C-9102 Conventional Photoelectric Smoke Detector: Features

The document summarizes a conventional photoelectric smoke detector. It features twin LEDs for 360 degree visibility and remote indicator output. It connects to compatible control panels via end of line units to transmit fire detection signals. Using infrared scattering technology, it can detect smoke particles entering its chamber and alarm when smoke density reaches a preset level. Diagrams show how to install the detector and connect it to control panels and remote indicators.

Uploaded by

firex sp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
180 views

C-9102 Conventional Photoelectric Smoke Detector: Features

The document summarizes a conventional photoelectric smoke detector. It features twin LEDs for 360 degree visibility and remote indicator output. It connects to compatible control panels via end of line units to transmit fire detection signals. Using infrared scattering technology, it can detect smoke particles entering its chamber and alarm when smoke density reaches a preset level. Diagrams show how to install the detector and connect it to control panels and remote indicators.

Uploaded by

firex sp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

C-9102 Conventional

Photoelectric Smoke Detector


Features
 Twin LED for 360°view.
 Remote indicator output available.
 Complies with EN 54-7 standard.

Description 0832-CPD-0521

C-9102 Conventional Photoelectric Smoke Detector is


non-addressable. Used together with end of line unit, it
can connect with compatible control panels to process
detection signals. It shows fire alarm by LED indicators 548d/01

and transmits the fire signal to the control panel. Using


Fig. 3 shows the installation of the detector.
infrared scattering technology, the smoke density can be
detected. The detector receives very weak infrared light Conduit
under normal smokeless condition. If smoke particles
enter the chamber, the received light signal will increase Back Box

by scattering. When smoke density reaches a pre-set


Base
level, the detector will alarm out. In order to reduce
interference and power consumption, the emitting circuit Detector

works in pulse mode to prolong the life of IR LED.

Connection and Cabling


Fig.1 shows the detector bottom and Fig. 2 the base.
45mm~75mm
100mm 03
Fig. 3
m
m
Application
Warning: The detector should be connected with a
fire alarm control panel or other devices with current
5mm

25mm
limit function. Otherwise the detector may be
damaged by heavy alarm current.
Mounting
 When the detector is connected with a compatible
DZ-03
Hole

C fire alarm control panel in series, with a P-9907 active end


of line unit connected to the end of loop, a 1N5819 Diode
should be connected on the detector base.
Fig. 1 Fig. 2  Used as the detector base, the AEOL is to
There are four terminals with numbers on the base. install a conventional detector on it. The system
1: Detection zone positive IN connection is shown in Fig. 4.
2: Detection zone positive OUT Diode Diode
Compatible Control Panel

3: Detection zone negative IN and OUT


Output+ 1 2 1 2
Alarm Zone

+ - - 1 2
+

2: Positive terminal of remote indicator


Output-
4: Negative terminal of remote indicator 4 3
4 3
4 3

Recommended Cabling
2
1.0mm or above fire cable is recommended but subject Remote Indicator Remote Indicator
Conventional Detector Conventional Detector Conventional MCP AEOL
to local codes.
Fig. 4
Installation
 When the AEOL is not used as the detector
A fixed installation direction is ensured by the location base, a cover should be put. The system
connection is shown in Fig. 5.
elements on the detector and the base. Fix the base with
Compatible Control Panel

Diode Diode
two tapping screws, and then align mark C on the
detector with A on the base, rotate the detector to align
Alarm Zone

Output+ 1 2
- 1 2
1 2
mark C with mark B (Refer to Fig. 1 and 2 for the position + + -

of the marks), the detector will be fitted to the base. Output-


4 3
4 3 3
4

Note: The detector shall be horizontally installed. If it


has to be installed on an inclined plane, the Remote Indicator Remote Indicator
Conventional Detector Conventional Detector Conventional MCP AEOL
inclination angle shall not be over 45º.

Fig. 5

30304604 Issue 1.02


 When the detector is connected with a compatible Specification
fire alarm control panel, with an end of line resistor
connected to the end of loop, there should be no diode Operating Voltage 24VDC (12VDC~28VDC)
connected on the base. The system connection is shown Standby Current ≤60μA
in Fig. 6. Alarm Current 10mA≤I≤30mA
Indicators Red. Quiet in normal condition.
Compatible Control Panel

Illuminates steadily in alarm.

4.7kΩ Resistor
Output+ 2 2 Remote Indicator Directly connecting with LED
Alarm Zone

1 - 1
+ + -

Output (built-in 2kΩ resistor in series).


Output-
4 3
4 3 Quiet in normal condition.
Illuminates steadily in alarm.
Remote Indicator Remote Indicator Maximum Ripple 4V (peak-to-peak)
Conventional MCP Conventional Detector Conventional Detector
Voltage
Fig. 6 Alarm Clear Instantaneous Power-off (5s Max.,
2.5VDC Max.)
Maximum 15 detectors can be connected in one zone.
Power-up Time ≤10s
Cooperating with end of line device, the compatible
Max. Wind Speed 7.6m/s (1500fpm)
panel can monitor the cable for open circuit and short
Wiring Polarized 2-core for detection zone
circuit. Panel will report if any detector is removed. With
cable.
Active End of Line unit (AEOL), the functioning of other
Polarized 2-core for remote
device will not be affected by the detector removal.
indicator.
Maintenance Ambient -10℃~+50℃
temperature
1. The detector should be installed just before Relative Humidity ≤95%, non condensing
commissioning and kept well before installation, Ingress Protection IP23
taken corresponding measures for dust-proof, Rate
damp-proof and corrosion-proof. Material and Color ABS, white (RAL 9016)
2. The dust-proof cover should not be removed until of Enclosure
the project plunged into usage. Otherwise it may not Dimensions Diameter: 100mm
report alarm properly. Height: 56mm (with base)
3. Clean the detectors regularly, at least once a year to Mounting Hole 45mm~75mm
ensure normal operation of the system. Distance
4. Maintenance should be carried out for false alarm Weight About 120g
detectors, either clean or replace the chamber if
necessary. Before cleaning, notify the proper
authorities that the system is under maintenance Accessories and Tools
and will temporarily be out of service. Disable the
automatic controls relating to the zone or system Model Name Remarks
under maintenance to avoid unwanted actions. P-9907 Active End of Line Unit Order separately
Steps for chamber cleaning: DZ-03 Base Order separately
a) Open the top cover of detector.
b) Draw out the chamber slightly shaking by Limited Warranty
hand.
c) Clean the internal of the chamber by alcohol GST warrants that the product will be free of charge for
repairing or replacing from defects in design, materials
cotton or other clean liquid swab with
and workmanship during the warranty period. This
tweezers. Make sure not to leave any fiber in warranty does not cover any product that is found to have
the chamber. been improperly installed or used in any way not in
d) Put back the chamber and the top cover. accordance with the instructions supplied with the product.
5. The detector should be tested after re-installed to Anybody, including the agents, distributors or employees,
ensure normal operation. is not in the position to amend the contents of this
6. Fire simulation test should be done to the detector warranty. Please contact your local distributor for products
at least every 6 months. not covered by this warranty.

This Data Sheet is subject to change without notice. Please contact GST for more information or questions.

Gulf Security Technology Co., Ltd.


No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
[email protected] www.gst.com.cn

30304604 Issue 1.02