0% found this document useful (0 votes)
211 views44 pages

Electrical Heat Tracing: in Hazardous Areas

The document discusses different types of electrical heat tracing cables and accessories that are approved for use in hazardous areas. It provides information on self-regulating heating cables with maximum temperatures up to 480°C, temperature controllers, junction boxes, and connection kits.

Uploaded by

Zeva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
211 views44 pages

Electrical Heat Tracing: in Hazardous Areas

The document discusses different types of electrical heat tracing cables and accessories that are approved for use in hazardous areas. It provides information on self-regulating heating cables with maximum temperatures up to 480°C, temperature controllers, junction boxes, and connection kits.

Uploaded by

Zeva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Electrical Heat Tracing

in Hazardous Areas

innovations in heat tracing


Table of Contents
Introduction 3

1. Heating Cables

Type ELSR-N Self-regulating Heating Cable up to 80 °C 4-5

Type ELSR-LS Self-regulating Heating Cable up to 80 °C 6-7

Type ELSR-H Self-regulating Heating Cable up to 210 °C 8-9

Type ELP/PFA Constant Wattage Heating Cable up to 260 °C 10-11

Type ELKM-AG-N PTFE-insulated Heating Cable up to 260 °C 12-13

Type ELK-MI/VA-Ex Heating Cable up to 480 °C 14-15

2. Measurement and Control

Type Ex-Box REG/DIS Temperature Controller 16-17

Type Ex-Box REG/LED Temperature Controller 18-19

Type Ex-Box LIM/DIS Temperature Limiter 20-21

Type Ex-Box LIM/LED Temperature Limiter 22-23

Type Ex-Control Hand-held Controller Pad 24-25

Type EL-CT Ex-Capillary Thermostat 26-27

Type ELTF-PTEx Temperature Sensor 28-29

3. Junction Boxes and Accessories

Type Ex-it-R Junction Box 30-31

Type ELAK-R Junction Box 32-33

Type ELAK-Ex-3 Junction Box 34-35

Type Ex-Con Splice Connector Kit 36-37

Type ELVB-SR…Ex-… Connection Kits 38-39


for Self-regulating Heating Cables

Type EL-ECN/L/H/P-Ex End Termination Kits 40-41


for Self-regulating Heating Cables

Cable Overview 42-43

7.02 Heat Tracing in Hazardous Areas


Electrical Heat Tracing
in Hazardous Locations
eltherm, as an ATEX and IECEx-certified company, fulfills the increased safety standards according to the latest
Ex-guidelines. Whether it is heating cables, measurement and control appliances or ancillaries – for all its prod-
ucts eltherm has approved equivalents for Heat Tracing Systems in Hazardous Locations.
Because of our worldwide operation and because our electrical heating systems are used in a very wide range
of applications, our products are checked and approved in accordance with many international directives and
norms for an extremely wide range of areas of application.

eltherm participates in international committees which define the worldwide standards of Electrical
Heat Tracing:
IEC 60079-30-1 (international):
Explosive atmospheres – Part 30-1: Electrical resistance trace heating – General and testing requirements
IEC 60079-30-2 (international):
Explosive atmospheres – Part 30-2: Electrical resistance trace heating – Application guide for design, instal-
lation and maintenance
IEC 62395-1 (international):
Electrical resistance trace heating systems for industrial and commercial applications
IEEE 515 (US):
IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for
Industrial Applications

www.eltherm.com 7.03
Heating Cable
Self-regulating
The versatile self-regulating heating cable ELSR-N is suited for frost protection and temperature maintenance in
the low temperature range of industrial applications. Likewise it is approved for use in hazardous areas. The BOT
version of this heating cable even withstands aggressive chemicals, oil and fuel and, thanks to this high chemical
resistance, stands out for a long lifetime.

Advantages: Applications:
Self-regulating Frost protection
Four nominal outputs Heat tracing on level indicators
Can be cut to length off the roll Chemical & petrochemical industries
Moisture proof Tank bottom heating of LNG storage tanks
UV-resistant Pipe heat tracing
Approved for use in hazardous areas Vessels and tanks
Automotive
Food processing industry

Type ELSR-N up to 80 °C

Protective braid
Cu, tin plated

Self-regulating
Bus wire heating Outer jacket
Insulation
1.23 mm2 element

Protective conductor Protection


Cu, tin plated aluminium foil

7.04 Heat Tracing in Hazardous Areas


Technical Information Type ELSR-N up to 80 °C
Data Design
Outer jacket TPE-O BO Protective braid and a thermoplastic outer jacket
Bus wire Nickel plated copper AO Aluminium foil and a thermoplastic outer jacket
Maximum exposure 80 °C BOT Protective braid and a fluoropolymer outer jacket
temperature (power off)
Maximum exposure 65 °C
temperature (power on) ELSR-N-…-2 output
(on insulated metallic pipes in accordance with EN 62395-1)
Nominal voltage 230 V
Bending radius, min. 25 mm 70
Installation – 45 °C
temperature, min. 60

Classification system IBExU II 2G Ex e IIC T6 Gb


50
II 2D Ex tb IIIC TX Db
ELS
Classification cable EPS II 2G Ex e IIC Gb 40 R-N
-40
II 2D Ex tb IIIC D -2
Output [W/m]

Certificates 12ATEX1431U 30 ELS


R-N
-30
IECEx EPS 12.0006U ELS
R-N
-2
20 -20-
2
ELSR-N
-10-2
Heating circuit lengths ELSR-N-…-2 on the following conditions: 10
230 V nominal voltage
Delayed action circuit breakers (C-characteristic) with 80 % maximum load
– 30 – 20 – 10 0 10 20 30 40 50 60
Maximum 10 % line voltage drop on the heating cable bus wire
Pipe temperature [°C]
Power connection to one (1) heater end

Switch-on Nominal Heating circuit length (m) for Dimen- Weight


Nominal sions
tempera- cutout ELSR-N- ELSR-N- ELSR-N- ELSR-N- Type approx. Art. No.
output approx.
ture value (A) 10-2 20-2 30-2 40-2 (mm) (g/m)
10 128 68 52 36 ELSR-N-10-2-AO 10 W/m at 10 °C 13.6 x 5.5 91 B0200130
16 177 109 83 57
ELSR-N-10-2-BO 10 W/m at 10 °C 14.1 x 5.8 108 B0200110
10 20 177 129 104 71
25 177 129 113 89 ELSR-N-10-2-BOT 10 W/m at 10 °C 13.8 x 5.6 108 B0200119
32 177 129 113 94
ELSR-N-20-2-AO 20 W/m at 10 °C 13.6 x 5.5 91 B0200230
10 106 57 45 31
16 160 92 71 50 ELSR-N-20-2-BO 20 W/m at 10 °C 14.1 x 5.8 108 B0200210
0 20 160 115 89 62 ELSR-N-20-2-BOT 20 W/m at 10 °C 13.8 x 5.6 108 B0200219
25 160 119 105 78
32 160 119 105 88 ELSR-N-30-2-AO 30 W/m at 10 °C 13.6 x 5.5 91 B0200330
10 90 50 39 28 ELSR-N-30-2-BO 30 W/m at 10 °C 14.1 x 5.8 108 B0200310
16 144 79 63 44 ELSR-N-30-2-BOT 30 W/m at 10 °C 13.8 x 5.6 108 B0200319
-10 20 149 99 78 55
25 149 111 98 69 ELSR-N-40-2-AO 40 W/m at 10 °C 13.6 x 5.5 91 B0200430
32 149 111 98 83 ELSR-N-40-2-BO 40 W/m at 10 °C 14.1 x 5.8 108 B0200410
10 78 44 35 25 ELSR-N-40-2-BOT 40 W/m at 10 °C 13.8 x 5.6 108 B0200419
16 125 70 56 40
-20 20 139 87 69 50
25 139 104 87 62
32 139 104 87 78
10 62 35 28 21
16 99 56 45 33
-40 20 124 71 57 42
25 124 88 71 52
32 124 88 71 66

www.eltherm.com 7.05
Heating Cable Light 'Super'
Self-regulating
The versatile self-regulating heating cable ELSR-LS is our ‘light’ version for temperatures up to 80 °C. This heating
cable is also suited and approved for use in hazardous areas. Since eltherm® self-regulating cables can be cut off
the roll to the desired length, the application cable is highly flexible to match our customer’s needs. Its long life
span guarantees for the efficient use in many industrial sectors.

