0% found this document useful (0 votes)
49 views2 pages

Product Bulletin: Series Automatic Transfer Switch Equipment

The document describes GE Zenith's ZTX Series automatic transfer switches for residential and light commercial use. The switches range in size from 40 to 400 amps and include microprocessor controls. The standard R-M3 control panel provides voltage and frequency sensing as well as time delays for transfer and retransfer. Optional R-M4 control adds a user interface.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views2 pages

Product Bulletin: Series Automatic Transfer Switch Equipment

The document describes GE Zenith's ZTX Series automatic transfer switches for residential and light commercial use. The switches range in size from 40 to 400 amps and include microprocessor controls. The standard R-M3 control panel provides voltage and frequency sensing as well as time delays for transfer and retransfer. Optional R-M4 control adds a user interface.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

g

GE Zenith Controls Product Bulletin


ZTX Series
Automatic Transfer Switch Equipment
GE Zenith’s ZTX Series switches are built for
residential and light commercial applications
requiring the dependability and ease of opera-
tion found in a power contactor switch.
• Ratings 40 to 400 amps (2, 3 and 4 pole)
• UL 1008, CSA and IEC
listed to 480 VAC 50/60Hz
• Double throw, mechanically interlocked
contactor mechanism
• Electrically operated, mechanically held
• Designed for standby applications

GE Zenith’s ZTX switches are equipped with the


R-M3 control panel (Module 3) as standard. This
microprocessor control includes: ZTX Series Light Commercial Switch
• Undervoltage sensing (90% pickup/ with R-M3 Control Panel (covers removed)
80% dropout) of the utility source
• Voltage and frequency sensing of
the generator source (90% voltage/ • Selectable 7, 14, 21 or 28 day (factory set
95% frequency pickup) 28 days) generator exerciser timer
• Time Delay Engine Start - 5 seconds (P) • Diagnostic LED indications
• Time Delay Engine Warmup -
Transfer to Generator - 20 seconds (W) Additional options include:
• Time Delay Utility Stabilization/ A3/A4 Auxiliary contacts (1 each) closed
Retransfer to Utility - 5 minutes (T) in utility and generator positions
• Time Delay Engine Cool Down - 5 minutes (U) • Special timer settings
All time delays are fixed.

The unit is available in open type,


NEMA 1 or NEMA 3R enclosures.
The R-M4 control option (Module
4) adds a user interface and func-
tionality, including:
• Indicating LEDs for power
availability, switch position
and load energized
GE Industrial Systems –
Power Equipment Business • Pushbuttons for test, engine
830 W. 40 th Street start (manual), generator ZTX with R-M4 Microprocessor Control Panel
Chicago, IL 60609 USA exerciser and diagnostic reset
773 299-6600, Fax: 630 850-6899
www.zenithcontrols.com

PB-1601E (9/01)
Specifications, Optional Features and Ordering Information
Ordering Information

Z T X R *
Block A Block C Block F Block E
Base Model Control Panel Operational Voltage Enclosure Type
R M 3 * C
2 5 NEMA 1 Enclosed
Microprocessor Control Panel 480V 3Ø, 3 wire, 60Hz
120/240V 1Ø, 3 wire, 60Hz
Module 3 No Control Interface S
R M 4 * 2 1 5 1 NEMA 3R

Block B Microprocessor Control Panel


120/208V 1Ø, 3 wire, 60Hz 440V 3Ø, 3 wire, 60Hz
X
Ampere Size Module 4 with Interface
3 Open Style Unit
5 2
4 2 0 * G
240V 3Ø, 3 wire, 60Hz 440V 3Ø, 3 wire, 50Hz
40 amps 200 amps
Enter the “G” Option 3 1 5 3
if the Engine Crank
8 2 2 Limiter Option is desired
208V 3Ø, 3 wire, 60Hz 440V 1Ø, 2 wire, 60Hz
80 amps 225 amps Block G
3 2 7 Accessories
1 0 3 0 220V 3Ø, 3 wire, 50Hz 277/480V 3Ø, 4 wire, 60Hz Then choose additional accessories
100 amps 300 amps
3 8 9 A3/A4
1 5 4 0 Block D 120/240V 3Ø, 4 wire, 60Hz 240/416V 3Ø, 4 wire, 60Hz Auxiliary Contacts (1 each)
150 amps 400 amps Switched Poles Closed in Normal
B 4 9 1 and Emergency
120/208V 3Ø, 4 wire, 60Hz 220/380V 3Ø, 4 wire, 60Hz
2 Poles

E 4 1 9 2
220/380V 3Ø, 4 wire, 50Hz
3 Poles 127/220V 3Ø, 4 wire, 60Hz For information on GE Zenith’s
ZTX OEM plans, please
F 9 3 consult our sales department.
4 Poles 240/416V 3Ø, 4 wire, 50Hz

Technical Specifications
Engine Cranking Limiter Lug Configuration
Amp Size Standard Lugs
The ZTX Series is available with an engine cranking module.
This accessory allows the engine to cycle crank 3 times with 40-150 1 - #8 to 3/0 AWG per pole
2 rests (10 seconds each), then it disconnects the engine start
function at the transfer switch if the engine fails to start. 200-225 1 - #6 to 250 MCM per pole

300-400 1 - #4 to 600 MCM per pole


Start signal disconnect also takes place on: overcrank, over-
speed, high temperature, low oil pressure and if the generator
circuit breaker is tripped or open.
UL 1008 Withstand and Closing Ratings
Coordinated Current
Specify accessory module as required: Amp Size
Molded Case Breakers Limiting Fuse *
M3G — Module 3 with crank limiter
R-M3 Control Panel M4G — Module 4 with crank limiter (12 - 28 VDC range) 40-225 30,000 200,000
(Single phase
300-400 50,000 200,000
version shown)
* consult factory for application information

Dimensions
Amp Size NEMA 1 NEMA 3R

40-100 18 H x 18 W x 8 D 18 H x 18 W x 8 D

150-200 24 H x 18 W x 10 D 24 H x 18 W x 10 D

150-225 36 H x 24 W x 14 D 36 H x 24 W x 14 D
Generator Crank Limiter Option
300-400 46 H x 24 W x 14 D 46 H x 24 W x 14 D

You might also like