0% found this document useful (0 votes)
45 views

Project April - Report

The document is a lighting design project report for an April project. It includes a cover page, preliminary remarks noting that energy consumption does not include dimming, and a table of contents listing the various sections and subsections of the report such as the luminaire list, site layout plans, illuminance calculations for different zones and light scenes. Product data sheets are also included for the different luminaires used.

Uploaded by

Mhmd Ghanim
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views

Project April - Report

The document is a lighting design project report for an April project. It includes a cover page, preliminary remarks noting that energy consumption does not include dimming, and a table of contents listing the various sections and subsections of the report such as the luminaire list, site layout plans, illuminance calculations for different zones and light scenes. Product data sheets are also included for the different luminaires used.

Uploaded by

Mhmd Ghanim
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 48

Date 05-Apr-22

Project April

Created with DIALux


Project April

Preliminary remarks

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Project April

Content

Cover page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .


Preliminary remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


Not yet a DIALux member - Area Lights (1x NLC L81-180W-25200Lm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7............................
Not yet a DIALux member - Area Lights (1x NLC L81-300W-42000Lm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............................
8
Not yet a DIALux member - Flood Light (1x NLC L900-600W-90000LM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............................
9

Site 1
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 .............................
WESTERN FENCE SIDE - 5m external zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . .24. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
illuminance
WESTERN FENCE SIDE - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . . . . 25 .............................
illuminance
NORTHERN FENCE SIDE A - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 26
.............................
illuminance
NORTHERN FENCE SIDE B - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 27
.............................
illuminance
NORTHERN FENCE SIDE A - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . .28
.............................
illuminance
NORTHERN FENCE SIDE B-15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . .29
.............................
illuminance
NORTHERN FENCE SIDE C -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 30
.............................
illuminance
NORTHERN FENCE SIDE D - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 31
.............................
illuminance
NORTHERN FENCE SIDE C - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 32
.............................
illuminance
NORTHERN FENCE SIDE D -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . .33.............................
illuminance
NORTHERN FENCE SIDE D - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 34
.............................
illuminance
NORTHERN FENCE SIDE D - 15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . 35
.............................
illuminance
NORTHERN FENCE SIDE E - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 36
.............................
illuminance
NORTHERN FENCE SIDE E - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 37
.............................
illuminance
NORTHERN FENCE SIDE F - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . .38
.............................
illuminance
Project April

Content

NORTHERN FENCE SIDE E -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 39


.............................
illuminance
NORTHERN FENCE SIDE E -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 40
.............................
illuminance
NORTHERN FENCE SIDE F -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 41
.............................
illuminance
NORTHERN FENCE SIDE F - 5m External zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . .42
.............................
illuminance
NORTHERN FENCE SIDE F -15m internal zone / Light scene 1 / Perpendicular . . . . . . . . . . . . . . . . . . . . . . . 43
.............................
illuminance

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
.............................
Project April

Description

5
Project April

Luminaire list

Φtotal Ptotal Luminous efficacy


3839934 lm 27300.0 W 140.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 Not yet a NLC L81- Area Lights 180.0 W 25200 lm 140.0 lm/W
DIALux 180W-
member 25200Lm

67 Not yet a NLC L81- Area Lights 300.0 W 42000 lm 140.0 lm/W
DIALux 300W-
member 42000Lm

3 Not yet a NLC L900- Flood Light 600.0 W 89978 lm 150.0 lm/W
DIALux 600W-
member 90000LM

6
Project April

Product data sheet

Not yet a DIALux member - Area Lights

Article No. NLC L81-180W-


25200Lm

P 180.0 W

ΦLamp 25200 lm

ΦLuminaire 25200 lm

η 100.00 %
Polar LDC
Luminous efficacy 140.0 lm/W

CCT 4000 K

CRI 100

7
Project April

Product data sheet

Not yet a DIALux member - Area Lights

Article No. NLC L81-300W-


42000Lm

P 300.0 W

ΦLamp 42000 lm

ΦLuminaire 42000 lm

η 100.00 %
Polar LDC
Luminous efficacy 140.0 lm/W

CCT 4000 K

CRI 100

8
Project April

Product data sheet

Not yet a DIALux member - Flood Light

Article No. NLC L900-600W-


90000LM

P 600.0 W

ΦLamp 90000 lm

ΦLuminaire 89978 lm

η 99.98 %
Polar LDC
Luminous efficacy 150.0 lm/W

CCT 4000 K

CRI 100

9
Project April

Site 1
Luminaire layout plan

10
Project April

Site 1
Luminaire layout plan

Manufacturer Not yet a DIALux P 180.0 W


member
ΦLuminaire 25200 lm
Article No. NLC L81-180W-
25200Lm

Article name Area Lights

Fitting 1x NLC L81-180W-


25200Lm

5 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 165.287 m / 225.744
m / 12.000 m 165.287 m 225.744 m 12.000 m 49

