Induced Draft Evaporative Condensers: S140-500 IOM/DEC 2001
Induced Draft Evaporative Condensers: S140-500 IOM/DEC 2001
IDC
INDUCED DRAFT
EVAPORATIVE CONDENSERS
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 2 INSTALLATION - OPERATION - MAINTENANCE
TABLE OF CONTENTS
Section 1.0 Pre-Installation ................................................................................... 4
1.1 Preface ................................................................................................... 4
1.2 Shipment Inspection ................................................................................ 4
1.3 Transit Damage Claims ............................................................................ 4
1.4 Unit Identification .................................................................................... 4
1.5 Safety Requirements ............................................................................... 4
1.6 Placement of IDC Units ........................................................................... 5
1.7 Field Piping Considerations for IDC Unit Installation ................................ 5
Section 2.0 Installation Procedures ....................................................................... 8
2.1 Installation Tools ...................................................................................... 8
2.2 Foundation Information ............................................................................ 8
2.3 Eliminator Placement ............................................................................ 12
2.4 Inlet Louver Installation ......................................................................... 12
2.5 Erecting the IDC Unit ............................................................................. 12
2.6 Optional Vibration Isolator ...................................................................... 12
Section 3.0 Startup & Operation .......................................................................... 16
3.1 Initial Startup (for new IDC Units) .......................................................... 16
3.2 Initial and Seasonal Start-Up ................................................................. 16
3.3 24-Hour Run In ...................................................................................... 17
3.4 Daily Operation ...................................................................................... 17
3.5 Seasonal Start up & Shutdown .............................................................. 18
3.6 Winter Operations .................................................................................. 18
Section 4.0 Maintenance ..................................................................................... 18
4.1 Maintenance Intervals ........................................................................... 18
4.2 Spare Parts Recommendations ............................................................. 20
4.3 Lubrication ............................................................................................. 21
4.4 Drivetrain ............................................................................................... 21
4.5 Sump Drainage ...................................................................................... 21
4.6 Belt Replacement and Tensioning .......................................................... 22
4.7 New Belt Run-in ..................................................................................... 22
4.8 Coil Assembly ....................................................................................... 22
4.9 Water Makeup Requirements ................................................................. 23
4.10 Water Treatment ................................................................................... 23
4.11 Protective Finish ................................................................................. 23
Section 5.0 Troubleshooting ................................................................................. 26
5.1 Condition: High Condensing Pressure .................................................... 26
5.2 Condition: Excessive Deposits, Scale, Or Turbidity ................................ 27
5.3 Condition: Excessive Slime Plugging Water/Air Passages ..................... 27
5.4 Condition: Low or High Water Level ........................................................ 27
5.5 Condition: Excessive Noise or Vibration ................................................ 27
IDC EVAPORATIVE CONDENSERS S140-500 IOM
INSTALLATION - OPERATION - MAINTENANCE Page 3
FIGURES
Figure 1-1. ID Plate Information ............................................................................. 4
Figure 1-2. IDC Unit-to-Unit Spacing Requirements ............................................... 6
Figure 1-3. IDC Unit-to-Wall Spacing Requirements ............................................... 7
Figure 2-1a. 12' x 12' Foundation Layout ................................................................ 9
Figure 2-1b. 12' x 18' Foundation Layout .............................................................. 10
Figure 2-1c. 12' x 20' Foundation Layout .............................................................. 11
Figure 2-2. Eliminator Orientation Cross Section ................................................. 12
Figure 2-3a. Assembly and Placement ................................................................ 13
Figure 2-3b. Assembly and Placement ................................................................ 14
Figure 2-4a. Vibration Isolator Feet ...................................................................... 15
Figure 2-4b. Vibration Isolator Rails ...................................................................... 15
Figure 4-1. Recommended Maintenance Intervals ............................................... 18
Figure 4-2. Recommended Spare Parts List ........................................................ 20
Figure 4-3. Sheave Alignment .............................................................................. 21
Figure 4-4. Sump Drain Location .......................................................................... 21
Figure 4-5. Belt Tensioning Schematic ................................................................. 22
Figure 4-6. Nozzle Orientation ............................................................................. 24
Figure 5-1. Standard IDC Series Unit Specifications ............................................ 30
Figure 5-2. Standard IDC Series Unit Dimensions ................................................ 31
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 4 INSTALLATION - OPERATION - MAINTENANCE
Water Chemistry – All evaporative-cooled condensers In general, IDC unit/s should always be located/elevated
operate on principles that encourage biological growth in on concrete pads, piers or structural steel so that exhaust
the recirculating water unless effective treatment is applied. air discharge of the fan orifice is at or above the elevation of
Recirculating water must be periodically analyzed for bio- nearby walls or structures/equipment.