Advantages: Applications:
Self-regulating Pipe heat tracing
Four nominal outputs Frost protection for industrial applications
Can be cut to length off the roll Temperature maintenance for pipes and vessels
Moisture proof Chemical & petrochemical industries
UV-resistant Paints & varnishes
Small dimensions Automotive
Food processing industry

Type ELSR- LS up to 80 °C

Protective braid
tinned copper

Bus wire Self-regulating Outer jacket


1.23 mm2 Insulation
heating element

Protective conductor Protection


Cu, tin plated aluminium foil

7.06 Heat Tracing in Hazardous Areas


Technical Information Type ELSR- LS up to 80 °C
Data Design
Outer jacket TPE-O BO Protective braid and a thermoplastic outer jacket
Bus wire 1,23 mm² nickel plated copper AO Aluminium foil and a thermoplastic outer jacket
Maximum exposure 80 °C
temperature (power off)
Maximum exposure 65 °C
temperature (power on) ELSR-LS-…-2 output
Nominal voltage 230 V (on insulated metallic pipes in accordance with EN 62395-1)

Bending radius, min. 25 mm 50


Installation – 50 °C 45
temperature, min.
40
Classification system IBExU II 2G Ex e IIC T6 Gb
II 2D Ex tb IIIC TX Db 35
EL
Classification cable EPS II 2G Ex e IIC Gb 30 SR
-LS
-30
II 2D Ex tb IIIC Db 25 -2
Output [W/m]

ELS
R-L
Certificates 12ATEX1431U 20 S-2
5-2
IECEx EPS 12.0006U ELS
15 R-L
S-1
5-2
10
Heating circuit lengths ELSR- LS -…-2 on the following conditions ELSR
-LS-1
5 0-2
230 V nominal voltage
Delayed action circuit breakers (C-characteristic) with 80 % maximum load
Maximum 10 % line voltage drop on the heating cable bus wire – 30 – 20 – 10 0 10 20 30 40 50 60
Pipe temperature [°C]
Power connection to one (1) heater end

Switch-on Nominal Heating circuit length (m) for Dimen- Weight


Nominal sions
tempera- cutout ELSR- LS - ELSR- LS - ELSR- LS - ELSR- LS - Type approx. Art. No.
output approx.
ture (°C) value (A) 10-2 15-2 25-2 30-2 (mm) (g/m)
10 152.0 103.0 64.0 49.0 ELSR-LS-10-2-AO 10 W/m at 10 °C 10.3 x 5.5 78 B0223104
16 196.0 160.5 103.0 78.0 ELSR-LS-10-2-BO 10 W/m at 10 °C 10.8 x 5.6 98 B0223102
10
20 196.0 160.5 126.0 97.5
ELSR-LS-15-2-AO 15 W/m at 10 °C 10.3 x 5.5 78 B0223154
25 196.0 160.5 126.0 112.5
ELSR-LS-15-2-BO 15 W/m at 10 °C 10.8 x 5.6 98 B0223152
10 141.0 84.0 54.0 44.0
16 188.5 134.0 87.0 70.0 ELSR-LS-25-2-AO 25 W/m at 10 °C 10.3 x 5.5 78 B0223254
0 ELSR-LS-25-2-BO 25 W/m at 10 °C 10.8 x 5.6 98 B0223252
20 188.5 145.0 108.0 87.5
25 188.5 145.0 116.0 104.0 ELSR-LS-30-2-AO 30 W/m at 10 °C 10.3 x 5.5 78 B0223304
10 119.0 71.0 47.0 38.0 ELSR-LS-30-2-BO 30 W/m at 10 °C 10.8 x 5.6 98 B0223302
16 173.5 114.0 75.0 61.0
-10
20 173.5 133.0 94.0 76.0
25 173.5 133.0 107.5 95.0
10 103.0 62.0 37.5 33.0
16 161.0 99.0 60.0 53.0
-20
20 161.0 124.0 75.0 66.0
25 161.0 124.0 94.0 83.0

www.eltherm.com 7.07
Heating Cable High Temp.
Self-regulating
The versatile self-regulating heating cable ELSR-H is for high temperatures up to 210 °C in
a large number of industrial applications. It is also suited and approved for use in hazard-
ous areas. The BOT version of this heating cable even withstands aggressive chemicals,
oil and fuel and, thanks to this high chemical resistance, stands out for a long life span.

Advantages: Applications:
Up to 120 °C/210 °C Chemical & petrochemical industries
Self-regulating Oil & gas industry
Six nominal outputs Power plants
Can be cut to length off the roll Ex-areas
Moisture proof Frost protection
Resistant to chemicals Water & sanitation utilities
Approved for use in hazardous areas Temperature maintenance on vessels, pipes & valves

Type ELSR-H up to 210 °C

Self-regulating Protective braid


heating element Cu, tin plated

Bus wire Insulation Outer jacket


1.23 mm2

7.08 Heat Tracing in Hazardous Areas


Technical Information Type ELSR-H up to 210 °C
Data Design
Outer jacket Fluoropolymer BOT Protective braid and a fluoropolymer outer jacket
Bus wire Nickel plated copper
Maximum exposure 210 °C
temperature (power off)
Maximum exposure 120 °C
ELSR-H-...-2-BOT output
temperature (power on) (on insulated metallic pipes in accordance with EN 62395-1)

Nominal voltage 230 V / (120 V, 277 V)* 90


Bending radius, min. 25 mm
80
Installation – 45 °C
temperature, min.
70
Classification system IBExU II 2G Ex e IIC T3 Gb EL
II 2D Ex tb IIIC TX Db SR
60 -H
-75
IBExU II 2G Ex e IIC T4...T6 Gb II 2D ELS
Ex tb IIIC TX Db (stabilized design) 50 R-H
-60
Classification cable EPS II 2G Ex e IIC Gb 40 ELSR
II 2D Ex tb IIIC Db -H-4
5
Output [W/m]

Certificates 12ATEX1429U 30
ELSR
IECEx EPS 12.0004U -H-30

*upon request 20 ELSR-H


-20
ELSR-H-1
5
Heating circuit lengths ELSR-H-...-2-BOT on the following conditions: 10 ELSR-H-10
230 V nominal voltage
Delayed action circuit breakers (C-characteristic) with 80 % maximum load
Maximum 10 % line voltage drop on the heating cable bus wire – 30 – 20 – 10 0 10 20 30 40 50 60 70 80 90 100 110 120
Power connection to one (1) heater end Rohrtemperatur [°C]