X-direction 5 pcs., Center - 187.787 m 225.763 m 12.000 m 50


center, 22.500 m
210.287 m 225.782 m 12.000 m 51
Arrangement A8
232.787 m 225.801 m 12.000 m 52

255.287 m 225.820 m 12.000 m 99

5 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 165.287 m / 224.744
m / 12.000 m 165.287 m 224.744 m 12.000 m 53

X-direction 5 pcs., Center - 187.787 m 224.763 m 12.000 m 54


center, 22.500 m
210.287 m 224.782 m 12.000 m 55
Arrangement A9
232.787 m 224.801 m 12.000 m 56

11
Project April

Site 1
Luminaire layout plan

X Y Mounting Luminaire
height

255.287 m 224.820 m 12.000 m 100

2 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 269.570 m / 211.000
m / 12.000 m 269.570 m 211.000 m 12.000 m 60

X-direction 2 pcs., Center - 269.570 m 186.000 m 12.000 m 61


center, 25.000 m

Arrangement A11

2 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 269.570 m / 211.450
m / 12.000 m 269.570 m 211.450 m 12.000 m 62

X-direction 2 pcs., Center - 269.570 m 186.450 m 12.000 m 63


center, 25.000 m

Arrangement A12

2 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 269.570 m / 210.550
m / 12.000 m 269.570 m 210.550 m 12.000 m 82

X-direction 2 pcs., Center - 269.570 m 185.550 m 12.000 m 83


center, 25.000 m

Arrangement A16

7 x Not yet a DIALux member Area Lights

12
Project April

Site 1
Luminaire layout plan

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 413.570 m / -15.000
m / 12.000 m 413.570 m -15.000 m 12.000 m 85

X-direction 7 pcs., Center - 413.570 m -34.642 m 12.000 m 86


center, 19.642 m
413.570 m -54.283 m 12.000 m 87
Arrangement A17
413.570 m -73.925 m 12.000 m 88

413.570 m -93.567 m 12.000 m 89

413.570 m -113.208 m 12.000 m 90

413.570 m -132.850 m 12.000 m 98

7 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 413.070 m / -132.850
m / 12.000 m 413.070 m -132.850 m 12.000 m 91

413.070 m -113.208 m 12.000 m 92


X-direction 7 pcs., Center -
center, 19.642 m 413.070 m -93.567 m 12.000 m 93

Arrangement A18 413.070 m -73.925 m 12.000 m 94

413.070 m -54.283 m 12.000 m 95

413.070 m -34.642 m 12.000 m 96

413.070 m -15.000 m 12.000 m 97

13
Project April

Site 1
Luminaire layout plan

Manufacturer Not yet a DIALux P 300.0 W


member
ΦLuminaire 42000 lm
Article No. NLC L81-300W-
42000Lm

Article name Area Lights

Fitting 1x NLC L81-300W-


42000Lm

11 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 8.001 m / 5.998 m /
12.000 m 8.001 m 5.998 m 12.000 m 1

X-direction 12 pcs., Center - 8.001 m 26.435 m 12.000 m 2


center, Distances not
equal 8.001 m 46.871 m 12.000 m 3

Arrangement A1 8.001 m 67.308 m 12.000 m 4

8.001 m 87.744 m 12.000 m 5

8.001 m 108.180 m 12.000 m 6

8.001 m 128.617 m 12.000 m 7

8.001 m 149.053 m 12.000 m 8

8.001 m 169.489 m 12.000 m 9

8.001 m 189.926 m 12.000 m 10

8.001 m 210.362 m 12.000 m 11

5 x Not yet a DIALux member Area Lights

14
Project April

Site 1
Luminaire layout plan

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 30.567 m / 231.003
m / 12.000 m 30.567 m 231.003 m 12.000 m 12

