Naffcom PMP Submittal
Naffcom PMP Submittal
Mep Contractor
M/s. AL- AMAN MODERN ENERGY.
TECHNICAL SUBMITTAL
FOR
UL/FM APPROVED FIRE PUMP SET
[DUTY POINT: 300 GPM @ 55 M(H) ]
K667-18 01 07/03/2018 For Approval Mani A.Mansour A.Mansour
REF REV DATE Technical Submittal PREPARED BY REVIEWED BY APPROVED BY
Supplied By
1010310450 ت.. لاير – س3,500,000.00 شركة ذات مسؤولية حمدودة (خمتلطة) – رأس املال
شركة ذات
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Riyadh, Kingdom of Saudi Arabia. Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
PO Box 67716 Postal Code 11517 PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
Tel: 966 1 2824444 Fax: 966 1 2824333 Tel: 966 2 2608888 Fax: 966 2 2608777 Tel: 966 3 8145111 Fax: 966 3 8145112
Page 2 of 149
Thank you very much for giving us an opportunity to introduce NAFFCO. We are one
of the leading organizations in Fire Protection Systems and related services on turnkey
basis.
The Company
M/s National Fire Fighting Manufacturing, FZCO has established and started the
operation of Branch of National Fire Fighting Manufacturing CO (NAFFCO), as its office
branch in the Kingdom of Saudi Arabia territories on 3rd January 2011. NAFFCO Branch is
authorized to use the name of NAFFCO as well as install its products and services in the
above mentioned territories taking into consideration that the former is well-equipped and
technically trained and qualified to execute all firefighting works accordingly.
National Fire Fighting Manufacturing is in this field for the past 25 years and has designed
and executed various types of Fire Protection Systems right from the conceptual design up
to commissioning and maintenance. The numerous projects executed by us in Government,
Oil field, Industrial, Private and Public sector throughout the Gulf are the classic examples of
our professional competency. We are specialized in Designing, Supply, Installation, Testing,
Commissioning, Servicing and Maintenance of various Fire Protection and Alarm Systems.
We have highly-qualified and well-experienced team of Engineers who are able to Design,
Install and Commission the system to meet the requirements of NFPA and Local Authorities.
The Quality is our company’s first motto.
We not only offer you a product, but we also back-up what we sell with full servicing,
maintenance and training options. We have dedicated Staffs for Maintenance of Fire
Fighting Systems and Equipment and we provide the service of our Engineers and
Technicians round the clock (24 hours) for emergency requirements. Further, we also
undertake annual and half yearly Maintenance contracts, which will ensure the smooth
functioning of the various Fire Fighting System Equipment throughout the year.
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 3 of 149 Email: [email protected]
Details of Company Product & Range of Systems
Supplies and installs a huge variety of Fire Fighting and Fire Protection Equipment’s. Some
of the main items are mentioned below: Fire Safety Equipment.
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 4 of 149 Email: [email protected]
RANGE OF SYSTEMS, we are providing:
» Dry & Wet Standpipe Systems
» Fire Hydrants (all types)
» All types of Valves
» Sprinkler Systems
» Deluge System
» Pre-action System
» Pro-Inert System
» WaterMist System
» VESDA System
» Wet Chemical Suppression System
» Gas Detection System
» Fire Alarm System (Addressable and Conventional)
» Emergency / Exit Lighting System
» CCTV and Access Control System
» Voice Evacuation System
Hazard Analysis & System Design as per NFPA and/or your specific Requirements.
Computer generated hydraulic calculations.
Engineering work and submittal preparation.
Installation of the systems we supply.
Testing & commissioning of the systems we install.
Maintenance of any Fire Detection or Protection System.
The Approvals
WE are using the international standard products, where equipments are with BS & UL
standards and approved by LPCB, KITEMARK, CE marked, UL & SABS. They also confirm to
NFPA (National Fire Protection Association) and can comply with Local Civil Defense
Authorities.
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 5 of 149 Email: [email protected]
We take this opportunity to introduce as one of the leading companies specialized in the
field of Fire Protection Systems and related support starting from Design, Supply,
Installation and Commissioning of the System on turnkey basis for the past 20 Years.
The key behind the success and growth of any Engineering Organization is the
Engineering and Project Execution Department. We have qualified Engineers and a
well equipped Engineering department. The successful completion of the numerous
prestigious projects, both in Government and Private Sectors throughout United
Arab Emirates, Qatar and Kingdom of Saudi Arabia is attributted to our Engineering
and Project Execution Department.
Project Execution is fully managed and supervised by a well qualified Engineer
dedicated in the field of Fire Protection.
Besides, our Design based on NFPA codes, BS & UL standards which are acceptable
by Local Civil Defense Authorities. Drawings are prepared by Auto Cad. We have also
technical library with all the latest standards and know-how in the Fire Fighting
field.
Therefore we assure you that the Engineering of NAFFCO will derive the best result
to the utmost satisfaction of the client reqirements.
Thanking you and assuring our best services at all times,
Best Regards,
ENGR.KHALID AL KHATIB
Chief Executive Officer
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 6 of 149 Email: [email protected]
STRUCTURE AND ORGANIZATION
P.O. Box : 67716, Postal Code 11517,
Branch of:
Names and Address of associated companies of National Fire Fighting Manufacturing FZCO:
1) National Fire Fighting Manufacturing - Parent Company
2) NAFFCO Flow Control - Parent Company
3) Technopro International Group - Parent Company
4) Brass Light - Parent Company
5) Dhabia Trading, Abu Dhabi, U.A.E. - Parent Company
6) NAFFCO, Qatar - Branch
7) Branch of National Fire Fighting Manufacturing CO (NAFFCO) - Branch
8) Dhabia AlKhaleej Trading Est., KSA - Subsidiary
9) Saudi NAFFCO for Fire Fighting Systems - Subsidiary
10) NAFFCO MISR - Subsidiary
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 7 of 149 Email: [email protected]
National Fire National Fire Fighting Manufacturing FZCO (ISO 9001) in Dubai is
our Manufacturing unit located in Jebel Ali, United Arab Emirates. NAFFCO
Electromechanical Co. undertakes turnkey projects in Dubai and Northern
Emirates. In Abu Dhabi and Al Ain, Dhabia Trading undertakes turnkey projects for
entire Fire Protection jobs. NAFFCO Qatar undertakes turnkey projects for entire
Fire Protection jobs in Qatar.
The entire group of companies are managed by our World Head Quarters in Jebel Ali,
Dubai.
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 8 of 149 Email: [email protected]
NAFFCO WORLDWIDE HEAD OFFICE
9595050111 ت.. لاير – س0550555055 فرع شركة أجنبية ذات مسؤولية محدودة – رأس المال
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Block 16, Reemas Ind. City, Istanbul Al Fuad Plaza, Palestine Road, Saeed business Tower, King Fahad Road,
Road(South), Exit 18, As Sulay, Riyadh, Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
Kingdom of Saudi Arabia. PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
PO Box 67716 Postal Code 11517 Tel: 966 12 2608888 Fax: 966 12 2607888 Tel: 966 13 8145111 Fax: 966 13 8145112
Tel: 966 11 2824444 Fax: 966 11 2824333
Tel: 966 1 2824222 Fax: 966 1 2824003
Website: www.naffco.com Page 9 of 149 Email: [email protected]
List of Won Projects
Page 10 of 149
List of FIRE FIGHTING PUMP Project in KSA
3 First Ring Road Project - Makkah BA AZAB Co. / Jabal Omar Development Company
22 Saudi technology Lube Oil Plant - Riyadh Saudi Technology Base Lube Oil Plant
Electronic Building for Technical College Al Ameya Companies Group /Technical and
47
- Abha Vocational Training Corporation -TVTC
Riyadh Metro South Labour Camp -
48 BACS
Riyadh
55 Labour Village 1A phase 1 & 2 – Rabigh Creet International Contracting Co. / Emmar
56 Multi Store SEC Car Parking - Jeddah Ola Mohamed Al Maghrabi Est.
57 Hyper Panda Fayhaa Branch - Riyadh Protection Boarder Safety Est. / Savola Group
78 500 Bed Hail General Hospital - Hail Dulb Contracting Co. / Ministry of Health
