SRL - Series Manual Book
SRL - Series Manual Book
for the
Table of Contents
1. General Description 4
2. Specifications 5
2.1 Model Range 5
2.1.1 60 Hz Models 5
2.1.2 50 Hz Models 6
3. System Design 13
3.1 The Air Circuit 14
3.1.1 Air-To-Air Heat Exchanger 15
3.1.2 Air-To-Refrigerant Heat Exchanger 15
3.1.3 Demister Separator 15
3.1.4 Condensate Chamber 15
3.1.5 Dew Point Temperature Sensor 16
3.1.6 Condensate Level Sensor 16
Page 1 of 56
SRL Service Manual
Revision 00
July 2007
4. Control System 22
4.1 Power Supply 22
4.3 Microprocessor Controls 22
4.2.1 Inputs 23
4.2.2 Outputs 23
4.2.3 Electrical Specifications 24
4.2.4 User Interface 24
4.2.4.1 Lights 25
4.2.4.2 Buttons 26
5. Installation 27
6. Start Up 29
7. Operation & Control 30
7.1 Turning the Dryer On or Off 30
7.2 User Parameter List 31
7.3 Accessing & Modifying User Parameters 32
8. Dryer Operating Modes 33
8.1 Continuous Mode 33
8.2 Cycling Mode 34
9. Condensate Drain Operation 35
9.1 SRL-250 35
9.2 SRL-325 to 6000 35
9.3 Drain Operating Mode (Parameter D3) 37
9.4 Manual Drain Activation 37
10. Alarms & Warnings 38
10.1 Alarm & Warning List 38
10.2 Troubleshooting Alarms & Warnings 39
10.2.1 HP - High Pressure (Alarm) 39
10.2.2 LP - Low Pressure (Alarm) 40
10.2.3 Ld - Low Dewpoint (Alarm) 41
10.2.4 Ht – High (Discharge) Temperature (Alarm) 42
10.2.5 Lt - Low (Evaporator) Temperature (Alarm) 43
10.2.6 CP – Compressor Protection (Alarm) 44
10.2.7 PdE – Parameter Data Error (Alarm) 44
10.2.8 Hd - High Dewpoint (Warning) 45
10.2.9 drE - Drain Error (Warning) 46
10.2.10 dSE - Dewpoint Sensor Error (Warning) 47
10.2.11 rSE – Evaporator Temperature Sensor Error (Warning) 47
10.2.12 Sr - Service Required (Warning) 48
(Continued on following page…)
Page 2 of 56
SRL Service Manual
Revision 00
July 2007
Page 3 of 56
SRL Service Manual
Revision 00
July 2007
1. General Description
The Sullair SRL Refrigerated Air Dryer reduces the dew point(1) of a compressed air stream by
reducing the temperature causing water and oil vapour (along with other evaporated contaminants) to
condense into liquids. These liquids are then separated from the air and discharged from the system.
The dry air is then re-heated before continuing downstream.
Air streams are measured in terms of their flow, temperature and
pressure. These variables fluctuate continuously throughout the
day and can change drastically throughout the year, depending on
the climate, conditions, and application. As they change, so does
the amount of heat in the air (called the “heat load”) and the
amount of moisture the air stream can carry.
Every refrigerated air dryer is designed to handle a maximum
incoming heat load. At any heat load below the maximum there is
the potential for energy savings as the dryer is absorbing less heat
than it is designed for.
The SRL is unique in that it can be operated either as a traditional
direct expansion dryer or a cycling dryer depending on the needs
and wishes of the end user.*
In direct expansion (a.k.a. “continuous”) mode the refrigerant compressor runs continuously, and the
dryer handles reduced heat loads by redirecting refrigerant away from the heat exchanger using a
bypass valve to maintain a constant outlet dewpoint. This is the simplest mode of operation, however
does not save any energy at part load.
In cycling mode the refrigerant compressor is cycled on and off depending on the temperature within
the heat exchanger. When there is less heat load, the heat exchanger absorbs less heat, and the
refrigerant system is cycled on and off only as necessary to keep the heat exchanger cold.*
(1) Dew point – a measurement of the amount of moisture in a gas, indicated as the temperature at which
the air would be saturated (i.e. the relative humidity would be 100%) and liquid condensate would begin
o o
to form. It is commonly shown as F or C. It is important when discussing dew point to specify if you are
referring to the “pressure dew point” (the dew point at the pressure of the system) or “atmospheric dew
point” (the equivalent dew point at atmospheric pressure) as the two are significantly different. For the
purposes of this manual, “dew point” should be considered synonymous with “pressure dew point".
Page 4 of 56
SRL Service Manual
Revision 00
July 2007
2. Specifications
2.1 Model Range
2.1.1 60 Hz Models
Page 5 of 56
SRL Service Manual
Revision 00
July 2007
2.1.2 50 Hz Models
Rated Pressure Absorbed Port
Sullair Voltage Condenser
Flow [1] Drop Power Size
Model Part # Volt Ph Hz AC/WC (m3/min) (mbar) (kW) (in)
SRL-120 02250169-405 400 3 50 AC 12 130 1.41 2"
SRL-140 02250169-406 400 3 50 AC 14 180 1.37 2"
SRL-180 02250169-407 400 3 50 AC 18 230 1.76 2"
02250169-408 AC 1.59
SRL-220 400 3 50 22 90 2 1/2"
02250169-421 WC 1.61
02250169-410 AC 2.29
SRL-260 400 3 50 26 130 2 1/2"
02250169-422 WC 2.28
02250169-411 AC 2.89
SRL-300 400 3 50 30 170 2 1/2"
02250169-423 WC 2.77
02250169-412 AC 3.60
SRL-350 400 3 50 35 240 2 1/2"
02250169-424 WC 3.49
02250169-413 AC 3.52
SRL-460 400 3 50 46 140 DN100
02250169-425 WC 3.39
02250169-414 AC 4.28
SRL-520 400 3 50 52 180 DN100
02250169-426 WC 3.87
02250169-415 AC 5.24
SRL-630 400 3 50 63 260 DN100
02250169-427 WC 5.05
02250169-416 AC 6.91
SRL-750 400 3 50 75 160 DN150
02250169-428 WC 6.20
02250169-417 AC 9.86
SRL-900 400 3 50 90 230 DN150
02250169-429 WC 8.87
02250169-418 AC 10.94
SRL-1210 400 3 50 120 190 DN150
02250169-430 WC 10.12
02250169-419 AC 15.25
SRL-1500 400 3 50 150 200 DN200
02250169-431 WC 14.09
02250169-420 AC 18.64
SRL-1800 400 3 50 180 260 DN200
02250169-432 WC 17.33
(1) Maximum rated flow at ISO conditions of 35 deg F & 7 bar g inlet, 25 deg F ambient.
