Ten Deadly Conditions in Electrical Systems
Ten Deadly Conditions in Electrical Systems
These deadly electrical problems can affect even luxury boats like this one.
Editor's note: This article describes ten conditions that, when present in your boat’s
electrical system, can cause serious problems. Portions of this article originally appeared
in Blue Sea Systems' September and October 2019 newsletters. The information this
article contains remains relevant today.
The greatest concern here is with AC circuits that feed receptacles that can be easily
overloaded.
Even when using 105°C rated wire at its maximum current rating, the wire may be too
hot to touch without burning yourself. At these high temperatures, corrosion at
terminals will be accelerated and the system may have shortened life.
The amperage at which fuses actually blow, and circuit breakers actually trip, is
considerably higher than their nominal ratings, the rating usually marked on the
unit.
Wire and circuit protection devices heat up dramatically when they carry 100
percent of their rated value for several minutes or more.
Heat from high current can melt wire insulation and fuse blocks.
SEA, Maxi, ATO and AGC fuses, and most circuit breakers, blow or trip at about 130
percent of their rating. ANL fuses blow from 140 percent to as high as 266 percent of
their rating. When fuses carry 100 percent of their rated current value, they generate
excessive heat. When wires carry 100 percent of their rated current value, they also
generate excessive heat. In combination, the heat produced by fuses and wires carrying
high current can melt wire insulation and fuse blocks.
This heat generation may become critical when loads run for a considerable time. Large
diameter wires take a long time to heat up, so short-term operations like bow thrusters,
windlasses, and macerator pumps seldom run long enough for this kind of heating to
occur. For example, a 2/0 wire may take 25 minutes to approach its maximum
temperature. In contrast, small diameter wires reach near peak temperature in less than
ten minutes.
For loads and appliances that run continuously for 10 to 30 minutes, choose circuit
protection and wire so that current does not exceed 80 percent of their rating. For more
information in this topic, refer to Blue Sea Systems’ Technical Brief: Choosing Circuit
Protection.
This boat nearly burned because a corroded shore power connection overheated
(BoatUS Seaworthy photo).
Shore power connectors can have both electrical and mechanical stresses applied. The
locking ring keeps the plug from backing out and fixes the two elements together so
that the connection is not moved by normal motions. The constant working of the
connection between shore power cord plug and receptacle with the boat's motion can
loosen the connection, increase corrosion and weaken spring contact tension.
The shore power cable and connection is the most easily overloaded point of wiring on
the boat because it feeds all of the AC system including receptacle circuits. Every new
appliance brought onboard can add a new load, and devices like electric grills, hair
driers, air conditioners and space heaters are designed to use about 12 Amps each. It is
easy to turn on more than the rated capacity of your system, and the circuit breaker
system will not trip until your overload is at about 130 percent or more. In this
condition, a weak connection between plug and receptacle can become a fire source.
Lack of a good connection between DC negative and AC safety ground may put AC
current in the water around your boat.
There is a downside to this green wire connection. This safety ground can also provide a
path for galvanic current if the boat is not adequately protected with galvanic isolators.
However, most marine industry organizations and professionals now consider it
standard practice to install this wire. Safety requires providing the grounding wire, either
directly or through a galvanic isolator, or using a properly installed marine isolation
transformer. Some people have left off the ground wire in a mistaken notion that they
are providing galvanic protection, but forget that they are compromising safety for
those on the boat, on the dock, and in the water. Electrically induced drowning is now
recognized as a previously undocumented cause of death. The Coast Guard is funding a
study to isolate and investigate this hazard.
The green wire can be tested and indicate continuity but be unable to safely carry
enough current to trip a circuit breaker during a fault. There are ways to check the
quality of the connection.
An Ohmmeter test may show very little resistance in a green wire installation, yet the
wire may be incapable of carrying 30 amperes or the higher currents needed to trip a
circuit breaker during a fault. The minimum resistance reading of an Ohmmeter will not
necessarily indicate if a connection is compromised, such as a connection making to
only a single strand of wire. There are specialized ground resistance testers that apply
significant current, but they are uncommon. Careful visual inspection of the grounding
connections helps, but even a careful surveyor may have a hard time finding all
connections and tracing the wiring path.
One way to test the green wire connection quality is to connect a spotlight or other
heavy 12V load, positive to the boat’s battery, and the negative to the safety ground pin
of the shore cord. In a properly wired boat, the safety ground pin should return to the
battery negative after first connecting at the AC panel. If the light burns bright and
steady, there probably is a good grounding system. This is a good check to perform if a
boat has an unknown maintenance history, has been rewired, or is being repaired after
damage.
