Aad03040d Ol
Aad03040d Ol
foreword
·Please read the instruction manual carefully to ensure safe and correct use of this product. ·
• Do not use our company's elevator door controller for purposes other than elevator door control.
• Please fully confirm the safety and applicability of the main elevator system before using it. To avoid major accidents, be sure
to set up safety measures such as double safety mechanisms and fail-safe. • Do not use this product on loads other than
i
Machine Translated by Google
Machine Translated by Google
Safety Precautions
Before installation, operation, maintenance and inspection, please be sure to read this manual and its attached
documents thoroughly so as to use it correctly. Use it only after you are proficient in the conditions, safety information
and precautions of the equipment. This manual is divided into two levels of "Danger" and "Caution" in the safety
precautions column.
Incorrect operation can result in a dangerous situation that could result in death
or serious injury.
In the event of mishandling, hazardous conditions can occur, situations that may
result in moderate or minor injury, and situations where item damage may occur.
2
Machine Translated by Google
Safety Precautions
1. System Design
Danger
•The STOP key is not used for emergency stop, so prepare an emergency stop switch separately. •Please use
the door clipping after fully confirming the safety and functional operability in the elevator main system
Checkout function.
•Be sure to input a safety sensor to the main controller of the elevator body, and perform door jamming detection on the main controller side.
The trapping detection function of the elevator door controller will not be activated in the open arrival area and the closed arrival area. Be
sure to take double safety measures. •Be sure to input the arrival signal (limit switch, etc.) to the main controller of the elevator body, and
perform door arrival detection on the main controller side. Do not use the elevator door controller open/close arrival signal (input signal and
•Depending on the setting of the forced operation time for abnormal opening operation and the stop selection during opening/closing
operation, the door may not stop even if the opening/closing command signal is OFF. Therefore, be sure to fully confirm the safety and
functional operability of the elevator main system before using it. •Depending on the start-up method and the settings of the instantaneous
stop and restart function, when the operation signal is ON, a sudden start (restart) may occur when the power is turned on or reset after a
power failure. Please design the machine to ensure safety even if it is started suddenly. •According to the setting of the start mode
function, when the operation signal is ON, after resetting the abnormal trip, perform "reset of abnormal trip", "reset the stop state by the
STOP function on the panel" or "reset the door width test" , a sudden restart may occur. Please design the machine to ensure safety even if
it is started suddenly.
•After using the retry function, it may automatically start suddenly (restart). Please carry out mechanical design, even if sudden
• Input the abnormal output of the elevator door controller in the main controller of the elevator main body, and input the abnormal output of the elevator door controller in the main controller side.
•In order to ensure safety, even in the event of abnormal stop, abnormal operation, or failure of the elevator door controller,
3
Machine Translated by Google
Safety Precautions
Notice
•Elevator door controller can easily set the operating speed from low speed to high speed. Therefore, please fully confirm the allowable range of the motor
and machinery before setting. •When using it when no signal arrives, please fully confirm the safety and functional operability of the elevator main
system before using it. •Door repeat control and door amplitude measurement will automatically change the direction of door movement. Please fully confirm
2. Installation
Notice
fire may occur. •Do not place near flammable objects. Otherwise, a
fire may occur. •Do not hold the terminal cover when transporting.
•According to the instruction manual, the installation site should be able to bear the weight of the equipment.
•Do not install or operate the elevator door controller with damage or missing parts.
4
Machine Translated by Google
Safety Precautions
3. Wiring
Danger
•Be sure to cut off the input power before wiring. Please do wiring work after 5 minutes after the input power is turned OFF. Otherwise,
electric shock and fire may result. •Be sure to connect the ground wire. Otherwise, electric shock and fire may result.
•Be sure to install the main unit before wiring. Otherwise, electric
Notice
•Please confirm that the rated voltage of the product is consistent with the voltage of the
AC power supply. Otherwise, a fire may occur. •Do not connect AC power to the
•To prevent the terminal block from falling off and disconnecting, do not apply stress to the wiring.
5
Machine Translated by Google
Safety Precautions
4. Operation
Danger
•Before turning on the power, confirm that the terminal block or connector is securely installed.
•Be sure to turn on the power after closing the terminal cover. Also, do not open the terminal cover while the power is on.
•When the elevator door controller is powered on, do not touch the terminal of the elevator door controller even when it is stopped.
son.
•When the data is changed during operation, the motor and motor load may change greatly, or the motor may suddenly change.
then start and stop. Please fully confirm the safety before use.
•After starting auto-tuning, the elevator door controller will automatically apply high voltage DC to the motor, so please
Do not touch.
•After starting auto-tuning, the elevator door controller will automatically drive the motor to run. Please fully
Notice
•The heat sink is in a high temperature state, please do not touch it.
sure to adjust and confirm each parameter before operation. Depending on the parameter settings, there may be
predictable action.
6
Machine Translated by Google
Safety Precautions
Danger
•Please do maintenance and inspection after 5 minutes after the input power is turned OFF. Otherwise, electric shock
may result.
•Non-designated personnel are not allowed to maintain, check and replace parts. Please put metal objects (watches,
bracelets, etc.) and use tools with insulation. Otherwise, electric shock may
result.
Notice
•Please entrust electrical engineering professionals to tighten the terminal screws regularly.
6. Others
Danger
•Do not use this product on loads other than three-phase AC permanent magnet synchronous motors. •It is
forbidden to disassemble or modify this product. Otherwise, electric shock may result.
7. General Notes
All the diagrams in this manual are sometimes drawn with the protective cover or shield removed in order to explain the structure of the
detailed part. When the product is running, be sure to cover the protective cover or shield according to the requirements of the manual.
7
Machine Translated by Google
Safety Precautions
8
Machine Translated by Google
content
1.1 The names of the parts and their functions ................................................ ................................. 10
ii
Machine Translated by Google
iii
Machine Translated by Google
iv
Machine Translated by Google
1
The names of the parts and their functions
1.1 The names of the parts and their functions ................................................ ................10
9
Machine Translated by Google
1 5
6 11
7 10
10
Machine Translated by Google
input, close action command input and multi-function input. The multi-function input has
11
Machine Translated by Google
12
Machine Translated by Google
2
Install
13
Machine Translated by Google
2. Installation
fire may occur. •Do not place near flammable objects. Otherwise, a
fire may occur. •Do not hold the terminal cover when transporting.
•According to the instruction manual, the installation site should be able to bear the weight of the equipment.
•Do not install or operate the elevator door controller with damage or missing parts.
14
Machine Translated by Google
2. Installation
humidity. ·A place where oil mist, dust and cotton dust are
and oil droplets. · Places with corrosive gas, explosive gas and flammable gas. ·Installed on
flammable materials such as wood or near flammable objects. · Places subject to frequent
vibrations.
ÿ Do not allow the ambient temperature to exceed the allowable ambient temperature.
The higher the ambient temperature, the shorter the lifespan. Please do not install it near a device that generates a large amount of heat, and
fully study the installation location and cooling method. • Allowable ambient temperature: -10ÿ+50ÿ (The measurement point of ambient
When installed horizontally, the cooling effect of the elevator door controller will be
reduced. Refer to "11.1 Ratings" (page 104) before use. Use under non-rated values will cause malfunction.
• • ×
15
Machine Translated by Google
2. Installation
To ensure the ventilation space required for cooling and the space required for wiring, be sure to leave the installation space as shown in the figure
below.
16
Machine Translated by Google
2. Installation
2.3 Dimensions
240
230
60
220
2-ÿ5 8
17
Machine Translated by Google
Machine Translated by Google
3
Wiring method
19
Machine Translated by Google
3. Wiring method
•Be sure to cut off the input power before wiring. Please set the input power to OFF
shock and fire may result. •Be sure to connect the ground wire.
•Be sure to install the main unit before wiring. Otherwise, electric
•Please confirm that the rated voltage of the product is consistent with the voltage of the
AC power supply. Otherwise, a fire may occur. •Do not connect AC power to the
output terminals (U·V·W). Otherwise, a fire may occur. •Please connect the wiring of
or sudden acceleration may occur. •Please connect the wiring of the control terminal
correctly.
•To prevent the terminal block from falling off and disconnecting, do not apply stress to the wiring.
20
Machine Translated by Google
3. Wiring method
L.N The main circuit power input is connected to the power frequency power supply.
Inverter output
It is the terminal for grounding.
Protective grounding
Earth resistance 100 ÿ or less
twenty one
Machine Translated by Google
3. Wiring method
avoid wrong wiring and operation, please pay attention to the following. (Otherwise it may cause equipment damage)
Be sure to connect the power supply to the main circuit power input terminals (L, N), and the motor to the synchronous motor connection
output terminals (U, V, W).•The terminals for power supply and motor wiring must be round crimp terminals with sleeves. Please select
crimp terminals according to wire size and screw size. • After wiring the main circuit, be sure to confirm the tightness. ·When connecting
directly below a large-capacity power transformer (500kVA or more), be sure to install an AC reactor on the input side of the elevator door
controller.
• The recommended wire for the main circuit is a 600V type 2 vinyl insulated wire with a continuous maximum allowable
temperature of 75°C.•If the overcurrent trip of the circuit breaker for wiring is completely electromagnetic, overheating will occur due to
inputting, be sure to connect a protective device against overcurrent, short circuit, leakage, etc.•The
protective grounding (PE) terminal should be grounded with a grounding resistance of 100ÿ or less.
0.2kW 5A 2 2
2 mm 2 mm
M2.5 0.4 N m
(AWG14) (AWG14)
0.4kW 10A
twenty two
Machine Translated by Google
3. Wiring method
Related parameters
needle arrangement Needle No. Terminal function
No.
-
1 0V terminal
ground. Incorrect connection may result in damage to the elevator door controller.
twenty three
Machine Translated by Google
3. Wiring method
Note) Common terminals C1, C2, and C3 are independent in the internal circuit. Do not ground this common terminal.
-
1 Common terminal of input signal (2~9)
4 Input terminal of multi-function control signal SW1 P026, P027, P038, P039
5 Input terminal of multi-function control signal SW2 P026, P028, P038, P039
6 Input terminal of multi-function control signal SW3 P026, P029, P038, P039
7 Input terminal of multi-function control signal SW4 P026, P030, P038, P039
8 Input terminal of multi-function control signal SW5 P026, P031, P038, P039
9 Input terminal of multi-function control signal SW6 P026, P032, P038, P039
-
10 Common terminal of input signal (2ÿ9)
Note) Common terminals 1 and 10 are connected internally. Do not ground this common terminal.
twenty four
Machine Translated by Google
3. Wiring method
•For the wiring of the control circuit terminals, please strip the outer sheath of the wire according to the specified size before use.
• Loosen the terminal screws, insert the wires, and tighten with the specified tightening torque.
· Twist and twist the stripped wires before wiring to avoid unevenness. Also, do not perform soldering
•If the tightening is loose, the wires may fall off, resulting in malfunction. If it is over-tightened, the screws and the unit may be damaged.
·Use shielded wires for control signal wires, and wire them separately from power wires or strong current circuits. (more than 20cm)
·The wiring length of the control signal line should be less than 30m.
· Since the input signal of the control circuit is a small signal, in order to prevent poor contact during contact input, please use the
Tightening torque
Terminal symbol Screw size wire size
Nm
25
Machine Translated by Google
3. Wiring method
·The input circuit is shown in the figure below. Be careful with back current and leakage current.
• Since the internal circuit is powered by the internal power supply +24V, do not supply power from the outside. If a voltage is applied,
• Connect no-voltage contact signal or open-collector signal to control circuit terminals No. 2 to 9.
• Common terminals 1 and 10 are internally connected. Do not ground the common terminal.
project Specification
26
Machine Translated by Google
3. Wiring method
ÿ Control circuit output terminals (terminal No.A1, C1, A2, C2, A3 to C3)
output points Relay 3 points, multi-function output (select and set by parameter)
Mechanical life More than 10 million times (on-off frequency 180 times/min)
More than 100,000 times (1c NC contact is more than 50,000 times, when the rated control capacity is
Electrical life
off frequency 20 times/min)
27
Machine Translated by Google
3. Wiring method
·Do not use terminals 1 (+24V output terminals) and 5 (0V terminals) for non-encoder power supplies. Also, do not take
land. Incorrect connection may result in damage to the elevator door controller.
project Specification
28
Machine Translated by Google
3. Wiring method
29
Machine Translated by Google
3. Wiring method
30
Machine Translated by Google
4
Operation panel
31
Machine Translated by Google
4. Operation panel
In signal display mode, the type of signal on the LED display is displayed. Please refer to parameter
number P021.
ÿ Display part as follows. ·Output frequency, current, signal, abnormal state and other action status, set frequency,
•Mode switching
MODE key
•Reset from parameter setting state and monitoring state to mode display
mode •Determining the setting value (The parameter No. increases and returns to the
SET key
mode display.) •Current display switching, signal status display switching •Long press:
•Stop of operation
•Reset after completion of door width measurement, start-up positioning operation, and completion of auto-tuning
32
Machine Translated by Google
4. Operation panel
mode monitored.