79 John Crane Factory - Dammam John Crane Saudi Arabia Co. Ltd.
80 Fakieh Poultry Feed Factory - Jeddah Hussein Ali Al Beabi Gen. Contracting Est.
Page 15 of 149
şēĴĝļēęįĔƸƸŲļ
Membership Certificate
Page 16 of 149
Page 17 of 149
Page 18 of 149
Page 19 of 149
1110107787
رﻗﻢ اﻟﺸﻬﺎدة ١١١٠١٠٧٧٨٧ :
١٤٣٨/٠٨/٠٤ :ﻫـ اﻟﺘﺎرﻳﺦ
اﻟﺮﻗﻢ اﳌﻤﻴﺰ ٣٠٠٣٩٩٧٧٧٤ : إدارة ﻛﺒﺎر اﳌﻜﻠﻔﻦﻴ
ﻣﻘﻴﺪة
)ﻏﺮﻴ ﺻﺎﻟﺤﺔ ﻟﴫف اﻻﻗﺴﺎط اﻟﻨﻬﺎﺋﻴﺔ(
ﺗﺸﻬﺪ اﻟﻬﻴﺌﺔ اﻟﻌﺎﻣﺔ ﻟﻠﺰﻛﺎة واﻟﺪﺧﻞ ﺑﺄن اﳌﻜﻠﻒ /ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ﻧﺎﻓﻜﻮ
ﴍﻛﺔ رﻗﻢ ٧٠٠١٦٦١٢٥٠وﺳﺠﻞ ﺗﺠﺎري رﻗﻢ ١٠١٠٣٠٥٩٨٨رﺧﺼﺔ رﻗﻢ ١٠٢٠٣٢٠١٩١٨٨
ﻗﺪم إﻗﺮاره ﻋﻦ اﻟﻔﱰة اﳌﻨﺘﻬﻴﻪ ﰲ ٢٠١٦/١٢/٣١م
وﻗﺪ ﻣﻨﺢ ﻫﺬه اﻟﺸﻬﺎده ﻟﺘﻤﻜﻴﻨﻪ ﻣﻦ إﻧﻬﺎء ﺟﻤﻴﻊ ﻣﻌﺎﻣﻼﺗﻪ ﻣﺎ ﻋﺪا ﴏف ﻣﺴﺘﺤﻘﺎﺗﻪ اﻟﻨﻬﺎﺋﻴﺔ ﻋﻦ اﻟﻌﻘﻮد.
ﻳﴪي ﻣﻔﻌﻮل ﻫﺬه اﻟﺸﻬﺎدة ﺣﺘﻰ ﺗﺎرﻳﺦ ١٤٣٩/٠٨/١٤ﻩ اﳌﻮاﻓﻖ ٢٠١٨/٠٤/٣٠م .
)اﻟﺮاﺑﻊ ﻋﴩ ﻣﻦ ﺷﻌﺒﺎن أﻟﻒ و أرﺑﻌﺎﻤﺋﺔ و ﺗﺴﻌﺔ و ﺛﻼﺛﻮن ﻫﺠﺮي(
اﻟﺨﺘﻢ اﻟﺮﺳﻤﻲ
Page 20 of 149
1110107787
رﻗﻢ اﻟﺸﻬﺎدة ١١١٠١٠٧٧٨٧ :
١٤٣٨/٠٨/٠٤ :ﻫـ اﻟﺘﺎرﻳﺦ
اﻟﺮﻗﻢ اﳌﻤﻴﺰ ٣٠٠٣٩٩٧٧٧٤ : إدارة ﻛﺒﺎر اﳌﻜﻠﻔﻦﻴ
ﻣﻘﻴﺪة
ﺻﻔﺤﺔ رﻗﻢ ١ :
ﻗﺎﻤﺋﺔ ﻓﺮوع اﳌﻜﻠﻒ ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ﻧﺎﻓﻜﻮ
وﺳﺠﻞ ﺗﺠﺎري رﻗﻢ ١٠١٠٣٠٥٩٨٨رﺧﺼﺔ رﻗﻢ ١٠٢٠٣٢٠١٩١٨٨
اﳌﺪﻳﻨﺔ إﺳﻢ اﻟﻔﺮع اﻟﺮﺧﺼﺔ رﻗﻢ اﻟﺴﺠﻞ
ﺟﺪة ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ٤٠٣٠٢٨٢٧١٨
اﻟﺪﻣﺎم ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ٢٠٥٠٠٩٥٧٢٢
اﳌﺪﻳﻨﺔ اﳌﻨﻮرة ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻌﺪات اﻟﺤﺮﻳﻖ ٤٦٥٠٠٨٠٧٢٨
أﺑﻬﺎ ﻓﺮع اﻟﴩﻛﺔ اﻟﻮﻃﻨﻴﺔ ﻟﺼﻨﺎﻋﺔ ﻣﻌﺪات اﻟﺤﺮﻳﻖ ٥٨٥٠٠٦٩٤٩٤
Page 21 of 149
Page 22 of 149
Page 23 of 149
Page 24 of 149
100171000181364
اﻟﻬﺎﺗﻒ٠٠٩٦٦٥٤٧٦٩٨٧٠٧ :
Page 25 of 149
100171000181364
Page 26 of 149
Product schedule
Page 27 of 149
PROPOSED PRODUCT SCHEDULE
Submittal Ref. No. K667-18, Rev. 01 Dated: 06/03/18
Project : DANA MALL PHASE 2
Location : JEDDAH
Mep Contractor : M/s. AL-AMAN MODERN ENERGY
NO. ITEM DISCRIPTION APPROVAL MAKE / ORIGIN
ELECTRIC MOTOR DRIVEN FIRE PUMP
MODEL: NF-6VTP115-3 STAGES UL NAFFCO / UAE
CUSTOMER DUTY POINT:300 GPM @ 55 M(H)
1 ACCESSORIES
1. AUTOMATIC AIR RELEASE VALVE – 11/2" -
2. DISCHARGE PRESSURE GAUGES - 3½" DIAL ¼" CONNECTION UL
3. FLOW METER -4" FM
ELECTRIC MOTOR UL
60 HP, 1760 RPM, 380 V, 3 PH, 60 HZ,
MARATHON / USA
HORIZONTAL FOOT MOUNTED, ENCLOSURE – ODP
2 Or Factory
ACCESSORIES
Equivalent Choice
4. RIGHT ANGLE GEAR DRIVE-G80A-70HP-RATIO-6:5 DE’DRAN FM
5. UNIVERSAL JOINT SHAFT -
شركة ذات
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Riyadh, Kingdom of Saudi Arabia. Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
PO Box 67716 Postal Code 11517 PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
Tel: 966 1 2824444 Fax: 966 1 2824333 Tel: 966 2 2608888 Fax: 966 2 2608777 Tel: 966 3 8145111 Fax: 966 3 8145112
شركة ذات
Head Office: Riyadh Branch Jeddah Branch Al Khobar Branch
Riyadh, Kingdom of Saudi Arabia. Jeddah, Kingdom of Saudi Arabia. Al Khobar, Kingdom of Saudi Arabia.
PO Box 67716 Postal Code 11517 PO Box 128121 Postal Code 21362 PO Box 67716 Postal Code 11517
Tel: 966 1 2824444 Fax: 966 1 2824333 Tel: 966 2 2608888 Fax: 966 2 2608777 Tel: 966 3 8145111 Fax: 966 3 8145112
Page 30 of 149
Vertical
Turbine
Fire Pumps
Page 31 of 149
AN INTRODUCTION TO NAFFCO
NAFFCO was founded in Dubai, UAE to become the world’s Our products have been consistently certified by UL, FM, BSI,
leading producer and supplier of life safety solutions. By LPCB and Global Mark according to the latest International
recognizing the importance and convenience of having easy Quality Standard for their strict adherence to ISO 9001 quality
access to multiple safety services, we became specialized by management system and certified for ISO 14001 environmental
offering complete solutions under one roof for all types of high management systems and BS OHSAS 18001 for occupational
quality firefighting equipment, fire protection systems, fire alarms, safety by UL DQS.
addressable emergency systems, security systems, custom-made
vehicles such as fire trucks, ambulances, mobile hospitals and Our success is driven by our passion to protect; our vision is to
airport rescue firefighting vehicles (ARFF). become the world’s number one provider of innovative solutions
in protecting life, environment and property.
With the most talented and dedicated employees from around
the world, NAFFCO has over 450 passionate engineers and over
3 million square feet of manufacturing facilities. We are currently
exporting to over 100 countries worldwide.
FEATURES
• Complete unit responsibility.
• Complete in-house fabrication capabilities.
• Hydrostatic strength testing facilities.
• Operation run test as per NFPA 20, UL 448 requirements.
• Vertical turbine models for capacities from 50 to 1500 US
GPM.
• Drivers: Electric motor drive or diesel engine drive.
• Electrical testing capabilities for motors and controllers as per
NFPA standards.
• Capable to supply additional accessories wherever required.
• Rugged construction for longer service life.
• Specifically designed for fire fighting applications as per NFPA
20.
• Excellent mechanical and hydraulic design characteristics for
efficient performance.
