33
om
Exercises 7SD8 – Line data

.c
ad
Make the settings for the following line data

ip
■ Vnom = 110 kV solidly grounded

i@
Kursunterlagen für Igor Stefanovic, [email protected]

■ Voltage transformer 110 kV / 100 V

ic
■ CT station A 500 A / 1 A

ov
an
■ CT station B 400 A / 1 A

om
■ Nominal current of the line
ef 400A

.c
st

ad
■ Line length l = 40 km

ip
■ Positive sequence impedance Zpos R' = 0,071 Ω/km X' = 0,379 Ω/km
■ Zero sequence impedance Z0
i @ R' = 0,146 Ω/km X' = 0,549 Ω/km
ic
ov
an
ef
st

Restricted © Siemens AG 2016 All rights reserved Siemens Power Academy TD Seite 2
33 SIPROTEC V5 - Application and exercises of system protection
om
Exercises 7SD8 – What to do

.c
ad
■ Device at your table check, connect supply voltage, connect

ip
to test device, read out ordering code

i@
(MLFB) and version
Kursunterlagen für Igor Stefanovic, [email protected]

■ DIGSI Manager Create substation and device

ic
ov
■ DIGSI device configuration check that the main protection function is

an
available and switched on

om
■ DIGSI Settings
ef
parameterize the setting of Idiff> - stage to

.c
st
120 A and of Idiff>> - Stage to 520 A

ad
■ Parameterize the topology

ip
■ DIGSI Matrix: Assign the pickup of both stages and trip to the LEDs 1...3
■Assign trip command on binary output no. 1
i @
ic

■ DIGSI Manager: Initialize the device


ov

■ Is the device operating?


an
ef
st

Restricted © Siemens AG 2016 All rights reserved Siemens Power Academy TD Seite 3
33 SIPROTEC V5 - Application and exercises of system protection
Exercises 7SD8 – stabilising characteristic

om
.c
ad
■ please measure the stabilizing quantity depending on the through flow
current

ip
i@
Kursunterlagen für Igor Stefanovic, [email protected]

■ Therefore inject currents with omicron Quick CMC on both sides

ic
through flow measured

ov
primary current stabilizing explanation

om
an
ef

.c
0A

ad
st

200 A

ip
400 A i@
600 A
ic
ov

800 A
an
ef
st

Restricted © Siemens AG 2016 All rights reserved Siemens Power Academy TD Seite 4