GET8032C Spectra Switchboard
GET8032C Spectra Switchboard
GE Energy
®
Spectra Series Switchboards
Information provided is subject to change without notice. Please verify all details with GE. All values are design or
typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or
implied, that such performance will be obtained under end-use conditions.
GE Energy
41 Woodford Avenue, Plainville, CT 06062
www.geindustrial.com
© 2013 General Electric Company
Section 1 - Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Section 2 - Features and Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 3 - Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Section 4 - Sizing and Dimension
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2 Typical Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Class 1 Switchboard - Group Mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.4 Class 2 Individually Mounted Main Group Mounted Feeders/
Class 5 Individually Mounted Switchboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.5 Utility Metering Compartments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.6 Outdoor Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.7 Instrument and Metering Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.8 Busway Entrance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.9 Low Voltage Transition Sections and Dual Voltage Switchboards . . . . . . . . . . . . . . . . . . . 26
4.10 Conduit Entrance Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.11 Switchboard Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Section 5 - Application Data
5.1 Standards/Codes/Ratings/Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2 Protective Device Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.3 Power Break® II Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.4 WavePro™ Low Voltage Power Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.5 High Pressure Contact Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.6 Molded Case Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.7 Fusible Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.8 Surge Protective Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.9 Power Management Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.10 Power Metering Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.11 Equipment Ground Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.12 Automatic Transfer Switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.13 Wire/Lug/Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Section 6 - Additional GE Switchboard Offerings
Class 3 Switchboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Section 7 - CSI Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Reference Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Appendix
Seismic Compliance Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Trip Units by Main Breaker and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
1
Spectra Series® Switchboards
Section 1 – Introduction
Class 1
2
Spectra Series® Switchboards
Section 1 – Introduction
3
Spectra Series® Switchboards
Section 1 – Introduction
Class 3 Class 5
5
Spectra Series® Switchboards
Section 2 – Features and Characteristics
Spectra Plug-In
Isolated bus
support rails (2).
Field changes are quick and easy. Fusible switch and circuit breaker modules each consist
of two assemblies: the protective device (fusible switch
unit or molded case circuit breaker) and a connecting
mechanism. The connecting mechanisms are the inter-
mediate electrical/mechanical connections between the
protective device and the bus structure in the interior.
The fusible connecting mechanism is in the same
housing as the fusible switch unit. The molded case
circuit breaker connecting mechanism is separate from
the breakers and is designed to accept standard GE
circuit breakers.
6
Spectra Series® Switchboards
Section 2 – Features and Characteristics
Bus Bar
I
F = I (L x B)
where
F = Clamping Force
I = Current
L = Conductor Length
B= Electromagnetic Field
The circuit breaker mounting module has provisions for
bolting various breaker ratings in place and barriers to The spring-reinforced jaw clamps onto the interior bus and maintains
divert ionized gases away from line terminals of opposite the electrical connection. At short circuit, a strong electro-magnetic
devices on the same module. Both types of connector- field develops around the jaw. The resulting force increases the jaw
mounting modules are UL listed and CUL certified. pressure on the bus and maintains a secure connection. The design
creates current paths and generates clamping forces as shown in
the illustration.
7
Spectra Series® Switchboards
Section 2 – Features and Characteristics
Features
The main and utility CT compartments are designed to
offer maximum flexibility. Individually-mounted main is
available with Power Break II insulated case circuit
breakers, 800A-4000A; high pressure contact switches,
800A-4000A; fusible switches, 400A-1200A; WavePro
low voltage power circuit breakers, 800A-5000A; molded
case circuit breakers, including microEntelliGuard,
400A-1200A; and bolted pressure switches. (800 - 4000A).
Standard utility current transformer compartments have barriers
rear, top and bottom. Door has concealed hinges, three-point
catch, with lockable and sealable handle. Optional side barriers are
available. Current transformer compartments to meet other utility
requirements are available.
PCU units are available, allowing for motor starter Power Breaker II circuit breakers with EntelliGuard TU and
applications up to 15hp. (plug-in only) Power+ trip units are available as mains, submains, and ties
in switchboards.
8
Spectra Series® Switchboards
Section 3 – Terminology
Amp Setting, adjustable varies the continuous current- Class V-Individually mounted mains and feeders without
carrying ability of a breaker through a predetermined compartmentalization.
range.
Compartment is an area within a section that is so
Arcing Fault is a high-impedance connection caused constructed as to isolate devices in that compartment
by current flowing through air between two live from the surrounding area except for openings used
conductors. for interconnections, control or ventilation.
Arcing Time, in a fuse, is the amount of time that Compression Lug, also called a crimp lug, is a lug that
elapses between the melting of the current-responsive is crimped to hold cable.
element, such as a link, to the final circuit interruption.
Arcing time is dependent upon such factors as circuit Continuous Load is when the maximum current is
voltage and impedance. expected to continue for three hours or more.
Available Short-Circuit Current is the maximum rms Current Density is rated current divided by the cross-
(root-mean-square) symmetrical current at a given point section area of the conducting member (cable, bus bar,
in a power system, operating with maximum generating etc.) expressed in amps per square inch.
capacity and connected load, can deliver to any zero
impedance short circuit applied at that given point. Current Sensors internally mounted current transformers
(CT) used by circuit breakers to measure current.
Blank Space Only is specified when corresponding Produce lower secondary current than traditional CTs,
vertical bus device mounting and connecting straps
are not furnished. Dead Front construction is where energized parts are
not exposed to a person on the operating side of the
equipment.
9
Spectra Series® Switchboards
Section 3 – Terminology
Distribution Switchboard is any switchboard which is Fire Pump Disconnect serves only the code required
not UL listed for service entrance or classified as a fire pump. It must be connected ahead of any main
main switchboard. device and sized to carry the locked rotor current of
the fire pump per NFPA-20. It also must be located in
Double-Branch is mounting that has two fusible switch an enclosure separate from other service disconnects.
units or circuit breakers installed side by side.
Frame Size is the physical size of the breaker with a
Draw-Out Mounted device can be removed from the specific range of amp ratings. For example, an F Frame
stationary portion of a switchboard without unbolting breaker is available in ratings of 70 amps to 250 amps
connections or mounting supports. Draw-out mounting in a 225 amp frame.
is available in Power Break II and WavePro devices only.
SPECTRA MAIN
Electrically Operated refers to an electrically operated SECTION ARRANGEMENT
mechanism to remotely open and close a circuit Customer SE UL
Meter
breaker and charge the spring. Typically used in E
P
M
automatic throwover schemes and automatic control Ground MP
Fault
schemes. Monitor
Panel Main
Equipment Grounding is the interconnection and Front Only Connected is a UL classification requiring
grounding of electrical conduction material that either that all line & load connections can be made from the
encloses or is adjacent to power conducting components. front of the switchboard.
Expansion Kit is an assembled kit that can be installed Front/Rear Access is configured where rear access is
in an empty side of a double-branch fusible switch unit required for some or all of the line and load connections.
to create a new fusible switch unit It includes the handle,
base plate, cover plate, load base and switch. Front and Rear Line-Up occurs when all sections in a
switchboard lineup are the same depth and front and
Feeder Circuit is all circuit conductors between the rear surfaces are aligned.
service equipment or the source of a separately derived
system and the final branch-circuit overcurrent device. Full Height Bus refers to the maximum vertical bus
length available for the group mounted panel section.
Filler Mounts on side of fusible switch module, circuit
breaker module, or between side trims to cover the Fully Rated Bus refers to having the same ampacity
front of the enclosure. The fillers plus trim comprise the for the horizontal bus across the whole line-up.
enclosure front around the installed devices.
10
Spectra Series® Switchboards
Section 3 – Terminology
Fuseholder or Fuse Block is an assembly of fuse clips Interrupting Rating is the highest rms-rated current a
and insulation for mounting and connecting a fuse into fuse or breaker is intended to interrupt under specified
the circuit. conditions.
Fusible Switch is a device that can switch off current flow Jaw refers to the metal parts that grip the interior bus
and to which a fuse(s) is added to protect conductors. bar and conduct electricity to the module bus bars. The
jaws are spring-reinforced to provide a highly reliable
Ground Bus is horizontal bus which is electrically con- electrical connection.
tinuous with the switchboard housing for termination
of circuit ground conductor. Key Interlock, commonly called Kirk-keys, provides a
mechanical method to interlock two or more devices
Ground Fault is a fault condition created when an utilizing a removable key which can only be inserted in
energized conductor comes in contact with earth one location at one time.
ground or metallic structure, or causes an arc current
to flow to ground. Line refers to the incoming (live) side of equipment or
device.
Group (Panel)-Mounted device is one of a closely
grouped assembly of devices which is mounted on a Load is the outgoing (switched) side of equipment or
common base or mounting surface utilizing panelboard device.
type construction. The total assembly is then mounted
in a switchboard combination or distribution section. Lug is a device to terminate cables.
Handle Lock Device is a mechanism to insert a lock to Magnetic Trip is synonymous with instantaneous trip
prevent operation of a circuit protective device. Most and describes a tripping action with no intentional time
commonly used to lock device in the open or off delay. Current exceeding the magnetic trip level will
position for safety while performing maintenance. actuate the trip mechanism and open the breaker
contacts immediately.
Heat Rise is the maximum temperature a component
in a switchboard can increase in temperature over a Main Device is a single device that disconnects all
defined amount 65°C per UL 891. ungrounded switchboard conductors, other than control
power conductors when used, from the supply bus.
I2t is the measure of heat energy developed within a
circuit, in which I2 stands for effective let-through Main Lug is the connecting means between the
current squared and t is time in seconds. incoming service cable and the bus bar.
Individually Mounted means device which is not Mechanical Lug is a terminal with one or more wire
panel-mounted and which may or may not be enclosed binding screws that are tightened to hold the conductor
in its own compartment. Separated from other devices or cable.
to minimize undesired influence from them. (i.e. GE
Class 3 and PowerBreak Switchboard). Power Break II, Mimic Bus functionally displays internal buswork by
HPC, WavePro and BPS devices are individually mounted applying tape or plastic strip on equipment exterior.
in Spectra.
NEMA Type 1 Enclosure - General Purpose Indoor is
Interior refers to the side rails, bus bars and insulation intended primarily to prevent accidental contact of
system that mounts in the enclosure. It is energized personnel with the enclosed equipment. The enclosure
through the main device (lugs, fusible switch or circuit is intended for use indoors where it isn't exposed to
breaker) and, in turn, energizes the installed circuit- unusual service conditions, dripping or splashing water,
protective devices (fusible switch or circuit breaker). steam or conductive dusts (NEMA PB2-5.02).
11
Spectra Series® Switchboards
Section 3 – Terminology
NEMA 3R Outdoor Enclosures are intended for use in Rejection Fuse and Clip is a combination of fuses and
wet locations or outdoors to protect the enclosed clips that will not accept fuses of lower ratings and
equipment against rain. They are sleet (ice) resistant types. Can be used for Class R and other fuse types.
but are not dust, snow or sleet (ice) proof. If conduit
connections are provided, these enclosures shall have Reverse Feed. The following devices have been tested
a conduit hub or equivalent provision for watertight and are listed for reverse feeding: Fixed trip molded case
connections at the conduit entrance when the conduit circuit breakers, MET, and Spectra Circuit Breakers.
enters at a level higher than the lowest live part. They Reverse feed devices may have incoming (line) bottom
have provisions for drainage. and load top. They simplify bottom feed connections
and minimize switchboard depth. High pressure contact
Overcurrent is any current in excess of the rated current switches (HPC) can be specified as bottom-fed devices.
of equipment or the ampacity of a conductor that can Power Break II circuit breakers with EntelliGuard TU
result from an overload, a short circuit or a ground fault. and Power+ programmers can be reverse-fed without
special ordering.
Phase Failure Relay senses a loss of voltage in any of
the three phases of a power system. It is used to alarm Rotor is a mechanism in a fusible switch unit that
or trip an overcurrent device. mechanically ensures all switch blades open/close
simultaneously.
Plug-in is a type of panelboard and disconnect with
capability to be connected without requiring hardware Selective Tripping is the application of circuit breakers
to be fixed to the panel. or fuses in series, so that, of the breakers or fuses
carrying fault current, only the one nearest the fault
Plug-in Mounted device for line and load is one that can opens and isolates the faulted circuit from the system.
be plugged in to make electrical connections to a line
and load bus bar. The device need not be self-supporting Series-Connected Rated Panel means the UL Listed
when withdrawn. It may be removed when switchboard short-circuit rating of the panel is equal to the IC rating
is energized. of the main protective device when properly applied
with branch circuit protective device. See section 6.2
Pole is the number of output terminals on a fusible for further details.
switch or breaker that must be insulated and separated
from each other. Service Disconnect is a device or group of devices that
disconnects all ungrounded load conductors from the
Power Panelboard is any panelboard that is not a service (supply) conductors. The number of service
lighting or appliance panelboard as specified by UL disconnects is limited to 6 per the NEC.
and NEC and is not limited as to the number and rating
of branch circuits, except for available spacing and Service Entrance Equipment usually consists of circuit
physical size. The dead-front panelboard is accessible breakers or switches and fuses and their accessories. It
from the front only. is located near the point of entrance of supply conduc-
tors to a building and is intended to constitute the main
Quick-make, Quick-break refers to the action of mech- control and means of cutoff for the supply to the building.
anism, where the speed of the contacts in opening and Service entrance equipment have a removable link
closing a breaker or fusible switch is not controlled by between the neutral bus and ground bus. The main
the operator. device must also be barriered from feeder devices.
Rear-Only Connected switchboards have all incoming Shunt Trip opens a circuit protection device by remote
and outgoing cable or bus connections accessible from control.
the rear. Other connections may be front accessible.
Single-Branch is A mounting module with a single
Rear Line-Up Sections in a switchboard line-up are device mounted in a designated vertical space. Refers
different depths and rear surfaces are aligned. to breakers or fused units.
12
Spectra Series® Switchboards
Section 3 – Terminology
Space and Busing for future when space and busing is Trip Function is that portion of the breaker that senses
only required for future inclusion of any specified fault conditions, controls the associated logic functions
devices, appropriate device supports, proper bus con- and initiates and powers the breaker trip device.
nections and corresponding vertical bus are furnished.
Trip Mechanisms are independent of manual control
Split Bus refers to a division in carrying current bars of handles. The breaker will trip when a fault occurs, even
the panel interior, of 1 1/4", to isolate line or load of the if the handle is held in the "ON" position.
panel board. Split bus arrangements allow arc fault
breakers to isolate a section of the panel bus. Under Voltage release instantaneously trips the breaker
when voltage (control or line) drops to 30%-70% of
Standard (80%) and 100% Ratings Circuit breakers or nominal rating.
fusible switches are to be applied at 80% of their ratings
unless the overcurrent devices and the assemblies in Voltage is electrical pressure that moves electrons
which they are mounted are listed for operation at 100% through a conductor and is measured in volts.
of their ratings (NEC Articles 210-22(c), 220-3(a), 220-
10(b), 384-16(c). Refer to listings for available 100% Voltage Rating is the rms alternating current voltage at
rated devices. which a fuse or circuit breaker is designed to operate.