ÿControl status
Control status and abnormal content can be monitored.
monitoring mode
ÿCustom setting 10 frequently used parameters can be registered, and data can
ÿParameter
Parameters can be monitored and changed. Change in the order
setting value
of P, H, d.
mode (when P parameter)
turn. ·Press the [SET] key in each mode to enter the state where data can be monitored or changed. Press the [MODE] key to return to the original
screen. When pressing the [SET] key by mistake, you can press the [MODE] key to return.
33
Machine Translated by Google
4. Operation panel
Note 1) The display changes according to the value of parameter "P021: Quick monitor selection".
Note 2) In frequency setting mode and rotation direction setting mode, it is displayed only when the value of parameter "P004:
34
Machine Translated by Google
5
Control status monitoring
35
Machine Translated by Google
The following items can be monitored in the control status monitor mode.
n013 Abnormal display (1 time ago) - Display the content of the abnormality one time ago
n014 Abnormal display (2 times ago) - Displays the content of the abnormality 2 times before
n015 Abnormal display (3 times ago) - Displays the content of the abnormality 3 times ago
36
Machine Translated by Google
internal DC voltage
voltage
display
n003
voltage, internal DC voltage. The displayed contents are not suitable for precision measurements. Please use only as a reference value.
(When precise numerical values are required, please use a separate measuring instrument.)
set frequency.
detects the actual motor speed through the encoder signal. The
frequency value calculated from the detected motor speed is displayed as the detected frequency.
Note 1) The number of motor poles (parameter H005) and the encoder constant (parameter H006) must be set.
"0": closed hold motion area, "1 to 4": open motion area "5": open hold motion
37
Machine Translated by Google
Displays the door position data when the OPEN arrival signal changes from OFF to
data of parameter P037 (setting data clear) to "4" to clear the data
of switching times.
rotation direction of the motor can also be displayed using the encoder signal.
F: Forward rotation (opening action), r: reverse rotation (closing action)
error information.
38
Machine Translated by Google
state.
On: The input terminal and the common terminal are closed
Off: The input terminal and the common terminal are in an open state
Note) The input signal display lights up when the input terminal is closed, and goes out when the input terminal is open.
It does not turn on when the input signal is ON and turn off when it is OFF.
39
Machine Translated by Google
40
Machine Translated by Google
41
Machine Translated by Google
When the pulse number of the encoder is 1024 pulses, "10.24" is displayed.
42
Machine Translated by Google
6
parameter setting
43
Machine Translated by Google
6. Parameter setting
Parameters can be monitored and set in "custom setting mode" and "parameter setting mode". Please change or set each
function parameter during stop. Some function parameters can also be changed during operation.
ÿSetting example
When the maximum output frequency is changed from 50.0Hz to 60.0Hz (the data of parameter P005 is changed from "50.0" to
"60.0")
2. Press the key to change to the P field parameter setting mode. (When setting a password,
4. Press the key to display the data of parameter P005. (display flashes)
(display flashes)
It becomes a normal stop state, and the operation of the elevator door controller can be performed.
44
Machine Translated by Google
6. Parameter setting
·After setting and changing the data, the setting data is written into the non-volatile memory inside the elevator door controller, and it is retained
even in the event of a power failure. ·When changing parameters that cannot be set during operation, if the operation signal is ON, "P.Err" will
flash and display, and return to the parameter number display after 2 seconds. Start operation without changing parameters.
45
Machine Translated by Google
6. Parameter setting
When data is changed during operation, the motor and motor load may change greatly, or it may start
and stop suddenly. Please fully confirm the safety before use.
For the function parameters that can be changed during operation, refer to the list of each parameter.
ÿSetting example
When changing the 1st deceleration time from 5.0 seconds to 10.0 seconds (change the data of parameter P002 from "5.0" to "10.0")
2. Press the key to change to the P field parameter setting mode. (When setting a password,
4. Press the key to display the data of parameter P002. (display flashes)
5. Press key, the data display value is changed to "10.0". (display section
flashing)
46
Machine Translated by Google
6. Parameter setting
(If the key is not pressed, the display will not be switched)
•When the parameter that cannot be set during operation is displayed during operation, if the operation signal is turned OFF, after the
47
Machine Translated by Google
6. Parameter setting
In the "custom setting mode", up to 10 functional parameters that need to be changed frequently can be selected arbitrarily, so as to
realize the change of data more easily. Custom parameter No. can be assigned from 1 to 10. Also holds during power outages.
ÿSetting example
Change the parameter assigned to the custom setting parameter "U001" from "P001" (1st acceleration time) to "P002" (1st
deceleration time).
3. Press the key to confirm the currently assigned function parameter No..
*The function parameter No. in the custom setting mode is displayed with dots after the symbols "P"
and "d". (When setting a password, the password must be entered. Please refer to parameter P036:
Password)
4. Press and hold the key for 2 seconds to enter the allocation setting state. (digital part flashes)
48
Machine Translated by Google
6. Parameter setting
The initial settings of custom parameters No.1 to 10 are shown in the table below.
Custom parameter No. Function parameter No. function name initial value
To restore the assignment settings of custom parameters No.1 to 10 to the initial state, please set the function parameter
The set value of "P037: Setting data clear" is set to "3". (The value of the data does not change.)
•Only the data can be displayed for the function parameters that cannot be changed during operation.
49
Machine Translated by Google
6. Parameter setting
Set, change, and check the function parameter data assigned to the custom setting parameter No. For the function parameters
that can be changed during operation, refer to the list of each parameter.
When data is changed during operation, the motor and motor load may change greatly, or it may
start and stop suddenly. Please fully confirm the safety before use.
ÿSetting example
When the data of "P002" (1st deceleration time) assigned in the custom setting parameter "U001" is changed from "5.0" to "10.0"
3. Press the key to confirm the currently assigned function parameter No..
*The function parameter No. in the custom setting mode is displayed with dots after the symbols "P"
and "d". (When setting a password, the password must be entered. Please refer to parameter P036:
Password)
4. Press the key to display the data of parameter P002. (display flashes)
(display flashes)
If the data is changed during operation, it will operate with the new data.
•For function parameters that cannot be changed during operation, only this data can be displayed.
50
Machine Translated by Google
6. Parameter setting
51
Machine Translated by Google
6. Parameter setting
P057 Low voltage anti-collision door resistance adjustment frequency 0ÿ100 1[msec] 15 15
P058 Low voltage anti-collision door limit frequency float • 0.5ÿ250.0 0.1[Hz] 2.0 2.0
*1: When the parameters are P048 to P054, the changed parameter values will take effect when the power is turned from OFF to ON.
52
Machine Translated by Google
6. Parameter setting
Synchronize asynchronous
H020 0Hz hold ASR integral time 0ÿ100.0 0.1[sec] 0.5 0.5
-
H021 Startup finished mode selection 0•1 1 1
-
H022 Start action selection 0 1 when power is restored 1 1
H024 Encoder error detection time 0.0 • 0.1ÿ2.0 0.01[sec] 1.0 1.0
-
H025 Encoder frequency multiplication setting 0•1 0 0
-
H026 ASR Amplification Switch Setting 0•1•2 0 0
-
H027 ASR Scale Increase 2 0ÿ100.0 5.0 5.0
53
Machine Translated by Google
6. Parameter setting
Synchronize asynchronous
H043 Slip judgment time at synchronous start 0ÿ9999 1[msec] 200 200
-
H044 H parameter password 0ÿ9999 0 0
54
Machine Translated by Google
6. Parameter setting
speed position 1 d008 Close speed position 2 • 0.00ÿ100.0 0.01[%] 60.00 60.00
acceleration and deceleration time 1 d021 • 0.0 • 0.1ÿ999.9 0.1[sec] 1.0 0.5
Open acceleration and deceleration time 2 • 0.0 • 0.1ÿ999.9 0.1[sec] 1.0 0.5
d022 Open acceleration and deceleration • 0.0 • 0.1ÿ999.9 0.1[sec] 0.5 1.2
time 3 d023 Open acceleration and • 0.0 • 0.1ÿ999.9 0.1[sec] 1.2 1.0
deceleration time 4 d024 Close acceleration • 0.0 • 0.1ÿ999.9 0.1[sec] 0.7 0.5
and deceleration time 1 d025 Close • 0.0 • 0.1ÿ999.9 0.1[sec] 1.0 0.5
acceleration and deceleration time 2 d026 • 0.0 • 0.1ÿ999.9 0.1[sec] 0.5 1.0
Close Acceleration and deceleration time 3 • 0.0 • 0.1ÿ999.9 0.1[sec] 1.7 1.0
d027 Close acceleration and deceleration time • 0.0ÿ300.0 0.1[%] 150.0 150.0
4 d028 Open to reach holding torque level d029 • 0.0ÿ300.0 0.1[%] 100.0 100.0
• 0.0
Close to reach holding torque level d030 Open/close holding action stop time • 0.1ÿ999.9 0.1[sec] 0.0 0.0
55
Machine Translated by Google
6. Parameter setting
d031 Hold standby frequency when open • 0.5ÿ250.0 0.1[Hz] 2.4 0.5
arrives d032 Hold standby frequency when • 0.5ÿ250.0 0.1[Hz] 2.4 0.5
close arrives d033 Hold standby time when open arrives • 0.0ÿ10.0 0.1[sec] 0.0 0.0
d034 Hold standby time when closing • 0.0ÿ10.0 0.1[sec] 0.0 0.0
d038 Door width measurement frequency d039 • 0.5ÿ250.0 0.1[Hz] 5.0 5.0
Abnormal detection time when reaching SW d040 0.0 • 0.1ÿ10.0 0.01[sec] 1.0 0.0
Overload detection frequency 1 when opening operation • 0.5ÿ250.0 0.1[Hz] 8.0 10.0
d041 Overload detection frequency 2 during opening • 0.5ÿ250.0 0.1[Hz] 16.0 50.0
d042 Overload detection current 1 during open action • 0.1ÿ100.0 0.1[A] 1.4 1.2
d043 Overload detection current 2 during open action • 0.1ÿ100.0 0.1[A] 1.4 1.2
d044 Overload detection judgment time during open action• 0 1ÿ9999 d045 Overload 1[msec] 0 0
• 0.5ÿ250.0
detection frequency 1 during closing action d046 Overload detection frequency 2 during 0.1[Hz] 8.0 10.0
d048 Overload detection current 2 during closing action • 0.1ÿ100.0 0.1[A] 1.4 1.2
d049 Judgment time of overload detection during closing action • 0 • 1ÿ9999 1[msec] 0 0
d050 Intrusion judgment frequency (low speed) • 0.0ÿ100.0 0.1[%] 50.0 50.0
frequency d053 Trap detection judgment time during open operation • 0 ÿ 1ÿ9999 1[msec] 300 100
d054 Intrusion detection judgment time during closing action• 0 ÿ 1ÿ9999 1[msec] 300 100
d055 The level of the maximum moment when the door is clamped • 0.0ÿ500.0 0.1[%] 250.0 250.0
d056 Standby time after sandwich detection • 0.0ÿ999.9 0.1[sec] 0.0 0.0
time d059 Forced open action judgment time • 0.0 • 0.1ÿ999.9 0.1[sec] 0.0 0.0
d060 Forced close action judgment time • 0.0 • 0.1ÿ999.9 0.1[sec] 0.0 0.0
d061 Abnormal open/close action forced action time• 0.0 • 0.1ÿ999.9 0.1[sec] 0.0 0.0
d062 Abnormal open/close action open arrival hold time• 0.0ÿ10.0 0.1[sec] 0.0 0.0
d063 Prohibited area when sandwich detection is open • 0.00ÿ100.0 0.01[%] 100.0 100.0
56
Machine Translated by Google
6. Parameter setting
change d064 Prohibited range during clamping detection and closing 0.01[%] 0.00 0.00
selection d070 Slip arrival judgment frequency • 0.1ÿ10.0 0.1[Hz] 0.5 0.5
d072 Slip differential switch arrival substitution selection • 0.0 • 0.1ÿ10.0 0.1[sec] 0.5 0.5
-
d073 Action selection after terminal detection 0•1 1 1
d074 Judgment time of overload detection when open arrives • 0 • 1ÿ9999 1[msec] 0 0
d075 Judgment time of overload detection when closing is reached• 0 • 1ÿ9999 1[msec] 0 0
d077 Input terminal abnormal closing action frequency 1 • 0.5ÿ250.0 0.1[Hz] 6.4 6.4
d078 Input terminal abnormal closing action frequency 2 • 0.5ÿ250.0 0.1[Hz] 8.0 8.0
d079 Input terminal abnormal close action frequency 3 • 0.5ÿ250.0 d080 0.1[Hz] 7.2 7.2
Input terminal abnormal close action frequency 4 • 0.5ÿ250.0 Input 0.1[Hz] 5.6 5.6
time 4 d085 Emergency opening action frequency • 0.5ÿ250.0 0.1[Hz] 20.0 20.0
d086 Emergency opening action acceleration and deceleration time • 0.0 • 0.1ÿ999.9 0.1[sec] 0.5 0.5
d087 Open low speed action frequency • 0.5ÿ250.0 0.1[Hz] 3.2 3.2
d088 Close low speed action frequency • 0.5ÿ250.0 0.1[Hz] 3.2 3.2
d089 Low-speed action acceleration and deceleration time • 0.0 • 0.1ÿ999.9 0.1[sec] 0.5 0.5
-
d090 Action selection when closing arrival signal is 0•1 1 1
abnormal d091 Close arrival signal detection width 0·0.1ÿ10.0 0.1[%] 8.0 8.0
57
Machine Translated by Google
6. Parameter setting
d096 Door closing clamping maximum torque level • 0.0ÿ500.0 0.1[%] 250.0 250.0
58
Machine Translated by Google
7
Initial setting and
59
Machine Translated by Google
•Before turning on the power, confirm that the terminal block or connector is securely installed.
sure to turn on the power after closing the terminal cover. In addition, do not open while power is on
terminal cover.
