Packet Power Multi-Circuit Monitoring
Packet Power Multi-Circuit Monitoring
BGS16-16P
Monitoring applications
Multi-Circuit Monitors
• Use full power monitoring to track power and energy
• Use current-only monitoring to lower costs
• Cut installation costs
- “Plug and Play” wireless data network
- No configuration needed on site
- Minimizes number of CT wires to run
- Choose prewired CT harnesses or loose CT leads
• Optional fusing
• Highly compact
• Wireless firmware updates
• Easy panel mapping tool
Current Transformers
Split Core CTs Rogowski Coil CTs
Inside Diameter Rated Amperage Inside Diameter Coil Length Typical Amperage
10 mm 15, 30, 50 68 mm 250 mm 100A to 1000A
16 mm 100 147 mm 500 mm 400A to 3000A
24 mm 100, 200, 300 211 mm 700 mm 1000A to 5000A
36 mm 200, 300, 400, 600 306 mm 1000 mm 2000A to 10,000A
50 x 50 mm 400, 600, 800
75x125 mm 300, 600, 800 Solid Core CTs
150x150 mm 800, 1000, 1200, 1600, 2000, 3000, 4000 Inside Diameter Rated Amperage
9 mm 35
Additional current ratings available 15 mm 60
Open Secure
• Compatible with any existing hardware • Unique purpose-built wireless protocol
can only be used for monitoring
• Send data to any DCIM or BMS using SNMP.
Modbus TCP/IP, Ethernet/IP, BACnet/IP, • Full separation of wireless monitoring
MTConnect, or MQTT and wired data network
• Proven in data centers worldwide
BGS16 BGS9H
BGS16-12C - 12 1 BGS9H-3P6C 3 6
BGS16-16P 16 - 1 BGS9H-6P 6 -
160 x 160 x 92 mm
(6.3 x 6.3 x 3.6 in)
BGS32 BGS15H
BGS32-16P12C 16 12 2 BGS15H-3P12C 3 12
BGS32-24P 24 - 2 BGS15H-6P6C 6 6
BGS32-32P 32 - 2 BGS15H-9P 9 -
241 x 160 x 96 mm
(9.5 x 6.3 x 3.8 in)
BGS18H
BGS18H-12P 12 -
BGS18H-15P 15 -
BGS18H-18P 18 -
254 x 305 x 64 mm
(10 x 12 x 2.5 in)
BGS72 BGS27H
BGS72-40P 40 - 3 BGS27H-21P 21 -
BGS72-48P 48 - 3 BGS27H-24P 24 -
BGS72-56P 56 - 4 BGS27H-27P 27 -
BGS72-64P 64 - 4
BGS72-72P 72 - 5
356 x 305 x 64 mm
(14 x 12 x 2.5 in)
Technical Specifications
Measurement
Measurements Full Power: V, A, Ah VA, W Wh, Power Factor, Hz, THDi, THDv
Current Only: A, Ah
Accuracy ± 1.0% (CT dependent); ± 0.5% available
Input voltage 100-480/277V AC; 480V or 600/347V AC
Input voltage configuration LLLN+E, LLL+E, LLN+E, LN+E, LL+E
Current range 15A to 10,000A
Frequency 50/60 Hz
Communications
Operating frequency 860 to 930 MHz and 2.4 GHz (frequencies vary by region)
Wired network protocols HTTPS to Packet Power EMX running locally or as cloud service; SNMP V1/V2c/V3;
Modbus TCP/IP; Ethernet/IP; MTConnect; BACnet/IP; MQTT
Firmware updates Wireless
Typical transmission range 10 to 30 meters indoors between any two devices in mesh network
Antenna Fully enclosed, fixed configuration
Monitoring unit to gateway ratio 10 to 50 BGS units per gateway (depending on model) with unlimited gateways per site
Multi-site support Yes
Encryption HTTPS, optional 128-bit wireless
Local display Volts, Amps, Wh and communications status (varies by model)