Electrical Heat Tracing: in Hazardous Areas
Electrical Heat Tracing: in Hazardous Areas
in Hazardous Areas
1. Heating Cables
eltherm participates in international committees which define the worldwide standards of Electrical
Heat Tracing:
IEC 60079-30-1 (international):
Explosive atmospheres – Part 30-1: Electrical resistance trace heating – General and testing requirements
IEC 60079-30-2 (international):
Explosive atmospheres – Part 30-2: Electrical resistance trace heating – Application guide for design, instal-
lation and maintenance
IEC 62395-1 (international):
Electrical resistance trace heating systems for industrial and commercial applications
IEEE 515 (US):
IEEE Standard for the Testing, Design, Installation, and Maintenance of Electrical Resistance Heat Tracing for
Industrial Applications
www.eltherm.com 7.03
Heating Cable
Self-regulating
The versatile self-regulating heating cable ELSR-N is suited for frost protection and temperature maintenance in
the low temperature range of industrial applications. Likewise it is approved for use in hazardous areas. The BOT
version of this heating cable even withstands aggressive chemicals, oil and fuel and, thanks to this high chemical
resistance, stands out for a long lifetime.
Advantages: Applications:
Self-regulating Frost protection
Four nominal outputs Heat tracing on level indicators
Can be cut to length off the roll Chemical & petrochemical industries
Moisture proof Tank bottom heating of LNG storage tanks
UV-resistant Pipe heat tracing
Approved for use in hazardous areas Vessels and tanks
Automotive
Food processing industry
Type ELSR-N up to 80 °C
Protective braid
Cu, tin plated
Self-regulating
Bus wire heating Outer jacket
Insulation
1.23 mm2 element
www.eltherm.com 7.05
Heating Cable Light 'Super'
Self-regulating
The versatile self-regulating heating cable ELSR-LS is our ‘light’ version for temperatures up to 80 °C. This heating
cable is also suited and approved for use in hazardous areas. Since eltherm® self-regulating cables can be cut off
the roll to the desired length, the application cable is highly flexible to match our customer’s needs. Its long life
span guarantees for the efficient use in many industrial sectors.
Advantages: Applications:
Self-regulating Pipe heat tracing
Four nominal outputs Frost protection for industrial applications
Can be cut to length off the roll Temperature maintenance for pipes and vessels
Moisture proof Chemical & petrochemical industries
UV-resistant Paints & varnishes
Small dimensions Automotive
Food processing industry
Type ELSR- LS up to 80 °C
Protective braid
tinned copper
ELS
R-L
Certificates 12ATEX1431U 20 S-2
5-2
IECEx EPS 12.0006U ELS
15 R-L
S-1
5-2
10
Heating circuit lengths ELSR- LS -…-2 on the following conditions ELSR
-LS-1
5 0-2
230 V nominal voltage
Delayed action circuit breakers (C-characteristic) with 80 % maximum load
Maximum 10 % line voltage drop on the heating cable bus wire – 30 – 20 – 10 0 10 20 30 40 50 60
Pipe temperature [°C]
Power connection to one (1) heater end
www.eltherm.com 7.07
Heating Cable High Temp.
Self-regulating
The versatile self-regulating heating cable ELSR-H is for high temperatures up to 210 °C in
a large number of industrial applications. It is also suited and approved for use in hazard-
ous areas. The BOT version of this heating cable even withstands aggressive chemicals,
oil and fuel and, thanks to this high chemical resistance, stands out for a long life span.
Advantages: Applications:
Up to 120 °C/210 °C Chemical & petrochemical industries
Self-regulating Oil & gas industry
Six nominal outputs Power plants
Can be cut to length off the roll Ex-areas
Moisture proof Frost protection
Resistant to chemicals Water & sanitation utilities
Approved for use in hazardous areas Temperature maintenance on vessels, pipes & valves
Certificates 12ATEX1429U 30
ELSR
IECEx EPS 12.0004U -H-30
Switch-on Nominal Heating circuit length (m) for ELSR-H- Dimen- Weight
tempera- cutout Nominal sions
Type approx. Art. No.
ture value (A) 10-2 15-2 20-2 30-2 45-2 60-2 75-2 output approx.
