Moisture Load Calculation Sheet: Humidity Ratio

This document contains a moisture load calculation sheet for a project to condition a room at a national fertilizers facility. It provides design conditions, room details, and calculates various moisture loads from permeation, doors, infiltration, occupants, and fresh air. The total moisture load on the room is calculated to be 642763.34 grams per hour. Based on this load and specified dehumidifier conditions, the required dehumidified CFM is calculated to be 3749 CFM and the selected CFM is 4000 CFM. The estimated heat addition of the dehumidifier is 245203 BTUH or 20.4336 tons of refrigeration.

Uploaded by

Karmandeep Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views1 page

Moisture Load Calculation Sheet: Humidity Ratio

This document contains a moisture load calculation sheet for a project to condition a room at a national fertilizers facility. It provides design conditions, room details, and calculates various moisture loads from permeation, doors, infiltration, occupants, and fresh air. The total moisture load on the room is calculated to be 642763.34 grams per hour. Based on this load and specified dehumidifier conditions, the required dehumidified CFM is calculated to be 3749 CFM and the selected CFM is 4000 CFM. The estimated heat addition of the dehumidifier is 245203 BTUH or 20.4336 tons of refrigeration.

Uploaded by

Karmandeep Singh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Moisture Load Calculation Sheet

Project Data Design Conditions


Customer Name: National Fertilisers Ambient conditions Room Conditions
Location: Panipat DBT 95 Deg F 86.00 Deg F
Altitude: 720 feet
Application / Area : SUBSTATION-1 Humidity Ratio 157 Gr/lb 86.00 Gr/lb
RH % NMT 50% set point 45 %
Design Factors Grain Difference 71.00 Gr/lb
Factor for grain difference F1 1.9 Room Size
Factor for space permeation F2 0.35 Area 1 135185.00 ft3
Factor for Construction F3 1 Area 2 0.00
Factor for vapor barrier F4 0.75 Area 3 0.00
Moisture Load through Permeation Total Room volume 135185.00 ft3
(Room volume/14) x grain diff. x F1 x F2 x F3 x F4
Total Room volume 135185 ft3
Total Permeation moisture Load 341933.56 Gr/hr
Moisture Load through Doors
(No of door openings per hr/7) x Door size ( sqft) x grain diff) x F1
No of openings/hr 5 No of doors 2 Nos
Door size 56 sq ft
Grain diff. from ambient to Room
71 Factor for grain diff.( F1) 1.9
Total Door moisture Load 10792.00 Gr/hr
Moisture Load through Fixed Openings
21.4 x (opening size sqft / wall thickness ft) x grain diff. for Fixed Open x F1
Fixed opening size sqft
Fixed opening wall thickness ft
No of fixed openings 0 Nos
DBT (DegF) WBT ( Deg F)
Fixed opening outside conditions
Abs.Hum(gr/lb) RH(%)
Grain diff. for Fixed opening area Factor for grain diff.
Total Fixed openings moisture Load 0.00 Gr/hr
Product moisture Load 0.00 Gr/hr
Infiltration load 243430.00 Gr/hr
Moisture load through occupants
No of Occupants x F5
No of Occupancy 4 Nos
Factor F5 : Factor for Latent heat disippated by person with light/ 4000
Total Occupancy Load 16000.00 Gr/hr
Fresh Air Moisture Loads Fresh air ( CFM) 0 Amb gr/lb 0 0.00 Gr/hr
Total moisture load-Room 612155.56 Gr/hr
Total GR/HR 612155.56
Safety Factor @ 5% 30607.78 Gr/hr
Additional Safety factors if any 0.00 Gr/hr
Total Room Moisture Load 642763.34 Gr/hr
Dehumidified CFM required
[14 (Total room moisture load/ 60)] / (Design grains - Deh leaving grains)
Room Design grains 86.00 gr/lb
Deh Process Outlet
Total DEH leaving grains 46 gr/lb Temp 125.00 DegF
Total Dehumidified CFM 3749 CFM
Selected CFM 4000 CFM

Heat Addition By Dehumidifier =( CFM x 1.08 x DELTA "T') BTUH 222912 BTUH
Heat Addition By Dehumidifier considering Safety Factor @ 10% 245203 BTUH
For Hygro Tech Engineers 20.4336 TR