DESCRIPTION
6
6 Discharge Flange Cast Iron ASTM A48 Class 40
Discharge Flange
Mounting Flange
TABLE OF DIMENSIONS
Model A B C x n* D E F G H J Q Smin
NF-4VTP22 150 95 135xn 25 495 465 Ø 180 145 Ø 172 320 422
NF-4VTP60 225 90 180xn - 495 465 Ø 235 145 Ø 233 380 600
NF-6VTP115 320 100 250xn 15 495 540 Ø 358 180 Ø 302 500 535
NF-8VTP170 320 120 300xn - 495 630 Ø 420 220 Ø 362 560 775
NF-8VTP230 320 120 300xn - 495 630 Ø 420 220 Ø 362 560 775
NF-10VTP285 320 150 330xn - 495 725 Ø 477 260 Ø 392 620 820
NF-10VTP340 320 150 330xn - 495 725 Ø 477 260 Ø 392 620 820
TABLE OF WEIGHTS
Single Bowl Strainer Suction Bell Column Pipe Discharge Head
Model Assembly (kg) (kg) (kg/m) (kg)
(kg)
NF-4VTP22 15 2 7 38 192
NF-4VTP60 29 3 11 39 200
NF-6VTP115 75 6.5 25 74 213
NF-8VTP170 132 8 35 109 338.6
NF-8VTP230 132 8 35 109 338.6
NF-10VTP285 188 8.5 50 143 491
NF-10VTP340 188 8.5 50 143 491
Page 38 of 149
10
GENERAL ARRANGEMENT DRAWING FOR FIRE PUMPS
ELECTRIC
FIRE PUMP
CONTROLLER
DIESEL
FIRE PUMP
CONTROLLER
www.naffco.com
PS PS
CLARKE ENGINE
150
100 METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
200 50
METERT ARE YS JJ KJKHNER NXCYUTH
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
250
HOSE VALVE
CAP & CHAIN
BUILDING
DIESEL TANK
TO ENGINE
TO HOSE
FROM ENGINE
NIPPLE HOSE
VALVE
ELBOW
OS&Y
GATE VALVE
HORIZONTAL OUTSIDE HOSE VALVE HEAD
ELECTRIC MOTOR (NUMBER OF HOSE VALVES IS VARIABLE)
DIESEL ENGINE VERTICAL MOTOR
RIGHT ANGLE PRESSURE RELIEF VALVE
GEAR DRIVE (FOR DIESEL ENGINE)
WASTE CONE
(FLANGED)
BACK TO TANK
Page 39 of 149
AIR RELEASE
VALVE SYSTEM
FLOW METER
TEST LINE PIPE
AND FITTINGS
1000 1500
100
300
2000
500
TO WASTE
2500
400
WIKAI
TO WASTE
OR SUPPLY
TEE
OS&Y OS&Y
GATE VALVE GATE VALVE
TEE
CONCENTRIC
VERTICAL TURBINE PUMP INCREASER
JOCKEY DISCHARGE
LINE
JOCKEY
OS&Y
CONTROLLER
GATE VALVE
PRESSURE SENSING LINE
TO SYSTEM
TO DRAIN
VALVE
CHECK
GATE VALVE
CAT.NO.NF/VTP/06/15 V.3
Page 40 of 149
Electric Motor
Page 41 of 149
Page 42 of 149
Page 43 of 149
CERTIFICATION DATA SHEET
OUTLINE: B-SS200079A-1512
FULL LOAD EFF: 93 3/4 LOAD EFF: 93.6 1/2 LOAD EFF: 93.6 GTD. EFF ELEC. TYPE NO LOAD AMPS
FULL LOAD PF: 89 3/4 LOAD PF: 87 1/2 LOAD PF: 81 91.7 SQ CAGE IND RUN 43.7 / 21.9
F.L. TORQUE LOCKED ROTOR AMPS L.R. TORQUE B.D. TORQUE F.L. RISE°C
88.5 LB-FT 977.5 / 488.8 130 LB-FT 147 240 LB-FT 271 40
SOUND PRESSURE SOUND POWER ROTOR WK^2 MAX. WK^2 SAFE STALL TIME STARTS APPROX. MOTOR
@ 3 FT. /HOUR WGT
DE BRACKET ODE BRACKET MOUNT ORIENTATION SEVERE HAZARDOUS DRIP SCREENS PAINT
TYPE TYPE TYPE DUTY LOCATION COVER
STANDARD STANDARD RIGID HORIZONTAL FALSE NONE FALSE NONE RED (ENAMEL)
Page 44 of 149
Page 45 of 149
Page 46 of 149
Page 47 of 149
Electric Fire Pump Controller
Page 48 of 149
Micro
Processor
Based
Fire Pump
Controllers
Page 49 of 149
AN INTRODUCTION TO NAFFCO
NAFFCO was founded in Dubai, UAE to become the world’s leading Our products have been consistently certified by UL, FM, BSI, LPCB
producer and supplier of life safety solutions. By recognizing the and Global Mark according to the latest International Quality
importance and convenience of having easy access to multiple Standard for their strict adherence to ISO 9001 quality management
safety services, we became specialized by offering complete system and certified for ISO 14001 environmental management
solutions under one roof for all types of high quality firefighting systems and BS OHSAS 18001 for occupational safety by UL DQS.
equipment, fire protection systems, fire alarms, addressable
emergency systems, security systems,custom-made vehicles such Our success is driven by our passion to protect; our vision is to
as fire trucks, ambulances, mobile hospitals and airport rescue become the world’s number one provider of innovative solutions
firefighting vehicles (ARFF). in protecting life, environment and property.
CAT.NO.NF/MPBFPC/06/15 Rev. 1
Page 51 of 149
www.naffco.com 3
UL LISTED ELECTRIC MOTOR
MICROPROCESSOR BASED CONTROLLER
MODEL NFY-SDM1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-DOM1 DIRECT ON LINE
NAFFCO Electric Motor Controllers for fire pumps are Power ratings vary from 40 to 400 horsepower, 230 /
listed by Underwriters Laboratories (UL file number 380 / 415 VAC, 50/60 Hz.
EX15064), in accordance with UL218 (Standard for Fire
Pump Controller), UL508a (Standard for Industrial Control Only high quality UL listed or UL recognized components
Panel), NFPA20 (National Fire Protection Association are used in these panels to guarantee the best possible
Pamphlet 20- Standard for Centrifugal Fire Pumps), reliability. Also high quality UL listed enclosures are
NFPA70 (National Electric Code) and NEMA. used.
Also approved by FM approvals (Factory Mutual), in This controller is completely wired, assembled,
accordance with FM standard 1321 / 1323 (Standard for programmed and tested at the factory before shipment,
Fire Pump Controller). and ready for immediate installation.
STANDARD FEATURES
• 230 / 380 / 415 VAC, 50/60 Hz main 3 phase system
power.
• Voltage Surge Protector.
• Main disconnecting switch with rotary handle sized for
disconnecting motor horsepower and voltage.
• Circuit breaker with shunt trip coil and rotary handle.
• Rated motor contactors.
• Emergency run mechanism to mechanically close motor
contactor contacts to start motor in case of emergency.
• Manual start and stop push buttons.
• 20x4 LCD display showing all system parameters and
variables.
• User friendly software enables user to program all related
parameters like timers, pressure, inputs, outputs … etc.
• Shows 3 phase line voltages.
• Shows 3 phase line motor currents.
• Shows real value of discharge pressure.
• Shows motor running hours.
• Shows ambient temperature.
• Starting delay timer (programmable) for sequence multi-
ple pumps starting.
• Automatic or manual shutdown after automatic start (se-
lectable).
• Automatic shutdown mode enabled/disabled indicator.
• Power ON/Healthy indicator.
• Automatic mode indicator.
• Manual mode indicator.
Page 52 of 149
www.naffco.com 3
STANDARD FEATURES
• Motor Run indicator/free contact. • Remote start on alarm / indicator / free contact
• Phase Loss/Failure alarm / indicator / free contact. (programmable).
• Phase sequence error alarm/indicator / free contact. • Manual local start on alarm/ indicator / free
• System error alarm / indicator / free contact. contact (programmable).
• Fail to start alarm / indicator. • Fail while run alarm / indicator / free contact
• System error alarm / indicator. (programmable).
• Pump lockout indicator / free contact. • Emergency start on alarm / indicator / free contact
• Push button for alarm silence (programmable).
(only for additional alarms). • Test on alarm/ indicator / free contact
• Motor locked rotor trip at 600% of FLA, after (programmable).
programmable time delay. • 10 additional programmable indicators (LED’s).
• Programmable automatic test, which can be • 10 additional programmable auxiliary digital inputs.
programmed to start at any desired day, hour and • 7 additional programmable output relays (free
minute in the week. contacts).
• Manual test push button. • Pressure transducer with analog voltage output.
• Motor overload alarm/ indicator / free contact • Data logging system for pressure and events.
(programmable). • USB port for saving recorded pressure and
• Over voltage alarm/indicator / free contact events on USB memory, and can be viewed
(programmable). with MS word and Excel.
• Under voltage alarm/ indicator / free contact • Electrically actuated built in discharge solenoid
(programmable). valve.
• Low discharge pressure alarm / indicator / free • Electrical alarm bell.
contact (programmable). • UL listed enclosure.
• Deluge valve on alarm / indicator / free contact
(programmable).
Fig (1)
Page 53 of 149
4 www.naffco.com
ELECTRIC FIRE PUMP CONTROLLER
FEATURES
Power ratings vary from 15 to 400 horsepower, 230 / • Circuit breaker with shunt trip coil and rotary handle.
