Product Datasheet: Circuit Breaker Compact Ns800N, 50 Ka at 415 Vac, Micrologic 2.0 A Trip Unit, 800 A, Fixed, 3 Poles 3D

This document provides specifications for a ComPact NS800N 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 800 A, fixed, 3 poles 3d circuit breaker. Key details include: - Rated for 800A at 50°C, 690V AC, with 50kA rated ultimate short-circuit breaking capacity. - Includes a Micrologic 2.0 A electronic trip unit with long-time and instantaneous protection functions. - Measures 210mm wide, 327mm high, 147mm deep, and weighs 14kg.

Uploaded by

ahmed elsheikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views3 pages

Product Datasheet: Circuit Breaker Compact Ns800N, 50 Ka at 415 Vac, Micrologic 2.0 A Trip Unit, 800 A, Fixed, 3 Poles 3D

This document provides specifications for a ComPact NS800N 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 800 A, fixed, 3 poles 3d circuit breaker. Key details include: - Rated for 800A at 50°C, 690V AC, with 50kA rated ultimate short-circuit breaking capacity. - Includes a Micrologic 2.0 A electronic trip unit with long-time and instantaneous protection functions. - Measures 210mm wide, 327mm high, 147mm deep, and weighs 14kg.

Uploaded by

ahmed elsheikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Product datasheet 33233

Characteristics circuit breaker ComPact NS800N, 50 kA at 415


VAC, Micrologic 2.0 A trip unit, 800 A, fixed,3
poles 3d

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range ComPact
Product name ComPact NS
Range of product ComPact NS630b...1600
Device short name Compact NS800N
Product or component type Circuit breaker
Device application Distribution
Number of poles 3P
Protected poles description 3d
(In) rated current up to 65 °C 800 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
Trip unit name Micrologic 2.0 A
Trip unit technology Electronic
Trip unit protection functions LI
Control type Rotary handle
Toggle
Circuit breaker mounting mode Fixed

Mar 10, 2021


1
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Mechanical durability 10000 cycles
Electrical durability 2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
Power losses 15 W
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 70 mm
Protection type L : for overload protection (long time)
I : for instantaneous short-circuit protection
Trip unit rating 800 A at 50 °C
Long-time pick-up adjustment type Ir Adjustable 9 settings
(thermal protection)
[Ir] long-time protection pick-up 0.4...1 x In
adjustment range
Long-time protection delay adjustment Adjustable 9 settings
type tr
[Tr] long-time protection delay 12.5…600 s at 1.5 x Ir
adjustment range 0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
Thermal memory 20 mn
Instantaneous protection pick-up Adjustable
adjustment type Ii
[Ii] instantaneous protection pick-up 1.5...10 x Ir
adjustment range
Earth-leakage protection Without
Zone selective interlocking ZSI With
Auxiliary contact composition 1 NO/NC
Local signalling 4 LEDs (red) for fault indication
1 LED (yellow) for overload
Display type LCD display
Type of measurement Ammeter
Width (W) 210 mm
Height (H) 327 mm
Depth (D) 147 mm
Net weight 14 kg

Environment
Standards EN/IEC 60947-2
Product certifications ASEFA
ASTA
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for operation -25…70 °C

2
Ambient air temperature for storage -40…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating
2000 m...5000 m with derating

Packing Units
Package 1 Weight 12.761 kg
Package 1 Height 3.000 dm
Package 1 width 4.000 dm
Package 1 Length 6.000 dm

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

Contractual warranty
Warranty 18 months