Seismic Forces - Simplified Static Force Method and Static Force Method
Seismic Forces - Simplified Static Force Method and Static Force Method
Structure conforming to the requirements of Section 208.4.8.1 may be designed using this
procedure.
The simplified static lateral-force procedure set forth in Section 208.5.1.1 may be used for the
following structures of Occupancy Category IV or V:
1. Buildings of any occupancy (including single-family dwellings) not more than three stories in
height excluding basements that use light-frame construction.
2. Other buildings not more than two stories in height excluding basements.
The forces at each level shall be calculated using the following equation:
The design storey shear, Vx, in anu storey is the sum of the forces Ft and Fx above that storey. Vx shall be
distributed to the various elements of the vertical lateral force-resisting system in proportion to their
rigidities, considering the rigidity of the diaphragm. See Section 208.7.2.3 for rigid elements that are not
intended to be part of the lateral force-resisting systems.
EXAMPLE:
• The total design base shear need not exceed the following:
• The total design base shear shall not be less than the following:
• In addition, for Seismic Zone 4, the total base shear shall also not be less than the following:
1. Method A:
For all buildings, the value T may be approximated from the following equation:
Where:
Alternatively, the value of Ct for structures with concrete or masonry shear walls may be taken as
STATIC FORCE METHOD
• The total design base shear in a given direction shall be determined from the following
equation:
• The total design base shear need not exceed the following:
• The total design base shear shall not be less than the following:
• In addition, for Seismic Zone 4, the total base shear shall also not be less than the following:
Where:
Z = zone factor
1. Method A:
For all buildings, the value T may be approximated from the following equation:
Where:
Ct = 0.0731 for reinforced concrete moment-resisting frames and eccentrically braced frames
• The total force shall be distributed over the height of the structure on conformance with
Equations 208-15, 208-16, and 208-17 in the absence of a more rigorous procedure.
Fi = lateral forces
• The concentrated force Ft at the top, which is in addition to Fn, shall be determined from the
equation:
• Ft need not exceed 0.25V and may be considered as zero where T is 0.7 s or less.
• The remaining portion of the base shear shall be distributed over the height of the structure,
including level n, according to the following equation:
EXAMPLE: DESIGN PROBLEM
Ten