Data Sheet: Tembreak 2 S1000-Se MCCB: Max in (A) of Frame
Data Sheet: Tembreak 2 S1000-Se MCCB: Max in (A) of Frame
MCCB Electrical Characteristics to IEC 60947-2, JIS C 8201-2-1 ANN 1, AS/NZS 3947-2, NEMA AB-1
Electrical characteristics
Rated operational voltage Ue (V) AC 50/60 Hz 690
DC -
Rated insulation voltage Ui (V) 800
Rated impulse withstand voltage U imp (kV) 8
Ultimate breaking capacity I cu (kA) 690V AC 20 1
(IEC, JIS, AS/NZS) 525V AC 30 1
440V AC 45
400/415V AC 50
220/240V AC 85
250V DC -
Service breaking capacity I cs (kA) 690V AC 15 1
(IEC, JIS, AS/NZS) 525V AC 23
440V AC 34
400/415V AC 38
220/240V AC 65
250V DC -
Rated breaking capacity (NEMA) (kA) 480V AC 30
240V AC 85
Rated short-time withstand current I cw (kA) 0.3 Seconds -
Protection
Adjustable thermal, adjustable magnetic
Fixed thermal, fixed magnetic
Microprocessor
Utilisation category A
Installation
Front connection (FC) -
Extension bar (FB)
Cable clamp (FW -
Rear connection (RC) •
Plug-in (PM) -
DIN rail mounting (DA) -
Dimensions height (mm) 273
width (mm) 3 pole 210
4 pole 280
depth (mm) 103
Weight weight (kg) 3 pole 11.0
4 pole 14.8
Operation
Direct Opening Action
Toggle operation
Door mounted ( HS ) / Breaker mounted handle (HB) •
Motor operation (MC) •
Endurance Electrical 690V AC
Mechanical cycles 4,000
cycles 10,000
Page 1 of 3
DATA SHEET: TEMBREAK 2 S1000-SE MCCB
Outline Dimensions S1000-SE
Front connected
Interpole barrier
(removable) Mounting hole
3P 3
4P 14 32 Drilling plan (front view)
HL ø1 HL
Toggle extension
13 (removable) 3P 4P
110
HL
80
HL
170 170
141
126
46.5 55.5
273
ASL ASL ASL ASL
90
117
28 13
132
M8
M8
32 25
Mounting screw 70 70
80
8
Tapped hole
45 70 70 70 14 37
15
Conductor 8 103
140 105 175 overlap, max 127.5
210 280
80.5 145
Rear connected
Drilling plan (front view) Panel cutout (front view)
when necessary HL
ø4
3 HL HL
ø1 5
103
13
8
30.5
126
136
126
25 32 20 R6
Conductor ASL
92
ASL ASL
overlap, max M8
122
Tapped hole
117
28 13
117
127
12
45
70 70 70
172
8 70 70
5
103 M8
43 70 70 43 43 70 70 70 43
127.5 Mounting screw
80.5 145
Panel cutout dimensions shown give an allowance
of 1.0mm around the handle escutcheon.
Interpole barrier Drilling plan (front view) Panel cutout (front view)
(removable)
3P Mounting hole 12.5 200.5
4P
HL HL 14 32 M8
3
Front Panel
ø1
(removable) HL HL
80
(18)
Pad lock
101.9
101.9
126
156
160
160
M8
28 13 Mounting screw
117
(15.5)
overlap, max 15 32 25
70 140
80
8
16 137.5
213 give an allowance of 1.5mm
around motor operator.
3
(removable) (18) ø1
5
HL
100 100
Pad lock
13
8
101.9
126
16
25 32 20
8
156
Conductor
263
103
overlap, max
26
28 13
200.5
117
117
(15.5)
122
45
12 70 70
Connector plug (19.8) M8 ø4
99.5 70 70 70 43 70 70 43 43 70 70 70 43 8 150 150
16 137.5 Mounting screw
200 200
213 M8
Tapped hole
Note: Studs are factory installed in horizontal direction both on the line and load sides.
Page 2 of 3
mal Magnetic Characteristics and Adjustments
Current & Temperature Curves
NE, S630-CE, S630-GE
current DATA
characteristic
SHEET:curves
TEMBREAK 2 S1000-SE MCCB
CE, S630-CE, S630-GE Characteristic Curves
Time/Current
S1000-SE
3
2 T
hour
IR
1
Ip
40 tR
30 tp
Ig
20 Isd
tsd
10
tg
minute
Ii
6
I
4
40
30
20
Tripping Time
10
1
second
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
10
20
30
40
50
80
100
125
200
300
400
500
600
1000
1500
2000
3000
4000
5000
8000
Percent Rated
Current In Percent Rated Current IR
In = 1000A
IR (A)
LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0
Characteristics No. 1 2 3 4 5 6
11 21 21 5 10 16
LT tR (s)
at 200% x IR at 600% x IR
Standard Isd xIR 2.5 5 8
ST tsd (s) 0.1 0.2
INST Ii xIR 14(Max: 10 x In) Note (1)
Ip xIR 0.8
PTA tp (s) 40
gF Ig xIn 0.2
Option Note(3) tg (s) 0.2
IN xIR 1.0/0.5 Note(2)
NP
tN (s) tN=tR
Note
(1) Ii max. = 10 x In. (2) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is identical to characteristic of
phase protection (tR vs. IR). (3) When you specify gF on MCCBs with 3 poles the terminal block is automatically fitted to connect with
the external neutral CT for 3 phases 4 wires system.
Page 3 of 3