Stationary-Mounted device can be removed only by X Value is an arbitrary vertical measurement of the
unbolting electrical connections and mounting supports. usable mounting space on a panelboard for a fusible
Should only be removed when switchboard is deenergized. switch or breaker. X is equal to 1 3/8 inches (1.375").
Height of the interior is the sum of the horizontally
Sub-main is a disconnect provided for the connection mounted, panel-mounted components.
of a wire or a cable to a bus bar fed by an over current
protective device in the panelboard.
13
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
4.1 General Switchboard Sizing Section width is determined by the width required for
Considerations the largest breaker in the section.
The following rules and arrangements must be consid-
3” Width
ered when sizing and dimensioning Spectra Series
switchboards.
A Top Cover
Switchboard depth is the most variable of section
dimensions, as depth varies depending on the type,
size, feed direction, the combination of devices Group
Available Mounted
required and the circuitry involved. Feeder Distribution
X Height Section
The standard switchboard height is 90", but reduced Panel “X” Height A (in.) B (in.)
height switchboards of 78" are available. 18X 28 28
23X 21 28
Group Mounted 28X 21 21
The group mounted sections utilize a panel mount 33X 14 21
arrangement similar or identical to that used in distribution 38X 14 14
43X 7 14
panels. Group mounted breakers can be used as feeders
48X 7 7
or mains for switchboard sections 1200A and below. 53X 7 0
Group mounted breakers are typically 80%, but 100%
rated group mounted breakers are available for 800A
G frames and 1200A K frames for trip ratings of 60A to
1200A with fully adjustable trip ratings and 125A to 3X
100 100 3X
1200A for traditional trip breakers. 150 150 3X
225 225 3X
250 250 3X
In addition to circuit breakers and fusible switches, 400 400 4X
600 600 4X
additional devices that may be available to mount in 250 3X
the group mounted area of the switchboard include 400 4X
600 4X
SPD, meters and motor starters. 800 6X
1200 6X
Sizing
GE SPD 7X
Breakers are sized by X space requirements where 77”
X=1.375". Smaller frame brakers are available twin See page 20 for more details
mounted or double branch mounted in which two
breakers of the same frame size are mounted adjacent Bolt-on Branch Devices
to each other. Single branch mounting is the only option Max.
“X”
Min.
available for larger frame breakers, such as the 800A Mounting Breaker Breaker Frames Width
Height
Amps (in.)
and 1200A K frames. 100 THQB, THHQB, TEY, TEB, FC, FB 3 35
150 TED, THED, SE 3 35
Double 225 TQD, THQD 3 35
250 SF, FE 3 35
400, 600 SG, FG 4 40
250 SF, FE 3 35
400, 600 SG, FG, SGHC, SGLC, SGPC 4 35
Single
SKHA, SKLA, SKHC, SKLC 6 40
800, 1200
SKPA, SKPC 6 45
1X space adder: Note that 1X space must be added to each single or double branch
mounted breaker that has internal accessories requiring side exit control wiring.
These include shunt trip, auxiliary switches, bell alarms and undervoltage releases.
14
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
15
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Bottom Cover
Main
Device
Group Mounted Class 1
Main Lugs Only (Bolt-on and Plug-in)
Top or Bottom Cable Min. Min.
Amp Rating Entry Max. Feeder Depth Width
X-Height (in.) (in.)②
400, 600, 800, 1000,
Blank Pull Section 38① 25 35
1200, 1600, 2000
① 38X interior for front only connection, 43X available with rear access.
Blank Pull Sections ② Minimum section width shown. Wider Section may be required.
Amperage Width Depth Refer to branch sizing tables.
800-1200 15 25
1600-2000 20 25
2500 25 25
3000 30 25 Main Circuit Breaker (Bolt-on and Plug-in)
4000 35 30 Main Available Min.
Amp
Type Device X- Feeder Depth
Range
Height X-Height (in.)
FGV, FGN,
400-600 4 34 25
FGH, FGL, FGP
Standard Circuit SGDA, SGHA,
EUSERC Pull Sections 125-600 4 34 25
Breaker SGLA, SGPA
Pull sections to EUSERC utility requirements are available in widths SKHA, SKLA,
300-1200 6 32 25
from 30" to 50". The minimum widths for each amperage are shown SKPA
in the table below. The standard landing uses two (2) 1/2" steel studs SGHC, SKLC,
60-600 4 34 25
on 1 1/4" vertical centers per 400A of rating. Multiple positions are SGPC
MicroEntelliGuard
SKHC, SKLC,
separated by 2". These sections are designed for bottom entry, 300-1200 6 32 25
SKPC
with open bottoms. A barrier is provided for service entrance to FGV, FGN.
meet NEC requirements. Busing for landings is included. Record Plus 400-600 4 34 25
FGH, FGL, FGP
16
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
M 1200A 1200A
SE UL UL UL
8
1200A 1200A 1200A
SKHC12
1200A
NO FUTURE
1200A 1200A EXTENSIONS
PROVIDED
Main 21 21 U
2X FILLER 3X FILLER
1 2
12 13
24
3 4 14 15
ZZ
1200A
5 16
Utility 6 7 17 18
8 9 19 20
G
10 11 21 BLANK
28
42
3X FILLER 28X 42
3X FILLER 28X
N
1200A 1200A 1200A
BUSSING DIAGRAM
3 3 3 3
Conduit Area Conduit Area 3 3 3 3
19D x 34W 19D x 34W 7 3 Conduit Area Conduit Area
Conduit Area 16D x 34W 16D x 34W
21D x 25W
3 3 3 3
5 3 5
ACCESS TO: Front Only PHASE: 3P4W GE STANDARD UTILITY (28 INCH)
TM CLASS: 2 AMPERE: 1200A CODE ZZ
LABEL: U/L SE BUS MTL: Cu Heat
C/T TYPE Window
VOLTAGE: 480/277V PLATE: Silver Plate
P/T TYPE
STYLE: Bolt-On RATING: Fully Rated
BUS BRACING (RMS SYM): 65000A PER GE DWG 75C143813 PV101,101A,101B
DEV.MIN.INT.RATING (RMS SYM): 35000A PER PWR CO SPEC. 75C323045A SH. 1
17
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Switchboard Frame
Neutral Bus Cover 3” A
Width (W)
10”
Ref. 20”
3” Ref.
Cover A Main
Ground Ground
C
Bar Bar
90”
Panel
Circuit “X”
Circuit Breakers
Breakers and/or Height
and/or C
Fusible Switches
90” Fusible
Switches Panel See Branch
“X” Sizing Tables
See Height
Branch
Sizing Cover B
Tables
1.50 25”
Cover B Typ. 3”
Front View Side View
Cable Fed Main Devices With or Without CT’s
1.50 25”
Typ. 3”
Front View Side View
Distribution Section
Panel "X" Height A B C
23X 21 28 35
33X 14 21 49
38X 14 14 56
43X 7 14 63
53X 7 0① 77
① Rear access required.
Section Layout Notes • After determining all applicable conditions, lay out
• These switchboard arrangements assume line cables switchboard and calculate branch circuit "x" heights,
enter top. When line cables enter from below, neutral including future space. Add spaces sufficient to fill
and ground bus are mounted at bottom, and A and B panel to standard X increment.
cover dimensions are reversed.
• All dimensions are in inches and X values (1X = 1 3/8
inches). ADS Fusible Switch Branch Device Sizing (Spectra Plug-In Only)
• Front access to load cables requires a 7" high cover Switch Fuse Blank
Min.
X
Min.
minimum. Branch Volts Poles Width Depth
Rating Class Option Height
(in.) (in.)
• Front access to neutral and/or ground bus requires a
Double 240V
14" high cover minimum. 30A
Branch 600V
2, 3P H, K, R Yes 40 4X 25
• Any circuit breakers with externally wired accessories
Double 240V 4X
(such as shunt trip, undervoltage release, auxiliary 60A 2, 3P H, K, R Yes 40 25
Branch 600V 5X
switches) will require a 1X filler between adjacent H, J, K,
devices. Double 240V 5X
100A 2, 3P R Yes 40 25
Branch
• For double branch units, only same circuit breaker 600V T 7X
type devices can be mounted across from each other. Single
H, K, R No
Branch
5 2.5 (Typ.) 3.12 (Typ.) 240V 40
200A Double 2, 3P J, T Yes 7X 25
Branch
Double
600V H, K, R Yes 45
Conduit Space Branch
(Typical all Single 240V J, T 40
Selections) 400A 2, 3P No 10X 25
.625 Dia. (Typ.) Branch 600V H, K, R 45
Mounting Holes Single 240V J, T 40
600A 2, 3P No 10X 25
Branch 600V H, K, R 45
• All single branch circuit breakers, in service entrance 800A Single 240V
2, 3P L No 45 19X 25
equipment, are mounted with load lugs staggered to 1200A Branch 600V
allow for equal cabling in both wire gutters. Main
device line lugs are located on the left side.
19
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Molded Case Circuit Breaker Branch Device Sizing – Molded Case Circuit Breaker Branch Device Sizing –
Plug-In Bolt-On
3-Pole 2-Pole 3-Pole 2-Pole
Max. Min. Min. Max. Min. Min.
Breaker Module② Module② Breaker Module② Module②
Mounting Breaker Width Depth Mounting Breaker Width Depth
Frames X X Frames X X
Amps (in.) (in.) Amps (in.) (in.)
Height Height Height Height
THQB, THHQB, TED, FB 3 2 35 25
3 — 35 25
TEY, TEYF TEY, TEYF 3 — 35 25
100 SE, SF 3 3 35 25 100
SE, SF, THED 3 3 35 25
SG 4 4 40 25
SG 4 4 40 25
FB 3 2 35 25
TEB, TED, TED 3 2 35 25
3 2 35 25
TQD, THQD 150 SE, SF 3 3 35 25
150 THED, SF 3 3 35 25
SG 4 4 40 25
SG 4 4 40 25
SF 3 3 35 25
TQD, THQD 3 2 35 25 Double 225
225 SF, FE➃ 3 3 35 25 SG 4 4 40 25
Double
SG 4 4 40 25 SF, FE➃ 3 3 35 25
250
TJD 6 6 45 25 SG 4 4 40 25
250 SF 3 3 35 25 400 SG 4 4 40 25
SG 4 4 40 25
SG, FG 4 4 40 25
TJD 6 6 45 25
400 micro-
SG 4 4 40 25 600① EntelliGuard
SG, FG 4 4 40 25 4 — 40 25
trip unit SGHC,
micro- SGLC, SGPC
600① EntelliGuard SF 3 3 35 25
4 — 40 25 250
trip unit SGHC,
SGLC, SGPC SG 4 4 35 25
Double 150 SEDA, SEHA, SG 4 4 35 25
4 4 40 25 400
Adjacent SELA, SEPA SK 6 6 40 25
to Fusible SFHA, SFLA,
Switch 250 SFPA
4 4 40 25 SG, FG 4 4 35 25
SF 3 3 35 25 micro-
250 Single 600 EntelliGuard
SG 4 4 35 25 4 — 35 25
trip unit SGHC,
TJD 6 6 35 25 SGLC, SGPC
400
SG 4 4 35 25
SKH, SKL 6 6 40 25
SG, FG 4 4 35 25
micro-
micro- 1200
600 EntelliGuard
Single EntelliGuard 6 — 40 25
4 — 35 25 trip unit SKHC,
trip unit SGHC, ➂
SKLC, SKP
SGLC, SGPC
SK 6 6 40 25 ① Double branch mounting available through 3000A.
② Add 2x to height for accessories on breakers.
micro- ➂ SKP requires 45" minimum width if used as a main breaker with cables.
1200 EntelliGuard ➃ FE shown at 100kAIC at 3X. If 150 kAIC, then X height is 5X.
6 — 40 25
trip unit SKHC,
SKLC, SKP ➂
Single SF 4 4 40 25
Adjacent
250
to Fusible
Switch SKP 6 6 45 25
① Double mounting not available in 2500A or higher main bus rating.
② Add 1x to height for accessories on breakers.
➂ SKP requires 45" minimum width if used as a main breaker with cables.
➃ FE shown at 100kAIC at 3X. If 150 kAIC, then X height is 5X.
20
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
3-Pole 2-Pole
Max. Min. Min.
Breaker Module① Module①
Mounting Breaker Width Depth
Frames X X
Amps (in.) (in.)
Height Height
14"
Spectra RMS
Breaker 150 150 3X
Twin 400 4 4 40 25
SGHHA, 250 250 3X
SGLLA, SGPPA 600 600 4X
Spectra RMS
600 4X
Breaker
Single 1000 8 6 40 25
SKHHA, SKLLA, 800 6X
SKPPA ➃
with micro-
40"
EntelliGuard
Single 1000 8 – 40 25 Spectra Breakers
Trip Unit
SKHHC,
SKLLC,
SKPPC➃ 25
"
Spectra RMS
Breakers
with micro- 7"
EntelliGuard
Twin 400 6 or 5➂ – 40 25 30A 30A 4X
Trip Unit➁
SGHHC, 60A 60A 5X
SGLLC,
SGPPC 100A 100A 5X
Spectra RMS
Breakers 200A 200A 7X
with micro-
EntelliGuard
Single 1000 8 – 40 25
Trip Unit➁ 400A & 600A 10X
SKHHC,
SKLLC,
SKPPC➃
① Add 1X per double or single branch for internal accessories side control wiring space
(Shunt trip, auxiliary switch, bell alarm, undervoltage release).
800A & 1200A 19X
② A voltage module must be used with microEntelliGuard trip units with metering.
➂ An auxiliary switch must be installed on breakers with microEntelliGuard trip units.
A 1X space for side control wiring is included.
➃ SKPP requires 45" minimum width.
77" 53X
45"
Ads Fused Switches
Notes
• 600A frame breakers can only twin mount on main bus under 2500A.
• 800A & 1200A breakers can mount in 40" wide section for 65kA
and under. For 100kA ratings, 45" section is required, except for
SKPP breakers, which always require a 45" wide section.
• X=1.375"
• Front/Rear Access 53X interior available.
21
• Font Only Access 43X interior available.
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Utility Compartment
When Required
5 2.5 3.12 (Typ.)
(Typ.)
Conduit Space
(Typical all
.625 Dia. Selections)
(Typ.)