logical culture plate counts. IDC units should not be oper- For other minimum spacing requirements see Figure 1-3.
ated without an effective biological treatment program. (IDC Unit/s to Wall Spacing Requirements) for examples
Note: Emergency “shock” treatment with chemical bio- showing (2) IDC condensers installed next to a single wall
cides may upset the unit’s appropriate pH range (creat- and next to a double wall; and, (1) multiple-cell IDC con-
ing an excessively corrosive environment for the mate- denser installed next to a double wall.
rials of construction) and may expose operators to strong 1.7 Field Piping Considerations for IDC Unit
chemicals that are corrosive or otherwise dangerous if
mishandled (see water treatment page in Section 4.0). Installation
1.6 Placement of IDC Units All IDC units require strongly supported and anchored field
piping. No field piping is to be supported by the IDC itself.
All IDC units must be located to minimize the effect of ex- Wind loading, temperature variation, etc., must be consid-
haust air recirculation. This can significantly derate an evapo- ered to allow for movement between the tower, building,
rative-cooled IDC’s capacity due to the exhaust air’s rela- optional vibration isolator/rails, and field piping. A qualified
tively higher heat and moisture (gained from evaporation of cooling system design engineer should provide final field-
tower water). piping plans and specifications.
In some worst case scenarios, up to 30% heat removal Before finalizing piping installation plans, it is recommended
capacity can be lost if a cooling tower is improperly located that related plans for cooling system/plant expansion be
or oriented. It is the owner’s responsibility to properly locate discussed with your field piping/system designer and Imeco
each unit and/or consult with a qualified engineer before sales representative. Incorporating pipe openings/sizes now
laying out structural/foundation supports and installing the allows for easier installation in the future.
IDC condenser.
Adequate space must be continuously available to allow
adequate airflow to the IDC inlet louvers to prevent dis-
charge air recirculation. Figure 1-2. IDC (Unit to Unit Spac-
ing Requirements) shows IDC condensers on an open
roof with the minimum required distance between the units.
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 6 INSTALLATION - OPERATION - MAINTENANCE
Figure 1-3. IDC Unit-to-Wall Spacing Requirements (Multiple Cell and Multiple Unit Installation)
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 8 INSTALLATION - OPERATION - MAINTENANCE
NOTE: Do not attempt to move the unit laterally with the weight on the isolators. If it is necessary to move the unit, remove the
weight from the isolators by raising the unit before moving. Failure to follow this procedure could result in damage to the isolator.
Do not use ridged connections between the unit and building structure when using vibration isolators. Use flexible connections
that allow for vibration and noise isolation.
11. Inspect spray nozzles and heat transfer section. 3.4 Daily Operation
12. Check the locking collar on each fan shaft bearing and The unit should be inspected, cleaned, and lubricated on a
tighten if necessary. periodic basis. The required services and recommended
13. Check the voltage and current of all three legs of the frequency for each are summarized in the Operation and
fan and pump motors. The current should not exceed Maintenance Schedule in this manual.
the rated service factor. After prolonged shutdowns, the A daily IDC operations log is a good method to assure that
motor insulation should be checked with a Megger no problems develop that may go unchecked. Entries to
Tester prior to restarting the motors. this “rough” log should be made once each shift. Any nota-
14. Start the fan(s) and check for proper rotation as indi- tions should be entered as they occur (or internal policy
cated by sticker on unit. dictates). It is essential that the maintenance manager ex-
15. Open the bleed line valve and adjust bleed to the rec- amine notations (from the previous 24 hours) on a daily
ommended rate. (Section 4.9). basis.
16. On units furnished with electric water level control pack- As safety/weather dictates, a visual check of the condenser
ages, ensure that the stilling chamber is free of ob- should be made once each shift (daily at a minimum) to
check operating conditions. Unusual leaks, noise, vibra-
structions.
tion, part damage/failures, or vandalism should be logged
3.3 24-Hour Run In immediately. Corrective action should be initiated immedi-
After 24 hours of operation under load, the following ser- ately as operations permit, or ensuing service scheduled.
vices should be performed: Associated equipment should also be part of the daily op-
1. Check unit for any unusual noise or vibration. erational checks for the IDC unit. In particular, filtration and
other water treatment equipment performance are impor-
2. Check the operating water level in the cold water sump. tant to satisfactory and problem-free unit operation.
Adjust if necessary.
