PDU Description

DESCRIPTION

7/1551-LZA 701 6001 Uen D


Copyright

© Ericsson AB 2009–2010. All rights reserved. No part of this document may be


reproduced in any form without the written permission of the copyright owner.

Disclaimer

The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Ericsson shall
have no liability for any error or damage of any kind resulting from the use
of this document.

Trademark List

All trademarks mentioned herein are the property


of their respective owners. These are shown in the
document Trademark Information.

7/1551-LZA 701 6001 Uen D | 2010-05-21


Contents

Contents

1 Product Overview 1
1.1 Purpose 1
1.2 Variants 1

2 Function Description 5
2.1 PDU 01 01 5
2.2 PDU 02 01 and PDU 02 02 5
2.3 Power Distribution Control 6

3 Technical Data 9
3.1 PDU 01 01 9
3.2 PDU 02 01 and PDU 02 02 9

4 Signal and Power Interfaces 11


4.1 PDU 01 01 11
4.2 PDU 02 01 12
4.3 PDU 02 02 12

7/1551-LZA 701 6001 Uen D | 2010-05-21


PDU Description

7/1551-LZA 701 6001 Uen D | 2010-05-21


Product Overview

1 Product Overview

This document describes the Power Distribution Unit (PDU).

Information about the placement in the Radio Base Station (RBS) cabinet can
be found in RBS Description.

1.1 Purpose
The PDU is the internal power distribution unit in the RBS. The main function
of the PDU is to distribute -48 V DC power to DC-powered units in the RBS.
The PDU works as an internal distribution unit within a cabinet. It receives one
feeding of input voltage connector and distributes the input voltage to separate
fused outputs through output connectors.

1.2 Variants
Table 1 lists the different PDU variants.

Table 1 PDU Variants


Cabinet Type Applicable RBSs -48 V DC
Indoor RBS 6201 PDU 01 01
Indoor RBS 6201 V2 PDU 02 01
Indoor RBS 6202 PDU 02 02
Outdoor RBS 6102 PDU 01 01

1.2.1 PDU 01 01
This PDU is an internal power distribution unit situated in a power
subrack.Figure 1 shows the front of the PDU 01 01.

7/1551-LZA 701 6001 Uen D | 2010-05-21 1


PDU Description

PDU 01 01
Fault Sys Volt
Test port
EC Bus
Oper

CB 1 CB 2 CB 3 CB 4 CB 5 CB 6 CB 7
H-UP <19A <16A <19A <16A <19A <16A
PCR PCR PCR PCR PCR PCR PCR

Ge0085C

Figure 1 PDU 01 01 Front

1.2.2 PDU 02 01
This PDU is an internal power distribution unit situated in a 19 inch RBS slot.
Figure 2 and Figure 3 show the PDU 02 01.

11
PCR EC Bu
s
10
PCR
8
PCR 11

8
PCR 10

7 9
PCR
6 8
PCR
5 7
PCR
4
PCR 6

P CR 3 5

2
PCR 4

1 3
PCR
2

02 01 11
PCR
PDU

Ge0787A

Figure 2 PDU 02 01

Note: There are 11 PCR switches on the top of the PDU 02 01 .

2 7/1551-LZA 701 6001 Uen D | 2010-05-21


Product Overview

PDU 02 01 1 2 3 4 5 6 7 8 9 10 11 EC Bus

1 11 EC Bus
PDU 02 01

Ge0714A

Figure 3 PDU 02 01 Front

1.2.3 PDU 02 02

This PDU is an internal power distribution unit situated in a 19 inch RBS slot. It
is similar to the PDU 02 01 except that it uses a different cable connector.Figure
4 shows the PDU 02 02.

7/1551-LZA 701 6001 Uen D | 2010-05-21 3


PDU Description

11
PCR EC Bu
s
10
PCR
8
PCR 11

8
PCR 10

7 9
PCR
6 8
PCR
5 7
PCR
4
PCR 6

3 5
PCR
2
PCR 4

1 3
PCR
2

02 02 11
PCR
PDU

Ge1038A

Figure 4 PDU 02 02

Note: There are 11 PCR switches on the top of the PDU 02 02 .

4 7/1551-LZA 701 6001 Uen D | 2010-05-21


Function Description

2 Function Description

This section describes the functions for the PDU variants.

