REF615 - Ordering Data
REF615 - Ordering Data
REF615
Product version: 4.0 FP1
22. IED case and IED plug-in unit on the upper part of the plug-in-unit. An order
For safety reasons, the IED cases for current number label is placed on the side of the plug-in
measuring IEDs are provided with automatically unit as well as inside the case. The order number
operating contacts for short-circuiting the CT consists of a string of codes generated from the
secondary circuits when a IED unit is withdrawn IED's hardware and software modules.
from its case. The IED case is further provided
with a mechanical coding system preventing Use the ordering key information to generate the
current measuring IED units from being inserted order number when ordering complete IEDs.
into a IED case for a voltage measuring IED unit
and vice versa, i.e. the IED cases are assigned to
a certain type of IED plug-in unit.
HBFFAEAGBCC1BCA11E
# Description
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired and
installed in a 19” equipment panel. Not available for standard K
configuration “G”.
615 series IED (including case) with test switch, wired and in-
stalled in a mounting bracket for CombiFlex rack mounting (RGHT L
19” 4U variant C). Not available for standard configuration “G”.
2 Standard
IEC B
3 Main application
Feeder protection and control F
IECA070913 V8 EN
70 ABB
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1
The standard configuration determines the I/O hardware and available options. HBFFAEAGBCC1BCA11E
The example below shows standard configuration “F” with chosen options.
# Description
4-8 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Non-directional O/C and directional E/F protection and CB control
B = Non-directional O/C and directional E/F protection, CB condition monitor-
ing and control and with the optional I/O module control of two network objects
C = Non-directional O/C and non-directional E/F protection and CB control
D = Non-directional O/C and non-directional E/F protection, CB condition
monitoring and control and with the optional I/O module control of two network
objects
E = Non-directional O/C and directional E/F protection with phase-voltage
based measurements, CB condition monitoring and control
F = Directional O/C and directional E/F protection with phase-voltage based
measurements, undervoltage and overvoltage protection, CB condition moni-
toring and control
G = Directional O/C and directional E/F protection, phase-voltage based pro-
tection and measurement functions, CB condition monitoring and control and
(sensor inputs)
H = Non-directional O/C and non-directional E/F protection, phase-voltage and
frequency based protection and measurement functions, synchro check, CB
condition monitoring and control
J = Directional O/C and directional E/F protection, phase-voltage and frequen-
cy based protection and measurement functions, synchro check, CB condition
monitoring and control
Std. conf. I/O options
A 4I + Uo (Io 1/5 A) + 3 BI + 6 BO AAAAA
A 4I + Uo (Io 0.2/1 A) + 3 BI + 6 BO AABAA
B 4I +Uo (Io 1/5 A) + 11 BI + 10 BO BAAAC
B 4I +Uo (Io 1/5 A) + 17 BI + 13 BO BAAAE*
B 4I +Uo (Io 0.2/1 A) + 11 BI + 10 BO BABAC
B 4I +Uo (Io 0.2/1 A) + 17 BI + 13 BO BABAE*
C 4I (Io 1/5 A) + 4 BI + 6 BO CACAB
C 4I (Io 0.2/1 A) + 4 BI + 6 BO CADAB
D 4I (Io 1/5 A) + 12 BI + 10 BO DACAD
D 4I (Io 1/5 A) + 18 BI + 13 BO DACAF*
D 4I (Io 0.2/1 A) + 12 BI + 10 BO DADAD
D 4I (Io 0.2/1 A) + 18 BI + 13 BO DADAF*
E 4I (Io 1/5 A) + 5U + 16 BI + 10 BO EAEAG
E 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO EAFAG
F 4I (Io 1/5 A) + 5U + 16 BI + 10 BO FAEAG
F 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO FAFAG
G 3Is + 3Us +Io (Io 0.2/1 A) + 8 BI + 10 BO GDAAH
H 4I (Io 1/5 A) + 5U + 16 BI + 10 BO HAEAG
H 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO HAFAG
J 4I (Io 1/5 A) + 5U + 16 BI + 10 BO JAEAG
J 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO JAFAG
ABB 71
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1
The communication module hardware determines the available communication proto- HBFFAEAGBCC1BCA11E
cols. Choose the hardware from one of the rows below to define the digits # 9-10.
# Description
9 Communication modules (Serial/Ethernet)
-
10 Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B +
AB
Ethernet 100Base-TX (1 x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST), incl. an RS-485 connector and an input for
BN
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX
(1 x RJ-45) + Serial RS-485 connector, RS-232/485 D-Sub
BB
9 connector + input for IRIG-B (cannot be combined with arc
protection)
Serial glass fibre (ST) + Ethernet 100Base-TX
BD1)
(3 x RJ-45) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC1)
+ 1 x LC) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE1)
+ 2 x LC) with HSR/PRP
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX and -FX (2 x RJ-45 + 1 x LC) with HSR/
NC1)
PRP
Ethernet 100Base-TX (3 x RJ-45) with HSR/PRP ND1)
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) with HSR/
NE1)
PRP
No communication module NN
1) = HSR/PRP functionality is only available for version 4.0 FP1 (digit #17-18 = 1E)
If serial communication is chosen, please choose a serial communication module including Ethernet (for example “BC”) if a service
bus for PCM600 or the WebHMI is required.
GUID-2B09FD03-F732-4AF6-BCC1-D3473FA2667C V3 EN
HBFFAEAGBCC1BCA11E
# Description
11 Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a com- A
munication module )
Modbus
B
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + Modbus
C
(for Ethernet or serial + Ethernet communication modules)
IEC 60870-5-103
D
(for serial or Ethernet + serial communication modules)
DNP3
E
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + IEC 60870-5-103
G1)
(for serial + Ethernet communication modules)
IEC 61850 + DNP3
H1)
(for Ethernet or serial + Ethernet communication modules)
72 ABB
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1
HBFFAEAGBCC1BCA11E
# Description
12 Language
English 1
English and German 3
English and Swedish 4
English and Spanish 5
English and Russian 6
English and Polish 7
English and Portuguese (Brazilian) 8
English and Italian A
English and French C
English and Czech E
13 Front panel
Small LCD A
Large LCD with single line diagram (SLD) B
14 Option 1
Auto-reclosing A
Arc protection (requires a communication module, cannot be
B
combined with communication modules BN or BB)
Arc protection and auto-reclosing (requires a communication
module, cannot be combined with communication modules BN, C
BB)
Power quality (only for std configuration J) D
Power quality and auto-reclosing (only for std configuration J) E
Power quality and arc protection (only for std configuration J,
requires a communication module, cannot be combined with F
communication modules BN or BB)
Power quality, arc protection and auto-reclosing (only for std
configuration J, requires a communication module, cannot be G
combined with communication modules BN or BB)
None N
15 Option 2
Directional earth-fault protection (only for std configuration: A, B,
A
E, F, G, J)
Admittance based earth-fault protection (only for std configura-
B
tion: A, B, E, F, G, J)
Wattmetric based earth-fault protection and directional earth-fault
C
protection (only for std configuration: A, B, E, F, G, J)
Harmonics based earth-fault protection and directional earth-fault
D
protection (only for std configuration: B, F, J)
Harmonics based earth-fault protection (only for std configuration:
E
D)
None (only for std configuration: C, D, H) N
16 Power supply
48...250 V DC, 100...240 V AC 1
24...60 V DC 2
17 Version
-
18 Version 4.0 XE
Version 4.0 FP1 1E
IECA070914 V9 EN
ABB 73