3. Readjust fan belt tension if required.
4. Inspect spray nozzles and heat transfer section.
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 18 INSTALLATION - OPERATION - MAINTENANCE
Note: Before performing any maintenance or inspection, make certain that all power has been disconnected, locked out,
and tagged properly.
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 20 INSTALLATION - OPERATION - MAINTENANCE
4.3 Lubrication To check both parallel and angular alignment, refer to Fig-
ure 4-3. Sheave Alignment and follow these instructions:
Standard Motors
1. While placing a straight edge across the top of both mo-
Standard IDC fan motors are specifically designed for this
tor and fan sheaves, check for four points of contact.
application to be maintenance free and no greasing is re-
quired. Replacement motors are available from Imeco. Part 2. If a four-point contact is achieved, skip to the belt
numbers can be found on the motor nameplate. tensioning section.
Special Motors 3. To adjust for parallel misalignment, adjust the motor or
fan shaft sheave.
On occasion, special motors (i.e. two-speed, Chem Duty,
etc.) may be specified. These motors must be maintained Fan Blade Inspection
per the motor supplier’s recommendations and may require Inspect fan blades for damage or debris. Ensure aluminum
external lubrication lines and special grease. blades are intact. Ensure that debris which can disturb fan
Note: The grease for special motor bearings and the fan balance is removed from fan.
bearings may not be compatible. Please check the lubri- 4.5 Sump Drainage
cation label on the unit.
The sump and piping should be drained every three months
Fan Bearings and the pump inlet screen should be cleaned. For units with
Check monthly and relubricate bearings (while bearings integral pumps, the water pump inlet is equipped with a
are being rotated). The grease will increase in temperature drain plug. Removing the plug allows the sump and pump
approximately 30°F (16.7°C) during relubrication. Use hand screen to be cleaned and flushed. An FPT coupling is pro-
grease gun only. vided to allow piping to be attached as shown in Figure 4-
Bearings used on the belt drive IDC units are prelubricated 4. Sump Drain Location.
with grease chosen for its chemical and mechanical stabil-
ity in an evaporitive-cooling environment. The type of grease
used is lithium-complex based with synthetic oil. For
relubrication, use any good quality lithium-based grease
conforming to NLGI Grade No. 2 consistency.
The following types of grease meet the above criteria:
•MOBILITH 22
•MOBILUX #2
•SHELL ALVANIA #2
•UNIREX N2
•TEXACO MULTIFAX #2
•TEXACO PREMIUM RB
Grease and grease fittings should be free of dust, rust, metal
particles, abrasives and chemical impurities such as free
acid or free alkali.
4.4 Drivetrain
Belt tension should be checked every month as described
in section 4.6. The sheaves should be tight on the shafts
and should be aligned properly to minimize belt wear. The
belts should be checked for wear along the edges, as any
irregularity will cause vibration.
Sheave Inspection
Check the sheaves for proper alignment, excessive corro-
sion, and wear or damage. Also, check the belt for exces-
sive heat. If the belt is too hot to touch, then the sheaves
may be damaged or need aligning.
If the sheaves have excessive corrosion or are worn or
damaged, they should be replaced. Check for sharp edges
from wear or pitting of the grooves from corrosion. Either Figure 4-3. Sheave Alignment
condition will promote belt wear and increase turnover.
Groove gauges are also available to make it easy to see if
the grooves are worn. If more than 1/32" of wear can be
seen, the sheave should be replaced.
Sheaves for the motor and fans are designed for this spe-
cialized application and are available from Imeco (do not
substitute).
Alignment of sheaves is extremely important for proper belt
installation. The sheaves are aligned at the factory, but should
be rechecked when new belts are installed. Use a straight
edge to check alignment. Misalignment will show up as a
gap between the outside face and the straight edge. Two Figure 4-4. Sump Drain Location
conditions for misalignment exist, angular and parallel.