22
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
The dimensions shown are minimum widths and depths CT Compartment Dimensions
of switchboard sections containing CT compartments CT Ampere Minimum Section Minimum Section
only. If there are other devices located in the section, Centerline Ratings Width (inches)① Depth (inches)①
actual width will be based on the largest device 600
required. Also, the entire switchboard lineup depth will 800
1000
be based on the largest device depth required. 1200
9" or 11" 35 35
1600
The following utilities have approved the type of 2000
metering compartment shown. Compartments are 2500
available with the following features: 3000
• CT bus bars mounted on high impact glass fiber poly- 4000 40 40
① Add 5" to depth when busway entrance is required.
ester insulation and arranged in an edgewise plane.
• Door with concealed hinges, 3-point catch and lock,
handle seal over CT compartment barriers rear and
bottom (top). Note: The bottom barrier is furnished at
top if main device is over CT compartment.
• 9" or 11" centerline is standard. For other centerlines,
refer to factory.
• CT bus bars drilled for transformers with NEMA
terminations.
• #10-32 and 1/4-20 screws for potential taps.
• Removable links provided if part of utility requirements.
• Cold sequence metering has CT compartment on load
side of main device. Hot sequence CT compartment
is on line side.
23
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
24
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
91”
91”
25
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Abbreviation Description CL
A Ammeter type AB40-250
V Voltmeter type AB40, 250 6”
TFR CL
EPM EPM
PQM PQM “W ”
TER
TEL
AS Ammeter Switch
VS Voltmeter Switch Top View
PL Pilot Light
TFF CL
PB Push Button CL CL
6”
GFR ITI GF Relay Transition Transition
Section CL Section
EPM 8” EPM 8”
2200 6000
Front
CL
12” Min.
PL 15” 15”
Transition Transition
A V 8” 8” Section Section
AS VS
PB
➁ 15" dimensions become 20" on outdoor switchboards.
Transition sections are 15" wide. Consult factory for 4.10 Conduit Entrance Space
non-standard applications. Incoming Line Sections
Depth
3 TC
Top Conduit area (TC) = Depth - 6"
Incoming Additional
Section Section(s)
Neutral location
Side Conduit
90” Front Rear
View Area
90” or
78” Plan View
Aux Neutral
Ground Used only on
front access
Service
Entrance
switchboards
6 3
Front
Neutral
LINE BOTTOM
Bottom Conduit area (BC) = Depth - 9"
3 BC 6
“W” “D”
Drawing is for basic guideline purposes, refer to factory for exact dimensions.
Switchboard Enclosure
Use the following table to determine the weight of the
steel only for each switchboard section, based on the
89.5” & 90” High
width and depth and whether indoor or outdoor.
Core & coil type QLC transformers provided in switchboard enclosures
cable connected to primary and secondary by equipment plant.
NEMA 1 Indoor Switchboard Enclosure Weight (lbs)
(with shipping skid and covers on all sides)
Self-Cooled Section Widths (inches)
KVA Depths
Width Depth 15 20 25 30 35 40 45 50 55 60
30 30" 35" 25 270 303 336 369 402 435 470 503 536 569
45 30" 35" 30 303 336 369 402 435 470 503 536 569 602
75 35" 35" 35 336 369 402 435 470 503 536 569 602 635
112.5 40" 35" 40 369 402 435 470 503 536 569 602 635 668
150 45" 40" 45 402 435 470 503 536 569 602 635 668 701
50 435 470 503 536 569 602 635 668 701 734
55 470 503 536 569 602 635 668 701 734 767
60 503 536 569 602 635 668 701 734 767 800
27
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Switchboard Internal Bus Weights Use the following table to determine the weight of the
The following table is used to determine the weight of vertical bussing for Group Mounted Sections. The table
the horizontal (through) bus within the switchboard assumes a worst case 2000A vertical bus with the
section. The bus material, bus ampacity and section vertical height determined by the X spacing (x=1-3/8”).
width determine the weight in pounds for the through Connection bus between panel and through bus is
bus in each section. included.
28
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
Use the following tables to determine the weight of the Switchboard Overcurrent Device Weights
bus used to connect individually mounted devices to the The weight of each individual breaker or fused switch must
horizontal bus and the weight of utility compartments. be added to determine the overall weight of the switchboard.
30
Spectra Series® Switchboards
Section 4 – Sizing and Dimensions
2000A
Spectra
Busway
7"
PQ MII
14" 6X Filler
20"
6X Filler
GE
80 SELA 125 SELA
PowerBreak II
GE PowerBreak II 2000A 400 SGLA
4000A Fixed Mntd
4000A Draw-out 20" 1000 SKLA
Bussed
Pull Section 600 SGLA
44"
6X Filler
6X Filler
2X Filler
SPD
77" 5 3X "
45
Thru Bus
Group Mounted
From Lug
Breakers
A Section
B Vertical Bus
C
Thru Bus
Breaker Thru Bus
Breaker
Neutral Riser
31
Spectra Series® Switchboards
Section 5 – Application Data
5.1 Standards/Codes/Ratings/Conditions
System Selectivity and Protection
The design of a protective system involves two separate
but interrelated steps:
1. Selection of the proper device. P1
2. Selection of the setting for the devices to achieve the
degree of protection and selectivity desired.
Device Selection
All protective devices should be applied within their
ratings - voltage, frequency, current and short circuit -
under usual switchboard service conditions. Additional
device selection considerations may be required if the Current
equipment is part of a system with required selectivity
per the NEC. Device selections need to be made
carefully to properly fulfill selectivity requirements.
32
Spectra Series® Switchboards
Section 5 – Application Data
Ground fault protection shall be provided for solidly Switchboard bus bars are rated on a current density
grounded wye services with more than 150 volts to basis -750A per square inch for aluminum and 1000A
ground but not exceeding 600 volts phase-to-phase per square inch for copper or heat rated. (Tested per
for each service disconnecting means rated 1000 standard).
amperes or more (NEC 230.95).
Frequency
Switchboard Enclosure AC switchboards are rated 60 Hertz and may be
The standard switchboard enclosure is a NEMA Type 1 applied on 50 Hertz services without derating. For
general purpose indoor enclosure. It is intended prima- other ratings, refer to factory.
rily to prevent accidental contact of personnel with live
parts and to provide protection against dirt and foreign Insulation Level
objects. NEMA 1 enclosures should be used indoors in Switchboards have an insulation level rating at twice
dry locations. the rated voltage plus 1000 volts. The dielectric test for
this rating consists of applying a 60 hertz voltage for 1
Devices may require ventilation for operation at rated minute phase-to-phase and phase-to ground with
current. The standard switchboard enclosure should switching devices closed.
not be used in environments where ventilation is not
acceptable. Working Space
The National Electrical Code (Article 110.26) requires
Outdoor enclosures are available and should be used that sufficient access and working space shall be
outdoors to protect the equipment against rain, and provided and maintained about electrical equipment to
indoors where water may intrude, such as beneath fire permit ready and safe operation and maintenance of
sprinklers. such equipment.
Access and Entrance to Working Space are marked with a short circuit rating. The switchboard
At least one entrance of sufficient area shall be provided will be fully rated or series connected rated. When fully
to give access to the working space about switchboards. rated, the short circuit rating of the switchboard is that
For switchboards rating 1200A or more and over six of the lowest rated device in the switchboard. Series
feet wide, there shall be one entrance not less than connected ratings are based on short circuit ratings
twenty-four (24) inches wide and six and one-half given to two or more devices connected in series.
(6-1/2) feet high at each end (NEC 110-26(c)).
In either case, the bus bar bracing must be equal to or
Exceptions to this are: exceed the short circuit rating of the switchboard. Bus
1. Where the equipment location permits a continuous bar bracings available are 65,000, 100,000, 150,000
and unobstructed way of exit travel. and 200,000 rms symmetrical amperes; 65,000 is the
2. Where work space is double the amount required. standard bracing.
34
Spectra Series® Switchboards
Section 5 – Application Data
GE's more stringent internal requirements, offering a 2. Switchboards can be applied for use in altitudes up
greater margin or performance and safety. to 6600 feet (2000 meters). Above 6600 feet, the
derating factors in Table on following page apply.
The following classifications and limitations of switchboard 3. Ambient temperature rating of installed protective
distribution sections have been established by Underwriters devices should not be exceeded without derating. The
Laboratories and the National Electrical Code. ambient temperature ratings of the most frequently
used devices are listed in Table on following page.
Note: An overcurrent protective device is a circuit breaker This temperature is around the device inside the
pole or single fuse. switchboard enclosure. Refer to the applicable
device standard for derating factors.
4. The National Electrical Code specifies ampacity of
Standard Test Circuit
Device conductors for various temperatures. Standard ratings
UL ANSI NEMA Power Factor (%)
are based on 30°C (86°F) ambient. Higher ambient
Molded Case Circuit
489 AB-1 20 temperatures will require derating as shown in NEC
Breakers
Power Break II Circuit Table 310-16. Maximum operating temperature of
489 AB-1 20
Breakers conductor insulation must not exceed that shown in
Low Voltage Power NEC Table 310-16.
1066 C37.50 20
Circuit Breakers 5. All device lugs and equipment lug assemblies are UL
High Pressure
Contact Switches
977 KS-2 20 listed and rated for use with conductors whose
Bolted Pressure ampacity is based on the ampere rating of 75°C
977 KS-2 20
Switches (167°F) conductors, which is in compliance with NEC
Fusible Switches 98 20 11.14. Higher temperature ratings may be used and
Fuses 198 E.B FU-1 20 in some cases should be used, but it must be
applied at it's 75°C ampacity. Lugs rated for 90°C
(stamped AL9CU). However, cables terminating in
Service Entrance Equipment our equipment can only be sized to 75°C.
• Must be located near the point of entrance of building 6. Switchboards will resist seismic forces of 0.6G in any
supply conductors. direction when installed with structurally certified
• Switchboard distribution sections may have up to six fasteners in accordance with the installation
operating handles to entirely disconnect switchboards instructions.
from the source. 7. For unusual service conditions, such as corrosive
• Must include connector for bonding and grounding atmosphere, vibration or unique equipment
neutral conductor. arrangements, refer to factory.
• A service entrance-type UL label must be factory
installed and will be provided on the equipment
(when specified). Altitude Temperature Voltage
Feet Meters Derating Derating
Service Conditions 6600 2000 1.00 1.00
1. Switchboards are rated for use in a 40°C room 8500 2600 .99 .95
ambient per UL891. For higher ambients, the current 13000 3900 .96 .80
rating of the equipment should be derated by
multiplying factors in the following Table. Short circuit ratings are not affected by altitude.
35
Spectra Series® Switchboards
Section 5 – Application Data
5.2 Protective Device Ratings The upstream protector can be a molded case breaker
Series Connected Ratings or fuse. Device combinations are not limited to those in
UL permits assigning a short circuit rating to a combi- the same equipment; They can be in different equip-
nation of molded case circuit breakers or fuses and ment, such as a switchboard feeder and a panelboard
molded case circuit breakers connected in series that main, or a switchboard feeder and panelboard branch-
is higher than the lowest rating protective device of the es in a main lug panelboard. Any distance between
combination. This is defined as series connected ratings. devices is permitted. To be a valid series rating applica-
The combination rating cannot exceed the rating of tion, total fault current magnitude must flow through
the protective device farthest upstream, although it will both protectors. Thus, fault current contribution from
exceed the rating of the downstream protector. motors, as well as power source fault current, must
flow through upstream and downstream protectors.
The upstream protector can be a molded case breaker
or fuse. Device combinations are not limited to those in Molded case circuit breakers may be applied as fully
the same equipment. They can be in different equipment, rated or series rated. In a fully rated system (figure
such as a switchboard feeder or a panelboard main adjacent), the short circuit rating of all protective
versus panelboard branches. Any distance between devices is equal to or exceeds the circuit short circuit
devices in different equipment is permitted. Total fault requirement. If mounted in equipment, the bus short
current magnitude must flow through both protectors. circuit withstand rating and equipment short circuit
Thus, fault current contribution from motors, as well as rating must also exceed the circuit available current.
power source fault current, must flow through
upstream and downstream protectors. In a series connected system (figure adjacent), the
short circuit rating of the upstream protector is “full”
Molded case circuit breakers may be applied as fully (meets or exceeds the available current in the system),
rated or series connected. but the downstream protector is not fully rated (is
rated less than the system available).
In a fully rated system, (figure adjacent), the short circuit
rating of all protective devices is equal to, or exceeds, In series or fully rated combinations, both protectors
the circuit short circuit requirement and, if mounted in may open on short circuits. Conversely, in selectively
equipment, the bus short circuit withstand rating and coordinated systems, only the device closest to the
equipment short circuit rating exceeds the circuit overcurrent of fault is permitted to open. In these sys-
available. tems, both devices must be fully rated, and the short
circuit level to which they are selective must be known.
In a series connected system, (figure adjacent), the
short circuit rating of the upstream protector is fully Examples where selectivity is desirable (and often
rated but the downstream protector is not fully rated. required) include:
• Buildings with important loads such as: elevators,
UL permits assigning a short circuit rating to a combi- emergency lighting, critical ventilation, etc.
nation of protective devices that is higher than the • Manufacturing facilities where loss of power can
lowest rating of the downstream device. This rating of result in economic loss due to production downtime
two devices in series is defined as a series rating. or damage to equipment.
Series ratings can exist for a combination of molded • Hospitals and medical facilities where life support is
case circuit breakers, or a combination of fuses and critical.
molded case circuit breakers. The rating of the combi-
nation cannot exceed the rating of the upstream Series Ratings are listed in publication DET-008.
device in the combination, but can exceed that of the Selectivity Ratings are listed in publication DET-537.
downstream device.
36
Spectra Series® Switchboards
Section 5 – Application Data
THED
Panelboard
480Y/277V
400A
37
Spectra Series® Switchboards
Section 5 – Application Data
5.3 Power Break® II Circuit Breaker inserting a ground fault rating plug. An optional target
Basic Configuration module allows for fault indication monitoring and also
The insulated case circuit breaker - GE pioneered the functions as a trip unit health indicator.
design and created the name. Power Break® II insulated
case circuit breakers offer reliable, flexible and easy- Rating Plugs
to-use circuit protection. The same interchangeable rating plugs are used in all
of the EntelliGuard TU trip units across the entire Power
Power Break II circuit breakers are UL Listed, CSA Break II breaker product line. Rating plugs are the key
Certified and IEC Certified for up to 200,000 amps at devices that establish the current rating of the breaker.