(mm) (g/m)
16 193.0 158.0 122.0 82.0 55.0 41.0 33.0 ELSR-H-10-2-BOT 10 W/m at 10 °C 12.4 x 5.0 120 B0221103
20 193.0 158.0 136.0 102.0 68.0 51.0 41.5
10 ELSR-H-15-2-BOT 15 W/m at 10 °C 12.4 x 5.0 120 B0221153
25 193.0 158.0 136.0 111.0 85.0 64.0 51.5
32 193.0 158.0 136.0 111.0 91.0 79.0 66.0 ELSR-H-20-2-BOT 20 W/m at 10 °C 12.4 x 5.0 120 B0221203
16 189.0 153.0 116.0 77.0 52.0 39.0 30.0
ELSR-H-30-2-BOT 30 W/m at 10 °C 12.4 x 5.0 120 B0221303
20 189.0 153.0 132.0 97.0 65.0 49.0 37.5
0
25 189.0 153.0 132.0 108.0 81.0 61.0 47.0 ELSR-H-45-2-BOT 45 W/m at 10 °C 12.4 x 5.0 120 B0221453
32 189.0 153.0 132.0 108.0 88.5 77.0 60.0 ELSR-H-60-2-BOT 60 W/m at 10 °C 12.4 x 5.0 120 B0221603
16 184.0 146.0 110.0 73.0 50.0 37.0 28.5 ELSR-H-75-2-BOT 75 W/m at 10 °C 12.4 x 5.0 120 B0221753
20 1840. 148.5 129.0 92.0 62.0 46.0 35.5
-10
25 1840. 148.5 129.0 105.5 77.0 58.0 44.5
32 184.0 148.5 129.0 105.5 86.5 70.0 57.0
16 180.0 139.0 104.0 70.0 47.0 36.0 26.5
20 180.0 145.0 125.5 87.0 59.0 44.0 33.5
-20
25 180.0 145.0 125.5 103.0 74.0 56.0 41.5
32 180.0 145.0 125.5 103.0 84.5 67.0 53.5
16 173.0 126.0 95.0 64.0 43.0 33.0 23.5
20 173.0 138.0 119.0 80.0 54.0 41.0 29.0
-40
25 173.0 138.0 120.0 98.0 68.0 51.0 36.5
32 173.0 138.0 120.0 98.0 81.0 61.0 46.5
www.eltherm.com 7.09
Constant Wattage Heating Cable
with Resistance Wire
These parallel heating cables offer tremendous flexibility in use, as they can easily be cut to the required length off
the roll, with the assurance of constant power output. There is no need for a connecting cable and input can be
unilateral. It is quick and easy to assemble; this saves a lot of time, and reduces costs considerably as a result. Since
output of up to 60 W/m is possible for lengths laid to piping, ELP parallel heating cables are particularly suitable
for piping with high output requirements such as in industrial process technology. The particularly temperature-
resistant outer shell in PFA and the high level of chemical resistance of the PFA ensure a long useful life.
Advantages: Applications:
Single end power input Vessels, piping, valves
Can be cut off the roll Building construction
Constant power output per meter Food processing industry
Long life cycle Paper industry
Laying without exact measuring possible
High chemical resistance
UV resistance
Bus wire
Heating zone 1m
Contact point Contact point Contact point L
www.eltherm.com 7.11
PTFE insulated Heating Cable
with Protective Braid + Outer Jacket
This versatile heating cable is used for frost protection and temperature maintenance, even under highly corro-
sive environmental conditions. The heating cable ELKM-AG-N is suited and approved for use in hazardous areas.
It is highly flexible permitting its use in many fields of application.
Impact resistance 4 Joule For suitable connection and termination kits please note our
considerable accessories catalogue unit.
Heat conductor Stranded
Nominal Outer diame- Weight Temperature Nominal Outer diame- Weight Temperature
resistance ter approx. approx. coefficient Art. No. resistance ter approx. approx. coefficient Art. No.