380 / 415 VAC, 50/60 Hz. • Rated motor connectors.
• Emergency run mechanism to mechanically close
Only high quality UL listed or UL recognized motor connector contacts to start motor in case of
components are used in these panels to guarantee emergency.
the best possible reliability. Also high quality UL listed • Manual start and stop push buttons.
enclosures are used. • 20x4 LCD display showing all system parameters and
variables.
This controller is completely wired, assembled, • User friendly software enables user to program all
programmed and tested at the factory before related parameters like timers, pressure, inputs, outputs
shipment, and ready for immediate installation. … etc.
STANDARD FEATURES • Shows 3 phase line voltages.
• 230 / 380 / 415 VAC, 50/60 Hz main 3 phase system • Shows 3 phase line motor currents.
power. • Shows real value of discharge pressure.
• Voltage Surge Protector. • Shows motor running hours.
• Main disconnecting switch with rotary handle sized for • Shows ambient temperature.
disconnecting motor horsepower and voltage. • Starting delay timer (programmable) for sequence
• Motor Run indicator/free contact. multiple pumps starting.
• Phase Loss/Failure alarm / indicator / free contact. • Automatic or manual shutdown after automatic start
• Phase sequence error alarm/indicator / free contact. (selectable).
• System error alarm / indicator / free contact. • Automatic shutdown mode enabled/disabled indicator.
• Fail to start alarm / indicator. • Power ON/Healthy indicator.
• System error alarm / indicator. • Automatic mode indicator.
• Pump lockout indicator / free contact. • Manual mode indicator.
• Push button for alarm silence • Remote start on alarm / indicator / free contact
(only for additional alarms). (programmable).
• Motor locked rotor trip at 600% of FLA, after • Manual local start on alarm/ indicator / free contact
programmable time delay. (programmable).
• Programmable automatic test, which can be • Fail while run alarm / indicator / free contact
programmed to start at any desired day, hour and (programmable).
minute in the week. • Emergency start on alarm / indicator / free contact
• Manual test push button. (programmable).
• Motor overload alarm/ indicator / free contact • Test on alarm/ indicator / free contact (programmable).
(programmable). • 10 additional programmable indicators (LED’s).
• Over voltage alarm/indicator / free contact • 10 additional programmable auxiliary digital inputs.
(programmable). • 7 additional programmable output relays (free
contacts).
• Pressure transducer with analog voltage output.
• Data logging system for pressure and events.
• USB port for saving recorded pressure and events
on USB memory, and can be viewed with MS word
and Excel.
• Electrically actuated built in discharge solenoid valve.
• Under voltage alarm / indicator / free contact
(programmable).
• Low discharge pressure alarm / indicator / free
contact (programmable).
• Deluge valve on alarm / indicator / free contact
(programmable).
• Electrical alarm bell.
• UL listed NEMA 2 enclosure.
ENCLOSURE OPTIONS:
• NEMA 3
• NEMA 4
• NEMA 12
Page 54 of 149
CAT.NO.NF/MPBFPC/06/15 Rev. 1 www.naffco.com 9
TIME DELAY BEFORE STARTING THE FIRE PUMP
Table (1)
• If remote start switch was momentarily actuated, • Two ways of shutdown are possible in this mode
motor will start directly and automatically, and it will (operator have to select one of them by software):
not stop unless operator presses stop push button on
the panel’s door. In this mode (remote start mode) there 1. Manual shutdown: After automatic start, motor can
will be no effect of deluge valve signal and low pressure be stopped in this mode only by pressing manual
stop push button. If the pump was on demand (low
signal. pressure or deluge valve active), and in auto mode,
• Motor automatic start by pressure sensor and deluge then pump cannot be stop manually, unless it is not on
valve can be disabled by pump lockout contact (external demand any more.
contact) which can be connected with controller (this 2. Automatic shutdown: After automatic start, controller
will keep motor running for a period (programmable).
option can be used in case of having a stand-by pump, After that, if the pump was not any more on
where it is not desired both pumps to start automatically demand, then controller will automatically shutdown
at the same time). the motor. If within this period, the pump became not
on demand, operator can shut it down manually by
pressing manual stop push button.
YES - selectable
Drop in pressure YES - selectable
(After running hold time)
YES - selectable
Deluge valve YES - selectable
(After running hold time)
Remote start NO YES
Manual start NO YES
Table (2)
• All alarm signals are operational in auto mode. • Manual test is operational in auto mode only, and it
• Automatic weekly test is only operational at auto can be applied by pressing test ON/OFF push button.
mode and can be enabled or disabled (operator Test can be terminated by pressing Test ON/OFF push
selection). If enabled, then user has to program the delay button again.
time before starting the test. Also to program the day,
hour and minute where the weekly automatic test is
desired to start. Test can be terminated by pressing Test
ON/OFF push button.
Page 55 of 149
6 www.naffco.com
FUNCTIONALITY
• During operation of the system, controller will be • If the controller closed contactors to start the motor
reading voltages, currents, pressure, and sensing many (due to auto or manual start), but the motor didn’t
input signals. These reading can be monitored on the start after some delay (programmable time delay),
LCD display. then controller will give alarm (fail to start alarm).
• If controller detected loss of one phase or more, then it Controller will sense if motor started or not by sensing
will give an alarm and will prevent the motor from starting, the motor current.
but if the loss of phase happened while the motor was • If the controller closed contactors to start the motor
running, then controller will give alarm but will not stop (due to auto or manual start), but the motor didn’t
the motor. start after some delay (programmable time delay),
• If controller detected phase reversal, it will give alarm because of LOCKED ROTOR, then controller will
and will not start the motor. activate the shunt trip coil of the MCCB and shut it
• Controller will detect over voltage, under voltage and down. Controller will sense if motor is in locked rotor
overload (over current), and will give alarms showing situation or not by sensing the motor current.
these errors.
RATING
Table (3)
Page 56 of 149
www.naffco.com 7
Page 57 of 149
Page
Page 58 of 137
51 of 149
Page
Page 59 of 137
52 of 149
Page
Page 60 of 137
53 of 149
Serving Over 100
100
00 Countries
C
Co
Cou
ou
oun
unt
ntr
ntri
ntrie
trie
ries
ies
ess Worldwide
W
Wo
Wor
Worl
orld
rld
rldw
ldw
dw
dwi
dwid
wid
wide
de
e
CAT.NO.NF/MPBFPC/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: [email protected]
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Page 61 of 149
Diesel Fire Pump
Page 62 of 149
Vertical
Turbine
Fire Pumps
Page 63 of 149
AN INTRODUCTION TO NAFFCO
NAFFCO was founded in Dubai, UAE to become the world’s Our products have been consistently certified by UL, FM, BSI,
leading producer and supplier of life safety solutions. By LPCB and Global Mark according to the latest International
recognizing the importance and convenience of having easy Quality Standard for their strict adherence to ISO 9001 quality
access to multiple safety services, we became specialized by management system and certified for ISO 14001 environmental
offering complete solutions under one roof for all types of high management systems and BS OHSAS 18001 for occupational
quality firefighting equipment, fire protection systems, fire alarms, safety by UL DQS.
addressable emergency systems, security systems, custom-made
vehicles such as fire trucks, ambulances, mobile hospitals and Our success is driven by our passion to protect; our vision is to
airport rescue firefighting vehicles (ARFF). become the world’s number one provider of innovative solutions
in protecting life, environment and property.
With the most talented and dedicated employees from around
the world, NAFFCO has over 450 passionate engineers and over
3 million square feet of manufacturing facilities. We are currently
exporting to over 100 countries worldwide.
FEATURES
• Complete unit responsibility.
• Complete in-house fabrication capabilities.
• Hydrostatic strength testing facilities.
• Operation run test as per NFPA 20, UL 448 requirements.
• Vertical turbine models for capacities from 50 to 1500 US
GPM.
• Drivers: Electric motor drive or diesel engine drive.
• Electrical testing capabilities for motors and controllers as per
NFPA standards.
• Capable to supply additional accessories wherever required.
• Rugged construction for longer service life.
• Specifically designed for fire fighting applications as per NFPA
20.
• Excellent mechanical and hydraulic design characteristics for
efficient performance.
