Project April - Report
Project April - Report
Project April
Preliminary remarks
Notes on planning:
Content
Site 1
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 .............................
WESTERN FENCE SIDE - 5m external zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . .24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
illuminance
WESTERN FENCE SIDE - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . 25 .............................
illuminance
NORTHERN FENCE SIDE A - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 26
.............................
illuminance
NORTHERN FENCE SIDE B - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 27
.............................
illuminance
NORTHERN FENCE SIDE A - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . .28
.............................
illuminance
NORTHERN FENCE SIDE B-15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . .29
.............................
illuminance
NORTHERN FENCE SIDE C -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 30
.............................
illuminance
NORTHERN FENCE SIDE D - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 31
.............................
illuminance
NORTHERN FENCE SIDE C - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 32
.............................
illuminance
NORTHERN FENCE SIDE D -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . .33.............................
illuminance
NORTHERN FENCE SIDE D - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 34
.............................
illuminance
NORTHERN FENCE SIDE D - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . 35
.............................
illuminance
NORTHERN FENCE SIDE E - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 36
.............................
illuminance
NORTHERN FENCE SIDE E - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 37
.............................
illuminance
NORTHERN FENCE SIDE F - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . .38
.............................
illuminance
Project April
Content
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
.............................
Project April
Description
5
Project April
Luminaire list
30 Not yet a NLC L81- Area Lights 180.0 W 25200 lm 140.0 lm/W
DIALux 180W-
member 25200Lm
67 Not yet a NLC L81- Area Lights 300.0 W 42000 lm 140.0 lm/W
DIALux 300W-
member 42000Lm
3 Not yet a NLC L900- Flood Light 600.0 W 89978 lm 150.0 lm/W
DIALux 600W-
member 90000LM
6
Project April
P 180.0 W
ΦLamp 25200 lm
ΦLuminaire 25200 lm
η 100.00 %
Polar LDC
Luminous efficacy 140.0 lm/W
CCT 4000 K
CRI 100
7
Project April
P 300.0 W
ΦLamp 42000 lm
ΦLuminaire 42000 lm
η 100.00 %
Polar LDC
Luminous efficacy 140.0 lm/W
CCT 4000 K
CRI 100
8
Project April
P 600.0 W
ΦLamp 90000 lm
ΦLuminaire 89978 lm
η 99.98 %
Polar LDC
Luminous efficacy 150.0 lm/W
CCT 4000 K
CRI 100
9
Project April
Site 1
Luminaire layout plan
10
Project April
Site 1
Luminaire layout plan
11
Project April
Site 1
Luminaire layout plan
X Y Mounting Luminaire
height
Arrangement A11
Arrangement A12
Arrangement A16
12
Project April
Site 1
Luminaire layout plan
13
Project April
Site 1
Luminaire layout plan
14
Project April
Site 1
Luminaire layout plan
15
Project April
Site 1
Luminaire layout plan
16
Project April
Site 1
Luminaire layout plan
Arrangement A10
17
Project April
Site 1
Luminaire layout plan
Individual luminaires
X Y Mounting Luminaire
height
18
Project April
Site 1
Luminaire layout plan
Individual luminaires
X Y Mounting Luminaire
height
19
Project April
Site 1
Luminaire list
30 Not yet a NLC L81- Area Lights 180.0 W 25200 lm 140.0 lm/W
DIALux 180W-
member 25200Lm
67 Not yet a NLC L81- Area Lights 300.0 W 42000 lm 140.0 lm/W
DIALux 300W-
member 42000Lm
3 Not yet a NLC L900- Flood Light 600.0 W 89978 lm 150.0 lm/W
DIALux 600W-
member 90000LM
20
Project April
21
Project April
Calculation surfaces
WESTERN FENCE SIDE - 5m external zone 18.7 lx 9.57 lx 21.9 lx 0.51 0.44 CG1
Perpendicular illuminance
Height: 0.000 m
WESTERN FENCE SIDE - 15m internal zone 41.2 lx 24.9 lx 74.3 lx 0.60 0.34 CG2
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE A - 5m External zone 12.9 lx 9.45 lx 22.4 lx 0.73 0.42 CG3
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE B - 5m External zone 28.2 lx 16.3 lx 36.6 lx 0.58 0.45 CG4
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE A - 15m internal zone 21.1 lx 13.2 lx 34.5 lx 0.63 0.38 CG5
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE B-15m internal zone 40.5 lx 22.4 lx 56.1 lx 0.55 0.40 CG6
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE C -15m internal zone 41.2 lx 25.0 lx 73.7 lx 0.61 0.34 CG7
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE D - 5m External zone 26.7 lx 18.5 lx 37.6 lx 0.69 0.49 CG8
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE C - 5m External zone 23.4 lx 13.4 lx 30.7 lx 0.57 0.44 CG9
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE D -15m internal zone 40.7 lx 23.3 lx 58.4 lx 0.57 0.40 CG10
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE D - 5m External zone 17.9 lx 10.5 lx 27.9 lx 0.59 0.38 CG11
Perpendicular illuminance
Height: 0.000 m
22
Project April
NORTHERN FENCE SIDE D - 15m internal zone 33.0 lx 16.4 lx 57.5 lx 0.50 0.29 CG12
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE E - 5m External zone 17.9 lx 7.94 lx 36.8 lx 0.44 0.22 CG13
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE E - 5m External zone 37.7 lx 28.2 lx 45.3 lx 0.75 0.62 CG14