Page 6 of 56
SRL Service Manual
Revision 00
July 2007
SRL-1000
SRL-1200
SRL-250
SRL-325
SRL-400
SRL-500
SRL-700
SRL-800
Type -- R407C
Refrigerant
Charge lb (kg) 3.26 (1.48) 5.07 (2.3) 5.29 (2.4) 5.95 (2.7) 9.92 (4.5) 13.23 (6) 14.33 (6.5)
Quantity Qty 1
Expansion Capillaries Internal Diameter mm 2.5 3.18 4
Length mm 2500 1500 900 1500 2800 2000
Min psig (barg) 62.4 (4.3)
Hot Gas Valve Setting
Max psig (barg) 66.7 (4.6)
Min °F (°C) 33.8 (1)
Suction Temperature
Max °F (°C) 48.2 (9)
Min °F (°C) 131 (55) 104 (40) 99 (37) 99 (37) 131 (55) 104 (40) 118 (48)
Discharge Temperature
Max °F (°C) 167 (75) 149 (65) 144 (62) 149 (65) 167 (75) 140 (60) 154 (68)
Min °F (°C) 35.6 (2)
Dew point temperature
Max °F (°C) 41 (5)
On psig (barg) 276 (19)
Fan Pressure Switch
Off psig (barg) 203 (14)
Number of Heat Exchangers Qty 1
High Pressure Switch Setting psig (barg) 406 (28)
Standard Supply Voltages Available -- (Note 1) 230 or 460V / 3ph / 60 Hz 460V / 3ph / 60 Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
Note 1 - Available in 230/1/60, 230/3/60 or 460/3/60.
SRL-2400
SRL-3000
SRL-3800
SRL-5000
SRL-6000
SRL-1400
SRL-1600
SRL-2000
Type -- R407C
Refrigerant
Charge lb (kg) 19.84 (9) 22.05 (10) 27.12 (12.3) 25.35 (11.5) 40.79 (18.5) 42.99 (19.5) 61.73 (28) 68.34 (31)
Quantity Qty 2 3 4 5 6
Expansion Capillaries Internal Diameter mm 3.18 4
Length mm 2800 1000 2100 4000 2300 2500
Min psig (barg) 62.4 (4.3)
Hot Gas Valve Setting
Max psig (barg) 66.7 (4.6)
Min °F (°C) 33.8 (1)
Suction Temperature
Max °F (°C) 48.2 (9)
Min °F (°C) 131 (55) 113 (45) 131 (55)
Discharge Temperature
Max °F (°C) 167 (75) 158 (70) 167 (75) 158 (70) 167 (75)
Min °F (°C) 35.6 (2)
Dew point temperature
Max °F (°C) 41 (5)
On psig (barg) 276 (19)
Fan Pressure Switch
Off psig (barg) 203 (14)
Number of Heat Exchangers Qty 2 3 4 5 6
High Pressure Switch Setting psig (barg) 406 (28)
Standard Supply Voltages Available -- 460V / 3ph / 60 Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
Page 7 of 56
SRL Service Manual
Revision 00
July 2007
SRL-1000
SRL-1200
SRL-250
SRL-325
SRL-400
SRL-500
SRL-700
SRL-800
Type -- R407C
Refrigerant
Charge lb (kg) 9.26 (4.2) 7.72 (3.5) 14.33 (6.5)
Quantity Qty 1
Expansion Capillaries Internal Diameter mm 3.18 4
Length mm 1200 2800 2000
Min psig (barg) 62.4 (4.3)
Hot Gas Valve Setting
Max psig (barg) 66.7 (4.6)
Min °F (°C) 33.8 (1)
Suction Temperature
Max °F (°C) NA 48.2 (9)
Min °F (°C) 140 (60)
Discharge Temperature
Max °F (°C) 185 (85)
Min °F (°C) 35.6 (2)
Dew point temperature
Max °F (°C) 41 (5)
Number of Heat Exchangers Qty 1
High Pressure Switch Setting psig (barg) 406 (28)
Supply Voltage -- 230 or 460V/3/60 460V / 3ph / 60 Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
SRL-2400
SRL-3000
SRL-3800
SRL-5000
SRL-6000
SRL-1400
SRL-1600
Page 8 of 56
SRL Service Manual
Revision 00
July 2007
SRL-120
SRL-140
SRL-180
SRL-220
SRL-260
SRL-300
SRL-350
SRL-460
Type -- R407C
Refrigerant
Charge kg 1.7 2.5 5.5 4.5 4.6 7.4 8.3
Quantity Qty 1 2
Expansion Capillaries Internal Diameter mm 2.5 3.18 4 3.18
Length mm 1500 4000 1500 1000 2800
Min barg 4.3
Hot Gas Valve Setting
Max barg 4.6
Min °C 1
Suction Temperature
Max °C 15
Min °C 45 60 45 60
Discharge Temperature
Max °C 70 85 70 85
Min °C 2
Dew point temperature
Max °C 5
On barg 19
Fan Pressure Switch
Off barg 14
Number of Heat Exchangers Qty 1 2
High Pressure Switch Setting barg 28
Standard Supply Voltages Available -- 400V / 3ph / 50Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
SRL1200
SRL1500
SRL1800
SRL520
SRL630
SRL750
SRL900
Type -- R407C
Refrigerant
Charge kg 8.5 10.3 12 12.5 19.5 25.5 31
Quantity Qty 2 3 4 5 6
Expansion Capillaries Internal Diameter mm 3.18 3.5 4
Length mm 1800 1000 2100 1300 1500 2300 2500
Min barg 4.3
Hot Gas Valve Setting
Max barg 4.6
Min °C 1
Suction Temperature
Max °C 15
Min °C 50 60 50 60 50 45
Discharge Temperature
Max °C 75 85 75 85 75 70
Min °C 2
Dew point temperature
Max °C 5
On barg 19
Fan Pressure Switch
Off barg 14
Number of Heat Exchangers Qty 2 3 4 5 6
High Pressure Switch Setting barg 28
Standard Supply Voltages Available -- 400V / 3ph / 50Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
Page 9 of 56
SRL Service Manual
Revision 00
July 2007
SRL-120
SRL-140
SRL-180
SRL-220
SRL-260
SRL-300
SRL-350
SRL-460
Type -- R407C
Refrigerant
Charge kg 3.4 4.2 3.3 7
Quantity Qty 1 2
Expansion Capillaries Internal Diameter mm 3.18 4 3.18
Length mm 4000 2000 1000 2800
Min barg 4.6
Hot Gas Valve Setting
Max barg 4.8
Min °C 1
Suction Temperature
Max °C NA 15
Min °C 60 45
Discharge Temperature
Max °C 85 70
Min °C 2
Dew point temperature
Max °C 5
Number of Heat Exchangers Qty 1 2
High Pressure Switch Setting barg 28
Standard Supply Voltages Available -- 400V / 3ph / 50Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
SRL1200
SRL1500
SRL1800
SRL520
SRL630
SRL750
SRL900
Type -- R407C
Refrigerant
Charge kg 6 6.3 10.4 8.3 11.5 17 20.5
Quantity Qty 2 3 4 5 6
Expansion Capillaries Internal Diameter mm 3.18 3.5 4
Length mm 1800 1000 2100 1300 1500 2000 2500
Min barg 4.6
Hot Gas Valve Setting
Max barg 4.8
Min °C 1
Suction Temperature
Max °C 15