(Ω/km) (mm) (g/m) (x 10 -3 / K) (Ω/km) (mm) (g/m) (x 10 -3 / K)
1.95 8.1 166 4.30 01TA002E 280.00 4.0 39 0.38 01TA128E
(Cu 10 mm2)
2.90 328.00 4.1 40.1 0.45 01TA132E
(Cu 6 mm2) 6.8 119 4.30 01TA003E
360.00 3.9 40 0.45 01TA136E
4.40
(Cu 4 mm2) 6.1 96 4.30 01TA004E 430.00 4.1 43 0.18 01TA143E
7.20 480.00 4.1 44 0.18 01TA148E
(Cu 2.5 mm2) 5.1 64 4.30 01TA007E
10.00 4.8 59 4.30 01TA010E 600.00 4.0 40 0.18 01TA160E
11.70 800.00 3.9 41 0.18 01TA180E
(Cu 1.5 mm2) 4.7 57 4.30 01TA011E
1000.00 4.0 43 0.04 01TA210E
15.00 4.5 50 4.30 01TA015E
1470.00 3.8 40 0.04 01TA214E
25.00 4.4 48 3.00 01TA025E
1750.00 3.8 37 0.04 01TA217E
31.50 4.7 56 1.60 01TA031E
1900.00 3.5 41 0.40 01TA219E
50.00 4.4 49 1.60 01TA050E
2900.00 3.9 41 0.40 01TA229E
65.00 4.2 46 1.60 01TA065E
4000.00 3.8 37 0.40 01TA240E
80.00 4.5 42 0.90 01TA080E
4700.00 3.8 35 0.15 01TA247E
100.00 4.4 50 0.90 01TA110E
6000.00 3.8 34 0.20 01TA260E
157.00 4.4 46 0.45 01TA115E
7000.00 3.8 33 0.15 01TA270E
180.00 4.1 42 0.90 01TA118E
8000.00 3.8 36 0.15 01TA280E
200.00 4.2 38 0.45 01TA120E
260.00 4.1 42 0.45 01TA126E For applications with fixed external diameter, please contact our engi-
neers first.
Weight tolerances are possible for manufacturing reasons.
Nominal resistances up to 1,500,000 Ω/km upon request. Cables shall neither intersect nor contact.
Resistance tolerance: +/- 5 %. Provide protection by means of circuit breaker FI 30mA.
Please observe the standards EN 60079-30-2, EN 60519-10.
www.eltherm.com 7.13
Heating Cable
Highly robust
Factory terminated heating cable, suitable for use in overpressure and vacuum applications. Can be used as radiant
heating with high output density. This heating cable is approved for use in hazardous areas. We provide engi-
neering services from initial design up to turnkey project execution. Complete engineering up to commissioning.
Laser welding technology enables us to provide high precision, safe and reliable MI connections.
Heating conductor
Resistance *Note: The output per meter of heating cable and the maximum pos-
No. Diameter = mm sible operating temperatures depend on the respective application.
Ω/km
For individual cases, we recommend that you contact our engineers –
1 3.20 10.000 we will be pleased to advise you.
2 3.20 6.300
This is just a summary of all available resistances. For further resistances,
3 3.20 4.000 please contact us.
4 3.40 2.500
5 3.60 1.600
6 3.90 1.000
A table of chemical resistances is available on our website
7 4.30 630
www.eltherm.com.
8 4.70 400
Other cross sections and lengths of cold leads are available
9 5.30 250 upon request.
10 6.50 160
www.eltherm.com 7.15
Ex-Box Temperature Controller
with Display
Ex-Box REG/DIS: Complying with latest Ex-protection directives 94/9/CE (ATEX 95) this electronic temperature
controller has been designed and developed especially for its use in hazardous areas. Programming and opera-
tion is done via the integrated operating panel with display.
Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Operation and programming in hazardous area Power plants
Increased safety through fail alarm Chemical & petrochemical
Integrated heating circuit monitoring industries
www.eltherm.com 7.17
Ex-Box Temperature Controller
with LED-Display
Ex-Box REG/LED: Complying with latest Ex-protection directives 94/9/CE (ATEX 95) this electronic temperature
controller has been designed and developed especially for its use in hazardous areas. Programming and opera-
tion is done via external Ex-Control manual control.
Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Increased safety, tamperproof, no unautho- Power plants
rised adjustments
Chemical & petrochemical
. Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants
www.eltherm.com 7.19
Ex-Box Limiter
with Display
The Ex-Box LIM/DIS is a limiter for switching off heating circuits in case of excess temperature or current overload.
Furthermore, output signal values for maximum and minimum temperatures are programmable. Programming
and operation is done via the integrated operating panel with display.
Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Operation and programming Power plants
in hazardous areas
Chemical & petrochemical
Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Display
Pharmaceutical industry
Plastics industry
Wastewater treatment plants
For suitable temperature sensors and accessories please note our consi-
derable accessories catalogue unit.
www.eltherm.com 7.21
Ex-Box Limiter
with LED-Display
The Ex-Box LIM/LED is a limiter for switching off connected heating circuits in case of excess temperature or
current overload. Furthermore, signal values for maximum and minimum temperatures are programmable.
Programming and operation is done via external panel Ex-Control for manual control.
