 1.7 1.7 3.3 3.3 4.4 6.5 6.5 9 11 15 21 28 33 40 54 67 80 105 130 160 200 200 260 350 500
*2 *2 *2 *2 *4 *4 *6 *6 8 10 10 16 16 20 32 40 40 63 80 80 100 160 160 200 250 315 400 500 800 800 800
30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 30 SB 50 SB 50 SB 100 S 100 S 100 S 100 S 100 S 100 S 225 S 225 S 400 S 400 S 400 S 400 S 600 S 600 S
3 3 3 3 3 3 3 5 10 10 10 20 20 20 30 30 50 50 75 100 100 100 100 150 200 300 300 400 400 600 800
1 1 1 1 1 1 1 1 1 1 1 1 1.5 1.5 1.5 2.5 4 6 10 10 16 25 25 35 50 70 55 120 150 185 300
Selection of Magnetic Motor Starter and No - Fuse Breaker
KW
Motor Rating
HP
Motor full Load Current A
Type destignation of magnetic starter MSO
220 V associated Thermal overload relay TH
3~ heater destignation A
50 Hz fuse (VDE0660 gT Time delay) A
NO - fuse Breaker Nf
Operating current rating A
Wire size mm 2

Motor full Load Current A


Type destignation of magnetic starter MSO
380 V associated Thermal overload relay TH
3~ heater destignation A
50 Hz fuse (VDE0660 gT Time delay) A
NO - fuse Breaker Nf
Operating current rating A
Wire size mm 2
M M

Motor full Load Current A


Type destignation of magnetic starter MSO
415 V associated Thermal overload relay TH
3~ heater destignation A
50 Hz fuse (VDE0660 gT Time delay) A
NO - fuse Breaker Nf
Operating current rating A
Wire size mm 2
Ketentuan - ketentuan di bawah ini adalah Harga rata - rata 1 PK = 736 Watt
untuk indikator kilo Ampere k.A dengan Ster Driehoek f = 50 Hz 1 kW = 1.36 HP
Sakelar ŋ = 1500 putaran / menit
I ■ arus yang di cari Tegangan 220 V 220
E1 ■ arus yang di cari 220 / 380 Daya 3.5 kW 0.37
√3 ■ 1,73 Daya 2 PK / HP 0.5
ARUS LISTRIK KW 1000 Cos ф ■ 0,8 Arus Listrik Nominal 8 Amp 1.7
I =
E1 √ 3 Cos ф Kabel Tanah (NYFGBY) mm2 2.5
contoh soal Kabel Isolasi PVC mm2 15
kVA . 1000 Jaminan dengan Amp 4
= E1 √ 3 Daya 112.048 Watt 13
Dia. Luar NYFGBY 3 intl. Ca mm2
112.048 x 0,8 x 1.000 kVA Dia. Luar NYFGBY 4 intl. Ca mm2 18.7
=
380 x 1,73 Dia Pipa dari 3 intl. Ca mm2
ARUS WATT Iw = I Cos ф Dia Pipa dari 4 intl. Ca mm2
ARUS BAYANGAN Iw = I Sin ф 89.638.400 VA
= 657.4 (658) 3 Phase

