Separation Technology
Separation Technology
fpg.co
OPEN
Distillation columns or systems are designed some thing in the same way as
a sequence of individual stills as previously mentioned. Each ‘still’ area
includes a variety of ‘TRAYS’ or getting in touch with gadgets organized top
to bottom above one another in the pillar. These containers or contactors
carry fluid and fumes into romantic get in touch with in order to acquire
the needed separating of the combination. The size of the structure and the
variety of containers or getting in touch with gadgets it contains, relies on
the cleanliness of the ‘Fractions’ needed.
be of the following types:
Columns for the distillation procedure can
The fluid drops towards the end of the structure. At the structure base, in
common, more warm is included to the fluid by a ‘Reboiler’ which may be
vapor warmed or a petrol shot heater kind.
The inclusion of warm here causes more vapours to increase up the pillar.
As the two stages of the combination – dropping fluid and increasing fumes
– come together, light elements are removed out of the fluid and get into the
gas stage while hefty elements in the fumes are compacted into the fluid
stage.
With this kind of distillation pillar there is usually only a top and base
product. The quality of the products relies on the size of the structure, the
variety of getting in touch with gadgets, the structure heat range and stress
and their control, and the speed of the increasing vapours.
THE SIEVE TRAY is a steel plate containing drilled gaps through which the
increasing fumes can complete into the liquid streaming across the tray.
Figure: 11
TRAY is just like the sieve type but, each opening is fixed with a
THE VALVE
flapper valve which starts as fumes goes through the opening. This kind is
used where fumes speed is not continuous and the valves avoid liquid from
throwing through the gaps at periods of low gas speed. Figure: 12
THE BUBBLE-CAP TRAY is the most effective separating program but,
is also
the most expensive. It includes a variety of ‘Chimneys’ or ‘Risers’ (small,
brief tube joints set into the tray), through which the fumes can complete.
Fitted over the riser is a ‘Cap’ which causes the increasing fumes to convert
through 180 °. This causes the gas to ‘Bubble’ through the liquid streaming
across the tray. The liquid stage on the tray is managed below the top of the
riser to avoid throwing of liquid down the structure. Figure: 13
Each of the above containers also has a ‘WEIR’ that preserves the
liquid
stage on the tray. As the liquid moves over the weir, it goes into a
‘DOWNCOMER’ – (a brief pipe), that provides the liquid down to the tray
below. The downcomer store is below the outer lining area of the liquid on
the tray below, performing as a closure to avoid gas from skipping the tray
above.
trilliumflow.com
OPEN
1. REFLUX RATIO
The reflux to a structure top is used to management the top heat range
thereby manages the cleanliness of the expense item.
The quantity of reflux compared to the item is known as the ‘Reflux Ratio’.
symbolizes chilled, compacted top item came back to the structure top and,
as such it is being reprocessed. The top item will therefore be more pure. In
general, the higher the reflux amount, the less the number of containers
needed for a given separating.
However, too great a amount may cause surging in the structure leading to
inadequate separating and causing ‘off-spec’ items throughout the program.
The reflux amount is normally managed by a heat range operator in the
fumes store which functions a management device in the reflux push
release. An increase in structure top heat range will cause the device to
start, improving the reflux amount, and viceversa.
2. TEMPERATURE GRADIENT
Temperature (and pressure) management of a distillation structure will
regulate the cleanliness of the items. The management of top heat range is
as mentioned above in ‘reflux’. Control over the supply inlt heat range and
that of the reboiler are also very essential.
Again, if supply and bottom temperature ranges are too great, too much
hefty fumes will rise up the structure and put side-stream items off-spec.
This condition, along with great reflux amount will again cause to surging
and inadequate separating. Opposite conditions can cause to fluid hunger
across the containers and again, a very disappointed process will outcome.
Examples:
range will outcome in hefty elements in the expense item.
High top heat
Low top heat range will outcome in a less hefty top item.
A further point is, that high-water content in the raw supply will cause
stress deluges as the water vaporises in the structure. The raw oil should be
as water free as possible.
Many modern distillation models are managed under great machine. This
method, due to the machine reducing the BP’s of the elements of the
combination to be separated, also decreases the quality of heat energy
needed to vaporise the elements.
Figure: 15
In the above plan, the outer lining place condenser is a ‘Total Condensing’
unit. This means that all liquids that can be compacted are modified to
fluid. Due to this, a machine is established in the structure the stage of
which relies on the degree of moisture build-up or condensation permitted
to take place. This is managed by the stage of distillate and how much of the
condensing surface place is protected. The fluid stage and therefore the
quality of condensing surface place available will decide the stage of
machine (Absolute Pressure) of the program.
ITSI-Biosciences Open
The region above the dew-point curve shows the equilibrium composition
of the superheated vapour while the region below the bubble-point curve
shows the equilibrium composition of the subcooled liquid.
For example, when a subcooled liquid with mole fraction of A=0.4 (point A)
is heated, its concentration remains constant until it reaches the bubble-
point (point B), when it starts to boil. The vapours evolved during the
boiling has the equilibrium composition given by point C, approximately
0.8 mole fraction A. This is approximately 50% richer in A than the original
liquid.
This difference between liquid and vapour compositions is the basis for
distillation operations.
Relative Volatility
yi = mole fraction of component ‘i’ in the vapour
a quote now.
Berthold Technologies Open
The hot supply now goes into the structure into the ‘Flash Zone’. At this
point, due to the greatly increased volume of the pillar, the less hefty
elements of the oil ‘ Display Off ‘ (vaporise), and increase up the pillar. The
hot fluid will fall towards the pillar base.
The base area of the pillar, below the Display Area, known as the ‘Stripping
Section’, contains containers – usually Bubble-cap or Filter type. The
structure base fluid is re-circulated & re-heated in a vapor or shot ‘Reboiler’
which pushes off vapours of mild finishes and some of the hefty finishes in
the fluid. These vapours increase up-wards through the containers and
contact the down-flowing fluid. This activity further eliminates (strips out),
mild finishes from the fluid.
The top area of the structure, above the flash zone, is known as the
‘Rectifying Section’. Here again, the increasing fumes passing through the
containers, connections the fluid streaming across them.
Action of the Trays Each plate in the structure is performing like a single
still as discussed in ‘Batch Distillation’. As we increase above the flash zone,
each following plate is a little bit chilly than the plate below.
The down-flowing fluid is known as ‘Internal Reflux’ and works in the same
way as in Figure: 7 (Page 14), where the fluid is came back to the previous
still.
The least heavy elements of the oil combination leave the top of the
structure as fumes. This is fed through condensers – usually water-cooled -
and the condensate, usually Naphtha and water, goes into the ‘Overhead
Device or Accumulator’.
In the recipient, mild fumes also build up. The management of these fumes,
(to a petrol program or flare), also manages the stress on the distillation
procedure at the needed stage.
The Naphtha fluid forms an program above the water. The water is cleared
away under management, to disposal. The Naphtha, also under stage
management, is separated into two – some is came back to the structure top
plate as ‘External Reflux’ which is used to management the structure top
warm range and thereby help to management the naphtha top quality.
The staying naphtha from the recipient is piped to storage space and / or to
other processes. The items making the part of the pillar -called ‘Side-
streams’, are usually approved through ‘Stripping Towers’ where an
hypodermic injection of superheated vapor eliminates last records of mild
finishes to fulfill the requirements needed for the item. The mild finishes
and vapor are approved back into the structure.
The side-stream items pass from the burning systems through supply / item
exchangers and water chillers to storage space.
The structure base item as already mentioned, is reheated in a reboiler to
remove mild finishes and to provide burning fumes in the structure. The
ultimate base item, such as hefty petrol oil is treated away via feed/product
warm exchangers and water chillers to storage space. In some distillation
systems, superheated vapor may be treated into the structure base to assist
the burning procedure.
Crude oil distillation is often carried out under machine circumstances. The
machine is produced by taking the expense fumes from the structure by
vapor ejectors via surface condensers.
The variety of elements in the fumes area cause a ‘Vapour Pressure’ above
the fluid and, again, the higher the heat range, the higher the fumes stress.
The fumes stress is termed as the ‘VP’ of the fluid at a particular heat range.
For any given fluid at a particular heat range, the variety of elements in the
fumes area is continuous, thereby providing a continuous VP
(37.8 °C) the VP is 1.0 psia and at 212 °F (100 °C) it is 14.7 psia (101 kPa). The
factor at which a fumes stress of a fluid is at its highest possible for the
particular heat range, the VP is known as the Soaked Vapour Pressure (SVP)
and, at this factor the fluid and its fumes are said to be at ‘Equilibrium’. (See
Figure: 1)
Figure : 1
At stability, the variety of elements coming into the fumes area is similar to
the variety coming back to the fluid. This situation continues to be
continuous as long as the heat range continues to be continuous.
Contact Us Now.
trilliumflow.com
OPEN
Downcomer Residence Time:
Sufficient residence time must
be provided in the downcomer to allow
adequate disengagement of vapour from the descending liquid, so that the
liquid is relatively vapour free by the time it enters the ray below.
Inadequate removal of vapour from the liquid may choke the downcomer.
the aerated liquid is calculated from:
The pressure drop through
h Hydraulic gradient = 0 for sieve tray (Detail calculation Refer Kister
Section 6.3.3)
hW = Weir height, in
hOW = Crest over the
weir, in
QL = Liquid flow per unit weir
length(GPM/in)
Downcomer Backup:
Downcomer backup flooding occur when the backup of aerated liquid in
the downcomer exceeds the tray spacing
Where,
% Backup should be less than 80%. If it is high the changes in the design as
stated above can
be made.
New Compressors
Available
Lab Gas Parts Ltd
A packed bed provides a mechanism for mass or heat transfer through
which the gas & liquid phases usually flow counter currently in the column.
The presence of tower packing elements provides a resistance to the flow of
these fluids that is greater than it would be in an empty column shell.