Advantages: Applications:
Rugged enclosure IP 65 Hazardous areas
Increased safety against unauthorised Power plants
changes of rated value
Chemical & petrochemical
Increased safety through fail alarm
industries
Integrated heating circuit monitoring
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants
For suitable temperature sensors and accessories please note our consi-
derable accessories catalogue unit.
www.eltherm.com 7.23
Ex-Control
Hand-held Controller Pad
Intrinsically safe hand held controller pad for use with the Ex-Box REG/LED and LIM/LED. The Ex-Control pad pro-
vides additional safety in a potentially explosive atmosphere. Adjustment of settings by unauthorized persons is
not possible since the controller can be removed.
Advantages: Applications:
Intrinsically safe controller pad Hazardous areas
Without an independent power supply Power plants
Programming and operation in hazardous
Chemical & petrochemical
areas
industries
Oil & gas industries
Pharmaceutical industry
Plastics industry
Wastewater treatment plants
Type Ex-Control
Ex-Control 0X60026
www.eltherm.com 7.25
Ex-Capillary
Thermostat
The capillary thermostat EL-CT is approved for use in hazardous areas Zones 1 and 2 for gas and Zones 21 and
22 for dust as a surface thermostat on pipes and vessels. There are different temperature ranges possible. The
material of the capillary tube is stainless steel and the rugged enclosure is made of aluminium.
Advantages: Applications:
Robust Industrial applications
Versatile use Use in hazardous areas
Heat tracing on pipes,
valves and vessels
Oil & gas industry
Type EL-CT
Admissible sensor
Designation Temperature range Art. No.
temperature, max.
EL-CT(2) 30 -10 °C up to +30 °C 60 °C 0X63032
EL-CT(2) 65 +5 °C up to +65 °C 100 °C 0X63065
EL-CT(2) 180 0 °C up to +180 °C 220 °C 0X63180
EL-CT(2) 320 +50 °C up to +320 °C 330 °C 0X63320
EL-CT 30 -50 °C up to +30 °C 50 °C 0X63030
EL-CT 50 0 °C up to +50 °C 105 °C 0X63050
EL-CT 200 0 °C up to +200 °C 230 °C 0X63200
EL-CT 500 +20 °C up to +500 °C 575 °C 0X63500
www.eltherm.com 7.27
ELTF-PTEx
Temperature Sensor
This temperature sensor has been designed according to Ex standard 94/9/EG especially for use in explosive gas
and dust atmosphere. An emphasis on safety, simple installation and fitting accuracy were the requirements that
our development engineers met.
Advantages: Applications:
Impact protection (U-profile) for sensor Hazardous areas
protection Power plants
Strain relief by hexagon-swaging Chemical and petrochemical plants
Bend protection Oil and gas industry
Decrease of parasitic coupling from Varnish and paint
surrounding electrical components Heating of instruments, devices and plants
because of fluoropolymer shielded Pipe, pump and valve heating
sensor cable
Type ELTF-PTEx
Length connecting
Type Temperature sensor Impact resistance (J) Art.-No.
cable (m)
ELTF-PTEx.2 Pt100 4-conductors 7 3 0X70002
Double - Pt100
ELTF-PTEx.4 7 3 0X70030
3-conductors
www.eltherm.com 7.29
Junction Box, Round,
with Mounting Stand
On-pipe Mounting in Hazardous Areas
The innovative junction box ELAK-Ex-R with mounting bracket (Ex-it) is suitable for use in potentially explosive at-
mosphere in accordance with Ex-guidelines 94/9/CE (ATEX 95) and provides a number of advantages. Thanks to
the shape of the box, for instance, it is not necessary to strongly bend the inserted cable thereby avoiding cable
damage. Due to the incorporated mounting bracket there is no need to provide angle irons. This is especially
advantageous to heat tracing on piping because the cable can directly be introduced via the mounting bracket.
Furthermore, fastening screws for heating lines and sensors are not required. A safety locking, with appropriate
tool included, prevents the cover to move. Additional features permitting the attachment of sign plates facilitate
easy identification of heating circuits in complex systems.