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 22 INSTALLATION - OPERATION - MAINTENANCE
4.6 Belt Replacement and Tensioning 4. If the above procedure still results in the belt squealing,
but the belt is still taut on the slack side, a more precise
Replacement
method of testing the belt tension must be used. In this
When the decision is made to replace the belt, follow these case, use a belt-tensioning gage available from V-belt
steps: drive manufacturers or from IMECO.
1. Lock out and tag the starter. All belt tension measuring devices should include operat-
2. After the power has been turned off and the motor guard ing instructions. These are spring-loaded devices that use
removed, loosen the motor mount adjustment nuts. a hook to place tension on a stationary belt. Tension read-
3. Move the motor until there is enough slack in the belt so ings are observed at a point where the belt deflects a pre-
it can be removed without prying. determined distance. Tension is usually applied at the belt
span’s mid-point as measured between the tangent of belt
4. Remove the old belts and inspect for unusual wear. Ex- contact for both sheaves. Reference Figure 4-5.
cessive wear may indicate problems with alignment or Belt Tensioning Schematic.
sheave damage.
4.7 New Belt Run-in
5. Use replacement belts from the factory to ensure a proper
belt equivalent. During initial startup of new belts, a belt run-in procedure is
recommended. During start-up, follow these instructions:
6. Inspect other drive components such as bearings and
sheaves for alignment, wear, lubrication, etc. During start-up, look and listen for unusual noise or vibra-
tion.
7. Clean the sheaves of debris before installing the new
belt. 1. After shutting down and locking out the starter, check the
bearings and motor. If they feel hot, the belt tension may
8. Install the new belt, align the drive, and tension the belt
be too tight.
according to the procedures outlined here.
2. Run the drive under full load for 24 hours of continuous
Tensioning
operation. Running the belts under full load allows them
Proper belt tension is very important to ensure maximum to seat themselves into the grooves.
belt life. If too little tension is applied, the belt will slip. Too
3. After running the drive, check the tension of the belts.
much tension can reduce belt and bearing life. It is not rec-
Re-tension to the recommended values. This run-in pro-
ommended that belt dressing be used when belt slippage
cedure will reduce the future need for re-tensioning and
occurs as this will damage the belt and cause premature
failure. will help extend the life of the belts.
1. Decrease the center distance between the sheaves (by 4.8 Coil Assembly
turning the tensioning nut counter clockwise) so the An evaporative-cooled condenser’s operational readiness
sheaves are somewhat loose. is dependent on the condition of the coil. Coils that are dirty,
2. Apply tension to the belt by turning the tensioning nut blocked from air-flow, or physically damaged may affect
clockwise. overall heat transfer capability of the IDC to a significant
3. Operate the drive a few minutes to seat the belt in the degree.
sheave grooves. Observe the operation of the drive dur- Periodically conduct a visual inspection of the coil section
ing start-up. A slight bowing of the slack side of the drive and refrigerant line connections. Remove any airborne de-
indicates proper tension. If the slack side remains taut bris that may have collected on the face of intake louvers or
during the peak load, the drive is to tight. Excessive bow- on the coils themselves. If separate air filtration exists prior
ing or slippage indicates insufficient tension. If the belt to the intake louvers, ensure that adequate “free area” ex-
squeals as the motor comes on, it is not tight enough. ists to meet intake-air CFM requirements.
The drive should be stopped and the belt tightened. Further need for cleaning or repair of an IDC coil should be
Note: Do not over-tighten the drive.
left to the judgement of a certified or factory-trained service operation. The water level is easily adjusted by loosening
person. Contact the local Frick representative if a coil or its the wing nut on the valve and raising or lowering the ball to
connections appears to have been significantly damaged. maintain the proper level. The recommended operating pres-
sure for the water makeup valve is 15 to 20 PSI.
4.9 Water Makeup Requirements
Moisture Eliminators
At its rated capacity (given in tons), an IDC unit will evapo-
rate 3 gallons/min per 100 tons. The moisture eliminators are located on top of the unit and
prevent losses of the spray water due to water being en-
When the water evaporates, any impurities remain. Recir- trained in the air stream as it passes through the unit. The
culating water flow then requires refreshing to prevent even- eliminators should be checked monthly to remove any ob-
tual scale build up. A bleed-off valve is located on the spray structions that might be trapped between the blades and to
pump discharge line to bleed off an equal amount of water ensure proper positioning.
to that evaporated. (3 GPM per 100 tons)
Water Distribution System
For conditions where the original water hardness is very
high or a large number of airborne contaminants may be The spray nozzles are accessible through the access door.