Packing tends to be used selectively for the following applications:
(3
a) Small tower diameters – When a tower diameter is less than 0.9m
feet), it is difficult to access the tower from inside to install and maintain
trays. Packing is normally a cheaper and more desirable alternative for
small diameter towers. However in special cases cartridge trays are used
for diameters less than 0.9m (3 feet)
b) Low pressure drop applications – Packing pressure drop is usually
much lower than trays. The open area of each tray is typically 5 % to 10 %
of the tower cross sectional area while the open area in a packed tower is
usually greater than 50 %.
range of packing materials is wider than that of
c) Corrosive systems – The
commonly available for trays. Ceramic and plastic packing is cheap and
effective for handling corrosive fluids.
packing is used to replace trays in
d) Existing tower revamps – Frequently,
order to increase the capacity of an existing tower.
classified as follows.
Based on the geometrical construction, packings are
Following are the points to be considered while selecting the proper type of
packing for particular service.
Specific surface area (m2/m3): This is the surface area per unit volume of
packing. This maximizes vapour liquid contact area & therefore efficiency.
Hence for random packings efficiency generally increases with decrease in
packing size. For structured packings efficiency increases as the space
between adjacent layers is decreased & for grid packings it increases as the
lattice opening are narrowed. Modern efficient third generation random
packings have specific surface area of 300 as compared to latest wire gauze
structured packings of 700 m2/m3.
liquid pockets are minimized. In case of latest type of saddles liquid pockets
are minimized which are there in older berl saddle type of packings.
PROCEDURE:
1. Basic concept.
Basic Concept:
PA= yA × P
PA= P°A× X A0
For lower value of xA linear relationship exists between PA & xA by a new
proportionality factor H’. This relationship is given by Henry’s law &
represented as
PA= H × X A
Azeotrope:
When the positive deviations from ideality are sufficiently large & the
vapor pressures of two components are not too far apart, the total pressure
curve at constant temperature may rise through maximum at some
concentration & such mixture is said to form an azeotrop or a constant
boiling mixture. Solutions like this sort cannot be completely separated by
ordinary distillation method. At azeotropic conditions y* = X & ? = 1.
Azeotropic composition as well as boiling point change with total operating
pressure.
A mixture whose total pressure is greater than that computed for ideality is
said to show positive deviation from Rault’s law. In this case partial
pressures of each component are larger than ideal.
1) Simple Distillation
2) Flash Vaporization
First method is generally used for batch type & remaining two for
continuous type for binary & multicomponet mixture.
FX F = DyDAV + WXW
Where
– Operating Pressure
– Feed location
This guideline covers the shortcut method to determine the above design
parameter
Specify Separation:
Normally, these two components are adjacent to each other in the volatility
list. For hand calculations, it is normally assumed for material balance
purpose that all components lighter than the light key are produced
overhead and all components heavier than the heavy product are produced
with the bottom product
Air: The least expensive cooling method. Design limits the process to an
11°C approach to the ambient summer temperature.
Cooling Water: The satisfactory temperature approach is 5 to 10°C.
Advantages
Disadvantages
For mature technologies the operating pressures of the column have been
standardized except for some variation due to site condition, reference can
be taken from similar plant/equipment.
The Underwood method can be used for calculating minimum reflux ratio.
The Underwood method assumes:
The first step is to evaluate? (Which must lie between the relative
volatilities of the keys) by trail and error from
Once s is determined, the minimum reflux ratio is
Where,
There are several considerations in deciding the reflux ratio; the following
comments indicate the effect of a change in the reflux ratio in relation to
the number of stages.
The higher the reflux rate, the higher the cost of condensing and
reboiling. These make up the bulk of the column operating costs.
As reflux ratio increases, the number of stages decreases, but column
diameter increases.
Close to minimum reflux rate, small increases in reflux ratio will reduce
the number of stages considerably and therefore column height, but
produce only a small increase in column diameter.
We have calculated
Knowing Sm/S from the graph below we can calculate S = Number of stage
Adjust actual reflux for feed vaporization if necessary
The Erbar and Maddox correlation is based on bubble point feed. For a
feed stream between the bubble point and dew point the following
relationship adjusts the vapor rate from the top tray for non bubble point
feed.
Once a base case tower has been simulated, optimization studies on trays
vs. reflux, feed tray location, etc. can be carried out. One criterion often
used for optimum location of the feed tray is to try and match the feed
composition as closely as possible to a corresponding tray composition. The
approximate feed location can be determined by the ratio of the total
number of theoretical stages above and below the feed plate from following
equation:
Fenske’s Equation
Kirkbridge’s Equation
Akashahetal’s Correction
Fenske’s Equation
(10)(eq. cont.)
Column Internals Explained : Part – 1
http://seperationtechnology.com/column-internals-explained-part-1/
In the recent years, efforts have been made to design structured & random
packings for mass transfer columns more & more effectively. These
developments are done to achieve greater throughputs; lower pressure
drops & better mass transfer efficiency. Column internals are also playing
important role for achieving the above targets & hence needs to be
designed carefully from both process & mechanical point of view. After the
packed column hydraulics, column internals needs to be designed. Packing
internals include support plates, distributors, redistributors, and bed-
limiters, feed pipes, collector trays & mist eliminators.
Support Plate
For random packings, gas injection type of support plate is used. Gas
injection type of support plate provides the separate passage for liquid &
gas. Support grid (made up of bars) is used to support the structured
packing. Support plates have a very high open area for gas & liquid passage
& do not add any significant pressure drop.
b) Bed Limiter: Bed limiters are commonly used with metal or plastic
packings. The primary function of these devices is to prevent expansion of
the packed bed as well as to maintain the bed top surface level. In towers,
the packed bed will not fluidize over the entire surface, vapour surges
fluidize random spots on the top of the bed, so that after return to normal
operation the bed top surface is quite irregular. Thus the liquid distribution
can be affected adversely by such an occurrence.
Bed Limiter
Hold-down plates are weighted plates used with ceramic or carbon tower
packings. With these packings, it is especially important to prevent
fluidisation of the packed bed top surface. The hold down plate must rest
freely on the top of the packed bed because beds of ceramic & carbon
packings tend to settle during operation. These plates usually act by their
own weight to prevent bed expansion. Weight (kg) of the hold down plates
can be calculated by the pressure drop across the packed bed (kg/m2)
multiplied by the column cross sectional area (m2). They weigh ~ 95-120 kg
per sq meter (20 lb to 30 lb per sq ft).
located in an inlet sump. All chimneys should have hats located a sufficient
space above the chimney to give a peripheral area of 1.25 times the
chimney area. If a leak-free design is required, the inlet sump should be
seal-welded and gasketing used on the chimney tray floor. A centre sump is
preferred over a side sump, as some flow restriction can occur at very high
liquid rates due to the shorter weir lengths of side sumps.
Resistance to fouling
Minimum height
capability
Higher cross-mixing
Distribution quality: Quantifying the uniformity of liquid distribution is
accomplished by calculating the distribution quality (DQ) of a distributor
based on the Moore & Rukovena model. It relates the liquid load across the
column area at the top of packed beds marking circles proportional to the
liquid flow through a particular orifice & then considering the irrigated,
overlapping, & un-irrigated areas of the circles.
Gravity Distributors: These are further classified as weir type & the orifice
type. Both of these types can handle large liquid flow rates. The weir type is
generally one of the least troublesome distributors, handle large liquid load
& has excellent turndown capability. However it can usually provide only a
limited no. of drip points (minimum 30 no. of weirs per m^2), extremely
sensitive to levelness & liquid surface agitation.
(trough) type. An orifice pan distributor consists of a pan equipped with the
circular or rectangular risers for vapour flow & perforations in the pan for
liquid flow. Orifice trough type distributors consist of parallel troughs with
perforations in the trough floors for liquid. Vapour rises in the space
between the troughs. The troughs are often interconnected by cross
channels (called as parting box) that equalize liquid levels in different
troughs. These trough type liquid distributors provide more open area for
vapour flow & are easier to support.
& plugging, but it can be designed
Orifice type may suffer from corrosion
with a large no. of drip points to provide superior liquid distribution.
Orifices are sized to maintain a minimum liquid head at desired turndown
conditions & to avoid distributor overflow during turn up condition. Very
small orifice diameters (<4mm) are avoided to prevent fouling.
Please refer the packing vendor catalogue for more details on liquid
distributor models/types.
Maximum & Minimum head: Maximum liquid head is the actual liquid
head on the deck of the distributor at turn up condition. The overall height
(riser/trough) of the liquid distributor shall be higher than this head by
following formula.
variation will increase due to low liquid head. Flow variation is a strong
function of mechanical points such as plate levelness, distributor deck
flatness as etc. Excessive flow variation will cause liquid misdistribution on
below packed bed, entrainment & hence needs to be minimised. Maximum
of 12% flow variation is allowed for liquid distributor or redistributor.
Process demand various feed to be introduced into the column
Feed pipes:
at various locations. The feed being introduced could be liquid only, liquid
& vapour above a packed & vapour only below a packed bed.
For liquid & vapour feed devices above a distributor, separating the two
phases is of primary response. The primary design factors are the feed flow
rate, desired turndown, column height needed for flashing vapour
distribution & mixing of the inlet liquid with overhead liquid. Flashing feed
devices such as flash feed gallery, flash feed chamber or flashing feed pipe
are used based on the composition of vapour in liquid.
Vapour only feed devices are required for reboiler returns or to introduce
vapour feed or to introduce vapour or gaseous feed. If the column offers
adequate pressure drop (> 4-5 mm of WC per m of packed bed height), the
packings themselves tend to mix the vapours. In the event of very low
pressure drop across the column (i.e. < 4-5); vapour channelling can
become a serious problem. The kinetic energy of the vapour (F factor) & its
composition at the point of introduction are the two main factors
considered in designing the vapour entry device. Vapour or gas feed pipes
are designed with a velocity of max 20m/s.
Contact Us Now.
trilliumflow.com
OPEN
To secure the motor bearings, golf club shafts, equipment and aide …etc,
the car lubricant oil is also strained. In all cases where filters or strainers
are used, they must be washed or the unclean components modified for
fresh ones as soon as the filtration procedure becomes inadequate and fluid
circulation reduces.
1. FILTERS (Figure: 24)
The program will have a means of calculating the stress fall across the
narrow and, when this D.P. gets to a certain point, an alert change may be
triggered. The filters must then be modified over, the unclean narrow is
then separated, de-pressured, cleared and started out up to eliminate the
unclean components. New components are then set up and it ‘boxed up’.