•When the elevator door controller is powered on, do not touch the terminals of the elevator door controller even in the
•When data is changed during operation, the motor and motor load may change greatly, or it may start and stop suddenly.
Please fully confirm the safety before use. After starting auto-tuning, the elevator door controller will automatically
•When using the auto-tuning function, after pressing the operation key (RUN) on the panel, the elevator door controller
automatically drives the motor. Please fully confirm the safety before use.
•The heat sink is in a high temperature state, please do not touch it.
sure to adjust and confirm each parameter before operation. Depending on the parameter settings, unexpected actions
may occur.
60
Machine Translated by Google
·When the setting value of parameter "H001: Motor selection" is "2" "3" "4", the door controller will automatically set
Set parameters "H002~H006" and "H010~H016". The set value of "H001: Motor selection" is "1"
When the motor is used, please manually set the parameters "H002~H006" and "H010~H012" according to the motor used.
·In the initial setting state, when the rotation direction is reversed during operation, please set the parameter "H007: Motor rotation direction"
•Parameters such as phase-to-phase resistance and inductance of each axis necessary for synchronous motor control can be automatically set by executing auto-tuning.
For the steps of auto-tuning, please refer to the item "H008: Auto-tuning".
0: Asynchronous motor
1: Synchronous motor
-
H001 Motor selection 2: Recommended motor 1 (50W)
-
2 •4 •6 •8 •10 •12•
H005 Number of motor poles [pole]
14 • 16 • 18 • 20
- 0: Initial setting
H007 Motor rotation direction setting
1: Reverse setting
-
H008 Autotune 0•1•2•3
61
Machine Translated by Google
-
H014 d-axis current integral increase 0ÿ32000
-
H015 q-axis current proportional increase 0ÿ32000
-
H016 q-axis current integral increase 0ÿ32000
·If the number of poles is less than 16, please use the motor with 1000ppr or more, and please use the motor with more than 16 poles.
• The parameters of the encoder offset value necessary for synchronous motor control can be automatically set by executing auto-tuning.
For the steps of auto-tuning, please refer to the item "H008: Auto-tuning".
62
Machine Translated by Google
·Be sure to confirm that the parameter settings of the motor and encoder to be used are correct.
·Before the elevator door controller is programmed into the system, be sure to confirm that the parameters of the motor and the encoder are set
correctly, and then confirm that the motor itself can rotate normally in the no-load state. ·In the test run, please switch to the inverter operation
ÿOperation steps 1.
Make sure that the parameter "P004: Control mode selection" is "0". 2. According to the
operation method, set "P003: Operation command selection". 3. After pressing the operation
command ON or RUN key, the operation starts. 4. After pressing the operation command
OFF or STOP key, the operation stops. The factory setting is P004=0 (inverter mode),
P003=0 (use the panel to set the running and rotation direction).
1) Set the parameter "P003: Operation command selection" to "0" or "1". 2) Press the MODE key on the
panel to switch to the frequency setting mode (display: Fr). 3) After pressing the SET key, use the UP/DOWN
key to display the frequency to be set, and then press the SET key to set.
63
Machine Translated by Google
There are 2 ways to set forward/reverse operation using the operation panel.
ÿForward/reverse key operation mode (parameter P003: When the operation command is selected as "1")
Press the UP (forward) key or DOWN (reverse) key on the panel to select the direction of rotation, then press the RUN key
Start running.
stop O Forward F
reverse r
ÿRotation direction setting mode operation mode (when parameter P003: operation command is selected as "0")
Press the MODE key twice in the "action state display mode" to enter the "rotation direction setting mode".
key to display the rotation direction data, then use the UP/DOWN key to change the rotation direction, and finally use the SET key to set
Certainly. (Forward rotation is set at the factory.) Then, press the RUN key to start the operation.
In door control, forward rotation is the opening action, and reverse rotation is the closing action.
64
Machine Translated by Google
ÿMOP function
·Press the UP key and DOWN key continuously during operation to change the frequency, which is called "MOP function".
·The MOP function can be used only when the parameter "P003: Operation command selection" is set to "0: Rotation direction setting
mode".
65
Machine Translated by Google
66
Machine Translated by Google
8
Operation mode and action
67
Machine Translated by Google
ÿSmooth debugging
Set H001~H006 according to the motor model specification (generally marked on the metal nameplate on the motor casing).
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
Asynchronous motor does not need parameter self-learning Synchronous motor start mode selection
ÿ ÿ
Set parameter P003 (0~1: for panel debugging, 2: for external IO control)
Set parameter P004 (1~2: door control encoder mode, 4~5 door control SW mode)
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
ÿRefer to chapter 8.4 Gate width measurement ÿRefer to chapter 8.5 Limit switch setting
ÿ ÿ
ÿRefer to chapter 8.6 Open Action, 8.7 Close Action, 8.8 Open/Close Hold Action
ÿRefer to chapter 8.9 Pinch detection action, 8.10 Emergency open action, 8.11 Emergency stop action, 8.12 Terminal input error
68
Machine Translated by Google
·Relevant parameters (H010~H016) are required to calculate the vector control when the synchronous motor is driven. ·There will
be a deviation between the electrical angle of the motor and the installation angle of the encoder. The deviation value (H009) needs to be
For the same type of motor, H010~H016 parameters are basically fixed. If the parameter values have been known before, or the same motor
has been automatically tuned, you can manually enter H010~H012, and H013~H016 will be automatically calculated according to the entered
values.
The value of H009 will be affected by the installation position of the encoder. So for each motor/encoder, at least one auto-tuning needs to be
performed separately.
kinds of auto-tuning actions are provided according to different usage requirements. Select the type of auto tuning by setting parameter H038.
0 Normal state
completes the automatic tuning of the Z-phase offset value of the encoder.
(H009). After
·After H008 is set, auto-tuning is performed according to the type of operation command (open command/close command). For details,
69
Machine Translated by Google
order to facilitate customers to use the automatic tuning function, this product provides a quick tuning
function. By pressing and holding the [ÿ] and [ÿ] buttons for more than 3s at the same time, the auto-tuning equivalent to H008 = 3 starts.
70
Machine Translated by Google
kinds of synchronous start/positioning methods are provided according to different usage requirements.
0 Synchronous start
• Depending on the type of operation command (open command/close command), the synchronous motor performs initial positioning when the power is
turned ON. • During the start-up positioning operation, "Sync" is displayed. If there is no abnormality, the panel display changes to "S.End". When an
error is detected, "En1", "En2", and "En6" are displayed, and "S.Err" stops the operation.
·When H021=0, stop running. After the operation command is turned OFF or the STOP key is pressed, the start-up positioning operation is completed
When H021=1, P004=1, 2, 3, after receiving the running command, the positioning operation at startup is performed according to the command
direction. After the positioning operation is completed, it will run in the direction of the running command at the frequency when the power is turned
on until the command requirements are met. After meeting the command requirements, it will run according to the normal running frequency.
When P004=0, once decelerates to 0Hz, it will act according to the running command until it reaches the set frequency.
·When H022=0, use the open/close command of the upper system to start the positioning operation.
71
Machine Translated by Google
·When H022=1, if the closing arrival signal is ON and the opening command is ON, the 0Hz hold action will be performed. if
·During the synchronous start action, the door opening direction movement is performed according to the set value of the parameter "H040: synchronous start torque"
do. The set value of "H040" is set according to the connected load status. When the load is small, if the set value is too large,
It will cause the load current to be too large and the door opening action to make abnormal noise; and when the load is large, if the set value is too small, it cannot be driven.
set up
Parameter No. function name Predetermined area
unit
H041 Encoder error detection time at synchronous start 0.01[sec] 0.0 • 0.1ÿ2.0
Precautions for the operation characteristics of the old version positioning start when H036=1
•Using the positioning operation of the old version of the positioning start, apply a voltage to the rotation direction according to the operation command to make it
·During the positioning operation, the operation is performed according to the set value of the parameter "H035: Start positioning operation voltage". "H035"
The set value of is set according to the connected load status. When the load is small, if the set value is too large, it will become over-power
When the load is large, if the set value is too small, the motor cannot be driven.
And if the set value is too large, some motors may heat up or cause the rotor magnet to demagnetize, please pay attention.
•When positioning is performed by turning ON the OPEN reaching command at the OPEN reach position, or at the CLOSE reach position by turning ON the CLOSE command
When the command is ON for positioning, some equipment may not be able to perform the micro-motion of the rotor, and the positioning operation cannot be performed.
completed normally. In this case, please set the setting value of parameter "H036: Reverse retry when starting positioning operation"
is "1" or "2".
·Do not start under stress in the opposite direction of rotation. If a reverse stress is applied, the positive
72
Machine Translated by Google
set up
Parameter No. function name Predetermined area
unit
-
H021 Startup finished mode selection 0•1
-
H022 Start action selection when power is restored 0•1
H023 Start positioning operation abnormal judgment time 0.1 [sec] 0.0ÿ999.9
-
H036 Reverse rotation when starting positioning and try again 0•1•2
Precautions for the new version of the positioning start action characteristics when H036=2
Apply voltage to the press motor while keeping the motor stationary and
According to the feedback data, the position of the rotor is estimated at this time, and the estimated error is within ±8.4%.
set up
Parameter No. function name Predetermined area
unit
H038 Synchronization/positioning start mode selection
-
0•1•2
73
Machine Translated by Google
ÿOutline of Action
When the door width measurement is performed, the opening and closing actions are automatically performed, and the measurement is performed from the closed arrival position to the open arrival position.
·The in-position signal must be set before executing the door width measurement.
Parameter No. function name Set value open arrival signal close arrival signal
0 Have Have
2 none none
ÿPress the [MODE] key to switch to the action status display mode.
ÿ When the operation command is ON or the RUN key is pressed, the open action will be performed until the open position is reached.
ÿAfter the opening is reached, the closing action is performed until the closing position is reached.
ÿ After the closing is reached, perform the opening action again until the opening reaches the position.
ÿAfter the action is completed, "d.End" will be displayed on the panel, and the parameter "d001: door amplitude setting value" will be saved.
ÿ After the operation command is turned OFF or the STOP key is pressed, the door width measurement is ended and the operation status display mode is returned.
74
Machine Translated by Google
door width measurement, it operates at the frequency set in "d038: Door width measurement frequency". • During door width
measurement, pinch detection is invalid. ·When no signal arrives, when the terminal of the door is touched, the arrival position is
detected by slippage and overload current, and the door width is measured.
set
Parameter No. function name Predetermined area
unit
0: Inverter mode 1:
Door control encoder mode (normal) 2:
as chapter 8.2.
75
Machine Translated by Google
ÿ Outline of Action
·In the door control SW mode, it is necessary to set the limit switch input.
Control circuit
Parameter No. name Predetermined area
Input terminal number
SW mode needs to use 4 limit switches for control, the corresponding settings are as follows:
1 Open to the input signal In door control mode, it operates as an open arrival signal when SW-ON is turned on.
2 close to the input signal In door control mode, it operates as a closing arrival signal when SW-ON is turned on.
3 open shift input signal In door control mode, it operates as an open shift signal when SW-ON is turned on.
4 Close the speed change input signal In door control mode, it operates as a closing speed signal when SW-ON is turned on.
In SW control, at least 4 groups of open arrival signal, closed arrival signal, open speed change signal and closed speed change signal are required.
·The state of contact a and contact b of the input signal is set by P026.
· Allocate the input signal logic of SW1 to SW6 to bit0 to bit5 of internal data, the logic of each SW ×
The sum of the added values is used as the set value, and is entered in decimal.
• The initial value is "0", and all inputs are assigned to "a contact input".
76
Machine Translated by Google
Terminal No. 9 8 7 6 5 4
bit No. 5 4 3 2 1 0
added value 32 16 8 4 2 1
77
Machine Translated by Google
the open command signal turns ON, the closed hold action is released and the open action is performed.
78
Machine Translated by Google
After the open command signal turns ON, the closed hold action is released and the open action is performed.
door field 0 1 2 3 4 5
d002 d003 d004 d005 d006
On arrival signal ON
79
Machine Translated by Google
During the opening operation, after detecting the jamming, the abnormal closing operation is temporarily performed until the closing is reached, and after reaching, the operation is performed again.