X-direction 6 pcs., Center - 52.857 m 231.003 m 12.000 m 13


center, Distances not
equal 75.147 m 231.003 m 12.000 m 14

Arrangement A2 97.437 m 231.003 m 12.000 m 15

119.727 m 231.003 m 12.000 m 16

11 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 8.001 m / 6.498 m /
12.000 m 8.001 m 6.498 m 12.000 m 17

X-direction 12 pcs., Center - 8.001 m 26.935 m 12.000 m 18


center, Distances not
equal 8.001 m 47.371 m 12.000 m 19

Arrangement A3 8.001 m 67.808 m 12.000 m 20

8.001 m 88.244 m 12.000 m 21

8.001 m 108.680 m 12.000 m 22

8.001 m 129.117 m 12.000 m 23

8.001 m 149.553 m 12.000 m 24

8.001 m 169.989 m 12.000 m 25

8.001 m 190.426 m 12.000 m 26

8.001 m 210.862 m 12.000 m 27

5 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 31.017 m / 231.003
m / 12.000 m 31.017 m 231.003 m 12.000 m 28

15
Project April

Site 1
Luminaire layout plan

X-direction 6 pcs., Center - X Y Mounting Luminaire


center, Distances not height
equal
53.307 m 231.003 m 12.000 m 29
Arrangement A4
75.597 m 231.003 m 12.000 m 30

97.887 m 231.003 m 12.000 m 31

120.280 m 231.271 m 12.000 m 32

4 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 122.870 m / 255.700
m / 12.000 m 122.870 m 255.700 m 12.000 m 36

X-direction 4 pcs., Center - 122.870 m 270.533 m 12.000 m 37


center, 14.833 m
122.870 m 285.367 m 12.000 m 38
Arrangement A5
122.870 m 300.200 m 12.000 m 39

3 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 123.270 m / 300.400
m / 12.000 m 123.270 m 300.400 m 12.000 m 40

X-direction 3 pcs., Center - 138.270 m 300.400 m 12.000 m 41


center, 15.000 m
153.270 m 300.400 m 12.000 m 42
Arrangement A6

4 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 154.005 m / 299.729
m / 12.000 m 154.005 m 299.729 m 12.000 m 43

X-direction 4 pcs., Center - 154.005 m 279.834 m 12.000 m 44


center, 19.895 m

16
Project April

Site 1
Luminaire layout plan

Arrangement A7 X Y Mounting Luminaire


height

154.005 m 259.940 m 12.000 m 45

154.005 m 240.045 m 12.000 m 46

3 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 268.870 m / 226.600
m / 12.000 m 268.870 m 226.600 m 12.000 m 57

X-direction 3 pcs., Center - 268.870 m 225.175 m 12.000 m 58


center, Distances not
equal 268.870 m 223.750 m 12.000 m 59

Arrangement A10

5 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 313.532 m / 172.297
m / 12.000 m 313.532 m 172.297 m 12.000 m 64

X-direction 5 pcs., Center - 338.532 m 172.297 m 12.000 m 65


center, 25.000 m
363.532 m 172.297 m 12.000 m 66
Arrangement A13
388.532 m 172.297 m 12.000 m 71

413.532 m 172.297 m 12.000 m 72

5 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 313.533 m / 172.775
m / 12.000 m 313.533 m 172.775 m 12.000 m 67

X-direction 5 pcs., Center - 338.533 m 172.775 m 12.000 m 68


center, 25.000 m
363.533 m 172.775 m 12.000 m 69

17
Project April

Site 1
Luminaire layout plan

Arrangement A14 X Y Mounting Luminaire


height

388.533 m 172.775 m 12.000 m 70

413.533 m 172.775 m 12.000 m 73

7 x Not yet a DIALux member Area Lights

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 411.397 m / 114.860
m / 12.000 m 411.397 m 114.860 m 12.000 m 74

X-direction 7 pcs., Center - 411.357 m 96.612 m 12.000 m 75


center, 18.248 m
411.316 m 78.364 m 12.000 m 76
Arrangement A15
411.275 m 60.116 m 12.000 m 77