2.1 PDU 01 01
This PDU has the following functions:

• Controlling power distribution (see Section 2.3 on page 6)

• System voltage measurement

• Selecting fuse trip values (by hardware cable) : 6, 10, and 20 A

• System Voltage Test Port

Figure 5 shows the block diagram of the PDU 01 01.

Note: Figure 5 shows the maximum continuous current value.

System Voltage test port

1×16A with hold-up

EC bus Supervision
Control 3×16A without hold-up

DC Input
3×19A without hold-up

7×E Fuse

Ge0122A

Figure 5 PDU 01 01 Block Diagram

2.2 PDU 02 01 and PDU 02 02


This PDU has the following functions:

• Controlling power distribution (see Section 2.3 on page 6)

7/1551-LZA 701 6001 Uen D | 2010-05-21 5


PDU Description

• System voltage measurement

• Selecting fuse trip values (by hardware cable) : 6, 10, and 18 A

Figure 6 shows the block diagram of the PDU 02 01 and the PDU 02 02.

Note: Figure 6 shows the maximum continuous current value.

Supervision
EC bus Control

9 x14A Without hold-up


DC Input

2 x14A With hold-up

11xE Fuse
Ge0717A

Figure 6 PDU 02 01 and PDU 02 02 Block Diagram

2.3 Power Distribution Control


The Priority Load, Cold-Start, and Remote Control functions are used to
control the PDU. The PCR hardware selector in the PDU is used to configure
the different functions.

2.3.1 Priority Load Function


When battery voltage drops below a specified level, the Priority Load function
prioritizes the outputs configured as Prio. When the Battery Fuse Unit (BFU)
signal is received, PDU disconnects all outputs not configured as Prio.

The P switch has the following settings:

6 7/1551-LZA 701 6001 Uen D | 2010-05-21


Function Description

Prio load P switch in upper position


Main load P switch in lower position

2.3.2 Cold-Start Function


At start up, the PDU checks the input signal for the Cold-Start function. When
this signal is detected at start up, the PDU only turns on the outputs configured
as cold outputs.

The cold-start signal is only read during start up.

Remaining outputs will be turned on when the cold-start signal is ceased.

The C switch has the following settings:

Cold start configured C switch in upper position


Non-cold start configured C switch in lower position

Note: For outdoor RBS without heater all cold-start switches must be in upper
position.

2.3.3 Remote Control Function


The Main Processor (MP) can control the output when the switch in the PDU
is configured as remote controllable.

The R switch has the following settings:

Remote controllable R switch in upper position


Non-remote controllable R switch in lower position

2.3.4 Software Control


Each output voltage is equipped with an E-FUSE function. The E-FUSE
function provides overload and short circuit protection.

When the R switch is set to the upper position (remote controllable), the
E-FUSE can be configured in the software.

Note: If the switch is set to the lower position, the function cannot be remotely
controlled.

The E-FUSE function can be set in the following two ways:

• Persistent control (same function as using the button on the PDU)

7/1551-LZA 701 6001 Uen D | 2010-05-21 7


PDU Description

• Temporary commands (active output control function that overrules the


persistent settings) that consists of Temporary Control Enabled and
Temporary On

Table 2 lists examples of different Persistent Control, and Temporary Command


configurations.

Table 2 Examples of Different Configurations


(3)
Persistent Temporary Cont Temporary On Output
(1) (2)
Control rol Enabled
0 1 1 On
1 1 1 On
1 0 1 On
0 0 1 Off
1 0 0 On
1 1 0 Off
(1) 1 - on, 0 - off
(2) 1 - allowed, 0 - temporary value disabled, use persistent state
(3) 1 - on, 0 - off

8 7/1551-LZA 701 6001 Uen D | 2010-05-21


Technical Data

3 Technical Data

This section describes the technical data for the PDU variants.

3.1 PDU 01 01
This section describes the technical data for the PDU 01 01.

Table 3 lists the technical data for the PDU 01 01.

