SK 3336.

455
Chillers Blue e
State: 04/05/2022 (Source: rittal.com/com-en)
SK 3336.455 - Chillers Blue e 8 - 48 kW
The Blue e chiller in the floor standing enclosure provides centralised, efficient cooling of the
cooling water. The microchannel technology reduces the volume of refrigerant required. Intuitive
operation via touch display and intelligent communications interfaces ensure user-friendly
operation and analysis. Integral safety functions, included as standard, ensure maximum safety.
Delivery times are also shortened, thanks to pre-defined option packages.

Features
Model No. SK 3336.455

Design Robust industrial standard


Variable air routing is possible via the l/h or r/h side panel
Floating contact for collective fault signal

Benefits Reduced volume of refrigerant, thanks to microchannel technology


Touch display for simplified user guidance
Integral safety functions
Pre-configured options

Colour Enclosure: RAL 7035


Base/plinth: RAL 7016

Supply includes Chiller wired ready for connection


Multilingual documentation including functional diagram and wiring
plans

Protection category to IEC 60 529 IP 44 (electrics)

Total cooling output Tw10 / Tu32 Cooling output Tw10 Tu32/50 Hz: 19.9 kW
Cooling output Tw10 Tu32/60 Hz: 22.9 kW

Total cooling output Tw18 / Tu32 Cooling output Tw18 Tu32/50 Hz: 24.4 kW
Cooling output Tw18 Tu32/60 Hz: 26.3 kW

Total cooling output to Cooling output Tw18 Tu35/50 Hz: 22.93 kW


DIN EN 14511 Tw18 / Tu35 Cooling output Tw18 Tu35/60 Hz: 25.29 kW

Air throughput (unimpeded air Air throughput at 50 Hz: 12,000 m³/h


flow) Air throughput at 60 Hz: 14,500 m³/h

Rated operating voltage 400 V, 3~, 50 Hz


460 V, 3~, 60 Hz

© Rittal 2022 2
Features
Dimensions Width: 760 mm
Height: 1,265 mm
Depth: 1,515 mm

Control voltage 24 V DC Yes

Precision controller Yes

Performance-enhanced pump Yes

Noise level 79 dB(A)

Operating temperature range 10 °C...43 °C

Operating temperature range of 10 °C...25 °C


cooling medium

Temperature hysteresis ± 0.25 K

Refrigerant/cooling medium Refrigerant: R410A


Quantity: 1.45 kg
Global Warming Potential (GWP): 2,088
CO2 equivalent (CO2e): 3.03 t

Pump pressure At 50 Hz: 4.5 bar


At 60 Hz: 6.7 bar

Volumetric flow (cooling medium) At 50 Hz: 55 l/min


At 60 Hz: 75 l/min

Power consumption Pel At 50 Hz: 11.3 kW


At 60 Hz: 14.4 kW

Rated current max. At 50 Hz: 22.6 A


At 60 Hz: 24.1 A

Water connections R 1¼" internal thread

Number of cooling circuits 1

Tank Material: PE plastic


Volume: 78 l

Operating weight 404 kg

Packs of 1 pc(s).

Weight/pack 326 kg

Copper weight (kg per piece) 0

© Rittal 2022 3
Features
Customs tariff number 84186900

EAN 4028177926905

ETIM 7.0 EC002516

ECLASS 8.0 27180713

Approvals
Approvals Approvals

Explanations Declaration of conformity

© Rittal 2022 4
Tender text
3336.455,,
Chiller Blue e,,

The Blue e chiller in the floor standing enclosure provides centralised,


efficient cooling of the cooling water.,,
The microchannel technology reduces the volume of refrigerant required.
Intuitive operation via touch display and intelligent communications
interfaces ensure user-friendly operation and analysis.,,
The integrated remote monitoring in the basic unit additionally ensures
maximum safety.,,

Total cooling output TW10 TU32, 50/60 Hz: 19,9 / 22,9 kW,,
Total cooling output TW18 TU32, 50/60 Hz: 24,4 / 26,3 kW
Total cooling output TW18 TU35, 50/60 Hz: 22,93 / 25,29 kW,,

Power consumption 50/60 Hz: 11,3 / 14,4 kW,,

Rated power input 50/60 Hz: 22,6 / 24,1 A,,

Volumetric flow (cooling medium) 50/60 Hz: 55 / 75 l/min,,

Pump pressure 50/60 Hz: 4,5 / 6,7 bar,,

Rated operating voltage: 400 V, 3~, 50 Hz; 460 V, 3~, 60 Hz,,

Colour: Enclosure: RAL 7035; Base/plinth: RAL 7016,,

Dimensions [WxHxD]: 760x1265x1515 mm,,

Operating temperature range: 10 °C to 43 °C,,


Liquid media temperature range: 10 °C to 25 °C,,

Temperature hysteresis: +/- 0,25 K,,

Number of cooling circuits: 1,,

Refrigerant / Quantity:,,R410a / 1450 g

Tank (Material): PE plastic,,

© Rittal 2022 5
Tank (contents): 78 l,,

Water connections: R 1 1/4" IG,,

Options: Performance-enhanced pump, precision controller, control


voltage 24 V DC,,

Noise level: 79 dB(A),,

Protection category IP to IEC 60 529: IP 44 (electrics),,

Weight: 326 kg,,


Weight in operating status: 404 kg