411.235 m 41.868 m 12.000 m 78

411.194 m 23.620 m 12.000 m 79

411.153 m 5.373 m 12.000 m 84

Individual luminaires

X Y Mounting Luminaire
height

122.822 m 300.641 m 12.000 m 47

153.742 m 300.349 m 12.000 m 48

411.282 m 115.916 m 12.000 m 80

414.188 m 172.507 m 12.000 m 81

18
Project April

Site 1
Luminaire layout plan

Manufacturer Not yet a DIALux P 600.0 W


member
ΦLuminaire 89978 lm
Article No. NLC L900-600W-
90000LM

Article name Flood Light

Fitting 1x NLC L900-600W-


90000LM

Individual luminaires

X Y Mounting Luminaire
height

8.070 m 230.700 m 12.000 m 33

8.700 m 231.100 m 12.000 m 34

8.200 m 231.200 m 12.000 m 35

19
Project April

Site 1
Luminaire list

Φtotal Ptotal Luminous efficacy


3839934 lm 27300.0 W 140.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 Not yet a NLC L81- Area Lights 180.0 W 25200 lm 140.0 lm/W
DIALux 180W-
member 25200Lm

67 Not yet a NLC L81- Area Lights 300.0 W 42000 lm 140.0 lm/W
DIALux 300W-
member 42000Lm

3 Not yet a NLC L900- Flood Light 600.0 W 89978 lm 150.0 lm/W
DIALux 600W-
member 90000LM

20
Project April

Site 1 (Light scene 1)


Calculation objects

21
Project April

Site 1 (Light scene 1)


Calculation objects

Calculation surfaces

Properties Ē Emin Emax g1 g2 Index

WESTERN FENCE SIDE - 5m external zone 18.7 lx 9.57 lx 21.9 lx 0.51 0.44 CG1
Perpendicular illuminance
Height: 0.000 m

WESTERN FENCE SIDE - 15m internal zone 41.2 lx 24.9 lx 74.3 lx 0.60 0.34 CG2
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE A - 5m External zone 12.9 lx 9.45 lx 22.4 lx 0.73 0.42 CG3
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE B - 5m External zone 28.2 lx 16.3 lx 36.6 lx 0.58 0.45 CG4
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE A - 15m internal zone 21.1 lx 13.2 lx 34.5 lx 0.63 0.38 CG5
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE B-15m internal zone 40.5 lx 22.4 lx 56.1 lx 0.55 0.40 CG6
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE C -15m internal zone 41.2 lx 25.0 lx 73.7 lx 0.61 0.34 CG7
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE D - 5m External zone 26.7 lx 18.5 lx 37.6 lx 0.69 0.49 CG8
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE C - 5m External zone 23.4 lx 13.4 lx 30.7 lx 0.57 0.44 CG9
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE D -15m internal zone 40.7 lx 23.3 lx 58.4 lx 0.57 0.40 CG10
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE D - 5m External zone 17.9 lx 10.5 lx 27.9 lx 0.59 0.38 CG11
Perpendicular illuminance
Height: 0.000 m

22
Project April

Site 1 (Light scene 1)


Calculation objects

NORTHERN FENCE SIDE D - 15m internal zone 33.0 lx 16.4 lx 57.5 lx 0.50 0.29 CG12
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE E - 5m External zone 17.9 lx 7.94 lx 36.8 lx 0.44 0.22 CG13
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE E - 5m External zone 37.7 lx 28.2 lx 45.3 lx 0.75 0.62 CG14
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE F - 5m External zone 14.6 lx 8.32 lx 20.9 lx 0.57 0.40 CG15
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE E -15m internal zone 20.5 lx 10.2 lx 48.6 lx 0.50 0.21 CG16
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE E -15m internal zone 74.2 lx 34.5 lx 107 lx 0.46 0.32 CG17
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE F -15m internal zone 37.4 lx 16.1 lx 62.2 lx 0.43 0.26 CG18
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE F - 5m External zone 28.7 lx 24.0 lx 33.1 lx 0.84 0.73 CG19
Perpendicular illuminance
Height: 0.000 m

NORTHERN FENCE SIDE F -15m internal zone 33.6 lx 17.1 lx 45.9 lx 0.51 0.37 CG20
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

23
Project April

Site 1 (Light scene 1)