• When the open inhibit input is turned ON, the open operation cannot be started.
In addition, during the opening operation, it stops immediately after the opening prohibition input turns ON.
When no signal arrives, the movable range of the door is the same as the measured value of the door width. Therefore, it is necessary to change the opening/closing to
The set value (d002, d006) of the reach position and set the reach range width. When there is no reach range, at
During normal operation, there are cases where the door position data cannot be converted into the reachable area. In order to ensure that the data can be changed
To reach the area, please change the setting of open/close reach position.
·When there is no arrival signal, it will judge the arrival situation at the positions of d002 and d006, and then enter the hold operation.
·D073 can be used to select how to act when there is no arrival signal and the door reaches the end of the door during the hold operation.
80
Machine Translated by Google
81
Machine Translated by Google
After the close action signal turns ON, the open hold action is released and the close action is performed.
open to holding Clamping Maximum Moment Level d096 closed reach hold
torque level torque level
d028 d029
d026
d025 d017 d027 d034 keep moving
d018
frequency
door field 5 6 7 8 9 0
d006 d007 d008 d009 d002
On arrival signal ON
100%
door position
0%
82
Machine Translated by Google
After the close action signal turns ON, the open hold action is released and the close action is performed.
d026
d025 d017 d027 d034 keep moving
d018
frequency
door field 5 6 7 8 9 0
d006 d007 d008 d009 d002
On arrival signal ON
83
Machine Translated by Google
During the closing operation, after detecting the jamming, the abnormal opening operation is temporarily performed until the opening is reached, and after the arrival, the operation is performed again.
close action.
• During the closing operation, it stops immediately after the emergency stop input turns ON.
When no signal arrives, the movable range of the door is the same as the measured value of the door width. Therefore, it is necessary to change the opening/closing to
The set value (d002, d006) of the reach position and set the reach range width. When there is no reach range, at
During normal operation, there are cases where the door position data cannot be converted into the reachable area. In order to ensure that the data can be changed
To reach the area, please change the setting of open/close reach position.
·When there is no arrival signal, it will judge the arrival situation at the positions of d002 and d006, and then enter the hold operation.
·D073 can be used to select how to act when there is no arrival signal and the door reaches the end of the door during the hold operation.
84
Machine Translated by Google
85
Machine Translated by Google
During the opening operation and closing operation, when the arrival signal turns ON or moves to the positions of d002 and d006, it enters
the hold standby operation. Then, after the hold standby time has elapsed, the hold operation is entered.
· The holding operation can be canceled by stopping or reverse operation (closed operation when open and held, and open operation
when closed and held). By setting the hold frequency to 0Hz, the door can be held at 0Hz after the hold standby action. (After the switch
function is activated, the control of returning to the original position is activated.) ·In the process of holding operation at 0Hz, if the parameter
"d028: Close to reach the holding torque level", "d029: Open to reach the holding torque level" is set or more than the set value torque, it
cannot be maintained.
86
Machine Translated by Google
ÿ Types and settings of parameters related to the open arrival hold standby action
ÿ Types and settings of related parameters when the open reaches the hold action
d095 Asynchronous motor open reaches holding torque current 0.1[A] 0.1ÿ100.0
ÿ Types and settings of related parameters when closing, reaching and holding standby action
d095 Asynchronous motor open reaches holding torque current 0.1[A] 0.1ÿ100.0
87
Machine Translated by Google
• The terminal is detected by combining slip and current by the setting of parameter "d069: Terminal detection/no-signal
characteristics • When d073 is set to 1, after a terminal (contact terminal) is detected, it is automatically set to hold
the door at 0Hz. ·When d068=1 or 2, please set the parameters of d069 and d073.
88
Machine Translated by Google
ÿ Types and settings of parameters related to the open arrival hold standby action
-
d068 No signal arrival selection 0•1•2
89
Machine Translated by Google
There are the following four methods for entrapment detection in each
method of inputting the safety sensor in the multi-function input terminal. It is assigned to any input by parameter "P027~P032: SW function
selection". ÿ Use the overload current detection (detect the current corresponding to the torque). The overload judgment conditions are set by
current, frequency, and time, and when the torque (current) becomes larger, it is judged that a trapping occurs. ÿ Use slip detection. Set the ratio
of the speed detected by the encoder (detection frequency) to the target speed (set frequency). ÿ Detect by time. When the time from the open
arrival position (or the closed arrival position) to the closed arrival position (or the open arrival position) exceeds the set time, it is judged that a
detection setting, only the slip detection is valid. Please set parameters as required.
The four types of trapping detection can be set repeatedly. However, when trapping is detected under multiple conditions, if all the causes of
trapping detection that are set are not eliminated, abnormal opening and abnormal closing operations will continue, and normal opening and closing
90
Machine Translated by Google
d053 Interruption detection judgment time 1[msec] during opening operation 0 or 1 to 9999
d054 Intrusion detection judgment time 1[msec] during closing action 0 or 1 to 9999
91
Machine Translated by Google
jamming is detected during the closing operation, the abnormal opening operation is started.
·When the open arrival signal turns ON after the abnormal opening action, and the closing action signal turns ON, it goes to the normal closing action.•When the pinching detection
is performed during the opening operation, the same operation as shown in the figure below is performed.
92
Machine Translated by Google
· If parameter "d062: Abnormal open/close action open/close arrival hold time" is set, the time set in d062 and the abnormal open/
abnormal close action will continue to be held after the arrival signal is detected. . See the action diagram on the previous page. ·If the
parameter "d056: Waiting time after trapping detection" is set, the abnormal opening/abnormal closing operation will be performed
after waiting for the set time in the state of frequency 0.0Hz and torque holding level 0.0%.
• During the waiting time after trapping detection, trapping detection cannot
be performed. · "d059: Forced opening action judgment time", "d060: Forced closing action judgment time", start counting after the
standby time.•In the case of emergency open operation and emergency stop, the standby time is skipped, and emergency open
operation and emergency stop operation are executed directly. (Emergency opening action and abnormal stop priority) ·It is counted
in parallel with the setting of "d061: Abnormal opening/closing action forced action time".•At start-up (start of door action) and when
opening/closing action is switched (from opening action to closing action, and from closing action to opening action), acceleration
torque is required, and the load (torque) becomes larger at the same time. In this case, set the standby time to prevent misoperation
of jamming detection. The waiting time before pinch detection using slip is set in parameter "d057", and the waiting time before pinch
93
Machine Translated by Google
ÿ Outline of Action
ÿWhen the emergency opening signal turns ON during the opening and closing operations, the current operation is terminated and the emergency operation is performed.
ÿAfter switching to the emergency open action, carry out the open action until the open arrival signal turns ON.
ÿ After the emergency open operation signal turns ON during stop, the emergency open operation will also be performed.
The emergency opening action signal is of the hold type. Even if the signal turns OFF in the middle, the emergency opening action will continue until the
Until the arrival signal turns ON and reaches the arrival level.
• During emergency open operation, ON/OFF of open command and close command signal is invalid. (emergency open action command has priority)
·In emergency open action, according to the parameters "d085: Emergency open action frequency", "d086: Emergency open action increase
d086 Acceleration and deceleration time of emergency open action 0.1[sec] 0.0 or 0.1ÿ999.9
94
Machine Translated by Google
ÿ Outline of operation ÿ
When the emergency stop input signal turns ON during the opening operation and closing operation, the operation in progress is
stopped. ÿ The operation is also stopped during emergency opening and abnormal closing.
emergency stop signal is valid only during the ON period. When the emergency stop signal changes from ON to OFF, if each signal of opening
action, closing action, emergency opening action, and abnormal closing action is ON, it will switch to each action. • During emergency stop, the
95
Machine Translated by Google
abnormal close action input is turned ON, it will operate according to the parameters "d077~d080: Abnormal close action frequency" and "d081~d084: Acceleration/deceleration
time".
there is no closing command signal input, the abnormal closing operation will be performed as long as the abnormal closing command signal is input. • During
the opening operation, even if the abnormal closing command signal is input, the opening operation will be performed and the abnormal closing operation will not be
performed. After the opening operation is completed, the abnormal closing operation is performed. • During the closing operation, after the abnormal closing command signal
turns ON, it switches to the abnormal closing operation. ·During the closing operation, after the abnormal closing command signal turns ON, even if it switches to the OFF
state immediately, the abnormal closing operation will be performed until the closing command signal is turned OFF. • During abnormal closing operation, when an opening
96
Machine Translated by Google
set up
Parameter No. function name Predetermined area
unit
d077 Terminal input abnormal closing action frequency 1 0.1[Hz] 0000 or 0.5ÿ250.0
d078 Terminal input abnormal close action frequency 2 0.1[Hz] 0000 or 0.5ÿ250.0
d079 Terminal input abnormal close action frequency 3 0.1[Hz] 0000 or 0.5ÿ250.0
d080 Terminal input abnormal close action frequency 4 0.1[Hz] 0000 or 0.5ÿ250.0
97
Machine Translated by Google
follows. Emergency stop action > Emergency open action > Open action > Abnormal close action based on terminal input > Close
action Even if the close command is ON, the open action will be performed after the open command is input.
98
Machine Translated by Google
9
Abnormal situations and countermeasures
99
Machine Translated by Google
• Please perform maintenance and inspection after 5 minutes after the input power is set to OFF
Operation.
The elevator door controller is equipped with a trip memory that stores the content of the abnormality that has occurred. Trip memory can be stored
The latest content and the content up to 3 times ago can be checked with monitor modes n012 to n015. which is
Even if the power is turned off, the memory contents can be saved.
•Momentary excessive current during deceleration or abnormality of the heat sink d020ÿd027)
SC3
overheat
OC1 Overcurrent during acceleration Confirm the output phase loss and eliminate the sudden change of the load
OU1 · The internal DC voltage is too large during acceleration ·Extend the acceleration time (parameters P001, d020ÿd027)
OU2 The internal DC voltage at constant speed is too large · Eliminate sudden changes in load
100
Machine Translated by Google
The output current reaches the electronic thermal setting for more than 1 minute
·Confirm the electronic thermal setting current (parameter P012)
OL More than 115% of constant current, or elevator door controller base
· Lighten the load
140% or more of quasi-current (2.4 A)
•Turn on the power while the operation signal is ON ·Confirm the startup mode (parameter P016)
OP •In the case of a timeout detected •Confirm the communication settings and wiring
•When the remote operation unit falls off during operation Reduced interference around elevator door controllers
En3 The opening and closing arrival signals are both ON. Confirm the opening and closing arrival signals
En4 No arrival signal in the door position data in the open arrival state Confirm the open arrival signal
En5 No arrival signal when the door position data is in the closed arrival state Confirm the closed arrival signal
Reduce the interference around the encoder and elevator door controller
Confirm that the motor wiring, encoder wiring and motor are
S.Err ·Start positioning operation abnormal
No fixed
CPU ·When too much interference is applied to the elevator door controller Reduced interference around elevator door controllers
101
Machine Translated by Google
In the display part of the operation panel, if the abnormality display lights up and stops, please reset it after correcting the
abnormality.
ÿIf the operation is set locally ((parameter P003 is set to "0" or "1"), press the "STOP key" on the operation
panel to reset and start again. ÿThe operation is set to external control input In this case ((parameter P003
stop reset is set to "2" or "3"), it can be reset after cutting off the "operation command key" of the external control input
Panel reset It can be reset by pressing the "STOP key" on the operator panel and can be started again.
Multi-function terminal reset function setting switch to "ON" once, and then reset to "OFF". It can then be started again.
102
Machine Translated by Google
9.3.2 The motor does not rotate (when the abnormal display lights up)
103
Machine Translated by Google
9.3.3 The motor does not rotate (when the abnormal display does not light up)
104
Machine Translated by Google
105
Machine Translated by Google
106
Machine Translated by Google
10
maintenance, inspection
107
Machine Translated by Google
•Please do maintenance and inspection after 5 minutes after the input power is turned OFF.
•Non-designated personnel are not allowed to maintain, check and replace parts. Before working, remove metal
objects (watches, bracelets, etc.) and use insulated tools. Otherwise, electric shock may result.
•Please entrust electrical engineering professionals to tighten the terminal screws regularly.
•When performing the megohm test between the power cord and the motor cord, disconnect the wiring connected to the elevator door controller and
measure with the electric wire. Do not perform megohm testing on control circuits.
•Because the elevator door controller is mainly composed of semiconductor components, in order to prevent the influence of the operating environment
such as temperature, humidity, dust, and vibration, as well as the failure caused by the aging and life of parts, please carry out daily inspection. The following
table shows the standard replacement years under normal operating conditions (annual average ambient temperature is 30°C, load rate is below 80%, and
1. Daily inspection: basically check whether there is any abnormality during operation. During operation, a multimeter is
generally used to check the input and output voltage of the elevator door controller. 2. Periodic inspection: Check the places
that must be stopped for inspection and the places that need regular inspection.
108
Machine Translated by Google
Wear failure (durable years, lifespan)...The durability is greatly affected by the use environment. 1. For
example, the life of a relay is determined by the roughness of its contact surfaces. Contact current value
and load inductance are the main factors affecting life. 2. Capacitors are mainly used as smoothing filters
in elevator door controllers, but because of the chemical reaction inside, the temperature has a great influence on their life.
