REF615 - Ordering Data

The document provides information on ordering feeder protection and control IEDs (Intelligent Electronic Devices). It describes the components that make up the order number, including the IED type, standard, main application, configuration, and communication module. The order number follows a specific format and string of codes to identify the hardware and software modules that make up the complete IED being ordered.

Uploaded by

keglobal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
92 views

REF615 - Ordering Data

The document provides information on ordering feeder protection and control IEDs (Intelligent Electronic Devices). It describes the components that make up the order number, including the IED type, standard, main application, configuration, and communication module. The order number follows a specific format and string of codes to identify the hardware and software modules that make up the complete IED being ordered.

Uploaded by

keglobal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Feeder Protection and Control 1MRS756379 M

REF615
Product version: 4.0 FP1

22. IED case and IED plug-in unit on the upper part of the plug-in-unit. An order
For safety reasons, the IED cases for current number label is placed on the side of the plug-in
measuring IEDs are provided with automatically unit as well as inside the case. The order number
operating contacts for short-circuiting the CT consists of a string of codes generated from the
secondary circuits when a IED unit is withdrawn IED's hardware and software modules.
from its case. The IED case is further provided
with a mechanical coding system preventing Use the ordering key information to generate the
current measuring IED units from being inserted order number when ordering complete IEDs.
into a IED case for a voltage measuring IED unit
and vice versa, i.e. the IED cases are assigned to
a certain type of IED plug-in unit.

23. Selection and ordering data


The IED type and serial number label identifies the
protection IED. The label is placed above the HMI

HBFFAEAGBCC1BCA11E

# Description
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired and
installed in a 19” equipment panel. Not available for standard K
configuration “G”.
615 series IED (including case) with test switch, wired and in-
stalled in a mounting bracket for CombiFlex rack mounting (RGHT L
19” 4U variant C). Not available for standard configuration “G”.

2 Standard
IEC B
3 Main application
Feeder protection and control F

IECA070913 V8 EN

70 ABB
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1

The standard configuration determines the I/O hardware and available options. HBFFAEAGBCC1BCA11E
The example below shows standard configuration “F” with chosen options.

# Description
4-8 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Non-directional O/C and directional E/F protection and CB control
B = Non-directional O/C and directional E/F protection, CB condition monitor-
ing and control and with the optional I/O module control of two network objects
C = Non-directional O/C and non-directional E/F protection and CB control
D = Non-directional O/C and non-directional E/F protection, CB condition
monitoring and control and with the optional I/O module control of two network
objects
E = Non-directional O/C and directional E/F protection with phase-voltage
based measurements, CB condition monitoring and control
F = Directional O/C and directional E/F protection with phase-voltage based
measurements, undervoltage and overvoltage protection, CB condition moni-
toring and control
G = Directional O/C and directional E/F protection, phase-voltage based pro-
tection and measurement functions, CB condition monitoring and control and
(sensor inputs)
H = Non-directional O/C and non-directional E/F protection, phase-voltage and
frequency based protection and measurement functions, synchro check, CB
condition monitoring and control
J = Directional O/C and directional E/F protection, phase-voltage and frequen-
cy based protection and measurement functions, synchro check, CB condition
monitoring and control
Std. conf. I/O options
A 4I + Uo (Io 1/5 A) + 3 BI + 6 BO AAAAA
A 4I + Uo (Io 0.2/1 A) + 3 BI + 6 BO AABAA
B 4I +Uo (Io 1/5 A) + 11 BI + 10 BO BAAAC
B 4I +Uo (Io 1/5 A) + 17 BI + 13 BO BAAAE*
B 4I +Uo (Io 0.2/1 A) + 11 BI + 10 BO BABAC
B 4I +Uo (Io 0.2/1 A) + 17 BI + 13 BO BABAE*
C 4I (Io 1/5 A) + 4 BI + 6 BO CACAB
C 4I (Io 0.2/1 A) + 4 BI + 6 BO CADAB
D 4I (Io 1/5 A) + 12 BI + 10 BO DACAD
D 4I (Io 1/5 A) + 18 BI + 13 BO DACAF*
D 4I (Io 0.2/1 A) + 12 BI + 10 BO DADAD
D 4I (Io 0.2/1 A) + 18 BI + 13 BO DADAF*
E 4I (Io 1/5 A) + 5U + 16 BI + 10 BO EAEAG
E 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO EAFAG
F 4I (Io 1/5 A) + 5U + 16 BI + 10 BO FAEAG
F 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO FAFAG
G 3Is + 3Us +Io (Io 0.2/1 A) + 8 BI + 10 BO GDAAH
H 4I (Io 1/5 A) + 5U + 16 BI + 10 BO HAEAG
H 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO HAFAG
J 4I (Io 1/5 A) + 5U + 16 BI + 10 BO JAEAG
J 4I (Io 0.2/1 A) + 5U + 16 BI + 10 BO JAFAG

* = The optional I/O module included.


