Load Calculation New

This document provides an air system sizing summary for a centralized air conditioning system in Riverside, California. It sizes the central cooling coil to have a total load of 5.6 tons (66.9 MBH) to serve a 907.6 square foot floor area with a peak cooling demand occurring in July. The minimum required outdoor air intake is calculated as 143 CFM to ventilate the six zones. Key data on the central cooling coil, supply fan, zone loads, and ventilation requirements are presented.

Uploaded by

Naqqash Sajid
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
124 views

Load Calculation New

This document provides an air system sizing summary for a centralized air conditioning system in Riverside, California. It sizes the central cooling coil to have a total load of 5.6 tons (66.9 MBH) to serve a 907.6 square foot floor area with a peak cooling demand occurring in July. The minimum required outdoor air intake is calculated as 143 CFM to ventilate the six zones. Key data on the central cooling coil, supply fan, zone loads, and ventilation requirements are presented.

Uploaded by

Naqqash Sajid
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Air System Sizing Summary for centralized airconditioning

Project Name: miran 10/23/2020


Prepared by: Mechanical Engineering 09:14AM

Air System Information


Air System Name centralized airconditioning Number of zones 1
Equipment Class SPLT AHU Floor Area 907.6 ft²
Air System Type VAV Location Riverside, California

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Peak zone sensible load
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.6 Tons Load occurs at Jul 1300
Total coil load 66.9 MBH OA DB / WB 97.8 / 67.0 °F
Sensible coil load 65.1 MBH Entering DB / WB 77.3 / 62.0 °F
Coil CFM at Jul 1300 2857 CFM Leaving DB / WB 55.0 / 53.6 °F
Max block CFM at Jul 1300 3150 CFM Coil ADP 52.5 °F
Sum of peak zone CFM 3150 CFM Bypass Factor 0.100
Sensible heat ratio 0.973 Resulting RH 44 %
ft²/Ton 162.8 Design supply temp. 55.0 °F
BTU/(hr-ft²) 73.7 Zone T-stat Check 1 of 1 OK
Water flow @ 10.0 °F rise N/A Max zone temperature deviation 0.0 °F

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max CFM at Jul 1300 3150 CFM Fan motor BHP 0.00 BHP
Standard CFM 2979 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 3.47 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 143 CFM CFM/person 11.92 CFM/person
CFM/ft² 0.16 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

Air System Information


Air System Name centralized airconditioning Number of zones 1
Equipment Class SPLT AHU Floor Area 907.6 ft²
Air System Type VAV Location Riverside, California

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Peak zone sensible load
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 64.3 3150 143 Jul 1300 36.4 907.6 3.47

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load gpm Load gpm Airflow
Zone Name (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 38.6 - 0.0 - 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Bedroom 2 1 9.0 Jul 1300 439 5.1 110.0 3.99
Bedroom 3 1 8.2 Jul 1300 403 4.6 94.6 4.27
Dinningroom and kitchen 1 13.3 Jul 1300 652 7.5 210.0 3.11
Livingroom 1 15.5 Jul 1300 758 8.7 255.0 2.97
master bedroom 1 11.5 Jul 1300 562 6.6 168.0 3.34
Hall 1 6.9 Jul 1300 336 3.9 70.0 4.79

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2010
Design Condition Minimum flow (heating)
Occupant Diversity (D) 1.000
Uncorrected Outdoor Air Intake (Vou) 114 CFM
System Ventilation Efficiency (Ev) 0.800
Outdoor Air Intake (Vot) 143 CFM

2. Space Ventilation Analysis Table


Space Area Time People Breathing
Minimum Floor Outdoor Averaged Outdoor Air Space Zone Space
Supply Air Area Air Rate Occupancy Air Rate Distribution Outdoor Air Outdoor Air Ventilation
(CFM) (ft²) (CFM/ft²) (Occupants) (CFM/person) Effectiveness (CFM) (CFM) Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Zone 1
Bedroom 2 1 21 110.0 0.06 2.0 5.00 0.80 21 17 0.800
Bedroom 3 1 20 94.6 0.06 2.0 5.00 0.80 20 16 0.800
Dinningroom and kitchen 1 28 210.0 0.06 2.0 5.00 0.80 28 23 0.800
Livingroom 1 32 255.0 0.06 2.0 5.00 0.80 32 25 0.800
master bedroom 1 25 168.0 0.06 2.0 5.00 0.80 25 20 0.800
Hall 1 18 70.0 0.06 2.0 5.00 0.80 18 14 0.800
Totals (incl. Space Multipliers) 143 114 0.800

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 639 - 30 ft² - -
Wall Transmission 2489 ft² 11703 - 2489 ft² 19917 -
Roof Transmission 908 ft² 33990 - 908 ft² 14310 -
Window Transmission 30 ft² 317 - 30 ft² 635 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 144 ft² 776 - 144 ft² 1555 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1098 W 3747 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 10236 - 0 0 -
People 12 2940 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 64348 2460 - 36417 0
Zone Conditioning - 62276 2460 - 34853 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2857 CFM 0 - 143 CFM 0 -
Ventilation Load 130 CFM 2844 -665 6 CFM 229 0
Supply Fan Load 2857 CFM 0 - 143 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 65120 1795 - 35083 0
Central Cooling Coil - 65120 1796 - -1753 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 36836 -
>> Total Conditioning - 65120 1796 - 35083 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Bedroom 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 319 - 15 ft² - -
Wall Transmission 339 ft² 1594 - 339 ft² 2750 -
Roof Transmission 110 ft² 4120 - 110 ft² 1734 -
Window Transmission 15 ft² 158 - 15 ft² 318 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 133 W 454 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8971 410 - 5061 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Bedroom 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 51 0.245 - 176 - 450
WINDOW 1 15 0.588 0.811 158 319 318
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 90 0.222 - 336 - 719
E EXPOSURE
WALL 99 0.222 - 557 - 791
W EXPOSURE
WALL 99 0.222 - 525 - 791
H EXPOSURE
ROOF 110 0.438 - 4120 - 1734