Generally speaking, when the temperature increases by 10ÿ, the life of aluminum electrolytic capacitors will be reduced by half,
which also determines the life of the elevator door controller. When the elevator door controller is used at high temperature, even if
other parts are still normal, if the aluminum electrolytic capacitor enters the wear-out failure period, in order to prolong the life of the
Relays
ÿ
109
Machine Translated by Google
Note) In the symbols of the inspection cycle items, ÿ represents daily, • represents 1-year cycle, and ÿ represents 2-year cycle.
Inspection Items Inspection Items Inspection Period Inspection Method Judgment standard instrument
place
Ambient temperature,
Check the ambient temperature, humidity thermometer
surroundings ÿ Refer to the installation precautions -10 to +50°C, humidity hygrometer below
humidity, dust, etc. 90% RH
Whether
hearing there is any abnormal vibration and sound in the whole device ÿ There should be no abnormal objects according to sight and
200V:
Whether the main circuit voltage of the power supply voltage is normalÿ Input voltage measurement multimeter
170 to 253V AC
1) Looseness of fastened •
1) Reinforced tightening 2)
overall parts 2) Overheating of parts 3) •• 1), 2) should be no exception
According to visual inspection
Cleaning 1) Distortion of
Is
there any damage to the main terminal block • According to visual should be normal
circuit
inspection alone 2) Check the protection circuit and type
• voltmeter 2) Used as elevator door simulate
controllernormal
2) Sequence
action short
protection
circuitcircuit
of alarm
should
· display circuit with the sequence
output 1), 2) According to smell, visual
protection action test
circuit
capacitor for liquid leakage and deformationÿ According to visual inspection should be normal
Display whether the indicator light is faulty ÿ According to the visual display should be normal
of whether the indicated value of the instrument is normal ÿ Confirm the indicated
The ammeter should be in the specification value, management
value
value voltmeter
110
Machine Translated by Google
Inspection Items Inspection Items Inspection Period Inspection Method Judgment standard instrument
place
111
Machine Translated by Google
112
Machine Translated by Google
11
Specification
113
Machine Translated by Google
11. Specifications
11.1 Ratings
1.0kg
Intermittent operation rating
0.4kW 2.4A 1.0kVA 1.2kVA
Note 3)
Note 1) The rated output capacity indicates the value when the output voltage is 230 V AC.
Note 2) The power supply capacity varies depending on the impedance on the power supply side. Please prepare a power supply with a value greater than that shown in the table above.
Note 3) Please open the operation time (t open) + close the operation time (t close) ÿ 8 seconds, and the duty ratio is below
114
Machine Translated by Google
11. Specifications
For the installation method, refer to "2.2 Precautions during installation" (page 15).
115
Machine Translated by Google
11. Specifications
project Specification
Certainly
lose
source
frequency
116
Machine Translated by Google
11. Specifications
project Specification
•Acceleration and deceleration time: each opening and closing operation frequency can be set
Door operation mode setting
•Door shift position: Up to 3 positions can be set
•Door holding torque: (can be individually set for opening and closing), door holding torque limit setting
Reset function Stop signal reset, external reset, panel reset, power reset
Instantaneous stop and restart operation function on/off, and 0Hz restart (selectable switching)
Select to try again: Select the presence/absence of the function, and retry the abnormal content
retry function
Retry times: 1 to 10 times can be set arbitrarily
Acceleration and deceleration time 0.04 to 999.9 seconds (acceleration and deceleration are individually set)
control Acceleration and deceleration characteristics Linear, S-shaped acceleration and deceleration (selection switching)
system
117
Machine Translated by Google
11. Specifications
project Specification
•Open command signal, close command signal: 1 point each, 1a contact signal
•Multi-function input signal: 6-point, 1a or 1b contact signal (selection switching) Note) It can be assigned to
one of the following by parameter setting. Open arrival signal, close arrival signal, external abnormal reset,
input signal
safety sensor signal, abnormal close input signal, emergency open action signal, emergency stop signal, open prohibition signal,
torque hold prohibition signal, low speed opening and closing action signal, output relay linkage signal, Parameter setting
change prohibition output specification: relay output 3 points, 1a contact × 2, 1c contact × 1 (contact capacity 230V AC, 0.3 A
resistance load) Note) It can be assigned to one of the following by parameter setting. Operation signal (open command signal,
close command signal), overload alarm, abnormal alarm, low voltage alarm, arrival signal (open arrival signal, close arrival
signal), sandwich detection signal (abnormal open action, abnormal close action), emergency Open action signal, emergency
control terminal stop signal, input terminal function linkage signal, start positioning action signal Door position detection signal: two-phase input,
output signal AB two-phase input, Z-phase input Power supply: 24 V DC -10%/+15%, 0.1A The following (encoder power supply only: provided
by the elevator door controller) Output frequency, output current, output voltage, internal DC voltage, set frequency, detection
frequency, door position field, door position, open arrival position data, door open Closing times, encoder detection status,
abnormal content (4 times), input signal status, output signal status, cumulative start-up time, cumulative operating time, jamming
show
abnormal content A symbol is displayed when the protection function is activated (the abnormal content can be stored 4 times)
current limit The current limiting function can be set at 1 to 200% of the rated output current
Instantaneous overcurrent (SC1-3), overcurrent (OC1-3), overvoltage (OU1-3), undervoltage (LU), overload/electronic thermal
relay (OL), external abnormality (AU), abnormal operation (OP), encoder error (En), temperature error (OH), speed error (OSP),
trip (stop)
Protect
Stall prevention function Overcurrent stall prevention function, overvoltage stall prevention function
Ambient temperature and humidity -10 to +50°C (no freezing), below 90% RH (no condensation)
Use environment Indoor, there should be no corrosive gas, flammable gas, oil mist, dust
protective structure IP20 cabinet installation type, except for the entry holes for main circuit wires and control circuit wires.
118
Machine Translated by Google
Appendix 1
List of P field parameters
119
Machine Translated by Google
•If the acceleration time is set too short, an overcurrent may flow depending on the load status.
120
Machine Translated by Google
•If the deceleration time is set too short, an overcurrent may flow depending on the load status.
121
Machine Translated by Google
Choose to use the operation panel or external control input signal to run/stop and forward/reverse.
Setpoint command status Operation method, control circuit terminal connection diagram initial value
Run: RUN
Stop: STOP
0 panels
Forward/Reverse: Set by "rotation direction setting mode" (dr mode)
Terminal No.1: 0
Common terminal
Terminal No.2:
·When the setting value is "2", pressing the STOP key will stop the operation. At this time, the LED display is as follows.
Press the STOP key again to release from the stopped state. In this case, if the operation signal of the control terminal has been input, the
122
Machine Translated by Google
ÿPrecautions for operation control through external control input When the
setting value of parameter "P003: Operation command selection" is "2", the value of parameter "P004: Control mode selection" is different,
open close
P004=1 P004=2 or 3 door
P004=0
command signal command signal
door control (normal) control (repeat) mode door
Inverter mode
mode control (door amplitude measurement) mode
*1: Operation when both open/close command signals during door control are OFF
•Continue to operate (hold action) in the open hold area and the closed hold area. To stop operation (keep
action), please set the parameter "d030: open/close hold action stop time".
· Stop the operation in the open action area and the closed action area. To continue running, set parameter "d061:
Abnormal open/close action forced action time", parameter "d067: stop selection during open/close action". *2: When both
open/close command signals during inverter mode control are ON, the running action operation status will not change. Stop In the middle,
when the open command signal and the close command signal are both ON, the operation will not be performed. *3: Regarding the
operation when the open/close command signals are both ON during door control, the operation state is open (forward) operation. (Open
command Priority) *4: Rotation direction setting during door control (repetition) At start-up: The rotation direction is set by the open
command signal and the close command signal, and the start is started. In operation: After the open (close) arrival signal is detected, the
automatic Reverse the direction of rotation. ·The holding time at the time of arrival can be set by "parameter d065: Repetition ON
123
Machine Translated by Google
0 Inverter mode Select when operating a synchronous motor with inverter control.
1 Door control encoder mode (normal) Select when door control operation is performed using an encoder.
2 Door Control Encoder Mode (Repeat) Select when performing repeated opening and closing demonstrations.
0
3 The gate control (gate width measurement) mode is a mode for measuring the gate width.
4-door control SW mode (normal) Elevator door control using variable speed, in-position switches.
5 Gate Control SW Mode (Repeat) Select when performing repeated opening and closing demonstrations.
•When using Gate Control (Normal) mode or Gate Control (Repeat) mode, be sure to
Measurement) mode to measure the gate width and then use it.
·Do not output frequencies higher than "P007: Upper limit frequency".
124
Machine Translated by Google
·If the upper limit frequency is lower than the maximum output frequency, the upper limit frequency will
take priority. ·The lower limit frequency setting is higher than the upper limit frequency (reverse setting), the upper limit frequency
will take priority.•If the data is changed during operation, it may accelerate or decelerate according to the set value. ·If the 0Hz
hold operation is performed in the hold area, please set the lower limit frequency to 0.0Hz.
output. ·If the parameter "H002: Motor rated voltage" is changed, the set value will be changed automatically.
125
Machine Translated by Google
0 Decelerate to stop According to the stop signal, reduce the frequency according to the deceleration time and then stop
1 Free running stop Stop the output of the elevator door controller immediately according to the stop signal
When decelerating to stop the elevator door controller, set the frequency to stop the output.
•If data is changed during operation, overcurrent may flow depending on the set value and load status.
Notice.
126
Machine Translated by Google
Detect motor overload, set the action level of the electronic thermal, and stop the output of the elevator door controller. action schedule
Whether the set value has a function Functional content initial value
140% of the rated current of the elevator door controller, OL trips within 1 minute
0 none
brake
*About derating
At low speed, the cooling capacity of the motor will be reduced, this function can automatically correct the action level
*Please set according to the rated current of the applicable motor. If the parameter "H003: Motor rated current" is changed,
ÿ Example of setting current value and thermal action (when parameter P011=1)
127
Machine Translated by Google
When accelerating or decelerating, relative to the inertia of the load, if the acceleration and deceleration time is set short, the output current exceeds the OCS
When the level is high, the acceleration or deceleration time will be extended.
•When the load fluctuates rapidly and accelerates and decelerates rapidly, if an excessive current flows instantaneously, a trip may occur.
·The operating level of the overcurrent stall prevention function can be set by “P024: OCS level”. Factory setting
During deceleration, relative to the inertia of the load, if the deceleration time is set short, the deceleration can be temporarily delayed to prevent
128
Machine Translated by Google
level), the frequency will be automatically reduced. When the load returns to normal, it will automatically return to the original
frequency and continue to operate. With this parameter, the deceleration time to reduce the frequency is automatically set when
the function is ON/OFF and the output current reaches the overcurrent stall level. Use "P024: OCS level" to set the action level
129
Machine Translated by Google
Use this parameter to set the startup action when the operation signal of the external control operation is input when the power is turned on.
•According to the setting of the startup mode, when the operation signal is ON, after the power is turned on, the
There may be a sudden start (restart) when the power failure is restored, please carry out the
•According to the setting of the start mode function, when the operation signal is ON, perform
After the reset of abnormal trip, perform "reset of abnormal trip", "STOP through the panel"
function release stop state" or "reset of gate amplitude test", there may be sudden
case of restart. Please design the machine to ensure safety even if it is started suddenly.
Immediately after turning on the power, when it reaches the undervoltage level (LU level) or higher
0 run
start up.
The OP trips when the undervoltage level (LU level) or higher is reached after the power is turned on.
1 "OP" stop
Turn off the running signal once, reset it and then turn it on again to run.
after standby time After the power is turned on, it reaches the insufficient voltage level (LU level) or more, and then
0
2
run Restart after the standby time. (The standby time is set by parameter P018)
The OP trips when the undervoltage level (LU level) or higher is reached after the power is turned on.
Turn off the running signal once, reset it and then turn it on again to run.
3 "OP" stop (In this setting, when the power is turned on and the operation signal is ON, the
The operation is the same as the data "1". However, during normal startup, it can be used during standby time
start later)
130
Machine Translated by Google
131
Machine Translated by Google
Select the power failure and instantaneous power failure restart mode according to the load status and the system. Built-in standby timer
function.
Depending on the setting of restart after instantaneous stop, when the operation signal is ON, it may
suddenly start (restart) when the power is turned on after the power failure is restored. Please design the
set value Minimum 15ms or more more than 15ms minimum Minimum 100ms or less over min. 100ms (Note 2)
0 • LU trips and operates according to the setting of the startup mode. ·Display
Note 1) The minimum time when operating at the rated output current is shown. (This
Note 2) The minimum time is displayed. (The time may become longer as the rated capacity increases.) Even if the power outage time is
relatively long (about 1 minute), it may restart after the power is restored. Therefore, when using elevator door controllers,
motors, and load equipment , it should be performed after about 4 minutes (standby time + 2 minutes) after the power is restored.
