Field Inspection and Test Record Transformer Protection Relay Test
Field Inspection and Test Record Transformer Protection Relay Test
TECHNICAL DATA
Manufacture SIEMENS
Type 7UT61215EB921BA0--0G
Serial No. BF1811509960
3. MEASUREMENT
Injected Side 1, 1 A 3Phase Injected Side 2,1 A 3Phase
Display Unit
Should be As found Should be As found
L1 Side 1 200 201.0 0 0 A
L2 Side 1 200 200.0 0 0 A
L3 Side 1 200 201.0 0 0 A
L1 Side 2 0 0 1000 1000 A
L2 Side 2 0 0 1000 1000 A
L3 Side 2 0 0 1000 1000 A
I diff. L1 1.328 1.33 1.270 1.27 I / InO
I diff. L2 1.328 1.33 1.270 1.27 I / InO
I diff. L3 1.328 1.33 1.270 1.27 I / InO
I rest. L1 1.328 1.34 1.270 1.27 I / InO
I rest. L2 1.328 1.33 1.270 1.28 I / InO
I rest. L3 1.328 1.34 1.270 1.27 I / InO
*Current tolerance is 1% of measured value or 1% Inom
*Differential tolerance is 2% of measured value or 2% Inom
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Page 1 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Name Mr.Somnuek S.
Signature
4. DIFFERENTIAL PROTECTION
Setting : 87- Pickup Value of Diff. Curr. = 0.30 I/InO
Page 2 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 3 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
6. INRUSH STABILIZATION
Setting : Inrush with 2.Harmonic Restraint = Yes
2nd Harmonic Restraint = 15 %
Time for Cross-blocking 2nd Harm. = 3.0 Cycle
n-th Harmonic Restraint = 5th
n-th Harmonic Content in-Diff = 30 %
Time for Cross-blocking n-th Harm. = 0.0 Cycle
Limit Idiff Fmax of n-th Harm.Restraint = 1.5 I/In0
2nd Harmonic block (%) Check the relay operated by 2nd harmonic . Checked
Side W1
Should be As found The relay will be blocked all trip signal P
IA 15.00 13.96
IB 15.00 14.53
IC 15.00 14.87
IABC 15.00 14.62
5th Harmonic block (%) Check the relay operated by 5th harmonic . Checked
Side W1
Should be As found The relay will be blocked all trip signal P
IA 30.00 28.48
IB 30.00 29.84
IC 30.00 30.01
IABC 30.00 31.98
Page 4 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 5 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Type : Universal Relay Testing Omicron CMC 256plus Serial no. : QF482R
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 6 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
TECHNICAL DATA
Manufacture SIEMENS
Type 7SJ80415EB961FB0--0G
Serial No. BF1811510151
3. MEASUREMENT
Injected 1 A, 115 VL-L 3Phase 50Hz
Display Unit
Should be As found
IL1 200 201 A
IL2 200 201 A
IL3 200 201 A
UL1 66.40 67 kV
UL2 66.40 67 kV
UL3 66.40 67 kV
UL12 115.00 116 kV
UL23 115.00 116 kV
UL31 115.00 116 kV
F 50.00 50.0 Hz
*Current tolerance is 1.5% of measured value or 1% Inom
*Voltage tolerance is 1.5% of measured value or 0.5% Vnom
*Frequency tolerance is 20 mHz
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Page 7 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Name Mr.Somnuek S.
Signature
Page 8 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
5. VOLTAGE PROTECTION ( 27 , 59 )
Setting : 27-1 Flexible Function 01 = ON 59-1 Flexible Function 03 = ON
27-1 Pickup Threshold = 92.0 V 59-1 Pickup Threshold = 126.5 V
27-1 Trip Time Delay = 5.0 s 59-1 Trip Time Delay = 5.0 s
27-1 Dropout ratio = 1.01 59-1 Dropout ratio = 0.99
27-2 Flexible Function 02 = ON 59-2 Flexible Function 04 = ON
27-2 Pickup Threshold = 80.5 V 59-2 Pickup Threshold = 138.0 V
27-2 Trip Time Delay = 1.0 s 59-2 Trip Time Delay = 1.0 s
27-2 Dropout ratio = 1.01 59-2 Dropout ratio = 0.99
Page 9 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 10 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 11 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Type : Universal Relay Testing Omicron CMC 256plus Serial no. : QF482R
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 12 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
TECHNICAL DATA
Manufacture MR
Type TAPCON 230 BASIC
Rated voltage Un 0 - 170
Rated frequency fn 50
Serial No. 1953799
2. RELAY SETTING
VT Setting : Parameter Setting :
3. METERING CHECK
Va-b 110 V 50 Hz
Display Unit
Shouled be Relay Reading
U actual 22.00 22.03 kV
U REF 22.00 22.00 kV
dU 0.0 0.13 %
F 50.0 50.0 Hz
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Page 13 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Name Mr.Somnuek S.
