Voice Evacuation System FS-7000 SERIES: Installation Manual
Voice Evacuation System FS-7000 SERIES: Installation Manual
3. FEATURES ........................................................................................................... 8
6. CONNECTIONS
6.1. Basic System Configuration ............................................................................. 29
6.2. Zone Expansion ............................................................................................... 31
6.3. 24 V DC Power Supply Expansion ................................................................... 33
6.4. Power Amplifier Expansion .............................................................................. 34
6.5. 2-Channel Broadcasts ...................................................................................... 35
6.6. Systems Combining the FS-7000RF, FS-7000RM, and FS-7010RM .............. 37
6.6.1. Connecting the FS-7000RF to 2 FS-7000RMs ...................................... 40
6.6.2. Joining the FS-7000RM to the FS-7010RM ........................................... 42
6.7. FS-7000GM
6.7.1. Changing the FS-7000CP's/7010CP's zone selector keys
into group selector keys ......................................................................... 43
6.7.2. Changing the FS-7000RM's zone selector keys
into group selector keys ......................................................................... 49
6.8. Connecting the FS-7000AT to 4-Wire System Attenuators .............................. 51
6.9. Standby Amplifiers ........................................................................................... 54
6.10. Timer-Operated Equipment .............................................................................. 56
6.11. Telephone Paging ............................................................................................ 56
6.12. BGM Players .................................................................................................... 57
6.13. FS-7000EV ....................................................................................................... 58
6.14. Automatic Fire Alarm Systems ......................................................................... 59
6.15. Power Failure Backup
6.15.1. Providing Backup Power Using
an Uninterruptible Power Supply (UPS) System ................................. 60
6.15.2. Power Backup Using
the DS-029B Emergency Power Supply Panel .................................... 60
3
7. TABLE FOR CABLES
7.1. Cables Supplied with Equipment ..................................................................... 64
7.2. Cables To Be Prepared by the Customers
7.2.1. FS-7000CP Control Panel .................................................................... 66
7.2.2. FS-7010CP Expansion Control Panel ................................................... 66
7.2.3. FS-7000JP Junction Panel ................................................................... 67
7.2.4. FS-7000PS DC Power Supply Panel .................................................... 67
7.2.5. FS-7000AT Attenuator Control Panel ................................................... 67
7.2.6. FS-7000EV Voice Evacuation Panel .................................................... 68
7.2.7. FS-7000GM Group Matrix Panel .......................................................... 68
7.2.8. FS-7000RF Remote Microphone Interface Panel ................................. 68
7.2.9. FS-7000RM Remote Microphone ......................................................... 68
7.2.10. FS-7006PA/7012PA Power Amplifiers .................................................. 69
7.2.11. YA-7000 Amplifier Auto Switching Module ........................................... 69
9. PARTS INSTALLATION
9.1. Installing Diodes on the FS-7000GM's Circuit Board ....................................... 71
9.2. Changing the Operation Mode of the FS-7000RM Microphone ....................... 75
12. SPECIFICATIONS
12.1. FS-7000CP Control Panel ............................................................................. 79
12.2. FS-7010CP Expansion Control Panel ........................................................... 80
12.3. FS-7000JP Junction Panel ............................................................................ 81
12.4. FS-7000PS DC Power Supply Panel ............................................................ 82
12.5. FS-7000AT Attenuator Control Panel ........................................................... 82
12.6. FS-7000EV Voice Evacuation Panel ............................................................. 83
12.7. FS-7000GM Group Matrix Panel ................................................................... 84
12.8. FS-7000RF Remote Microphone Interface Panel ......................................... 84
12.9. FS-7000RM Remote Microphone ................................................................. 85
12.10. FS-7010RM Remote Microphone Extension ................................................. 85
12.11. FS-7006PA/7012PA Power Amplifiers .......................................................... 86
12.12. YA-7000 Amplifier Auto Switching Module .................................................... 87
SUPPLEMENT
4
1. SAFETY PRECAUTIONS
• Before installation or use, be sure to carefully read all the instructions in this section for correct and safe
operation.
• Be sure to follow all the precautionary instructions in this section, which contain important warnings and/or
cautions regarding safety.
• After reading, keep this manual handy for future reference.
5
Be sure to follow the instructions below when rack-
WARNING mounting the unit. Failure to do so may cause a fire
or personal injury.
· Install the equipment rack on a stable, hard floor.
When the Unit is in Use
Fix it with anchor bolts or take other arrangements
• All units to prevent it from falling down.
· When connecting the unit's power cord to an AC
Should the following irregularity be found during
outlet, use the AC outlet with current capacity
use, immediately switch off the power, disconnect
allowable to the unit.
the power supply plug from the AC outlet and
contact your nearest TOA dealer. Make no further • All units
attempt to operate the unit in this condition as this
Avoid installing the unit in humid or dusty locations,
may cause fire or electric shock.
in locations exposed to the direct sunlight, near the
· If you detect smoke or a strange smell coming heaters, or in locations generating sooty smoke or
from the unit. steam as doing otherwise may result in fire or
· If water or any metallic object gets into the unit electric shock.
· If the unit falls, or the unit case breaks
When unpacking or moving the unit, be sure to
· If the power supply cord is damaged (exposure of
handle it with two or more persons. Falling or
the core, disconnection, etc.):
dropping the unit may cause personal injury and/or
FS-7000PS/7006PA/7012PA only
property damage.
· If it is malfunctioning (no tone sounds.)
6
2. SYSTEM SUMMARY
Confirmation signal
FS-7000PS FS-7000EV
230 V AC
50 Hz
EV IN Cont
Timer-operated TIMER
sound source BUSY Floor identifier signals 1 – 10
FLOOR ID
CP MIC
CP microphone TALK SW
AUX
Sound source
CALL FS-7006PA
PBX
BUSY
FS-7000JP
FS-7000RF
AT CONT
Max. 50 zones
Speaker outputs 1 – 10
Attenuator controls
1 – 10
FS-7000AT
7
3. FEATURES
• The FS-7000EV is loaded with English language messages when shipped from the factory.
• The semiconductor memory incorporated in the FS-7000EV ensures stable rebroadcast of recorded
messages.
• If speaker lines are shorted, the line protection fuse disconnects the shorted lines and a line short indication
is displayed.
• Simultaneous 2-channel broadcasts can be made of BGM (background music) and announcement
broadcasts (emergency and priority broadcasts), allowing BGM broadcasts to continue in zones not selected
for announcement broadcasts, even when announcements are being made.
• Up to 4 remote microphones can be connected.
• Up to 200 speaker lines can be controlled.
• Time signals can be simultaneously broadcast over all zones by connecting timer-operated sound sources.
• All-zone calls can be made from a telephone set by connecting the system to a telephone exchange.
• Connection of the emergency power supply panel permits emergency broadcasts to be made even during a
power failure.
4. INSTALLATION PRECAUTIONS
• The required power voltage for this system is 230V AC. Calculate the total combined power consumption of
all equipment in the system to ensure ample power capacity. Note that the system may not work properly
due to breaker cutoff or power voltage drops when the total supply voltage is insufficient.
• About the handling of the power supply cord (FS-7000PS only):
The supplied power cord is intended for exclusive use with the FS-7000PS Power Supply Panel. Avoid using
this power cord for any other equipment than the PS-7000PS panel.
• Ensure that the rear of the component is sufficiently distant from the rear wall to facilitate maintenance
service. Speaker line protection fuses and output overcurrent fuses are located on the component rear
panel. Sufficient space must be provided between the back of the component and the rear wall surface to
change the fuses.
• When mounting the FS-7000PS and FS-7006PA or FS-7012PA in an equipment rack, mount a Perforated
Panel larger than 1U size* just above and below each component, as shown in the following figure.
• When mounting the FS-7006PA or FS-7012PA power amplifier in an equipment rack, keep the rear of the
amplifier at least 10 cm away from the rear wall so that its rear panel-mounted fan vent is not blocked.
• Each component is designed with robust construction. However, be sure to use reinforcement brackets
when mounting if extra strength is required.
• No rack mounting screws are supplied with the system. Use the appropriate screws for the racks used.
8
5. NOMENCLATURE AND FUNCTIONS
5.1. FS-7000CP Control Panel
The FS-7000CP is a standard operation panel for the FS-7000 Series Voice Evacuation Systems.
It is designed to be used in conjunction with the FS-7000JP panel, and enables individual paging calls to up to
10 zones plus all-zone calls.
The number of zones can be expanded to up to 200 zones in 10-zone units by connecting the FS-7010CP
expansion panel. Further, connection of both the FS-7000GM panel and the FS-7010CP panel permits
creation of up to 20 broadcast zone groups.
The FS-7000CP is equipped with a built-in pre-amplifier function and chime unit (ascending 4-note tone).
Audio output can be set to either a 2-channel output of background music (BGM) and priority broadcast or a 1-
channel output of mixed BGM and priority broadcast.
[Front]
3
2
6 7 8 9 10 11 12 13 14
1. Power Indicator • EV
Lights when power is supplied and the FS- Adjusts the volume of the EV Audio Input on the
7000CP is ready for operation. rear panel.
• TIMER
2. CP Microphone Adjusts the volume of the Timer Input on the rear
Make announcements while holding down the panel.
Talk Switch (3). The microphone can be used only
• PAGING
while the FS-7000CP panel is in use or
Adjusts the volume of the Paging Input on the rear
emergency broadcasts are in progress.
panel.
3. Talk Switch • RM MIC
Hold down this switch to make announcements Adjusts the volume of the RF Audio Input on the
using the microphone. rear panel.
• CP MIC
4. Volume Controls Adjusts the volume of the CP Microphone (2).
Adjust the sound volume for each audio input. • CHIME
Turning the control clockwise increases the Adjust the volume of the built-in 4-tone chime.
volume, while turning it counterclockwise
• BGM 1 – 4
decreases the volume.
Adjusts the volume of BGM Inputs 1 – 4 on the
Controls are arranged from left to right as follows:
rear panel.
