Checkfire 210 Detection and Actuation System: Features
Checkfire 210 Detection and Actuation System: Features
CHECKFIRE 210
Detection and
Actuation System
Features
n Supervised power, detection, release, and communication
circuits
n Display module with LED system status indicators
n Compact size
BRANCH TERMINATOR
(ON END OF DETECTOR)
CHECKFIRE 210
SPOT THERMAL ELECTRIC MANUAL DISPLAY MODULE
DETECTORS (INSTALL ACTUATOR AND BRACKET
WITH HEAT SHIELD AND BRACKET
AND BRACKET)
DETECTION
CIRCUIT
CABLE
EOL AND TEES
DEVICE
DISPLAY
VISUAL CABLE
SEAL
INTERFACE
CONTROL
MODULE
RELEASE CIRCUIT
DROP CABLE
RELAY CIRCUIT
RELEASE CIRCUIT
CABLE
ELECTRIC- CABLE AND TEES
PNEUMATIC RELAY
ACTUATOR CABLE-LEADS
EXPELLANT
GAS
CARTRIDGE
AGENT
TANK
009269
Typical System Connections Display Module
The CHECKFIRE 210 Display Module communicates with the The CHECKFIRE 210 Display Module communicates with the
CHECKFIRE 210 Interface Control Module (ICM) through the Interface Control Module (ICM) to indicate system status.
display cable using threaded circular connectors. Color-coded Installation within reach of the operator provides easy access to
receptacles in the ICM are the central connection point for all operator controls.
system cables.
GUARD
System Cabling: Enables communication and control of DOOR
components.
n IP67 connectors
n Linear detectors
DELAY/RESET/ PUSH TO ACTIVATE/
n Spot thermal detectors SILENCE BUTTON ALARM WHEN LIT
BUTTON AND LED
n Pressure switch (detection circuit #2 only)
Release Circuit: Connects to a maximum of 10 electric-pneu- n Dust and water tight (IP67 rated)
matic actuators installed on agent tank expellant gas cartridges
using release circuit cable(s), tee(s), and release circuit drop n Durable high-strength glass-filled nylon material
cable(s). n Surface or bracket mounted
External Power Circuit: Provides a direct connection to the n Two index pins on back for secure mounting
vehicle power source using power circuit cable(s) and a single n Ambient temperature range: -40 °F to 185 °F (-40 °C to 85 °C)
fused power circuit cable, when external power is required.
n LED indicators provide notification of system status (internal
Auxiliary Output Circuit: Connects to external notification sounder matches LED pulse rate)
devices.
n PUSH To Activate / Alarm When Lit manual-activation button
Display Circuit: Connects display module with ICM. and LED
Relay Circuit: Provides connection for two independent internal – Provides manual actuation (immediate release)
relay contacts for connection by others. – Indicates alarm condition
n Guard door with visual seal to protect manual-activation
button
Detection n DELAY/Reset/Silence Button
A Linear Detector with an activation temperature rating of
– Restarts Time Delay #1 (TD1) before TD1 sequence expires
356 °F (180 °C) provides fire detection in the protected area. Two
twisted spring steel conductors separated by a heat-sensitive – Resets system (during non-alarm status)
insulator are limited to a minimum bend radius of 2 1/2 in. (64 –S
ilences internal sounder during fault conditions and isolate
mm). For easy installation, red color-coded connectors match mode
the red connectors of the entire detection circuit.
Spot Thermal Detectors have the temperature rating stamped
on the detector and are color-coded blue for 250 °F (121 °C) and
red for 350 °F (177 °C) operating temperatures. The included
retaining nut securely holds the detector in the required bracket
and heat shield.
Interface Control Module (ICM)
The CHECKFIRE 210 Interface Control Module (ICM) is
the central connection point for input/output circuits.
Through communication with the display module,
operators receive continuous system status updates,
and operator input commands go directly to the ICM.
Color-coded receptacles match with color-coded cable
connectors providing quick visual confirmation of
proper circuit connections.
BATTERY
COMPARTMENT
009267
ISOLATE
SWITCH
Battery Module
A supervised 3.6 VDC lithium CHECKFIRE 210 Battery
Module provides internal power for the CHECKFIRE
210 System. A connector pigtail extending from the
top of the battery connects to the ICM battery cable.
COLOR-CODED
RECEPTACLES (7
PLACES) 009271
Electric-Pneumatic Actuator
With a focus on ease of installation and safety, the
Electric-Pneumatic Actuator reduces system complex-
The protective battery compartment cover is held ity. The Protracting Actuation Device (PAD) directly
in place with 4 captive screws. Besides the internal actuates the electric-pneumatic actuator pin eliminat-
power supply, the battery compartment includes ing the need for pneumatic actuation.
the battery cable, a mini USB connection port, and
the programming interface (button and LEDs). The The re-designed PAD with plug-in spade connectors
system programming may be accomplished with the is easy to install and replace without tools. After plug-
manual programming button and indicator LEDs or ging the PAD into the release circuit drop cable, the
by using a computer with the ANSUL CHECKFIRE 210 cable is hand-tighted to the top of the electric-pneu-
Programmer software communicating through the matic actuator.
mini USB port.
An isolate switch on the side of the ICM provides ease
of access to temporarily disable the automatic system
release function. While disabled, manual system
release is still available. An amber isolate LED on the
display module continues to pulse until the switch is
returned to normal.
n Dust and water tight (IP67 rated)
n Ambient temperature range: -40 °F to 185 °F For installer safety during assembly of the Electric-
(-40 °C to 85 °C) Pneumatic Actuator to an expellant gas cartridge,
the actuator includes a new preventor. The integral
n Internal battery compartment with IP67 cover
preventor reduces the possibility of attaching the
n System isolate switch actuator with the pin not completely retracted. It also
n Steel mounting plate provides a metal to metal seat with the expellant gas
cartridge eliminating the spacing washer.
If required, optional pneumatic actuation is available.
Electric Manual Actuator System Specifications
The newly designed Electric Manual Actuator (EMA) Interface Control
provides electrical activation of the fire suppression Module Power: Internal power source
system. Pulling the pin and striking the red button and/or: 12/24 VDC nominal
sends a signal to the interface control module for external power
immediate actuation of the electric-pneumatic actua- (24 hour operation)
tor. Upon actuation, the expellant gas cartridge initi- Operating
ates fire suppression system operation. Temperature Range: -40 °F to 185 °F
(-40 °C to 85 °C)
Shock: In accordance with UL1254
Vibration: In accordance with UL1254
Moisture and Dust: IP67 per IEC 60529
Electromagnetic
Compatibility: Heavy Industrial EMC Directive
Compliant (2004/108/EC)
Approvals
FM Approved and CE Marked
009268
Ordering Information
Part No. Description
Part No. Description
Display Cables
System Components
439452 Cable, Display, 2 ft (0.61 m)
439560 Display Module, CHECKFIRE 210
439454 Cable, Display, 5 ft (1.53 m)
439564 Mounting Bracket, CHECKFIRE 110/210
439456 Cable, Display, 10 ft (3.05 m)
439561 Interface Control Module, CHECKFIRE 210
439458 Cable, Display, 20 ft (6.10 m)
439569 Electric-Pneumatic Actuator
(normally supplied with agent tanks) 439460 Cable, Display, 30 ft (9.15 m)
439400 Electric Manual Actuator (EMA) 439462 Cable, Display, 50 ft (15.24 m)
440537 Electric Manual Actuator Bracket 439449 Connector, Bulkhead, Display Cable