ARUS MOTOR kW 1000 = 136,2285714 Amp = 138,228 Amp


I = E1 √ 3 Cos ф ŋ 160 Amp setelah dikali faktor pengaman 20 %

Tegangan yang hilang per 1000 mt Penampang mm2 0.5


dan 1 Amp pada jaringan arus bolak balik dengan Cos ф = D.B mencari kVA Tegangan yang hilang Volt
Daya Watt x 0,8 Cos  = kVA 1 intl Amp
kekuatan arus listrik maks sampai 1000 V , ditanam ditanah 2 intl Amp
untuk beban yang tidak tetap / beban variable = 1,4 x ( Amp ) 3 dan 4 intl Amp
dengan jaminan = 0,8 x ( Amp ) Max. Amp 8
untuk kabel udara terbuka = 0,8 x ( Amp ) Jaminan depan Amp 6
kekuatan arus listrik maksimum dalam pipa dengan kawat isolasi PVC
suhu keliuling max 30 ºC
K = Tegangan tinggi / rendah
π2 = Telepon
I = berlaku semua ukuran
k = berlaku semua keperluan dengan armaturen besar / kecil
s = stabilizer
220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220
0.74 1.1 1.5 2.2 3 3.7 5.5 7.4 9.4 11 15 18.5 22 25 29 37 40 44 52 59 66 74
1 1.5 2 3 4 5 7.5 10 12.5 15 20 25 30 34 40 50 55 60 70 80 90 100
3.1 4.4 6.8 9.8 11.6 13.9 20.4 27.4 32.5 39.5 54 68 75 85 100 129 140 153 173 200 220 245
2.5 2.5 2.5 2.5 2.5 4 4 6 15 15 23 23 36 38 50 70 70 95 120 150 130 185
1.5 1.5 1.5 2.5 2.5 4 6 10 16 16 25 28 35 35 50 70 70 95 120 150 150 185
6 6 10 10 10 20 25 35 50 30 80 80 100 100 125 180 180 200 225 250 250 300
13 13 10 13 13 14.3 14.5 15.6 17.3 19.6 25.4 25.4 30.5 30.5 31.2 35.4 25.4 39.7 42.4 47.4 47.4 53
18.7 18.7 18.7 18.7 18.7 18.4 18.4 19.3 21.8 26.4 30.5 30.5 33.7 33.7 33.9 33.5 33.5 43.2 47.3 50.9 50.9 57.2

0.75 1 1.5 2.5 4 6 10 16 25 35 60 70 95 120 150 185 240 300


16.4 5.5 6.2 4.12 2.47 1.54 0.55 0.7 0.4 1.35 0.28 0.2 164 0.13 0.1 0.38
31 41 55 70 85 130 170 210 250 320 385 450 510 575 670 760
25 33 42 53 70 25 125 150 150 230 275 315 300 405 470 830
22 28 37 47 55 55 110 135 150 200 240 200 315 350 420 475
9 11 14 20 25 33 43 51 83 103 132 150 187 235 270 315 373 430
6 6 10 15 20 25 35 60 80 100 125 150 200 225 250 300 350 400
TABEL & RUMUS

Tebal Irisan - irisan penghantar dari tembaga dalam perdagangan UKURAN NOMINAL PIPA
Irisan penghantar tembaga Max. Arus Harga keamanan terhadap Air Inchi mm
mm 2 Amp Amp ½ 15
0.5 8 6 ¾ 20
0.75 9 6 1. 25
1 11 6 1¼ 30
1.5 14 10 1½ 40
2.5 20 15 2 50
4 25 20 2½ 65
6 31 25 3 80
10 43 35 4 100
16 75 60 5 125
25 100 80 6 150
35 125 100 8 200
50 160 125 10 250
70 200 160 12 300
95 240 200 14 350
120 280 225 16 400
150 325 250
185 380 300
240 450 350
300 525 400
400 640 500
500 760 600
625 880 700
800 1050 850
1000 1250 1000
TABEL PERBANDINGAN MOISTURE G. 1

KLASIFIKASI KADAR AIR KELEMBABAN TEMPERATUR TEMPERATUR


ELEKTRODA YANG DI IJINKAN Relatif Penyimpanan Pemanasan
Dalam Oven
AWS % % ºc ºc - jam
E 6010 3 s/d 5 20 s/d 60
E 6011 2 s/d 4 20 s/d 60 Ikuti petunjuk pabrik pembuat
E 6012 , E 6013 , E 6020 1 60 nax.
E 6027 , E 7014 , E 7024 0.5 60 nax. 37 s/d 48 135 ± 5
E 7015 , E 7016 0.4 60 nax. 287 ± 10
E 7018 , E 7028 0.4 60 nax. 54 s/d 165 343 ± 10