9
5. Tone Controls • PAGING
Adjust high and low frequencies of the output. Remains lit during broadcasts from the
Frequencies are accentuated when the control is component connected to the paging input.
rotated clockwise, and attenuated when rotated • RM MIC
counterclockwise. Controls are arranged from left Remains lit during broadcasts from the FS-
to right as follows: 7000RM.
• PRIORITY BASS • CP IN-USE
Adjusts the low frequencies of the Priority Output Remains lit during broadcasts from the FS-
on the rear panel. 7000CP. Announcements can be made via the
• PRIORITY TREBLE CP Microphone (2).
Adjusts the high frequencies of the Priority Output
on the rear panel. 9. Speaker Line Short Indicator
• BGM BASS Lights when 1 or more speaker lines connected
Adjusts the low frequencies of the BGM Output on to the FS-7000JP have shorted.
the rear panel. (See page 77.)
• BGM TREBLE
10. All-Zone Call Indicator
Adjusts the high frequencies of the BGM Output
Lights when the All-Zone Call button (13) is
on the rear panel.
pressed to select all broadcast zones
simultaneously. (Lights continuously only while
6. Zone Indicators
the FS-7000CP is operating or emergency
Light to indicate current broadcast zones.
broadcasts are being made.)
Note
These indicators also light during emergency 11. Chime Button
broadcasts when broadcast zones are selected by Sounds a built-in 4-tone chime. This button can
signal inputs from an automatic fire alarm system. be used only while the FS-7000CP is operating.
10
[Rear]
15 16 17 18 19 20 21 22 23 24 25 26 27
28 29 30 31 32 33 34 35 36 37 38
15. DC Power Input Terminal 19. BGM Input 1 Sensitivity Selector Switch
Connect 24 V DC power to this terminal. Power Sets the input sensitivity of BGM Input 1 (18) to
is supplied from the FS-7000PS. "–60 dBV" or "0 dBV." (Default: 0 dBV)
(M3 screw terminal; barrier distance: 6.4 mm)
20. Paging Input Terminal
16. BGM Input Terminals 2,3,4 Connect audio and control signals from
Connect background music equipment to these equipment (such as telephone paging
terminals. When the output is set to 2-channel equipment) to this terminal. Input signals to this
broadcast, background music is supplied from terminal are broadcast when the control
the BGM Output (30). When the output is set to terminals are closed.
1-channel broadcast, background music is mixed Audio: –60 dBV/–20 dBV selectable, 600 Ω,
with priority broadcasts and provided from the balanced
Priority Output (31) as well. However, activation Control: Open voltage: 26 V DC; short-circuit
of the muting function* due to signal inputs other current: under 2 mA
than BGM will attenuate the BGM level. 5P terminal block
BGM inputs 2 – 4: –20 dBV, 10 kΩ, unbalanced,
2P RCA jack 21. Paging Input Sensitivity Selector Switch
* Muting function: A function that automatically Sets the input sensitivity of Paging Input (20) to
decreases the volume of original broadcast when "–60 dBV" or "–20 dBV."
another broadcast is initiated during original (Default: –20 dBV)
broadcast, and restores the original broadcast
volume level when the other broadcast is 22. RF Audio Input Terminal
completed. Used to connect the FS-7000RF. Audio signals
from the FS-7000RM are input via the FS-
17. Mute Switch 7000RF. (0 dBV, 600 Ω, balanced, 3P terminal
Sets whether or not to attenuate the signal levels block)
of BGM Inputs 2 – 4 (16) when a broadcast is
made from the BGM Input 1 (18). (Default: OFF) 23. Auxiliary Input Terminal
Signals received by this terminal are mixed with
18. BGM Input Terminal 1 signals from the CP Microphone (2) and output
Connect background music equipment to this while the FS-7000CP is in operation.
terminal. When the output is set to 2-channel (–20 dBV, 600 Ω, unbalanced, 2P terminal block)
broadcast, BGM is supplied from the BGM
Output (30). Setting the muting function permits 24. Auxiliary Input Volume Control
this input to take precedence over BGM Inputs 2 Adjusts the sound volume of Auxiliary Input (23).
– 4. When the output is set to 1-channel
broadcast, background music is mixed with
priority broadcasts and provided from the Priority
Output (31) as well. However, activation of the
muting function due to signal inputs other than
BGM will attenuate the BGM level. (–60 dBV/0
dBV selectable, 600 Ω, balanced, 3P terminal
block)
11
25. Timer Input Terminal 32. Automatic Fire Alarm System Input Terminal
Connect audio and control signals from timer- Connect this terminal to the floor identifier signal
operated equipment to this terminal. Input transmitted from the automatic fire alarm system.
signals to this terminal are broadcast with the The identifier signal automatically selects zones
highest priority when the control terminals are and broadcasts audio alarms to such zones.
closed. (Open voltage: 26 V DC; short-circuit current:
Audio: 0 dBV, 600 Ω, unbalanced under 5 mA; 12P terminal block; 10 zones +
Control: Open voltage: 26 V DC; short-circuit COM + COM)
current: under 2 mA Note
4P terminal block This terminal is not connected when the FS-
7000EV is not used.
26. EV Audio Input Terminal
Used to connect the FS-7000EV. This input can 33. EV Control Terminal
be used only while an emergency broadcast is Connect the FS-7000EV to this terminal.
being made. (0 dBV, 600 Ω, unbalanced, 2P
terminal block) 34. RF Zone Control Terminal
Use this terminal to connect the FS-7000RF.
27. Output Mode Selector Switch Data regarding broadcast zones transmitted from
Sets the audio output to "1-CH" (1-channel) or the FS-7000RF is input to this terminal.
"2-CH" (2-channel) broadcasts.
(Default: 2-channel broadcast) 35. RF Control Terminal
Use this terminal to connect the FS-7000RF.
28. Functional Earth Terminal
Connect this terminal to the functional earth 36. CP Control Terminal
terminal of external equipment if excessive noise Use this terminal to connect the FS-7010CP. All
is generated when the FS-7000CP is connected of the FS-7010CP units that are mounted in the
to the external equipment. This could reduce system must be connected to this terminal.
noise.
Note: This terminal is not for protective earth. 37. JP Control Terminal
Connect this terminal to the FS-7000JP when the
29. All-Zone Call Mode Selector Switch FS-7000GM is not connected to the system.
Sets the mode of broadcast to be initiated with Note
the All-Zone Call button (13). When the FS- This terminal is not used when the FS-7000GM
7000AT has been connected to the system, if is connected to the FS-7000CP.
this switch is set to "URGE" (general urgency)
and an all-zone call is made, a 24 V DC for 38. JP/GM Control Terminal
controlling attenuators is output, permitting the Connect this terminal to the FS-7000JP or FS-
call to bypass the attenuator. (Default: "NORM") 7000GM.
When the FS-7000GM is not connected to the
30. BGM Output Terminal
FS-7000CP:
Signals from the BGM Inputs 1 – 4 (16 and 18)
Connect this terminal to the FS-7000JP in order
are mixed and output. Connect this terminal to
to control speaker line ON/OFF operations.
the power amplifier for BGM broadcast. (0 dBV,
600 Ω, balanced, 3P terminal block) When the FS-7000GM is connected to the FS-
7000CP:
31. Priority Output Terminal Connect this terminal to the FS-7000GM. The
Zone Selector keys (7) on the front panel
When the Output Mode Selector Switch (27)
function as group selector keys.
is set to 2-channel broadcast:
Outputs signals other than those from the BGM
Inputs 1 – 4 (16 and 18). Connect this terminal to
the power amplifier intended for priority
broadcast.
When the Output Mode Selector Switch (27)
is set to 1-channel broadcast:
Outputs signals from all audio inputs. Signals
output from sources other than BGM Inputs 1 – 4
causes these 4 BGM input signals to atttenuate.
Connect this terminal to the power amplifier. (0
dBV, 600 Ω, balanced, 3P terminal block)
12
5.2. FS-7010CP Expansion Control Panel
The FS-7010CP is used to expand the broadcasting capacity of FS-7000 Series Voice Evacuation Systems.
Announcements and background music can be broadcast to up to 10 individual zones. Connecting the FS-
7000GM to the FS-7000CP/FS-7010CP combination permits broadcasts to be made to up to 20 zone groups.
[Front]
2 3 4 1
[Rear]
5 6 7 8 9 10 11 12
7. Automatic Fire Alarm System Input Terminal 11. JP Zone Control Terminal
Connect this terminal to floor identifier signals Connect this terminal to the FS-7000JP in order
transmitted from the automatic fire alarm system. to control speaker line ON/OFF operations.
The identifier signal designates broadcast zones
to provide audio alarm to such zones. (Open 12. GM Zone Control Terminal
voltage: 26 V DC; short-circuit current: under 5 Connect this terminal to the FS-7000GM when
mA; 12P terminal block; 10 zones + COM + COM) the FS-7000GM is connected to the FS-7000CP.
Note: This terminal is not connected when the FS-
7000EV is not used.
13
5.3. FS-7000JP Junction Panel
The FS-7000JP panel is used in conjunction with the FS-7000CP and the FS-7010CP to connect speaker
lines in FS-7000 Series Voice Evacuation Systems. It can connect up to 10 speaker lines. If speaker lines are
shorted, the line protection fuses disconnect the shorted lines, leaving broadcasts to other speaker lines
functioning intact. The FS-7000JP is equipped with BGM input and priority broadcast input, with BGM
broadcast zones selectable using the keys on the front panel. Priority broadcast zones are selected using the
FS-7000CP.
[Front]
2 3 4 1
14
[Rear]
5 6
7 8 9 10 11 12 13 14 15 16
15
5.4. FS-7000PS DC Power Supply Panel
The FS-7000PS supplies 24 V DC power to each component used in FS-7000 Series Voice Evacuation
Systems. Connecting the DS-029B provides a power supply for emergency broadcasts even during power
failures.
[Front] 1 2 3
2. AC Power Indicator
Lights when AC power is supplied and the FS-
7000PS is ready for operation on AC power.
[Rear]
4 5 6 7 8 9 10 11
16
5.5. FS-7000AT Attenuator Control Panel
The FS-7000AT is used in conjunction with FS-7000 Series Voice Evacuation Systems to control 4-wire
system attenuators. Up to 10 zones can be attenuator-controlled. When general urgency or emergency
broadcasts are made, the FS-7000AT provides 24 V DC power to allow such broadcasts to bypass the
attenuators. The output status of each line can be monitored by the indicators on the front panel.