Advantages: Applications:
No static charge Hazardous areas
Rapid closing of the cover through Chemical & petrochemical industries
snap fit, no tool required Power stations
Increased mechanical safety through Industrial plants with a need for frost protection
round shape or temperature maintenance
Permits fixing of customer identification
plates
Up to 3 heating cables can be connected
Type Ex-it-R
Junction box, with mounting feet, round, dia. 150 mm, height 125 mm, polyamide enclosure, to connect 3 self-regulating
Ex-it-R 0X80070
heating cables ELSR-N/-H, 1 connecting cable, 1 sensor cable, 1 double-Pt100, insulating thickness max. 100 mm
T-branch, with mounting feet, round, dia.150 mm, height 125 mm, polyamide enclosure, to connect up to 3 self-regulating
Ex-it-R-T 0X80082
heating cables ELSR-N/-H, insulating thickness max.100 mm
Junction box, with mounting feet, round, dia. 150 mm, height 125 mm, polyamide enclosure, to connect 1 double-Pt100, 1
Ex-it-R-Pt 0X80092
sensor cable, insulating thickness max. 100 mm
Note: Connection and termination kits are not included in the Ex-it-R system. Please place a separate order for these items which depend on the type
of heating cable used.
www.eltherm.com 7.31
Junction Box, Round
for Hazardous Areas
The innovative junction box ELAK-Ex-R is suitable for use in potentially explosive atmosphere in accordance with
Ex-guidelines 94/9/CE (ATEX 95). Thanks to its exceptional shape it provides a number of advantages. Due to
the form of the box, for instance, it is not necessary to strongly bend the inserted cable thereby avoiding cable
damage.
A safety lock, with appropriate tool included, prevents the cover from moving. Additional features permitting
the attachment of sign plates facilitate easy identification of heating circuits in complex systems. Suited for wall-
mounting.
Advantages: Applications:
No static charge Hazardous areas
Rapid closing of the cover through Chemical & petrochemical industries
snap fit, no tool required Power stations
Increased mechanical safety through Industrial plants with a need for frost protection
round shape or temperature maintenance
Permits fixing of customer identification
plates
Up to 3 heating cables can be connected
Type ELAK-Ex-R
ELAK-Ex-R1 Star point for ELK-AG-... 3 x M16 (4-9 mm), 1 x threaded plug M20, 1 x threaded plug M25 0X80071
Two-phase heating circuit or as star-supply box 2 x M16 (4-9 mm), 1 x M25 (8-17 mm),
ELAK-Ex-R2 0X80072
for ELK-AG-... 1 x threaded plug M16, 1 x threaded plug M20
ELAK-Ex-R4 Supply: 1 heating cable ELK-AG-... + EL-CT 2 x M16 (4-9 mm), 2 x M25 (8-17 mm) 0X80074
ELAK-Ex-R5 Supply: 1 heating cable ELSR-... + EL-CT dia. 150 mm, height 125 mm, polyamide enclosure, for ELSR + EL-CT, Ex e 0X80075
ELAK-Ex-R7 Supply: 1-3 heating cable ELSR-... 1 x M25 (8-17 mm), 2 x threaded plug M25, 1 x Bohrung M25 0X80077
Supply: 1-2 Pt 100, 2-4 conductors + up to 1 x M25 (8-17 mm), 1 x M16 (4-9 mm), 2 x threaded plug M16,
ELAK-Ex-R8 0X80078
2 sensor lines max. 2.5 mm² 1 x threaded plug M20
Note: Connection and termination kits are not included in the ELAK-Ex-R-system. Please place a separate order for these items which depend on the
type of heating cable used.
www.eltherm.com 7.33
Junction Box
for Hazardous Areas
This junction box ELAK-Ex-3 in conventional design is suitable for use in potentially explosive atmosphere in ac-
cordance with Ex-guidelines 94/9/CE (ATEX 95). Moreover, the unit ELAK-Ex-3 covers a significantly wide range of
ambient temperatures as shown on the data sheet. The junction box can be wall-mounted and is also available
with stands for mounting on pipes.
Advantages: Applications:
Covers a wide range of temperatures Hazardous areas
Suited for mounting on pipes Chemical & petrochemical industries
Power stations
Industrial plants with a need for frost protection
or temperature maintenance
Type ELAK-Ex-3
ELAK-Ex-3.1 Star point for ELK-AG-... 3 x M12 (3-6 mm), 35 A, 1 x threaded plug M25 0X80051
Two-phase heating circuit or as star-supply box
ELAK-Ex-3.2 1 x M25 (9-17 mm), 2 x M12 (3-6 mm), 1 x sealing plug M12 0X80052
for ELK-AG-...