Min °C 45 60 55 60 55
Discharge Temperature
Max °C 70 85 80 85 80
Min °C 2
Dew point temperature
Max °C 5
Number of Heat Exchangers Qty 2 3 4 5 6
High Pressure Switch Setting barg 28
Standard Supply Voltages Available -- 400V / 3ph / 50Hz
Control Software Release Code dt.3
All parameters refer to operating conditions at zero air flow.
Page 10 of 56
SRL Service Manual
Revision 00
July 2007
Page 11 of 56
SRL Service Manual
Revision 00
July 2007
2.4.2 50 Hz Models
Page 12 of 56
SRL Service Manual
Revision 00
July 2007
3. System Design
The SRL dryer consists of two circuits: the Air Circuit and the Refrigeration Circuit:
F
G
The A The
Refrigerant Air
Circuit E B Circuit
C
D
H I
The refrigerant The liquids condense
cools the air. & are drained away.
• The Air Circuit: Consisting primarily of:
A. Air-to-Air heat Exchanger,
B. Air-to-Refrigerant Heat Exchanger,
C. Slowflow Demister Separator, and
D. Condensate Chamber
The air enters the dryer and passes through the Air-to-Air Heat Exchanger (A) where it is
cooled by the outgoing air. The air then passes through the Air-to-Refrigerant Heat Exchanger
(B) where it is further cooled by the refrigerant. The air then passes through the Slowflow
Demister Separator (C) where the condensate is separated from the air. The condensate
collects in the Condensate Chamber (D), before being discharged from the system by a
condensate drain (not shown). The air passes back through the Air-to-Air Heat Exchanger
where it is reheated by the incoming air before leaving the dryer.
• The Refrigeration Circuit: Consisting primarily of:
B. Air-to-Refrigerant Heat Exchanger,
E. Refrigerant Compressor,
F. Hot Gas Bypass
G. Condenser,
H. Refrigerant Filter, and
I. Expansion Device.
The refrigerant passes through the Air-to-Refrigerant Heat Exchanger (B) where it absorbs
heat from the air and evaporates into a gas. It then passes through the Refrigerant
Compressor (E) where it is compressed, and then through the Condenser (G) where it is
cooled by either the ambient air (air cooled models) or with cooling water (water cooled
models). This causes it to condense back into a liquid. It then passes through the Refrigerant
Filter (H) where any impurities are removed, and then the Expansion Device (I) where it is
expanded causing it to cool before returning to the Air-to-Refrigerant Heat Exchanger.
In some conditions, a portion of the refrigerant is directed clockwise through the Hot Gas
Bypass (F) and recirculated back to the compressor to avoid excessive cooling.
Page 13 of 56
SRL Service Manual
Revision 00
July 2007
Page 14 of 56
SRL Service Manual
Revision 00
July 2007
The Air-to-Air Heat Exchanger is an aluminium fin, cross flow exchanger. The Air-to-Air Heat
Exchanger is also often called a “Pre-cooler / Re-heater” because the hot air entering the dryer is pre-
cooled by the cold air exiting the dryer; while at the same time the cold air exiting the dryer is re-
heated by the hot air entering. Then end result is that the pre-cooling offers a significantly reduced
heat load on the refrigerant circuit (which offers notable energy savings), and the re-heating offers
elimination of condensation accumulation on the downstream air piping, as well as increasing the
temperature of the air, keeping it well away from the dew point. The air leaving the dryer is
approximately 10 degrees cooler than the air coming in.
All models are equipped with a Slowflow demister type moisture separator to remove the condensed
liquids from the compressed air. The liquid droplets impact the stainless steel fibers of the demister,
and coalesce into larger drops where they are pulled into the Condensate Chamber by gravity.
The demister combines a high efficiency with a low pressure drop. It is significantly larger than
standard demisters (typically at least four times as large) and as such the air velocity across it is much
slower. In addition, the Slowflow design provides increased contact time allowing high separation
efficiency. The Slowflow demister separator guarantees perfect operation at all air flows, unlike
centrifugal separators which quickly lose efficiency at lower air flows, and standard demisters which
lose efficiency at higher air flows.
Once separated the condensate is removed from the air circuit by the condensate drain. The dry, cold
air then passes through the “re-heating” side of the air-to-air exchanger.
Condensate is collected in the condensate chamber before being discharged from the system through
the Condensate Drain. On the SRL-325 to 1200 (60Hz) or SRL-120 to 350 (50Hz) the condensate
chamber is integrated into the air side heat exchanger assembly. On the SRL-1400 to 6000 (60Hz) or
SRL-460 to 1800 (50Hz) the condensate chamber is external to the heat exchanger assembly.
Page 15 of 56
SRL Service Manual
Revision 00
July 2007
All models except the SRL-250* have a Level Sensor in the Condensate Chamber. This sensor sends
a signal to the microprocessor when the level of condensate reaches it, which then opens the
Condensate Drain Valve. Details of condensate drain operation are covered in Section 9.