132
Machine Translated by Google
133
Machine Translated by Google
and restarts (runs) after the standby time has elapsed. Use this function when you want to continue running.
After using the retry function, it may automatically start suddenly (restart). Please design the machine
Retry only for abnormal overcurrent and abnormal overheating of heat sink (SC1/SC2/SC3/OC1/
1
OC2/OC3)
0
2 Retry only for overvoltage abnormality (OU1/OU2/OU3)
Retry only for abnormal overcurrent, abnormal overheating of heat sink (SC1/SC2/SC3/OC1/OC2/
3
OC3) and abnormal overvoltage (OU1/OU2/OU3)
initial value 1
134
Machine Translated by Google
During retry, no error alarm is output. If an error still occurs even after retrying within the set number of
times, an error alarm will be issued. • If an unselected error occurs during retry, an error alarm will be
output, and the number of retries accumulated so far will be cleared.•Once the power is turned off, the
number of retries accumulated so far will be cleared. • If no error occurs for more than 5 minutes, the
135
Machine Translated by Google
Press the SET key in the action status display mode to select the display content.
0: Current display 1:
set value
Signal display mode
initial value 0
136
Machine Translated by Google
0: Output frequency
Data setting range (%)
1: Line speed
initial value 0
Set the magnification relative to the output frequency when the line speed is displayed.
you want to display a linear speed of 180 (m/min) at 24 Hz, set the magnification (K) to "7.5".
137
Machine Translated by Google
Quick action level) and the action level of the current limit function.
• The OCS level and the current limit level are the same level.
·It has nothing to do with electronic thermal level and overload detection level.
In order to "reduce motor noise" and "avoid mechanical system resonance", the carrier frequency can be changed.
If the carrier frequency is changed, the setting values of H013~H016 will be changed automatically.
138
Machine Translated by Google
ÿ Setting method
· Allocate the input signal logic of SW1 to SW6 to bit0 to bit5 of internal data, the logic of each SW ×
The sum of the added values is used as the set value, and is entered in decimal.
• The initial value is "0", and all inputs are assigned to "a contact input".
a contact input = "0": when the input signal is in the open state (terminal level is "L"), the detection is ON. b contact
input = "1": the input signal is in the closed state (terminal level is "H") ”), the detection is ON
ÿSetting example When SW1 and SW2 are b-contact input and other signals are a-contact
Set value=(0×32)+(0×16)+(0×8)+(0×4)+(1×2)+(1×1)=3
Terminal No. 9 8 7 6 5 4
bit No. 5 4 3 2 1 0
added value 32 16 8 4 2 1
The ON-OFF status of each SW changes according to the input logic setting, so when using each terminal, please fully
·Open command input (terminal No.2) and close command input (terminal No.3) are fixed to a contact input.
139
Machine Translated by Google
Control circuit
Parameter No. name Predetermined area initial value
Input terminal number
0 (asynchronous motor
P030 SW4 function selection No.7 0ÿ16
3)
0 (asynchronous motor
P031 SW5 function selection No.8 0ÿ16
4)
P032 SW6 function selection No.9 0ÿ16 0
140
Machine Translated by Google
1 open to the input signal In door control mode, it operates as an open arrival signal when SW-ON is turned on.
2 Close to the input signal In door control mode, it operates as a closing arrival signal when SW-ON is turned on.
3 open variable speed input signal In door control mode, it operates as an open shift signal when SW-ON is turned on.
4 Close the variable speed input signal In door control mode, it operates as a closing speed signal when SW-ON is turned on.
6 Safety sensor input signal Execute abnormal open action at SW-ON during closing action.
7 Abnormal close input signal During door control, it acts as an abnormal close signal under SW-ON.
9 Emergency stop input signal Emergency stop at SW-ON, and stop after displaying "E.StP".
11 Torque hold inhibit input signal adjusts the open/close reach holding torque to 0% through SW-ON.
Under SW-ON, the external (panel) change of all parameters of U/P/H/d is prohibited.
16 Parameter setting change prohibition
Even.
141
Machine Translated by Google
·Non-excitation when ON: When the coil is in the non-excited state, the relay is ON
set value
excitation De-excited
When the open command (operation signal) is ON, it is ON, and the open command (operation signal) is ON.
1 r1 Open (run) signal
signal) is OFF when OFF
When the closing command (operation signal) is ON, it is ON, and the closing command (operation signal) is ON.
2 r2 close (run) signal
signal) is OFF when OFF
4 r4 Abnormal alarm 1 ON when the elevator door controller becomes abnormal trip state
The elevator door controller becomes abnormally low voltage (LU), or stops
5 r5 Low voltage alarm 2
ON when the middle panel display turns OFF horizontal
It is ON when the encoder detection position is in the closed hold area, or is closed.
7 r7 Close arrival signal 1
ON when the arrival signal is ON
142
Machine Translated by Google
It is ON when the encoder detection position is in the closed hold area, or is closed.
9 r9 close arrival signal 2
ON when the reaching signal is ON and reaching the closing holding torque level
When the encoder detection position is in the open hold area, it is ON and detected
10 r10 open arrival signal 3
terminal, or ON when the ON arrival signal is ON
When the encoder detection position is in the closed hold area, it is ON and detected
11 r11 Close arrival signal 3
terminal, or ON when the closed arrival signal is ON
12 r12 Open clamp detection signal ON when clamp detection operation occurs, OFF when abnormal open operation is completed
13 r13 Clamping detection signal ON when clamping detection operation occurs, OFF when abnormal closing operation is completed
14 r14 Emergency open action signal ON when emergency open action is ON, ON before emergency open action is completed
15 r15 Emergency stop signal ON when the emergency stop input signal is ON, OFF when it is OFF
16 r16 ON when input terminal function linkage is set to output RY linkage function of SW function
ON when the start positioning operation starts, and when the start positioning operation is completed
17 r17 Start positioning action signal
OFF
Input the abnormal output of the elevator door controller into the main controller of the elevator main body, and perform the power on the main controller side.
· To ensure safety, even in the event of an abnormal stop, abnormal operation, or failure of the elevator door controller
143
Machine Translated by Google
P036 Password
After completing the data setting of each parameter, a password can be set to prevent accidental data changes.
initial value 0
In the case of setting a password, after pressing MODE SW in the "control state monitoring mode", the password input display changes to
"P.PS", after entering the password and pressing SET SW, the "custom setting mode" can be called out. ", "P field parameter setting mode",
"H field parameter setting mode", "d field parameter setting mode". When the MODE SW is pressed without entering the password in the
password input display "P.PS", it returns to the "operation status display mode".
*If the password is not known, it will return to "0000" after pressing the key.
/ key. (The display part flashes after the password that has been set is displayed)
144
Machine Translated by Google
key.
The subsequent operation steps are the same as the normal data change steps.
Please keep your password safe so that you don't forget it.
1 Initialize all parameters other than the H field (P field, d field parameters).
3 Set the function assignment of the custom setting mode to the assignment at the factory.
·Set the set value to a value other than "0", and press the SET key. After the data is changed, the displayed value automatically changes to "0", and the
change is completed.
145
Machine Translated by Google
When assigning the safety sensor input to the multi-function input SW1 to SW6 (terminal No.4 to 9), it is possible to set the
filter.
initial value 10
·When the setting value is increased, the anti-interference ability becomes stronger, but the response speed of the control input terminal becomes slower. lower
After setting the value, the anti-interference ability becomes weaker, but the response speed of the control input terminal becomes faster.
Set the filter constants of the control input terminals (No.2 to 9).
initial value 10
·When the setting value is increased, the anti-interference ability becomes stronger, but the response speed of the control input terminal becomes slower. lower
After setting the value, the anti-interference ability becomes weaker, but the response speed of the control input terminal becomes faster.
•When the operation is started using the open command signal (terminal No.2) and the close command signal (terminal No.3), even if the
The low setting value also has internal processing time, and the response speed is slower than other terminals.
Set the judgment torque for overspeed trip. The protection is activated when the set speed becomes a few % of the rated frequency of the motor. determination
The time is fixed at 100msec. "OSP" will be displayed during overspeed trip, and the operation will stop.
146
Machine Translated by Google
Select the acceleration/deceleration mode from linear, S-shaped (2 times, 3 times) acceleration/deceleration.
·The acceleration/deceleration time is the same regardless of the setting of the acceleration/deceleration mode (linear/S-curve acceleration/deceleration).
147
Machine Translated by Google
frequency range.
50 50Hz mode
Fixed VF mode independent of maximum output frequency and base frequency.
60 60Hz mode
148
Machine Translated by Google
initial value 15
Only valid when V/F mode is FF mode. Used to set the base frequency of the inverter.
149
Machine Translated by Google
During stop deceleration or when forward/reverse switch is performed, when the output frequency of the elevator door controller is lower than the stop
initial value 0
150
Machine Translated by Google
0 MEWTOCOL-COM
1 Modbus (RTU) 0
2 Optional panel
Note) When the setting value is "2: optional panel", the value of parameter "H049~P054" will be automatically set by the system
Certainly.
48 4800bps
96 9600bps 192
1 1 bit
1
2 2 bit
0 none
1 odd 0
2 even number
151
Machine Translated by Google
initial value 1
initial value 5
152
Machine Translated by Google
By modifying this parameter, the backup of the current parameter and the reading of the parameter from the backup area are realized.
-
0
P056 Low voltage prevents heavy hammer from hitting the door
ÿP056: Low voltage prevents heavy hammer from hitting the door
0 The function of preventing heavy hammer from hitting the door under low voltage is invalid.
0
1 The low voltage prevents the heavy hammer from hitting the door effectively.
initial value 15
153
Machine Translated by Google
initial value 10
Similar to P044. Set for torque boost during door closing action.
By setting this parameter, select whether to restart the synchronization after an encoder error occurs.
By setting this parameter, select whether to restart the synchronization after an encoder error occurs.
0 No timeout alarm.
0
1~60 Set door open overtime alarm time
Through the setting of this parameter, select when the door open signal or stop signal is received suddenly during the door closing process.
154
Machine Translated by Google
Appendix 2
H field parameter list
155
Machine Translated by Google
Factory initial
Setpoint function name action
value
Please set it when using a motor not recommended by our company. Please set the control required
1 Any synchronous motor
of each motor parameter (H002ÿH006, H010ÿH016).
Recommended synchronous motor 1 Each motor parameter (H002ÿH006, H010ÿH016) is automatically set to recommended
2 2
(50W) Motor 1 50W for use.
Recommended synchronous motor 2 Each motor parameter (H002ÿH006, H010ÿH016) is automatically set to recommended
3
(50W) For motor 2 50W.
Recommended synchronous motor 3 Each motor parameter (H002ÿH006, H010ÿH016) is automatically set to recommended
4
(80W) For motor 3 80W.
156
Machine Translated by Google
Set the rated frequency, rated current, rated voltage and number of poles of the motor to be used.
Parameter No. function name set unit Predetermined area initial value
50 (asynchronous motor
H002 Motor rated voltage 1[V] 0ÿ250
200)
1.4 (Asynchronous electrical
H003 Motor rated current 0.1[A] 0.0ÿ100.0
machine 3.6)
-
2.4.6.8.10.12.14.16 16 (asynchronous motor
H005 Number of motor poles
·18·20 6)
·If "H002: Motor rated voltage" is changed, "P008: Maximum output voltage" will be set automatically. (horse
·If "H003: Motor rated current" is changed, "P012: Thermal current" will be set automatically.
·If "H004: Motor rated frequency" is changed, "P005: Maximum output frequency" will be set automatically.
If the number of poles is less than 16, please use the motor with 1000ppr or more, and please use the motor with more than 16 poles.
Encoders with angular resolutions above 3000ppr.
157
Machine Translated by Google
number (p/r)].
set up
Parameter No. function name Predetermined area initial value
unit
•When the encoder is installed with a reducer, etc., the value obtained by dividing the number of pulses per revolution by the reduction ratio is used as the
set value.
Encoder constant (converted value of motor shaft)=[number of pulses per encoder revolution]÷[reduction ratio]
If the number of poles is less than 16, please use the motor with 1000ppr or more, and please use the motor with more than 16 poles.
158
Machine Translated by Google
Please confirm the installation state (direction) of the motor carefully before setting it.
set up
Parameter No. function name Predetermined area initial value
unit
-
H007 Motor rotation direction setting 0.1 1
Rotation direction (when the motor rotating shaft is viewed from the front)
When the set value is "0" When the set value is "1"
159
Machine Translated by Google
H008 Autotune
Auto-tuning of encoder Z-phase offset value and motor constant is possible.
set up
Parameter No. function name Setting range initial value
unit
-
H008 Autotune 0.1.2.3 0
In the mode of auto-tuning the Z-phase offset value of the encoder (H009), it returns to the operation state display mode, and press
1
RUNSW performs constant measurement.
After setting the data offset in the auto-tuning motor constant (H010, H011, H012) mode, it returns to the
2 In status display mode, press RUNSW to measure constants. 0
After measuring H010, H011, and H012, the set values of H013 to H016 can also be automatically changed.