Switch-on Nominal Heating circuit length (m) for ELSR-H- Dimen- Weight
tempera- cutout Nominal sions
Type approx. Art. No.
ture value (A) 10-2 15-2 20-2 30-2 45-2 60-2 75-2 output approx.
(mm) (g/m)
16 193.0 158.0 122.0 82.0 55.0 41.0 33.0 ELSR-H-10-2-BOT 10 W/m at 10 °C 12.4 x 5.0 120 B0221103
20 193.0 158.0 136.0 102.0 68.0 51.0 41.5
10 ELSR-H-15-2-BOT 15 W/m at 10 °C 12.4 x 5.0 120 B0221153
25 193.0 158.0 136.0 111.0 85.0 64.0 51.5
32 193.0 158.0 136.0 111.0 91.0 79.0 66.0 ELSR-H-20-2-BOT 20 W/m at 10 °C 12.4 x 5.0 120 B0221203
16 189.0 153.0 116.0 77.0 52.0 39.0 30.0
ELSR-H-30-2-BOT 30 W/m at 10 °C 12.4 x 5.0 120 B0221303
20 189.0 153.0 132.0 97.0 65.0 49.0 37.5
0
25 189.0 153.0 132.0 108.0 81.0 61.0 47.0 ELSR-H-45-2-BOT 45 W/m at 10 °C 12.4 x 5.0 120 B0221453
32 189.0 153.0 132.0 108.0 88.5 77.0 60.0 ELSR-H-60-2-BOT 60 W/m at 10 °C 12.4 x 5.0 120 B0221603
16 184.0 146.0 110.0 73.0 50.0 37.0 28.5 ELSR-H-75-2-BOT 75 W/m at 10 °C 12.4 x 5.0 120 B0221753
20 1840. 148.5 129.0 92.0 62.0 46.0 35.5
-10
25 1840. 148.5 129.0 105.5 77.0 58.0 44.5
32 184.0 148.5 129.0 105.5 86.5 70.0 57.0
16 180.0 139.0 104.0 70.0 47.0 36.0 26.5
20 180.0 145.0 125.5 87.0 59.0 44.0 33.5
-20
25 180.0 145.0 125.5 103.0 74.0 56.0 41.5
32 180.0 145.0 125.5 103.0 84.5 67.0 53.5
16 173.0 126.0 95.0 64.0 43.0 33.0 23.5
20 173.0 138.0 119.0 80.0 54.0 41.0 29.0
-40
25 173.0 138.0 120.0 98.0 68.0 51.0 36.5
32 173.0 138.0 120.0 98.0 81.0 61.0 46.5

www.eltherm.com 7.09
Constant Wattage Heating Cable
with Resistance Wire
These parallel heating cables offer tremendous flexibility in use, as they can easily be cut to the required length off
the roll, with the assurance of constant power output. There is no need for a connecting cable and input can be
unilateral. It is quick and easy to assemble; this saves a lot of time, and reduces costs considerably as a result. Since
output of up to 60 W/m is possible for lengths laid to piping, ELP parallel heating cables are particularly suitable
for piping with high output requirements such as in industrial process technology. The particularly temperature-
resistant outer shell in PFA and the high level of chemical resistance of the PFA ensure a long useful life.

Advantages: Applications:
Single end power input Vessels, piping, valves
Can be cut off the roll Building construction
Constant power output per meter Food processing industry
Long life cycle Paper industry
Laying without exact measuring possible
High chemical resistance
UV resistance

Type ELP/PFA up to 260 °C

Bus wire 2. Insulation 3. Insulation


1.5 mm2

1. Insulation Heating Protective braid Outer jacket


conductor nickel-plated copper PFA

7.10 Heat Tracing in Hazardous Areas


Type ELP/PFA
Technical Information
up to 260 °C
Data Standards
Insulations PFA Manufactured DIN VDE 0721-52
according to EN 62395-1; 2007-05
Protective braid Nickel-plated copper
Certificates 12ATEX1438U
Outer jacket PFA
IECEx EPS 12.0009U
Nominal temperature 260 °C
Classification II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
Moisture proof Yes
Bending radius, min. 25 mm
Bus wire cross section 2 x 1.5 mm2 Cables shall neither intersect nor contact.
Provide protection by means of circuit breaker FI 30.
Nominal voltage 230 V AC/DC Please observe the standards IEC 62395-2, EN 60519-10.
Installation temp., min. -45 °C
Start-up temp., min. -45 °C

Bus wire
Heating zone 1m
Contact point Contact point Contact point L

Contact point Contact point


PE

Active heating cable Protective braid

Working Dimensions Contact Maximum heating circuit length


Nominal
Type temp. approx. spacing Art. No. Length (m) at Length (m) at
output Type W/m
max (mm) (m) 50 °C 150 °C
ELP/PFA 15 BOT 15 W/m 205°C 8.0 x 5.5 1.0 B0332015 ELP/PFA 15 BOT 15 161 119
ELP/PFA 30 BOT 30 W/m 190°C 8.0 x 5.5 1.0 B0332030 ELP/PFA 30 BOT 30 98 82.5
ELP/PFA 45 BOT 45 W/m 175°C 8.0 x 5.5 1.0 B0332045 ELP/PFA 45 BOT 45 65.5 65.5
ELP/PFA 60 BOT 60 W/m 160°C 8.0 x 5.5 1.0 B0332060 ELP/PFA 60 BOT 60 50 50
Bus wire cross section 2 x 2 mm² upon request. Heating circuit lengths ELP/PFA on the following conditions
16 A circuit breaker, 80 % utilisation
Max. 10 % voltage drop
Power connection to one (1) heater end

www.eltherm.com 7.11
PTFE insulated Heating Cable
with Protective Braid + Outer Jacket
This versatile heating cable is used for frost protection and temperature maintenance, even under highly corro-
sive environmental conditions. The heating cable ELKM-AG-N is suited and approved for use in hazardous areas.
It is highly flexible permitting its use in many fields of application.

Advantages: Applications, especially in


High chemical and mechanical resistance hazardous areas: e.g.
Heat tracing on tanks
Can be used in all industrial areas
Heat tracing on vessels
High operation temperature Heat tracing on filters
Can be used in liquids Heat tracing on hoppers
Easy to install, even on complex shapes Pipe, valve and pump heating
Tank containers
Highly flexible
IBC’s
Resistant to steam purging Heating hoods
Automotive
Varnishing plants

Type ELKM-AG-N up to 260 °C

Heating conductor stranded Protective braid


nickel-plated copper

Insulation Outer jacket


PTFE PFA

7.12 Heat Tracing in Hazardous Areas


Type ELKM-AG-N
Technical Information
up to 260 °C
Data Standards
Insulation PTFE Manufactured according to DIN VDE 0253,
EN 60079-30-1
Protective braid Nickel plated copper
Certificates EPS 12ATEX1466U
Outer jacket PFA
Classification II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
Nominal voltage max. 550 V
Output, max. 30 W/m*
Operating temp., max. 260 °C
Bending radius, min. 2.5 x outer diameter *Note: The output per meter of heating cable and the maxi-
mum possible operating temperatures depend on the respec-
Installation temp., min. -60 °C tive application. For individual cases, we recommend that you
Moisture proof IP68 contact our engineers – we will be pleased to advise you.

Impact resistance 4 Joule For suitable connection and termination kits please note our
considerable accessories catalogue unit.
Heat conductor Stranded

