Lighting Calculation Sheet

This document provides a step-by-step calculation to determine the number of luminaires required for a room. It lists the room dimensions, applicable height, room index, and other factors such as reflectance, utilization factor, light loss factor, and lumens from lamps. Based on the room being 18 meters long and 8 meters wide, with a room index of 3.69, utilization factor of 0.63, and required lux level of 100, the calculation determines that 13.1 luminaires are required, which is 5.4 luminaires per length and 2.4 luminaires per width.

Uploaded by

nirmalb21
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views

Lighting Calculation Sheet

This document provides a step-by-step calculation to determine the number of luminaires required for a room. It lists the room dimensions, applicable height, room index, and other factors such as reflectance, utilization factor, light loss factor, and lumens from lamps. Based on the room being 18 meters long and 8 meters wide, with a room index of 3.69, utilization factor of 0.63, and required lux level of 100, the calculation determines that 13.1 luminaires are required, which is 5.4 luminaires per length and 2.4 luminaires per width.

Uploaded by

nirmalb21
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

CALCULATION OF NUMBER OF LUMINAIRES REQUIRED FOR A ROOM

LENGTH OF ROOM (metre) 18

WIDTH OF ROOM (metre) 8

VALID

APPLICABLE HEIGHT OF ROOM (metre) 1.5 Height is considered as vertical distance from luminaire to desk or bench surface where illumination is expected.

ROOM INDEX (K) 3.69

VALID

REFER LUMINAIRE CATALOGUE FOR UTILISATION FACTOR OF LUMINAIRE ELSE REFER BELOW SHOWN TABLE & STEPS TO ASESS UTILISATION FACTOR FOR AREA UNDER CONSIDERATION
For the horizontal row select the reflectance that best describes the room.
For the vertical column select the room index value K as calculated above.
The utilisation factor for this fitting in this room is where the row and column intersect.

Ceiling Walls Floor

Air
REFLECTANCE VALUES TABLE Conditioned
Office 0.7 0.5 0.2

Industrial 0.5 0.3 0.2


Room
Index
Reflectance (K)
UTILIZATION FACTOR TABLE
(FOR 2x36 LUMINARIES) Ceiling Wall Floor 0.75 1 1.25 1.5 2 2.5 3 4 5
0.5 0.3 0.2 0.3 0.37 0.42 0.46 0.52 0.56 0.59 0.63 0.66

UTILISATION FACTOR AS ASSESSED 0.63

LUX LEVEL REQUIRED (lux) 100

LIGHT LOSS FACTOR (refer table below) 0.7

LIGHT LOSS FACTOR


Air
Conditioned 0.8
Office
Clean
TYPICAL LLF VALUES Industrial
0.7

Dirty
0.6
Industrial

Page 1 of 4
CALCULATION OF NUMBER OF LUMINAIRES REQUIRED FOR A ROOM

LUMENS FROM LAMPS IN ONE FITTING 2500


(refer table below for typical values)

Standard Triphos
Lumen
outputs of 18 Watt / 1300
fluorescent 1150 Lumens Lumens
lamps

36 Watt / 3350
3000 Lumens Lumens

Lumen
18 Watt /
output of PL
1200 Lumens
lamps

36 Watt /
2900 Lumens

NUMBER OF LUMINAIRES REQUIRED 13.1

LUMINAIRES REQUIRED/LENGTH 5.4

LUMINAIRES REQUIRED/WIDTH 2.4

Page 2 of 4
ONSIDERATION

Page 3 of 4
foot metre
10 3.048