[Front]
2 3 1
[Rear]
4 5 6 7 8
6. AT Control Terminal
Connect this terminal to the FS-7000JP to control
ON/OFF operations of the Attenuator Control
Output (8).
17
5.6. FS-7000EV Voice Evacuation Panel
The FS-7000EV is an emergency broadcast operation panel for FS-7000 Series Voice Evacuation Systems.
This panel is not required if the system is to be used solely for general-purpose public address applications. It
is possible to start and reset emergency broadcasts through manual operation. The FS-7000EV has a built-in
voice alarm device that can make both evacuation and false-alarm announcements. Not only are evacuation
announcements automatically broadcast when the system receives a fire instruction signal from the connected
automatic fire alarm system, they can also be initiated using the Evacuation Announcement button on the front
panel. False alarm announcements can be initiated using the False Alarm Announcement button on the front
panel. Evacuation and false alarm announcement messages can also be recorded using the appropriate
buttons on the front of the panel, in which case the recorded message can be confirmed by listening with
headphones.
[Front] 2 3 4 5 6 7 8 9 1
10 11 12 13
18
[Rear]
14 15 16 17 18 19 20 21 22 23
14. DC Power Input Terminal 20. Emergency Control Contact Output Terminal
Connect this terminal to 24 V DC power. Power There are an output that is activated and an
is supplied from the FS-7000PS Power Supply output that is deactivated during emergency
Panel. announcements.
(M3 screw terminal; barrier distance: 6.4 mm) (Relay output; rated voltage: 30 V DC; current
capacity: 1 A; 3P terminal block)
15. Functional Earth Terminal
Connect this terminal to the functional earth 21. Automatic Fire Alarm System Confirmation
terminal of external equipment if excessive noise Signal Input Terminal
is generated when the external equipment is Connect this terminal to a confirmation signal
connected to the FS-7000EV. This could reduce (fire confirmation signal) from the automatic fire
noise. alarm system. Evacuation announcements are
Note: This terminal is not for protective earth. broadcast if they have not yet been initiated
when this signal is received.
16. EV Audio Output Terminal [Open voltage: 24 V DC; short-circuit current: 6
Connect this terminal to the FS-7000CP for mA, 2P terminal block (1 channel + COM)]
broadcasting evacuation announcements and
other voice alarms. Such alarms are output only 22. Emergency Power Control Terminal
when the Mode Selector switch (5) is set to the Activates an emergency power supply unit
Normal position. connected to the FS-7000PS in order to enable
(0 dBV, 600 Ω, unbalanced, 2P terminal block) emergency broadcasts during power failures.
Connect this terminal to the FS-7000PS.
17. USB Terminal
Connect this terminal to a PC or other equipment Control input: Rated voltage: 24 V DC; current
using the USB cable. With this connection the capacity: 100 mA
built-in sound source can be rewritten using Starting output: Open collector output; rated
dedicated software. voltage: 30 V DC; current capacity: 100 mA
(M3 screw terminal; barrier distance: 6.4 mm)
18. USB Communication Indicator
Lights or flashes during USB communications. 23. EV Control Terminal
Connect this terminal to the FS-7000CP Control
19. Emergency ON Output Terminal Panel.
Activated during emergency broadcasts. This
terminal is connected to the FS-7006PA or FS-
7012PA amplifier to disable PA attenuators while
emergency announcements are being made.
(Relay output; rated voltage: 30 V DC; current
capacity: 1 A; 2P terminal block)
19
5.7. FS-7000GM Group Matrix Panel
The FS-7000GM panel is used in conjunction with FS-7000 Series Voice Evacuation Systems to make group
broadcasts. The FS-7000GM connects to the FS-7000CP and FS-7000RF and enables group broadcasts by
selecting multiple speaker lines simultaneously via the zone selector keys on the FS-7000CP or FS-7000RM.
Up to 20 groups and 50 speaker lines can be made available per unit, which can be expanded to 20 groups
and 200 speaker lines by connecting 4 units.
[Front]
[Rear]
2 3 4 5 6
20
5.8. FS-7000RF Remote Microphone Interface Panel
The FS-7000RF is used to connect the FS-7000RM to FS-7000 Series Voice Evacuation Systems. Up to 4
FS-7000RM units can be connected using the FS-7000RF. It is possible to control 50 speaker lines as well as
all-zone calls. Connection of the FS-7000GM enables broadcasts to be made to up to 20 zone groups.
[Front]
2 1
21
[Rear]
3 4 5
6 7 8 9 10 11
22
5.9. FS-7000RM Remote Microphone
The FS-7000RM Remote Microphone is used solely for general-purpose public address applications in FS-
7000 Series Voice Evacuation Systems. It enables broadcasting to up to 10 individual zones, as well as all-
zone calls. One FS-7000RF panel is required in order to connect the FS-7000RM to the system. Up to 4 FS-
7000RM units can be connected. Pressing the FS-7000RM's chime key causes the FS-7000CP's built-in 4-
tone chime to sound. Connection of 4 FS-7010RMs enables broadcasts to 50 individual zones as well as all-
zone calls (expandable by 10 lines per FS-7010RM). Further, up to 20 broadcast zone groups can be created
by connecting the FS-7000RF to an FS-7000GM Group Matrix Panel.
Tip
Connection of 6 FS-7010RM Remote Microphone Extension units enables broadcasting to 50 individual zones
and 20 zone groups, as well as all-zone calls.
[Top]
9 10
11
1
2
3
13 4
5
6
7
8
1. Power Indicator
Lights when power is supplied and the 12
FS-7000RM is ready for operation.
2. Fault Indicator
Lights when any failure is detected in
9. Zone Identification Card
communications with the FS-7000RF or when any
Write the names of the broadcast zones on this
failure occurs on the FS-7000RM itself.
card and insert it into the card receptacle from
(See page 77.)
top.
3. All-Zone Call Indicator Note
Remains lit while an all-zone call is broadcast from Since this card is not supplied with the FS-
the FS-7000RM. (Lights only when calls are made 7000RM, prepare it according to the instructions
from this FS-7000RM.) given on page 91.
4. All-Zone Call Key 10. Zone Selection Indicators
Selects all broadcast zones simultaneously. Light when the corresponding Zone Selector
5. Chime Key keys (11) are pressed. (Light only when the FS-
Sounds a 4-tone chime built inside the FS- 7000RM's keys are used.)
7000CP. 11. Zone Selector Keys
6. Broadcast Reset Key Select broadcast zones. Connection of the FS-
Resets broadcast zones selected via the All-Zone 7000RF to the FS-7000GM permits simultaneous
Call key (4) or Zone Selector keys (11), selection of multiple broadcast zones.
terminating broadcasts from the FS-7000RM. 12. Talk Key
7. Busy Indicator Microphone announcements can be made only
Lights green when a broadcast is made from this while this key is pressed.
FS-7000RM, and lights orange when a broadcast Tip
is made from other equipment. Key operation can be changed to allow
microphone announcements to alternate
8. Talk Key Indicator
between ON and OFF each time this key is
Lights when a microphone announcement is made
pressed. (See page 75.)
using the Talk key (12).
13. Microphone
23
[Right Side] [Rear]
13
15
14
16 17 18 19 20
24
5.10. FS-7010RM Remote Microphone Extension
The FS-7010RM is an extension unit for the FS-7000RM to be used in FS-7000 Series Voice Evacuation
Systems. Ten zones can be expanded per FS-7010RM. Up to 6 FS-7010RM units can be connected to the
FS-7000RM.
1 2
3
4
25
5.11. FS-7006PA/7012PA Power Amplifiers
These power amplifiers are used in conjunction with FS-7000 Series Voice Evacuation Systems. The FS-
7006PA's output is rated at 600 W and the FS-7012PA is rated to deliver 1,200 W. By mounting the YA-7000
module in a power amplifier and connecting a standby amplifier to it, the power amplifier can be automatically
switched over to the standby amplifier if the power amplifier fails. When initiating emergency broadcasts, the
volume control on the front panel is bypassed by closing the Volume Bypass Control terminals on the rear
panel, allowing broadcasts of emergency message at maximum volume.
[Front]
5 6 7 8
3
2
4 1
5. Fault Indicator
Lights when an output muting function* is
operated or when a failure is detected.
If the YA-7000 is used, this indicator lights when
the YA-7000 detects a failure and the power
amplifier is switched over to a standby amplifier.
(See page 77.)
26
[Rear]
10 11 12 13 14
10. Power Cord 13. Volume Control Bypass Control Input Terminal
Connect this cord to the wall AC outlet (230 V Bypasses Volume Control (3) on the front panel
AC, 50 Hz). and allows announcements to be made at
maximum volume.
11. Speaker Output Terminal (with cover) (Open voltage: under 24 V DC; short-circuit
This high-impedance, 100 V line output is current: under 10 mA; 2P terminal block)
connected to the FS-7000JP.
Note 14. Audio Signal Input Terminal
Connect this terminal to the YA-7000 when the Connect this terminal to the FS-7000CP's Priority
YA-7000 has been mounted. Output and BGM Output.
(0 dB, 10 kΩ, balanced, 3P terminal block)
• FS-7006PA
M4 screw terminal; barrier distance: 9 mm; load
impedance: 16.7 Ω
• FS-7012PA
M4 screw terminal; barrier distance: 9 mm; load
impedance: 8.3 Ω
Note
Never connect this terminal to the speaker output
terminal of other FS-7006PA or FS-7012PA
power amplifier. Failure to follow this instruction
could lead to equipment failures.
27
5.12. YA-7000 Amplifier Auto Switching Module
The YA-7000 module is designed to be mounted in the power amplifier of FS-7000 Series Voice Evacuation
Systems. Connecting a standby amplifier to the YA-7000 module installed in the main amplifier (FS-7006PA or
FS-7012PA) permits the main amplifier to be switched over to the standby amplifier if the main amplifier fails.