DESCRIPTION
6
6 Discharge Flange Cast Iron ASTM A48 Class 40
Discharge Flange
Mounting Flange
TABLE OF DIMENSIONS
Model A B C x n* D E F G H J Q Smin
NF-4VTP22 150 95 135xn 25 495 465 Ø 180 145 Ø 172 320 422
NF-4VTP60 225 90 180xn - 495 465 Ø 235 145 Ø 233 380 600
NF-6VTP115 320 100 250xn 15 495 540 Ø 358 180 Ø 302 500 535
NF-8VTP170 320 120 300xn - 495 630 Ø 420 220 Ø 362 560 775
NF-8VTP230 320 120 300xn - 495 630 Ø 420 220 Ø 362 560 775
NF-10VTP285 320 150 330xn - 495 725 Ø 477 260 Ø 392 620 820
NF-10VTP340 320 150 330xn - 495 725 Ø 477 260 Ø 392 620 820
TABLE OF WEIGHTS
Single Bowl Strainer Suction Bell Column Pipe Discharge Head
Model Assembly (kg) (kg) (kg/m) (kg)
(kg)
NF-4VTP22 15 2 7 38 192
NF-4VTP60 29 3 11 39 200
NF-6VTP115 75 6.5 25 74 213
NF-8VTP170 132 8 35 109 338.6
NF-8VTP230 132 8 35 109 338.6
NF-10VTP285 188 8.5 50 143 491
NF-10VTP340 188 8.5 50 143 491
Page 70 of 149
10
GENERAL ARRANGEMENT DRAWING FOR FIRE PUMPS
ELECTRIC
FIRE PUMP
CONTROLLER
DIESEL
FIRE PUMP
CONTROLLER
www.naffco.com
PS PS
CLARKE ENGINE
150
100 METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
200 50
METERT ARE YS JJ KJKHNER NXCYUTH
METERT ARE YS JJ KJKHNER NXCYUTHD SBDAGU BSGDG VWDGUGDG DG DGQGD GDSHIU GHGK QGDUYGHD H DGG G
250
HOSE VALVE
CAP & CHAIN
BUILDING
DIESEL TANK
TO ENGINE
TO HOSE
FROM ENGINE
NIPPLE HOSE
VALVE
ELBOW
OS&Y
GATE VALVE
HORIZONTAL OUTSIDE HOSE VALVE HEAD
ELECTRIC MOTOR (NUMBER OF HOSE VALVES IS VARIABLE)
DIESEL ENGINE VERTICAL MOTOR
RIGHT ANGLE PRESSURE RELIEF VALVE
GEAR DRIVE (FOR DIESEL ENGINE)
WASTE CONE
(FLANGED)
BACK TO TANK
Page 71 of 149
AIR RELEASE
VALVE SYSTEM
FLOW METER
TEST LINE PIPE
AND FITTINGS
1000 1500
100
300
2000
500
TO WASTE
2500
400
WIKAI
TO WASTE
OR SUPPLY
TEE
OS&Y OS&Y
GATE VALVE GATE VALVE
TEE
CONCENTRIC
VERTICAL TURBINE PUMP INCREASER
JOCKEY DISCHARGE
LINE
JOCKEY
OS&Y
CONTROLLER
GATE VALVE
PRESSURE SENSING LINE
TO SYSTEM
TO DRAIN
VALVE
CHECK
GATE VALVE
CAT.NO.NF/VTP/06/15 V.3
Page 72 of 149
Diesel Engine
Page 73 of 149
Page 74 of 149
Referance No :-14207 Page 85 of 143
FIRE DRIVER DIESEL ENGINE SPECIFICATIONS ENGINE MODEL - FD 95 H
AUTO MODE
1 AUTO-MANUAL selector switch move to AUTO POSITION.
ENTER RPM
NOTE
DO NOT LEAVE selector switch in MANUAL MODE during AUTOMATIC OPERATION of the FIRE PUMP
OIL PRESSURE GAUGE WATER TEMP. GAUGE VOLTMETER BAT. - 1 VOLTMETER BAT. - 2
125
862
280
138
16
100
16
10
10
38
0
0
OIL
PRESSURE WATER BATTERY BATTERY
TEMP
Page 75 of 149
Referance No :-14207 Page 86 of 143
Page 76 of 149
Referance No :-14207 Page 87 of 143
Diesel Fire Pump Controller
Page 77 of 149
Micro
Processor
Based
Fire Pump
Controllers
1-1/2” BS 336 male
Page 78 of 149
An Introduction to NAFFCO
NAFFCO FZCO is among the world’s leading firefighting technology and fire safety solutions, NAFFCO
manufacturers and suppliers of top-tier firefighting has worked in both the private and government sectors,
equipment, fire protection systems, fire alarms, security as well as manufacturing plants, hospitals, stadiums,
and safety engineering systems worldwide. Since malls and other organizational projects, delivering
its humble beginnings, NAFFCO has grown from its comprehensive fire safety and engineering solutions.
headquarters in Dubai, UAE to expand to serving over
100 countries around the world. NAFFCO is associated with globally renowned
international companies in the fire protection industry
such as Esser, Secutron, Megalights, Evax, Fike, Central,
One Stop Shopping for All Your Fire Safety Shield, Mueller, Giacomini, RB Pumps, Bombas, Ideal
and Security Needs Pumps, Joslyn Pumps, Peerless Pumps.
Page 79 of 149
2 www.naffco.com
DIESEL ENGINE CONTROLLER
FEATURES
STANDARD FEATURES
• System error alarm / indicator. • Test running indicator / free contact.
• AC power healthy indicator. • Automatic mode indicator / free contact.
• DC power healthy indicator / free contact. • Manual mode indicator.
• Speed switch error or failed while running alarm / • Battery Charger 1 error indicator.
indicator. • Battery Charger 2 error indicator.
• Automatic shutdown enabled/disabled indicator. • Battery 1 failure alarm / indicator.
• Low discharge pressure alarm / indicator / free contact • Battery 2 failure alarm / indicator.
(programmable). • Low oil pressure alarm / indicator.
• Deluge valve on alarm / indicator / free • High water temperature alarm / indicator.
contact(programmable). • Over speed shut down alarm / indicator.
• Remote start on alarm / indicator / free • Engine failed to start alarm / indicator.
contact(programmable). • Cranking coil 1 failure alarm / indicator.
• 10 additional programmable indicators. • Cranking coil 2 failure alarm / indicator.
• 11 additional programmable digital inputs. • UL listed NEMA 2 enclosure.
• 8 additional programmable output relays (free
contacts). ENCLOSURE OPTIONS:
• Common alarm free contact. • NEMA 3
• Electrical alarm bell. • NEMA 4
• Push button for alarm silence (only for additional
• NEMA 12
alarms).
• Pressure transducer with analog voltage output.
• Data logging system for pressure and events.
• USB port for saving recorded pressure and events
on USB memory, and can be viewed with MS word
and Excel.
• Electrically actuated built in discharge solenoid valve.
• 220 / 110 VAC main line system power.
• 12 / 24 VDC system control voltage.
• Automatic / Manual / OFF mode (selectable).
• Two 12 / 24 VDC, 10 Amps smart automatic
microprocessor battery chargers.
• Protection circuit breakers before and after battery
chargers.
• 20x4 LCD display showing all system parameters and
variables.
• User friendly software enable user to program alliterated
parameters like timers, pressure, inputs,outputs … etc.
• Shows battery 1 and 2 voltages.
• Shows battery 1 and 2 charging currents.
• Shows real value of discharge pressure.
• Shows engine running hours.
• Showing ambient temperature.
• Automatic cranking from two different batteries.
• Two push buttons for manual cranking from two
different batteries.
• Manual stop push button.
• Programmable automatic weekly test, which can be
programmed to start at any desired day, hour and
minute in a week.
• Manual test push button.
• Starting delay timer (programmable) for sequence
multiple pumps starting.
• Automatic or manual shutdown after automatic start
(selectable).
• Compatible with fuel solenoid engines and stopped
solenoid engines.
• Engine run indicator / free contact.
Page 80 of 149
10 www.naffco.com CAT.NO.NF/MPBFPC/06/15 Rev. 1
STANDARD FEATURES
• Showing ambient temperature. • Engine run indicator / free contact.
• Automatic cranking from two different batteries. • Test running indicator / free contact.
• Two push buttons for manual cranking from two • Automatic mode indicator / free contact.
different batteries. • Manual mode indicator.
• Manual stop push button. • Battery Charger1 error indicator.
• Programmable automatic weekly test, which can • Battery Charger2 error indicator.
be programmed to start at any desired day, hour • Battery1 failure alarm / indicator.
and minute in a week. • Battery2 failure alarm / indicator.
• Manual test push button. • Low oil pressure alarm / indicator.
• Starting delay timer (programmable) for sequence • High water temperature alarm / indicator.
multiple pumps starting. • Over speed shut down alarm / indicator.
• Automatic or manual shutdown after automatic start • Engine failed to start alarm / indicator.
(selectable). • Cranking coil 1 failure alarm / indicator.
• Compatible with fuel solenoid engines and stopped • Cranking coil 2 failure alarm / indicator.
solenoid engines.