* There is not enough volume in the condensate chamber of the SRL-250 to allow efficient zero air loss drain
operation, so no level sensor is required.
Page 16 of 56
SRL Service Manual
Revision 00
July 2007
3.2.2 Compressor
All models (with the exception of the SRL-250*) are
equipped with compliant scroll refrigerant compressor
with a three phase motor. These compressors are
maintenance-free and installed on vibration damping
mountings.
The compressor reduces the pressure in the evaporator
ensuring the refrigerant evaporates at the correct
pressure (and therefore temperature). It compresses
the evaporated refrigerant and sends it to the
condenser.
Piston Compressor: Scroll Compressor:
The scroll compressor has two spirals (scrolls). One SRL-250 SRL-325 to 6000
stays stationary, while the other orbits within it. As this
motion occurs, the pockets between the two spirals are pushed to the centre while simultaneously
being reduced in volume. When the pocket reaches the center of the scroll form, the gas, now at a
high pressure, is discharged.
The SRL-325 to 1400 (60Hz) and SRL-120 to 520 (50Hz) are equipped with thermal overload
protection via a thermo amperometric internal switch. The SRL-1600 to 6000 (60Hz) and SRL-630 to
1800 (50Hz) are equipped with external electronic thermal protection.
Compliant scroll compressors are not damaged by liquid returns, and as such, they do not require pre-
heating upon start-up. They also offer significant advantages in terms of energy savings, reliability,
high efficiency and quiet operation.
Page 17 of 56
SRL Service Manual
Revision 00
July 2007
3.2.3 Condenser
Page 18 of 56
SRL Service Manual
Revision 00
July 2007
3.2.6 Refrigerant
The refrigerant is the medium used to transfer energy. By changing pressure and temperature and
changing from a liquid to a gaseous state it effectively transforms the input energy (i.e. compressor
electrical energy) to output energy (i.e. cooling of the air). All models feature R407C refrigerant.
R407C is classified as an environmentally friendly refrigerant, and offers an ODP (Ozone Depletion
Potential) of zero. As a consequence R407C has no planned phase-out date and can be used without
restrictions. It also offers a very low GWP (Global Warming Potential) level. R407C furthermore
features a high COP (Coefficient of Performance), thereby ensuring that the dryer’s power
consumption is kept to a minimum.
Page 19 of 56
SRL Service Manual
Revision 00
July 2007
Page 20 of 56
SRL Service Manual
Revision 00
July 2007
Page 21 of 56
SRL Service Manual
Revision 00
July 2007
4. Control System
The SRL-250 and larger dryers are fitted with microprocessor controls.
Page 22 of 56
SRL Service Manual
Revision 00
July 2007
4.2.1 Inputs
Consists of both analog inputs (J2) and digital inputs (J1 & J3).
4.2.2 Outputs
Page 23 of 56
SRL Service Manual
Revision 00
July 2007
Page 24 of 56
SRL Service Manual
Revision 00
July 2007
4.2.4.1 Lights
Power LED
o Yellow: indicates the dryer is off, but connected to a power supply.
o Green: indicates the dryer is operating.
Warning LED
o Red: indicates the dryer has a warning or alarm.
Drain LED
o Green: indicates the drain valve is open.
Power LED
Page 25 of 56
SRL Service Manual
Revision 00
July 2007
4.2.4.2 Buttons
Alarm Reset / Up
o Standard Function: Resets Alarm or Warning.
o In Alarm Menu: Scrolls up to previous alarm or item.
o In Parameter Menu: Scrolls up to previous parameter or increases a
value (when modifying a parameter).
Drain / Exit
o Standard Function: Manually operates the drain valve according to
timed mode settings. (See Section 9)
o In Alarm Menu: Exits the current alarm, item or menu.
o In Parameter Menu: Exits the current parameter or menu.
On/Off / Enter
o Standard Function: Turns the dryer on and off.
o In Alarm Menu: Enters the current alarm or item.
o In Parameter Menu: Enters the current parameter or saves changes to
its value (when modifying a parameter).
Page 26 of 56
SRL Service Manual
Revision 00
July 2007
5. Installation
The SRL dryers have Nema 1 protection against the ingress of moisture and particles. They must be
installed indoors or provided adequate protection against wind, rain and direct sunlight. Faults
occurring from improper installation are not covered by warranty.
• Orient the unit so that there is adequate access to the control panel and drain compartment.
Verify that a minimum clearance of 5 ft (1.5 m) is left around the machine for maintenance access
and ventilation to the unit. For models with condenser fans in the top panel, leave at least 7 ft (2
m) above the dryer for adequate cooling air discharge.
• Refer to the Operating Limits in Section 2 for details on maximum and minimum ambient
temperatures.
• Verify that the power supply provided matches the the power supply indicated on the rating label
for the dryer.
• Connect the supply power cables and ground in accordance with all applicable regulations.
• Protect the dryer with an overcurrent and ground circuit breaker (0.3 Amps).
• Connect the inlet and outlet compressed air piping connections to the dryer using the correct ports
as indicated on the dryer.
SRL-250 through 1200 have BSP threaded inlet and outlet ports. BSP to NPT adapters
are provided (loose) and must be installed. Attempting to thread in NPT pipe into the
BSP ports will damage to the threads.
• Install a bypass line around the dryer, and inlet and outlet isolation valves, so that maintenance or
calibration operations can be carried out without interrupting the downstream compressed air
supply.
Do not flow air through the dryer when it is OFF. Open they bypass line and close the
inlet and outlet isolation valves at all times when the dryer is in the OFF position.
• Install a Sullair 1 micron coalescing pre-filter (SCF or PF) immediately upstream of the dryer to
prevent rust, pipe scale, bulk water, oil or other pollutants from entering the system and clogging
the heat exchangers, separator, or condensate drain. This can cause pressure drop, condensate
carry over, loss of efficiency, and or damage to the dryer.
Page 27 of 56
SRL Service Manual
Revision 00
July 2007
• If necessary, protect the dryer from vibration using vibration dampeners and/or flexible hoses on
the inlet and outlet.
• Also if necessary, protect the dryer from pulsation in the air stream by installing a upstream wet air
receiver.
• Pressure safety relief valves must be installed in the compressed air system in accordance with
local regulations. Verify that these valves will protect the dryer from any pressure above 203 psig
at all times.