Nominal Outer diame- Weight Temperature Nominal Outer diame- Weight Temperature
resistance ter approx. approx. coefficient Art. No. resistance ter approx. approx. coefficient Art. No.
(Ω/km) (mm) (g/m) (x 10 -3 / K) (Ω/km) (mm) (g/m) (x 10 -3 / K)
1.95 8.1 166 4.30 01TA002E 280.00 4.0 39 0.38 01TA128E
(Cu 10 mm2)
2.90 328.00 4.1 40.1 0.45 01TA132E
(Cu 6 mm2) 6.8 119 4.30 01TA003E
360.00 3.9 40 0.45 01TA136E
4.40
(Cu 4 mm2) 6.1 96 4.30 01TA004E 430.00 4.1 43 0.18 01TA143E
7.20 480.00 4.1 44 0.18 01TA148E
(Cu 2.5 mm2) 5.1 64 4.30 01TA007E
10.00 4.8 59 4.30 01TA010E 600.00 4.0 40 0.18 01TA160E
11.70 800.00 3.9 41 0.18 01TA180E
(Cu 1.5 mm2) 4.7 57 4.30 01TA011E
1000.00 4.0 43 0.04 01TA210E
15.00 4.5 50 4.30 01TA015E
1470.00 3.8 40 0.04 01TA214E
25.00 4.4 48 3.00 01TA025E
1750.00 3.8 37 0.04 01TA217E
31.50 4.7 56 1.60 01TA031E
1900.00 3.5 41 0.40 01TA219E
50.00 4.4 49 1.60 01TA050E
2900.00 3.9 41 0.40 01TA229E
65.00 4.2 46 1.60 01TA065E
4000.00 3.8 37 0.40 01TA240E
80.00 4.5 42 0.90 01TA080E
4700.00 3.8 35 0.15 01TA247E
100.00 4.4 50 0.90 01TA110E
6000.00 3.8 34 0.20 01TA260E
157.00 4.4 46 0.45 01TA115E
7000.00 3.8 33 0.15 01TA270E
180.00 4.1 42 0.90 01TA118E
8000.00 3.8 36 0.15 01TA280E
200.00 4.2 38 0.45 01TA120E
260.00 4.1 42 0.45 01TA126E For applications with fixed external diameter, please contact our engi-
neers first.
Weight tolerances are possible for manufacturing reasons.
Nominal resistances up to 1,500,000 Ω/km upon request. Cables shall neither intersect nor contact.
Resistance tolerance: +/- 5 %. Provide protection by means of circuit breaker FI 30mA.
Please observe the standards EN 60079-30-2, EN 60519-10.

www.eltherm.com 7.13
Heating Cable
Highly robust
Factory terminated heating cable, suitable for use in overpressure and vacuum applications. Can be used as radiant
heating with high output density. This heating cable is approved for use in hazardous areas. We provide engi-
neering services from initial design up to turnkey project execution. Complete engineering up to commissioning.
Laser welding technology enables us to provide high precision, safe and reliable MI connections.

Advantages: Applications, especially in


Factory terminated hazardous areas: e.g.
Hermetically sealed metal sheath Moisture proof applications at
high outputs and temperatures
Highly robust and mechanically stable
Can be immersed in fluids
Moisture proof
Heat tracing on piping
Higher chemical resistance
Chemical & petrochemical industries
Higher operating temperatures
Machinery and plant construction
Higher output per meter
Equipment engineering
High precision, safe and reliable laser
welding connections Vacuum technology

Type ELK-MI/VA-Ex up to 480 °C

Heating conductor

Insulation Outer jacket


magnesium oxide VA 1.4541/ AISI 321

7.14 Heat Tracing in Hazardous Areas


Type ELK-MI/VA-Ex
Technical Information
up to 480 °C
Data Standards
Outer jacket Stainless steel 1.4541/ AISI 321 Manufactured according to EN 60079-30-1
Operating temp., max. 480 °C Certificates Cable EPS 13 ATEX 1 627 U
IECEx EPS 14.0013U
Ambient temp. min. -60 °C
Certificates System FM15ATEX0046X
Nominal output Up to 250 W/m
IECEx FME 15.0009X
Nominal voltage Up to 500 V AC
Classification Cable II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
Impact resistance 7J
Classification System II 2 G Ex db e IIC T6…T1 Ta = -60°C
Cold lead, length 2 x 0.50 m to +60°C Gb
II 2 D Ex tb IIIC T85°C…T450°C Ta
Cold lead, cross section 2.50 mm²
= -60°C to +60°C Db; IP64
Cable gland Brass M20 x 1.5
Protective conductor Integrated
connection
IP rating IP 65
Protection class I
Min. bending radius Diameter x 5
Moisture proof Yes

Important: Avoid multiple bends with minimum bending radius


(risk of cable damage).

Resistance *Note: The output per meter of heating cable and the maximum pos-
No. Diameter = mm sible operating temperatures depend on the respective application.
Ω/km
For individual cases, we recommend that you contact our engineers –
1 3.20 10.000 we will be pleased to advise you.
2 3.20 6.300
This is just a summary of all available resistances. For further resistances,
3 3.20 4.000 please contact us.
4 3.40 2.500
5 3.60 1.600
6 3.90 1.000
A table of chemical resistances is available on our website
7 4.30 630
www.eltherm.com.
8 4.70 400
Other cross sections and lengths of cold leads are available
9 5.30 250 upon request.
10 6.50 160

www.eltherm.com 7.15
Ex-Box Temperature Controller
with Display
Ex-Box REG/DIS: Complying with latest Ex-protection directives 94/9/CE (ATEX 95) this electronic temperature
controller has been designed and developed especially for its use in hazardous areas. Programming and opera-
tion is done via the integrated operating panel with display.

Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Operation and programming in hazardous area Power plants
Increased safety through fail alarm Chemical & petrochemical
Integrated heating circuit monitoring industries

Display Oil & gas industries


Pharmaceutical industry
Plastics industry
Wastewater treatment plants

Type Ex-Box REG/DIS

7.16 Heat Tracing in Hazardous Areas


Type Ex-Box REG/DIS
Technical Information
Data Cable entries
Certificate IBExU 04 ATEX 1165 X 1 x M25 for voltage supply
(9 – 13 mm; with add-ons for 11 - 15 mm)
Classification ll 2G Ex emb [ib] llC T4 Gb ll 2D 1 x exchangeable panel seal 7-10.5 mm
Ex tb IIIC T100°C Db -32°C <= Ta 1 x M25 for heating line (2-fold 6 mm)
<= 60°C 1 x M20 for sensor (tension range 3 – 4 mm)
1 x vent screw M20
Dimensions 140 x 140 x 150 mm (w x h x d)
(without wall-mounting bracket,
excluding glands)
Enclosure Aluminium
IP rating IP 65
Ambient temperature - 32 up to 60 °C
Switching capacity 16 A
Display 2 x 4 35-segment LED
Operating voltage 230 V +/– 10 %
Nominal current Max. 100 mA
Load current, max. 16 A (ohm resistive load)
Load output 230 V / 16 A, 2-pole
Alarm output Optically separated 100 mA
Interface Intrinsically safe for Ex-Connect
(bus connection)
Measurement input Pt100 2/3 wire, intrinsically safe
Measurement range -40 °C up to +300 °C
Control characteristics Dual mode controller
Weight Approx. 3.5 kg

Designation Art. No.

Ex-Box REG/DIS 0X60020

For suitable temperature sensors and accessories please note our


considerable accessories catalogue unit.

www.eltherm.com 7.17
Ex-Box Temperature Controller
with LED-Display
Ex-Box REG/LED: Complying with latest Ex-protection directives 94/9/CE (ATEX 95) this electronic temperature
controller has been designed and developed especially for its use in hazardous areas. Programming and opera-
tion is done via external Ex-Control manual control.

Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Increased safety, tamperproof, no unautho- Power plants
rised adjustments
Chemical & petrochemical
. Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants

Type Ex-Box REG/LED

7.18 Heat Tracing in Hazardous Areas


Type Ex-Box REG/LED
Technical Information
Data Cable entries
Certificate IBExU 04 ATEX 1165 X 1 x M25 for voltage supply
(9 – 13 mm; with add-ons for 11 - 15 mm)
Classification ll 2G Ex emb [ib] llC T4 Gb ll 2D 1 x exchangeable panel seal 7-10.5 mm
Ex tb IIIC T100°C Db -32°C <= Ta 1 x M25 for heating line (2-fold 6 mm)
<= 60°C 1 x M20 for sensor (tension range 3 – 4 mm)
1 x vent screw M20
Dimensions 140 x 140 x 150 mm (w x h x d)
without wall-mounting bracket,
excluding glands)
Enclosure Aluminium
IP rating IP 65 Features
Ambient temperature - 32 up to 60 °C
Interface for manual control panel Ex-Control
Switching capacity 16 A
LED green: OK, no heating
Operating voltage 230 V +/– 10 %
LED orange: OK, heating on
Nominal current Max. 100 mA
LED red blinking: alarm or fault but still ready for operation
Load current, max. 16 A (ohm resistive load)
LED red permanent: severe fault, load disconnection
Load output 230 V / 16 A, 2-pole
Alarm output Optically separated 100 mA
Interface Intrinsically safe for Ex-Control
Measurement input Pt100 2/3 wire, intrinsically safe
Measurement range -40 °C up to +300 °C
Control characteristics Dual mode controller
Load disconnection 2-phase
Weight Approx. 3.5 kg

Designation Art. No.

