Performance Calculation Sheet Unit 5 25-02-2022

The document provides performance data for various units including an APH unit, three LPH units, two HPH units, and a condenser unit from a power plant. Key data points include temperatures at various points, pressure levels, temperature differences, gains, and effectiveness. The data shows values for both rated units 1-6 and 7-10 as well as actual measured data for some units.

Uploaded by

SHIBAM SINGH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
241 views7 pages

Performance Calculation Sheet Unit 5 25-02-2022

The document provides performance data for various units including an APH unit, three LPH units, two HPH units, and a condenser unit from a power plant. Key data points include temperatures at various points, pressure levels, temperature differences, gains, and effectiveness. The data shows values for both rated units 1-6 and 7-10 as well as actual measured data for some units.

Uploaded by

SHIBAM SINGH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

APH PERFORMANCE DATA

UNIT 5
DATE 2/25/2022 Time
GENERATION 103
CALCULATION
Description Units Rated(#1-6) Rated(#7-10)
Air leakage into APH system (%)-assumed AL 9 9
Temperature of the combustion air at inlet to APH (TAI) 0
C 35 35
Temperature of the combustion air at Outlet of APH (TAO) 0
C 280 273
Temperature of the flue gas at Outlet of APH (TGO) 0
C 130 119
Temperature of the Flue gas at Inlet of APH (TIN) 0
C 319 309

Corrected Flue gas Temperature out of APH (TGONI)


0
C 139 127
Effectiveness (Gas side efficiency) % 63.41 66.46

X-Ratio % 73.50 76.52


TGONI={AL X Cpa X (TGO – TAI)/(100 X Cpg)}+T GO

PUT DATA ONLY IN GREEN FIELDS


5
6:10 PM
MW

APH A APH B
15.00 15.00
36 25
251 247
122 148
303 301
135 167
62.75 48.46
77.93 60.25
O – TAI)/(100 X Cpg)}+T GO

IN GREEN FIELDS
LPH 1,2,3 PERFORMANCE DATA
UNIT 5
DATE 2/25/2022 Time 6:10 PM
GENERATION 103
Description Units Rated(#1-6) Rated(#7-10) LPH-1 LPH-2
Steam inlet pressure LPH-1/2/3  kg/cm2 0.37/0.80/2.3 0.3 0.8

Steam inlet sat temperature(Ts) LPH-1/2/3 o


C 73.53/92.96/124.06 68.64 92.96

Condensate inlet temperature(Ti) o


C 51/69.8/88.8 52 67

Condensate outlet temperature (To) LPH-


1/2/3
o
C 69.8/88.8/119.8 67 85

Drip temperature (Td) LPH-1/2/3 o


C 57/75.8/94.4 58 83

TTD of LPH-1/2/3(Ts-To) o
C 3.73/4.16/4.26 1.64 7.96

DCA of LPH-1/2/3 (Td-Ti) o


C 6.0/6.0/5.6 6 16

Condensate temperature gain LPH-1/2/3


(TR)=(To-Ti) 0C 18.8/19/31 15 18

ADD 1KSC TO GAUGE PRESSURE TO GET ABS PRESSURE


PUT DATA ONLY IN GREEN FIELDS
RATED VALUES ARE FOR 120 MW

COMMENTS: DRIP TEMP. OF LPH-03 IS SHOWING WRONG VALUE.(WR004587_19)


6:10 PM
MW
LPH-3
2.1

121.14

85

116

100

5.14

15

31
HPH 5 &6 PERFORMANCE DATA
UNIT 5
DATE 2/25/2022 Time 6:10 PM
GENERATION 103 MW
Description Units Rated(#1-6) Rated(#7-10) HPH-5 HPH-6
Steam inlet pressure HPH-5/6  kg/cm2 12.15/30.4 13.58/35.4 12.4 29.2

Steam inlet sat temperature(Ts) HPH-5/6 o


C 187.6/233.07 192.7/242.13 188.56 231.29

Feed water inlet temperature(Ti) o


C 152.4/187.6 150/190 146 171

Feed water outlet temperature (To) HPH-


5/6
o
C 187.6/233.5 190/240 171 202

Drip temperature (Td) HPH-5/6 o


C 158.4/193.6 167/204 150 180

TTD of HPH-5/6(Ts-To) o
C 0/-0.43 2.63/2.03 17.56 29.29

DCA of HPH-5/6 (Td-Ti) o


C 6.0/6.0 17/14 4 9

FW temperature gain HPH-5/6 (TR)=(To-Ti) 0


C 35.2/45.9 40/50 25 31

ADD 1KSC TO GAUGE PRESSURE TO GET ABS PRESSURE


PUT DATA ONLY IN GREEN FIELDS
RATED VALUES ARE FOR 120 MW
CONDENSER PERFORMANCE DATA
UNIT 5
DATE 2/25/2022 Time
GENERATION 103
Description Units Rated(#1-6) Rated(#7-10)
CW inlet temperature (Ti) o
C 34 36

CW outlet temperature(To) o
C 41 42.96

Condenser vacuum  kg/cm2 0.9127 0.9127

Condenser Pressure(absolute)  kg/cm2 0.1033 0.1033

Saturation temperature Ts (from steam table) o


C 46.1 46.1

Hot well temperature(at inlet of running CEP) o


C 45.1 45.1
Thw

Ejector suction air temperature Tej o


C >41 >41

ΔT of Cooling water (To-Ti) o


C 7 6.96

Initial temperature difference (Ts-Ti) o


C 12.1 10.76

Terminal temperature difference(TTD) Ts-To o


C 5.1 3.8
Condensate sub cooling (Ts- Thw) o
C 1.0 1.0
Air offtake temperature (Ts-Tej) o
C 5.1 5.1

Condenser effectiveness (To-Ti)/(Ts-Ti) 0.58 0.64

PUT DATA ONLY IN GREEN FIELDS

RATED VALUES ARE FOR 120 MW


A
5
6:10 PM
MW
Condenser Performance
32

40

0.888

0.1280

50.32

46.6

43.6

18.32

10.32
3.72
6.72

0.44