240 volts rms symmetrical interrupting capacity without They provide an essential scaling function for the unit's
fuses or current limiters. These insulated case circuit microprocessor and ensure maximum accuracy.
breakers can be applied on ac power systems through
600 volts. Featuring a 2000A compact design up to 40% Rating plugs have rejection features that allow them to
smaller than its predecessors, Power Break II circuit break- be inserted only with breakers containing the correct
ers consist of three envelope sizes from 800 to 4000 amps. current sensors. Rating plugs for the EntelliGuard TU
trip units are compatible with Power Break and AKR
Greater Convenience and Operational Safety. breakers with EntelliGuard TU trip units. See Table below.
The controls and status indicators you need most are
readily accessible. The flush-mounted handle, ON/OFF Rating Plug and Current Sensor Ratings
Frame Sensor
buttons, rating plug test receptacles, bell alarm reset Envelope Max. Rating
buttons (with or without lockout) are easily reached, and Rating Plug Amps (X)
Size Rating (Amps)
all are double-insulated from live components. For added (Amps) (S)
security, a standard padlock device lets you prevent 200 100, 150, 200
800
400 100, 150, 200, 225, 250, 300, 400
accidental or unauthorized closing of the breaker.
300, 350, 400, 450, 500, 600, 700,
800, 1600 800
750, 800
Quick, Error-Free Installation of Universal 2000 1000 400, 450, 500, 600, 700, 750, 800
Accessories 1600 600, 700, 750, 800, 900, 1000, 1100,
1600
Drop-in bell alarm, bell alarm with manual lockout, 1200, 1250, 1500, 1600
750, 800, 900, 1000, 1100, 1200,
shunt trip (with or without lockout) and undervoltage 2000 2000
1250, 1500, 1600, 1900, 2000
release install in seconds. No special tools. No breaker 1000 400, 450, 500, 600, 700, 750, 800
disassembly. Just slide them into place. The modules 750, 800, 900, 1000, 1100, 1200,
2500 2000
1250, 1500, 1600, 1900, 2000
are universal across all frame sizes, and each is 3000 1000, 1100, 1200, 1250, 1500, 1600,
mechanically keyed to its compartment so you make 2500
1900, 2000, 2200, 2400, 2500
the right connection, every time. These accessories are 3000 3000
1200, 1250, 1500, 1600, 1900, 2000,
field installable and upgradeable. 2200, 2400, 2500, 3000
1500, 1600, 1900, 2000, 2200, 2400,
4000 4000 4000
2500, 3000, 3600, 3400, 4000
Advanced, Solid-State Trip Units
EntelliGuard TU trip units give you new ways to moni-
tor and control the Power Break II breaker with Current Sensors
unprecedented ease. A simple keypad lets you program Toroidally wound current sensors are furnished for all
and display a variety of functions, including tripping major protective functions, and for use with all Power
characteristics, remote communications, status infor- Break II trip units. Toroidal sensors, including a second
mation and protective relaying. The trip unit display also air-core winding, are provided with the high-range
allows viewing of many standard metering parameters as instantaneous function. Current sensors are factory
well as pickup alarms, trip target indications and fault installed and are not changeable in the field. There are
status information. For less demanding functionality, 11 current ratings for the Power Break II breaker line
the Power+ trip unit gives you a second choice in through 4000 amps. See table above for current ratings.
Power Break II breaker control. Tripping characteristics Rating plugs must be coordinated with the current
are easily adjusted by a set of simple-to-use switches. sensor rating (S) listed on the face of the rating plug.
The trip unit is upgradable to ground fault by simply
38
Spectra Series® Switchboards
Section 5 – Application Data
Accessory Configuration
Activation of the bell alarm - alarm only and bell alarm
with lockout are controlled by switch settings on the
rear of the trip unit. To change the conditions that acti-
vate these accessories, configure the trip unit switch
settings as described below.
For complete information on Power Break II circuit breakers, refer to publication GET-8052.
39
Spectra Series® Switchboards
Section 5 – Application Data
40
Spectra Series® Switchboards
Section 5 – Application Data
41
Spectra Series® Switchboards
Section 5 – Application Data
EntelliGuard TU Trip Unit Features (All Frames)➂ WavePro Breaker Interrupting Ratings
Trip Unit Suffix Rated Short-Circuit RMS
PM AC Frame Symmetrical kA
Function Description Breaker
M (Metering Voltage, Size Short- With Without
Type
(Metering) & Nominal (amps) Time Instantaneous Instantaneous
Relaying) (max) Withstand Trip Trip
Selectable phase current, WPS-08 800 30 30 30
Amperes (A) X X
±2.0% WPH-08 800 42 42 42
Voltage (V) L-L or L-N Volts, ±1.5% X X
WPX-08 800 50 50 50
Energy (kWh, Total energy usage on
X X WPS-16 1600 42 42 42
MWh) breaker, ±3.5%
600 WPH-16 1600 65 65 65
Real Power (kW) L-L or L-N Power, ±3.5% X X
(635) WPS-20 2000 65 65 65
Frequency (Hz) Circuit Frequency, ±1 Hz X X
WPS-32 3200 65 65 65
Undervoltage Adjustable pickup: 50-90%;
X WPH-32 3200 85 85 85
Trip adjustable delay: 1-15 s, OFF
Overvoltage Adjustable pickup: 110-150%; WPS-40 4000 85 85 85
X WPS-50 5000 85 85 85
Trip adjustable delay: 1-15 s, OFF
Voltage Adjustable pickup: 10-50%; WPS-08 800 30 30 30
X
Unbalance adjustable delay: 1-15 s, OFF WPH-08 800 42 42 42
Current Adjustable pickup: 10-50%; WPX-08 800 65 65 65
X
Unbalance adjustable delay: 1-15 s, OFF WPS-16 1600 50 50 50
Adjustable pickup: 10-990 kW; 480 WPH-16 1600 65 65 65
Power Reversal X
adjustable delay: 1-15 s, OFF (508) WPS-20 2000 65 65 65
Setup as line-to-load or load- WPS-32 3200 65 65 65
Power Direction X
to-line WPH-32 3200 85 85 85
Communication X X WPS-40 4000 85 85 85
① Time delay shown at lower limit of band. Ground fault pick up not to exceed 1200 amps. WPS-50 5000 85 85 85
② Power+ not available on 5000 amp (WPS-50) circuit breaker.
WPS-08 800 30 42 30
In or X = Rating plug amps WPH-08 800 42 50 42
CT or S = Sensor amp rating
LT or C = Long-time current setting
WPX-08 800 65 65 65
ST = Short time characteristic WPS-16 1600 50 65 50
240 WPH-16 1600 65 65 65
(254) WPS-20 2000 65 65 65
Product Specifications➂ WPS-32 3200 65 85 65
Fused Breaker Ratings (Max. 600 Vac. 50/60 Hz) WPH-32 3200 85 130 85
Breaker Frame Size Fuse Rating, A① Interrupting Rating WPS-40 4000 85 130 85
Type (amps) Min. Max. RMS Symmetrical kA WPS-50 5000 85 130 85
WPF-08 800 300 1600 200 ① The maximum fuse rating is the largest fuse that tests show will result in proper
performance of the breaker and fuse in combination under short-circuit conditions.
WPF-16 1600 450 2500 200 Only Gould-Shawmut fuses should be used for proper coordination.
WPS-20② 2000 2000 2500 200 ② Fuses are mounted on separate fuse roll-out element.
WPS-32② 3200 2000 4000 200
WPS-40② 4000 2000 5000 200
WPS-50② 5000 2000 5000 200
Operating Time (Cycles on 60 Hz Base; All Frame Sizes)
Shipping Weight Closing electrically
Draw-Out Breaker Net (lbs) Time from energizing closing circuit
Element Manual Electrical until contacts touch 5
WPS/WPH/WPX-08 200 205 Open (maximum clearing time)
WPF-08 245 250
WPS/WPH-16 210 215
With instantaneous overcurrent trip 3
WPF-16 255 260 With shunt trip 3.5
WPS-20 220 225
WPS/WPH-32 475 485 For further information on WavePro Low Voltage
WPS-40 535 545
WPS-50 575 585
Power Circuit Breakers, refer to DET-167
42
Spectra Series® Switchboards
Section 5 – Application Data
43
Spectra Series® Switchboards
Section 5 – Application Data
GE HPC Switch Interrupting Ratings • All frame sizes have maximum UL listed interrupting
Available Ratings Contact ratings of 200 kA @ 240 Vac and 100 kA @ 480 Vac
Interrupting Switch-fuse
Rating Based on Combination with 600 Vac ratings to 65 kA depending on frame
Type Continuous Maximum Ability to Operate at Switch-rated size. UL listed current limiting versions are provided
Amperes ac Volts on Overload ac Volts with through the SG600 frame for the 65 kA @ 480 Vac
Unassisted by Class L Fuse
the Fuse
and the 100 kA @ 480 Vac models, with no increase
800, 1200, "Open" -
in physical frame size.
1600, 2000, 12X amp rating; • Spectra® RMS Mag-Break instantaneous-only motor
HPC/R 600 200,000
2500, 3000, "Close-Open" - circuit protectors also use the same digital, solid-state
4000 12X amp rating trip unit and rating plugs as the circuit breakers. The
interchangeable rating plug establishes the instanta-
For further information on HPC switches, see GET-6205 neous pickup range (with tracking short-time) but
or contact your local GE Account Manager. does not change the frame ampere rating.
• Spectra® RMS molded case switches have a fixed,
high-set instantaneous trip (without tracking short-time
function) and have short-circuit withstand ratings equal
5.6 Molded Case Circuit Breakers to their equivalent breaker frame size interrupting
Features rating in most cases.
• Spectra® RMS breakers are ambient insensitive. Trip
Spectra® RMS Molded Case Circuit Breakers times will not vary over the range 10-50°C breaker
SE150, SF250, SG600, and SK1200 circuit breaker frames ambient. Refer to GET-7002 for further application
have a digital, solid-state, rms sensing trip system with information.
field installable, front-mounted rating plugs to establish • Spectra® RMS breakers contain no parts that would
or change the breaker ampere rating. Adjustable support fungus growth and are, therefore, inherently
instantaneous with tracking short-time is standard on fungusproof.
all frames including SE150. The trip system uses digital
sampling to determine the rms value of sinusoidal and Record Plus® Molded Case Circuit Breakers
nonsinusoidal currents. Record Plus® represents the very latest in molded case
circuit breaker design. Utilizing design features such as
microEntelliGuard Trip Units double-break rotary contact structures and advanced
Spectra® SG600 and SK1200 breakers are now available ablative materials to enhance interruption, Record Plus®
with microEntelliGuard™ trip units - the newest and most is capable of interrupting ratings up to 200kA. High
advanced trip unit available in the Spectra® line of kAIC ratings, selective coordination, reduced arc flash
molded case circuit breakers. Based on the EntelliGuard® energy, and current limitation embody the core design
TU trip unit platform, the microEntelliGuard™ trip unit principles of Record Plus®.
has the same HMI interface and incorporates the
advanced features and protective functions for improved FC 100 and FB 100 circuit breakers are supplied with
system protection, coordination, selectivity, performance factory installed non-user interchangeable thermal-
and diagnostic capabilities. The microEntelliGuard™ trip magnetic trip units and can be supplied with or without
unit uses the same universal rating plugs and test kit lugs. FB breakers are available in 1-, 2- and 3-pole
offered for the EntelliGuard® TU trip unit. versions. FC is available in 2- and 3-pole versions, both
in a 3-pole footprint.
A complete circuit breaker consists of a UL listed circuit
breaker frame and a rating plug (UL listed interchangeable FE250 and FG600 circuit breakers are supplied equipped
trip unit). Terminal lugs for cable connection are available with factory installed non-user interchangeable elec-
if required. tronic trip units that feature the use of front accessible,
• All frames use the same UL listed, field-installable user installed rating plugs to establish or change the
internal accessories (auxiliary switch, shunt trip, breaker’s amp rating. Rating plugs are user specified
undervoltage release and bell alarm). and ordered under separate product number.
44
Spectra Series® Switchboards
Section 5 – Application Data
Instantaneous pickup levels are adjustable and set via Quick Reference Guide
a front-mounted adjusting knob. Both are available in Ratings do not apply to molded case switches.
2- and 3-pole versions, each in a 3-pole footprint.
The interruption ratings and voltages shown in the
All frames use common internal accessories (auxiliary tables are maximum ratings. A circuit breaker of the
switches, UV releases, shunt trips, and bell alarms) UL type given in the left-hand column may be applied at
listed for field installation. the given circuit voltage in any electrical distribution
system where the available fault current at the load
UL listed maximum short circuit ratings at 480VAC are terminals of the breaker does not exceed the value in
150kA for the 100A frames and 200kA for the 600A frames. the table. That circuit breaker type may also be applied
at intermediate values of circuit voltage provided the
Unless noted otherwise, all circuit breakers and available fault current at the load terminals of the
accessories are listed in UL file number E11592. breaker does not exceed the value in the table for the
higher value of voltage.
Other MCCB Features
• UL489 Listed
• Broad product line to meet virtually any application
need.
• Reduced downtime. A tripped breaker is easily spotted
and can be immediately reset after the fault has been
corrected.
• Eliminates single phasing. A common trip bar discon-
nects all poles simultaneously on both overloads and
short circuits.
• Offers application flexibility through the use of a wide
variety of accessory devices and special attachments.
• Repetitive operation — no fuses to replace.
• Breakers can be repetitively tested. Fuses must be
destroyed to confirm calibration accuracy.
45
Spectra Series® Switchboards
Section 5 – Application Data
THQL 32015
1 — 1 50
TQL/TQB/ 120/240 52
10 2 — — — — — — — 3 9/32 2 2 3/8 — — — — 25
TQC 52
3 240 — 3 15
15-70 1 — 1 50
THQL1 120/240 10
THQB1 15-125 2 — —
— — — — — 3 9/32 2 2 3/8 — — — — 25
THQC1 10
15-100 3 240 — 3 15
15-70 1 — 1 50
THHQB1 120/240 22
2 — — — — — — — 3 9/32 2 2 3/8 — — — — 25
THHQC1 15-100 22
3 240 — 3 15
15-70 1 — 1 50
120/240 22
THHQL1 15-125 2 — — — — — — — 3 9/32 2 2 3/8 — — — — 25
22
15-100 3 240 — 3 15
1 — 1 50
TXQL1 120/240 65
TXQB1 15-30 2 — — — — — — — 3 9/32 2 2 3/8 — — — — 25
TXQC1 65
3 240 — 3 15
TQDL 125-200 2 120/240 — — 10 — — — — — — 6 1/16 2 2 3/8 — — — — 12
THQDL 125-200 2 120/240 — — 22 — — — — — — 6 1/16 2 2 3/8 — — — — 12
100-225 2 240 10 10 2 3/4 — 1
TQD1 — — — — — — — 6 9/16 2 5/8 2 7/16 2 7/16 27/32
100-225 3 240 — 10 4 1/8 11/16 1
100-225 2 240 22 22 2 3/4 — 1
THQD1 — — — — — — — 6 9/16 2 5/8 2 7/16 2 7/16 27/32
100-225 3 240 — 22 4 1/8 11/16 1
2 240 22 22 10 1
TJD 250-400 — — — — — — 10 1/8 8 1/4 3 13/16 3 15/16 3 13/16 1 3/8 1 3/16
3 240 — 22 1
CB3 Ground Fault, Equipment Ground Fault and Arc Fault (UL File E-51075; Fixed Thermal Magnetic Trip Unit)
THQB
1 120 10 — 1 10
THQC
THQL 15-30 — — — — — — — 3 9/32 2 3/8 — — — —
...GF, GFEP, 2 120/240 — 1 2 10
AF
THHQL
...GF
THHQB 15-30 1 120 — 22 — — — — — — — 3 9/32 1 2 3/8 — — — — 10
...GF
AF
1 UL listed as HACR (heating, air conditioning and refrigeration).
2
Not UL listed.