Ex-Box REG/LED 0X60021

For suitable temperature sensors and accessories please note our


considerable accessories catalogue unit.

www.eltherm.com 7.19
Ex-Box Limiter
with Display
The Ex-Box LIM/DIS is a limiter for switching off heating circuits in case of excess temperature or current overload.
Furthermore, output signal values for maximum and minimum temperatures are programmable. Programming
and operation is done via the integrated operating panel with display.

Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Operation and programming Power plants
in hazardous areas
Chemical & petrochemical
Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Display
Pharmaceutical industry
Plastics industry
Wastewater treatment plants

Type Ex-Box LIM/DIS

7.20 Heat Tracing in Hazardous Areas


Type Ex-Box LIM/DIS
Technical Information
Data Cable entries
Certificate IBExU 04 ATEX 1165 X 1 x M25 for voltage supply
(9 – 13 mm; with add-ons for 11 - 15 mm)
Classification ll 2G Ex emb [ib] llC T4 Gb ll 2D 1 x exchangeable panel seal 7-10.5 mm
Ex tb IIIC T100°C Db -32°C <= Ta 1 x M25 for heating line (2-fold 6 mm)
<= 60°C 1 x M20 for sensor (tension range 3 – 4 mm)
1 x vent screw M20
Dimensions 140 x 140 x 150 mm (w x h x d)
(without wall-mounting bracket,
excluding glands)
Enclosure Aluminium
IP rating IP 65
Ambient temperature - 32 up to 60 °C
Switching capacity 16 A
Operating voltage 230 V +/– 10 %
Nominal current Max. 100 mA
Load current, max. 16 A (ohm resistive load)
Load output 230 V / 16 A, 2-pole
Alarm output Optically separated 100 mA
Interface Intrinsically safe for Ex-Connect
(bus connection)
Measurement input Pt100 2/3 wire, intrinsically safe
Measurement range -40 °C up to +300 °C
Control range +50 °C up to +300 °C
Load disconnection 2-phase
Weight Approx. 3.5 kg

Designation Art. No.

Ex-Box LIM/DIS 0X60024

For suitable temperature sensors and accessories please note our consi-
derable accessories catalogue unit.

www.eltherm.com 7.21
Ex-Box Limiter
with LED-Display
The Ex-Box LIM/LED is a limiter for switching off connected heating circuits in case of excess temperature or
current overload. Furthermore, signal values for maximum and minimum temperatures are programmable.
Programming and operation is done via external panel Ex-Control for manual control.

Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Increased safety against unauthorised Power plants
changes of rated value
Chemical & petrochemical
Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants

Type Ex-Box LIM/LED

7.22 Heat Tracing in Hazardous Areas


Type Ex-Box LIM/LED
Technical Information
Data Cable entries
Certificate IBExU 04 ATEX 1165 X 1 x M25 for voltage supply
(9 – 13 mm; with add-ons for 11 - 15 mm)
Classification ll 2G Ex emb [ib] llC T4 Gb ll 2D
1 x gland 7-10.5 mm
Ex tb IIIC T100°C Db -32°C <= Ta
1 x M25 for heating line (2-fold 6 mm)
<= 60°C
1 x M20 for sensor (tension range 3 – 4 mm)
Dimensions 140 x 140 x 150 mm (w x h x d) 1 x vent screw M20
(without wall-mounting bracket,
excluding glands)
Enclosure Aluminium
IP rating IP 65 Features
Ambient temperature - 32 up to 60 °C
Interface for manual control panel Ex-Control
Switching capacity 16 A
Programmable parameter are identical to Ex-Control
Operating voltage 230 V +/– 10 %
LED green: normal operation state
Nominal current Max. 100 mA
LED red, blinking: alarm
Load current, max. 16 A (ohm resistive load)
LED red, permanent: fault
Load output 230 V / 16 A, 2-pole
Alarm output Optically separated 100 mA If a fault (excess temperature, overcurrent and internal fault) is indicated,
Interface Intrinsically safe for Ex-Control it will not automatically reset. Reset of the fault is done via the Ex-Control.
Measurement input Pt100 2/3 wire, intrinsically safe
Measurement range -40 °C up to +300 °C
Control range +50 °C up to +300 °C
Load disconnection 2-phase
Weight Approx. 3.5 kg

Designation Art. No.

Ex-Box LIM/LED 0X60023

For suitable temperature sensors and accessories please note our consi-
derable accessories catalogue unit.

www.eltherm.com 7.23
Ex-Control
Hand-held Controller Pad
Intrinsically safe hand held controller pad for use with the Ex-Box REG/LED and LIM/LED. The Ex-Control pad pro-
vides additional safety in a potentially explosive atmosphere. Adjustment of settings by unauthorized persons is
not possible since the controller can be removed.

Advantages: Applications:
Intrinsically safe controller pad Hazardous areas
Without an independent power supply Power plants
Programming and operation in hazardous
Chemical & petrochemical
areas
industries
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants

Type Ex-Control

7.24 Heat Tracing in Hazardous Areas


Type Ex-Control
Technical Information
Data Programmable parameters
Certificate IBExU 04 ATEX 1165 X Upper set point of adjustable temperature range
Dimensions (enclosure) 135 x 80 x 35 mm (w x h x d) Temperature set point
Classification ll 2G Ex ib llC T4 Gb ll 2D Ex tb IIIC Alarm, excess temperature
T100°C Db -32°C <= Ta <= 60°C
Alarm, low temperature
IP rating IP 65
Load disconnection – excess temperature
Cable entrance 1.5 m connecting cable with
Bus address 1 – 32
5-pole plug
Adjusting point Pt100
Display 2 x 4 35-segment LED
illuminated Temperature unit °C and °F
Interface Intrinsically safe for Ex-Box
LED/LIM
Weight 0.5 kg
Fault indication
Sensor short
Sensor cut
Excess temperature Pt100
Low temperature Pt100
Internal excess temperature
External bus fault
Internal bus fault
Internal hardware fault
Supply voltage fault

Designation Art. No.

Ex-Control 0X60026

www.eltherm.com 7.25
Ex-Capillary
Thermostat
The capillary thermostat EL-CT is approved for use in hazardous areas Zones 1 and 2 for gas and Zones 21 and
22 for dust as a surface thermostat on pipes and vessels. There are different temperature ranges possible. The
material of the capillary tube is stainless steel and the rugged enclosure is made of aluminium.