Table 3 Technical Data for PDU 01 01


Description Value
Normal voltage range -39.5 to -57.6 V DC
Maximum continuous current 125 A
Output capacity continuous load 4 x 16 A plus 3 x 19 A
Holdup function > 10 ms on output for CB1
Power consumption 8 W (excluding distribution loss)
Power dissipation 60 W
Temperature Range
Normal -40C to +60C
Limited performance (manual control) -40C to -10C
Dimensions
Height 43 mm
Width 145 mm
Depth 225 mm
Weight < 1.7 kg

3.2 PDU 02 01 and PDU 02 02


This section describes the technical data for the PDU 02 01 and the PDU 02 02.

Table 4 lists the technical data for the PDU 02 01 and the PDU 02 02.

Table 4 Technical Data for PDU 02 01 and PDU 02 02


Description Value
Normal voltage range -39.5 to -58.5 V DC

7/1551-LZA 701 6001 Uen D | 2010-05-21 9


PDU Description

Description Value
Maximum continuous current 115 A
Output capacity continuous load 11 x 14 A
Holdup function > 10 ms on DC output 1 and 2
Power consumption 10 W (excluding distribution loss)
Power dissipation 60 W
Temperature Range
Normal -40C to +60C
Limited performance (manual control) -40C to -10C
Dimensions
Height 21.4 mm
Width 434 mm
Depth 200 mm
Weight < 4 kg

10 7/1551-LZA 701 6001 Uen D | 2010-05-21


Signal and Power Interfaces

4 Signal and Power Interfaces

This section describes the interfaces for the PDU variants.

Information about the optical indicators can be found in Interpreting Optical


Indicators.

4.1 PDU 01 01
This section describes the interfaces for the PDU 01 01.

Table 5 lists details for the external interfaces on the PDU 01 01.

Table 5 PDU 01 01 Interfaces


Marking Description Connector Location
No marking Bus bar Bus bar Rear
connector
Fault Optical indicator, N/A Front
red
Oper Optical indicator, N/A Front
green
EC bus EC bus RJ-45 Front
CB1, H-UP DC out with ET 20 A Front
hold-up; optical
indicator, green
CB 2, 4, 6, <19 A DC out without ET 20 A Front
hold-up; optical
indicator, green
CB 3, 5, 7, <16 A DC out normal; ET 20 A Front
optical indicator,
green
On/off button N/A Front

Sys. Volt Test Test port for Hirschmann MBU Front


Port system voltage 02, 931-337-000
P Priority Load Hardware Front
function switch selector
C Cold-Start Hardware Front
function switch selector
R Remote Control Hardware Front
function switch selector

7/1551-LZA 701 6001 Uen D | 2010-05-21 11


PDU Description

4.2 PDU 02 01
This section describes the interfaces for the PDU 02 01.

Table 6 lists details for the external interfaces on the PDU 02 01.

Table 6 PDU 02 01 Interfaces


Marking Description Connector Location
No marking Bus bar Eaton Heinemann On the end of
connector 20980-35/TP cable
Optical indicator, N/A Front
red
Optical indicator, N/A Front
green
EC Bus EC Bus RJ-45 Front
1-2 DC out with ET 20 A Front
hold-up, optical
indicator green
3-11 DC out without ET 20 A Front
hold-up, optical
indicator green
On/off button N/A Front

P Priority Load Hardware selector Top


function switch
C Cold-Start Hardware selector Top
function switch
R Remote Control Hardware selector Top
function switch
Optical indicator, N/A Front
green
Power Distributi N/A Front
on Fault, Optical
indicator, yellow

4.3 PDU 02 02
This section describes the interfaces for the PDU 02 02.

Table 7 describes the external interfaces on the PDU 02 02.

12 7/1551-LZA 701 6001 Uen D | 2010-05-21


Signal and Power Interfaces

Table 7 PDU 02 02 Interfaces


Marking Description Connector Location
No marking Bus bar Anderson SB120 On the end of
connector cable
Optical indicator, N/A Front
red
Optical indicator, N/A Front
green
EC Bus EC Bus RJ-45 Front
1-2 DC out with ET 20 A Front
hold-up, optical
indicator green
3-11 DC out without ET 20 A Front
hold-up, optical
indicator green
On/off button N/A Front

P Priority Load Hardware selector Top


function switch
C Cold-Start Hardware selector Top
function switch
R Remote Control Hardware selector Top
function switch
Optical indicator, N/A Front
green
Power Distributi N/A Front
on Fault, Optical
indicator, yellow

7/1551-LZA 701 6001 Uen D | 2010-05-21 13