• Ensure that the inlet compressed air and ambient air in and around the dryer do not contain solid
or gaseous contaminants. All compressed and condensed gases can generate acids or chemical
products which may be aggressive against the aluminium heat exchanger or the other components
inside the dryer. Take particular care with sulphur, ammonia, chlorine, and installations in marine
environments.
• Protect the dryer from instantaneous or continuous flows in excess of the dryers’ maximum rated
capacity. This may require installation of a down stream air receiver.
• Ensure the drain outlet is free from restriction and back pressure. Do not connect drain outlets into
a common header if there is any chance that any condition (i.e. multiple drains discharging at the
same time could cause a restriction or back flow.)
Page 28 of 56
SRL Service Manual
Revision 00
July 2007
6. Start-up
Before starting up the dryer, make sure that the air inlet and outlet isolation valves are closed, and the
bypass valve is open. This will ensure there is no air flow through the dryer.
For water cooled units do not open the isolation valves to allow cooling water to flow of
water through the condenser until immediately before start up, otherwise, the HP (high
pressure) alarm may occur. In this case, reset the alarm on the control panel, wait few
minutes and restart the dryer. You may have to restart the unit repeatedly to get this
alarm to disappear.
On three-phase units if the phases are inverted, the compressor and the fan will rotate
in the wrong direction. In this case:
a) The scroll compressor is not displacing any refrigerant. It will be noisy
and the dryer will vibrate. Since the dryer is not producing any cooling
effect, after 15 minutes, the “Hd” (High dew point) warning will come on.
b) The fan is moving air in the wrong direction. This can be verified by
comparing the air flow to the air flow indicated in the User Guide and on
the name plate inside the electrical panel.
Shut down the dryer, isolate the power supply, and swap the two phases.
Let the dryer operate without air flow until the dew point drops to operating levels and the dryer
begins to cycle.
Slowly open the inlet isolation valve to pressurise the dryer, then open slowly the outlet isolation valve.
Close the bypass valve.
The dryer is now on line and operating.
Page 29 of 56
SRL Service Manual
Revision 00
July 2007
Page 30 of 56
SRL Service Manual
Revision 00
July 2007
(1) Parameters B3, B7 & B9 are passcode protected and cannot be changed or reset without the
proper code. Refer to Section 10.3 & 10.4 for further information.
(2) Parameter B8 only displays the temperature being read by the sensor. It cannot be modified.
(3) Parameter C7 changes the dryer operating mode. CYC = Cycling Operation Mode.
Con = Continuous (Non-Cycling) Mode. Refer to Section 8 for further information.
(4) Parameter D3 changes the drain operating mode. CAP = Capacitive (Zero Air Loss) Mode,
tiM = Timed Mode, Con =Continuous (Deactivated) Mode. Refer to Section 9 for further
information.
(5) Cycling Operation Mode and Capacitive Drain Mode are not applicable to the SRL-250.
Page 31 of 56
SRL Service Manual
Revision 00
July 2007
• When you get to the parameter you want, press Enter to see it’s value.
or
(1)
• Press the Up or Down buttons to modify it’s value . or
(1) Parameters B3, B7 & B9 are passcode protected and cannot be changed or reset without the proper
code. Contact Sullair for further information.
(2) If you press Exit without first pressing Enter to save your changes, you will exit without saving and the
parameter will revert to it’s previous value.
Note that once inside the parameters menu, the meaning of the buttons is different from the standard
operation. (See section 3.2) It is not possible to:
• Turn the dryer On or Off
• Reset a warning or alarm
• Display the alarm report
• Activate the drain valve
Once in the parameters menu, if the user does not press any button for 5 minutes, the controller will
exit the menu and return to standard operating mode.
To exit the parameter menu and return to the standard operating mode, press Exit.
Page 32 of 56
SRL Service Manual
Revision 00
July 2007
As the temperature, pressure and flow of the incoming air flow varies, so does the amount of heat the
refrigerant absorbs. If the flow of refrigerant did not constantly adjust to match this incoming heat
load, the temperature of the evaporator (and therefore the outlet dewpoint of the air) would increase
as the heat load increased, and decrease as the heat load decreased. If the temperature in the
evaporator dropped below freezing, the forming condensate would freeze, and the evaporator would
quickly block with ice.
Therefore it is vital that the refrigerant circuit be constantly controlled to maintain a steady temperature
(and therefore pressure) in the evaporator. Ultimately the temperature in the evaporator is maintained
at about 35 to 39 degrees Fahrenheit – just above freezing. In this way, the dryer provides the lowest
possible dewpoint, while keeping the condensate in liquid form so it can be removed.
Note that in this arrangement the solenoid upstream of the Hot Gas Bypass valve is constantly open.
Page 33 of 56
SRL Service Manual
Revision 00
July 2007
As the temperature in the evaporator decreases, these three values are fed into an algorithm which
calculates whether or not to turn the refrigerant compressor off. This algorithm is designed to maintain
a minimum dewpoint, while ensuring maximum energy savings, and protecting the compressor from
excessive starts and stops.
When these three goals have been met, the compressor is turned off and the “Energy Saving” light
turns on indicating the compressor is stopped and the dryer is saving energy.
It should be noted that there is no specific temperature at which the compressor will turn off. The
microprocessor must also consider other factors such as the amount of time since the compressor
was last turned off, and therefore may delay turning the compressor off regardless of the temperature
of the evaporator. In these cases, the Hot Gas Bypass Valve will ensure the temperature in the
evaporator is maintained to avoid freezing.
While the compressor is off, the temperature in the evaporator will begin to rise. This is due to heat in
the air flow (or, if there is no airflow, due to the ambient). When the evaporator reaches a preset
temperature value, the compressor is turned back on.
The purpose of the “cycling” mode is solely to save energy. Dewpoint will fluctuate moreso in Cycling
mode than in Continuous mode so it is suggested that if energy costs are not a concern, the dryer is
operated in continuous mode for optimum performance and reliability.
Page 34 of 56
SRL Service Manual
Revision 00
July 2007
Condensate collects in the Condensate Chamber (3.1.4). The Level Sensor (3.1.6) continuously
monitors the level of condensate, closing the contacts and sending a signal to the microprocessor
(digital input ID4) when it senses liquid.