After setting the data offset in the auto-tuning motor constant (H010, H011, H012) mode, it returns to the
In status display mode, press RUNSW to measure constants.
3
After measuring H010, H011, and H012, the set values of H013 to H016 can also be automatically changed.
After the motor-related measurement is completed, the door width measurement is performed.
•When starting auto-tuning, the inverter will automatically drive the motor to operate, so do not approach it. otherwise,
It can cause electric shock and personal injury.
If the
axis inductance", "H012: q-axis inductance".
160
Machine Translated by Google
When measuring the motor constant + Z-phase offset, set parameter H008 to "2".
For motor constant + Z-phase offset + door width measurement, set parameter H008 to "3".
161
Machine Translated by Google
4. Auto-tuning completed
When auto-tuning is over, data is automatically written to parameter H009 or H010, H011,
•When measuring motor constant & Z-phase offset value: parameters H009ÿH012
• When it cannot be tuned correctly, it will trip after displaying "tEr1" and "tEr2". Please press STOP SW to set the parameters
manually.
162
Machine Translated by Google
set up
Parameter No. function name Predetermined area initial value
unit
·Set the setting value of parameter "H008: Auto-tuning" to "1", "2" to perform auto-tuning, this parameter
·Set the setting value of parameter "H009: Auto-tuning" to "2" to perform auto-tuning, this parameter will automatically
action is set.
·Before driving the motor, please confirm whether the parameter is set correctly. When this parameter is set incorrectly, the motor may
163
Machine Translated by Google
Parameter No. function name set unit Predetermined area initial value
Change the setting of parameter "H008: Auto-tuning" to "2", execute auto-tuning, parameter "H010ÿ
·Change parameters "H010ÿH012", parameters "H013: d-axis current proportional increase", "H014: d-axis
Current integral increase", "H015: q-axis current proportional increase", "H016: q-axis current integral increase" will
is automatically set.
·If this parameter is not set correctly, the torque characteristic of the motor will not be exerted, and the motor may reverse or rotate rapidly.
• For each constant, set the average value of 1/2 of the measured values between phases (UV, VW, UW).
164
Machine Translated by Google
set up
Parameter No. function name Predetermined area initial value
unit
H013 d-axis current proportional increase - 0ÿ32000 71.1
H014 d-axis current integral increase - 0ÿ32000 228.9
H015 q-axis current proportional increase - 0ÿ32000 72.1
H016 q-axis current integral increase - 0ÿ32000 228.9
·After setting parameters "H010: Phase-to-phase resistance", "H011: d-axis inductance", "H012: q-axis inductance",
165
Machine Translated by Google
set up
Parameter No. function name Predetermined area initial value
unit
-
H017 ASR ratio increase by 1 0ÿ100.0 5.0
·Increase the setting value of H017, the tracking of the set speed will be faster, but if the setting is too large, the speed will be unstable.
·Reduce the setting value of H018, the tracking of the set speed will be faster, but if the setting is too small, the speed will be unstable
166
Machine Translated by Google
Set the operation mode after the positioning operation at startup is completed.
after finishing •After the start-up positioning operation is completed, "S.End" is displayed on the display LED, and the
0
stop Stop running. When returning to normal mode, the operation command is temporarily turned OFF.
·After the start-up positioning operation is completed, when P004=1~3, it will start after receiving the operation command. 1
Execute the initial position detection of the Z phase of the encoder, and continue to start synchronously until the
after finishing
1 Up to this point, after reaching it, it will act according to the operation command.
action
When P004=0, once decelerates to 0Hz, it will act according to the running command until it reaches 0Hz.
·When the parameter "P033~P035: RY function selection" is set to "17" or "r17", the corresponding relay
It turns ON when the positioning operation starts and turns OFF when it is completed.
167
Machine Translated by Google
·When a signal arrives, select the action when the power is restored.
•If the door is manually activated during a power failure, the position of the door is different from that at the
last power-off, so unexpected operation may occur during startup. Please fully confirm the safety and
0 Use the open/close command issued by the upper system to perform the positioning operation at startup.
When the power supply is restored, if the closing command from the upper system is ON, the door position after the power supply is restored 1
is the closed reaching position, and if the closing command is ON, the 0Hz hold action is performed based on the door position when the
1
power was turned off last time. (When the open command signal is ON, the positioning operation at startup is performed.)
• When the setting value is "1", if the door is manually operated during a power failure, the door will not operate normally because the
door position is different from the last time the power was turned off. • When used when no signal arrives, the positioning operation at
·When H004=2, even if the setting value of H022 is set to "1", the operation with the setting value of "0" will be performed.
168
Machine Translated by Google
If the positioning operation at startup is not completed within the set time, an error signal can be set.
set up
Parameter No. function name Predetermined area initial value
unit
169
Machine Translated by Google
When the pulse signal of the encoder is absent or the rotation direction of the pulse signal is different from the rotation direction of the command, the encoder will be detected.
·When abnormality is detected, one of "En1, En2, En7" will be displayed, and abnormal trip will occur.
set up
Parameter No. function name Predetermined area initial value
unit
• The initial value "0.0" is a setting that does not judge as abnormal. Error detection is not performed.
• The initial value is set to "0.0" at the time of shipment (no error detection function). When using the encoder error detection function,
• If the encoder error detection time is set too short, "En2" (encoder reverse detection error) may occur.
• In the auto-tuning state, the abnormality detection of the encoder cannot be performed when the positioning operation is started.
• If the encoder multiplier is set to 4, it will be detected at a resolution that is 4 times the encoder resolution.
0 1 octave
H025 Encoder frequency multiplication setting 0
1 4 times
170
Machine Translated by Google
set value do do
Low speed: ASR ratio increased by 1/min1 Low speed: ASR proportional increase 2/min2
2
High speed: ASR ratio increased by 3/min3 High Speed: ASR ratio increased by 4/min4
H017/H018 H017/H018
H017/H018 H027/H028
[Hz] [Hz]
Open action:
ASR ratio increase
H029/H032
ASR integration time
Close action:
H017/H018
Close action:
H027/H028
171
Machine Translated by Google
·In order to change the performance by the operation and the operation, set "1".
·To change the performance at low speed and high speed within the operating system, set the
"2". The cutting rate refers to H033 and H040.
·H026: The setting of ASR amplification is "1", "2", which can be used to set the speed inversion.
controlled increase.
set up
Parameter No. name Predetermined area initial value
unit
-
H027 ASR Scale Increase 2 0ÿ100.0 5.0
-
H029 ASR ratio increase by 3 0ÿ100.0 5.0
-
H031 ASR ratio increased by 4 0ÿ100.0 5.0
172
Machine Translated by Google
·H026: ASR Amplification cut setting "2" , Set low speed and high speed cut rate.
set up
Parameter No. name Predetermined area initial value
unit
·H033ÿH034 do not build a slope, cut the ASR increase to 1, and cut the increase.
173
Machine Translated by Google
set up
Parameter No. name Predetermined area initial value
unit
·When the door of the equipment used is heavy, please set it larger; when the door is light, please set it smaller.
·Do not start under stress in the opposite direction of rotation. If a reverse stress is applied, the positive
174
Machine Translated by Google
set up
Parameter No. name Predetermined area initial value
unit
-
H036 Retry selection when starting positioning 0.1.2 2
0 do not retry
When an error occurs in the start positioning operation in the command direction, the start positioning operation in the opposite direction is performed.
1
When an error occurs in both directions, it is "S.Err" and trips on error.
When the positioning operation cannot be completed according to the close command, the start positioning operation in the opposite direction is performed. Neither did the opposite direction
2
When the start positioning operation is completed, keep 0.0Hz.
·When operating with the setting of H036=2, be sure to set H021=1 and H022=1.
·When the setting of H036=2 becomes 0.0Hz, the start positioning operation is not completed. pass
Turn OFF the run command again, or turn ON the open command, and perform the positioning operation again. If it is completed normally,
175
Machine Translated by Google
When inputting the Z signal to the Z-phase input section of the encoder, set this parameter to "1".
set up
Parameter No. name Setting range initial value
unit
-
H037 Retry selection when starting positioning 0.1 0
It is used to set the synchronous start or positioning start mode when the electrical angle is obtained after the first power-on.
0 Synchronous start
176
Machine Translated by Google
The parameters H039ÿH043 are valid only when H038 is set to "1" and the door machine is started synchronously.
ÿH041: Encoder abnormality detection time during synchronous start When synchronous
start-up operation, there is no pulse signal of the encoder or the rotation direction of the pulse signal and the rotation direction of the command are different, the encoder abnormality
is detected.
synchronous start operation, judge the slip difference as a percentage of constant slip.
177
Machine Translated by Google
During synchronous start operation, the judgment time setting of slip judgment is satisfied.
After finishing the data setting of H parameters, in order to prevent accidental data changes, the H parameter password can be set.
initial value 0
178
Machine Translated by Google
Appendix 3
d Field parameter list
179
Machine Translated by Google
When the operation in the door control (door width measurement) mode is completed, the measurement results are stored.
Parameter No. Function name setting unit Predetermined area initial value
-
d001 Door amplitude measured value 0ÿ65535 65535
·If the set value is changed, the door control may not operate normally.
·When performing door control, be sure to set parameter "P004: Control mode selection" to "3" to execute door control
180
Machine Translated by Google
reach position and the open reach position are set between "0ÿ100".
•Specify the speed change position data during the opening and closing operations.
set up
Parameter No. function name Predetermined area initial value
unit
When no signal arrives, the movable range of the door is the same as the measured value of the door width, so it is necessary to change the opening/closing arrival
position setting value, and set the reach range width. When there is no reach range, during normal operation, the
The current door position data cannot be converted into the arrival area. In order to ensure that the data can be transformed into the reachable field, please update
181
Machine Translated by Google
d010 Closed arrival hold frequency d015 open arrival hold frequency
·d011ÿd014: Designate the running frequency (speed command) of the opening action.
·d016ÿd019: Designate the running frequency (speed command) of the closing action.
182
Machine Translated by Google
d020 open acceleration and deceleration time d024 Close acceleration and deceleration time 1
1 d021 open acceleration and deceleration time d025 Close acceleration and deceleration time 2
2 d022 open acceleration and deceleration time d026 Close acceleration and deceleration time 3
3 d023 open acceleration and deceleration time 4 d027 Close acceleration and deceleration time 4
·d020ÿd023: Specify the acceleration/deceleration time of the frequency when switching the open action.
·d024ÿd027: Specify the acceleration/deceleration time of the frequency when switching the closed action.
d025 Close acceleration and deceleration time 2 0.1[sec.] 0.0 or 0.1ÿ999.9 1.0 0.5
d026 Close acceleration and deceleration time 3 0.1[sec.] 0.0 or 0.1ÿ999.9 0.5 1.0
183
Machine Translated by Google
Specify the maximum value of the torque limit in the holding operation in proportion to the rated torque.
set up
Parameter No. function name Predetermined area initial value
unit
In the open hold area and the close hold area, after the close command signal and the close command signal are both OFF, the setting continues to open.
Time to hold the action and close the hold action. When the open hold action and close hold action are stopped, this parameter is used to set
set time.
Set value = "0": Continue running (hold action) (do not stop)
Setting value = "0.1~999" (seconds): After the set time, the operation will be stopped (maintaining action).
set up
Parameter No. function name Predetermined area initial value
unit
d030 Open/close hold action stop time 0.1[sec.] 0.0 or 0.1ÿ999.9 0.0
184
Machine Translated by Google
d031 on arrival hold standby frequency d033 on arrival hold standby time
d032 closed arrival hold standby frequency d034 closed arrival hold standby time
Specify the operating frequency when the opening action reaches the holding standby action, or the closing action reaches the holding standby action
set up
Parameter No. function name Predetermined area initial value
unit
d031 Open to hold standby frequency 0.1[Hz] 0.5ÿ250.0 2.4 (0.5 for asynchronous motor)
d032 Closed arrival hold standby frequency 0.1[Hz] 0.5ÿ250.0 2.4 (0.5 for asynchronous motor)
parameter
function name set unit Predetermined area initial value
No.
After the power is turned on, the operation signal turns ON, the operation starts at the operating frequency when the power is turned ON, and the arrival signal is detected.
set up
Parameter No. function name Predetermined area initial value
unit
185
Machine Translated by Google
Specify the frequency when operating in the gate width measurement mode.
set up
Parameter No. function name Predetermined area initial value
unit
•Be sure to use the gate width measurement frequency at low speed. Please use the factory default value (5.0Hz)
Measure the amplitude of the door, and adjust the frequency when the door is not moving and moving slowly.
When the door position data reaches the holding area, there is no arrival signal, or the open arrival signal and the closed arrival signal are simultaneously
set up
Parameter No. function name Predetermined area initial value
unit
·The factory setting value is set to "0" (no arrival SW error detection function).
• During auto-tuning and start-up positioning operations, abnormality detection cannot be performed.
186
Machine Translated by Google
• Set the detection conditions for pinch detection by current during open operation. When current pinch detection is not performed,
•As shown in the figure below, the overload level can switch the current detection level according to the output frequency.