46
Spectra Series® Switchboards
Section 5 – Application Data
TEY and TEYF (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CUL LR 57114)
UL Listed Interrupting Ratings— kA
Maximum
Voltage Rating Vac Vdc Dimensions (In.) Approx.
Circuit Ship
Breaker Ampere No. 120/ Wt./Std.
Type Rating Poles ac dc 120 240 240 277 480 600 125 250 5001 H W D A B C E Pack
1 277 125 65 14 14 — 10 — — 1
TEY2 15-100 2 250 — — — 10 — 5 1/4 2 3 1/16 — — — — —
— 5
480/277 65 14 14
3 — — — — 3
1 277 125 65 14 14 — 10 — — 1
TEYF2 15-100 2 250 — — — 10 — 5 1/4 2 3 1/16 — — — — —
— 5
480/277 65 14 14
3 — — — — 3
E150 (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CUL LR 57114)
1 120 125 10 — 5 — — 1 3/8 26 lb/24
—
2 3 2 250 — — — — — 5 — 6 5/16 2 3/4 3 3/8 2 41/64 2 15/64 23/32 24 lb/12
TEB 10-100
240 — 10
3 — — — — 4 1/8 11/16 28 lb/8
10-100 3 1 277,347 4 125 — 14 10 — 10 — — 1 3/8 26 lb/24
—
TED2 3 2 480 250 — — — 10 — 6 5/16 2 3/4 3 3/8 2 41/64 2 15/64 23/32 24 lb/12
10-150 18 — 18 —
3 480, 600 500 14 — 10 4 1/8 11/16 28 lb/8
15-30 1 277,347 4 125 — 65 — — 20 6 — — 1 3/8 — 26 lb/24
15-100 2 480 250 65 — 20 6 — 24 lb/12
THED 2 — — 6 5/16 3 3/8 2 41/64 2 15/64 23/32
65 — 25 — 4 1/8 11/16
15-150 3 600 500 18 — 10 28 lb/8
42
K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CUL LR 40350)
2 250 10 — 33 lb/1
TKM8 300-800 600 — — 42 — 30 22 — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
3 500 20 22 39 lb/1
2 38 lb/1
TKM12 600-1200 600 — — — 42 — 30 22 — — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
3 41 1/2 lb/1
2 250 40 — 33 lb/1
THKM8 300-800 600 — — 65 — 35 25 — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
3 — 40 22 39 lb/1
2 38 lb/1
THKM12 600-1200 600 — — — 65 — 35 25 — — — 15 1/2 8 1/4 5 1/2 8 9/16 5 11/16 1 3/8 5/8
3 41 1/2 lb/1
1 UL listed with poles in series for 500 Vdc ungrounded battery applications. 3 10 amp not UL listed. 5 480Y/277 Vac.
2 UL listed as HACR (heating, air conditioning, and refrigeration). 4 UL listed/CUL Certified for 10kA @ 347 Vac (TED) and 6 UL listed at 10,000 amps
18kA @ 347V (THED). Also rated 10kA @ 480V but not UL listed.
47
Spectra Series® Switchboards
Section 5 – Application Data
SE 150
Spectra® RMS Circuit Breakers UL/CUL Ratings
Solid-State with Interchangeable Trip Unit (Rating Plug)
Circuit UL Listed Interrupting Rating—kA Dimensions Inches (mm) Approx. Ship
Breaker Ampere No. Maximum Wt./Std.
Type Rating Poles Vac 240 Vac 480 Vac 600 Vac H W D A B C E Pack
SE150 Current Limiting (UL File No. E-11592; CUL LR 40350)1
2 480 —
SED2, 3 18 18
3 600 14
15-150
2 480 —
SEH2 65 25
3 600 18 6.31 4.12 3.38 2.41 2.47 .69 .72 5.65 lb/1
2 480 — (160) (105) (86) (61) (63) (18) (18)
SEL 100 65
3 600 25
15-150
2 480 —
SEP 200 100
3 600 25
SF-250 Current Limiting (UL File No. E-11592; CUL LR 40350)1
2 480 —
SFH2 70-250 65 35
3 600 22
2 480 —
10.12 4.12 3.81 3.87 3.87 .69 1.19 9.15 lb/1
SFL 100 65
3 600 25 (257) (105) (97) (98) (98) (18) (30)
70-250
2 480 —
SFP 200 100
3 600 25
SG600 Current Limiting (UL File No. E-11592; CUL LR 40350)1,4
2
SKL12 600-1200 600 100 65 42
3
2
SKP12 600 200 100 65
3
1 UL listed as HACR (heating, air conditioning and refrigeration). 5 microEntelliGuard™, MicroVersaTrip® Plus and MicroVersaTrip PM® Trip Units only.
2 Not current-limiting circuit breaker. 6 Add 1.76 inches (45 mm) to each end with lugs and lug cover installed.
3 UL List as HID (high intensity discharge). 7 Add 4.00 inches (101 mm) to upper end for SKP (100 kAIC-480V) lug cover.
4 Includes microEntelliGuard™, MicroVersaTrip® Plus and MicroVersaTrip PM® Trip Units.
48
Spectra Series® Switchboards
Section 5 – Application Data
FG 600
49
Spectra Series® Switchboards
Section 5 – Application Data
50
Spectra Series® Switchboards
Section 5 – Application Data
Bus
Ground
SPD
Neutral
Display
51
Spectra Series® Switchboards
Section 5 – Application Data
52
Spectra Series® Switchboards
Section 5 – Application Data
The EPM 6000 excels in metering energy accurately The EPM 9650 is GE’s most advanced 9000 meter with
exceeding ANSI C12.20 (0.2%) and IEC 687 (0.2%) energy advanced power quality capability and waveform
measurement standards. The unit utilizes high speed recording functions. The unit utilizes ACCU-Measure®
DSP technology with high resolution A/D conversion to Technology to provide highly accurate revenue grade
provide revenue certifiable accuracy for utility billing, readings coupled with advanced data analysis. The
substation metering, sub-metering and critical metering unit measures over 15,000 electrical parameters
applications. including real time harmonics to the 127th order, voltage
surges and sags, waveform recordings, transients and
Features and Benefits a large assortment of advanced monitoring functionality.
• High accuracy Multifunction Power meter The unit also provides advanced expandable I/O with
• Superior performance at competitive pricing up to 256 points for control, data acquisition and alarms
• Ultra compact, easy to install, program and use functions. This meter is ideally suited for critical power
• 0.2% Class Revenue Certifiable energy and demand applications, common couplings with Utilities, load or
metering process control and most other power monitoring
• Fits both ANSI and DIN cut-out applications.
• Large 3 line .56” bright LED display for better visibility
and longer life Features and Benefits
• User programmable for different system voltages • Power/Energy accuracy better than 0.04% provide
and current measurements highest grade revenue accuracy
53
Spectra Series® Switchboards
Section 5 – Application Data
• Harmonics measurements to the 127th order including • Medium and low voltage systems
%THD and K-Factor in real time • Commercial, industrial, utility
• Waveform Scope Mode on all channels • Flexible control for demand load shedding, power
• Multiple Historical, Alarm and Power Quality Logs factor, etc.
• Advanced Waveform Recording and Analysis • Power Quality analysis tool
• Up to 512 Samples per Cycle Resolution Protection and Control
• Four digital communication ports with standard • A V W var VA varh Wh PF Hz unbalance
Modbus Protocol • A W var VA demand
• Advanced Alarms and Control Set-Point Functions • Load shedding
• Up to 256 points of expandable I/O • Power factor control
• 3 Line LED or Touch-Screen LCD displays • Pulse input totalizing
• Ideal for critical loads, site-wide monitoring, power Monitoring and Metering
transformers, transmission lines, feeders, and generators • Ia Ib Ic In
• Va Vb Vc Vab Vbc Vca
• V I unbalance
PQMII Power Quality Meter • True PF crest and K factor
• Hz W var VA
• Wh varh VAh W cost
• Demand: A W var VA
• Harmonic analysis through 63rd with THD and TIF
• Event recorder - 150 events
• Waveform capture
• Data logger - 98,000 events
The PQM II is an ideal choice when continuous moni- • Voltage Disturbance Recorder (VDR)
toring of a three phase system is required. It provides User Interface
metering for current, voltage, real and reactive power, • Front RS232 serial port (1,200 to 19,200 bps)
energy use, cost of power, power factor and frequency. • Two Rear RS485 serial ports
Programmable setpoints and 4 assignable output • Ethernet connectivity provided by MultiNet
relays allow control functions to be added for specific • EnerVista software is provided for setup and monitoring
applications. This includes basic alarm on over/under functions
current or voltage, unbalance, demand based load • Dial-in modem capabilities
shedding, and capacitor power factor correction control.
More complex control is possible using the 4 switch
inputs which also can be used for status such as
breaker open/closed, flow information etc. 5.11 Equipment Ground Fault Protection
The National Electrical Code Section 230-95 requires
New In Version 2.10: ground fault protection of equipment for solidly
• Voltage Disturbance Recorder (VDR) to monitor voltage grounded wye electrical service of more than 150 volts
dips (voltage sags) and voltage spikes (voltage swells) to ground, but not exceeding 600 volts, phase-to-phase,
with capacity for 500 sag/swell events. for each service disconnecting means rated 1000
• DNP 3.0 Communications Protocol standard feature. amperes or more. The maximum setting of the ground
Features and Benefits fault protection shall be 1200A and the maximum time
• Mounting Versatility delay shall be one second for ground fault currents
• Keypad with large illuminated 40-character display equal to or greater than 3000A. The following discus-
• Any assignable output may be used to trigger an alarm sion applies only to solidly grounded wye systems.
• May be connected to DCA or SCADA systems Ungrounded and resistance grounded systems require
• Flash upgradable special considerations and should be referred to your
• Compatible with MultiNet Serial to Ethernet Converter local GE representative.
Applications
• Metering of distribution feeders, transformers, gener- The NEC requirement is for ground fault protection
ators, capacitor banks and motors only on the main protective device. This is satisfactory
54
Spectra Series® Switchboards
Section 5 – Application Data
only if loss of power to the entire system is acceptable Break insulated case circuit breakers, WavePro low
under ground fault conditions. If not acceptable, then voltage power circuit breakers and molded case circuit
ground fault protection should be applied on successive breakers are self-powered. The consist of three compo-
downstream protectors until an acceptable level of nents, a programmer, current sensors and flux shifter,
system outage is obtained. The NEC recognizes this which are integral parts of the circuit breaker.
lack of selectivity and requires health care facilities
which have ground fault protection to have two levels The EntelliGuard TU and Power Plus trip units can be
with selectivity between the main and feeder devices. used to detect ground fault current as it flows out from
the source, or as it returns to the source, A neutral
Detection of Ground Fault Current sensor (current transformer) is available for systems
Ground fault current may be monitored as it flows out with neutral loading.
from the source or as it returns to the source. In either
case, care must be exercised to ensure that there is When monitoring the outgoing ground fault current,
not ground connection on the neutral downstream the currents in each phase and neutral, if used, are
from the ground fault sensors, and that systems with summed up vectorially. In the absence of ground fault
neutral interties and multiple grounds have ground currents, the vector sum of the phase and neutral
fault sensors properly placed and connected so that all currents, IG is zero. When a ground fault occurs, the
returning ground fault current is detected. Spot networks, vector sum, IG corresponds to the ground fault current.
secondary selective arrangements (main-tie-main) and When ordering the EntelliGuard TU unit, suffix G provides
systems with emergency generators are the most fre- integral ground fault protection.
quently encountered examples of multiple ground and
neutral interties which require special consideration. G N A B C
Power
Fortunately, the most commonly encountered system, Supply
and
Phase
the radial, lends itself to straightforward designs. Function Trip
Ground Function
Function
Ground Fault Equipment To
Ground fault protection may be supplied as an integral Protection
Device
part of the trip unit used with molded case, insulated
case and WavePro low voltage power circuit breakers.
NEC230-95(c) reads as follows: the ground fault protection When monitoring the returning ground fault current,
system shall be performance tested when first installed. the EntelliGuard TU unit with suffix GR is ordered. The
The test shall be conducted in accordance with approved neutral CT is placed in the ground return circuit, not
instructions which shall be provided with the equipment. the neutral circuit. The trip unit responds to the current
A written record of this test shall be made and shall be which the CT sees. Extreme care must be taken to insure
available to the authority having jurisdiction. that the CT is placed to detect all of the returning
ground fault currents.
Testing by qualified personnel
Performance testing of the ground fault protection sys-
tem should be undertaken only by qualified personnel.
GR R
Particularly in the tests requiring the use of a high-current
test set, it is usually necessary to obtain the services of To
A B C N
a qualified testing organization. General Electric's Protective
Device
Installation and Service Engineering organization, the
Apparatus Service Shops, and GE's extensive FAS
(Factory Authorized Service) Teams are qualified and
equipped to provide this testing service. Ground Fault Relays
ITI ground fault relays and sensors are designed to
EntelliGuard TU Trip Units form a system for detecting a ground fault current on
EntelliGuard TU and Power Plus units used on Power a ground ac power system. When a ground fault
55
Spectra Series® Switchboards
Section 5 – Application Data
To A
Protective
G N A B C Device GRD
GSR Phase Bus
52-BT
56
Spectra Series® Switchboards
Section 5 – Application Data
57
Spectra Series® Switchboards
Section 5 – Application Data
58
Spectra Series® Switchboards
Section 5 – Application Data
• “Test-Norm” keyed test switch. This maintained contact UPS ON MAIN #1 CLOSED GEN CLOSED Exerciser Tuner
XFER NO-XFER
59
Spectra Series® Switchboards
Section 5 – Application Data
3. The switch should now be in the UPS enable position. Manual control
If not, turn switch to this position. Manual transfer
4. If UPS fails and power is still available, the UPS will 6. To manually transfer load from normal to alternate
be bypassed to allow power to PLC. source (when normal source is still available):
5. If replacing the UPS, turn selector to UPS bypass. This – Turn the keyed selector switch to “Manual.”
will allow the UPS to be shut down without disturbing – Turn the keyed test switch to “Test.” Engine starts
the PLC. Caution: Wiring to UPS circuit is still alive! if normal source fails, engine will start automatically.