The microprocessor opens the solenoid drain valve (coil YV3) when it gets a signal from the Level
Sensor continuously for 30 seconds (Parameter D4 – Drain Open Delay).
The condensate is then discharged from the Condensate Chamber through the solenoid drain valve
under pressure.
The microprocessor closes the solenoid drain valve when it stops getting a signal from the level
Sensor continuously for 5 seconds (Parameter D5 – Drain Close Delay).
Page 35 of 56
SRL Service Manual
Revision 00
July 2007
Every 100 cycles (Parameter D7 – Extended Cycle Interval), the microprocessor goes through an
extended cycle, keeping the drain open for 10 seconds (Parameter D6 –Drain Close Delay [Extended
Cycle]) after the level Sensor stops sending a signal. This allows the drain to periodically clean itself.
If the drain has been open for 30 seconds and the Level Sensor still senses liquid (Parameter D8 –
Drain Alarm Setting), the dryer goes into alarm. “drE” flashes on the display, and the microprocessor
automatically changes to timed operation in accordance with the interval and duration settings in User
Parameters D1 & D2. When the Level Sensor stops sensing liquid, the microprocessor will
automatically change back to zero air loss operation.
If desired the user can force the drain on the SRL-325 through 6000 to always operate in timed mode
or they can deactivate drain control completely*. This is achieved by adjusting Parameter D3 – Drain
Operating Mode. See Section 9.4 for details on this parameter.
* In this case, the solenoid valve must be removed and a separate self controlling condensate drain installed.
Page 36 of 56
SRL Service Manual
Revision 00
July 2007
Capacitive (Zero Air Loss): The drain solenoid valve (output YV3) is controlled by the
level sensor (input ID4) found inside the integrated or external condensate chamber.
This option is on the SRL-325 to 6000 (60hz) or SRL-120 to 1800 (50Hz) ONLY)
Timed: The drain solenoid valve (output YV3) is controlled by the duration and interval
settings in Parameters D1 & D2.
Continuous (Deactivated): For use when customer prefers to install a separate self
controlled external drain. (Signal to open N03 is always activated - even if the dryer is
off.)
Note: Since the SRL-250 has no level sensor, if the “Capacitive” mode was set on this
model, the microprocessor would get no signal to open, and would keep the valve
closed permanently.
Note that when the drain is set to Continuous (Deactivated) Mode, the drain solenoid
valve must be removed and an external self controlled condensate drain must be
installed. The external drain can be powered through the board output NO3 (24V) or
directly from the electrical cabinet.
When set in either Capacitive or Timed mode, the drain valve can be manually activated by
pressing the Drain Button. When the button is pressed the solenoid valve coil is energized
for the duration time set in parameter D1. The manual drain activation is always possible no
matter what the dryer status or signal coming from the level sensor.
If you press the Drain Button while the drain is activated by the controller, it will cause the drain valve
to close.
For further information on the Drain LED and Drain Button, please refer to Sections 4.2.4.1 & 4.2.4.2.
Page 37 of 56
SRL Service Manual
Revision 00
July 2007
The control board is provided with an alarm relay with NO/NC contacts. The relay is normally
energized once the controller is powered in order to provide an alarm indication when a fault happens
or when power is disconnected.
When the controller gets a signal to indicate an alarm or warning, it cuts power to the alarm relays,
turns on the “Warning” light, and displaying the alarm code on the digital display. Each alarm/warning
is identified with a number which is used to pass the information through the serial port.
Page 38 of 56
SRL Service Manual
Revision 00
July 2007
What it means: High pressure switch registers a refrigerant pressure above 406 psig (28 barg).
What it does: Cuts power to compressor contactor & alarm contacts. Turns the dryer OFF. Turns
on Warning Light & blinks “HP” on the digital display.
Possible Causes & Remedies:
1) High ambient temperature in the compressor room due to:
a. Warm weather,
b. Poor compressor room ventilation,
c. Poorly located dryer (restricted air flow through the condenser),
d. Compressor aftercooler is exhausting warm air near the dryer.
Remedy - increase ventilation to the compressor room, duct the compressor after-cooler
out of the room, or move the dryer to a cooler location.
2) The condenser is dirty causing a reduction of air flow and/or cooling if the refrigerant.
Remedy - Clean the condenser coils and condenser pre-filter (if applicable) by blowing
compressed air backwards through them. Be careful not to bend the fins.
3) The condenser fan is not coming on because of a failure of the fan motor, contacts, or
pressure switch. (Can be confirmed by checking the condensing pressure with a gauge.)
Remedy - Replace the detective component.
4) Excessive thermal load on the dryer due to excessive air flow rate and/or air inlet
temperature. (Can be confirmed using the instructions in Section 13.)
Remedy – Improve the efficiency of the aftercooler on the compressor, install an additional
or larger air or water cooled aftercooler upstream the dryer, or install a larger dryer. If the
overload is limited to a very short period of time, this alarm can be avoided by partially
opening the air by pass line to reduce the load to the dryer. Please note that this will
significantly increase the downstream dew point.
5) Defective high pressure switch. (Can be confirmed by checking the condensing pressure
with a gauge.)
Remedy - Replace the detective component.
6) Incorrect start-up procedure. Compressed air was allowed to flow through the dryer
before it was started, causing an immediate HP alarm on start up.
Remedy – Isolate the dryer from the air flow by closing the inlet and outlet isolation valves
and opening the bypass line. Start the dryer with no air flow. You may need to start the
dryer repeatedly before the alarm clears.
To Reset: Press ALARM RESET. Power restored to alarm relay, Warning Light goes off.
Dryer remains OFF. Display clears.
Press ON/OFF to restart dryer.
Notes: Alarm can only be cleared if the pressure is below 304 psig (21 barg).
Page 39 of 56
SRL Service Manual
Revision 00
July 2007
What it means: Low pressure switch registers a refrigerant pressure below 22 psig (1.5 barg) for 2
minutes or more.
What it does: Cuts power to compressor compressor contactor & alarm contacts. Turns dryer
OFF. Turns on Warning Light & blinks “LP” on the digital display.
Possible Causes & Remedies:
1) A low refrigerant charge is causing the compressor to pull the suction pressure
below 22 psig.
Remedy – Check or leaks at welds, threaded connections, schrader valve caps,
and joints of the condenser and evaporator. Repair the leak, pull the system to deep
vacuum and charge the dryer with the correct amount of refrigerant as specified in
the Section 2.3.
