0% found this document useful (0 votes)
548 views

User Manual Mu250 Graphics-1

1. The document provides an overview and technical specifications for the MU250 3-Phase Voltage Relay, including its typical application diagram, setting ranges, case dimensions, and accuracy ratings. 2. Key features of the MU250 relay include overvoltage, undervoltage, unbalance, phase loss, and phase sequence protection, with setting ranges from 1% to 25% and time delays from 0.1 to 30 seconds. 3. The front panel includes buttons for scrolling through parameters, a 4-digit LED display, and indicators for pickup, trip, and auxiliary power, allowing direct readout of settings and measurements.

Uploaded by

Hamza Amir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
548 views

User Manual Mu250 Graphics-1

1. The document provides an overview and technical specifications for the MU250 3-Phase Voltage Relay, including its typical application diagram, setting ranges, case dimensions, and accuracy ratings. 2. Key features of the MU250 relay include overvoltage, undervoltage, unbalance, phase loss, and phase sequence protection, with setting ranges from 1% to 25% and time delays from 0.1 to 30 seconds. 3. The front panel includes buttons for scrolling through parameters, a 4-digit LED display, and indicators for pickup, trip, and auxiliary power, allowing direct readout of settings and measurements.

Uploaded by

Hamza Amir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

5. Typical Application Diagram 7.

Technical Data MU250 3-Phase Voltage Relay User's Guide V2


L1
L2 Setting Ranges Brief Overview
Undervoltage : Off, 1% – 25% The Data LED showing value. Press “UP” or
L3
N Time delay for undervoltage : 0.1s – 30s “DOWN” to scroll through the parameters as
(OPTIONAL) Overvoltage : Off, 1% – 20% shown in Figure 2 and 3 (depends on L-L or L-N
Time delay for overvoltage : 0.1s – 30s h a setting).
Unbalance : Off, 3% – 20% g
1 2 3 4 5 6 7
Time delay for unbalance : 0.5s – 30s
Phase loss : Fixed time <0.5s
R1 R2 b
Phase sequence : Fixed time <0.5s
Start time delay : 0s – 999s U 12
8 9 10 11 12 13 14
MU250 c

Power Supply Input f d


Figure 5 Phase to phase voltage
MU250-415V : 380V(-25%)-415V(+20%) AC e U 23
Neutral connection is optional when Phase MU250-220V : 220V(-25%)-240V(+20%) AC
option is set to L-L. Neutral connection is MU250-110V : 100V(-25%)-120V(+20%) AC Figure 1: Front panel overview
required when Phase option is set to L-N. (refer
to Setting b - Phase) Supply frequency : 45Hz to 65Hz a – Auxiliary power Symbols
Maximum power consumption : 3VA
supply LED
U<< - Undervoltage U 31
Contacts b – Trip/Pickup LED
Contact arrangement : Change-over t<< - Undervoltage time
Contact rating : 5A, 250V AC(cosϕ=1) c – Up key delay
6. Case Dimensions Contact material : Silver alloy
Operating time : 15 ms max d – Down key U>> - Overvoltage Frequency
Expected electrical life : 100,000 operations at rated current
Figure 2: Display for L-L setting. 415V and
71 mm 70 mm Expected mechanical life : 5 x 106 operations e – Reset/Mode key t>> - Overvoltage time 50.0Hz shown as example
delay
Indicators f – Test key
20 mm Auxiliary supply : Green LED indicator - Unbalance/phase
Pickup indicator : Red LED indicator g – Function LED
Trip : 7-segment display and red LED
85 mm
45 mm

Side t - Unbalance time


Front indicators h – Data LED delay
Mechanical U 1N
Mounting : Din rail mounted
20 mm Approximate weight : 0.31kg

30 mm 20 mm 20 mm Accuracy 1. General Description


Figure 6: Case Dimensions Protection thresholds : ±3% U 2N
Time delay : 0-0.5s, ± 15% with a minimum MU250 is a voltage relay that combines overvoltage,
of 40ms
undervoltage, unbalance, phase loss, phase sequence
: 0.6s and above, ± 3%
and delay start functions. It can be connected with or
Measurements : ± 3%
without neutral wire.
U 3N
MU250 incorporates a 4-digit LED display which
allows direct numerical readout of set values, actual
measured value and system indication.