A half gallon of gasoline carried on board to fuel the dinghy motor turns a diesel boat
into a gasoline boat. The starter, alternator, switches, and circuit breakers have all been
selected according to the rules for a diesel engine system. Dinghy fuel, if carried on
board, should be stored in lockers that vent overboard just like propane lockers.
Gasoline vapors are heavier than air and will pour down the companionway or from
internally vented lockers right into the bilge and engine spaces.
GFCI receptacles have contacts to open when a fault is detected and as of this writing
there are no such devices with ignition protection, and it may not be possible to do so.
Any receptacle in a gasoline engine room is suspect because plugging in or unplugging
an appliance can generate sparks. The use of portable power tools in such spaces is also
very dangerous because of brush arcing in the universal motors.
The power companies have developed a standard for 120 volt single-phase power
distribution in which one of the two conductors is designated the “hot” wire (the black
wire in North America) and the other, by default, the neutral (the white wire). However,
neither power conductor in an AC system is permanently at either a positive or a
negative potential. Their respective potentials alternate between zero, the maximum
positive, zero, and the maximum negative potential. This is what makes it AC.
If a shore cord is incorrectly wired so that the hot and neutral wires are reversed, the
“new” hot line now has no overcurrent protection because the branch circuit wiring is
only protected by a 30 or 50-ampere main circuit breaker. Worse, turning off the branch
circuit breaker leaves the circuit hot. The circuit breaker does turn the load on and off,
so all seems normal.
The branch circuit wires are only protected by the larger main circuit breaker in
the event of a failure of the white wire to ground.
Anyone working on the wiring and turning off the branch circuit breaker will still
be in contact with a live wire if the main breaker isn’t off. This can be a serious
shock hazard.
The outer shell of conventional screw in light bulbs is intended to be the neutral
conductor with a voltage near ground. Any broken bulb is dangerous to remove
when energized, and reverse polarity makes it worse.
Boats not wired to present-day ABYC standards may have only a single pole main
breaker and no reverse polarity lights to indicate a reverse polarity fault. This can
occur in internal wiring or more probably in marina wiring that is not performed
correctly. Private docks, and some commercial docks, may not always be wired by
skilled electricians and properly inspected.
Your boat should have a two pole main breaker if wired for 120V. It should also have a
reverse polarity indicator or warning device. A three pole breaker is appropriate for the
main breaker in a 120/240V system, because neutral faults can also exist in these
systems, with either an open neutral or reverse polarity generating hazards or damage
to equipment.
Inverters and changers are provided with grounding connections on both the AC side
and DC side. This grounding can prevent shocks from AC, and fire hazard from DC.
Frequently only the AC grounding connection is made. A fault in the DC side of the
system could provide enough current to overheat the AC grounding conductor without
blowing the large DC fuse. Therefore, a high amperage capacity DC grounding path
back to the DC system is required.
There is no mention of adequate measures to wire inverters and chargers in ABYC E-11
where most guidelines for electrical systems are found, so knowledge of proper
installation is readily overlooked. This information is actually contained in ABYC A-25 for
inverters, and A-24 for chargers.
Because this hazard has only recently been recognized, the installation instructions for
older generation inverters typically do not include this precaution, but most newly
designed units do. You may buy a new inverter from off the dealer shelf today and not
get the proper information because the instructions may have been written a few years
ago. For example, the instructions for a newly introduced inverter recommend a 2/0
cable for a 3 KVA inverter, but the instructions from the same manufacturer on their
older models give no recommendation at all.
The ground wire to the DC grounding system should not be smaller than one size
below the wire size required for the DC current carrying conductors.
The DC overcurrent protection device should not be sized at more than 150
percent of the capacity of the grounding conductor.
The ABYC Standards call for GFCIs to protect receptacles and therefore the appliances
that are plugged into the receptacle. However, the Standards do not require GFCIs for
permanently-wired appliances such as hot water heaters, space heaters, battery chargers
and air conditioners. These devices are assumed to be protected by a solid safety
ground connection to the case. However, it is good practice to also protect these
devices with GFCIs. It is possible to use the output of one GFCI receptacle to feed other
receptacles and permanently wired devices. By doing so, you can choose to provide
more protection than the minimum in the ABYC Standard thereby protecting these
downstream receptacles and devices.
GFCIs should be tested frequently, especially in areas subject to lightning or if there has
been any electrical malfunction onboard. Because of the corrosive atmosphere of the
marine environment, these devices may have a shorter life span on a boat than they
have ashore.
Be careful when using a wet-dry vacuum or other power tools in areas where fuel or
other explosive vapors are present.