[Front]
1 2 3 4
1. Speaker Output Terminal (with cover) 3. Standby Amplifier Input Terminal (with cover)
This high-impedance, 100V line speaker output Connect this terminal to the standby amplifier's
terminal connects to the FS-7000JP. Signals from speaker output.
the Main Amplifier Input (2) are output when the (M4 screw terminal; barrier distance: 9 mm)
main amplifier (i.e. power amplifier in which the
YA-7000 has been mounted) is operating Note
correctly, and signals from the Standby Amplifier Only 1 piece of the FS-7006PA or FS-7012PA can
Input (3) are output if a main amplifier failure is be connected to this terminal. Never connect 2 or
detected. more units to this terminal, as the excessive load
(M4 screw terminal; barrier distance: 9 mm) could cause the amplifier to fail.
Note
Only 1 piece of FS-7006PA or FS-7012PA can be
connected to this terminal. Never connect 2 or
more units to this terminal, as the excessive load
could cause the amplifier to fail.
28
6. CONNECTIONS
WARNING
The TERMINALS marked with the symbol are HAZARDOUS LIVE.
The external wiring to these terminals requires installation by an INSTRUCTED PERSON.
The basic system consists of the FS-7000CP, FS-7000JP, FS-7000PS, and FS-7006PA or FS-7012PA. This
basic configuration allows 1-channel/10-zone general-purpose broadcasts to be made. To configure
scheduled (timer-controlled) broadcasts, telephone paging, or BGM broadcasts other than announcements
using the CP microphone, refer to the specific connection instructions for the relevant pieces of equipment.
Connection examples in this chapter show the FS-7012PA being used as the power amplifier, but the same
wiring instructions also apply to the FS-7006PA.
[System Operation]
• Ten different broadcast zones can be selected individually or simultaneously.
• Broadcasts can be either announcements (made using the CP microphone installed on the FS-7000CP
Control Panel) or background music (BGM).
• The broadcast zones to be used are selected at the FS-7000CP.
• Announcements made using the CP microphone to zones where BGM broadcasts are in progress will be
audible over the BGM in those zones.
[Notes]
• Only 1 FS-7006PA or FS-7012PA unit can be connected to the FS-7000JP's Priority Input. Never connect 2
or more units to this terminal, as the excessive load could cause the amplifier to fail.
• The FS-7000JP's maximum output per speaker line varies depending on the connected power amplifiers.
Maximum power output is 500 W when the FS-7012PA is connected, and 280 W when the FS-7006PA is
connected. If the load capacity exceeds the maximum power output, divide speaker lines into 2 or more
lines.
• A 0.5A fuse is preinstalled by the factory for speaker line protection.
Depending on the total wattage of all the connected speakers on a line, replace the fuse with one having the
correct rating, referring to the following table:
[Settings]
Set the FS-7000CP's output mode selector switch to "1-CH."
29
[Wiring Diagram]
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables.
FS-7000PS
230 V AC
DC POWER OUT
FS-7000CP
DC POWER IN
JP ZONE/
GM GROUP CONT
Speaker lines
SP OUT
FS-7000JP
DC POWER IN
PRIORITY IN
JP ZONE CONT
JP CONT
FS-7012PA
SP OUT
INPUT
230 V AC
30
6.2. Zone Expansion
If more than 10 broadcast zones are required, then additional FS-7010CP and FS-7000JP panels may be
added as needed. Adding 1 each of these units will increase by 10 zones. Up to 19 each of the FS-7010CP
and FS-7000JP can be added, allowing expansion to a maximum of 200 zones. The current of the 24 V DC
power supplied from the FS-7000PS is 5 A. If the addition of the expansion panel causes the 24 V DC
capacity to exceed 5 A, then add the required number of the FS-7000PS panels and divide the power supply.
[Note]
The FS-7000PS panel must be added if the total of current consumption of 24 V DC-operated equipment
(such as the FS-7010CP and FS-7000JP) exceeds 5 A.
31
[Wiring Diagram]
The following figure shows a configuration in which 2 each of the FS-7010CP and FS-7000JP units have been
added to the basic system.
FS-7000CP
DC POWER IN
JP ZONE/
CP CONT GM GROUP CONT
CP CONT
FS-7010CP JP ZONE CONT
DC POWER IN CP CONT
JP CONT
FS-7010CP CP CONT JP ZONE CONT
DC POWER IN
JP CONT
Speaker lines
SP OUT 1 – 10
FS-7000JP DC POWER IN
PRIORITY IN
JP ZONE CONT
JP CONT
Speaker lines
SP OUT
11 – 20
FS-7000JP DC POWER IN
PRIORITY IN
JP ZONE CONT
JP CONT
Speaker lines
SP OUT 21 – 30
FS-7000JP DC POWER IN
PRIORITY IN
JP ZONE CONT
JP CONT
FS-7012PA
SP OUT
INPUT
230 V AC
32
6.3. 24 V DC Power Supply Expansion
If the addition of zones causes the total of current consumption of 24 V DC-operated equipment to exceed 5
A, then add the required number of the FS-7000PS panels.
[Notes]
• Make connections between negative (–) terminals of the 24VDC output of all FS-7000PS panels.
• Divide the power supply to 24 V DC-operated equipment in order to keep the current supplied from a single
FS-7000PS panel at 5A or less. (Refer to the following table showing each component's current
consumption at 24 V DC.)
[Wiring Diagram]
The following figure shows only the wiring related to the expansion of the 24 V DC power supply.
FS-7000PS
230 V AC
DC POWER OUT
FS-7000PS
230 V AC
DC POWER OUT
33
6.4. Power Amplifier Expansion
Power amplifiers must be expanded when the total of speaker line load capacity exceeds 1,200 W and a
single power amplifier cannot handle this load. However, since only 1 power amplifier can be connected to
each FS-7000JP panel, the number of speaker lines must also be increased by adding the FS-7010CP and
FS-7000JP, even if the number of necessary speaker lines is less than 10.
[Notes]
• Only 1 piece of the FS-7006PA or FS-7012PA can be connected to the FS-7000JP's Priority Input. Never
connect 2 or more units to this terminal, as the amplifier could fail.
• The total of the FS-7000JP's speaker line output must not exceed the power amplifier output.
[Wiring Diagram]
The following figure shows only the wiring related to the power amplifier expansion.
PRIO OUT
FS-7000JP
PRIORITY IN
FS-7000JP
PRIORITY IN
FS-7012PA
SP OUT
INPUT
230 V AC
FS-7012PA
SP OUT
INPUT
230 V AC
34
6.5. 2-Channel Broadcasts
To provide 2-channel priority/background music broadcasts, first add a BGM player and power amplifiers to
the basic system configuration, then perform the wiring described on the next page. Select BGM broadcast
zones using the FS-7000JP's BGM Zone Selector Keys.
See page 57 regarding the connection of BGM player.
[System Operation]
• Broadcasts can be made to up to 10 selected zones.
• Background music and announcements using the CP microphone can be broadcast simultaneously to
different zones.
• Zones to which announcements are broadcast from the CP microphone are selected at the FS-7000CP.
• BGM broadcast zones are selected at the FS-7000JP.
• Selecting zones in which BGM broadcasts are in progress at the FS-7000CP interrupts the BGM broadcasts
in those zones, allowing announcements from the CP microphone to be heard instead.
[Notes]
• Only 1 piece of the FS-7006PA or FS-7012PA can be connected to each of the FS-7000JP's Priority Input
and BGM Input. Never connect 2 or more units to these terminals, as the excessive load could cause the
amplifier to fail.
• The FS-7000JP's maximum output per speaker line varies depending on the connected power amplifiers.
Maximum power output is 500 W when the FS-7012PA is connected, and 280 W when the FS-7006PA is
connected. If the load capacity exceeds the maximum power output, divide speaker lines into 2 or more
lines.
• A 0.5 A fuse is preinstalled by the factory for speaker line protection. Depending on the total wattage of all
the connected speakers on a line, replace the fuse with one having the correct rating. (See page. 29.)
[Settings]
Set the FS-7000CP's Output Mode Setting switch to the "2-CH" position.
35
[Wiring Diagram]
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables.
FS-7000PS
230 V AC
DC POWER OUT
FS-7000CP
DC POWER IN
JP ZONE/
GM GROUP CONT
BGM IN
JP ZONE CONT
PRIORITY IN JP CONT
SP OUT
INPUT
230 V AC
SP OUT
INPUT
230 V AC
36
6.6. Systems Combining the FS-7000RF, FS-7000RM, and FS-7010RM
When using the FS-7000RM, add the FS-7000RF and perform the wiring shown below.
Then, connect the FS-7000RF and the FS-7000RM. When expanding the FS-7000RM's Zone Selector Keys,
connect the FS-7010RM to the FS-7000RM.
[Notes]
• For the FS-7000RF's RF Zone Control Terminal 3 and subsequent terminals, make connections in such a
way that Terminal 3 is connected to the second FS-7010CP, Terminal 4 to the third FS-7010CP, and
Terminal 5 to a fourth FS-7010CP.
• If the FS-7000GM is to be connected to the FS-7000CP, the FS-7000RF's RF Zone Control Terminal will
need to be connected to a different terminal (see page 47 for details).
[Wiring Diagram]
The figure shows only the wiring related to the FS-7000RF.
For the wiring of other models, refer to the relevant system wiring diagrams, such as those for basic
configuration and zone expansion.
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables.
FS-7000PS
230 V AC
DC POWER OUT
FS-7000CP
RF IN
DC POWER IN
RF CONT
RF ZONE CONT
FS-7010CP
RF ZONE CONT
DC POWER IN
DC POWER IN
RF CONT RF OUT
37
[Settings]
Set the Function Switch on the FS-7000RF's rear panel to match the needs and uses of the system, as
described below.
1 2 3 4 5 6 7 8
Normal Urgency
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Number of zones
Up to 10 zones 11 – 20 zones 21 – 30 zones 31 – 40 zones 41 – 50 zones
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
38
(4) Priorities Among FS-7000RM Units (SW #7 and #8): Last-in-first-out / First-in-first-out / Individual
priority / None
(Default: Last-in-first-out)
Designate priorities among announcements made simultaneously from multiple connected FS-7000RM
microphones. There are 4 priority setting methods, as follows:
• Last-in-first-out (LIFO)
The announcement from the FS-7000RM last operated takes precedence.