ELAK-Ex-3.4 Supply: 1 heating cable ELK-AG-...+ EL-CTB 2 x M25 (9-17 mm), 2 x M12 (3-6 mm) 0X80054
ELAK-Ex-3.5 Supply: 1 heating cable ELSR-... + EL-CT 122 x 120 x 90 mm, polyester enclosure, for ELSR + EL-CT, Ex e 0X80055
ELAK-Ex-3.7 Supply: 1-3 heating cable ELSR-... 1 x M25 (9-17 mm), 2 x threaded plug M25, 1 x bore hole M25 0X80057
Supply 1-2 Pt100, 2-4 wire + up to 2 conductors 1 x M25 (9-17 mm), 1 x threaded plug M25, 1 x M12 (3-6 mm),
ELAK-Ex-3.8 0X80058
+ up to 2 sensor lines max 2.5 mm² 2 x sealing plug M12
Note: Connection and termination kits are not included in the ELAK-Ex-3-system. Please place a separate order for these items which depend on the
type of heating cable used.
www.eltherm.com 7.35
Ex-Con
Splice Connector Kit
This splice connector kit for eltherm heating cables was developed especially for the application in hazardous
areas. The Ex-Con 22/4 provides a special feature as it is applicable in temperature ranges up to -60°C. In doing
so, our engineers focused on a high level of safety, simple installation and perfect fit.
Advantages: Applications:
Cold and dry termination Chemical & petrochemical industry
Simple installation Oil & gas industry
No restriction to eltherm branded Paints & varnishes
heating cables Heat tracing of apparatus, appliances & plants
Heat tracing of pipes, pumps & valves
Type Ex-Con
T6 60 °C 45 °C 25 °C
T5 75 °C 60 °C 40 °C
T4 110 °C 95 °C 75 °C
T3 170 °C 155 °C 135 °C
www.eltherm.com 7.37
Connection Kits
for Self-regulating Heating Cables
and Constant Wattage Heating Cables
These connection kits for self-regulation heating cables and constant wattage heating cables have been specially
developed for use in hazardous areas, Ex e.
Advantages: Applications:
Easy termination Pipe heating
Time-saving Frost protection for industrial plants
Hazardous areas
Chemical and petrochemical plants
Oil and gas industry
Container and tanks
Food industry
ELVB-SR…Ex-… / ELVB-ELPEx-25
ELVB-SREx-25
ELVB-SREx-IT ELVB-ELPEx-25
www.eltherm.com 7.39
End Termination Kits
for Self-regulating Heating Cables
and Constant Wattage Heating Cables
These end termination kits for self-regulating heating cables and constant wattage heating cables have specially
been developed for use in hazardous areas.
We offer several custom-fit end termination kits for our low temperature and a special kit for our high tempera-
ture heating cables, and a kit suitable for our constant wattage heating cable ELP-PFA.
Advantages: Applications:
Easy termination Pipe heating
Time-saving Frost protection for industrial plants
Hazardous areas
Chemical and petrochemical plants
Oil and gas industry
Container and tanks
Food industry
Type EL-ECN/L/H/P-Ex
EL-ECH-Ex:
EL-ECL-Ex: EL-ECP-Ex:
www.eltherm.com 7.41
ELSR: Application in Hazardous Areas
Temperature Controller
Pipe Ex-Box REG/DIS
Mounting Ex-it-R
Fitting Insulation Junction Box
Temperature
Bushing Sensor
ELTF-PTEx Termination Kit
EL-EC-H-Ex
Ex-Con-SR
Warning Sign Bushing Mechanical
Fastener
Self-adhesive
Tape
Products:
Heating Cable ELSR-N, ELSR-LS, ELSR-H
Measurement and Control, e. g. Ex-Box Temperature Controller
Temperature Sensor ELTF-PTEx
Connection Kits, e. g. Ex-Con-SR (or ELVB...Ex...)
Junction Boxes, e. g. Ex-it-R (or ELAK-Ex-...)
Termination Kits EL-EC...ex
Insulation Bushings ELISD-...
Mechanical Fasteners and/or Self-adhesive Tapes and Foil ELB-...
Pipe Mounting Fittings ELMW-..., ELB-...
Warning Signs EL-WS...
Products:
Resistance Heating Cable ELK-...
Temperature Controller e. g. Ex-Box-REG-DIS
Limiter, e. g. Ex-Box-LIM -DIS
Temperature Sensor ELTF-PTEx
Splice Connector Kits Ex-Con-...
Insulation Bushings ELISD-...
Mechanical Fasteners and/or Self-adhesive Tapes and Foil ELB-...
Pipe Mounting Fittings ELMW-..., ELB-...
Warning Signs EL-WS...
www.eltherm.com 7.43
160623_07_EX_EN – Subject to change without notice