washed into the recirculating spray water, a higher bleed- After tagging and locking out the fan motor, remove a sec-
off rate or chemical treatment may be required. Consult a tion of eliminators to find the spray header underneath (DO
local water treatment company for recommendations. NOT OPERATE UNIT WITHOUT ELIMINATORS). The large
orifice, cleanable type nozzles should be checked monthly
4.10 Water Treatment to see that the spray pattern is complete and even. Figure
If the condition of the water is such that constant bleed-off 4-6. PowerFlow™ Orientation, shows the nozzle in the
will not control scale or corrosion, chemical treatment may spray headers with the proper in-line orientation.
be necessary. If a water treatment program is used it must If the nozzles are not operating properly, check that the
meet the following requirements: strainer in the pan or that the water distribution pipes do not
•The chemicals must be compatible with zinc gal- have accumulated dirt or debris. Also, check the nozzles by
vanic protection. removing them and clean any that may need cleaning.
•The circulating water must be maintained between NOTE: When cleaning the nozzles and distribution sys-
6.5 and 7.5 pH, 1000 PPM (maximum) tem, always ensure that the initial orientation of the
dissolved solids, 125-PPM (maximum) Chlorides, nozzles is maintained.
and 125-PPM (maximum) Sulfites. Heat Transfer Section
•Chemicals should be fed into the recirculated wa- The coil should be examined monthly for signs of scale
ter, but not into the cold water sump, on a continu- buildup, and any obstructions between the tubes should be
ous metered basis to avoid localized high con- removed. If there is evidence of scale buildup on the coil,
centrations which may cause corrosion. These check the bleed valve for adequate bleed-off. If the bleed-
chemicals are normally fed into the pump dis- off valve is functioning properly, contact your local water
charge line. Batch feeding of chemicals does not treatment company for recommendations.
provide adequate control of water quality and is Pan-Water Electric Level Control Packages
not recommended.
Inspect Stilling Chamber for obstructions every three
•Acid water treatment is not recommended. months.
•The use of simple bleed-off or chemical treatment
for control of scale or corrosion does not preclude
4.11 Protective Finish
the need to control biological contamination. Treat- Standard IDC units are protected by a thick layer of hot dip
ment with biocide is a necessary portion of re- galvanizing. it should be part of the maintenance program
quired water treatment! to annually inspect and “touch-up” any significant scratches
For specific recommendations on water treatment, contact that may penetrate the heavy layer of Zinc protection. Deep
a competent water treatment supplier. The following para- scratches should be cleaned of any surface soil, grease,
graphs provide detailed information regarding critical main- etc., and then coated with a “zinc-rich” cold galvanizing
tenance considerations. compound or Zinc solder.
Bleed-Off Valve If surrounding components will not be damaged by
flame-level heat, a blowtorch can be used to slowly heat
Check monthly to ensure that it is not blocked and that the scratch to the melt point of a Zinc solder rod. Apply the
water is flowing as required. The bleed valve should always Zinc until it smoothly flows over the scratch. Discontinue
be open, unless the flow is controlled by a water treatment torch application and quickly use a manual wire brush to
system. spread the molten Zinc evenly over the damaged area.
Strainer Care must be taken not to use this technique near any heat
The pan water strainer is located at the bottom of the pan sensitive bearings, belts, mastic seals, etc. A “hot work”
section at the suction connection of the spray pump. The approval should be obtained from the work area’s desig-
strainer should be cleaned monthly, or as conditions re- nated Safety Officer before conducting the procedure.
quire, to keep it clean. The strainer is easily accessible by Special units constructed from Stainless Steel components
removing the inlet louver at the pump end. Do not operate generally do not require “special care” to maintain normal
the unit without the strainer. corrosion protection. However, Stainless Steel units should
Makeup Valve be protected from direct exposure to caustic or acidic chemi-
A float-actuated valve controls the pan-water level. This valve cals.
should be checked monthly for proper operation and water All units should be cleaned as local conditions require. Also,
level. The pan water level should be even with the centerline periodic inspections for structural or component damage
of the overflow when the unit is not running. This will pre- from wind, lightening, or freezing weather will help maxi-
vent the pump from cavitating when the spray system is in mize the unit’s life.
S140-500 IOM IDC EVAPORATIVE CONDENSERS
Page 24 INSTALLATION - OPERATION - MAINTENANCE