UV-Technology: Technical Documentation ELC N6 / Elc N8 / Elc N10
UV-Technology: Technical Documentation ELC N6 / Elc N8 / Elc N10
UV-
TECHNOLOGY
Technical Documentation
ELC® N6 / ELC® N8 / ELC® N10
GB
eta plus electronic gmbh
Lauterstraße 29, D-72622 Nürtingen, Telefon +49 (0) 70 22 - 60 02-80, Fax +49 (0) 70 22 – 6 58 54
Postfach 1411, D-72604 Nürtingen, e-mail: [email protected]
eta plus electronic gmbh
––––––––––––––––––––––––––––
Lauterstraße 29, 72622 Nürtingen,
EingetragenTelefon +49 7022
unter HRB 6002-80,
724321 Fax +49 USt.-Id.-Nr.
AG Stuttgart, 7022 65854, DE
E-mail: [email protected], www.eta-uv.de
146267800
Eingetragen unter HRB 724321 AG Stuttgart, USt.-Id.-Nr.
Geschäftsführer: DE 146267800,
Dr. Peter Geschäftsleitung: Uwe Uhlemann, Dr. Markus Roth
Schwarz-Kiene
ELC® („Electronic Lamp Control“) is a registered trademark of
IST Metz GmbH.
Contents
1 Safety ................................................................................................. 1
1.1 Definition of Symbols .................................................................................1
1.2 Safety Advice ..............................................................................................1
1.3 Correct operation........................................................................................2
1.4 Extended use ..............................................................................................2
2 Description of functions................................................................... 3
3 Installation ......................................................................................... 4
3.1 Mounting of casing .....................................................................................4
3.1.1 Back mounting ................................................................................................ 5
3.1.2 Side by side rack mounting............................................................................. 6
3.2 Connection ..................................................................................................8
3.3 Control current connections....................................................................12
3.4 Explanations of the control functions for ELC.......................................14
3.4.1 Release relay ................................................................................................ 14
3.4.2 Control input START..................................................................................... 14
3.4.3 Setting lamp power ....................................................................................... 14
3.4.4 Table: lamp power ........................................................................................ 15
3.4.5 Earth fault control.......................................................................................... 16
5 Troubleshooting.............................................................................. 19
5.1 Repair ELC ................................................................................................19
6 Technical Data................................................................................. 20
1 Safety
Stop (Stop Danger). This symbol warns of serious danger of severe injury to
persons. It must be strictly observed.
The installation and starting up may only be carried out by skilled electricians.
Do not open the ELC before it is disconnected from the mains. BEWARE OF
RESIDUAL VOLTAGE! The unit may still be live up to three minutes after it has
been switched off.
2 Description of functions
The electronic ballast ELC is designed to operate medium pressure discharge lamps as
described in chapter 6.
In contrast to conventional ballasts (inductive lamp ballast or transformer or transformer with
transductor), the lamp with an electronic ballast is operated with high frequency (approx.
100 kHz). The lamp does not flicker and dimming is infinitely adjustable to a range between
20 % and 100 % of the electric power or to between 15 % and 100 % of the UV radiation
respectively.
Dimming
The possibility of dimming the lamp has two advantages. Firstly the lamp can be switched to
minimum load (standby operation) during longer idle times and energy can thus be saved.
Secondly the optimum lamp power can be determined and adjusted as appropriate.
Power control
The ELC offers a high level of lamp power constancy due to its integrated power control.
Variations in operating voltage of ± 10 % do not affect lamp power.
Ignition device
When the lamp is switched on the ELC initiates trigger pulses to fire the lamp; a separate
ignition device is not required.
Other performance characteristics
• High level of electrical efficiency.
• The ELC has a network power factor of > 0.9. It can be operated directly at the network
without compensation.
• The potential-free control inputs allow various lamp conditions such as maximum lamp
power, dimming or standby to be set.
• The digital control inputs are designed for control voltages of between 10 and 30 V AC or
DC. Therefore ELC can be easily integrated into the installation’s electric system.
• Lamp current and lamp power are continuously recorded and output as analogous
0-10 V signals.
• The ELC monitors the lamp cables for earth fault.
• The potential of both lamp outputs is separated from that of the supply voltage.
• The ELC is both short-circuit proof and safe in open circuit operation at the lamp output.
3 Installation
The ELC must be installed in a control cabinet with at least IP 54 protection (see
EN 60529). Operation without a control cabinet or in a control cabinet with a
lower degree of protection is not permitted.
The ELC may only be installed vertically (control connections at the bottom,
power connection at the top) allowing for at least the minimum spacing as
shown. No other positioning is possible.
The installation possibilities are shown in 3.1.1 and in 3.1.2.
The ELC should not be mounted in the immediate proximity of sensitive
electronic equipment. An appropriate distance must be maintained to scatter
field transformers or other inductors.
The flow of cool air in ELC must be safeguarded. The ambient temperature must
not exceed the values described in chapter 6!.
Impure cooling air could affect the functionality of the ELC. This can be avoided
by installing a fine air filter.
min. 20
min. 20 min. 20
pin-and-socket connector
for control signals
min. 50
90 mm
Top
473 mm
500 mm
min. 100
23 mm 270 mm 23 mm
130 mm
mains connection
319 mm
min. 20
pin-and-socket connector
for control signals
min. 50
min. 100
Top
520 mm
539 mm
473 mm
min. 100
M8 (4x)
23 mm 80 mm
130 mm
mains connection
321 mm
If “side-by-side rack mounting“ is preferred, assembly brackets and screws can be provided
upon request.