The fresh narrow is then filled again and/or re-pressurized by using the
little collections and valves offered. While reloading, air is venting to make
sure that the narrow is liquid/gas full. It is then placed on ‘standby’. Where
a single narrow device is set up, again, the avoid is used while washing is
performed.
2. STRAINERS
Where little pipes like petrol resources, air to equipment and vapor /
condensate techniques are worried, strainers are set up to make sure the
sleek function of equipment and vapor barriers by eliminating strong
contaminants.
Sample calculation:
across 100 mesh lined Basket Type strainer
Estimate pressure drop
provided in a 6″ line with following data.
Flow rate = 700GPM
Viscosity = 100cP
Specific Gravity =
1
The Pressure Drop
Chart for Basket strainers indicates a drop of 0.9psi.
The Screen openings chart indicates the % open area of 100 mesh is 30%.
From chart one correction factor to be 1.2.
= 1.08 psi
by the specific gravity of the fluid actually flowing through the
Multiply P1
strainer to get P2.
=1
Since specific gravity
Pressure drop (P2) = P1 X
Sp. Gravity
= 1.08 X 1
=1.08psi
2 multiply P2 by the appropriate component factor (CF) to get
Using chart
P3.
chart 2, (P3) = P2 X (CF)
Using
= 1.08 X 0.35
= 0.38psi
Let, P4 =
P2 – P3 = 1.08 – 0.38
= 0.7psi
Multiply
P3 by the appropriate body loss factor (BF) in chart 3 to get P5
Using chart 3, P5 = P3 X (BF)
= 0.38 x 1.6
= 0.61psi
= 4.55psi
Annexures:
February 14th, 2012 in Other Unit Operations
General steps for packed column hydraulics
http://seperationtechnology.com/packed-column-hydraulics/
trilliumflow.com
OPEN
The results of process calculations for the column from simulation package
are made available to the concerned engineer in the form of stage wise
loading summaries & its properties, which will be generated in column
environment of simulation software such as Hysys, Chemcad, Pro-II as etc.
These loadings are used to generate the PDS for packed column.
Packed bed height & total no. of beds needs to be finalised based
on the
HETP (with desired safety margin for particular service) of selected
packings. Theoretical no. of stages getting after doing process design of a
particular column on simulation software needs to be converted into actual
no. of stages or actual packed bed height) based on HETP concept.
Particular type of packing to be selected based on the guidelines as given
above or from past experience on similar column.
For e.g. for 5 no. of theoretical stages for IMTP#15 packings, total bed height
will be HETP times the theoretical no. of stages. As approximate HETP value
of IMTP # 15 packing is 350mm. Total packed bed height will be calculated
as below.
Hence total packed bed height for above case will be 1750mm.
HETP & other physical properties such as surface area, packing
factor, void
fraction as etc of different packings are to be taken from packing vendor or
from open literature as given in reference documents.
be infinite in
There is no conclusive evidence that packed bed may not
depth, from a process point of view. There are however mechanical
limitations such as crushing or deformation exists for deep beds. Maximum
packed bed height for different packings is the ratio of maximum allowable
load (kg/m2) to its density plus liquid hold up in kg/m3. Generally maximum
bed height of 8m is recommended for random & structured packings.
d) After fixing the column configuration (diameter & packed bed height),
internals such as liquid
collector tray, feed pipe, as etc needs to be
distributor, redistributor,
designed.
Contact Us Now.
trilliumflow.com
OPEN
There are several software programs for packed bed hydraulic calculations
released by vendors, some of them have been installed on their website
also. These programs, vendor brochures or column-sizing mode in
simulation software’s can be used for process studies and preliminary
designs. For final designs, the Process Engineer should obtain the hydraulic
calculations from packing vendors.
ii) Ordinate value to be taken from for upper flooding curve from above
chart & calculate the flooding vapour mass velocity by following formula.
each type of packings. Lower packing factor values means higher the
capacity & lower the efficiency of a particular type of packing. Kindly refer
table 6.3, (page no. 196) of Mass Transfer Operations of Treybal for packing
factor.
General Guidelines
7. Corrosion
1. Residence time
2. Stagnate zones
3. Sharp transitions
4. Emulsion issues
Consideration must also include the fact that fouling gets worse over time.
Fouling is not static.
Fouling Mechanisms
Condensation
Many processes contain suspended solids, which can settle out on the mass-
transfer surface. Products of sedimentation can include salts, metal oxides,
catalyst fines, and coke fines. Precipitation and crystallization of dissolved
salts can occur when process conditions become super saturated, especially
at mass transfer surfaces. Ammonia salt deposition resulting from both
water vaporization and direct solid deposition from the gas phase is a
common refining problem.
Sometimes the deposits formed do not adhere strongly to the surface and
are self limiting, the thicker a deposit becomes, the more likely is to be
removed by the fluid flow and thus attain some asymptotic average value
over time. Sedimentation fouling is strongly affected by velocity and less so
by temperature, however a deposit can bake on a surface and become very
difficult to remove.
1. Evaporation of solvent
2. Cooling below the solubility limit for solution with normal solubility,
solubility increases with temperature.
3. Heat above the solubility of solutions with inverse solubility such as;
CaCO3, CaSO4, CA3(PO4)2, CaSiO3, Mg(OH)2, MgSiO3, Na2SO4, Li2S04
and Li2Co3 in water.
4. Mixing of streams with different composition.
5. Variation of pH, which affects the solubility of CO2 in water.
Foaming System
Chemical Reaction
Corrosion
Workflow management
for AM
Authentise Inc.
Process Review
Equipment Selection
The most suitable mass transfer equipment for fouling service may also be
the least efficient for mass transfer. Grid packing and shed decks can
handle nearly every fouling service, but have low efficiencies when
compared to sieve trays, random, and structured packings.
Packing
For packed towers the key fouling factors revolve around liquid
distribution and packing residence time. The longer the residence times the
less suitable. Low-pressure drop, smooth surface, low residence time
packings perform best in fouling service. The order of preference is:
1. Grid
2. Structured packing
3. Random packing
Packing Distributor Concern
Tray
The industry prefers trays in fouling service because of the long history of
success trays have had in fouling service applications. The first continuous
distillation column with bubble cap trays was developed in 1813 and
structured packing was developed in 1964. The database and application
know how is much larger with trays. The best trays to use in fouling
services are sieve trays and dual flow trays. Moveable and fixed valve trays
are less resistant to fouling because the valves are areas where fouling can
seed and propagate. Distillation is part art, part science. As in any science,
as you explore the limits you will find the
Baffle Trays
1. Shed Decks
Shed decks are essentially angle iron beams of various sizes from two to ten
inches that are placed in rows across the column. They typically are at on
24 inch tray spacing. They may be set in overlapping rows or rotated 90
degrees from tray to tray. The open area on the tray is typically 50%. The
positives of shed deck are that the fouling potential of the decks is almost
zero because there are no stagnate zones and low residence time.
Unfourtunaly, the efficiency of the tray almost matches the fouling
potential, particularly if wide shed decks are utilized. Shed decks work well
in fouling applications where their application is essentially for heat-
transfer purposes.
2. Disk and donut trays
Disk and donut trays are slightly sloped trays that allow the liquid to splash
from inner circle ring to outer circle ring. Fouling potential of this tray is
low along with the efficiency.
3. Side to side trays
Side-to-side trays are trays that allow the liquid to splash from side to side.
Fouling potential of this tray is low, as with efficiency.
Dual Flow Trays
Dual flow trays are the trays of preference for heavy fouling services. Dual
flow trays have no downcomers, where products of fouling phenomena can
accumulate or where polymer and solids can seed and propagate. Dual flow
trays are designed with enough open area on the tray decks to eliminate
stagnation and promote back mixing. A disadvantage to dual flow trays is
that they are limited in turndown potential.
The vapor and liquid transfer up and down the column through the holes
on the tray deck. This is an advantage in combating vapor-phase fouling as
the underneath of the tray is washed. The continuous agitation of the liquid
on the topside of the trays combined with continuous underside
wetting/washing action makes this tray suitable for fouling services.
Two types of dual flow trays are available; standard deck and rippled deck.
The standard deck has a flat plate, and the rippled deck has sinusoidal
waves.
1. Standard austenitic stainless steel such as 316 (18Cr 10Ni 3Mo) can be
utilized for resistance to acids and reasonable resistance to pitting
corrosion. Type 304L (18Cr 10Ni) stainless steel has a good resistance to
nitric acid. Austenitic stainless steels have relatively low strength, poor
anti erosion and abrasion properties and do not possess the ability to
resist stress corrosion cracking.
2. Super austenitic stainless steels with relatively high nickel content
(approximately 20 Cr 29 – 34 Ni), sometimes referred to as alloy 20 are
more costly than standard austenitic steels but provide excellent
resistance to acids and some acid chlorides.
Use of Additives
An additive may act to resist fouling in one or more of the following ways.
1. Chemically react with the fouling species to modify it’s fouling potential.
2. Change the physical interaction between the foulant and the equipment
surface.
3. Modify the deposit residing on the surface, so that is can be removed by
fluid flow.
Stagnant Zone
Sharp Transition
If the fouling potential is in the vapor phase, the overhead vapor may be
drawn from the side of the tower versus the tower over head to eliminate
transition line length and an additional corner.
Emulsion Issue
trilliumflow.com
OPEN
A distillation column has three basic sources of reject heat, the bottoms
product, the condensing overhead vapor, and the distillate product. The
two basic heat inputs are the reboiler and the feed.
Bottoms Product :
The ability to use the heat in the bottoms product will depend on its
requirements for downstream processing. If the product is required hot
downstream, it is impractical to cool it and then to reheat the bottoms
stream. If the stream does not need to remain hot, the following represent
possible uses of the bottoms liquid heat.
Condenser Duty – The largest potential reject heat source of the distillation
column is the condenser. All this heat is available at essentially a single
temperature, and all the heat duty must be removed. Possible uses of the
condenser duty could be to supply heat to a neighboring column reboiler, to
produce waste steam, or to heat large liquid streams at low levels, such as
supplying hot water for a building.
Reboiler Duty – The reboiler represents the largest heat input to the
distillation column. The reboiler requires heat at a single high temperature.
