DESCRIPTION
Disclaimer
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Ericsson shall
have no liability for any error or damage of any kind resulting from the use
of this document.
Trademark List
Contents
1 Product Overview 1
1.1 Purpose 1
1.2 Variants 1
2 Function Description 5
2.1 PDU 01 01 5
2.2 PDU 02 01 and PDU 02 02 5
2.3 Power Distribution Control 6
3 Technical Data 9
3.1 PDU 01 01 9
3.2 PDU 02 01 and PDU 02 02 9
1 Product Overview
Information about the placement in the Radio Base Station (RBS) cabinet can
be found in RBS Description.
1.1 Purpose
The PDU is the internal power distribution unit in the RBS. The main function
of the PDU is to distribute -48 V DC power to DC-powered units in the RBS.
The PDU works as an internal distribution unit within a cabinet. It receives one
feeding of input voltage connector and distributes the input voltage to separate
fused outputs through output connectors.
1.2 Variants
Table 1 lists the different PDU variants.
1.2.1 PDU 01 01
This PDU is an internal power distribution unit situated in a power
subrack.Figure 1 shows the front of the PDU 01 01.
PDU 01 01
Fault Sys Volt
Test port
EC Bus
Oper
CB 1 CB 2 CB 3 CB 4 CB 5 CB 6 CB 7
H-UP <19A <16A <19A <16A <19A <16A
PCR PCR PCR PCR PCR PCR PCR
Ge0085C
1.2.2 PDU 02 01
This PDU is an internal power distribution unit situated in a 19 inch RBS slot.
Figure 2 and Figure 3 show the PDU 02 01.
11
PCR EC Bu
s
10
PCR
8
PCR 11
8
PCR 10
7 9
PCR
6 8
PCR
5 7
PCR
4
PCR 6
P CR 3 5
2
PCR 4
1 3
PCR
2
02 01 11
PCR
PDU
Ge0787A
Figure 2 PDU 02 01
PDU 02 01 1 2 3 4 5 6 7 8 9 10 11 EC Bus
1 11 EC Bus
PDU 02 01
Ge0714A
1.2.3 PDU 02 02
This PDU is an internal power distribution unit situated in a 19 inch RBS slot. It
is similar to the PDU 02 01 except that it uses a different cable connector.Figure
4 shows the PDU 02 02.
11
PCR EC Bu
s
10
PCR
8
PCR 11
8
PCR 10
7 9
PCR
6 8
PCR
5 7
PCR
4
PCR 6
3 5
PCR
2
PCR 4
1 3
PCR
2
02 02 11
PCR
PDU
Ge1038A
Figure 4 PDU 02 02
2 Function Description
2.1 PDU 01 01
This PDU has the following functions:
EC bus Supervision
Control 3×16A without hold-up
DC Input
3×19A without hold-up
7×E Fuse
Ge0122A
Figure 6 shows the block diagram of the PDU 02 01 and the PDU 02 02.
Supervision
EC bus Control
11xE Fuse
Ge0717A
Note: For outdoor RBS without heater all cold-start switches must be in upper
position.
When the R switch is set to the upper position (remote controllable), the
E-FUSE can be configured in the software.
Note: If the switch is set to the lower position, the function cannot be remotely
controlled.
3 Technical Data
This section describes the technical data for the PDU variants.
3.1 PDU 01 01
This section describes the technical data for the PDU 01 01.
Table 4 lists the technical data for the PDU 02 01 and the PDU 02 02.
Description Value
Maximum continuous current 115 A
Output capacity continuous load 11 x 14 A
Holdup function > 10 ms on DC output 1 and 2
Power consumption 10 W (excluding distribution loss)
Power dissipation 60 W
Temperature Range
Normal -40C to +60C
Limited performance (manual control) -40C to -10C
Dimensions
Height 21.4 mm
Width 434 mm
Depth 200 mm
Weight < 4 kg
4.1 PDU 01 01
This section describes the interfaces for the PDU 01 01.
Table 5 lists details for the external interfaces on the PDU 01 01.
4.2 PDU 02 01
This section describes the interfaces for the PDU 02 01.
Table 6 lists details for the external interfaces on the PDU 02 01.
4.3 PDU 02 02
This section describes the interfaces for the PDU 02 02.