2) A defective low pressure switch is giving a wrong signal to the controller. Can be
confirmed by checking the evaporator pressure with a gauge.
Remedy - Replace the detective component.
To Reset: Press ALARM RESET. Power restored to alarm relay, Warning Light goes off.
Dryer remains OFF. Display clears.
Press ON/OFF to restart dryer.
Notes: Alarm can only be cleared if the pressure is above 36 psig (2.5 barg).
Page 40 of 56
SRL Service Manual
Revision 00
July 2007
What it means: Temperature sensor B1 (dew point temperature) registers a temperature below
28.4oF (-2oC) for 3 minutes or more.
What it does: Cuts power to compressor contactor & alarm contacts. Turns dryer OFF. Turns on
Warning Light & blinks “Ld” on the digital display.
Possible Causes & Remedies:
1) Hot Gas Bypass Valve is miscalibrated, causing it to allow pressure in the
evaporator to go too low, causing the temperature to go below 28.4oF (-2oC).
Remedy – Adjust the Hot Gas Bypass Valve as outlined in Section 12.
2) Low ambient temperature is causing excessive cooling of the refrigerant in the
condenser. The dryer may be installed outdoors, in an unheated room, or near a
vent. This cause can be confirmed by checking the condensation pressure with a
gauge. It will stay below 261 psig and the fan never comes on.
Remedy – Increase the ambient temperature in the room or duct the air for the
condenser from a warmer source. Alternately, you can partially cover the
condenser coils in order to reduce the air flow across them, thereby reducing the
cooling effect.
3) A defective fan pressure switch is causing the condenser fan to stay on all the
time causing excessive cooling of the refrigerant.
Remedy – Replace the defective component.
4) The dewpoint temperature sensor (B1) is miscalibrated, causing a low reading.
This can be confirmed by using a temperature gun to check the temperature at the
location of the dew point probe, and comparing it to what the probe is reading.
Remedy – Replace the defective component.
To Reset: Find the cause of the alarm and fix the problem.
Press ALARM RESET to clear alarm. Power restored to alarm relay, Warning Light
goes off. Dryer remains OFF. Display clears.
Press ON/OFF to restart dryer.
Notes: Alarm can only be cleared if the dew point temperature is above 28.4oF (-2oC).
The low dew point alarm is possible whether the dryer is ON, or in Remote Off
Mode – as long as there is power to the controller.
Page 41 of 56
SRL Service Manual
Revision 00
July 2007
Page 42 of 56
SRL Service Manual
Revision 00
July 2007
Page 43 of 56
SRL Service Manual
Revision 00
July 2007
What it means: The compressor protection module registers a motor winding temperature above
the allowable limit.
What it does: Cuts power to compressor contactor & alarm contacts. Turns dryer OFF. Turns on
Warning Light & blinks “CP” on the digital display.
Possible Causes & Remedies:
1) Scroll compressor is rotating backwards because the phases are inverted. The
compressor is not displacing any refrigerant, so there is no cooling of the
compressor causing it to overheat. The compressor will generally be noisy, and
there will be no cooling in the refrigerant circuit.
Remedy - Swap two phases on the power supply.
2) One phase of the power supply is disconnected. Because of the missing phase,
the compressor is pulling high Amps, causing overheating of the windings.
Remedy – Ensure that the electrical connections at the compressor terminal and
the contactor are correctly attached and tight.
To Reset: Find the cause of the alarm and fix the problem.
Press ALARM RESET to clear alarm. Power restored to alarm relay, Warning Light
goes off. Dryer remains OFF. Display clears.
Press ON/OFF to restart dryer.
Notes: Alarm can only be cleared if the compressor protection module registers a winding
temperature within allowable limits.
What it means: The microprocessor found an anomaly during a periodic check of the flash memory
and the stored parameters.
What it does: Resets all parameters to their default settings. Cuts power to compressor contactor
& alarm contacts. Turns dryer OFF. Turns on Warning Light & blinks “PdE” on the
digital display.
To Reset: Press ALARM RESET to clear alarm. Power restored to alarm relay, Warning Light
goes off. Dryer remains OFF. Display clears.
Press ON/OFF to restart dryer.
Page 44 of 56
SRL Service Manual
Revision 00
July 2007
Page 45 of 56
SRL Service Manual
Revision 00
July 2007
What it means: Drain Operating Mode (Parameter D3) is set to Capacitive (Zero Air Loss) Mode,
and although the drain valve has been open for 30 seconds, the condensate level
sensor is still registering condensate in the chamber.
What it does: Cuts power to the alarm contacts. Turns on Warning Light & alternates between
“drE” and the dewpoint reading on the digital display. The drain is operated in
Timed Mode according to the interval and duration settings (parameters D1 & D2).
Possible Causes & Remedies:
1) Blockage, restriction or back pressure in the condensate discharge line.
Condensate is not being evacuated efficiently and is backing up in the heat
exchanger.
Remedy – Find the cause of the blockage, restriction or back pressure and fix it.
2) Defective condensate level sensor gives a signal indicating condensate is
present even if there is none.
Remedy - Replace the defective component.
3) Defective condensate drain valve.
Remedy – Replace the defective component.
To Reset: The drain will automatically return to Capacitive (Aero Air Loss) Mode operation
when the level sensor stops sensing liquid for at least 5 seconds, but alarm will not
automatically clear.
Push Alarm Reset to clear the alarm. The alarm will also clear if the drain operating
mode (Parameter D3) is changed to Timed or Continuous (Deactivated) Modes.
Notes: The drain alarm is possible whether the dryer is ON or in Remote Off Mode – as
long as there is power to the controller, and Parameter D3 is set to “Capacitive”
mode.
Even though the drain automatically operates in Timed Mode during this alarm,
Parameter D3 will continue to show that Capacitive Mode is the set mode of
operation.
Page 46 of 56
SRL Service Manual
Revision 00
July 2007
Page 47 of 56
SRL Service Manual
Revision 00
July 2007
What it means: Dryer has on for longer than the Service Required Warning Interval (Parameter
B9: Default 6000 hours) without service or inspection.
What it does: Cuts power to the alarm contacts. Turns on Warning Light & alternates between
“Sr” and the dewpoint reading on the digital display.
To Reset: Press ALARM RESET. Power restored to alarm relay & Warning Light goes off
for 24 hours.