It is desirable to minimize the steam consumption if possible by using
condensing vapors from other columns, hot process streams, or special
very low pressure steam.
trilliumflow.com
OPEN
trilliumflow.com
OPEN
Introduction:
Once the process design stage ends, the equipment design begins. This stage of
design converts process requirements into actual hardware.
One of the most prominent hardwares used for mass transfer is tray. Tray
columns are widely used in various types of mass transfer operations. All the
simulation results, which predict a certain number of theoretical stages, can be
converted to actual trays depending upon tray efficiency for a particular service.
In any conventional tray vapour rises through the liquid pool on the tray deck
and then disengages from the liquid in the space above the deck. Liquid enters
the tray from a downcomer above and leaves via a downcomer below.
1. Active area for mixing vapour and liquid: This is the zone where mass
transfer occurs.
2. Vapour space above the active area: This is the zone in which liquid is
separated from vapour.
3. Downcomer between trays. This zone has two functions, first moving liquid
from one contacting tray to another and second disengaging vapour from
liquid.
Each of these zones takes up vertical and horizontal space in the tower.
Selection Guide for Tray Column:
The factors discussed below influence the choice between trays & packings. As
these are guidelines for selection of trays or packings for a particular service, it
is recommended to analyze each design case on its own merit for selection.
Sr.
No. System Favouring Tray Column System Favouring Packed Column
Solid Vaccum
1 handling system
High liquid
2 rate Low pressure drop application
Revamps-
The pressure drop reduction
composition
Feed and temperature
can
3 be translated into capacity gain, an
variable
energy gain or separation
improvement.
Large diameter
4 columns Small diameter columns< 900 mm
7
polymerisation and
colils, & side draw
degradation.
9 Chemical reactions
The industry, based on its experience, has standardised the type to be used in
certain services. If this reference is not available the guideline as per Appendix
1 are to be used
Types of Tray
The particular tray selection and its design can materially affect the
performance of a given distillation, absorption, or stripping system. Each tray
should be designed so as to give as efficient a contact between the vapour and
liquid as possible, within reasonable economic limits.
Valve tray:
Valve trays are perforated sheet metal decks on which round, liftable valves are
mounted. The vapour flows through valves which are installed parallel to the
outlet weir. Valve trays combine high capacity and excellent efficiency with a
wide operating range.
Sieve tray:
Sieve trays are flat perforated plate in which vapour rises through small holes in
tray floor, & bubbles through liquid in fairly uniform manner. They have
comparable capacity as valve trays.
Advantages:
Disadvantages:
Vapour rises through risers or uptakes into bubble cap, out through slots as
bubbles into surrounding liquid on tray. It is mainly used in special applications.
Advantages:
Moderate capacity
Most flexible (high & low vap. & liquid rates)
Can provide excellent turndown.
Disadvantages:
A dual flow tray is a sieve tray with no downcomers. This tray operates with
liquid continuously weeping through the holes. Due to the absence of
downcomers, dual flow tray gives more tray area hence a greater capacity than
any of the common tray types. They are ideal for revamp where if some
efficiency can be sacrificed for more capacity. They are least expensive to make
and easiest to install and maintain.
Baffle trays:
For a baffle tray column the gas flows upwards through the baffle openings and
in doing so contacts the liquid showering down from one baffle to the next.
Baffle tray columns have almost same flooding capacity as cross flow trays.
Types of baffles used are disc & donut and segmental baffles for various column
diameters.
Dual flow and baffle trays are used for fouling applications, solid / slurry
handling services, corrosive services.
Sr. Bubble-Cap
Factors Sieve Tray Valve Tray Tray Dual-Flow Tray
No.
Moderately
1 Capacity High High High Very High
Moderately
2 Efficiency High High High Least
Pressure
5 Drop Moderate Moderate High Low to Moderate
~ 2-3 times of
~1.2 times sieve
6 Cost Low Least
sieve trays trays
Low to
7 Maintenance Low Relatively High Low
Moderate
High: Tends to
Fouling Low to collect
8 Low Extremely Low
Tendency Moderate Solids
Effects of Low to
9 Low High Very Low
Corrosion moderate
Some information
Proprietary,
Design Available.Instability
10 Well Known but readily Well Known
information can occur in large
available
dia. (>8 feet)
Extremely low
Liquid
Often used Where high Capacity revamps,
Main flow & Where
11 when turndown Highly fouling and
turndown is
Application leakage must be
is not
critical required corrosive services
minimized
Tray Parameters
Tray spacing is the distance between two trays. Generally tray spacing ranges
from 8 to 36 inches (200 mm to 900 mm). Prime factor in setting tray spacing is
the economic trade-off between column height and column diameter. Most
columns have 600 mm tray spacing. Cryogenic columns have tray spacing of
200-300 mm.
An outlet weir maintains a desired liquid level on the tray. As the liquid leaves
the contacting area of the tray, it flows over the tray weir to enter into the
downcomer.
This is the vertical distance between the tray floor and the bottom edge of the
downcomer apron. The Normalpractice is to use a downcomer clearance of 1/2
inch less than the overflow weir height to provide a static liquid seal
Inlet weirs and recessed seal pans are primarily used for achieving a
downcomer seal in cases where a potential positive sealing problem exists and
clearance under downcomer is limited
f) Downcomers:
Passage of liquid from the top tray to the bottom of tray occurs via
downcomers. Downcomers are conduits having circular, segmental, or
rectangular cross sections that convey liquid from upper tray to a lower tray in
a distillation column.
Flow path length is the distance between the inlet downcomer & outlet
downcomer. The minimum limit for flow path length is 400 mm in order to
provide good contacting between vapour and liquid. This is also necessary for
the mechanical reason of providing tray manway.
Centre to centre distance between holes is called pitch. Normal practice is to use
a hole pitch to hole diameter ratio between 2.2 to 3.8.
Derating factors are often closely related to the foaming tendency of the system.
Higher the foaming tendency, the lower is the Derating factor. System factors
are used in three of the rating correlations (jet flood, down comer backup flood,
down comer choke) to account for system effects on hydraulic capacity limits. It
includes both foaming effects and high vapour density.
Bubbling area is the column area, which is actually available for vapour
bubbling through liquid. It can be defined as column area minus downcomer
areas, downcomer seal & large calming zones.
This is the ratio of hole area to bubbling area. The default practice is to target a
hole area of 8 to 10 % of bubbling area for pressure services. The acceptable
range for percentage hole area is 5 % to 15 %. However for some critical
services, we can go % hole area up to 17-17.5% provided that weeping is under
control. Hole areas below 5 % are not used.
Anti jump baffles plates suspended vertically above centre or off centre
downcomers, which stops liquid jumping from one deck onto the opposite deck,
flow path
a) Flood:
Jet Flood:
Occurs when the pressure available for a given height of liquid and froth in the
downcomer cannot overcome the total pressure drop across the tray This
pressure imbalance causes the froth in the downcomer to start backing-up until
it reaches the tray above, causing an increased accumulation of liquid on it. It
requires high liquid and vapour loads.
The mechanism by which this type of flooding occurs is one related to frictional
pressure losses in the downcomer becoming excessive. In addition, the vapour
carried into the downcomer must separate from the liquid and then flow
counter-current to the liquid entering the downcomer. When the combination
of vapour exiting and the liquid entering becomes excessive, the downcomer
entrance is choked causing the liquid to backup on the tray. It requires relatively
high liquid rates, surpassing a velocity limitation on the downcomer.
b) Weeping/Dumping
The pressure exerted by the vapour is insufficient to hold up the liquid on the
tray. Therefore, liquid starts to leak through perforations.
Turndown ratio defines the range of vapour load between which the column
can operate without substantially affecting its’ primary separation objective (i.e.
fractionation efficiency) or over which acceptable tray performance is achieved.
The tray efficiency stays at or above the design value throughout the turndown
range.
Tray Sizing
ii) Above every feed, product drawoff, or point of heat addition or removal.
iii) Below every feed, product drawoff, or point of heat addition or removal.
v) At any point in the column where the calculated vapour or liquid loading
peaks
The sizing is done at all above load points and also detailed sizing is checked at
all above load points. All design parameters given in the design procedure
below are calculated at all above load points at turndown and turn-up loads so
that the feasibility of design for varied loads is tested.
Nomograph Method
C-Factor Method:
The following calculations are done at all the loading points mentioned above
and diameters are found separately. If the difference in calculated diameter at
different sections exceeds 20 percent, different diameters for the sections are
likely to be economical. The section having different diameter should be at least
20ft in length else same diameter can be maintained.
hct = Clear Liquid height at the transition from the froth to spray regime, in of
liquid.
Assumption: The starting values for these can be dH=1/4″, S=24″, h ct=2″
This is the velocity of upward vapour at which liquid droplets are suspended.
Calculate Flood Velocity (uN) using following equation:
iii. Net Area Calculation
The net area represents smallest area available for vapour flow in the inter-tray
spacing. Calculate Net Area (AN) from the flood velocity using following
equation: Assume the column is to be designed for 80% of flood.
Value of VCL obtained from table below. No derating factor is required for this
calculation, as VCL values have taken care of foaming
Downcomer Layout:
The total tower cross-section area AT less the area at the top of the downcomer
(sometime refer to as free area, the term free area.)
The net area represents the smallest area available for vapour flow in the inter-
tray spacing.
AN = AT – AD
The total cross-section area AT less the area at the inlet & outlet downcomer is
called as bubbling area.
AB = AT – ADT – ADB
? = sin-1(h/R)
?/2 = ?/2 – ?
Where,
Fractional weir blockage is the fraction of total weir length that is available for
liquid flow by using picket and fence type of weir. Blocked (Picket fence) weirs
are used for handling low liquid loading.
Down-comer area
AD = ASECT– ATRI
The side downcomer area can be calculated as that for single pass tray. It should
be noted that side down-comers are on both sides.
? = 2*(?/2- ?)
In case of more than two pass trays we have to define one more parameter, i.e.
off-center downcomer location from centerline. This needs to be done on a case-
by-case basis.
ForSinglePassTray:
FPL= (tray diameter) minus (side DC width of the tray) minus (bottom width of
DC of tray above)
Where,
C) Detailed Design
Flooding Check:
– It was derived from a much wider database of commercial and pilot-scale
column data.
