Satchwell TM

DRT4453

ROOM TEMPERATURE SENSOR

Specification No: DRT4453.


This Room Temperature sensor is designed to provide temperature
control of heating and air conditioning plant. For typical applications
see relevant controller data sheets.

FEATURES
• Aesthetically styled, low profile packaging
• Enclosure to NEMA-1 standard
• Simple wiring and commissioning

Data Sheets DS 13.310 - UNC532 (BAS)


DS 2.021 - CSC DS 13.311 - UNC532 (Σ)
DS 2.041 - CMC DS 13.320 - UNC496 (BAS)
DS 2.105 - CZT DS 13.321 - UNC596 (BAS)
DS 2.110 - CXR DS 13.322 - UNC496 (Σ)
DS 2.701 - MMC4701 DS 13.323 - UNC596 (Σ)
DS 2.751 - MMC4601 DS 2.120 - KMC
DS 2.801 - IAC420 Multi-Lingual Instructions
DS 2.951 - IAC600 MLI 1.040 - Mounting
DS 10.101 - MN300 Details
DS 10.102 - MN440
DS 10.103 - MN500
DS 10.104 - MN620

Satchwell
SPECIFICATIONS
Type DRT4453
Temperature Sensor 'T' Type
Mounting Room
Temperature Sensing Range 0 to +50°C
Dimensions 121mm Height x 79mm Width x 24mm Depth
Output 5573Ω @ 20°C (see Characteristics)
Protection Class IP 10

Enclosure: Conforms to NEMA-1 standard


Wiring: 2-wire low voltage dc. Not polarised.
Operating Environment: 0 to +50°C; 10 to 90%RH non-condensing
Head: Moulded base with screw on lid.
Terminals: Four screw terminals, maximum cable size 1.0mm2
Characteristics: Non linear - see graphs in Characteristics section.
Compatible Controllers: BAS, Satchwell Σ, IAC, KMC, MMC, MN, CZU, CZT, CXR, CSC, CMC

CHARACTERISTICS
Sensor Temperature v Resistance
DRT4453: -5 to 100°C

10000

9000

8000

7000
Resistance (Ω)

6000

5000

4000

3000

2000

1000
Temperature (°C)
0
-5 0 5 10 20 25 30 35 40 45 55 60 65 70 75 80 90 95 100

Ohms 8092 7660 7182 6666 5573 5024 4492 3986 3517 3089 2358 2055 1791 1562 1363 1193 921 814 721

EUROPEAN COMMUNITY DIRECTIVES • A removable cover.


Cautions
This equipment meets all requirements of European Community
Directives for General Product Safety (92/59/EEC), and Refer to data sheet relevant to the controller to which sensor is to
Electromagnetic Compatibility (89/336/EEC). be connected.
Maximum resistance, 15Ω per core.
INSTALLATION
1. Unclip the cover (place thumb in middle of sensor, grasp top edge
INSTALLATION GUIDELINES of cover with fingers and pull firmly).
These sensors are suitable for indoor use only. When selecting a 2. Remove the electronic assembly from the base plate by loosening
mounting location, make certain the following conditions are met: the four captive screws at top of assembly.
• Do not install where excessive moisture, corrosive fumes, vibration, 3. Mount sensor base plate to single-gang junction box or flush to wall
or explosive vapours are present. using screws provided.
• Do not install near large contactors, electrical machinery, welding 4. Wire the sensor base plate as follows:
equipment, switches, and associated cabling a. Strip 6mm of insulation from wires.
• Locate where ambient temperatures do not exceed 50°C or fall b. Connect wires to screw terminals as shown in connection
below 0°C and relative humidity does not exceed 90% or fall below diagrams on Page 3.
10%, non-condensing.
c. Push excess wire back through the base plate to minimise air
LOCATION AND WIRING flow restriction.
Locate the sensor on an inside wall. The location should represent the 5. Set electronic assembly onto bottom hooks of base plate.
average temperature in the room or space. Make certain sensor is
located out of direct sunlight, away from sources of heat or cold, and 6. Secure electronic assembly to base plate by tightening all four
away from concealed ducts or pipes. screws at top of assembly.
The sensor comprises three major parts: 7. Insert bottom tabs of cover and then snap top of cover into place.
• A pre-wirable base plate for wiring to the controller.
• An electronic assembly containing the sensor and associated
circuitry.
2
Do not install screw in this
location. Damage to unit
will result.

MAINTENANCE
Cautions
This product contains no user serviceable parts.

CONNECTION DIAGRAMS

DRT

1 Temperature Output
(Non-Polarised)
2

DIMENSION DRAWINGS

76.2
79 24 60.3

38.1
48.4
121

1 2

3 4
118.5
82.6

Dimensions in mm

3
Cautions
• Do not apply power to the system until it has been checked by a
qualified technician and the commissioning procedures have been
completed.
• If any equipment covers have to be removed during the installation of
this equipment, ensure that they are refitted after installation to
comply with UL and CE safety requirements.
• These sensors must only be used in conjunction with the appropriate
TAC Satchwell controllers shown on Page 2.
• Observe wiring precautions given on the data sheet for the controller
that the sensor will be connected to.
• Do not exceed the maximum ambient temperature.
• Interference with parts under sealed covers invalidates guarantee.
• Design and performance of TAC Satchwell equipment is subject to
improvement and therefore liable to alteration without notice.
• Information is given for guidance only and TAC Satchwell does not
accept responsibility for the selection and installation of its products
unless information has been given to the Company in writing relating
to a specific application.
• A periodic system and tuning check of the control system is
recommended. Please contact your local TAC Satchwell office for
details.

Copyright © 2005, TAC AB TAC Headquarters


All brand names, trademarks and registered trademarks are Malmö, Sweden
the property of their respective owners. Information contained +46 40 38 68 50
within this document is subject to change without notice. All
rights reserved.
Satchwell Helpline
DS 1.040 12/05 +44 (0) 1753 611000
[email protected]

www.tac.com Satchwell

You might also like