Page 81 of 149
www.naffco.com 9
• If remote start switch was momentarily actuated, stand-by pump, where it is not desired both pumps
the diesel engine will start directly and automatically, to start automatically at the same time).
and it will not stop unless operator presses stop push • Automatic starting for the diesel engine will be done
button on the panel’s door. In this mode (remote start by automatic cranking from battery 1, and if failed
mode) there will be no effect of the low oil pressure from battery 2, with certain cranking and rest
alarm, high water temperature alarm, and also will be period (period is programmable). Controller will try
no effect of deluge valve signal and low pressure signal. to crank engine up to six times, but if engine did
• Engine automatic start by pressure sensor and not start after these six attempts, “Failed To
deluge valve can be disabled by pump lockout contact Start Alarm” will be activated, as shown in fig (2):
(external contact) which can be connected with
controller (this option can be used in case of having a
Figure (2)
• If remote start switch was momentarily actuated, stand-by pump, where it is not desired both pumps
the diesel engine will start directly and automatically, to start automatically at the same time).
and it will not stop unless operator presses stop push • Automatic starting for the diesel engine will be done
button on the panel’s door. In this mode (remote start by automatic cranking from battery 1, and if failed
mode) there will be no effect of the low oil pressure from battery 2, with certain cranking and rest
alarm, high water temperature alarm, and also will be period (period is programmable). Controller will try
no effect of deluge valve signal and low pressure signal. to crank engine up to six times, but if engine did
• Engine automatic start by pressure sensor and not start after these six attempts, “Failed To
deluge valve can be disabled by pump lockout contact Start Alarm” will be activated, as shown in fig (2):
(external contact) which can be connected with
controller (this option can be used in case of having a
Page 82 of 149
10 www.naffco.com
METHODS OF STOPPING THE FIRE PUMP
YES - selectable
Drop in pressure With delay
(After running hold time)
YES - selectable
Deluge valve With delay
(After running hold time)
• If one of the batteries was dead or disconnected, the alarms was activated, and alarm will remain until
controller will automatically crank all six attempts from operator resets it by pressing reset PB.
the healthy battery and ignore the dead battery. • In this mode (auto), operator can’t start the diesel
• Two ways of shutdown are possible in this mode (operator engine by the manual cranking push buttons.
must select one of them by software): • Over speed alarm is functional in this mode, and
will stop the pump directly and automatically and
1. Manual shutdown: After automatic start, engine can actuate alarm, and controller will not start engine
be stopped in this mode only by pressing manual
stop push button, but engine can’t be stopped if again unless operator resets the over speed relay
the pump was still on demand (pressure still low or at diesel engine, and then resets the Over Speed
deluge valve still active), unless user put the switch on Alarm by pressing reset PB of the controller.
OFF position. • All alarm signals are operational in auto mode.
2. Automatic shutdown: After automatic start, controller
will keep engine running for a period varies from 1 to • Automatic weekly test is only operational at auto
120 minutes (programmable). After that, if the pump mode and can be enabled or disabled (operator
was not any more on demand, then controller will selection). If enabled, then user has to program
automatically shutdown the engine. If within this the delay time before starting the test. Also to
period, the pump became not on demand, operator program the day, hour and minute where the
can shut it down manually by pressing manual stop
push button. weekly automatic test is desired to start. Test can be
• When the engine is running because the pump terminated by pressing Test ON/OFF push button.
being on demand (due to low pressure or activation • Manual test is operational in auto mode only, and
of deluge valve or remote start), it will not stop if there it can be applied by pressing test ON/OFF push
was high water temperature alarm, or low oil pressure button. Test can be terminated by pressing Test
alarm, but if it was running and the reason of starting ON/OFF push button again.
has gone then it will directly stop if any of these two
RATINGS
Figure (6)
Page 83 of 149
www.naffco.com 11
Page 84 of 149
Page 85 of 149
Page 86 of 149
Page 87 of 149
Serving Over 100
100
00 Countries
C
Co
Cou
ou
oun
unt
ntr
ntri
ntrie
trie
ries
ies
ess Worldwide
W
Wo
Wor
Worl
orld
rld
rldw
ldw
dw
dwi
dwid
wid
wide
de
e
CAT.NO.NF/MPBFPC/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: [email protected]
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Page 88 of 149
Jockey Pump
Page 89 of 149
Page 90 of 149
Page 91 of 149
Page 92 of 149
Page 93 of 149
Page 94 of 149
Jockey Pump Controller
Page 95 of 149
Micro
Processor
Based
Fire Pump
Controllers
1-1/2” BS 336 male
Page 96 of 149
An Introduction to NAFFCO
NAFFCO FZCO is among the world’s leading firefighting technology and fire safety solutions, NAFFCO
manufacturers and suppliers of top-tier firefighting has worked in both the private and government sectors,
equipment, fire protection systems, fire alarms, security as well as manufacturing plants, hospitals, stadiums,
and safety engineering systems worldwide. Since malls and other organizational projects, delivering
its humble beginnings, NAFFCO has grown from its comprehensive fire safety and engineering solutions.
headquarters in Dubai, UAE to expand to serving over
100 countries around the world. NAFFCO is associated with globally renowned
international companies in the fire protection industry
such as Esser, Secutron, Megalights, Evax, Fike, Central,
One Stop Shopping for All Your Fire Safety Shield, Mueller, Giacomini, RB Pumps, Bombas, Ideal
and Security Needs Pumps, Joslyn Pumps, Peerless Pumps.
Page 97 of 149
2 www.naffco.com
UL LISTED JOCKEY PUMP CONTROLLER
MODEL NFY-JSD1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-JDO1 DIRECT ON LINE
NAFFCO Jockey Pump Controllers for fire pumps are UL recognized components are used in these panels
listed by Underwriters Laboratories (UL file number to guarantee the best possible reliability. Also high
E309408), in accordance with UL508a (Standard for quality UL listed enclosures are used.
Industrial Control Panel), NFPA70 (National Electric
Code) and NEMA. The controller is completely wired, assembled and
tested at the factory before shipment, and ready for
Power ratings vary from 1.5 to 40 horsepower, 380 to immediate installation.
415 volts, 50 or 60 Hz. Only high quality UL listed or
STANDARD FEATURES
• Main disconnected switch with rotary handle, sized for
disconnecting motor horsepower and voltage.
• Motor Starter rated to motor’s horsepower, with
thermal and short circuit protection.
• Rated motor contactors.
• Circuit breaker for protection of control circuit.
• Selector switch for Hand—Off—Automatic operation.
• Star—Delta starting timer. ( in Model NFY-JSD1 )
• Power ON/Healthy indicator/free contact.
• Pump Run indicator/free contact.
• Pump Trip indicator/free contact.
• Adjustable pressure switch.
• UL listed enclosure.
SEQUENCE OF OPERATION
This controller is working under three modes automatic
off and manual mode.
AUTOMATIC START
In this mode, controller will start the Jockey pump
automatically and directly at low pressure detection
by the pressure switch, and will stop the pump
automatically and directly when the pressure goes up
again.
MANUAL START
In this mode, controller will start the Jockey pump
directly, and will not stop until selector switch is
switched off or in Auto mode.
Page 98 of 149
12 www.naffco.com
UL LISTED JOCKEY PUMP CONTROLLER
MODEL NFY-JSD1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-JDO1 DIRECT ON LINE
NAFFCO Electric Motor Controllers for fire pumps are UL recognized components are used in these panels to
listed by Underwriters Laboratories (UL file number guarantee the best possible reliability. Also high quality
E309408) in accordance with UL508a (Standard for UL listed enclosures are used.
Industrial Control Panel), NFPA70 (National Electric
Code) and NEMA. The controller is completely wired, assembled and tested
at the factory before shipment, and ready for immediate
Power ratings vary from 1.5 to 40 horsepower, 380 to installation.
415 volts, 50 or 60 Hz. Only high quality UL listed or
STANDARD FEATURES
• Main disconnected switch with rotary handle, sized for
disconnecting motor horsepower and voltage.
• Motor Starter rated to motor’s horsepower, with
thermal and short circuit protection.
• Rated motor connectors.
• Circuit breaker for protection of control circuit.
• Selector switch for Hand—Off—Automatic operation.
• Star—Delta starting timer. ( in Model NFY-JSD1 )
• Power ON/Healthy indicator/free contact.
• Pump Run indicator/free contact.
• Pump Trip indicator/free contact.
• Adjustable pressure switch.
• Run Period Timer
• UL listed NEMA 2 enclosure.
ENCLOSURE OPTIONS:
• NEMA 3
• NEMA 4
• NEMA 12
RATING
RATED SHORT CIRCUIT
POWER RATED VOLTAGE FREQUENCY ENCLOSURE SIZE
CONTENT CURRENT
(HP) (VAC) (Hz) (mm)
(A) (kA)
1.5 380 - 415 50 or 60 3.3 5 500(H) x 400(W) x 250(D)
2 380 - 415 50 or 60 4.3 5 500(H) x 400(W) x 250(D)
3 380 - 415 50 or 60 6.1 5 500(H) x 400(W) x 250(D)
5 380 - 415 50 or 60 9.7 5 500(H) x 400(W) x 250(D)
7.5 380 - 415 50 or 60 14 5 500(H) x 400(W) x 250(D)
10 380 - 415 50 or 60 18 5 500(H) x 400(W) x 250(D)
15 380 - 415 50 or 60 27 5 500(H) x 400(W) x 250(D)
20 380 - 415 50 or 60 34 5 500(H) x 400(W) x 250(D)
25 380 - 415 50 or 60 44 5 600(H) x 500(W) x 250(D)
30 380 - 415 50 or 60 51 5 600(H) x 500(W) x 250(D)
40 380 - 415 50 or 60 66 5 600(H) x 500(W) x 250(D)
CAT.NO.NF/MPBFPC/06/15 Rev. 1
Page 99 of 149
www.naffco.com 11
Page 100 of 149
Page 101 of 149
Page 102 of 149
Motor Line Terminal Wire Size Per Phase Output Motor Wire Siz Per Phase Ground Wire
Min Max Min Max Min Max
Power AWG or AWG or AWG or AWG or AWG or AWG or
[HP] MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq.