– It can predict sieve and valve tray entrainment flooding within ± 15 and ±
20 percent respectively.
Fractional Hole
12 Area 0.06-0.20
ii. Clear Liquid height at the transition from the froth to spray ((hct)
The Fair correlation has been standard of the industry for entrainment flood
prediction. Fair’s correlation tends to be conservative, especially at high
pressure and liquid rate.
3 Hole size
Hole£ ½ in (sieve tray)
4. Hydraulic checks
– Entrainment
Froth Regime
This is the most commonly encountered flow regime in operating columns. The
froth formed under this regime is described as one where the size and shape of
bubbles is non-uniform and with rather large size distribution, as well as
travelling at varying velocities. The liquid surface is either wavy or it presents
oscillations. This is a liquid continuous flow regime.
Spray Regime
This regimes occurs at relatively high vapour velocities (i.e. large vapour flow
rates) and low liquid loads, characteristics which are typical of vacuum systems.
The vapour velocity is so large, that the liquid phase is completely disrupted and
is no longer a continuous phase on top of the tray; liquid is a dispersed phase
present only in the form of drops, and therefore the continuous phase is the
vapour.
Emulsion Regime
The determination of regime on tray given below is only for information and
has no use in sizing.
If the value of actual flow parameter exceeds 0.0208 then the regime of
operation is emulsion.
Where,
p – pitch in inches
5. Entrainment:
If entrainment is excessive, column diameter or tray spacing are usually
increased. As recommended value, the entrainment from the tray should not
exceed about 0.10 lb liquid entrained per pound of liquid flow.
This method holds good for froth and emulsion regime. However it is less
accurate for spray regime. For a trays operating at a high liquid to vapour ratio,
0.1 lb of liquid entrained per pound of liquid is an excessive quantity of
entrained liquid.
Contact Us Now.
trilliumflow.com
OPEN
. . . . . . . (1)
N = Number of trays in the column
? = Murphie Plate efficiency
a = Relative volatility (light to heavy)
S = Separation Factor
D = Distillate
B = Bottoms
LK = Light Key
HK = Heavy Key
x = Concentration, mole fraction
P = Column pressure in ATM
K = Reflux ratio R/RM
If equation (1) shows the column may benefit from more trays, you can run
several cases with reflux as the variable (heat load changes) and determine
the saving in energy.
You have the option of adding more trays or replacing existing trays with
more efficient type trays.
Contact Us Now.
trilliumflow.com
OPEN
A computer program has been developed to calculate the effective liquid
heating and vapor cooling duties as functions of temperature throughout a
simulated distillation column. The heating and cooling curves for the base
case Demethaniercolunm from Figure 1 have been calculated using this
program, and the results are shown in Figure 3. About 170 MMBtu/hr are
transferred in this column, reboiler, and condenser as the liquid is heated
to 54OF while the vapor is cooled to -139?F.
For maximum energy and capital efficiency, the heating and cooling curves
should be approximately parallel but slightly closer at lower temperatures.
In Figure 3, the heating and cooling curves approach each other near the
bottom of the column at 40OF where methane is almost completely
separated from ethylene. Below this point heat is exchanged primarily
between ethylene and propylene in the vapor and liquid streams. The
heating and cooling curves also approach each other just above the bottom
feed at -20OF, just above the middle feed at -94OF, and just below the
condenser at -135OF. This column is well designed to optimize the thermal
efficiency given the limitations of three feeds, a single interexchanger, and
45 theoretical stages. Figure 4 shows the liquid mole percents of methane,
ethylene, ethane, and propylene throughout the column as functions of
temperature. This figure emphasizes the separation between methane and
ethylene taking place with propylene entering the column with the middle
and bottom feeds at -94OF and -20OF. At the very bottom of the column,
propylene is condensed by vaporizing ethylene. This occurs because some
propylene is vaporized in the reboiler along with the methane and
ethylene, and it must then be condensed further up the column. The same
phenomenon occurs at -40OF just above the bottom feed, and contributes to
the thermodynamic inefficiency of the process design.
June 8th, 2012 in Design Distillation System, Distillation Technology,
Operations of Distillation System
Optimization of Distillation System Operations
http://seperationtechnology.com/optimization-of-distillation-system-operations/
aquarius-prolife.com
OPEN
Your operating procedures were probably written before the large increase
in energy cost drew attention to energy conservation as one primary
objective. In addition, the operators are probably using the procedures only
as a guide and have developed their own procedures based upon ease of
operation.
The optimization of the reflux ratio of the distillation column can produce
significant energy savings. The investigation can start by checking the
operating manual and column performance specifications for the design
conditions, including the reflux ratio. If the design conditions are no longer
valid due to changes in feed composition or product requirements, it is
recommended that a vigorous distillation calculation be made. If the
calculations are very difficult, you can make use of commercial computer
programs made available through various computing service bureaus. The
design reflux should be compared with the actual ratios controlled by each
shift operator. The daily laboratory analyses of the column products are
compiled and compared with the design specifications. If the column is
operated at a reduced production rate, the design reflux rate should be
calculated for this reduced rate.
It is extremely difficult to change people, even more difficult when it
requires more work effort without visually seeing the results. If one
operator was found who operated the column at a lower reflux ratio than
the others, you might get the confidence of the operators by getting all the
operators to maintain this ratio. If you merely write a note in the unit’s
operating log leaving instructions, you will probably not be successful in
lowering the reflux ratio. You must work closely with the superintendent,
foremen, and operators instilling confidence as you show the energy
savings resulting from their efforts. If the operating department has
monthly meetings for the supervisory people, you can use it as a forum to
present your objectives, how you plan to approach them, and request their
support and assistance. Later you can report progress and discuss problem
areas.
Steam or fuel usage per pound of product can be tabulated daily along with
reflux ratio, product purity, etc. and compared with column performance
before the change. The savings in energy can be converted to a monetary
value and reported to the operating people. As an alternate you might
represent the energy savings as barrels of imported oil per year.
If the product from the column is feed to another unit in the plant, then the
effect of lowering the purity on the other unit must be determined. Thus,
the energy conservation project requires the additional collection and
tabulation of operating data. A statistical approach may be required to fully
interpret the results of changes due to the variability of the processes by
changes in other parameters.
One of the most talked about energy wasters is steam leakage from “bad”
steam traps and leaking fittings. Steam traps are blamed for being
inefficient or worn out and causing as much as 10% of the generated heat
from steam to be lost. Is this true or just a sales method to sell more traps?
It turns out that steam leaks cause a significant energy loss.
Mr. Goyette, in his article “Estimating the Costs of Steam Leaks”, (see
appendix 7-C) shows the cost effect of steam leakage from various size holes
(1/8″, 1/16″, and 1/32″) in a 150 psig steam system. The cost was based upon
incremented steam costs. An example showed that a 1-inch union was
found leaking at a loss of $3000 per year. The repair cost was $50 or a six
day payout. Of all the energy savings steps that the Tenneco plant did, Mr
Goyette said the single largest contributor was steam-leak repairs. Steam
traps will wear out. Armstrong Machine Works claim that the inexpensive
disk type steam trap wears out in 6 months and should be replaced that
frequently. If condensate is recovered, leaking traps can cause an excessive
return temperature and cause failure of the condensate return pumps.
Severe water hammer can occur as hot steam contacts condensate that has
cooled below the temperature of the steam. The following steps are
recommended for saving energy in your steam condensate distribution
system and starting an effective steam energy management program:
Develop an estimate of the cost of steam leaks based upon your plant
costs similar to the Goyette article described above. A method for
demonstrating visually to plant people what these losses are can be
made.
Run a survey, recording all leaks, size, cost, and location.
Check the operation of all installed disc traps used for drips and steam
tracing. If found leaking, consider replacing with a more efficient type
trap. Before replacing, check installation design and confirm trap size
(not over or undersized).
Check installation and operation of steam traps used on equipment
using the sound detection method, the pyrometer method, or the glove
method. The installation should be checked for proper trapping. Items
checked include strainer, check valve, back pressure, orifice, and inert
gas venting. Improper venting can cause a severe reduction in heat
transfer rate.
Check vent valves on steam jacketed equipment and kettles for proper
operation (removal of inerts without steam loss).
while the gas moves upward, usually passes through the mist extractor to
remove small droplet of entrained liquid, and then the vapour phase flows
out of vessel.
2. Vane Packs
or Swirl Decks.
3. Mutilcyclone
4. Filter Separators
5. Cyclones
There are separator where inlet diverter is can also be used(As Per GPSA).
micron.
Size Range is 150 to 300
For Flare Knock Out Drum
Where,
? = Viscosity ,cP.
Where,
After calculating
value of C'(Re)2 value of C’ (Drag Coefficient) can be
obtained from the below graph.
The Vessel diameter calculated shall also satisfy the following Criteria:
If Liquid De -Gassing is Required:
Where,
Flow Rate , m3/sec.
Q = Liquid
? = Dynamic Viscocity , Kg/ms.
trilliumflow.com
OPEN
Less investment
Less investment cost in the column system is the main advantage of the
dividing wall column design. Figure 5 shows the current configuration of
the extractive distillation section with three columns: the Main Washer, the
Rectifier, and the Afterwasher. Figure 6 shows the same system using the
dividing wall configuration that combines the Rectifier and Afterwasher
into one column. The result is one less column, and elimination of one pair
of pumps used to pump the Afterwasher bottoms to the Rectifier in the
conventional scheme.
Figure 7 shows the conventional scheme for the distillation section of the
butadiene plant. The first column is used to separate propyne from the 1,3
butadiene, while the second column separates the 1,2 butadiene and
heavier compounds from 1,3 butadiene. Using a dividing wall column, these
two column systems can be combined into one column system shown in
Figure 8, resulting in a significant reduction in piece count and investment
cost. The equipment eliminated is one column, one overhead system
(condenser, drum and pumps), and one reboiler. The total reduction is six
pieces of equipment.
The above two systems combined result in nine less pieces of equipment.
Since a typical butadiene unit contains 90 to 100 pieces, this piece count
reduction gives an overall savings of about ten percent in engineering costs
and five to eight percent in equipment and commodities costs. Construction
costs will also be reduced correspondingly resulting in an overall
investment savings of five to eight percent.