Advantages: Applications:
Robust Industrial applications
Versatile use Use in hazardous areas
Heat tracing on pipes,
valves and vessels
Oil & gas industry

Type EL-CT

7.26 Heat Tracing in Hazardous Areas


Type EL-CT
Technical Information
Data
Ex-Classification II 2G Ex db IIC T6 Gb II 2D Ex tb IIIC T80°C Db Ta -32°C...+50°C [CT]
Ta -50°C...+50°C [CT(2)] (Important: Classification is subject to
modification depending on the cable entrances used by the
customer!)
Certificate IBExU 03ATEX1130X
IECEx IBE 14.0069
IP rating IP 66
Ambient temperature -32 up to +50 °C [CT], -50 °C up to + 50 °C [CT(2)]
Switching capacity 16 A at 230 V [CT] / 10 A at 400 V [CT(2) only]
Switching differential 1 pol. [CT], 1 pol., changeover contact [CT(2)]
Switching contact 1 pole
Capillary tube Stainless steel
Enclosure Lacquer-coated aluminium, dimensions (l x h x d),
approx. 120 x 120 x 110 mm
Bending radius capillary tube 5 mm
Cable entrance 1 x gland M20, clamping range 10-14 mm
1 x thread M 20 x 1.5
Salt-water proof Yes

Admissible sensor
Designation Temperature range Art. No.
temperature, max.
EL-CT(2) 30 -10 °C up to +30 °C 60 °C 0X63032
EL-CT(2) 65 +5 °C up to +65 °C 100 °C 0X63065
EL-CT(2) 180 0 °C up to +180 °C 220 °C 0X63180
EL-CT(2) 320 +50 °C up to +320 °C 330 °C 0X63320
EL-CT 30 -50 °C up to +30 °C 50 °C 0X63030
EL-CT 50 0 °C up to +50 °C 105 °C 0X63050
EL-CT 200 0 °C up to +200 °C 230 °C 0X63200
EL-CT 500 +20 °C up to +500 °C 575 °C 0X63500

www.eltherm.com 7.27
ELTF-PTEx
Temperature Sensor
This temperature sensor has been designed according to Ex standard 94/9/EG especially for use in explosive gas
and dust atmosphere. An emphasis on safety, simple installation and fitting accuracy were the requirements that
our development engineers met.

Advantages: Applications:
Impact protection (U-profile) for sensor Hazardous areas
protection Power plants
Strain relief by hexagon-swaging Chemical and petrochemical plants
Bend protection Oil and gas industry
Decrease of parasitic coupling from Varnish and paint
surrounding electrical components Heating of instruments, devices and plants
because of fluoropolymer shielded Pipe, pump and valve heating
sensor cable

Type ELTF-PTEx

7.28 Heat Tracing in Hazardous Areas


Type ELTF-PTEx
Technical Information
Data Design
Classification II 2G Ex e IIC T2…T6 Gb II 2D Ex tb Sensor cable ELTF-PTEx.2 4 x 0.14 mm2, PTFE-insulated,
IIIC TX Db shield Cu nickel plated,
outer jacket ø 3.5 mm
Certificates IECEx IBE 12.0002X, ATEX1004X
fluoropolymer
Standards IEC 60079-0 ed.6, IEC 60079-7 ed.4,
Sensor cable ELTF-PTEx.4 6 x 0.14 mm2, PFA-insulated
IEC 60079-31 ed.1
shield Cu nickel plated,
Permissible ambient -45 °C to +235 °C outer jacket ø 4.4 mm
temp. fluoropolymer
Max. measuring current 10 mA Protection tube Mat. 1.4301, 6 x 6 x 46 nn, with
safety bar and mounting eye
IP-rating IP 65
ø 4.1 mm
Accuracy class "B" according to IEC 751
Installation dimension 12 x 8 x 46 cm

Max measuring voltage and operating temperature


Max. measuring Max operating
Type
voltage temperature
T6 1,3 V 80 °C
T5 1,3 V 95 °C
T4 1,5 V 130 °C
T3 1,7 V 195 °C
T2 1,7 V 235 °C

Length connecting
Type Temperature sensor Impact resistance (J) Art.-No.
cable (m)
ELTF-PTEx.2 Pt100 4-conductors 7 3 0X70002
Double - Pt100
ELTF-PTEx.4 7 3 0X70030
3-conductors

Longer connecting cables upon request.

www.eltherm.com 7.29
Junction Box, Round,
with Mounting Stand
On-pipe Mounting in Hazardous Areas
The innovative junction box ELAK-Ex-R with mounting bracket (Ex-it) is suitable for use in potentially explosive at-
mosphere in accordance with Ex-guidelines 94/9/CE (ATEX 95) and provides a number of advantages. Thanks to
the shape of the box, for instance, it is not necessary to strongly bend the inserted cable thereby avoiding cable
damage. Due to the incorporated mounting bracket there is no need to provide angle irons. This is especially
advantageous to heat tracing on piping because the cable can directly be introduced via the mounting bracket.
Furthermore, fastening screws for heating lines and sensors are not required. A safety locking, with appropriate
tool included, prevents the cover to move. Additional features permitting the attachment of sign plates facilitate
easy identification of heating circuits in complex systems.

Advantages: Applications:
No static charge Hazardous areas
Rapid closing of the cover through Chemical & petrochemical industries
snap fit, no tool required Power stations
Increased mechanical safety through Industrial plants with a need for frost protection
round shape or temperature maintenance
Permits fixing of customer identification
plates
Up to 3 heating cables can be connected

Type Ex-it-R

7.30 Heat Tracing in Hazardous Areas


Technical Information Type Ex-it-R
Data Mounting bracket
Classification II 2G Ex e IIC T6 Gb II 2D Ex tb IIIC Working temperature -20 °C up to +200 °C
ELAK-Ex-R TX Db
Enclosure PPS
Classification Ex-it-R II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
Insulating thickness, max. 120 mm
Standards Ex-it-R IEC 60079-0 ed.6, IEC 60079-7 ed.4,
IEC 60079-31 ed.1 Pipe outer diameter ≥ 20 mm

Ambient temperature -40 °C up to +50 °C IP rating IP 65

Enclosure Polyamide, no static charge Classification II 2G Ex e II II 2 D Ex tD A21 IP65

Dimensions (approx.): Dia. 150 mm, 125 x 160 mm Certificate IBExU09ATEX1023U

Ex-it-R Heigth approx. 280 mm total, the


junction box is attached to the
mounting feet.
Impact resistance 7 Joule
IP rating IP 65
Terminal blocks, heating cable connection: max. 6 mm²
Terminal blocks, temperature sensor connection: max. 1.5 mm²

Type Description Art. No.

Junction box, with mounting feet, round, dia. 150 mm, height 125 mm, polyamide enclosure, to connect 3 self-regulating
Ex-it-R 0X80070
heating cables ELSR-N/-H, 1 connecting cable, 1 sensor cable, 1 double-Pt100, insulating thickness max. 100 mm
T-branch, with mounting feet, round, dia.150 mm, height 125 mm, polyamide enclosure, to connect up to 3 self-regulating
Ex-it-R-T 0X80082
heating cables ELSR-N/-H, insulating thickness max.100 mm
Junction box, with mounting feet, round, dia. 150 mm, height 125 mm, polyamide enclosure, to connect 1 double-Pt100, 1
Ex-it-R-Pt 0X80092
sensor cable, insulating thickness max. 100 mm

Note: Connection and termination kits are not included in the Ex-it-R system. Please place a separate order for these items which depend on the type
of heating cable used.

www.eltherm.com 7.31
Junction Box, Round
for Hazardous Areas
The innovative junction box ELAK-Ex-R is suitable for use in potentially explosive atmosphere in accordance with
Ex-guidelines 94/9/CE (ATEX 95). Thanks to its exceptional shape it provides a number of advantages. Due to
the form of the box, for instance, it is not necessary to strongly bend the inserted cable thereby avoiding cable
damage.
A safety lock, with appropriate tool included, prevents the cover from moving. Additional features permitting
the attachment of sign plates facilitate easy identification of heating circuits in complex systems. Suited for wall-
mounting.

Advantages: Applications:
No static charge Hazardous areas
Rapid closing of the cover through Chemical & petrochemical industries
snap fit, no tool required Power stations
Increased mechanical safety through Industrial plants with a need for frost protection
round shape or temperature maintenance
Permits fixing of customer identification
plates
Up to 3 heating cables can be connected

Type ELAK-Ex-R

7.32 Heat Tracing in Hazardous Areas


Technical Information Type ELAK-Ex-R
Data
Classification II 2G Ex e IIC T6 Gb II 2D Ex tb IIIC
TX Db
Standards IEC 60079-0 ed.6, IEC 60079-7 ed.4,
IEC 60079-31 ed.1
Ambient temperature -40 °C up to +50 °C
Nominal current See type plate, max. 28 A
each terminal
Nominal voltage See type plate, max. 550 V
Terminals heating cable Max. 6 mm² (optional 10 mm²)
Terminals temp.sensor Max. 1,5 mm²
(if required)
Enclosure Polyamide, no static charge
Dimensions (approx.) Ø 150 mm, height 125 mm
Impact resistance 7 Joule
Cable glands Polyamide
IP rating IP65
Weight Approx. 0,7 kg
Type of mounting Wall-mounting

Type Application Features Art. No.