MU250 has 2 relay outputs (R1 and R2). R1 is Frequency


energized under normal operating condition. R2 can
be configured as normally energized or de-energized. Figure 3: Display for L-N setting. 240V and
Both R1 and R2 can be assigned to operate 50.0Hz shown as example
separately by various tripping elements.
a) Auto Scroll
2. Voltage and Frequency Display
Auto scroll let the display to scroll to the next
During power up, when the relay is not under tripping available parameter every 10 seconds. To toggle
condition, the display will show voltage and frequency auto scroll mode, press "UP" and "DOWN"
reading. The Function LED indicates which line/phase simultaneously.
of voltage is being displayed or shows 'F' when
frequency is being displayed.
4 1
3. Settings c) Undervoltage 4. Trip
Voltage/Frequency Display
a) Setting Display Undervoltage pickup occurs when any line to line or a) Trip Display
line to neutral voltage is less than [nominal voltage -
Trip History
When the relay is not under tripping condition, U<< %], relay trips when delay time is elapsed.
During pickup, Trip/Pickup LED blinks. During tripping
pressing “RESET/MODE” can scroll through various condition, Trip/Pickup LED on. Function LED and Data
1 U<< Undervoltage % d) Overvoltage
settings. Function LED showing number or alphabet to LED blinks with trip source as shown below:
indicate which setting is being view as shown in
Figure 4. Table 1 gives description of each setting. 2 t << Undervoltage time delay Overvoltage pickup occurs when any line to line or line
Function
to neutral voltage is more than [nominal voltage + U>> LED Data LED Description
Tip: To quickly jump back to voltage display during 3 U>> Overvoltage % %], relay trips when delay time is elapsed.
1 trip voltage Undervoltage trip
setting display, press and hold “RESET/MODE” for
more than 1.5 seconds. 4 t >> Overvoltage time delay e) Unbalance 3 trip voltage Overvoltage trip
5 Ub Unbalance trip
Unbalance is calculated as:
b) Programming Setting 5 Unbalance %
5 PL Phase loss trip
(Vmax-Vmin)/Vmin X 100% 5 PS Phase sequence trip
Step 1: Press “RESET/MODE” until the Function LED 6 t Unbalance time delay
shows the required setting. Where Vmax is the maximum voltage among the 3 t EST Test
A tstart Start time delay voltages. Vmin is the minimum voltage among the 3
Step 2: Press “UP” and “DOWN” simultaneously to Table 3: Trip display
voltages.
enter programming mode. Unbalance pickup occurs when unbalance is more
The Function LED blinks to indicates the relay is in b Phase
than set %, relay trips when delay time is elapsed. b) Trip Reset
programming mode.
c Nominal voltage
Phase Sequence trip occurs when the phase During tripping condition, press “RESET/MODE” to
Step 3: Press “UP” or “DOWN” to select the desired sequence in any 2 or all of the lines are reversed. reset the relay, the relay will reset if condition
value. d Relay R1 function
permits. If relay is set to Auto reset, the relay will
Phase Loss trip occurs when any voltage is less than reset automatically if the condition is 5% below trip
Step 4: To save the selected value, press “UP” and E Relay R2 function 70% of nominal. condition.
“DOWN” simultaneously again. It will exit the
programming mode with the Data LED displaying the
F Relay R2 type f) Starting Delay c) Trip Test
newly set value.
Starting delay is the delay time for R1 to turn on during Trip test is used to simulate a tripping condition.
To exit programming mode without saving the selected g Auto/Manual reset
power up under normal condition. Press “TEST” button and hold for 1.5s, trip LED
setting, press “RESET/MODE” once.
blinks. After 1.5 seconds, “tESt” will blink, R1 off and
Figure 4: Display mode when pressing g) Relay Function Selection R2 will operate by relay R2 type. Press
Reset/Mode “RESET/MODE” to reset.
During tripping, output contact relay R1 or R2 will be
Setting Function Setting Range Description de-energized/energized if the related tripping element is d) Trip History Display
1 U<< Undervoltage off, 1-25 % Undervoltage % from nominal voltage activated.
The setting is shown below: During Voltage and frequency display, Press
2 t<< Undervoltage delay 0.1-30 s Time delay for undervoltage “RESET/MODE” button to jump to Trip History
3 U>> Overvoltage off, 1-20 % Overvoltage % from nominal voltage Code Phase OV UV Code : Displays on Data LED Display. Display shows the previous trip status with
4 t>> Overvoltage delay 0.1-30 s Time delay for overvoltage 0 0 0 0 Phase: Unbalance, Phase Loss a 'dot' blinking at Function LED. To clear trip history,
1 0 0 1 and Phase Sequence press "UP" and "DOWN" simultaneously.
5 Unbalance off, 3-20% Unbalance %
2 0 1 0
OV : Overvoltage
6 t Unbalance delay 0.5-30 s Unbalance time delay UV : Undervoltage e) Trip Bypass Mode
3 0 1 1
A t start Starting delay 0-999 s On time delay of R1 during power up
4 1 0 0 To disable tripping due to incorrect setting, press
b Phase L-L, L-N L-L: Display and uses Line to Line voltage 5 1 0 1 “RESET/MODE” and “TEST” simultaneously during
L-N: Display and uses Line to Neutral 6 1 1 0
power up. The Trip LED slow blink to indicate Trip
voltage 0= De-activated Bypass Mode. Go into programming mode to correct
7 1 1 1 1= Activated
c Nominal Voltage 380, 400, 415 V or Nominal voltage. Value depends on L-L or the setting. Power off and on to reset the relay. The
220, 230, 240 V L-N setting Table 2: Relay function selection relay will return to normal if no button is pressed for
longer than 2 minutes.
d Relay R1 function 0-7 *Refer to Table 2
E Relay R2 function 0-7 *Refer to Table 2
F Relay R2 type 0-1 0: Normally de-energized
1: Normally energized
g Auto/Manual resetting 0=auto, 1=manual auto: auto reset when trip condition clear
manual: press "RESET/MODE" to reset
Table 1: Description of functions

2 3

You might also like