Since nine pieces of equipment are eliminated using the dividing wall
column technology, there is also a savings in maintenance costs associated
with the plant. In particular, two pump services (four pumps) are
eliminated. This reduces the costs associated with maintaining these pumps
(seal repairs, etc.).
The other disadvantages are associated with the dividing wall column
application in the distillation section. These are higher pressure drop and
higher temperature difference from top to bottom resulting from a single
operating pressure in the column. The operating pressure is set by the
temperature of the condensing medium which is usually cooling water.
Therefore, the top pressure for the dividing wall column is about the same
as the top pressure for each of the conventional columns. Since the dividing
wall column has more trays than each of the separate columns, the
pressure drop is higher than either of the conventional columns.
Conclusion
With the ability to optimize dividing wall column designs, BASF has
developed the new butadiene process with dividing wall column
technology that saves on energy consumption and investment cost. This
makes the best technology for butadiene extraction available today even
better.
Your plant engineering files should contain all the design information for
the process. If it is not available, this information should be requested from
the original design company. In particular, process flow sheets, design
calculations, piping and instrumentation drawings, specifications of the
equipment purchased, performance characteristics of the equipment,
utility usage tabulations, and revisions since the original installation are
very valuable for the analysis. Examples of process flow sheets are found in
Figures 2-1 and 2-2.
Design values for fuel, steam, and electrical usage should be found on the
utility summary forms. Calculated values for specific operating conditions
should be in the process calculations. Values for fuel and steam usage
should be indicated on the process flow sheet. For example, if the design
values showed 30,000 lbs per hr. of 75 psig saturated steam to produce 6000
lbs per hr of product, the ratio of the pounds of 75 psig saturated steam to
pounds of product is 5. If the condensate is not recovered, the energy usage
is (1185 – 48)5 or 5685 Btu per lb. If a competitor operated with the same
ratio of steam to product, but recovered the condensate at 200º F, his
energy usage is (1185 – 188)5 = 4985 Btu per lb. This is an energy saving of
12%.
A heat and material balance can be made of the existing operation after the
plant instrumentation has been corrected. This information will be
compared with the original design balance and other energy figures found.
When developing a heat and material balance for the existing operation,
you may have insufficient information recorded on daily operating and
laboratory logs to compile the balance. Since distillation units are generally
well instrumented, the only expense burdens for a plant data collection test
are the manpower to collect the data and laboratory charges to perform the
analyses on the special samples. Of course, if one flow meter measures
steam usage to two different units, an additional meter must be added to
separate the units.
After all instruments are checked, you can take one data set of readings,
noting time to make readings, and problems in collecting readings or
samples. A heat and material balance can be calculated and inconsistencies
noted. For example, in making an energy balance across an exchanger, the
heat transferred to the colder stream is found higher than the cold stream.
An incorrect temperature reading or flow rate may be the reason. When
this “dry run” is completed and changes made, the plant test and evaluation
are performed.
A data collection run for the electrical usage is determined by reading
amperage loads on each motor and reading the wattmeter for the unit over
the test period. Electric motors connected to instrument air and plant
air compressors should be included in the energy audit.
May 1st, 2012 in Operations of Distillation System
LOW TEMPERATURE SEPARATION
http://seperationtechnology.com/low-temperature-separation/
The level of temperature fall relies on the quantity of stress fall and the
improve in quantity. This concept is used in LTS to get the elimination of
regular water from Organic Gas.
This procedure information protects only one LTS device. Based on the
variety of regular water wells and quantity of gas to be prepared, the
overall flower will involve several models (or trains).
INLET MANIFOLDS
(Figure: 18)
Each generating well is piped to the inlt shut-down numerous where it goes
through a shut-down device (SDV) which is managed by the automated
urgent shut-down program. Each SDV has a start-up avoid and crammed.
From the shut-down device, the well flow-lines complete to the inlt
numerous where each range is fixed with a circulation factor to gauge the
gas circulation rate. The gas then goes to the flower via a crammed device.
At the inlt numerous the regular water wells can be redirected to the ‘Flow
Splitter’ boat V.1 as managing circumstances require.
This boat is rounded and provides to individual well liquids from the gas
flow. The main objective of the splitter is to redirect all or part of a well
flow fluid circulation from its regular practice to one or more teaches, by
managing a sequence of valves at the inlt numerous as development needs.
The above plan is displaying only one inlt flowline, the other basins are
similar and all may supply the circulation splitter or go straight to one of
the LTS teaches.
Figure: 19
The stress and temperature figures and devices recognition figures used in
this description are simply illustrations and not actually real procedure
information.
The fluid circulation from the inlt numerous and/or the circulation splitter
goes to a well-stream chilly at about 1700 Psi and up to 240 °F. In the
flowline to the chilly, a shut-down device – SDV – is set up which ends on
initial of the shut-down program.
The well-stream chilly is an Air-fin type having two lovers. The store
temperature of the chilly is instantly managed by a Heat range Operator
(TIC) which adapts the message of the fan knives to sustain an store of
about 130 °F. During freezing, cold climate, it may be necessary to closed
down one fan to sustain the needed temperature.
The fluid circulation from the chilly is piped to the Advanced Separator (KO
Drum V.2). (Fig: 20).
This is a rounded 3-phase separator boat with a base fluid start. However,
hydrocarbon condensate is re-entrained in the store gas by a ‘Stinger’
procedure which ‘sucks’ the gas condensate out with the gas.
The regular water stage is piped away from the start to the strain headlines
managed by a Stage Operator (LIC) which functions a Stage Management
Valve (LICV) in the strain range. The regular water which is thrown out to
the strain headlines is metered and documented.
Since it is likely that fluid ‘slugs’ will get into the flower from the regular
water wells, V.2 will provide to capture these slugs and reduce the problem
of procedure problems in downstream devices.
The wet gas and condensate keep the top of the boat and complete to the
pipe part of a gas/gas exchanger (# 1) at about 130 °F and is chilled by
freezing dry gas from the LTS to about 95 °F. In the range to the exchanger,
a SDV is set up to release liquids to width on initial of the shut-down
program.
The chilled, wet gas goes into the Choke Knock-out boat V.3.
courses for
Coursa
free
Open
For lean-phase problems, the solution is trivial. The student only needs to
draw a straight operating line from the known conditions at the top of the
column (xa,ya) which just touches the equilibrium line. If the equilibrium
line is also straight (eg. Henry’s law y= mx) then this will occur at end b of
the column where Lb leaves in equilibrium with the entering gas Vb at the
point xb=yb/m (Figure 2a).
However, for rich phase systems (concentrations greater than 10%) the
operating line has significant curvature because the ratio of L to V varies
down the length of the column. In this case, assuming the required
operating line passes through the point (yb/m, yb) may not always be
correct. If the operating line is concave up then it is possible that the
operating line may cut the equilibrium line at some point between ya and
yb (Figure 2c), and so the operating line through (yb/m, yb) gives too low an
estimate of La,min. What is more, the student only becomes aware of this
error if they take the time to plot the operating line for the minimum liquid
flowrate case, whereas they often without checking go on to solve the main
part of the question which involves calculating the number of stages
required when La is some multiple of La,min.
In this case where the operating line is concave up (or concave down for
stripping problems), to find the operating line which just touches the
equilibrium line the students must either adopt a lengthy trial and error
approach, or else they must solve the problem graphically [2,3] by first
converting the problem into mole (or mass) ratios, X and Y, where X = x/(1-
x) is the moles of solute per mole inert carrier fluid and Y = y/(1-y) is the
moles of solute per mole of inert carrier vapour (0 < X,Y < ¥). When mole
ratios are used, the liquid and vapour flow rates are given as =(1-xa)La and
=(1-y)Va, the moles of solute-free liquid and vapour flow respectively. For
mutually insoluble solute streams, and remain constant, and so the
operating line is a straight line given by the equation:
Once the equilibrium data has also been converted into mole ratios and
plotted, the minimum condition can easily be found graphically using a
ruler to find the straight line starting at (Xa, Ya ) which touches the
equilibrium line. The slope of this line is , from which La,min can be
calculated.
This paper presents a new analytical approach for finding the minimum
liquid flowrate in rich phase problems which does not require converting
the problem into mole ratios. The new method requires that an analytical
expression for the equilibrium line be known and that this remains
constant through the length of the column ie. the column must be operating
isothermally. This method involves re-arranging equation (1) into an
explicit expression for y in terms of x and solving to find the point at which
it just touches the equilibrium line. This analytical method can be taught to
students to complement the traditional graphical approach.
Since the flow of inert carrier fluid remains constant for mutually insoluble
streams, (1-x)L = (1-xa)La. Therefore:
Equation (6) can also be differentiated to give the equation for the slope of
the operating line at any point:
La,min occurs when the operating line and equilibrium line touch at a single
point between ya and yb. This intersection point can be found analytically
and is given by (see Appendix A):
Step 1. Begin by assuming that the pinch point where the operating line just
touches the equilibrium line is at the base of the column. Therefore xb =
yb/m and La is found by an overall material balance around the column:
Step 3a. If the slope of the operating line at xb = yb/m is less than the slope of
the equilibrium line (i.e. dy/dx < m). This indicates that the operating line
has crossed the equilibrium line from above, as shown in Figure 2b, so the
La found in Step 2 is the correct La,min.
Step 3b. If the slope of the operating line is greater than the slope of the
equilibrium line (i.e. dy/dx > m), then this indicates that the operating line
is intersecting the equilibrium line from below, as shown in Figure 2c. In
this case equation (8) is then be used to find the correct minimum liquid
flowrate.
For stripping problems, the operating line lies below the equilibrium line
and the full conditions are known at end b, but not end a. The aim is to find
Vb,min and the requirements for the slope of the operating line at the point
of intersection are reversed. The solution procedures for both absorption
and stripping problems are summarised in Table 1. A worked example
problem illustrating both this solution procedure and the traditional
approach is given in Appendix B.
The above solution procedure can be easily adjusted to consider other
analytical expressions for the equilibrium line, y* = f(x). If the equilibrium
line is given by equilibrium data which does not readily fit any simple
analytical expression, then the student has no choice but to convert the
problem into mole ratios and solve graphically.