ELAK-Ex-R1 Star point for ELK-AG-... 3 x M16 (4-9 mm), 1 x threaded plug M20, 1 x threaded plug M25 0X80071
Two-phase heating circuit or as star-supply box 2 x M16 (4-9 mm), 1 x M25 (8-17 mm),
ELAK-Ex-R2 0X80072
for ELK-AG-... 1 x threaded plug M16, 1 x threaded plug M20
ELAK-Ex-R4 Supply: 1 heating cable ELK-AG-... + EL-CT 2 x M16 (4-9 mm), 2 x M25 (8-17 mm) 0X80074

ELAK-Ex-R5 Supply: 1 heating cable ELSR-... + EL-CT dia. 150 mm, height 125 mm, polyamide enclosure, for ELSR + EL-CT, Ex e 0X80075

ELAK-Ex-R7 Supply: 1-3 heating cable ELSR-... 1 x M25 (8-17 mm), 2 x threaded plug M25, 1 x Bohrung M25 0X80077
Supply: 1-2 Pt 100, 2-4 conductors + up to 1 x M25 (8-17 mm), 1 x M16 (4-9 mm), 2 x threaded plug M16,
ELAK-Ex-R8 0X80078
2 sensor lines max. 2.5 mm² 1 x threaded plug M20

Note: Connection and termination kits are not included in the ELAK-Ex-R-system. Please place a separate order for these items which depend on the
type of heating cable used.

www.eltherm.com 7.33
Junction Box
for Hazardous Areas
This junction box ELAK-Ex-3 in conventional design is suitable for use in potentially explosive atmosphere in ac-
cordance with Ex-guidelines 94/9/CE (ATEX 95). Moreover, the unit ELAK-Ex-3 covers a significantly wide range of
ambient temperatures as shown on the data sheet. The junction box can be wall-mounted and is also available
with stands for mounting on pipes.

Advantages: Applications:
Covers a wide range of temperatures Hazardous areas
Suited for mounting on pipes Chemical & petrochemical industries
Power stations
Industrial plants with a need for frost protection
or temperature maintenance

Type ELAK-Ex-3

7.34 Heat Tracing in Hazardous Areas


Technical Information Type ELAK-Ex-3
Data
Classification II 2G Ex e IIC T6...T4 Gb
II 2D Ex tb IIIC T80 °C Db
Certificate EPS13 ATEX 1506X,
IECEx EPS 13.0002
Standards EN 60079-0:2009, EN 60079-7:2007,
EN 60079-31:2009
Ambient temperature -40 °C up to +50 °C (T6, T85 °C)
-40 °C up to +55 °C (T5, T100 °C)
-40 °C up to +60 °C (T4, T100 °C)
Nominal current See type plate, max. 36 A
Nominal voltage See type plate, max. 550 V
Terminals Min. 0,5 mm², max. 10 mm²
(except ELAK-Ex-3.8)
Enclosure Polyester
Dimensions (approx.) l x h x d 122 x 120 x 90 mm
Impact resistance 7 Joule
Cable glands Polyamide
IP rating IP65 / 66 depending on design The ELAK-Ex-3 unit fitted with the mounting stand ELMW-9
Weight Approx. 1 kg (122 x 120 – Art. No. 0941009) is also suited for mounting on
pipes. The mounting stand is 100 mm high.
Type of mounting Wall-mounting

Type Application Features Art. No.

ELAK-Ex-3.1 Star point for ELK-AG-... 3 x M12 (3-6 mm), 35 A, 1 x threaded plug M25 0X80051
Two-phase heating circuit or as star-supply box
ELAK-Ex-3.2 1 x M25 (9-17 mm), 2 x M12 (3-6 mm), 1 x sealing plug M12 0X80052
for ELK-AG-...
ELAK-Ex-3.4 Supply: 1 heating cable ELK-AG-...+ EL-CTB 2 x M25 (9-17 mm), 2 x M12 (3-6 mm) 0X80054

ELAK-Ex-3.5 Supply: 1 heating cable ELSR-... + EL-CT 122 x 120 x 90 mm, polyester enclosure, for ELSR + EL-CT, Ex e 0X80055

ELAK-Ex-3.7 Supply: 1-3 heating cable ELSR-... 1 x M25 (9-17 mm), 2 x threaded plug M25, 1 x bore hole M25 0X80057

Supply 1-2 Pt100, 2-4 wire + up to 2 conductors 1 x M25 (9-17 mm), 1 x threaded plug M25, 1 x M12 (3-6 mm),
ELAK-Ex-3.8 0X80058
+ up to 2 sensor lines max 2.5 mm² 2 x sealing plug M12

Note: Connection and termination kits are not included in the ELAK-Ex-3-system. Please place a separate order for these items which depend on the
type of heating cable used.

www.eltherm.com 7.35
Ex-Con
Splice Connector Kit
This splice connector kit for eltherm heating cables was developed especially for the application in hazardous
areas. The Ex-Con 22/4 provides a special feature as it is applicable in temperature ranges up to -60°C. In doing
so, our engineers focused on a high level of safety, simple installation and perfect fit.

Advantages: Applications:
Cold and dry termination Chemical & petrochemical industry
Simple installation Oil & gas industry
No restriction to eltherm branded Paints & varnishes
heating cables Heat tracing of apparatus, appliances & plants
Heat tracing of pipes, pumps & valves

Type Ex-Con

7.36 Heat Tracing in Hazardous Areas


Technical Information Type Ex-Con
Data
Classification II 2G Ex e IIC T6…T3 Gb
II 2D Ex tb IIIC TX Db
Certificate 04ATEX1005X , 07ATEX1080X,
07ATEX1023X, IECEx IBE 13.0012 X
Standard EN 60079-0:2009,
EN 60079-7:2007,
EN 60079-31:2009

Maximum maintenance temperature (Ex-Con-22/4 & -25/7) Example: assembled unit


Type up to 10 A up to 16 A up to 20 A

T6 60 °C 45 °C 25 °C
T5 75 °C 60 °C 40 °C
T4 110 °C 95 °C 75 °C
T3 170 °C 155 °C 135 °C

Classification Impact Nominal Rated Operating


Diameter Length
for Cable cross section resistance current voltage temperature Art. No.
(mm) (mm)
ELKM AG (J) (A) (V) (°C)
Ex-Con-22/4-Si Up to 2.5 mm² 4 20 550 22 x 120 105 -60 up to 200 0X81140
Ex-Con-25/7 Up to 2.5 mm² 7 20 550 25 105 -32 up to 200 0X81115
Ex-Con-36/4* 2.5 mm² up to 35 mm² 4 145 550 36 175 -32 up to 200 0X81120

* Electric current / operating temperatures: Please refer to separate instruction.

Impact Nominal Rated Operating


Classification Diameter Length
Cable cross section resistance current voltage temperature Art. No.
for ELSR (mm) (mm)
(J) (A) (V) (°C)
3 x 1.5 mm²
Ex-Con-SR 4 145 240 (550) 36 210 -32 up to 200 0X81125
and 3 x 2.5 mm²

www.eltherm.com 7.37
Connection Kits
for Self-regulating Heating Cables
and Constant Wattage Heating Cables
These connection kits for self-regulation heating cables and constant wattage heating cables have been specially
developed for use in hazardous areas, Ex e.