Signature
4. VOLTAGE REGULATION
4.1 VOLTAGE REGULATION TEST
Should be Relay Operated (V)
Function
(V) Pick up Drop off
Raise 108.57 108.3 108.6
Low 111.43 111.4 111.2
Page 14 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
l Keypad checked 4
Page 15 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Type : Universal Relay Testing Omicron CMC 256plus Serial no. : QF482R
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Date 28 June 2019
Page 16 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
TECHNICAL DATA
Manufacture SIEMENS
Type 7SJ82 (P1J82332)
Serial No. BM1811009392
3. MEASUREMENT
Injected 1 A, 110 VL-L 3Phase 50Hz
Display Unit
Should be As found
IL1 1000 1000 A
IL2 1000 1000 A
IL3 1000 1001 A
UL1 12.70 12.697 kV
UL2 12.70 12.693 kV
UL3 12.70 12.705 kV
UL12 22.00 21.998 kV
UL23 22.00 22.009 kV
UL31 22.00 22.000 kV
F 50.00 50.00 Hz
*Current tolerance is 0.1% of measured value
*Voltage tolerance is 0.1% of measured value
*Frequency tolerance is 20 mHz
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Page 17 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
Name Mr.Somnuek S.
Signature
Page 18 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
5. VOLTAGE PROTECTION ( 27 , 59 )
Setting : 27-1 Measured value = phase-to-ground 59-1 Measured value = phase-to-ground
27-1 Threshold = 50.800 V 59-1 Threshold = 69.850 V
27-1 Dropout ratio = 1.01 59-1 Dropout ratio = 0.99
27-1 Operate delay = 5.00 s 59-1 Operate delay = 5.00 s
27-2 Measured value = phase-to-ground 59-2 Measured value = phase-to-ground
27-2 Threshold = 44.450 V 59-2 Threshold = 76.200 V
27-2 Dropout ratio = 1.01 59-2 Dropout ratio = 0.99
27-2 Operate delay = 1.00 s 59-2 Operate delay = 1.00 s
Page 19 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
6. ARC PROTECTION
Setting : Threshold I> = 2.000 A
Threshold 3I0> = 1.000 A
Channel = Arc module 1.channel 1
Operating mode = current and light
Page 20 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 21 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. INC1 Date : 27/6/2019
Type : Universal Relay Testing Omicron CMC 256plus Serial no. : QF482R
WITNESSED BY
RESPONSIBILITY TESTED BY CHECKED BY WITNESSED BY
APPROVED BY
Name Mr.Somnuek S.
Signature
Page 22 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT1 Date : 27/6/2019
TECHNICAL DATA
Manufacture SIEMENS
Type 7SJ80215EB901FA0--0S
Serial No. BF1809510023
3. MEASUREMENT
Injected 1 A 3Phase 50Hz
Display Unit
Should be As found
IL1 600 600 A
IL2 600 600 A
IL3 600 602 A
F 50.00 50.0 Hz
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Page 23 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT1 Date : 27/6/2019
Name Mr.Somnuek S.
Signature
Page 24 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT1 Date : 27/6/2019
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Name Mr.Somnuek S.
Signature
Page 25 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT1 Date : 27/6/2019
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Name Mr.Somnuek S.
Signature
Page 26 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT2 Date : 27/6/2019
TECHNICAL DATA
Manufacture SIEMENS
Type 7SJ80215EB901FA0--0S
Serial No. BF1809510022
3. MEASUREMENT
Injected 1 A 3Phase 50Hz
Display Unit
Should be As found
IL1 600 603 A
IL2 600 602 A
IL3 600 603 A
F 50.00 50.0 Hz
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Page 27 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT2 Date : 27/6/2019
Name Mr.Somnuek S.
Signature
Page 28 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT2 Date : 27/6/2019
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Name Mr.Somnuek S.
Signature
Page 29 of 30 QCF-021.2
FIELD INSPECTION AND TEST RECORD
Costomer : CPRAM CO., LTD. Location : 22kV SWG. OUT2 Date : 27/6/2019
Company DEMCO PCL. DEMCO PCL. CPRAM CO., LTD. EMUNICS CO., LTD.
Name Mr.Somnuek S.
Signature