IECA070915 V9 EN

ABB 71
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1

The communication module hardware determines the available communication proto- HBFFAEAGBCC1BCA11E
cols. Choose the hardware from one of the rows below to define the digits # 9-10.

# Description
9 Communication modules (Serial/Ethernet)
-
10 Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B +
AB
Ethernet 100Base-TX (1 x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST), incl. an RS-485 connector and an input for
BN
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX
(1 x RJ-45) + Serial RS-485 connector, RS-232/485 D-Sub
BB
9 connector + input for IRIG-B (cannot be combined with arc
protection)
Serial glass fibre (ST) + Ethernet 100Base-TX
BD1)
(3 x RJ-45) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC1)
+ 1 x LC) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE1)
+ 2 x LC) with HSR/PRP
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX and -FX (2 x RJ-45 + 1 x LC) with HSR/
NC1)
PRP
Ethernet 100Base-TX (3 x RJ-45) with HSR/PRP ND1)
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) with HSR/
NE1)
PRP
No communication module NN

1) = HSR/PRP functionality is only available for version 4.0 FP1 (digit #17-18 = 1E)

If serial communication is chosen, please choose a serial communication module including Ethernet (for example “BC”) if a service
bus for PCM600 or the WebHMI is required.
GUID-2B09FD03-F732-4AF6-BCC1-D3473FA2667C V3 EN

HBFFAEAGBCC1BCA11E

# Description
11 Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a com- A
munication module )
Modbus
B
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + Modbus
C
(for Ethernet or serial + Ethernet communication modules)
IEC 60870-5-103
D
(for serial or Ethernet + serial communication modules)
DNP3
E
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + IEC 60870-5-103
G1)
(for serial + Ethernet communication modules)
IEC 61850 + DNP3
H1)
(for Ethernet or serial + Ethernet communication modules)

1) = Only available for version 4.0 FP1 (digit #17-18 = 1E)


GUID-45F9436D-9C24-48C1-A5F5-77B0EA230FB2 V3 EN

72 ABB
Feeder Protection and Control 1MRS756379 M
REF615
Product version: 4.0 FP1

HBFFAEAGBCC1BCA11E

# Description
12 Language
English 1
English and German 3
English and Swedish 4
English and Spanish 5
English and Russian 6
English and Polish 7
English and Portuguese (Brazilian) 8
English and Italian A
English and French C
English and Czech E
13 Front panel
Small LCD A
Large LCD with single line diagram (SLD) B
14 Option 1
Auto-reclosing A
Arc protection (requires a communication module, cannot be
B
combined with communication modules BN or BB)
Arc protection and auto-reclosing (requires a communication
module, cannot be combined with communication modules BN, C
BB)
Power quality (only for std configuration J) D
Power quality and auto-reclosing (only for std configuration J) E
Power quality and arc protection (only for std configuration J,
requires a communication module, cannot be combined with F
communication modules BN or BB)
Power quality, arc protection and auto-reclosing (only for std
configuration J, requires a communication module, cannot be G
combined with communication modules BN or BB)
None N
15 Option 2
Directional earth-fault protection (only for std configuration: A, B,
A
E, F, G, J)
Admittance based earth-fault protection (only for std configura-
B
tion: A, B, E, F, G, J)
Wattmetric based earth-fault protection and directional earth-fault
C
protection (only for std configuration: A, B, E, F, G, J)
Harmonics based earth-fault protection and directional earth-fault
D
protection (only for std configuration: B, F, J)
Harmonics based earth-fault protection (only for std configuration:
E
D)
None (only for std configuration: C, D, H) N
16 Power supply
48...250 V DC, 100...240 V AC 1
24...60 V DC 2
17 Version
-
18 Version 4.0 XE
Version 4.0 FP1 1E
IECA070914 V9 EN