1.5 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
2 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
3 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
7.5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
10 12 3.3 8 8.4 12 3.3 8 8.4 8 8.4 6 13.3
15 10 5.3 6 13.3 10 5.3 6 13.3 8 8.4 6 13.3
20 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
25 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
30 6 13.3 6 13.3 6 13.3 6 13.3 6 13.3 1/0 53.5
40 4 21.2 1 42.4 4 21.2 1 42.4 4 21.2 1/0 53.5
AWG OR TIGHTENING
TORQUE USING
CIRCULAR EXTERNAL DRIVE
WRENCH
MILL SIZE LP.In N.m
14 75 8.5
12 75 8.5
10 75 8.5
8 75 8.5
6 110 12.4
4 110 12.4
2 150 16.9
1 150 16.9
1/0 180 20.3
2/0 180 20.3
3/0 250 28.2
4/0 250 28.2
250 325 36.7
350 325 36.7
500 375 42.4
600 375 42.4
700 375 42.4
750 375 42.4
800 500 56.5
1000 500 56.5
CAT.NO.NF/MPBFPC/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: [email protected]
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Page 104 of 149
Accessories
DATED 07-01-07
Line Pump Meter Range Model Number Model Number Model Number Model Number
Size GPM Min. & Max. Grooved Butt Weld 150# Flanged <Threaded>
GPM *300#
FLANGED*
**1-1/4” 25 12.5 – 50 * 1.25”-25-G 1.25”-25-B * 1.25”-25-F 1.25”-25-T
* DENOTES NON-
NON-STOCK ITEM, PLEASE CHECK WITH FACTORY FOR AVAILA
AVAILABILITY
**SIZES 1-1/4”, 2”, 2-1/2", & 14” ARE NOT FM APPROVED PER FACTORY MUTUAL**
Model: SD-P
TECHNICAL DATA :
DIAL SIZE : 90mm 3 1/2½”
½,
,]Ê
°
g
g £xä
g Óää
g Óxä
g Îää
g Îxä
g {ää
g {xä
g xää
g xä
g Çxä
£äää
£Óää
g
nORn
"
Óä {ä nä {ä nä £ää £Óx £xä Óää Óxä Îää {ää xää xä Çxä £äää £Óää
Îä Èä Èä £xä Îxä {xä
1 1 1 1 1 1 8 D C I 6 8 I ; 6 8 I D G N 3 3 3 3 3 3
1 1 1 1 1 1 8 D C I 6 8 I ; 6 8 I D G N 3 3 3 3 3 3
½,
,]Ê
°
FEATURES
• Meets NFPA 30 requirements.
• Sized as specified by NFPA 20 for fire pump applications.
• Designed and Fabricated in accordance with UL 142 (Steel Aboveground
Tanks for Flammable and Combustible Liquids) standard .
• Tested for tightness against leakage.
• Top quality fittings and fabrication materials.
• Sturdy lifting lug and legs.
• Vent opening to prevent build-up of pressure or vacuum inside the tank
during filling, emptying or due to atmospheric temperature changes.
• Approved welding process.
Vent Assy.
Inlet NOTES
D 1. Fuel tank outlet must be even with
1 4 5 5 engine fuel pump centerline.
Lift Lug
2. Fuel tank should be located as close to
Expansion Volume 5%
engine as possible.
3. Fuel tank should have a slope of 6 mm
per foot towards drain plug.
1
2
4. Fuel tanks should be located above
ground.
Fuel to Engine
Sump Volume 5%
5. The usable volume of the fuel tank is
90% of the total fuel tank volume.
3
Fuel from Engine
6. Vent pipe and fuel lines should be of
black steel pipe.
Drain
7. All pipe lines should be inspected
Ø2.5" Removable Leg
Minimum 500mm thoroughly to ensure that joints are leak
free.
150 150
8. Fuel tank should be cleaned periodically
W L
DIESEL TANK SIDEVIEW DIESEL TANK ELEVATION and fuel level should be checked weekly for
fire pump applications.
Applicable welding processes are Gas Metal Arc Welding (GMAW) and/or Shielded Metal Arc Welding (SMAW). Shell, Dish
Head and Lift Lug material is carbon steel, ASTM A36 and legs shall be of carbon steel pipe, ASTM A53. Standard height for the
tank leg is minimum 500 mm.
TANK DIMENSIONS
CAPACITY (GALLONS) DIA (D) LENGTH (L) WIDTH (W)
70 600 1050 430
150 800 1250 575
250 1000 1325 720
310 1070 1450 768.5
All Dimensions are in mm unless otherwise indicated.
FITTINGS
ITEM DESCRIPTION MATERIAL QTY
1 1/2" NIPPLE CARBON STEEL 2
2 1/2" NPT BALL VALVE BRASS 1
3 1" NPT PLUG CARBON STEEL 1
4 4" NIPPLE CARBON STEEL 1
5 2" NIPPLE CARBON STEEL 2
In line with NAFFCO policy for continuous product development, Page 116 of 149 NAFFCO FZCO | Email: [email protected] | www.naffco.com
NAFFCO has the right to change specifications without prior notice.
Serving Over 100
100
00 Countries
C
Co
Cou
ou
oun
unt
ntr
ntri
ntrie
trie
ries
ies
ess W
Worldwide
Wo
Wor
Worl
orld
rld
rldw
ldw
dw
dwi
dwid
wid
wide
de
e
CAT.NO.NF/FP/RAP/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: [email protected]
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.
Page 117 of 149
Product Listings / Certificates / Approvals
QXXW.EX16182
Centrifugal Fire Pumps, Vertical Turbine
Page Bottom
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
QXZF.EX5190
Fire Pump Motors
If you notice a change to your QXZF Listing Card, click here to learn more.
Page Bottom
Number Rated
Model FL Service of Ins Prot. Ambient
No. Output Hz/DC Volts Amps Factor Poles Speeds RPM Phases Class Type (°C)
Models HJN; followed by three digits or letter or combination of both; followed by 1 or 2; followed by a letter A through D;
followed by one numeral 0 through 9 or any Letter A through Z; followed by 1, 2, 3 or 4; followed by one digit 1 through 9;
followed by one numeral 0 through 9 and one letter A through Z; followed by one numeral 0 through 9 and one letter A through
Z; followed by one numeral 0 through 9 and one letter A through Z.
Models T; followed by letter C; followed by a letter A; followed by three digits or letter or combination of both; followed by one
digit 0 through 9; followed by a letter A through D; followed by one digit 0 through 9 or any Letter A through Z; followed by one
digit 1 through 5; followed by one digit 1 through 9; followed by one digit 1 through 3; followed by one digit 0 through 9 or one
letter A through Z; followed by one digit 0 through 9 or one letter A through Z; followed by one digit 0 through 9 or one letter A
through Z.
Trademark and/or Tradename: "2GREEN" , "Century" , "Century Electric" , "EX5190" , "EconoMaster" , "Fasco" , "Genteq" , "HeatMaster" ,
"LEESON" , "LEESON ELECTRIC" , "LEESON Electric" , "Lincoln Motors" , "Marathon" , "Marathon Electric" , "Marathon Generators" , "Marathon
Motors" , "Morrill Motors" , "Regal" , "Sinya Motor" , "Source 1" , "Uppco" , "York" ,
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
QYLU.EX15238
Internal-combustion Engines for Driving Stationary Fire Pumps
Page Bottom
See General Information for Internal-combustion Engines for Driving Stationary Fire Pumps
Rated
No. of Rated Speed
Model Cylinders HP (rpm)
FD 30 H 3 19 2900
FD 50 H 4 36 2900
FD 80 H 4 50 2900
FD 80 R 4 50 2900
FD 110 R 6 87 2900
FD 95 H 6 95 2900
6 175 3000
6 255 3000
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
QYZS.EX15064
Pump Controllers, Fire
Page Bottom
Diesel Engine Fire Pump Controller, Model NFY-D, followed by R1, followed by -110 or -230, followed by -50 or -60, followed by -12 or -24,
may be followed by additional suffixes.
Microprocessor-Based Diesel Engine Fire Pump Controller, NFY Type Diesel Engine Fire Pump Controllers, Model NFY, followed by -D,
followed by -M1, followed by -110 or -230, followed by -50 or -60, followed by -12 or -24, may be followed by additional suffixes.