6. If for some reason the power is lost while the selec- – Alternate source available light indicates when
tor switch is in UPS bypass position, the UPS will not voltage and frequency are more than 98%.
supply power to the PLC. Turn selector switch to UPS – Use breaker control switches to trip normal breaker
enable position to allow the UPS to power the PLC. and close alternate breaker.
60
Spectra Series® Switchboards
Section 5 – Application Data
61
Spectra Series® Switchboards
Section 5 – Application Data
• Indicating light show the following: 4. Testing – use the keyed test switch to simulate loss
ATO: of normal or alternate source.
Green – Breakers open
Red – Breakers closed Manual operation –selector switch on manual
Amber – Breaker trip by overcurrent 1. Use breaker control switches to transfer loads.
White – Source power available
Blue – Manual mode of operation Interlock prevents closing all three breakers.
UPS (if used):
White – UPS on Overcurrent trip lockout – to reset, push breaker trip
Green – PLC control power available button.
• Breakers are electrically interlocked to prevent the
sources from being paralleled.
• Bypass switches on drawout breakers disconnect UPS operating instructions
automatic closing and tripping control from a fully Typical operation – selector switch on UPS enable
withdrawn breaker. 1. Upon start-up, UPS will be on and charging without
• Manual retransfer to normal instead of automatic output. The UPS will be bypassed if UPS switch is in
retransfer is readily accomplished by using the stan- UPS enabled or UPS bypass position. PLC control
dard controls. This is done by turning the selector power light should be on.
switch to manual any time after an automatic transfer 2. To enable output, press the test button on the UPS until
from normal to alternate source, but before the end a short beep is heard. The UPS on light will turn on.
of the retransfer timing period. Then the load may be 3. The switch should now be in the UPS enable posi-
transferred back to the normal source by using the tion. If not, turn switch to this position.
breaker control switches to trip the alternate (or bus 4. If UPS fails and power is still available, the UPS will
tie) breaker and close the normal breaker. be bypassed to allow power to PLC.
5. If replacing the UPS, turn selector to UPS bypass. This
will allow the UPS to be shut down without disturbing
UPS ON MAIN #1 CLOSED TIEN CLOSED MAIN #2 CLOSED
the PLC. Caution: Wiring to UPS circuit is still alive!
WHITE RED RED RED 6. If for some reason the power is lost while the selec-
MAIN #1 TRIPPED TIEN TRIPPED MAIN #2 TRIPPED SOURCE #1 AVAIL.
tor switch is in UPS bypass position, the UPS will not
supply power to the PLC. Turn selector switch to UPS
AMBER AMBER AMBER WHITE
enable position to allow the UPS to power the PLC.
PLC MAIN #1 OPEN TIEN OPEN MAIN #2 OPEN
CONTROL POWER SOURCE #2 AVAIL. MANUAL MODE
Automatic control
GREEN GREEN GREEN GREEN WHITE BLUE
Normal control
UPS UPS
ENABLE BYPASS
OPEN CLOSE OPEN CLOSE OPEN CLOSE Normal
TEST 1 TEST 2 MANUAL AUTO 1. When both normal sources are available at rated
voltage and the selector switch is on auto, the bus
* Key Operator # Key Operator
tie breaker will be open and both main breakers will
NOTE: Ship in UPS Bypass!
be closed, serving their respective loads.
*Key operated switch with key removal in all (3) positions
#Key operated switch with key removal in both positions Automatic transfer
2. When source voltage on one of the normal sources
drops below the dropout setting of the 3-phase
Operating instructions undervoltage relay:
Three-breaker automatic throwover – After 5 second time delay (PLC adj.), the main
Automatic operation – keyed selector switch on auto breaker will open and the bus tie breaker will close,
1. When normal source fails, its load is transferred to transferring the load to the alternate source
the alternate source.
2. When normal source is restored, retransfer takes Automatic retransfer
place automatically after delay. 3. When normal service is restored, automatic retransfer
3. If manual retransfer is preferred, turn the keyed will take place after a timing period of 15 min. (PLC
selector switch to manual after transfer to alternate adjustable). Should normal power be restored and
source. the alternate power source lost during the retransfer
62
Spectra Series® Switchboards
Section 5 – Application Data
timing period, the load will be instantaneously trans- Overcurrent lockout and reset
ferred back to the normal source. For manual 8. When a breaker trips on overcurrent, it will be
retransfer after automatic transfer, see step 7. locked out electrically and mechanically to prevent
reclose until hand reset. This is indicated by its
Testing amber indicating light. To reset, push the yellow bell
4. Loss of either normal source may be simulated by alarm button on the breaker.
turning the keyed test switch to “Test.” This will initiate
transfer as described in step 2. The load will be sup- Interlocking
plied from the alternate source as long as the test 9. Interlocking provisions prevent interconnections of
switch is left in the “Test” position. Return the keyed normal and alternate sources. All breakers may be
test switch to “Normal” and retransfer will proceed in the open position, but only two can be in the
as described in steps 3 and 4. closed position simultaneously.
63
Spectra Series® Switchboards
Section 5 – Application Data
Lug sizes and quantity also apply to main devices Minimum Cable Bending Space Reference Tabulation
Standard Main Lug Terminations (75°C Cable Ampacity Rating Applies)
Ampere Quantity and Size Lug Conductor MCM Size Cable Bending
Amps
Qty Al Cu 500 750 Space
Rating Per Ø and Ñ 3 x x 12
800 (3) 250-600 MCM 2 x x 16
800①
3 x x 12
1000 (4) 250-600 MCM
3 x x 19
1200 (4) 250-600 MCM 3 x x 12
1600 (6) 250-600 MCM 3 x x 19
1000①
4 x x 13
2000 (7) 250-600 MCM 3 x x 19
2500 (9) 250-600 MCM 4 x x 13
3 x x 19
3000 (10) 250-600 MCM 1200①
4 x x 13
4000 (13) 250-600 MCM 4 x x 21
5000 (15) 250-600 MCM 5 x x 13
4 x x 21
6000 (18) 150-600 MCM 1600
6 x x 13
Note: Lug sizes do not apply to Class I group mounted MCCB mains. Quantity will vary. 5 x x 21
Chart based on 500 MCM AL cable rated at 310 amps per cable. 6 x x 13
5 x x 21
2000
7 x x 13
6 x x 21
Standard Lug sizes unless otherwise noted 7 x x 13
6 x x 21
Lugs Cable Range Cable Material Qty. Holes 2500
9 x x 13
#14 - 1/0 CU/AL 1 7 x x 21
#6 - 2/0 CU/AL 1 8 x x 13
Aluminum #6 - 350MCM CU/AL 1 7 x x 21
3000
Mechanical 10 x x 13
1/0 - 600MCM CU/AL 1
8 x x 21
3/0 - 800MCM CU/AL 1 11 x x 13
500 - 1000MCM CU/AL 2 9 x x 21
4000
#14 - 2/0 CU 1 13 x x 13
Copper 11 x x 21
#6 - 350MCM CU 1
Mechanical 14 x x 13
300 - 800MCM CU 1
11 x x 21
#8 - 1/0 CU/AL 1 5000
17 x x 13
2/0 - 4/0 CU/AL 1 13 x x 21
#4 - 300MCM CU/AL 1 ① Compression lugs are provided at 100 KA
Aluminum 250 - 350MCM CU/AL 1
Compression 2/0 - 500MCM CU/AL 1 or 2
400 - 600MCM AL 1 or 2 Standard Fusible Switch Module Terminations (Cu/Al Mechanical)
500 - 750MCM AL 1 or 2 Amp Rating Voltage Wire Size (Cu/Al) # Wires Per Pole
750 - 1000MCM AL 2 30 240/600 #14-#2 1
#6 - 1/0 CU 1 60 240 #14-#2 1
Copper 2/0 - 300MCM CU 1 60 600 #14-1/0 1
Compression 250 - 500MCM CU 1 or 2 100 240/600 #14-1/0 1
200 240/600 #6-250 MCM 1
500 - 750MCM CU 1
400 240/600 1/0-250 MCM or #2-600 MCM 2 or 1
600 240/600 1/0-250 MCM or #2-600 MCM 4 or 2
800 600 1/0-250 MCM or #2-600 MCM 6 or 3
1200 600 1/0-250 MCM or #2-600 MCM 8 or 4
64
Spectra Series® Switchboards
Section 5 – Application Data
Optional Fusible Switch Module Terminations Molded Case Circuit Breaker Lugs, Line Shields,
Max # Wires Per Pole Covers and Bus Connectors
60A 60A Catalog
30A 100A 200A 400A 600A 800A 1200A Accessory Wire Size For Use With
240V 600V Number
Cu/Al Mechanical #14-6 Cu, #12-2 Al TQC (15-60A) TQAL 3
#6 - 350 MCM 1 2 2 4 4 #4-1/0 Cu-Al TQC (70-100A) TQAL 4
3/0 - 800 MCM Cu #1-300 MCM TQD TCAL 25
250 - 800 MCM Al E150, THLC1, TB1
#14-8 TCAL 14
(15-30A)
Cu Mechanical E150, THLC1, TB1
#14-3 Cu, #12-1 Al TCAL 12
#4 - #14 1 1 (15-60A)
#6 - #14 1 E150, THLC1, TB1
#6-2/0 Cu, #4-2/0 Al TCAL 12A
(70-90A)
#6 - 1/0 1 1 E150, THLC1, TB1
#6 - 250 MCM 1 #3-3/0 Cu, #1-3/0 Al TCAL 15
(100-150A)
1/0 - 600 MCM 2 2 4 #4-300 MCM F225 Load end TCAL 24
1/0 - 4/0 4 4 8 4 Line end TCAL 26
Copper-
Cu/Al Compression Aluminum J400, J600 (thru 400A)
#8 - 1/0 1 1 1 1 Lugs (1) 6-600 MCM or
TJD TCAL 43
(2) 2/0-250 MCM
#4 - 300 MCM 1 (2) 4/0-350 MCM Cu or
J600 (45-600A) TCAL 63
2/0 - 500 MCM 2 2 4 4 (2) 300-500 MCM Al
400 - 500 MCM Cu 2 2 4 4 (1) 750 MCM Cu-Al J400, TJD TCAL 47
400 - 600 MCM Al 2 2 4 4 (2) 3/0-250 MCM Cu-Al
750 - MCM Cu 2 2 4 4 (2) 1/0-250 MCM or
K1200 TCAL 41
(1) #4-600 MCM
500 - 750 MCM Al 2 2 4 4
(2) 2/0-500 MCM K1200 TCAL 61
Cu Compression
(3) 3/0-500 MCM K1200 TCAL 81①➁
#6 - 1/0 1 1 1 1
(4) 250-350 MCM or TCAL 121➃
2/0 - 300 MCM 1 K1200 (1000-1200A)
(4) 250-500 MCM Al
250 - 500 MCM 2 2 4 4 (4) 250-350 MCM TK4V - Load end TCAL 131➃
400 - 750 MCM 2 2 4 4 #14-2/0 E150, TB1 (thru 150A) TCO 12
#1-300 MCM TQD (100 -225A) TCT 25
F225 Load end TCO 24
#14-300 MCM Line end TCO 26
Copper Only (1) 6-600 MCM or
J400 TCO 43
Lugs with (2) 2/0-250 MCM
Follower and (2) 250-350 MCM J600 TCO 63
Extra Plating (1) 1/0-600 MCM or
K1200 TCO 41➁
(2) 1/0-250 MCM
(2) 2/0-500 MCM K1200 TCO 61
(3) 250-500 MCM K1200 (700-1000A) TCO 81A
(4) 250-400 MCM K1200 (1200A) TCO 121
TEB, TEC, TED, THED TEDLS
Line Shield TFH and TFK TFKLS
TJJ and TJK TJKLS
TCO41, TCAL41 Lugs 789A448G3➂
Lug Cover,
TCO61, TCAL61,
TKM Breaker
(two per TCAL81 Lugs, TCO81A 789A448G1
breaker) TCO121; TCAL 121
789A448G2
Lugs
Connector
TKM TKMC1
(back strap)
① Not suitable for 1000-amp aluminum conductor.
➁ Not UL listed.
➂ End cover supplied with 800A frame is used as lug cover.
➃ Suitable for 500 MCM copper for voltage drop considerations.
65
Spectra Series® Switchboards
Section 5 – Application Data
66
Spectra Series® Switchboards
Section 6 – Additional GE Switchboard Offerings
67
Spectra Series® Switchboards
Section 6 – Additional GE Switchboard Offerings
Record Plus
Frame 100A 250A 600A
Size FBV/FCV FBN/FCN FBH/FCH FBL/FCL FCS FEN FEH FGN FGH FGL FGP
240Vac 65 150 200 200 42 150 200 150 200 200 200
480Vac 35 65 100 150 25 65 100 65 100 150 200
600Vac 22 25 35 42 18 — — 25 35 42 65
68
Spectra Series® Switchboards
Section 6 – Additional GE Switchboard Offerings
69
Spectra Series® Switchboards
Section 6 – Additional GE Switchboard Offerings
Main Devices➄
Insulated Case Circuit Breakers Height Width Depth
Stationary
800
Drawout 14"
Stationary 22" Std
1600
Drawout 30" Opt
Stationary 50", 60"
2000
Power Drawout 21"
Break II Stationary
2500
Drawout 35" 22" Std
Stationary 30" Opt
3000
Drawout
22" Std
4000➅ Drawout 42" 60"
30" Opt
➀ Feeder devices can be located in the same section with mains rated 3000A and lower.
➁ Requires 7" blank at top to meet 6’6" rule.
➂ Maximum 3 per stack with 21" blank.
➃ Maximum 2 per stack with 14" blank.
➄ A 2" transition is needed when using a Power Break II or AKR main device.
➅ Selections adjacent to a 4000A device or AKR breaker must be a minimum of 30"
wide. Add 2" for non walk-in outdoor construction.