Discussion
The new method proposed is fully analytical. However, the intuitive
understanding behind the derivation which students need to appreciate is
based on a graphical understanding of the problem. Hence, it cannot
replace the traditional graphical approach using solute-free coordinates. It
is, however, complimentary and provides students with a different set of
tools for tackling such problems. In addition, the derivation of this method
serves to remind students that the basic tools of analytical geometry they
learnt at school can be applied to apparently unrelated engineering
problems.
Equation (6) is not only useful for finding the point at which the operating
line touches the equilibrium line. It can also be used to help plot the curved
operating lines that occur in any rich-phase problem. This is required in
order to be able to step off the number of stages via the McCabe-Thiele
method, or to perform the numerical integration required to find the
number of transfer units in a packed column.
Even if the full analytical method is not used, the equation for the slope of
the operating line, equation (7), is valuable because it enables students to
test whether the end point (yb, yb/m) is the correct pinch point without
having to plot the full operating line.
Equations (8) and (9) are also potentially useful for software packages for
computer based learning packages where each student in a class can be
given different computer generated problems to solve independently and
then enter their answers into the computer for checking.
Conclusion
Explicit equations for the operating line and its slope in rich-phase gas
absorption and stripping problems have been derived with x as the only
variable. These expressions, although trivial to derive, are not presented in
any of the standard introductory texts on separation processes. They have
been used to develop a new analytical method for finding the minimum
liquid flowrate in rich-phase problems without needing to convert the
problem into solute-free coordinates and then use graphical methods.
Contact Us Now.
trilliumflow.com
OPEN
Producing High purity BTX components (benzene, toluene and xylenes) are
important building blocks in many chemical processes. In particular,
considerable quantities of benzene and paraxylene are used in the
production of major petrochemical intermediates for the polymer industry.
Naphtha cracking produces light olefins for polymer applications, but also
produces pyrolysis gasoline (pygas), which is rich in aromatic compounds
and a significant source of BTX. Pygas has been a component in the gasoline
pool, but is increasingly used for its higher petrochemical value. This
requires the separation of BTX components, via extraction, from aliphatic
compounds and C9+ aromatics for producing high purity BTX.
increases. Also, due to aromatics limitations in the gasoline pool, the high
value of ethylene, propylene and high purity BTX intermediates, the idea of
converting C7+ pygas to these highly desired components is an attractive
option.
Cuts originating from 2nd Stage Pygas Hydrogenation units are employed
as feedstocks. The principal catalytic reactions are:
o Conversion of non-aromatics (especially C6 to C8
alkanes) into ethane and
LPG.
The high activity and selectivity of the catalyst used in this application,
APU-11, provide a number of significant benefits:
o Production of a pure benzene cut
o Co-production of LPG
o Potential to increase ethylene and propylene by recycling ethane and LPG
to the steam cracker furnaces
feedstock, and the xylenes fraction does not require further extraction
before separation to recover paraxylene.
In some locations, ethane and LPG are the desired products; in others they
provide cracking furnace feedstocks. Typical olefin yields based on the
original pygas feed are 12.5% are 3.2% for C2= and C3=, respectively.
o Converting low value pygas, especially the C9+ fraction often sent to fuel
oil, into BTX, C2 and LPG
o Increasing C2= and C3=
production by recycling C2-C4 paraffins to the
cracking furnaces The following slides and illustrations present a more
detailed review of the process and economic advantages of APU.
Introduction
The Olefinas capacity of 250 000 TPA of Ethylene from feed ethane and
propane. To achieve this capacity, a two column C2 Splitter 110El/110E2 was
installed, to handle 37% of plant load.
The old unit 107E was retrayed to handle 63% of the plant load. Column
overhead gas at 16.8 barg is fed to a heat pump compressor, and retumed at
higher pressure of 35 barg to supply heat for reboiling. A sketch of this
system appears below ( Fig. 1 ).
The problem of high pressure drop across C2 Splitter 107E:
The Olefinas I Plant has built in flexibility for handling ethane and propane
feeds, but historically had problems in operating at design load.
The expected loads to 107E for the three design cases are tabulated in Table
1.
Historically, at high load there were frequent increases in pressure
differential across the column. Often, this was related to hydrate formation,
which was handled by decreasing the load and injecting Methanol into the
column. Dehydrator regeneration was improved; but incidents of
increasing pressure drop in 107E continued.
AspenPlus was used for simulating this column for better understanding
the system. AspenPlus predicted a Flood Factor of 0.89 for the Typical Feed
Case and 0.99 at the highest design load, corresponding to the Mixed Feed
Case. This raised doubts of the adequacy of design of this system. The
process licensor was contacted to obtain an explanation. When it was
confirmed that the design was adequate, a systematic check was carried out
to establish the cause for the high pressure drop.
A scan at low load was carried out to confirm that all the trays were in
place. The reflux was increased to flow-rates that were often problematic,
and another scan carried out which confirmed that there was no alarming
abnormality. Simulation of the column during this scan provided a valuable
insight on how to use AspenPlus effectively.
A scan at high load was planned and carried out, just prior to a plant
turnaround. This achieved stable operation for a short period of time,
which confirmed that there was no abnormality in the column. It was
recommended that the trays in the bottom section of the column be checked
out during the plant turnaround.
Armed with the valuable insights gained during the scan, and with a
validated simulation, the operation of this system was critically reviewed.
For two defined design cases, the feed was to be introduced at tray 64 or at
tray 74. Since there were frequent variations in feed availability to the
plant, and since actual operation was inbetween design cases, the feed
location was being maintained at tray 74. It was shown that by maintaining
reflux to feed ratio above 3.0, feed could always be introduced at tray 64.
Loss of ethylene to column bottom stream was reduced, due to this
simplified operation.
During the plant turnaround in March 1997, the column 107E was opened
for inspection. Here was some dirt in the bottom section, between trays 81
and 85 which reduced the active area by around 5 percent. These were
cleaned; there was no other abnormality in the column. Whenth e columnw
as again in operation, close to the typical feed case, it was loaded to around
110 percent of the feed estimated for this case. The system operated stably,
and has since operated at higher than design capacity on many occasions.
Actual operation of the column was simulated using AspenPlus (see Table 2,
below).
It was seen that the pressure drop predicted by simulation was always less
than the actual pressure drop. Also, the flood factor predicted was always
high; but from the experience of previous evaluations, it was knownth at
this was not a matter of concern.
While this troubleshooting was carried out over a long time span, there
were well defined gains:
1. The problem of high pressure drop across 107E was due to hydrate
formation. With improved operation, these incidents have been all but
eliminated.
2. The plant has a nameplate capacity of 250 000 TPA, or 750 T/day.
Previously, production was limited to 80% of this capacity, because of some
other problems and suspected C2 splitter column design inadequacy. Now,
the same column operates at higher than design expectation, and the plant
has operated on several occasions to produce more than 800 T/day,
reaching 850 T/day on one occasion.
3. Scanning of columns in operation is a well known tool for
troubleshooting. This was effectively used for eliminating suspicions of
fallen or partially blocked trays.
Introduction
The old unit 107E was retrayed to handle 63% of the plant load. Column
overhead gas at 16.8 barg is fed to a heat pump compressor, and retumed at
higher pressure of 35 barg to supply heat for reboiling. A sketch of this
system appears below ( Fig. 1 ).
The Olefinas I Plant has built in flexibility for handling ethane and propane
feeds, but historically had problems in operating at design load.
The expected loads to 107E for the three design cases are tabulated in Table
1.
AspenPlus was used for simulating this column for better understanding
the system. AspenPlus predicted a Flood Factor of 0.89 for the Typical Feed
Case and 0.99 at the highest design load, corresponding to the Mixed Feed
Case. This raised doubts of the adequacy of design of this system. The
process licensor was contacted to obtain an explanation. Whenit was
confirmed that the design was adequate, a systematic check was carried out
to establish the cause for the high pressure drop.
Since the high pressure drop had been experienced for many years, a
partial blockage of some trays was suspected. It was decided to get the
column scanned by TRU-TEC. This involved scanning the column
throughout its length during stable operation, using a technique that has
been very effectively applied by TRU-TECA. radioactive source and a
detector are positioned outside the column, across the active area of the
trays in a column, and lowered simultaneously, in small steps. The detector
signal varies, depending on what is between the source and the detector.
This is recorded in a portable computer, and later printed out and
interpreted.
A scan at low load was carried out to confirm that all the trays were in
place. The reflux was increased to flow-rates that were often problematic,
and another scan carried out which confirmed that there was no alarming
abnormality. Simulation of the column during this scan provided a valuable
insight on how to use AspenPlus effectively.
A scan at high load was planned and carried out, just prior to a plant
turnaround. This achieved stable operation for a short period of time,
which confirmed that there was no abnormality in the column. It was
recommended that the trays in the bottom section of the column be checked
out during the plant tumaround.
Armed with the valuable insights gained during the scan, and with a
validated simulation, the operation of this system was critically reviewed.
For two defined design cases, the feed was to be introduced at tray 64 or at
tray 74. Since there were frequent variations in feed availability to the
plant, and since actual operation was inbetween design cases, the feed
location was being maintained at tray 74. It was shown that by maintaining
reflux to feed ratio above 3.0, feed could always be introduced at tray 64.
Loss of ethylene to column bottom stream was reduced, due to this
simplified operation.
During the plant turnaround in March 1997, the column 107E was opened
for inspection. Here was some dirt in the bottom section, between trays 81
and 85 which reduced the active area by around 5 percent. These were
cleaned; there was no other abnormality in the column. Whenth e columnw
as again in operation, close to the typical feed case, it was loaded to around
110 percent of the feed estimated for this case. The system operated stably,
and has since operated at higher than design capacity on many occasions.
Actual operation of the column was simulated using AspenPlus (see Table 2,
below).
It was seen that the pressure drop predicted by simulation was always less
than the actual pressure drop. Also, the flood factor predicted was always
high; but from the experience of previous evaluations, it was knownth at
this was not a matter of concern.
While this troubleshooting was carried out over a long time span, there
were well defined gains:
1. The problem of high pressure drop across 107E was due to hydrate
formation. With improved operation, these incidents have been all but
eliminated.