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Bedroom 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 319 - 15 ft² - -
Wall Transmission 314 ft² 1505 - 314 ft² 2506 -
Roof Transmission 95 ft² 3543 - 95 ft² 1492 -
Window Transmission 15 ft² 158 - 15 ft² 318 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 114 W 391 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8241 410 - 4574 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Bedroom 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 38 0.222 - 133 - 307
WINDOW 2 15 0.588 0.811 158 319 318
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 77 0.222 - 289 - 618
E EXPOSURE
WALL 99 0.222 - 557 - 791
W EXPOSURE
WALL 99 0.222 - 525 - 791
H EXPOSURE
ROOF 95 0.438 - 3543 - 1492

Hourly Analysis Program v4.90 Page 6 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' Dinningroom and kitchen '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 498 ft² 2266 - 498 ft² 3977 -
Roof Transmission 210 ft² 7865 - 210 ft² 3311 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 254 W 867 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13323 410 - 7547 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' Dinningroom and kitchen '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 111 0.222 - 384 - 886
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 135 0.222 - 505 - 1078
E EXPOSURE
WALL 126 0.222 - 709 - 1006
W EXPOSURE
WALL 126 0.222 - 669 - 1006
H EXPOSURE
ROOF 210 0.438 - 7865 - 3311

Hourly Analysis Program v4.90 Page 7 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' Livingroom '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 552 ft² 2561 - 552 ft² 4408 -
Roof Transmission 255 ft² 9550 - 255 ft² 4021 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 309 W 1053 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 15489 410 - 8688 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' Livingroom '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 111 0.222 - 384 - 886
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 135 0.222 - 505 - 1078
E EXPOSURE
WALL 153 0.222 - 861 - 1222
W EXPOSURE
WALL 153 0.222 - 812 - 1222
H EXPOSURE
ROOF 255 0.438 - 9550 - 4021

Hourly Analysis Program v4.90 Page 8 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' master bedroom '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 468 ft² 2158 - 468 ft² 3737 -
Roof Transmission 168 ft² 6292 - 168 ft² 2649 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 203 W 694 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 11469 410 - 6645 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' master bedroom '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 96 0.222 - 332 - 767
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 120 0.222 - 449 - 958
E EXPOSURE
WALL 126 0.222 - 709 - 1006
W EXPOSURE
WALL 126 0.222 - 669 - 1006
H EXPOSURE
ROOF 168 0.438 - 6292 - 2649

Hourly Analysis Program v4.90 Page 9 of 13


Space Design Load Summary for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' Hall '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 97.8 °F / 67.0 °F HEATING OA DB / WB 34.0 °F / 28.5 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 318 ft² 1618 - 318 ft² 2539 -
Roof Transmission 70 ft² 2622 - 70 ft² 1104 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 129 - 24 ft² 259 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 85 W 289 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6854 410 - 3902 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' Hall '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 21 0.222 - 73 - 168
DOOR 24 0.300 - 129 - 259
S EXPOSURE
WALL 45 0.222 - 168 - 359
E EXPOSURE
WALL 126 0.222 - 709 - 1006
W EXPOSURE
WALL 126 0.222 - 669 - 1006
H EXPOSURE
ROOF 70 0.438 - 2622 - 1104

Hourly Analysis Program v4.90 Page 10 of 13


System Psychrometrics for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

July DESIGN COOLING DAY, 1300

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 97.8 0.00794 130 400 2844 -665
Vent - Return Mixing Outlet 77.3 0.00903 2857 1199 - -
Preheat Coil Outlet 77.3 0.00903 2857 1199 0 -
Central Cooling Coil Outlet 55.0 0.00889 2857 1199 65120 1796
Supply Fan Outlet 55.0 0.00889 2857 1199 0 -
Cold Supply Duct Outlet 55.0 0.00889 2857 1199 - -
Zone Air - 76.3 0.00908 2857 1237 62276 2460
Return Plenum Outlet 76.3 0.00908 2857 1237 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.021 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4488.5 BTU/(hr-CFM)
Site Altitude = 1539.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 64348 Cooling 62276 76.3 2857 1237 0 0

Hourly Analysis Program v4.90 Page 11 of 13


System Psychrometrics for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 34.0 0.00216 6 400 -229 0
Vent - Return Mixing Outlet 67.0 0.00216 143 609 - -
Preheat Coil Outlet 67.0 0.00216 143 609 0 -
Central Cooling Coil Outlet 55.0 0.00216 143 609 1753 0
Supply Fan Outlet 55.0 0.00216 143 609 0 -
Cold Supply Duct Outlet 55.0 0.00216 143 609 - -
Zone Air - 68.6 0.00216 143 619 -34853 0
Return Plenum Outlet 68.6 0.00216 143 619 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.021 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4488.5 BTU/(hr-CFM)
Site Altitude = 1539.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -36417 Heating -34853 68.6 143 619 36836 0

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for centralized airconditioning
Project Name: miran 10/23/2020
Prepared by: Mechanical Engineering 09:14AM

Location: Riverside, California


Altitude: 1539.0 ft.
Data for: July DESIGN COOLING DAY, 1300
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

0.012

34 52 0.010
1
0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v4.90 Page 13 of 13