Breaker type Device combination Frame size Breaker cubicle Minimum section Minimum equipment Optional
or bus rating (amperes) vertical height width ③ depth [Front/Rear equipment
(inches) (inches) compt] (inches) depth (inches)
WPS-08
WPH-08 800 60 [30 / 30] 67/74
WPX-08
WPF-08 21 22 67 [37 / 30] 74/81**
WPS-16 60 [30 / 30] 67/74
WPH-16 1600 60 [30 / 30] 67/74
WPF-16 67 [37 / 30] 74/81**
WPS-20 60 [30 / 30] 67/74
WPS-20 with fuse roll-out 2000 56 60 [30 / 30] 67/74/81 ➁
WPS-32 30 60 [30 / 30] 67/74/81 ➁
WPH-32 35 60 [30 / 30] 67/74/81 ➁
3200
WPX-32 60 [30 / 30] 67/74/81 ➁
WPS-32 with fuse roll-out 84 38 60 [30 / 30] 67/74/81 ➁
WPS-40 35 30 60 [30 / 30] 67/74/81 ➁
WPX-40 4000 35 30 60 [30 / 30] 67/74/81 ➁
WPS-40 with fuse roll-out 84 38 67 [37 / 30] 74/81**
WPS-50 74 [37 / 37] 81**
WPX-50 5000 35 38 74 [37 / 37] 81**
WPS-50 with fuse roll-out ➀ 74 [37 / 37] 81**
1600-4000A main bus rating — — — 60 [30 / 30] 67/74
5000A main bus rating — — — 67 [30 / 37] 74/81 ➁
➀ Breaker and fuse roll-out must be mounted in separate vertical sections
➁ 81" depth available only when these devices are used in a line-up with items identified with **
③ Section width can be increased for additional cable / conduit space. 22" sections can be increased to 30" wide, 30" wide sections can be increased to 38" wide.
70
Spectra Series® Switchboards
Section 7 – CSI Specifications
71
Spectra Series® Switchboards
Section 7 – CSI Specifications
9. Main horizontal bus bars shall be [standard tapered and negative energy.
per UL] [fully rated and arranged for future extensions]. d. The Monitor shall record and store total bi-directional
E. Enclosure accumulated energy and total accumulated apparent
1. Switchboard(s) shall be [NEMA 1] [NEMA 3R non walk-in] energy.
[NEMA 3R walk-in] deadfront construction or as indicated e. The Monitor shall monitor max/min average demand
on drawings. values for all current and power readings. The demand
2. NEMA 3R construction shall be as listed below. interval shall be user programmable. [Maximum
a. Consist of standard indoor cubicles with a front frame and minimum values shall be stored with a
and roof assembly to provide a weather resistant date/time stamp.]
structure. Filtered front and rear roof vents. Space
heaters [fed from control power transformer in NOTE TO SPECIFIER: THE FOLLOWING REFLECTS CAPABILITIES OF
switchboard.] [fed from separate source as indicated THE EPM6000:
on drawings.] 4. The Monitor shall have an accuracy of +/- 0.1% or better
b. Front hinged doors with 3 point catch with padlocking for volts and amps, and 0.2% for power functions,
provision and wind stop. Bolted rear covers. and shall meet IEC687 (0.2%)
c. Walk-in construction shall have a minimum 30 inch 5. The monitor shall include a three line, integrated,
wide clear walk through space light-emitting diode (LED) display.
d. [Front to rear full depth lifting beams.] a. The Monitor must be capable of displaying one leg
e. Include the following options of volts, amps and total power simultaneously.
(1) Thermostatic control for space heaters. b. The display shall provide user access to all phase
(2) Gasketing. voltages (phase to neutral and phase to phase),
(3) [Fluorescent lighting and convenience outlets.] currents (phase and neutral) , watts, VARs, VA,
(4) [Rear hinged doors with 3 point catch with power factor, frequency and kwh
padlocking provision and wind stop.] c. The display must provide user access to max/min
F. Utility Metering Section values for all displayed quantities.
1. Provide utility metering section where indicated on d. The display shall have a % load bar display for
drawings. Pull section and metering compartment shall ease of full load viewing
comply with [EUSERC and] [utility name] requirements. 6. The monitor shall be microprocessor based and shall
2. Compartment shall be barriered from the rest of the be fully user programmable.
section, have a hinged lockable front cover, removable 7. [The monitor shall be provided with an RS485 digital
bus links with provisions for mounting current trans- communications port. The Monitor shall communicate
formers, and when required, provisions for mounting using a MODBUS RTU protocol and shall have a
voltage transformers. Current and voltage transformers communication baud rate of at least 57k.]
shall be supplied and installed by the utility company. 8. [The monitor shall be provided with one KYZ pulse
G. User Metering outputs]
1. Provide a UL listed and digital multifunction power
monitor. The monitor case shall be fully enclosed and NOTE TO SPECIFIER: THE FOLLOWING REFLECTS CAPABILITIES OF
shielded THE GE PQMII METER
2. The monitor shall accept a voltage monitoring range 9. The Monitor shall have an accuracy of +/- 0.2% or
of up to 600 volts, phase to phase. better for volts and amps, and 0.4% for watts.
a. The Monitor shall withstand 200% rated current 10. Voltages and currents shall be sampled at 64 samples
continuously. It shall withstand 10X rated current per cycle.
for at least 3 seconds. Isolation shall be no less 11. The Monitor shall have up to 1MB of non-volatile RAM
than 2500V AC. for data trending and waveform capture.
b. Surge withstand shall conform to IEEE a. The monitor shall be capable of retaining historical
C37.90.1,62.41 and IEEE 1000-4 data in a non-volatile memory with a programmable
c. Shall have a standard ANSI C39.1 case mount. number for a single parameter. The user can select
3. The Monitor shall provide true RMS measurements of any combination of values to be stored.
voltage, phase to neutral and phase to phase; current, b. Interval of snapshots shall be triggerable on pro-
per phase and neutral; real power, reactive power, grammable changes of state of voltage and current.
apparent power, power factor and frequency. c. The Monitor shall store waveform events for all 6
a. The Monitor must be capable of providing readings channels of voltage and current for a minimum of
for both instantaneous and average readings. 100 events. Each event will consist of readings of
b. The Monitor must also be capable of providing all 60 cycles, 10 cycles prior to the event, and 50 cycles
single phase real, apparent, reactive power and past the event.
power factor values. d. Event recording shall be triggered when the RMS of
c. The Monitor shall record and store total bi-directional voltage or current exceeds user programmable
energy. It shall include separate registers for positive high-speed set points.
73
Spectra Series® Switchboards
Section 7 – CSI Specifications
e. The Monitor must be able to record each of the 8 samples per millisecond. All changes in status shall
channels of voltage or current per event if the be time stamped to the nearest millisecond and placed
event continues past the initial 60 cycles. Recording in an event log with time and event label information.
duration set-point shall be programmable.] 19. Power meter shall provide a separate IRIG-B input for
12. The Monitor shall have three serial communication time synchronizing to GPS time signal. IRIG-B input
port; 1 RS232C and 2 RS485. Ports must be capable shall accept un-modulated time signal input from a
of communicating simultaneously to different devices. standard GPS satellite clock.
13. The Monitor shall communicate using a MODBUS RTU 20. Power meter shall be equipped with 4MB of non-volatile
or DNP open protocol and support communications RAM for recording logs and programming information.
baud rates of up to 19.2K a. Meter shall store historical trending data, power quality
14. The Monitor shall calculate the harmonic signature, data, and waveform recordings in memory.
%THD and K-Factor for all voltage and current inputs b. In the event of loss of control power, data stored in
with valid data for harmonic spectrum capability to memory shall be retained for at least 10 years.
the 32nd harmonic. c. Memory shall be allocated to the various logging
15. The Monitor must be capable of capturing a graphic functions required. All logging features required
image of the waveform for each of the 6 channels of shall be simultaneously available at the specified
Voltage and Current and make it available in a RAM buffer levels. Exercising any one feature at the specified
for retrieval through the digital communication port. level shall not limit exercising of any or all other
features to their full, specified level.
NOTE TO SPECIFIER: THE FOLLOWING CAPABILITIES ARE FURNISHED d. Meter shall store all programming and set-up
ON THE GE EPM9650Q METER. parameters in non-volatile memory. In the event of
16. The monitor shall have the following minimum accuracy loss of control power, meter programming data stored
requirements. in memory shall be retained for at least 10 years.
a. Voltage accuracy shall be within less than 0.01% 21. Power meter shall measure and record the magnitude
for the 1 second readings and less than 0.1% for and phase angle of all harmonics through the 127th
the100 millisecond readings. for all voltages and currents. Meter shall provide %THD
b. Current accuracy shall be within less than 0.025% and K-Factor for all channels. All harmonic values
for the 1 second readings and less than 0.1% for shall be available through the digital communications
the 100 millisecond readings. ports in real time.
c. Power and energy accuracy shall be within less 22. Power meter shall capture and record all CBEMA
than 0.04% at unity PF and within 0.06% at 0.50 PF. quality events. CBEMA events shall be date/time
d. Frequency accuracy shall be within less than 0.001 Hz. stamped to the millisecond. Entries to CBEMA log shall
e. Power meter shall meet ANSI C12.20 and IEC 687 include date/time stamp, duration, and magnitude
accuracy requirements. information. The CBEMA log shall be downloadable
17. Power meter shall provide multiple digital communi- through the digital communications ports.
cation ports and support multiple open protocols. 23. Power meter shall capture and record out-of-limit
a. Meter shall include four (4) independent, digital conditions in a log. Entries to Limits log shall be made
communication ports. Each port shall be RS-485 anytime a monitored quantity exceeds the user set
architecture. Port 1 shall be user selectable as limit assigned to that quantity. Entries to the Limits
either RS-232 or RS-485 architecture. log shall be time stamped to the millisecond and
b. Each port shall be user configurable with regard to include the measured quantity value and label.
speed, protocol, address, and other communications 24. Power meter shall provide waveform recording to
parameters. All ports shall support a maximum capture and record transients and quality problems
communication speed of 115k baud simultaneously. on current and voltage waveforms. Meter shall sample
c. One communication port shall be configurable as waveform at a user configurable rate of 16 to 512
either a Master or a Slave port. The Master configu- samples per cycle (60Hz cycle).
ration shall enable the unit to act as an RTU and a. Meter shall hold at least 96 records of waveform
interface with other Modbus devices and EI I/O recording in non-volatile memory. Each record shall
Modules communicating using Modbus RTU protocol. be a minimum of 8 cycles in duration at the highest
d. Meter shall offer both Modbus and DNP 3.0 open sample rate or 64 cycles in duration at the lowest
protocols as standard configurations. All instanta- sample rate. Each waveform record shall include
neous data, logged data, event data, power quality pre-event and post-event data.
analysis and waveform information shall be available b. A waveform record shall be taken whenever the
using these open protocols. RMS value of voltage or current exceeds user-set
18. Meter shall have at least eight high-speed status inputs limits or a status change occurs on any one of the
for capturing external events. All high-speed status eight high-speed status inputs.
inputs shall be monitored at a user set rate from 1 to
74
Spectra Series® Switchboards
Section 7 – CSI Specifications
6. A charging handle, close push-button, open push- d. Short time pickup and delay. Short time pickup
button, and Off/On/Charge indicator shall be located shall be adjustable from 1.5 to 9 times the long
on the breaker escutcheon and shall be visible with time pickup setting in 0.5 increments with an OFF
the breaker compartment door closed. option. Provide minimum of 12 short time delay
7. Where drawout breakers are specified, the drawout bands with three selectable I2t bands.
design shall permit the breaker to be withdrawn from e. [Adjustable ground fault pickup and delay. Ground
an engaged position, to a test position, and to a dis- fault pickup shall be adjustable from 0.4 to 1.0
engaged position. times the breaker sensor rating in 0.05 increments.
8. Breaker digital electronic trip units shall be as Provide a minimum of 15 ground fault delay bands
described in Article 2.03.O. with three selectable I2t bands.] [Where indicated
N. Digital Electronic Trip Unit for Molded Case Circuit Breakers on the drawings provide GF alarm only function
1. Each main, feeder[, and tie circuit breaker shall be which shall operate an output control contact]
equipped with a digital electronic trip unit. The trip unit
shall provide protection from overloads, [and] short SPECIFIER NOTE: NEUTRAL PROTECTION MAY BE ADVISABLE IN
circuits [and ground faults]. The protective trip unit shall 120/208V APPLICATION OR OTHER APPLICATIONS WHERE EXCESSIVE
consist of a solid state, microprocessor based pro- TRIPLEN HARMONICS MAY BE ENCOUNTERED. TRIPLE HARMONICS
grammer; tripping means; current sensors; power supply CAN CAUSE NEUTRAL CURRENTS TO EXCEED 150% OF THE PHASE
and other devices as required for proper operation. CURRENT. IF THE NEUTRAL CONDUCTORS, INCLUDE EQUIPMENT
2. Furnish GE microEntelliGuard digital electronic trip BUS AND TERMINATIONS ARE NOT SUITABLY SIZED THIS COULD
units or equal that complies with all of the following. RESULT IN OVERLOADED CONDUCTORS OR EQUIPMENT.
3. The protective trip unit shall consist of a solid state, f. [Neutral Protection: Trip shall provide ability to protect
microprocessor based programmer; tripping means; against neutral conductor overload. Protection shall
current sensors; power supply and other devices as be the same as that for the phase conductors with
required for proper operation. settings at 50%, 100% or 150% of phase conductor
4. Long time and short time protective functions shall protection settings for long time and short time
have true RMS sensing technology for harmonic rich pickups and delays. Sensing shall be provided via a
currents including up to the 19th harmonic. neutral current sensor or from a summation
5. High contrast liquid crystal display (LCD) unit shall display calculation using phase current sensor signals.]
settings, trip targets, and the specified metering displays.
6. A multi-button keypad shall provide local setup and SPECIFIER NOTE: ZSI IMPLEMENTATION REQUIRES AT LEAST TWO
readout of all trip settings on the LCD. LEVELS OF CIRCUIT BREAKERS THAT HAVE ZSI CAPABILITY. THE
7. UL Listed interchangeable rating plug. It shall not be DOWNSTREAM BREAKER THAT SENDS THE SIGNAL AND THE
necessary to remove the trip unit to change the rating UPSTREAM BREAKER THAT RECEIVES IT AND ADJUSTS ITS PROTECTION
plug. Rating plugs shall be available in sizes from 40% TIMING ACCORDINGLY. GE SPECTRA MICROENTELLIGUARD G AND
to 100% of the breaker sensor rating K FRAME CBS ARE ABLE TO PROVIDE ZSI FOR THE INSTANTANEOUS
8. The trip unit shall have an integral test jack for testing via FUNCTION. INSTANTANEOUS ZSI ENABLES SELECTIVITY BETWEEN
a portable test set and connection to a battery source. THESE MOLDED CASE CIRCUIT BREAKERS AND SIMILARLY EQUIPPED
9. Noise immunity shall meet the requirements of IEEE ENTELLIGUARD G, OR WAVEPRO CIRCUIT BREAKERS UP TO THE
C37.90. FULL SHORT CIRCUIT RATING OR WITHSTAND RATING OF THE
10. The trip unit shall display trip targets for long time, LINE SIDE DEVICE.
short time, and ground fault, if included. g. [Zone Selective Interlocking for Short Time and Ground
11. Provide visual illuminated indication of the trip unit Fault protection.] [Zone Selective Interlocking for Short
(normal, pickup, trip, error). Time, Ground Fault and Instantaneous protection.]