2. The plant has a nameplate capacity of 250 000 TPA, or 750 T/day.
Previously, production was limited to 80% of this capacity, because of some
other problems and suspected C2 splitter column design inadequacy. Now,
the same column operates at higher than design expectation, and the plant
has operated on several occasions to produce more than 800 T/day,
reaching 850 T/day on one occasion.
Split Tower –
The feed stream will be split so that the condenser duties of the high
pressure column approximately matches the required reboiler duty of the
low pressure column. (See Figure 4-3 for an example split tower
arrangement). The heat, input to the reboiler, of the high pressure column
rises to the condenser where it then provides the reboiling duty of the other
column. By use of the split tower arrangement, we have cut our energy use
almost in half. Note that instead of two columns, any number of columns
can be used in the split tower fashion. However, For each additional tower,
an extra delta T must be supplied, plus the temperature drop across the
column. In addition, the energy savings drops as each column is added. The
two tower system saves 50% of the energy. Another tower saves (50 – 33) or
only 17%. A fourth tower will save only 8.3%. So our write up will deal with
only the two column arrangement.
The split tower system has a single reboiler and single condenser. The
temperature difference between the reboiler and condenser will be much
greater than that of an ordinary column. This occurs because the two
columns each have their own temperature difference to be met from the
top to bottom, and the driving force for the condenser reboiler must be
supplied. As a result of this for the split tower arrangement to work, the
following factors must be present:
2. The pressure must not be so large as to require too heavy column walls.
3. The low pressure column must not be too low, so low a vacuum as to
cause trouble.
4. The products must not be degraded by the highest temperature or
frozen, or too viscous at the lowest temperature.
5. The heat source must be able to supply heat at a temperature above that
of the reboiler.
The feed to a single tower will be split in two for the two column
arrangement. Therefore, the individual columns will be about one-half the
size of the single column. However, the relative volatility and the mass
flowrate/area through the columns will change with the pressure, resulting
in a differently sized tower than just one-half the size.
In designing the split tower arrangement, the low pressure column should
be set by the achievable condenser temperature. Then the split tower
should be worked backwards from this point, a reasonable temperature
drive given for the condenser-reboiler, then the high pressure column
found, finally resulting in a temperature for the reboiler. With this
temperature the available heat sources should be examined, for example,
the various steam pressures, and one chosen. The delta T available should
then be distributed between the reboiler, condenser-reboiler, and
condenser to obtain the minimum required heat exchanger surface area.
The feed between the towers should be split in order to approximately give
equal duties for the high pressure condensation and low pressure reboiling
under design operating conditions.
The control of a split column will be more complex than that of a single
column. The object of the control system will be to decouple the two towers
to a certain extent. The use of an auxiliary condenser on the high pressure
column and a auxiliary reboiler on the low pressure column will give
energy efficiency and good control. Control can also be had by having only
one auxiliary exchanger, and by having one of the columns run at a higher
duty than the other. The feed split ratio between the columns can be used
as part of the control. Note that the bottoms of the high pressure tower can
be mixed with the low pressure bottoms and flashed in the low pressure
tower. This would result in a uniform bottoms composition.
The split tower design offers a good possibility of energy savings with a
new installation. Where an existing column exists already, it would be
possible to increase capacity by adding another tower next to the existing
one and installing a new condenser-reboiler so that the existing column
will become one-half of a split tower arrangement. In cases where no
capacity increase is desired, but the column original size was such that two
towers were used, it may be possible to convert it to a split tower operation
by installing a more efficient column internal trays and by adding a
condenser reboiler, new piping, and new instrumentation. The savings that
can result from a split tower design are very much affected by the cost of
energy to the reboiler, so the true energy cost should be evaluated before
using a split tower.
trilliumflow.com
OPEN
2. When the column can be operated with cooling water for the condenser
and waste heat (1 ATM or less steam) for the reboiler.
theGB4000.com
Thinking Of The BCX Ultra?
Free Shipping And Free Documentary
thegb4000.com
OPEN
1. A large amount of heat can be transferred with little work. For example,
suppose we had a heat/work ratio of 10. This means that for every Btu of
work added, we replace 10 Btu’s of heat that would otherwise be
required. This can lead to overall savings also. Assume we generate one
Btu of electricity from three Btu’s of fuel heat (33% efficiency). Then
overall we save 10/3 = 3.33 Btu of heat for every Btu fuel used by the
vapor re-compression system over that of the conventional system.
2. The heat flow to supply the condenser or reboiler may be of particular
value. For example if the column is cold, the cooling must be
accomplished by expensive refrigeration. This is also true at high
temperatures 500°F+ where energy added to the reboiler can no longer
be supplied simply by steam. The vapor re-compression cycle, by being
balanced, is affected only to a limited effect by the relation of the actual
temperature to the ambient. The pressure in a vapor re-compression
column can be set where desired to achieve maximum separation.
3. By freeing the condenser and reboiler of the desire to hold temperature
between a minimum of about 100°F to a maximum of about 500°F, the
points easily reached by cooling water and condensing steam, we can
set the temperature, and therefore the pressure, at any point we wish.
This effect is of particular importance where changing the pressure
effects the relative volatility. By operating at more favorable conditions
we can reduce the reflux requirement and therefore the heat duties. The
effect of the pressure change on the column will be to change the wall
thickness, and column diameter, the diameter falling as the reflux is
reduced, but increasing as the pressure drops. Do not neglect the effects
of pressure changes on the overall column.
4. Work energy from excess high pressure steam which is generated for
low pressure steam requirements may be available in the overall plant
balance. This energy would be very cheap if the alternative or current
practice is to wastefully let down the steam across a valve. A steam
turbine driver for the vapor compressor can be used, giving a low work
energy cost.
5. Electricity can be brought in from the outside to run the compressor
driver, so that large amounts of steam are not needed. Thus the steam
plant can be smaller.
6. The vapor re-compression system uses little cooling water or steam flow.
Possible utility savings can occur as less cooling water is discharged, and
the steam, condensate, and cooling water lines can be made smaller.
7. Swings in the ambient temperature and weather will have little effect on
the operation of vapor re-compression.
The fluid used (cooling water and steam) in the reboiler and
condenser will have a much higher heat transfer coefficient than the
column fluids.
The EX TD driving force for both the reboiler and condenser will be
much higher than that allowed across the condenser rebolier as its
heat/work efficiency drops with increasing T D across the system.
The EX TD across the condenser-reboiler causes a loss in efficiency,
therefore requiring a larger compressor, driver, and work input. The
EX TD will be minimized to allow a smaller compressor and driver.
These items add up to the fact that the exchanger surface required
for the condenser-reboiler will probably be significantly larger than
the combined surface on the condenser and reboiler in a
conventional column.
4. Auxiliary units such as extra reboilers, condensers will be required in
order to balance the heat duty and control the column.
5. The mechanical complexity of the vapor compressor is high, the system
requiring more maintenance and suffering more breakdowns.
6. More instrumentation will be required to control the compressor and
the other auxiliary items of the vapor re-compression system.
7. The control of the vapor re-compression system is different than that
faced in an ordinary column. New methods will have to be learned by
the operating personnel.
8. Flexibility is lost as the column has only limited ability to function at
other than design conditions. The compressor will be sized to be most
efficient at one operating rate. Increasing the column reflux over design
will be very hard.
9. Altering the column for reuse to operate for a new situation will be
more difficult than with a conventional column, as the vapor re-
compression system will probably need to be replaced.
10. Continuous auxiliary refrigeration may be required for a low pressure
column with vapor re-compression that would be run at higher
temperature by a conventional distillation system.
trilliumflow.com
OPEN
Application
3) Building the control model for an MVC application from that data,
As shown in figure 1, the feed entering the column is controlled with a flow
controller. Pressure control is used to remove any light hydrocarbons that
are present in the extract. The benzene product is withdrawn from the
distillation column as a sidedraw product. The benzene flow is set by a
control tray temperature controller, which resets the sidedraw flow
controller setpoint. The toluene and heavier aromatics exit the column as
the bottoms stream that is controlled with a bottoms sump level controller.
Reflux is controlled with a reflux drum level controller resetting a reflux
flow controller set point. The heat input, to the column, is controlled with a
reboiler steam flow controller. With this base level control scheme, the
column operator has three Manipulated Variables (MV’s) that he can set. He
sets the setpoint for the feed flow controller to match the extract production
from the liquid/liquid aromatics extractor. The temperature controller
setpoint is set to achieve the desired benzene recovery and the reboiler
steam flow controller setpoint is set to achieve the desired benzene product
purity.
This is a fairly simple system but it is a control challenge. Due to the fact
that it is a fairly easy separation (low cost) but with disparate values of the
two products, it is a high recovery as well as a high product purity
separation. This high purity of both major products means that this is a
highly non-linear system. This implies high process sensitivity, at the
constraints. The further one goes from the constraints, the lower the
sensitivity and therefore, the easier the control. With low energy penalty
for departure from constraints and easier control, it is easy for a human
operator to drift away from constraint. This is where the automatic control
opportunity lies.
This data was used to calculate process gains of toluene in the benzene
product to steam rate as a function of the benzene product composition in
figure 3. This figure shows the high process sensitivity at the higher
impurity levels and demonstrates that the process gain is very much
dependent on where the process is tested. Of course, the point at which the
model must have the highest degree of accuracy is at the constraints. From
figure 3, it should be clear that it would be difficult to conduct a practical
test at the constraints because of the high process sensitivity. The high non-
linearity implies that the test must be carried out in a very narrow band of
controlled variable (CV) values but with a real process, the test must impart
sufficient CV variation to extract the true process dynamics from the noisy
process data. Testing a dynamic simulation, with no noise, means that a
very small perturbance can be imparted and an accurate process gain
measured at the constraint.
The controller configuration file was built and the controller tuned. With
this procedure, there was a high degree of confidence in the process gains,
but a very low confidence in the process dynamics. Therefore, the
controller tuning was far less aggressive than normal.
To demonstrate the benefits, the service switch position is plotted with the
reflux to feed ratio for the past 3 years, as figure 6. The only manipulation
of the raw data was to remove the process unit downtime periods. For the
purpose of this figure, the reflux to feed ratio was normalized by dividing
the actual ratio by the maximum reflux to feed ratio for this period.