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE F - 5m External zone 14.6 lx 8.32 lx 20.9 lx 0.57 0.40 CG15
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE E -15m internal zone 20.5 lx 10.2 lx 48.6 lx 0.50 0.21 CG16
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE E -15m internal zone 74.2 lx 34.5 lx 107 lx 0.46 0.32 CG17
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE F -15m internal zone 37.4 lx 16.1 lx 62.2 lx 0.43 0.26 CG18
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE F - 5m External zone 28.7 lx 24.0 lx 33.1 lx 0.84 0.73 CG19
Perpendicular illuminance
Height: 0.000 m
NORTHERN FENCE SIDE F -15m internal zone 33.6 lx 17.1 lx 45.9 lx 0.51 0.37 CG20
Perpendicular illuminance
Height: 0.000 m
23
Project April
WESTERN FENCE SIDE - 5m external zone 18.7 lx 9.57 lx 21.9 lx 0.51 0.44 CG1
Perpendicular illuminance
Height: 0.000 m
24
Project April
WESTERN FENCE SIDE - 15m internal zone 41.2 lx 24.9 lx 74.3 lx 0.60 0.34 CG2
Perpendicular illuminance
Height: 0.000 m
25
Project April
NORTHERN FENCE SIDE A - 5m External zone 12.9 lx 9.45 lx 22.4 lx 0.73 0.42 CG3
Perpendicular illuminance
Height: 0.000 m
26
Project April
NORTHERN FENCE SIDE B - 5m External zone 28.2 lx 16.3 lx 36.6 lx 0.58 0.45 CG4
Perpendicular illuminance
Height: 0.000 m
27
Project April
NORTHERN FENCE SIDE A - 15m internal zone 21.1 lx 13.2 lx 34.5 lx 0.63 0.38 CG5
Perpendicular illuminance
Height: 0.000 m
28
Project April
NORTHERN FENCE SIDE B-15m internal zone 40.5 lx 22.4 lx 56.1 lx 0.55 0.40 CG6
Perpendicular illuminance
Height: 0.000 m
29
Project April
NORTHERN FENCE SIDE C -15m internal zone 41.2 lx 25.0 lx 73.7 lx 0.61 0.34 CG7
Perpendicular illuminance
Height: 0.000 m
30
Project April
NORTHERN FENCE SIDE D - 5m External zone 26.7 lx 18.5 lx 37.6 lx 0.69 0.49 CG8
Perpendicular illuminance
Height: 0.000 m
31
Project April
NORTHERN FENCE SIDE C - 5m External zone 23.4 lx 13.4 lx 30.7 lx 0.57 0.44 CG9
Perpendicular illuminance
Height: 0.000 m
32
Project April
NORTHERN FENCE SIDE D -15m internal zone 40.7 lx 23.3 lx 58.4 lx 0.57 0.40 CG10
Perpendicular illuminance
Height: 0.000 m
33
Project April
NORTHERN FENCE SIDE D - 5m External zone 17.9 lx 10.5 lx 27.9 lx 0.59 0.38 CG11
Perpendicular illuminance
Height: 0.000 m
34
Project April
NORTHERN FENCE SIDE D - 15m internal zone 33.0 lx 16.4 lx 57.5 lx 0.50 0.29 CG12
Perpendicular illuminance
Height: 0.000 m
35
Project April
NORTHERN FENCE SIDE E - 5m External zone 17.9 lx 7.94 lx 36.8 lx 0.44 0.22 CG13
Perpendicular illuminance
Height: 0.000 m
36
Project April
NORTHERN FENCE SIDE E - 5m External zone 37.7 lx 28.2 lx 45.3 lx 0.75 0.62 CG14
Perpendicular illuminance
Height: 0.000 m
37
Project April
NORTHERN FENCE SIDE F - 5m External zone 14.6 lx 8.32 lx 20.9 lx 0.57 0.40 CG15
Perpendicular illuminance
Height: 0.000 m
38
Project April
NORTHERN FENCE SIDE E -15m internal zone 20.5 lx 10.2 lx 48.6 lx 0.50 0.21 CG16
Perpendicular illuminance
Height: 0.000 m
39
Project April
NORTHERN FENCE SIDE E -15m internal zone 74.2 lx 34.5 lx 107 lx 0.46 0.32 CG17
Perpendicular illuminance
Height: 0.000 m
40
Project April
NORTHERN FENCE SIDE F -15m internal zone 37.4 lx 16.1 lx 62.2 lx 0.43 0.26 CG18
Perpendicular illuminance
Height: 0.000 m
41
Project April
NORTHERN FENCE SIDE F - 5m External zone 28.7 lx 24.0 lx 33.1 lx 0.84 0.73 CG19
Perpendicular illuminance
Height: 0.000 m
42
Project April
NORTHERN FENCE SIDE F -15m internal zone 33.6 lx 17.1 lx 45.9 lx 0.51 0.37 CG20
Perpendicular illuminance
Height: 0.000 m
43
Project April
Glossary
Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.
Allocation of the light colors to the color temperature ranges acc. to EN 12464-1:
Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).
The general color rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colors (see DIN 6169 or CIE 1974) to a reference light source.
Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.
44
Project April
Glossary
Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.
Unit: %
Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be
determined anywhere in space (inside or outside). The illuminance is not a product
feature because it is a recipient value. Luxometers are used for measuring.
Unit: Lux
Abbreviation: lx
Formula symbol: E
Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.
Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.
Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.
45
Project April
Glossary
Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.
Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It
is the only photometric value that the human eye can perceive.
Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.
This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).
46
Project April
Glossary
Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.
Unit: Lumen
Abbreviation: lm
Formula symbol: Φ
Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.
Unit: Candela
Abbreviation: cd
Formula symbol: I
P (power)
Electric power consumption
Unit: watt
Abbreviation: W
Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the color of the surface.
47
Project April
Glossary
Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.
UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).
Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.
Wall zone Circumferential area between working plane and walls that is not taken into account for
the calculation.
Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.
48