0% found this document useful (0 votes)
65 views1 page

Pages From 0-Fan Coil Unit (Zamil) - 2

1) The document provides specifications for a chilled water fan coil unit with a cooling capacity of 3.23 kW and airflow of 170 L/s that is designed for a location in KSA. 2) The unit has a forward curved fan, 2 row cooling coil, and optional 1 kW electric heater. 3) Key performance details are provided such as entering/leaving water temperatures, psychrometric data, electrical specifications, dimensions, and sound power levels.

Uploaded by

Vic Bayot
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views1 page

Pages From 0-Fan Coil Unit (Zamil) - 2

1) The document provides specifications for a chilled water fan coil unit with a cooling capacity of 3.23 kW and airflow of 170 L/s that is designed for a location in KSA. 2) The unit has a forward curved fan, 2 row cooling coil, and optional 1 kW electric heater. 3) Key performance details are provided such as entering/leaving water temperatures, psychrometric data, electrical specifications, dimensions, and sound power levels.

Uploaded by

Vic Bayot
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Chilled Water Fan Coil Units Selection 02-August-18

Version
7.6.2
Customer : MESMACK Co. LTD Designer : Sajed
Project : 028-C51-JTI PHASE 6 Location : KSA
Reference : FCU-01
INPUT
Blower Motor Speed External Static Pressure Supply Airflow Altitude Frequency
General Data
[Pa] [L/s] [m] [Hz]
MED 45 170.00 ± 20 % 0.00 60
Cooling Data Required Ent Dry Bulb Temp Ent Wet Bulb TempEnt Water Dt Water Flowrate
Total Capacity Temperature
[kW] [°C] [°C] [°C] [°C] [L/s]
2.64 27.00 20.80 7.20 5.60
Heating Data Required Ent Dry Bulb Temp Ent Water Dt Water Flowrate
Total Capacity Temperature
[kW] [°C] [°C] [°C] [L/s]
0
2 0 0 0 0
OUTPUT
Unit Model DWX04 PERFORMANCE DATA
Fan Data Cooling
Fan Type Forward Curved Total Cooling Capacity [kW] 3.23
Size [mm] 146x196 Fan Speed Med
Quantity 1 Sensible Capacity [kW] 2.71
SHR 0.84
Air Flowrate [L/s] 170
Cooling Coil Data Entering Water Temperature [°C] 7.20
Coil Face Area [ ft² (m²)] 1.75 (0.16) Leaving Water Temperature [°C] 12.80
Coil Tube Diameter [Inch] 3/8 Water Flow Rate [L/s] 0.138
Rows 2R/4Crkt Water Pressure Drop [kPa] 6.2
Fins Per Inch 12 Psychrometric Data Entering Leaving
Heating Coil Data Dry Bulb Temperature [°C] 27 13.6
Coil Face Area [ ft² (m²)] - Wet Bulb Temperature [°C] 20.8 12.4
Coil Tube Diameter [Inch] - Relative Humidity [%]
Rows - Humidity
Fins Per Inch - Enthalpy [kJ/kg]
Specific Volume [m³/kg]
Piping Connection
Chilled Water in/out [Inch] 5/8-5/8 Heating
Hot Water in/out [Inch] -
Electric Heater [kW] 1
Weight and Dimensions Electric FLA [A] 4.35
Length [mm (Inch)] 863 (34.0) -
Width [mm (Inch)] 520 (20.5) -
Height [mm (Inch)] 246 (9.7) -
Weight [kg] 34 [kPa] -
Filter Data Psychrometric Data Entering Leaving
Return Air Filter Size [Inch] 7.5 x 14.6 Dry Bulb Temperature [°C] - -
Return Air Filter Qty 2 Wet Bulb Temperature [°C] - -
Relative Humidity [%] - -
Power Supply Humidity - -
208/230V-1Ph-60Hz Enthalpy [kJ/kg] - -
- - Specific Volume [m³/kg] - -
Electrical Data
Blower Motor [W] 60
Blower Speed [RPM] 800
Blower Motor FLA [A] 0.66
MCA [A] 6.26
MOCP [A] 15

Sound Power Data


Frequency [Hz] 125 250 500 1000 2000 4000 8000
dB 61 57 52 51 49 44 39