• First-in-first-out (FIFO)
The announcement from the FS-7000RM first operated takes precedence. Until this announcement is
completed, other FS-7000RM microphones cannot make broadcasts.
• Individual Priority*
The announcement from the FS-7000RM assigned a smaller address number takes precedence. The FS-
7000RM with an address number smaller than that of the FS-7000RM currently making broadcasts can make
broadcasts to the selected zones. However, the FS-7000RM with a larger address number must wait until the
current announcement is completed.
• None
No priority relationship exists among the FS-7000RM units. Announcements from different FS-7000RMs are
mixed and broadcast to the selected zone.
* If Individual Priority is selected, the smaller the address number, the higher priorities among the connected
FS-7000RMs.
39
6.6.1. Connecting the FS-7000RF to 2 FS-7000RMs
FS-7000RF
: Supplied cable
See page 64; Table for Cables.
AUDIO DC24 V #2 DC24 V #4 BUS #2/#4 AUDIO DC24 V #1 DC24 V #3 BUS #1/#3
Pin Arrangement
#7 DC 24 V +
#7 DC 24 V +
#8 DC 24 V –
#8 DC 24 V –
#5 AUDIO C
#4 AUDIO H
#5 AUDIO C
#4 AUDIO H
#3 BUS +
#3 BUS +
#6 BUS –
#6 BUS –
RJ45’s
FS-7000RM FS-7000RM
RF LINK RF LINK
Connect the RJ45 connector to the FS-7000RM's FS-7000RF Link Terminal. Strip the other ends of the cable
and connect them to the FS-7000RF's FS-7000RM Link Terminal.
Notes
• If a long distance between the FS-7000RM and the FS-7000RF causes the FS-7000RM's voltage to drop
below 20 V, the power supply must be augmented using an AC adapter.
• The total cable length from the FS-7000RF to each FS-7000RM must not exceed 800 m.
40
[Settings]
Note
Remote microphones cannot be used with any other settings.
0 10 20
or
OFF ON
41
6.6.2. Joining the FS-7000RM to the FS-7010RM
Step 1. Turn over the FS-7000RM and FS-7010RM and bring both units next to each other.
Step 2. Using the cable supplied with the FS-7010RM, connect the FS-7000RM's Connection Terminal to the
Connection Terminal on the FS-7010RM's left side panel.
Step 3. Join the FS-7000RM to the FS-7010RM using the connecting plate (B) and the 4 screws supplied with
the FS-7010RM.
Step 4. Join the FS-7000RM to the FS-7010RM using the 2 connecting plates (A) and the 8 screws supplied
with the FS-7010RM.
Note
Follow the same procedure when joining any additional FS-7010RM to the FS-7010RM.
: Supplied cable
See page 64; Table for Cables.
FS-7010RM FS-7000RM
[Bottom surface]
FS-7010RM FS-7000RM
[Bottom surface]
42
6.7. FS-7000GM
Connect the FS-7000GM to the system when selecting broadcast zone groups using the zone selector keys of
the FS-7000CP or FS-7000RM. For each FS-7000GM, up to 50 zones can be programmed for group
selection. Add 2 or more FS-7000GMs (up to 4 units) to the system to program more than 50 zones for group
selection.
6.7.1. Changing the FS-7000CP's/7010CP's zone selector keys into group selector keys
If the FS-7000GM is connected to the FS-7000CP, the FS-7000CP's individual zone selector keys can be
used as group selector keys, permitting multiple broadcast zones to be selected simultaneously by pressing a
single key. Further, connecting the FS-7010CP to the FS-7000GM makes up to 20 group selector keys
available.
[System Operation]
The individual zone selector keys on the FS-7000CP panel, and on the first one of 6 connected FS-7010CP
panels, function as group selector keys, while those on the 2nd to 6th FS-7010CP panels function as
individual zone selector keys.
Note: Open the cover and install the necessary parts before use.
Install the necessary diodes and connectors on the circuit board first according to the desired
group broadcast zone allocation. The FS-7000GM comes supplied with the necessary parts and
cannot be used without this modification. For details, see page 71; Installing Diodes on the FS-
7000GM Circuit Board.
43
[Wiring Diagram (Example of 20 groups/50 individual zones)]
The figure below shows only the wiring related to group broadcasts.
For the wiring of other models, refer to the relevant system wiring diagrams, such as those for basic
configuration and zone expansion.
FS-7000CP
DC POWER IN
JP ZONE/
GM GROUP CONT
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
DC POWER IN
Speaker lines
FS-7000JP SP OUT 1 – 10
DC POWER IN
(1st unit)
JP ZONE CONT
JP CONT
Speaker lines
FS-7000JP SP OUT 41 – 50
DC POWER IN
(5th unit)
JP ZONE CONT
JP CONT
44
[Wiring Diagram (Example of 20 groups/100 individual zones)]
The figure below shows only the wiring related to group broadcasts.
For the wiring of other models, refer to the relevant system wiring diagrams, such as those for basic
configuration and zone expansion.
: Supplied cables
FS-7000CP : Cables prepared separately
See page 64; Table for Cables.
JP ZONE/
GM GROUP CONT
GM GROUP GM GROUP
CONT OUT CONT IN GM ZONE CONT
FS-7000GM
2 1 2 1 5 4 3 2 1
(1st unit)
GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
(2nd unit)
GM GROUP
CONT IN
To next page
45
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables. From previous page
Speaker lines
1 – 10
FS-7000JP SP OUT
(1st unit)
JP ZONE CONT
JP CONT
Speaker lines
41 – 50
FS-7000JP SP OUT
(5th unit)
JP ZONE CONT
JP CONT
Speaker lines
51 – 60
FS-7000JP SP OUT
(6th unit)
JP ZONE CONT
JP CONT
Speaker lines
91 – 100
FS-7000JP SP OUT
(10th unit)
JP ZONE CONT
JP CONT
46
[Connections between FS-7000RF and FS-7000CP/FS-7010CP when FS-7000GM is connected to FS-7000CP]
Connect the FS-7000RF's RF Zone Control Terminal to the RF Zone Control Terminal of the FS-7000CP
and/or FS-7010CP connected to the FS-7000JP. Do not connect the RF Zone Control Terminal of the FS-
7000CP and/or FS-7010CP connected to the FS-7000GM's GM Group Control Input.
JP ZONE/
GM GROUP CONT
RF ZONE CONT
FS-7010CP JP ZONE CONT
(1st unit)
JP CONT GM ZONE CONT
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
RF ZONE CONT
FS-7000RF
5 4 3 2 1
Speaker lines
1 – 10
FS-7000JP SP OUT
(1st unit)
JP ZONE CONT
JP CONT
Speaker lines
41 – 50
FS-7000JP SP OUT
(5th unit)
JP ZONE CONT
JP CONT
47
[Example of 20 groups/50 individual zones]
: Supplied cables
: Cables prepared separately
FS-7000CP
See page 64; Table for Cables.
JP ZONE/
GM GROUP CONT
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
RF ZONE CONT
FS-7000RF
5 4 3 2 1
Speaker lines
1 – 10
FS-7000JP SP OUT
(1st unit)
JP ZONE CONT
JP CONT
Speaker lines
41 – 50
FS-7000JP SP OUT
(5th unit)
JP ZONE CONT
JP CONT
48
6.7.2. Changing the FS-7000RM's zone selector keys into group selector keys
If the FS-7000GM is connected to the FS-7000RF, the FS-7000RM's individual zone selector keys can be
used as group selector keys, permitting multiple broadcast zones to be selected simultaneously by pressing a
single key. Further, connecting the FS-7010RM to the FS-7000RM makes up to 20 group selector keys
available.
: Supplied cables
See page 64; Table for Cables.
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
49
[Wiring Diagram (Example of 20 groups/100 individual zones)]
The figure below shows only the wiring related to group broadcasts. For the wiring of other models, refer to
the relevant system wiring diagrams, such as those for basic configuration and zone expansion.
: Supplied cables
See page 64; Table for Cables.
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 2 1 5 4 3 2 1
(1st unit )
GM GROUP
CONT OUT
GM GROUP
CONT IN GM ZONE CONT
FS-7000GM
2 1 5 4 3 2 1
(2nd unit )
GM ZONE CONT
GM GROUP CONT
5 4 3 2 1
FS-7000RF
2 1
* If the FS-7000GM is connected to the FS-7000CP and 20 group selector keys are created, the 6th, 7th, 8th,
9th and 10th units of the FS-7010CP should be read as the 7th, 8th, 9th, 10th, and 11th units.
50
6.8. Connecting the FS-7000AT to 4-Wire System Attenuators
When an emergency broadcast is made, or when a general urgency broadcast is made from the CP
microphone or FS-7000RM, if the FS-7000AT has been connected to the FS-7000JP, then 24 V DC power will
be supplied to the attenuators to allow these broadcasts to be made at maximum volume by overriding the
attenuators.
Tip
The type of attenuator that can be connected directly is a 4-wire system attenuator for which attenuation
becomes "0" when 24 V DC power is supplied. If another type is used, an additional external circuit must be
installed.
[System Operation]
• 24 V DC power is supplied to the 4-wire system attenuators when an emergency broadcast is made and the
emergency broadcast can bypass the attenuators.
• All-zone calls from the CP microphone or remote microphone can also be set to bypass attenuators.
• Attenuator lines correspond in a one-to-one relationship to the speaker lines of the FS-7000JP connected to
the FS-7000AT.
[Note]
The FS-7000PS to be connected to the FS-7000AT's 24 V DC Input for ATT Control Output must be different
from the one that supplies the 24 V DC power to each panel. Sharing the same FS-7000PS could cause
equipment failures. For the FS-7000PS connected to the 24 V DC Input for ATT Control Output, remove a
jumper wire between F.G and S.G located on the rear panel.
51
[Wiring Diagram]
: Supplied cables
: Cables prepared separately
Note See page 64; Table for Cables.
FS-7000PS Remove a jumper wire between
F.G and S.G (This unit only.)