To reset the alarm for another 6000 hours, contact Sullair or your authorized
Sullair distributor and ensure the dryer & filters are inspected and maintained in
accordance with the schedules in their respective user guides.
The alarm reset (Parameter B3) and it’s interval (Parameter B9) are locked and
can only be modified after entering a special pass code. See Section 10.3 for
further information.
Notes: Unlike the other alarms, the “Sr” warning is not recorded in the alarm history.
Page 48 of 56
SRL Service Manual
Revision 00
July 2007
Every 6000 hours the dryer will display the “Sr” (Service Required) warning. The dryer will continue to
function normally while this warning is displayed. The purpose of this warning is to ensure that the
dryer is maintained in accordance with the maintenance schedule outlined in Section 10.1.
Please Note:
The purpose of the “Service Required” warning is to ensure proper maintenance
in accordance with the recommendations of the User Guide.
For this reason, pressing Alarm Reset will only reset the warning for 24 hours,
and parameters B3 (Reset Service Required Warning) and B9 (Service Required Warning Interval)
are locked - their values cannot be changed by pushing the Up and Down buttons.
3) Press Enter to access this parameter. The display will show you it’s value is “no”.
(The value cannot be changed by pressing the Up or Down buttons.)
4) Press the Up & Enter buttons simultaneously for 5 seconds. The value will change to “Yes” for &
a moment and then change back to “no”. The alarm has now been reset.
5) Press Exit to exit the parameter. The display will show you are at Parameter “B3”.
6) Press Exit again to exit the User Parameter Menu. The display will show the dewpoint if the dryer
is on, “OFF” if the dryer is off, or “rOF” if the dryer is in Remote Off Mode.
Page 49 of 56
SRL Service Manual
Revision 00
July 2007
3) Press Enter to access this parameter. The display will show you it’s value is “6” (6000 hours).
(The value cannot be changed by pressing the Up or Down buttons.)
4) Press the Up & Enter buttons simultaneously for 5 seconds. This unlocks the parameter &
so it can be modified).
5) Press the Up or Down buttons to change it’s value (min = 1000 hours, max = 999,000 hours) or
6) Press Enter to save your changes and exit the parameter. The display will show you are at Parameter “B8”.
Press Exit to exit the User Parameter Menu. The display will show the dewpoint if the dryer is on,
“OFF” if the dryer is off, or “rOF” if the dryer is in Remote Off Mode.
Page 50 of 56
SRL Service Manual
Revision 00
July 2007
Page 51 of 56
SRL Service Manual
Revision 00
July 2007
Please Note:
The purpose of the Alarm History Report warning is to provide critical information to service personnel
when troubleshooting the unit.
1) Press the Alarm Reset & Alarm Report buttons simultaneously to access the User Parameter
&
Menu. The display will show you are at Parameter “A1”.
2) Press the Down button repeatedly to scroll down to Parameter “B7”.
3) Press Enter to access this parameter. The display will show you it’s value is “no”.
(The value cannot be changed by pressing the Up or Down buttons.)
4) Press the Up & Enter buttons simultaneously for 5 seconds. The value will change to “Yes” for &
a moment and then change back to “no”. The alarm has now been reset.
5) Press Exit to exit the parameter. The display will show you are at Parameter “B7”.
6) Press Exit again to exit the User Parameter Menu. The display will show the dewpoint if the dryer
is on, “OFF” if the dryer is off, or “rOF” if the dryer is in Remote Off Mode.
Page 52 of 56
SRL Service Manual
Revision 00
July 2007
The SRL-250 to 6000 can be simply connected to an external supervisor system (otherwise known as
BMS or Building Management System).
To do so an (optional) RS485 serial card is fitted to the back of the microprocessor.
This allows direct connection to a BMS using the MODBUS RTU protocol, without the need for any
intermediate Gateway.
Control of:
• Dryer on/off
• Alarm reset (if allowed)
Page 53 of 56
SRL Service Manual
Revision 00
July 2007
Page 54 of 56
SRL Service Manual
Revision 00
July 2007
Refer to the User Guide supplied with the dryer for further details.
Page 55 of 56
SRL Service Manual
Revision 00
July 2007
Page 56 of 56
SRL Service Manual
Revision 00
July 2007
Level sensor
Electrical supply &
connection
digital input & output
connections
Page 57 of 56
SRL Service Manual
Revision 00
July 2007
• Mount a precision pressure gauge on the ¼” schrader valve on the refrigerant tube at the outlet of
the evaporator. Make sure to use as short a hose as possible on the gauge to avoid refrigerant
losses which may affect the dryer performance, especially on smaller models.
• Remove the cap on the Hot Gas Bypass Valve.
• To increase the evaporation pressure, turn the regulating screw clockwise (loading the internal
spring)
• To decrease the evaporation pressure, turn the regulating screw anti-clockwise (unloading the
internal spring).
• After adjusting, wait a few minutes to allow the pressures to stabilise. Re-adjust as necessary.
Page 58 of 56
SRL Service Manual
Revision 00
July 2007
Page 59 of 56
SRL Service Manual
Revision 00
July 2007
Page 60 of 56
SRL Service Manual
Revision 00
July 2007
13.2 An Example
To determine the maximum air flow capacity of a given dryer at any set of given conditions, apply the
correction factors given above, using the following equation:
This will give the maximum amount of flow the dryer can handle at those conditions. You can then
compare that to the actual air flow to determine if the dryer is undersized for the application.
Example: A customer complains that every day around noon, his SRL-400 shows an “Hd” (High
Dewpoint) alarm. You ask him to confirm the actual operating conditions when the alarm occurs,, and
after consulting with his plant manager, he tells you the following:
Using the above correction factor tables you quickly find the three Correction Factors are:
A = 1, B = 0.63, C = 1.03
Using your calculator, and knowing that an SRL-400 is rated for 400 cfm at standard conditions, you
plug these values into the formula and find out that the maximum capacity of the SRL-400 at those
conditions is:
400 cfm x 1 x 0.63 x 1.03 = 260 cfm
So, the customer is putting more air flow through this dryer than it is designed to handle. This is what
is causing the High Dew point alarm.
You can tell him that he needs to call his local Sullair distributor and order an SRL-500, which would
adequately handle his 300 cfm at these warm conditions (since 500 cfm x 1 x 0.63 x 1.03 = 324 cfm).
Page 61 of 56