3.2 Connection
L1 The power connections of the
L2
L3 ELC are situated on top of the
N
PE casing.
earthed lead network side
automatic cutout Fig. 3 shows the electrical
wiring plan.
L1 L2 L3
The connection of mains supply cables and lamp feeder cables must be
separated from control cables.
Mains connection
The mains connection of the ELC is
situated at the top right.
The cross section of the earthed wire
must be at least 4 mm².
The three phases must be provided with
an automatic cut-out.
In order to avoid damaging the terminal pins, please do not exceed the
following torque:
•
•
L1, L2, L3: 0,6 – 0,8 Nm
Grounding conductor: 3,0 – 4,0 Nm
The lamp feeder cable must correspond with the cable parameters described in
chapter Technical Data.
60 12
(measurements in mm)
The lamp feeder cable between the switch cabinet and lamp assembly must be laid in a
metal insulating tube. For the correct installation of the lamp assembly and lamp please
observe the corresponding manufacturer’s instructions.
Pin assignment
1 2 3 4 5 6 7 8 9 10
Start2 Max2 Min2 GND GND GND GND ES2 n.c. OK2
20 19 18 17 16 15 14 13 12 11
Lampenleistung
Lamp power
100%
20 %
0V 10 V Set value
ES
In order for the earth fault control to function properly
it is essential that it be connected as prescribed,
8 13 particularly the earth connectors.
Control
The relay contact ES (pins 8 and 13 on the control
R_error
If an earth fault occurs during lamp operation we recommend shutting down the
installation rapidly and correcting the error. The lamp must not be started if
earth fault has occurred.
In order to avoid an unwanted reaction of the earth fault control during faultless
operation, the isolation resistance of the lamp cables and all lamp connectors
must be greater than 10 Mohm.
If the release relay RELEASE (s. 3.4.1) is open the earth fault relay ES will not
give clear information! In this case an error message “earth fault“ should not be
issued.
4 Operation of ELC
You always have to ensure that the correct lamp type is used (see chapter 6) and that all
wireing is properly connected !
If a HIGH signal has already been given to the digital START control input before
the ELC is switched on, then the lamp will not start up. In the case of a power
failure, the ELC cannot automatically switch on the lamp when power returns.
Before switching on the lamp, a LOW signal must be applied to the digital control
input.
Turn the ELC on maximum lamp power during the lamp warm-up period.
Maximum lamp power can be adjusted as follows:
• HIGH signal at the digital MAX control input or
• 10 V control voltage at the analogous SET VALUE control input.
During warm-up the lamp power stays at a very low level over a longer period of time and
after approximately 60 seconds rapidly increases to its nominal power. The lamp is operated
with increased power until the nominal power is reached.
The adjustment of lamp power via the analogous SET VALUE control input is
only possible if a LOW signal is applied to the digital MIN and MAX control
inputs.
In order to avoid heat accumulation in the ELC, the operating voltage should be
left on for a few minutes. Before restarting, the lamp must be sufficiently cooled
down as it cannot be fired otherwise.
5 Troubleshooting
Troubles Possible causes Corrective action
No RELEASE after having The ELC is not provided Check fuses and voltage of
switched on the ELC. with operating voltage terminals
Relay RELEASE open
Lamp is switched-ON Switch-OFF lamp
(control input START at
HIGH)
Fault in ELC Contact manufacturer,
see 5.1
Lamp does not fire after being Lamp is too hot Let lamp cool down, increased
switched on, and the relay cooling probably required
RELEASE opens
Lamp not connected Check plug contacts between
ELC and lamp
Lamp defective Replace lamp
6 Technical Data
General data ELC
mains frequency 50 / 60 Hz
tolerance mains voltage nominal voltage ± 10 %
recommended air flow 120 m3 / h per ballast
Control range approx. 20 - 100 %
Firing voltage 2000 V / < 1 sek.
Protection IP 20
Ambient temperature 0°C to +40°C in operation
-20°C to +70°C during storage and transportation, before initial operation leave
at least 4 hrs at room temperature
Permissible pollution pollution severity 2 according to VDE 0110
Permissible humidity relative atmospheric humidity 80 %, non-condensing
Dimensions (H x W x D) approximately 500 x 320 x 130 mm
Weight approximately 16 kg
Installation position only vertical (lamp and power connection at the top; control connections at the
bottom) respecting the minimum spacing in 3.1
EMC Verified according to
EN 55011
EN 61000-3-3
EN 61000-6-2
Safety Verified according to
EN 50178
Leakage current Leakage current > 3 mA, see Chapter 1 “Safety“
Power factor typ. 0,95 typ. 0,94 typ. 0,94 typ. 0,94 typ. 0,94 typ. 0,94
Power efficiency typ. 0,96 typ. 0,95 typ. 0,96 typ. 0,95 typ. 0,96 typ. 0,95
Line protection* 16 A 16 A 16 A 16 A 25 A 25 A
Lamp power 6 kW 6 kW 8 kW 8 kW 10 kW 10 kW
8068 1,6 kV 2x2,5 mm² 5-20 m 5-20 m 5-20 m 5-20 m 5-20 m 5-20 m
Ø 10,5 mm