230 V AC
DC POWER OUT
FS-7000PS
230 V AC
DC POWER OUT
FS-7000EV
DC POWER IN
EMERG OUT
EV OUT
3 EV CONT
FS-7000CP
EV CONT
EV IN
DC POWER IN
JP ZONE/
GM GROUP CONT
FS-7000JP
SP OUT
DC POWER IN
PRIORITY IN
JP ZONE CONT
AT CONT JP CONT
FS-7000AT
AT CONT
DC POWER IN
ATTENUATOR CONT / OUT
DC POWER IN Speaker and attenuator
FS-7012PA connections
(See next page.)
SP OUT
INPUT
230 V AC
VOL-BYPASS CONT IN
52
[Speaker/Attenuator Connection Diagram]
FS-7000JP
SP OUT
5 4 3 2 1
C H C H C H C H C H
COM
N SP
6 5 4 3 2 1
Note
The maximum output current of the FS-7000AT's ATT Control Output is 0.75 A per circuit. If the current
exceeds this limit, the FS-7000AT's built-in protection circuit cuts off the output. When a control current larger
than 0.75 A is needed, divide both the ATT Control Output lines and the FS-7000JP's speaker lines into 2 or
more lines.
53
6.9. Standby Amplifiers
So that the power amplifier can be automatically switched over to the standby amplifier to allow broadcasts to
continue when the amplifier fails, mount the YA-7000 in the power amplifier and connect the power amplifier to
the standby amplifier. (See page 76; Mounting the YA-7000 in the power amplifier.)
[Notes]
• Use a standby amplifier of the same type as the main amplifier, or one with a rated output larger than that of
the main amplifier. If the standby amplifier's rated power output is smaller than that of the main amplifier, the
standby amplifier could be damaged by overload.
• Set the volume controls on the front panels of both the main and standby amplifiers to the same position.
• Standby amplifiers cannot be used with other main amplifiers.
• Only 1 power amplifier (FS-7006PA or FS-7012PA) can be connected to each of the YA-7000's main and
standby amplifier inputs. Never connect 2 or more amplifiers to these terminals, as the excessive load could
cause the amplifier to fail. Connect the YA-7000's Speaker Output only to the FS-7000JP's Priority Input and
BGM Input.
54
[Wiring Diagram]
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables.
FS-7000PS
230 V AC
DC POWER OUT
FS-7000EV DC POWER IN
EV OUT
FS-7000CP
EV CONT EV IN
DC POWER IN
JP ZONE/
GM GROUP CONT
Speaker lines
SP OUT
FS-7000JP DC POWER IN
PRIORITY IN
JP ZONE CONT
JP CONT
SP OUT
INPUT
230 V AC
VOL-BYPASS CONT IN
FS-7012PA
(Standby amplifier)
SP OUT
INPUT
230 V AC
VOL-BYPASS CONT IN
55
6.10. Timer-Operated Equipment
To make timer-operated broadcasts, connect the device equipped with the play make output to the FS-
7000CP's Timer Input as follows. While the Timer Input's (+) and (–) terminals are closed, audio signals
entering the Timer Input are output to all speaker lines.
[Connection Diagram]
FS-7000CP
TIMER IN
H
E
Cable used: See page 66; Table for Cables.
Audio output C
BGM player
To enable telephone paging, connect control and audio signals from the telephone exchange's paging trunk to
the FS-7000CP's Paging Input. While the Paging Input's (+) and (–) terminals are closed, audio signals
entering the Paging Input are output to all speaker lines.
[Connection Diagram]
FS-7000CP
PAGING IN
LEVEL
Control signal
[Settings]
Set the Paging Input Sensitivity Selector Switch to "–60 dBV" (microphone signal level) or "–20 dBV" (line
signal level) depending on the audio signal level connected to the Paging Input.
56
6.12. BGM Players
The FS-7000CP is equipped with 4 BGM Inputs (BGM IN 1 – 4) for broadcasting background music.
The BGM Input 1 is provided with a muting function* that overrides other BGM Inputs 2 – 4.
*Muting function: A function that automatically decreases the volume of original broadcast when another
broadcast is initiated during original broadcast, and restores the original broadcast volume
level when the other broadcast is completed.
FS-7000CP
BGM IN
BGM IN 1
4 3 2
MUTE LEVEL
(dBV)
• BGM input 1 is monaural. When using a stereo device, mix the left and right channel signals before
connecting.
• BGM Inputs 2 through 4 are equipped with stereo connection terminals to facilitate the connection of
playback devices such as CDs and MDs. On each BGM input, its left and right channel signals are mixed
inside the FS-7000CP and converted to a monaural signal.
[Settings]
1. BGM Input 1 Sensitivity Selector Switch
Set this input sensitivity to "–60 dBV" (microphone signal level) or "–20 dBV" (line signal level) depending
on the audio signal level connected to the BGM Input 1.
2. Mute Switch
The signal levels of BGM Inputs 2 through 4 can be attenuated by the signal entering the BGM Input 1.
Setting the switch to ON attenuates the signals to Inputs 2 through 4, while setting it to OFF causes these
inputs to be mixed.
57
6.13. FS-7000EV
Connecting the FS-7000EV enables automatic evacuation guidance broadcasts that are interlocked with floor-
identifier signals from the connected automatic fire alarm system or manually operated voice guidance
broadcasts. The FS-7000EV's built-in voice alarm provides pre-recorded fire evacuation announcements and
false-alarm announcements, the recordings on which can be changed as needed, for example when used at
installation sites. (For the recording method, refer to the separate Operating Instructions.)
[Wiring Diagram]
: Supplied cables
: Cables prepared separately
FS-7000PS See page 64; Table for Cables.
230 V AC
DC POWER OUT
FS-7000EV
DC POWER IN
EV OUT
FS-7000CP
EV CONT
DC POWER IN EV IN
JP ZONE /
GM GROUP CONT
FS-7000JP Speaker
DC POWER IN SP OUT
lines
PRIORITY IN
JP ZONE CONT
JP CONT
FS-7012PA
SP OUT
INPUT
230 V AC
VOL-BYPASS CONT IN
58
6.14. Automatic Fire Alarm Systems
Fire evacuation announcements can be made to the broadcast zones selected automatically when the
connected automatic fire alarm system is activated. The FS-7000EV is used for evacuation guidance
broadcasts. Connect the instruction signals for selecting broadcast zones, which are transmitted from the
connected automatic fire alarm system, to the Fire Alarm System Input of the FS-7000CP or FS-7010CP.
If the Fire Alarm System Input's Terminals 1 and C are shorted, then the FS-7000JP's Speaker Output 1 is
selected. Similarly, Speaker Output 10 is selected at the Fire Alarm System Input 's Terminal 10. When a
single instruction signal covers a single floor with multiple broadcast zones, make connections so that the
instruction signal is routed to multiple fire alarm inputs and these zones can be selected simultaneously via a
single instruction signal. If announcements must be automatically broadcast to the fire floor, and immediately
upper and lower floors, the automatic fire alarm system needs be set to output such an instruction signal
immediately after smoke detectors are activated.
[Note]
Connect the instruction signal from the automatic fire alarm system to the Fire Alarm System Input of the FS-
7000CP and FS-7010CP connected to the FS-7000JP. Avoid connecting the signal to the FS-7000CP and
FS-7010CP connected to the FS-7000GM's GM Group Control Input.
[Wiring Diagram]
FS-7000CP
C C 10 1
1 – 10, C
11 – 20
C 10 1
59
6.15. Power Failure Backup
If broadcasts need to continue even during power failures, power must be supplied from an uninterruptible
power supply system (UPS) or emergency power supply unit.
6.15.1. Providing Backup Power Using an Uninterruptible Power Supply (UPS) System
Using a UPS as a backup power source permits both emergency and general-purpose broadcasts to continue
without interruption even if the main power source fails.
Procure a UPS that meets the following requirements and use it to supply AC power to equipment like the FS-
7000PS, FS-70006PA and FS-7012PA that must operate continuously even during power failures. If the UPS
does not meet the following requirements, it may shorten the amount of time that backup power can operate
and/or may prevent continued broadcasts. Therefore, it is important that the UPS selected meets the
necessary requirements.
[UPS Requirements]
• Switching time: Under 10 ms
• Capacity (W) is larger than the total capacity (W) of equipment being backed up.
• Capacity (VA) is larger than the total capacity (VA) of equipment being backed up.
• Backup time, calculated from the total capacity (W and VA), is over twice as long as the desired backup
time.
• Output wave should be a sine wave.
6.15.2. Power Backup Using the DS-029B Emergency Power Supply Panel
When the DS-029B is being used for power backup, emergency broadcasts can still be made even during
power failures, but general-purpose broadcasts become unavailable. Only equipment other than the FS-
7006PA and FS-7012PA can be backed up using the emergency power supply unit. Therefore, power
amplifiers that operate on 24 V DC power must be used, or a UPS must be prepared for the FS-7006PA and
FS-7012PA.
I2
Discharge current I (A)
I1
0
T1 T2
Time T (min)
The Storage battery capacity C required to operate for a fixed period of time (T2) after waiting for a fixed
period of time (T1) can be calculated as follows. Select a battery with the capacity larger than the calculation
result. Using Table 1 (Battery capacity conversation time) or Approximate expression (A), determine Capacity
conversion time K corresponding to Discharge time T, then calculate the required battery capacity using the
equation on the next page. Also, use Table 2 (Current consumption during power failures) to determine the
current consumption during standby or operation.
60
Storage battery capacity C (Ah) = 1 [ K 1 I 1 + K 2 ( I 2 - I 1 ) ]
L
Where,
C: Required storage battery capacity at 25°C
L: Maintenance rate* (generally 0.8)
K1: Capacity conversion time corresponding to the sum (T1+T2) of Waiting time T1 and Operation time T2.
K2: Capacity conversion time corresponding to Operation time T2.
I1: Current consumption in standby mode from the time that power fails until emergency broadcasting begins.
This is the sum of all currents needed by the FS-7000EV, DS-029B, and other equipment consuming
power even during power failures.
I2: Power consumption during emergency broadcasts (the 24 V DC current consumption of the entire
system). When 4-wire system attenuators are connected, their current consumptions are also included.