WESTERN FENCE SIDE - 5m external zone

Properties Ē Emin Emax g1 g2 Index

WESTERN FENCE SIDE - 5m external zone 18.7 lx 9.57 lx 21.9 lx 0.51 0.44 CG1
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

24
Project April

Site 1 (Light scene 1)


WESTERN FENCE SIDE - 15m internal zone

Properties Ē Emin Emax g1 g2 Index

WESTERN FENCE SIDE - 15m internal zone 41.2 lx 24.9 lx 74.3 lx 0.60 0.34 CG2
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

25
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE A - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE A - 5m External zone 12.9 lx 9.45 lx 22.4 lx 0.73 0.42 CG3
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

26
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE B - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE B - 5m External zone 28.2 lx 16.3 lx 36.6 lx 0.58 0.45 CG4
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

27
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE A - 15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE A - 15m internal zone 21.1 lx 13.2 lx 34.5 lx 0.63 0.38 CG5
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

28
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE B-15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE B-15m internal zone 40.5 lx 22.4 lx 56.1 lx 0.55 0.40 CG6
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

29
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE C -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE C -15m internal zone 41.2 lx 25.0 lx 73.7 lx 0.61 0.34 CG7
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

30
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE D - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE D - 5m External zone 26.7 lx 18.5 lx 37.6 lx 0.69 0.49 CG8
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

31
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE C - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE C - 5m External zone 23.4 lx 13.4 lx 30.7 lx 0.57 0.44 CG9
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

32
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE D -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE D -15m internal zone 40.7 lx 23.3 lx 58.4 lx 0.57 0.40 CG10
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

33
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE D - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE D - 5m External zone 17.9 lx 10.5 lx 27.9 lx 0.59 0.38 CG11
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

34
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE D - 15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE D - 15m internal zone 33.0 lx 16.4 lx 57.5 lx 0.50 0.29 CG12
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

35
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE E - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE E - 5m External zone 17.9 lx 7.94 lx 36.8 lx 0.44 0.22 CG13
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

36
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE E - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE E - 5m External zone 37.7 lx 28.2 lx 45.3 lx 0.75 0.62 CG14
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

37
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE F - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE F - 5m External zone 14.6 lx 8.32 lx 20.9 lx 0.57 0.40 CG15
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

38
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE E -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE E -15m internal zone 20.5 lx 10.2 lx 48.6 lx 0.50 0.21 CG16
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

39
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE E -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE E -15m internal zone 74.2 lx 34.5 lx 107 lx 0.46 0.32 CG17
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

40
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE F -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE F -15m internal zone 37.4 lx 16.1 lx 62.2 lx 0.43 0.26 CG18
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

41
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE F - 5m External zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE F - 5m External zone 28.7 lx 24.0 lx 33.1 lx 0.84 0.73 CG19
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

42
Project April

Site 1 (Light scene 1)


NORTHERN FENCE SIDE F -15m internal zone

Properties Ē Emin Emax g1 g2 Index

NORTHERN FENCE SIDE F -15m internal zone 33.6 lx 17.1 lx 45.9 lx 0.51 0.37 CG20
Perpendicular illuminance
Height: 0.000 m

Utilization profile: DIALux presetting, Standard (outdoor transportation area)

43
Project April

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (correlated color temperature)


Body temperature of a thermal radiator that serves to describe its light color. Unit: Kelvin
[K]. The lesser the numerical value the redder; the greater the numerical value the bluer
the light color. The color temperature of gas-discharge lamps and semi-conductors are
termed "correlated color temperature" in contrast to the color temperature of thermal
radiators.

Allocation of the light colors to the color temperature ranges acc. to EN 12464-1:

Light color - color temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

CRI (color rendering index)


Designation for the color rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13.3: 1995.

The general color rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colors (see DIN 6169 or CIE 1974) to a reference light source.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (daylight factor)


Unit: %

44
Project April

Glossary

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

g1 Often also Uo (overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be
determined anywhere in space (inside or outside). The illuminance is not a product
feature because it is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

45
Project April

Glossary

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/m² year

Light loss factor See MF

LLMF (lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It
is the only photometric value that the human eye can perceive.

Unit: Candela per square meter


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

46
Project April

Glossary

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

MF (maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (power)
Electric power consumption

Unit: watt
Abbreviation: W

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the color of the surface.

47
Project April

Glossary

RMF (room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls that is not taken into account for
the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.

48