187
Machine Translated by Google
• Specify the detection conditions for pinch detection by current during closing operation. Do not perform pinch detection using current
•As shown in the figure below, the overload level can switch the current detection level according to the output frequency.
188
Machine Translated by Google
• Set the detection conditions for pinch detection using slip during opening or closing. No use slip
Set the ratio of the target speed (set frequency) to the speed detected by the encoder (detection frequency)
set up
Parameter No. function name Predetermined area initial value
unit
Intrusion determination
d050 0.1[%] 0.0ÿ100.0 50.0
Frequency (low speed)
Entry judgment
d051 0.1[%] 0.0ÿ100.0 70.0
Frequency (high speed)
·The setting values of parameters d50, d51, and d52 are the same during the opening action and the closing action.
·When d053=0 and d054=0, the pinch detection by slip is not performed.
189
Machine Translated by Google
ÿThe difference
between the slip and target speed (set frequency) and the speed detected by the encoder (detection frequency) is called "slip" when
expressed as a ratio.
ÿAbout the setting of the trapping judgment frequency (d051, d052) The
parameter "d051, d052: trapping judgment frequency" is calculated from the ratio of the detection frequency detected by the encoder to
the target speed (set frequency).•When the frequency detected by the encoder is smaller than the set jamming judgment frequency and
exceeds the jamming detection judgment time, it is determined that a jamming door has occurred.
If the parameter "d053: clamping judgment switching frequency" is changed, the frequency lower than the value set in d053 can be set
by "parameter d050: clamping judgment frequency (low speed)" )" to switch the set detection level. ·In the initial value, d053=0.5, so the
detection level becomes the value set by "parameter d051: Interference judgment frequency (high speed)".
190
Machine Translated by Google
d055 Open the door and clamp into the maximum torque level
·Set the maximum value of torque limit when detecting jamming when opening the door when operating in door control (normal) mode.
set up
Parameter No. function name Predetermined area initial value
unit
d055 The level of the maximum moment when the door is clamped 0.1[%] 0.0ÿ500.0 250.0
•In the case of heavy load, such as lowering the set value, the motor may not drive.
·Increase the set value, it will become over-current when it is clamped, and the protection function of the elevator door controller may take effect.
191
Machine Translated by Google
•When the abnormal opening/closing operation is not executed immediately after the jamming detection, set the waiting time until the operation is executed.
During the standby time, the set frequency is 0.0Hz, and the torque holding level is 0.0%.
set up
Parameter No. function name Predetermined area initial value
unit
•When the set value is "0.0", there is no waiting time, and immediately after the jamming is detected, it switches to the abnormal open operation.
• After trapping detection, trapping detection is not performed during the standby time.
•When detecting the jamming in units of time, set the parameters "d059: Forced open action judgment time",
"d060: Forced closing action judgment time" counts the time from the elapse of the standby time.
·The setting of parameter "d056: Standby time" is invalid during emergency open operation and emergency abnormal stop. (tight
·Parameter "d076: Abnormal open/close action forced action judgment time" is a parallel count.
192
Machine Translated by Google
At startup (when door action starts) and when opening/closing action is switched (from opening action to closing action, from closing action
to the opening action), the acceleration torque is required, and the load (torque) becomes larger at the same time. In this case, set the
set up
Parameter No. function name Predetermined area initial value
unit
•In the case of heavy load, please set this parameter when a pinch action occurs before the opening/closing action is performed.
At startup (when door action starts) and when opening/closing action is switched (from opening action to closing action, from closing action
to the opening action), the acceleration torque is required, and the load (torque) becomes larger at the same time. In this case, set the
set up
Parameter No. function name Predetermined area initial value
unit
Overload detection
d057 1[ms] 100ÿ9999 300
Startup confirmation time
•In the case of heavy load, please set this parameter when a pinch action occurs before the opening/closing action is performed.
193
Machine Translated by Google
• When performing trap detection by time, specify the time when it is judged to be abnormal. We do not perform insertion of use time
·If the time from the closed arrival position to the open arrival position during the opening action is more than the set value of d059, it will be judged
It is determined that a trapping has occurred, and a forced transition is made to the abnormal closing operation.
·If the time from the open arrival position to the close arrival position during the closing action is more than the set value of d060, it will be judged
It is determined that trapping has occurred, and a forced transition is made to the abnormal opening operation.
set up
Parameter No. function name Predetermined area initial value
unit
*When the setting value is "0", the trapping detection is performed without using the time.
194
Machine Translated by Google
Select the operation when both the open and close command signals are OFF during the abnormal open operation by the trapping detection.
*Set value = "500 (seconds)": do not stop (act before reaching the open position)
set up
Parameter No. function name Predetermined area initial value
unit
The stop action of the open/close hold area is set according to the parameter "d030: open/close hold action stop time"
And action.
·Stop action during normal open/close action is set according to the setting of parameter "d067: Stop selection during open/close action"
Decide to act.
•After the abnormal opening/closing operation caused by the jamming detection is activated, set the opening arrival position/closing arrival position and then switch to the
set up
Parameter No. function name Predetermined area initial value
unit
195
Machine Translated by Google
·In case of d063, the range from the set value to 100% is the trapping detection prohibited area.
·In case of d064, the range from 0% to the set value is the trapping detection prohibited area.
set up
Parameter No. function name Predetermined area initial value
unit
sandwich checkout
d063 0.01[%] 0.00ÿ100.0 100.0
Open action prohibited area
sandwich detection
d064 0.01[%] 0.00ÿ100.0 0.0
closed motion prohibited area
• In door control (repeat) mode, set the hold action time when opening/closing arrives.
set up
Parameter No. function name Predetermined area initial value
Unit
·Door control (repeatedly) is set according to parameter "P004: Control mode selection".
196
Machine Translated by Google
Select the stop action when both the open/close command signals are OFF during the open/close action.
According to the setting of stop selection in open/close action, there will be open/close command signal
OFF, the door will not stop. Therefore, be sure to fully confirm the safety and functional operability of the elevator
·The stop action of the open/close hold area will operate according to the setting of parameter "d030: Open/close hold action stop time".•The
stop action during the abnormal open action caused by the trapping detection is performed according to the setting of the parameter "d061:
197
Machine Translated by Google
• Door control without signal arrival determines the open/closed arrival position based on slip.
• Door amplitude measurement control without signal arrival is detected by slip or current.
1 none Can be checked out, can be checked out, can be checked out 1
• When no signal arrives, no open/close arrival signal error (En4, En5) is detected.
(En3: all arrival signals are ON, En4: no open arrival signal, En5: no closed arrival signal)
·When used when no signal arrives (parameter d068=1 or 2) and when the terminal is detected, after the arrival
·d073: Be sure to set the setting value of action selection after terminal detection to 1.
198
Machine Translated by Google
•Set the frequency and time for determining the arrival of slip. The detection frequency calculated from the encoder signal, such as
From the state where the slip reaches the judgment frequency (set value) or less to the judgment time or more, it is judged that the slip has reached
up.
set up
Parameter No. function name Predetermined area initial value
unit
When the power is ON, if the slip arrival judgment malfunction occurs during door width measurement, please lower the parameter
At startup (when door action starts) and when opening/closing action is switched (from opening action to closing action, from closing action
When the slip arrival judgment malfunction occurs, please increase the setting of parameter "d071"
value.
199
Machine Translated by Google
·After detecting the arrival of the slip difference of the opening action, the set door position data is rewritten as the parameter "d001: door width setting
set up
Parameter No. function name Predetermined area initial value
unit
d072 Substitution selection for slip on arrival 0.1[sec.] 0.0 or 0.1ÿ10.0 0.5
·When the arrival is detected by the arrival signal, regardless of the setting value of the parameter d072, rewrite the parameter "d001:
100%), set to operate at the hold frequency or set to 0.0Hz after detection.
200
Machine Translated by Google
• Specify the judgment time for limit stop detection after the overload torque execution is reached.
• The judgment torque for overload detection is specified by parameters "d040 to d043, d044 to d047".
set up
Parameter No. function name Predetermined area initial value
unit
on arrival
d074 1[ms] 0 or 1 to 9999 0
Overload detection judgment time
·When no signal arrives, when the detection is performed by the load torque, the parameter "d069: Terminal detection
Specify "1 to 3" in the setting value of "Judgment selection when no signal arrives".
201
Machine Translated by Google
d076 Judgment time of forced open action when input terminal is abnormally closed
•When the abnormal closing operation is executed according to the command of the multi-function input SW, the jamming detection is performed using the time.
•If the time from the start of abnormal closing action to reaching the closing position is more than the set value, it is determined that an occurrence has occurred
set up
Parameter No. function name Predetermined area initial value
unit
*When the initial value is "0", the trapping detection at the time of abnormal closing operation is not performed.
·When the abnormal closing action is executed from the multi-function SW, the parameters "P027ÿP032" will correspond to any terminal
202
Machine Translated by Google
·According to the command of the multi-function input SW, designate the operation frequency when the abnormal closing action is executed.
set up
Parameter No. function name Predetermined area initial value
unit
input terminal
d077 0.1[Hz] 0.5ÿ250.0 6.4
Abnormal closing action frequency 1
input terminal
d078 0.1[Hz] 0.5ÿ250.0 8.0
Abnormal closing action frequency 2
input terminal
d079 0.1[Hz] 0.5ÿ250.0 7.2
Abnormal closing action frequency 3
input terminal
d080 0.1[Hz] 0.5ÿ250.0 5.6
Abnormal closing action frequency 4
·When the abnormal closing action is executed from the multi-function SW, the parameters "P027ÿP032" will correspond to any terminal
203
Machine Translated by Google
d081 Input terminal abnormal closing action acceleration and deceleration time 1
d082 Input terminal abnormal closing action acceleration and deceleration time 2
d083 Input terminal abnormal closing action acceleration and deceleration time 3
d084 Input terminal abnormal closing action acceleration and deceleration time 4
·According to the command of multi-function input SW, designate the switching frequency of operation when abnormal closing action is executed.
set up
Parameter No. function name Predetermined area initial value
unit
·When the abnormal closing action is executed from the multi-function SW, the parameters "P027ÿP032" will correspond to any terminal
204
Machine Translated by Google
·According to the command of the multi-function input SW, specify the operation frequency and acceleration/deceleration time when the emergency opening is performed.
Parameter No. function name set unit Predetermined area initial value
d086 Acceleration and deceleration time of emergency open action 0.1[sec.] 0.0 or 0.1ÿ999.9 0.5
·When the emergency open action is executed from the multi-function SW, the parameters "P027~P032" will correspond to any terminal
·According to the command of the multi-function input SW, specify the frequency of switching to the operating frequency when performing low-speed operation.
Parameter No. function name set unit Predetermined area initial value
·When the abnormal closing action is executed from the multi-function SW, the parameters "P027ÿP032" will correspond to any terminal
205
Machine Translated by Google
d039: Arrival signal SW abnormality detection time, abnormality detection has been set and set
When d068=1, the action after the arrival signal abnormality is detected can be selected.
Input the abnormal input of the elevator door controller in the main controller of the elevator main body
out, the abnormality detection of the elevator door controller is performed on the main controller side.
·Even if the elevator door controller has abnormal stop, abnormal action, or malfunction
In order to ensure safety, the design of machinery and systems must also be carried out.
· When using this function, please fully confirm the safety and
parameter
function name set unit Predetermined area initial value
No.
When an abnormality is detected, the operation continues with the action of no arrival signal (d068=2) while blinking En5.
En5 can be cleared by turning off the power, but when En5 occurs, the arrival judgment becomes closed. Arrival signal ON or
1 Judgment condition of d069. This condition will be maintained even if the power is turned OFF.
When the closing arrival signal is normally ON, the arrival judgment condition will be cleared and return to the normal ON/OFF of the closing arrival signal.
determination.
• During the start-up positioning operation, the arrival signal SW abnormality is not detected during the frequency operation when the power is turned ON.
·When abnormal output is set by RY function selection of P033~P035, while En5 is flashing
206
Machine Translated by Google
·The abnormal detection width of the closed arrival signal can be set. Above this set value, if the
parameter
function name set unit Predetermined area initial value
No.
• This set value and "d002: Closed reach position" apply to the or condition.
parameter
function name set unit Predetermined area initial value
No.
207
Machine Translated by Google
• When controlling an asynchronous motor, by setting this parameter, adjust the motor's holding capacity when the open position and the close position are in position.
current.
parameter
function name set unit Predetermined area initial value
No.
d094 When the asynchronous motor is closed, the holding torque current is 0.1[A] 0.0ÿ100.0 0.5
d095 Asynchronous motor open reaches holding torque current 0.1[A] 0.0ÿ100.0 0.4
d096 Close the door and clamp into the maximum torque level
The maximum torque value setting is inserted during door closing. Similar to d055.
set up
Parameter No. function name Predetermined area initial value
unit
d055 The level of the maximum moment when the door is clamped 0.1[%] 0.0ÿ500.0 250.0
•In the case of heavy load, such as lowering the set value, the motor may not drive.
·Increase the set value, it will become over-current when it is clamped, and the protection function of the elevator door controller may take effect.
208