*Maintenance rate is a correction value used to guarantee needed battery capacity and satisfy specified load
characteristics while accounting for variations caused by battery age and usage conditions. As a general
guideline, it is assumed that battery capacity decreased to 80% of the original represents the end of the
battery's useful life, and therefore a maintenance rate of 0.8 is used in these calculations.
When capacity conversion coefficients corresponding to the operation time (discharge time) of more than 100
minutes is needed, approximate values can be obtained from the following expression:
Confirm attenuator current consumption using the relevant specification sheets or manuals.
61
[Calculation Example]
Storage battery capacity required for a system of the following configuration to operate for 10 minutes after
waiting for an hour from the start of a power failure can be calculated as follows:
K1: 1.80 (60 minutes of standby time + 10 minutes of operation time = 70-minute capacity conversion time)
K2: 0.333 (capacity conversion time for 10-minute operation time)
I1: 0.04 A (total standby current consumption from the above table)
I2: 0.90 A (total operation current consumption from the above table)
= 0.45
From this, it can be seen that if a battery with capacity of 0.45 Ah is used, the system will be able to operate
for 10 minutes.
62
[Wiring Diagram]
The figure shows only the wiring related to the DS-029B Emergency Power Supply Panel.
For the wiring of other models, refer to the relevant system wiring diagrams, such as those for basic
configuration and zone expansion.
: Supplied cables
: Cables prepared separately
See page 64; Table for Cables.
DS-029B
230 V AC
FS-7000PS
CONT
230 V AC START
DC POWER OUT IN
EMERG POWER
PS CONT
FS-7000EV
DC POWER IN
PS CONT
EV CONT
EV OUT
FS-7000CP
EV CONT
DC POWER IN EV IN
JP ZONE /
GM GROUP CONT
JP CONT
Speaker lines
FS-7000JP
DC POWER IN SP OUT
JP ZONE CONT
JP CONT
Note
When not connecting the DS-029B Emergency Power Supply Panel, Cables No. 18 and No. 19 connecting
between both PS CONT terminals of the FS-7000PS and FS-7000EV are not needed.
63
7. TABLE FOR CABLES
Each number corresponds to the cable number in wiring diagrams.
1 1
XAP14P XAP14P
14 14 FS-7010CP 1
60 cm
Terminals to be connected
FS-7000CP [CP CONT] <--> FS-7010CP [CP CONT]
FS-7010CP [CP CONT] <--> FS-7010CP [CP CONT]
1 1
XAP4P XAP4P
4 4
2.5 m
FS-7000JP 1
Terminals to be connected
FS-7000CP [JP CONT] <--> FS-7000JP [JP CONT]
FS-7010CP [JP CONT] <--> FS-7000JP [JP CONT]
1 1
XAP5P XAP5P
5 5
60 cm FS-7000EV 1
Terminals to be connected
FS-7000CP [EV CONT] <--> FS-7000EV [EV CONT]
1 1
XAP6P SMR6P
6 6
2.5 m FS-7000RF 1
Terminals to be connected
FS-7000CP [RF CONT] <--> FS-7000RF [RF CONT]
1 1
SMR10P SMR10P
10 10
2.5 m
Terminals to be connected
FS-7000JP 1
FS-7000CP [JP ZONE/GM GROUP CONT] <--> FS-7000JP [JP ZONE CONT]
FS-7000GM 7
FS-7000CP [JP ZONE/GM GROUP CONT] <--> FS-7000GM [GM GROUP CONT IN]
FS-7010CP [JP ZONE CONT] <--> FS-7000JP [JP ZONE CONT]
FS-7010CP [JP ZONE CONT] <--> FS-7000GM [GM GROUP CONT IN]
FS-7010CP [GM ZONE CONT] <--> FS-7000GM [GM ZONE CONT]
FS-7000GM [GM ZONE CONT] <--> FS-7000RF [GM ZONE CONT]
FS-7000GM [GM GROUP CONT IN] <--> FS-7000RF [GM GROUP CONT]
FS-7000GM [GM GROUP CONT IN] <--> FS-7000GM [GM GROUP CONT OUT]
64
No. Cables Equipment Quantity
1 1
XAP11P SMR10P
10 10
11
FS-7010CP 1
2.5 m
FS-7000RF 1
Terminals to be connected
FS-7000CP [RF ZONE CONT] <--> FS-7000RF [RF ZONE CONT]
FS-7010CP [RF ZONE CONT] <--> FS-7000RF [RF ZONE CONT]
FS-7010CP [RF ZONE CONT] <--> FS-7000GM [GM ZONE CONT]
1 1
XAP12P XAP12P
12 12 FS-7000AT 1
60 cm
Terminals to be connected
FS-7000JP [AT CONT] <--> FS-7000AT [AT CONT]
1 1
RJ45 RJ45
8 8
3m
Terminals to be connected
FS-7000RM [RF LINK] <--> FS-7000RF [AUDIO, DC24 V, BUS] FS-7000RM 1
Note: For the FS-7000RF, detach the RJ45 connector and connect the stripped
cable end.
Pin1 (white/orange): Not connected Pin5 (white/blue): AUDIO C
Pin2 (orange) : Not connected Pin6 (green): BUS –
Pin3 (white/green): BUS + Pin7 (white/brown): DC24 V +
Pin4 (blue): AUDIO H Pin8 (brown): DC24 V –
1 8
XAP8P XAP8P
8 1
8 cm FS-7010RM 1
Terminals to be connected
FS-7000RM [EXTENSION] <--> FS-7010RM [EXTENSION]
FS-7010RM [EXTENSION] <--> FS-7010RM [EXTENSION]
65
7.2. Cables To Be Prepared by the Customers
The following tables show the cables used as viewed from each component and the connectors they are to be
connected to. Since the cables used by a component to connect to the target component are also shown in
the target component's cable list, take care not to duplicate connections when counting the number of cables
needed.
• The 3P removable terminal plugs supplied with each component are referred to in abbreviated form as
"3PTB".
• Determine the cable length depending on the system equipment configuration.
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
2 2-core
RF IN 3PTB shielded cable 3PTB RF OUT FS-7000RF
3 Single-core
EV IN 2PTB shielded cable 2PTB EV OUT FS-7000EV
2-core
BGM OUT 3PTB shielded cable 3PTB INPUT FS-7006PA
4
FS-7012PA
2-core
PRIO OUT 3PTB shielded cable 3PTB INPUT FS-7006PA
5
FS-7012PA
6 2-core
BGM IN 1 3PTB –– –– BGM player
shielded cable
BGM IN 2 2P RCA jack Single-core –– –– BGM player
shielded cable x 2
7 BGM IN 3
BGM IN 4
2-core Telephone
PAGING IN 5PTB shielded cable –– Audio
8 exchange
Parallel PVC cable –– Control (paging trunk)
9 Single-core Playback
AUX IN 2PTB shielded cable –– –– equipment, etc.
Single-core Timer-operated
TIMER IN 4PTB shielded cable –– Audio
10 playback equipment
Parallel PVC cable –– Control
Heat-resistant
FIRE ALARM 12PTB –– –– Fire alarm system
cable
SYSTEM
11 No. of connected
fire alarm lines + 1
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
Heat-resistant
FIRE ALARM 12PTB –– –– Fire alarm system
cable
SYSTEM
11 No. of connected
fire alarm lines + 1
66
7.2.3. FS-7000JP Junction Panel
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
12 FS-7012PA
YA-7000
13 FS-7012PA
YA-7000
DC POWER OUT M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER IN FS-7000CP
FS-7010CP
FS-7000JP
1 FS-7000AT
FS-7000EV
FS-7000GM
FS-7000RF
ATTENUATOR
DC POWER OUT M3 screw terminal Parallel PVC cable M3 screw terminal CONT FS-7000AT
17
DC POWER IN
18 PS CONT/
PS CONT/CONT M3 screw terminal Parallel PVC cable M3 screw terminal FS-7000EV
CONT
19 PS CONT/START PS CONT/
M3 screw terminal Parallel PVC cable M3 screw terminal START FS-7000EV
20 EMERG POWER/
IN M3 screw terminal Parallel PVC cable M4 screw terminal OUTPUT DS-029B
21 EMERG POWER/
CONT M3 screw terminal Parallel PVC cable M4 screw terminal REMORT (left) DS-029B
22 EMERG POWER/
START M3 screw terminal Parallel PVC cable M4 screw terminal REMORT (right) DS-029B
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
67
7.2.6. FS-7000EV Voice Evacuation Panel
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
3 Single-core
EV OUT 2PTB 2PTB EV IN FS-7000CP
shielded cable
18 PS CONT/CONT M3 screw terminal Parallel PVC cable M3 screw terminal PS CONT/CONT FS-7000PS
19 PS CONT/START M3 screw terminal Parallel PVC cable M3 screw terminal PS CONT/START FS-7000PS
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
1 DC POWER IN M3 screw terminal Parallel PVC cable M3 screw terminal DC POWER OUT FS-7000PS
2 2-core
RF OUT 3PTB 3PTB RF IN FS-7000CP
shielded cable
AUDIO M3.5 CAT. 5 STP RJ45 RF LINK FS-7000RM
screw terminal
26 DC24 V
BUS
BUS
68
7.2.10. FS-7006PA/7012PA Power Amplifiers
4 2-core
INPUT 3PTB 3PTB BGM OUT FS-7000CP
shielded cable
5 2-core
INPUT 3PTB 3PTB PRIO OUT FS-7000CP
shielded cable
12 SP OUT M4 screw terminal Speaker cable M4 screw terminal BGM IN FS-7000JP
30 SP OUT M4 screw terminal Speaker cable M4 screw terminal SUB AMP IN YA-7000
SUB AMP IN M4 screw terminal Speaker cable M4 screw terminal SP OUT FS-7006PA
30
FS-7012PA
69
8. REMOVABLE TERMINAL PLUG CONNECTION
Cautions
• Avoid soldering cable conductor, as contact resistance may increase when the cable is tightened and the
solder is crushed, possibly resulting in an excessive rise in joint temperatures.
• Use cables of AWG 12 – 24.