12. The trip unit shall be provided with a ten event trip
history log. Each trip event shall be recorded with type, SPECIFIER NOTE: ALSO KNOWN AS A MAINTENANCE SWITCH OR
phase and magnitude of fault that caused the trip ALTERNATE SETTING GROUP. CALLED A RELT SETTING IN GE
13. As a minimum, the trip unit shall have the following LITERATURE. IN GE SWITCHBOARDS IT WILL BE PROVIDED ON
protective functions: INDIVIDUALLY MOUNTED BREAKERS ONLY, NOT ON GROUP MOUNTED
a. Current setting or long time pickup, adjustable from BREAKERS. A 3-POSITION SWITCH WILL BE PROVIDED THAT ALLOWS
50% to 100% of the rating plug value. TESTING OF CONTROL POWER AND INDICATES TRIP PROTECTIVE
b. Adjustable long time delay with typical inverse time STATUS VIA A CONTACT CLOSURE PROVIDED BY THE TRIP UNIT.
characteristics (minimum of 10 bands). In addition, h. [Reduced Energy Let-Through (RELT) Instantaneous
a set of straight line fuse shaped long time delay trip. When specified this feature shall be provided
bands shall be provided to facilitate selectivity with on individually mounted breakers to provide a tem-
downstream fuses (minimum 7 bands). porary setting for the instantaneous trip setting of
c. Instantaneous pickup, adjustable from 2.0 to 10 the breaker. Setting shall be adjustable down to
times the rating plug in 0.5 increments 1.5X of the rating plug and shall be enabled
76
Spectra Series® Switchboards
Section 7 – CSI Specifications
through a switch mounted on front of the switchboard. unit shall consist of a solid state, microprocessor
The switch shall be combined with an indicating based programmer; tripping means; current sensors;
light that positively indicates that the RELT is enabled power supply and other devices as required for prop-
or disabled.] er operation. Furnish GE Entelliguard TU digital elec-
14. The trip unit shall display rms current, each phase, on tronic trip units as specified below.
the LCD. 2. As a minimum, the trip unit shall have the following
protective functions unless otherwise indicated on the
SPECIFIER NOTE: INCLUDE THE FOLLOWING FOR ADVANCED drawings:
METERING OPTIONS: a. adjustable current setting or long time pickup;
15. [The following monitored values shall also be displayed b. adjustable long time delay (22 bands);
on the trip unit LCD: c. switchable, adjustable short time pickup and delay
a. Voltage, rms, line-to-line, or line-to-neutral; (11 bands) with 3 I2t selectable slopes;
b. Energy, KWH, total; d. adjustable instantaneous pickup;
c. Demand KWH, over an adjustable time period of 5 e. [adjustable ground fault pickup and delay] [Where
to 60 minutes; indicated on the drawings provide GF alarm only
d. Peak demand, KW, user resettable; function]
e. Real power, KW, line-to-line, line-to-neutral; f. [Reduced Energy Let-Through (RELT) Instantaneous
f. Total (apparent) power, KVA, line-to-line, line-to-neutral. trip. When specified this feature shall be provided to
g. Reactive Power, KVAR, line-to-line, line-to-neutral. provide a temporary setting for the instantaneous
h. Power Factor (%) trip setting of the breaker. Setting shall be adjustable
i. Frequency (Hz)] down to 1.5X of the rating plug and shall be enabled
16. Trip shall be provided with serial communications through a switch mounted on front of the switchboard.]
using Modbus RTU protocol. Manufacturerís literature
shall provide full register map. SPECIFIER NOTE: ZSI IMPLEMENTATION REQUIRES AT LEAST TWO
17. Trip unit shall provide waveform capture capability for LEVELS OF CIRCUIT BREAKERS THAT HAVE ZSI CAPABILITY. THE
fault events. Capture data shall include 4 cycles before DOWNSTREAM BREAKER THAT SENDS THE SIGNAL AND THE
and 4 cycles after the event or can be initiated through a UPSTREAM BREAKER THAT RECEIVES IT AND ADJUSTS ITS PROTECTION
Modbus command. Data shall be provided in a Comtrade TIMING ACCORDINGLY. GE POWERBREAK II CBS ARE ABLE TO
file format for use by power management system. PROVIDE ZSI FOR THE INSTANTANEOUS FUNCTION. INSTANTANEOUS
18. If a manufacturerís trip unit can not incorporate the ZSI ENABLES SELECTIVITY BETWEEN THESE CIRCUIT BREAKERS
above specified metering functions, separate device(s) AND SIMILARLY EQUIPPED ANSI RATED ENTELLIGUARD G OR
with equal function shall be provided for each breaker WAVEPRO CIRCUIT BREAKERS UP TO THE FULL SHORT CIRCUIT
RATING OR WITHSTAND RATING OF THE LINE SIDE DEVICE.
SPECIFIER NOTE: INCLUDE THE FOLLOWING FOR PROTECTIVE g. [Zone Selective Interlocking for Short Time and Ground
RELAY OPTION: Fault protection.] [Zone Selective Interlocking for Short
19. [The following protective relay functions shall be provided. Time, Ground Fault and Instantaneous protection.]
User shall be able to enable or disable each option as 3. As a minimum, the trip unit shall include the following
required by the coordination study. If the manufacturers features:
trip unit cannot incorporate the specified functions, a. Long time and short time protective functions, if
separate device(s) with equal function shall be provided provided, shall have true RMS sensing technology
for each breaker. and thermal long time memory.
a. Undervoltage, adj. pickup, 50 to 90 percent; adj. b. Ground fault protective function, if provided, shall
delay, 1 to 15 seconds. contain a memory circuit to integrate low level arcing
b. Overvoltage, adj. pickup, 110 to 150 percent; adj. fault currents with time, to sum the intermittent
delay, 1 to 15 seconds. ground fault spikes.
c. Voltage unbalance, adj. pickup, 10 to 50 percent; c. High contrast liquid crystal display (LCD) unit shall
adj. delay, 1 to 15 seconds. display settings, trip targets, and the specified
d. Current unbalance, adj. pickup, 10 to 50 percent; metering displays.
adj. delay, 1 to 15 seconds. d. Multi-button keypad to provide local setup and
e. Reverse power, adj. pickup, 10 KW to 990 KW; adj. readout of all trip settings on the LCD.
delay, 1 to 15 seconds. e. UL Listed interchangeable rating plug. It shall not
f. Load alarm, adj. ON, 0.55 to 1.0 x Longtime pickup; be necessary to remove the trip unit to change the
adj. OFF, 0.5 to 0.95 x Longtime pickup.] rating plug.
O. Digital Electronic Trip Unit for Insulated Case Circuit Breakers f. An integral test jack for testing via a portable test
1. Each insulated case PowerBreak II breaker shall be set and connection to a battery source.
equipped with a digital electronic trip unit. The trip g. A mechanism for sealing the rating plug and the
unit shall provide protection from overloads, [and] trip unit.
short circuits [and ground faults]. The protective trip
77
Spectra Series® Switchboards
Section 7 – CSI Specifications
h. Noise immunity shall meet the requirements of ments (1 to 15 seconds) and shall be able to be
IEEE C37.90.2. switched OFF. If the manufacturers trip unit can not
i. Display trip targets for long time, short time, and incorporate the specified functions, separate device(s)
ground fault, if included. with equal function shall be provided for each breaker.
j. The trip unit shall keep a log of the last ten events a. Undervoltage, adj. pickup, 50 to 90 percent; 1%
including overcurrent trips, protective relay trips. increment adj. delay, 1 to 15 seconds.
The log shall store rms currents, phase, type of trip, b. Overvoltage, adj. pickup, 110 to 150 percent; 1%
trip counter, time and date for each event. increment adj. delay, 1 to 15 seconds.
k. Instantaneous trip shall utilize filtering which permits c. Voltage unbalance, adj. pickup, 10 to 50 percent;
fully selective operation with downstream current adj. delay, 1 to 15 seconds.
limiting devices up to the short time rating of the d. Current unbalance, adj. pickup, 10 to 50 percent;
circuit breaker, when the instantaneous pickup is 1% increment adj. delay, 1 to 15 seconds.
set above the current limiting threshold. e. Reverse power, selectable direction, adj. pickup, 10 KW
to 990 KW; 10kW increment adj. delay, 1 to 15 seconds.]
SPECIFIER NOTE: INCLUDE THE FOLLOWING FOR COMMUNICATION P. Individually Mounted Fusible Switches
OPTION: 1. Furnish GE type HPC high pressure contact fusible
l. [The trip unit shall include Modbus RTU communication switches.
capability. The trip unit, through dedicated secondary 2. High pressure contact fusible switches shall be butt
terminals on the breaker, shall provide a communication type contact construction with multiple, spring loaded
port for communication with and access to a remote com- main arms and an arcing arm per pole. An over-center
puter. All metering, setpoints, protective trip counts, and other toggle mechanism shall provide quick make, quick
event signaling shall be retrievable by the remote computer.] break operation.
4. The trip unit shall include the following metering functions, 3. Switches shall have a molded insulating case and
which shall be displayed on the LCD (if the manufacturers cover with integrally molded interphase partitions. All
trip unit can not incorporate the specified functions, current carrying parts shall be silver plated copper.
separate device(s) with equal function shall be provided 4. Fusible switches shall be equipped with mounting
for each breaker): provisions for UL class L fuses. Switches shall have an
a. Current, RMS, each phase; interrupting rating of 200 kAIC RMS SYM at 600V when
used with class L fuses. Provide a complete set of UL
SPECIFIER NOTE: INCLUDE THE FOLLOWING FOR METERING OPTION: class L fuses for each switch.
b. [Voltage, RMS (V), line-to-line or line-to-neutral. 5. Switches shall be rated for making and breaking 12
c. Energy (kWh, MWH, GWH), each phase and total, times nameplate rating current at 600 VAC. Switches
user resettable. shall be rated to carry 100 percent of their frame
d. Peak Power Demand (KW, MW), user resettable. ampacity continuously.
e. Real power (KW, MW), each phase and total. 6. Switches shall be manually operated and stationary
f. Reactive power (KVAR, MVAR), each phase and total. mounted. Switches shall have a front mounted operating
g. Apparent power (KVA, MVA) , each phase and total handle for charging the closing springs and closing the
h. Frequency (Hz). switch and a push-button for opening the switch.
i. Power factor. Switches shall include a visible external ON - OFF indicator.
j. Waveform capture capability. Upon triggering, a total 7. Switches shall have defeatable, front access, coin proof
of eight cycles of voltage (each phase) and current interlocks. Interlocks shall prevent opening switch door
(each phase) shall be recorded. The eight cycles shall when switch is ON and prevent turning switch ON
include four pre-trigger and four post-trigger cycles. when door is open. Switches shall include provisions
The waveform capture shall be configurable to trigger for padlocking the switch in the open position.
by manually over communications (when specified), 8. Provide the following UL listed accessories:
by a overcurrent trip, by a protective relay trip (when a. [120] [240] [480] VAC Electric trip [and control
specified), or by a current alarm. Waveform data power transformer].
shall be available in “Comtrade” file format via serial b. [Blown- fuse Protector.]
communications or at a front port at the trip unit.] c. [Provision for Key Interlock.]
d. [Auxiliary Switches with [1] [2] [3] [4] single-pole,
SPECIFIER NOTE: INCLUDE THE FOLLOWING FOR PROTECTIVE double-throw elements.]
RELAY OPTION: e. Ground fault protection} relay with mechanical
5. [The trip unit shall include all of the following protective ground fault indicator, test function, adjustable
functions. It shall be possible to disable, by user pro- current pick-up and time delay, and current sensors
gramming, any combination of unwanted protective as required. Ground fault relay shall have an internal
functions. Except for reverse power, relay settings shall memory circuit that integrates intermittent arcing
be in 1 percent steps over indicated range. Each function ground faults with time.]
shall have a time delay, adjustable in 1-second incre-
78
Spectra Series® Switchboards
79
Spectra Series® Switchboards
Reference Publications
Integrated Switchboards
• DEA-373A
Commercial Metering Switchboards
• DEA-340
Jiffy II Switchboards
• DEA-344
Busway
• DE-307
ZTS
• Standard: PB-5066
• Delay: PB-5067
• Bypass: PB-5068
DC
• GIZ-2691
Process Control Unit (PCU)
• DET-104
PowerBreak II
• GET-8052
Powerpanel
• GET-7006
AV3 Access Switchboard
• DET-138
80
Spectra Series® Switchboards
Appendix
Seismic Compliance Certification
For Spectra & Jiffy Series Switchboards
Qualified to IEEE-693-1997 HIGH Level with 1.33 Amplification Factor.
Qualified to IBC-2009 Sds = 1.05g, Ss = 158%, Ip = 1.5, for z/h > 0
Sds = 1.67g, Ss = 250%, Ip = 1.5, for z/h = 0
in accordance with ICC-ES-AC156.
10
RRS
ZPA: 0.68g
0.1
1 10 100
Frequency [Hertz]
Lowest equipment natural frequency: 4.5 Hz Qualified by shake-table testing, Wyle Laboratories, May, 1998,
July, 1998, March, 2001
See GE document 10095999P1 for Certification Report, interpretation of test data and P.E. stamp.
81
Spectra Series® Switchboards
Appendix
Trip Units by Main Breaker and Functions
Trip Units
MicroVersaTrip® Plus MicroVersaTrip® PM Power + EntelliGuard® TU microEntelliGuard™
Power® Break II ● ● ● ●
Main Breaker
Spectra® ● ● ●
Long ● ● ● ● ●
Short ● ● ● ● ●
Instantaneous ● ● ● ● ●
Ground ● ● ● ● ●
Ground Fault Alarm ● ●
Neutral Protection ● ●
Functions
ZSI ● ● ●
RELT ● ● ●
Waveform Capture ● ● ●
Metering ● ● ●
Communications ● ● ●
Protective Relays ● ●
Note: MicroVersaTrip® is in legacy status and is for replacement only.
82
Information provided is subject to change without notice. Please verify all details with GE. All values are design or
typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or
implied, that such performance will be obtained under end-use conditions.
GE Energy
41 Woodford Avenue, Plainville, CT 06062
www.geindustrial.com
© 2013 General Electric Company
imagination at work
GET-8032C (02/13)