Electric Fire Pump Controller, Model NFY, followed by -SD or -DO, followed by R1 followed by -380 or -415, followed by .yyy, where yyy
represents two or three digits denoting hp from 40-400 hp, followed by -50 or -60, may be followed by additional suffixes.
Microprocessor-Based Electric Fire Pump Controller, NFY Type Electric Fire Pump Controllers, Model NFY, may be followed bt -ATS, followed
by -SD - DO or -SS, followed by -M1, followed by 230, 380 or 415, followed by yyy where yyy represents two or three digits denoting power in
HP, followed by 50 or 60, and may be followed by additional suffixes.
Microprocessor-based variable speed drive electric fire pump controller, Model NFY, may be followed by -ATS, followed by -VFD, followed
by -DO or -SS, followed by M1, followed by 380 or 415, followed by yyy where yyy represents two or three digits denoting power in HP, followed
by 50 or 60, and may be followed by additional suffixes.
These controllers are suitable for use on circuits capable of delivering high fault currents with maximum values as shown in the following table.
For NFY-DO and NFY-SS Series Utilizing LSIS CO LTD Circuit Breakers
Models with suffix "-ATS are provided with Automatic Transfer Switches and are suitable for use on circuits capable of delivering high fault
currents. The withstand rating of the normal power side is the same as the withstand ratings of controllers without transfer switches. The
withstand rating of the alternate power side is determined by the transfer switch as indicated by the following tables:
+ - Branch Circuit Protection provided by same circuit breaker models specified in the NFY-SD, NFY-DO and NFY-SS short-circuit
tables.
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
NITW.E309408
Industrial Control Panels
Page Bottom
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
VEVX.EX6714
Gauges, Pressure
Page Bottom
Gauges, Pressure
Pressure indicating gauge, Model SD-P, 3-1/2 in. size, with dials graduated 0-250 psi.
Model SD-P1, 3.5 in. size, with dials graduated 0-300 psi.
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
EEEV.MH49928
Aboveground Flammable-liquid Tanks
Page Bottom
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2018 UL LLC".
Model NFY
Model NFY-aM1-b-c-d-e Electric Motor Fire Pump Controller - Low Voltage
Standard Enclosure: NEMA/UL Type 2.
Ambient Temperature Operating Range: 39°F (4°C) to 122°F (50°C)
b=
a= M1 =
Voltage, VAC
Starting Type Control Type Ho
(3 phase)
d = Frequency (Hz)
e = Additional suffixes denoting optional equipment
50
60
Model NFY-DM1
Model NFY-Da-b-c-d-e Diesel Engine Fire Pump Controller
Standard Enclosure: NEMA/UL Type 2.
Ambient Temperature Operating Range: 39°F (4°C) to 122oF (50°C)
b= c=
a=
Voltage Frequency
Control Type
(VAC) (Hz)
M1 –
110 50
Microprocessor
230 60
Based
d=
e = Additional suffixes denoting optional equipment
Battery Voltage (VDC)
Pump
Rating, Meter
gal/min Line
(dm3 Size, Model
/min) in. Designation
150 3 3-150-X*
(570)
200 3 3-200-X*
(755)
250 4 4-250-X*
(945)
300 4 4-300-X*
(1135)
400 4 4-400-X*
(1515)
450 4 4-450-X*
(1705)
450 5 5-450-X*
(1705)
500 5 5-500-X*
(1895)
750 5 5-750-X*
(2840)
500 6 6-500-X*
(1895)
750 6 6-750-X*
1000 6 6-1000-X*
(3785)
1250 6 6-1250-X*
(4730 )
1000 8 8-1000-X*
(3785)
1250 8 8-1250-X*
(4730)
1500 8 8-1500-X*
(5680)
2500 8 8-2500-X*
(9465)
3000 8 8-3000-X*
(11 355)
1500 10 10-1500-X*
(5680)
2000 10 10-2000-X*
(7570)
2500 10 10-2500-X*
(9465)
3000 10 10-3000-X*
(11 355)
3500 10 10-3500-X*
(13 250)
4000 10 10-4000-X*
(15 140)
4500 10 10-4500-X*
(17 035)
2000 12 12-2000-X*
(7570)
2500 12 12-2500-X*
(9465)
3000 12 12-3000-X*
(11 355)
3500 12 12-3500-X*
(13 250)
4000 12 12-4000-X*
(15 140)
4500 12 12-4500-X*
(17 035)
5000 12 12-5000-X*
(18 925)
Each system consists of a Global Vision Venturi, a differential pressure meter (for portable or permanent installation) and
associated fittings. Meter faces are available in direct readout in both GPM (gallons per minute) and LPM (liters per minute), or
optional 3
m/h (cubic meters per hour).
* The suffix “X” signifies the available end connections as follows:
F- Flanged ends 150 lb (rated working pressure = 275 psi [1895 kPa])
F3- Flanged ends 300 lb (rated working pressure = 500 psi [3445 kPa])
B- Weld ends (rated working pressure = 500 psi [3445 kPa])
G- Grooved ends (rated working pressure = 500 psi [3445 kPa])
Models G40A, G60A, G80A, G100A, G125A, G150A, G200B, G250A, G300A, G350A, G400A,
G450A, F500A, F590A ...
Model (kW) r/min 1:2 4:7 2:3 3:4 4:5 5:6 10:11 1:1
G40A 40 1760 900 1000 1173 1320 1408 1467 1578 1760
(30)
G60A 60 1760 900 1000 1173 1320 1408 1467 1578 1760
(45)
G80A 80 1760 900 1000 1173 1320 1408 1467 1578 1760
(60)
G100A 100 1760 900 1000 1173 1320 1408 1467 1578 1760
(75)
G125A 125 1760 900 1000 1173 1320 1408 1467 1578 1760
(93)
G150A 150 1760 880 1006 1173 1307 1398 1493 1579 1760
(112)
G200B 200 1760 880 1006 1173 1307 1398 1493 1579 1760
(149)
G250A 250 1760 880 1006 1173 1307 1398 1493 1579 1760
(186)
G300A 300 1760 880 1006 1173 1307 1398 1493 1579 1760
(224)
F500A 500 1760 897 1019 1173 1320 1408 1467 1584 1760
(373)
F750A 750 1760 897 1019 1173 1320 1408 1467 1584 1760
(559)
Usable Vert.
Power, Shaft Horizontal Shaft r/min, Speed Increasing Ratios
hp Speed, Driver:Driven
Model (kW) r/min 11:10 6:5 5:4 4:3 3:2 7:4 2:1
G40A 40 1760 1963 2112 2200 2347 2640 3061 3520
(30)
G100A 100 1760 1963 2112 2200 2347 2640 3061 3520
(75)
G125A 125 1760 1963 2112 2200 2347 2640 3061 3520
(93)
G150A 150 1760 1961 2074 2216 2369 2640 3080 3452
(112)
G200B 200 1760 1961 2074 2216 2369 2640 3080 3452
(149)
G250A 250 1760 1961 2074 2216 2369 2640 3080 3452
(186)
G300A 300 1760 1961 2074 2216 2369 2640 3080 3452
(224)
G450A 450 1760 1963 2112 2200 2347 2640 3061 3520
(336)
Scope:
Design Installation, Maintenance and Training of Fire Fighting which includes Sprinklers, Fire
Alarm, Low voltage, Voice evacuation, Emergency Light and Fire Suppression System Covering
Clean Agent, Co2, Inert Gas, Deluge Water Spray System and Foam System including Fire
Doors for Industrial and Construction Applications.
Manufacturing for Fire Fighting Equipment, Fire Extinguishers, Fire Pump Set Assemblies,
Hydrants (Wet and Dry), Hose Reels and Cabinet for the Fire Protection Systems.
Through an audit, documented in a report, it was verified that the management system
fulfills the requirements of the following standard:
DQS Inc.
Ganesh Rao
Managing Director
Accredited Body: DQS Inc., 1130 West Lake Cook Road, Suite 340, Buffalo Grove, IL 60089 USA
Administrative Office: Deutsch Quality Systems (India) Pvt. Ltd., 5th Floor, Anjaneya Techno Park,
147, HAL Airport Road, Kodihalli, Bangalore - 560 017 - India
Annex to Certificate
Registration No. 20002009 QM08
NAFFCO FZ CO.
Plot no. S10201
Jebel Ali Free Zone ( South)
Dubai
UAE
Noted
Noted
Noted
Noted
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Main Contractors
Scope
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply
Comply as noted our proposed electrical motor is ODP with 1760 RPM Type.
Comply
Comply
Comply
Comply
Comply
Comply as
Noted,Proposed
fuel tank capacity is
coming 150 Gallon
which is the Comply
sufficiant capacity
for your
requirement as per
NFPA 20
Standard,please
refer our fuel tank
data sheet in
technical submittal Comply
for more details...
Comply
Comply
Comply
N/A
N/A
N/A
Comply as
noted,proposed
jockey pump is joslyn
Comply manufactured and
TEFC type.
Comply
Installation contractors
scope
Installation Contractors
scope
Comply
Comply