20 mm
Connector connections
Step 2. Retighten the terminal screw. (Pull on the cable to ensure it is securely connected.)
Slotted screwdriver
2 1
Tightens Loosens
Terminal screw
Shielded cable 1
Tip
Recommended slotted screwdriver type: Screwdriver with blade that is 3 mm in width
3 mm
70
9. PARTS INSTALLATION
9.1. Installing Diodes on the FS-7000GM's Circuit Board
Note
All installations described in this chapter should be performed by qualified professionals only.
Failure to follow this instruction could lead to improper or faulty installation and equipment malfunctions.
Prior to installation, confirm that the following parts have been included in the package:
Step 2. Solder the required parts to the circuit board according to the setting contents.
Note
Mount the parts on the circuit board surface as shown by the indicator markings and solder them from
the reverse side of the board.
2-1. Solder 7 EH10P posts to connectors CN101, CN202 and CN301 through CN305 (shown shaded in
the figure below).
CN101
Circuit board
CN202
Circuit board
indicator markings
71
2-2. Solder diodes to the circuit board according to group broadcast channel assignments.
For example, the board in the figure below would function as follows:
• Pressing Group Selector key 3 permits broadcasts to zones 3, 5, and 6.
• Pressing Group Selector key 5 permits broadcasts to zones 6, 7, and 11.
Install a diode at each of the speaker lines covered by each Group Selector key.
Circuit board
Max. height after soldering: 8mm
Solder
Trim excess lead wires after soldering.
72
Step 3. Remove the 5 screws (indicated by the arrow in the figure) that fix the FS-7000GM's case, then
remove the case.
FS-7000GM’s top
Step 4. Detach the tapes that fix cables from connectors CN4 and CN9.
Cables are affixed to the inside of the unit's bottom surface with tape.
These will be connected in Step 6.
Step 5. Using the supplied screws, mount the soldered circuit board on the mounting sleeves located on the
inside of the unit's bottom surface.
Parts-mounted side
Up Circuit board
Sleeve
Notes
• Ensure the correct mounting side by confirming the orientation of screw holes when mounting on the circuit
board.
• Take care not to pinch the cables in Step 4 between the circuit board and the sleeves during installation.
73
Step 6. Connect the FS-7000GM unit to its circuit board using the supplied connector-equipped cables.
Connect one end of the cable to CN301 on the FS-7000GM circuit board and insert the other cable
end into the rear panel-mounted connector receptacle opening for "GM ZONE CONT 1" (indicated on
the rear panel).
Similarly, connect the other cables to CN302 and "GM ZONE CONT 2," CN303 and "GM ZONE
CONT 3," CN304 and "GM ZONE CONT 4," and CN305 and "GM ZONE CONT 5."
Then, insert the cables affixed to the FS-7000GM's bottom surface with tape into CN101 and CN202
on the circuit board. The CN101 connects to CN4 on the circuit board already mounted in the FS-
7000GM unit, while the CN202 connects to CN9 (refer to the internal wiring diagram).
Connector
1 2 3 4 5
CN4 CN9
74
9.2. Changing the Operation Mode of the FS-7000RM Microphone
By changing the position of the unit's internal jumper, microphone operation mode can be changed from the
default "PTT" (Press-to-Talk) mode, which permits microphone announcements only while the Talk key is
pressed, to "Alternate" mode, in which microphone announcements alternate between ON and OFF with each
press of the Talk key.
Note
All changes described in this chapter should be performed by qualified professionals only. Failure to follow this
instruction could lead to improper or faulty installation and equipment malfunctions.
Step 1. Remove the 8 screws on the FS-7000RM's bottom surface and remove the unit's case.
Step 2. Change the position of the jumper socket located on the circuit board mounted on the removed base
case.
Step 3. Replace the case after the above modification has been completed.
Note
Take care not to pinch cables when replacing the case.
75
10. MOUNTING THE YA-7000 IN THE POWER AMPLIFIER
Step 1. Use nippers or a similar tool to remove the amplifier's rear-mounted YA-7000 receptacle
panel by cutting away the portions marked with (6 places).
Connector
Step 3 . Mount the YA-7000 in the power amplifier's rear panel using the 2 supplied M3x6 screws.
Step 4 . Set the YA-7000's Operation Mode Selector Switch to the Normal position.
76
11. FAILURE INDICATION
The FS-7000CP, FS-7000JP, FS-7000RF, FS-7000RM, FS-7006PA, and FS-7012PA are equipped with
failure indicators that show the status of any problems that may occur. When such an indicator lights or
flashes, it means that a problem may have occurred in the equipment or in the wiring.
If the power indicator is not illuminated, the equipment could be malfunctioning. In such cases, check to see if
power is being supplied correctly, or if a fuse has blown. A blown fuse often means that the problem may have
occurred within the wiring as well as in the equipment itself.
In such cases, replace the fuse(s) and check the correctness of the wiring before turning the power on again.
If an indicator lights continuously or flashes, the following possible causes may be considered:
FS-7000CP's One or more of the speaker lines have The speaker line corresponding to the FS-
Speaker Line Short shorted, causing the associated line 7000JP's Speaker Line indicator that
indicator lights. protection fuse of FS-7000JP to blow. continuously lights red may be shorted.
Locate and fix the speaker line short,
FS-7000JP's replace the line protection fuse, then press
Speaker Line the Reset switch mounted on the rear
Indicator lights red. panel of the FS-7000JP.
FS-7000RF's Fault Communications are not being • Confirm that the number that has been
indicator lights red. performed correctly with the FS- set using the setting switch agree with
7000RM units of the number the actual number of the connected FS-
designated using the setting switch, or 7000RM units.
equipment failures may have occurred. • Confirm that the FS-7000RM's address is
set correctly.
• Confirm that there is no fault with the
wiring leading to the FS-7000RM.
FS-7000RM's Fault Communication with the FS-7000RF is • Confirm that the number of units that has
indicator lights. not being performed correctly, or been set using the FS-7000RF's setting
equipment failures may have occurred. switch agrees with the actual number of
the FS-7000RM units connected.
• Confirm that the unit has the correct
address settings.
• Confirm that there is no fault with the
wiring leading to the FS-7000RF.
77
Symptom Possible Cause Check/Remedy
FS-7006PA's or Output is not being provided correctly Remove the output wiring and turn the
FS-7012PA's Fault because of a short in the output wiring. power on again. If the Fault indicator light
indicator lights. goes out, then the problem may be with
the wiring. Check the wiring to determine
where the problem may be.
Equipment failure or excessive high Check the following points if the indicator
heat build-up inside the unit. automatically goes out within 30 minutes
after it has lit.
• Check installation conditions for
appropriate ventilation.
• Check the connected load capacity for
possible overload.
• Check to see if input and output cables
are installed close to each other.
78
12. SPECIFICATIONS
12.1. FS-7000CP Control Panel
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Microphone ................................................ 1 Removable terminal plug (4 pins) .............. 1
Removable terminal plug (2 pins) .............. 2 Removable terminal plug (5 pins) .............. 1
Removable terminal plug (3 pins) .............. 4 Removable terminal plug (12 pins) ............ 1
79
12.2. FS-7010CP Expansion Control Panel
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Connection cable (14 pins, 60 cm) ............. 1 Removable terminal plug (12 pins) ............ 1
Connection cable (10 pins, 2.5 m) ............. 1
80
12.3. FS-7000JP Junction Panel
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Fuse (0.5 A) ............................................... 2 Connection cable (4 pins, 2.5 m) ............... 1
Connection cable (10 pins, 2.5 m) ............. 1 Removable terminal plug (2 pins) .............. 2
81
12.4. FS-7000PS DC Power Supply Panel
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Power cord (1.8 m) ..................................... 1 Fuse (8 A) .................................................. 1
Fuse (6.3 A) ............................................... 1
Note: The design and specifications are subject to change without notice for improvement.
• Accessory
Connection cable (12 pins, 60 cm) ............ 1
82
12.6. FS-7000EV Voice Evacuation Panel
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Connection cable (5 pins, 60 cm) .............. 1 Removable terminal plug (3 pins) .............. 1
Removable terminal plug (2 pins) .............. 3
83
12.7. FS-7000GM Group Matrix Panel
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Circuit board ............................................... 1 Machine screw M3 x 4 ............................... 8
Posts with base (EH10P) ........................... 7 EH-SMP connector .................................... 5
Diode ...................................................... 200 Connection cable (10 pins, 2.5 m) ............. 7
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Connection cable (6 pins, 2.5 m) ............... 1 Removable terminal plug (3 pins) .............. 1
Connection cable (10 pins, 2.5 m) ............. 1
84
12.9. FS-7000RM Remote Microphone
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessory
Connection cable (3 m) .............................. 1
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Connection cable (8 pins, 8 cm) ................ 1 Linkage bracket B ...................................... 1
Linkage bracket A ...................................... 2 Tapping screw 3 x 8 ................................. 12
85
12.11. FS-7006PA/7012PA Power Amplifiers
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Terminal cover ........................................... 1 Removable terminal plug (2 pins) .............. 2
Machine screw M4 x 8 ............................... 2 Removable terminal plug (3 pins) .............. 2
86
12.12. YA-7000 Amplifier Auto Switching Module
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Terminal cover ........................................... 1 Machine screw M4 x 8 ............................... 2
Machine screw M3 x 6 ............................... 2
87
SUPPLEMENT
1. SETTINGS TABLE
Record switch settings and internal jumper positions in this table in order to facilitate maintenance.
Mark the appropriate items with a check.
FS-7000CP
FS-7000RF
88
FS-7000RM Address #0
FS-7000RM Address #1
FS-7000RM Address #2
FS-7000RM Address #3
89
FS-7000GM
Connected equipment
Group selector key No. 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Speaker 25
line No. 26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
90
2. FS-7000RM/FS-7010RM ZONE IDENTIFICATION CARDS
Write the names of broadcast zones on the zone identification cards for the FS-7000RM and FS-7010RM.
Use this page as a template, either copying the card itself or creating a similar card with the same dimensions.
Tear-off line
Insertion
direction
136
7 9 x 13 = 117 Unit: mm
Insertion
direction
29
30
FS-7000RM
91
133-22-065-60