Advantages: Applications:
Easy termination Pipe heating
Time-saving Frost protection for industrial plants
Hazardous areas
Chemical and petrochemical plants
Oil and gas industry
Container and tanks
Food industry

ELVB-SR…Ex-… / ELVB-ELPEx-25

ELVB-SREx-25

7.38 Heat Tracing in Hazardous Areas


Technical Information
Data
Classification III 2G Ex e IIC Gb II 2D Ex tb IIIC Db
II 2G Ex db e IIC Gb II 1D Ex ta IIIC Da ELVB-SRAN-Ex-20 / ELVB-SRAL-Ex-20
(ELVB.SRA…-Ex-20)
Directives EN 60079-7, -31; IEC 60079-7, -31;
IEEE 515 + CSA 130-3
EN 60079-7, -31, IEC 60079-7, -31
(ELVB-ELPEx-25)
Permissible ambient -55 °C up to +70 °C
temperature (in case of protected installation)
-25 °C up to +70 °C (in case of higher
grade of mechanical stress)
ELVB-SRA…-Ex: -60 °C up to +80 °C
ELVB-ELPEx-25: -25 °C up to +70 °C
(in case of higher grade of mechanical stress), ELVB-SRAH-Ex-20
-55 °C up to +70 °C
(in case of protected installation)
Certificates IBExU07ATEX1022X
ELVB-SRA...-Ex-20: SIRA01ATEX1270X
ELVB-ELPEx-25: IBExU07ATEX1022X

ELVB-SREx-IT ELVB-ELPEx-25

Type Cable glands Glue Suitable for Art.-No.

Silicone glue „LT“, 5 g tube,


ELVB-SREx-25 M25 x 1.5 PE gland (black) ELSR-N, -LS, -H, -FHP 0X81PA1
blue screw cap, transparent glue

Silicone glue „LT“, 5 g tube, ELSR-N, –H for Mounting


ELVB-SREx-IT 091AIT1
blue screw cap, transparent glue post Ex-it-R

Silicone glue „LT“, 5 g tube,


ELVB-SRAN-Ex-20 M20, brass ELSR-N, -FHP 0X81PND
blue screw cap, transparent glue

Silicone glue „LT“, 5 g tube,


ELVB-SRAL-Ex-20 M20, brass ELSR-LS 0X81PLD
blue screw cap, transparent glue

Silicone glue „HT“, 5 g tube,


ELVB-SRAH-Ex-20 M20, brass ELSR-H 0X81PHD
red screw cap, red glue

ELVB-ELPEx-25 M25, PE gland (black) - ELP-PFA 0X81EP2

All articles including termination instruction.

www.eltherm.com 7.39
End Termination Kits
for Self-regulating Heating Cables
and Constant Wattage Heating Cables
These end termination kits for self-regulating heating cables and constant wattage heating cables have specially
been developed for use in hazardous areas.
We offer several custom-fit end termination kits for our low temperature and a special kit for our high tempera-
ture heating cables, and a kit suitable for our constant wattage heating cable ELP-PFA.

Advantages: Applications:
Easy termination Pipe heating
Time-saving Frost protection for industrial plants
Hazardous areas
Chemical and petrochemical plants
Oil and gas industry
Container and tanks
Food industry

Type EL-ECN/L/H/P-Ex

7.40 Heat Tracing in Hazardous Areas


Technical Information
Data
Classification II 2G Ex e IIC Gb II 2D Ex tb IIIC Db
EL-ECN-Ex:
Directives EN 60079-7, -31; IEC 60079-7, -31;
IEEE 515 + CSA 130-3
Permissible ambient -45 to 85 ° C, EL-ECN-Ex
temperature -45 to 85 ° C, EL-ECL-Ex
-40 to 210 ° C, EL-ECH-Ex
Certificates IECEx IBE 12.0001U, 05ATEX1154U

EL-ECH-Ex:

EL-ECL-Ex: EL-ECP-Ex:

Type End cap Glue Suitable for Art.-No.

Silicone glue „LT“, 5 g tube,


EL-ECN-Ex Silicone, transparent, with Ex-imprint ELSR-N up to 80 °C 0X81EN1
blue screw cap, transparent glue

Silicone glue „LT“, 5 g tube,


EL-ECL-Ex Silicone, transparent, with Ex-imprint ELSR-LS up to 80 °C 0X81EL1
blue screw cap, transparent glue

Silicone glue „HT“, 5 g tube,


EL-ECH-Ex Silicone, red, with Ex-imprint ELSR-H up to 210 °C 0X81EH1
red screw cap, red glue

Silicone glue „HT“, 5 g tube,


EL-ECP-Ex Silicone, red, with Ex-imprint ELP-PFA bis 210 °C 0x81EP1
red screw cap, red glue

All articles including termination instruction.

www.eltherm.com 7.41
ELSR: Application in Hazardous Areas
Temperature Controller
Pipe Ex-Box REG/DIS
Mounting Ex-it-R
Fitting Insulation Junction Box
Temperature
Bushing Sensor
ELTF-PTEx Termination Kit
EL-EC-H-Ex

Ex-Con-SR
Warning Sign Bushing Mechanical
Fastener
Self-adhesive
Tape

Products:
Heating Cable ELSR-N, ELSR-LS, ELSR-H
Measurement and Control, e. g. Ex-Box Temperature Controller
Temperature Sensor ELTF-PTEx
Connection Kits, e. g. Ex-Con-SR (or ELVB...Ex...)
Junction Boxes, e. g. Ex-it-R (or ELAK-Ex-...)
Termination Kits EL-EC...ex
Insulation Bushings ELISD-...
Mechanical Fasteners and/or Self-adhesive Tapes and Foil ELB-...
Pipe Mounting Fittings ELMW-..., ELB-...
Warning Signs EL-WS...

Remark: This is just a schematic overview, not an installation instruction.


For detailed information, please contact our engineers.

7.42 Heat Tracing in Hazardous Areas


EHT in Hazardous Areas
Limiter Temperature Controller
Temperature Ex-Box REG/DIS
Ex-Box LIM/DIS
Controller Limiter
Ex-Box REG/DIS Ex-Box LIM/DIS
Pipe Mounting
Fitting
Insulation Splice Connector Temperature
Bushing Kits Ex-Con Sensors ELTF-PTEx

Warning Sign Temperature


Sensors ELTF-PTEx

Self-adhesive Splice Connector


Tape and Foil Kits Ex-Con

Products:
Resistance Heating Cable ELK-...
Temperature Controller e. g. Ex-Box-REG-DIS
Limiter, e. g. Ex-Box-LIM -DIS
Temperature Sensor ELTF-PTEx
Splice Connector Kits Ex-Con-...
Insulation Bushings ELISD-...
Mechanical Fasteners and/or Self-adhesive Tapes and Foil ELB-...
Pipe Mounting Fittings ELMW-..., ELB-...
Warning Signs EL-WS...

Remark: This is just a schematic overview, not an installation instruction.


For detailed information, please contact our engineers.

www.eltherm.com 7.43
160623_07_EX_EN – Subject to change without notice

eltherm GmbH Your reliable partner worldwide:


Headquarters / Production site
eltherm UK Ltd. www.eltherm.uk.com
Ernst-Heinkel-Straße 6 -10 eltherm Spain, S.L.U. www.eltherm.es
57299 Burbach, Germany eltherm Asia-Pacific Pte Ltd. www.eltherm-ap.com
eltherm (Shanghai) Co., Ltd. www.eltherm-ap.com
Phone +49 (0) 27 36/44 13-0 eltherm Canada Inc. www.eltherm.ca
Fax +49 (0) 27 36/44 13-50 eltherm South Africa (Pty) Ltd. www.eltherm.co.za
E-Mail [email protected]
Web www.eltherm.com

innovations in heat tracing

You might also like