Hi-Fog For Buildings: Technical Introduction
Hi-Fog For Buildings: Technical Introduction
Technical introduction
© Jussi Tiainen
HI-FOG® is the trade name of the high- story buildings, water leakage from a HI-FOG® is the result of unceasing and
pressure water mist fire protection sys- discharge in upper stories only makes relentless research and development.
tem developed and manufactured by the situation worse. HI-FOG® has been tested in more full-
Marioff. The HI-FOG® Water Mist Fire scale fire tests than any other water mist
Protection System uses extremely small The exceptional performance of HI-FOG® fire protection system and ranks among
amounts of pure water to control, sup- helps ensure water use is kept to a the most widely certified.
press or extinguish fires. minimum. In demonstrations compar-
ing HI-FOG® traditional sprinklers, High-pressure water mist systems as ex-
Traditional sprinkler systems employ HI-FOG® used nearly ten times less wa- emplified by HI-FOG® are a major step
wetting as the fire fighting mechanism, ter to bring the fire under control – 470 l forward in water-based fire protection.
and therefore require very large amounts (119 gal.) compared to 5000 l (1321gal.). The number of application areas, test
of water. HI-FOG® uses water much standards and performance criteria,
more efficiently, up to 90% less than a Tested and approved type approvals, and market acceptance
traditional sprinkler system, while deliv- The fire fighting performance of any in the form of customer references are
ering equivalent or better performance water mist system is dependent upon growing at an accelerating rate.
for the same application. many factors. Therefore, any system
should undergo full-scale fire testing as HI-FOG® can be used to fight both solid
The potential damage and risk to life part of an approval process based on a and liquid fires. There are very few fire
posed by a fire are clear and well under- commonly accepted set of performance risks which cannot be protected against.
stood. The potential damage caused by criteria. Water-based fire fighting systems cannot
a water-based fire fighting system, how- be used to fight liquid metal fires or to
ever, is often underestimated. In multi- protect materials which react adversely
when combined with water.
VdS OH2
Approval FM LH FM LH VdS OH1 VdS OH1 VdS OH3 IMO
Parking garage
Technology
11m (36ft)
Max room height 5m (16ft) 5m (16ft) 4m (13ft) 4m (13ft) 3m (10ft) 5m (16ft)
6600m3
volume unlimited unlimited unlimited unlimited unlimited unlimited
(233077ft3)
Hotels
APPLICATION
Data Centers *
Heritage buildings
Hospitals
Fire is a process which involves a chemical • Fuel: solid (Class A), liquid (Class B) or gas-phase
reaction between a combustible fuel and • Oxygen
oxygen. The four prerequisites for this • Heat
process to be sustained: • Uninterrupted chemical reaction
The size of a fire is described by its heat fixed system’s role typically consists of
release rate, measured in Watts (W). A controlling or suppressing the fire until • Control
flaming fire that can be approached with it is extinguished manually such that re- Limitation of fire size, decrease of
a hand-held extinguisher typically has a ignition cannot occur. heat release rate and prevention of
heat release rate of under 1 Megawatt structural damage
(MW). As a rule of thumb, one square The three different fire-fighting terms
metre of visible flame corresponds to used to describe the objective of a fire • Suppress
1 MW of fire. A fire is becoming serious fighting system. These terms describe Sharp reduction in rate of heat
when it reaches 5 MW. different results and should be used release and prevention of re-growth
carefully and precisely when describing
• Extinguish
At least one of the four prerequisites for the performance of fixed fire fighting
Complete suppression until there
sustained burning must be eliminated systems.
are no burning combustibles
to extinguish a fire. It is rarely possible
to remove the combustible fuel, but the Manual intervention is always required
Source: NFPA 750 standard on water mist
remaining prerequisites can be affected to completely extinguish a fire when
fire protection systems, 2010 edition
by different fire fighting agents. suppression and/or control systems are
in used.
Fires can be fought manually or with
the aid of fixed fire fighting systems. A
Water mist as a fire fighting agent ter into tiny droplets, resulting in high A fine mist of potable water is dis-
Water is the oldest, most widely used and evaporation which leads to more effi- charged through specially designed
the most widely available fire fighting cient cooling and inerting. HI-FOG® sprinkler and spray heads. The
agent in the world. It has superior fire water mist is discharged at high velocity
fighting capabilities over a wider range Therefore, a lot less water is needed by high-pressure pumps, quickly pen-
of applications compared to other avail- by a HI-FOG® system to achieve the etrating a fire while cooling the space. It
able fire fighting agents while remaining same performance as traditional water blocks the radiant heat, preventing the
non-toxic and environmentally friendly. sprinkler systems. HI-FOG® also has fire from spreading.
Water fights fire with three mechanisms: the added benefit of protecting the sur-
roundings from radiant heat. Depending on the application, HI-FOG®
• Cooling: when water turns into
is designed to extinguish fire (typically
vapour, it absorbs more heat than any
Small droplets as such do not guaran- flammable liquid fires) or suppress and
other fire fighting agent
tee effective fire fighting. They need to control fire (solid fuel fires). HI-FOG® is
• Inerting: when water evaporates, its penetrate the outward flows of flame a high-pressure water mist system that
volume expands over 1,700 times, produced by the fire. The effectiveness is powered by constant-pressure electric
displacing oxygen locally of a water mist system is determined by or diesel pumps, or by pressurized gas.
• Blocking: when in the form of water HI-FOG® water mist’s range of pen-
mist, the radiant heat is blocked • Droplet size
etration may be up to 8 m (26.3 ft)
• Number of droplets horizontally under normal conditions;
The evaporation rate of water depends even greater distances may be reached
on surface area: water in a bucket evap- • Droplet penetration into the fire vertically. The good range of penetration
orates much more slowly than water means HI-FOG® water mist can spread
spread out on a floor. The surface area The combination of these properties is quickly throughout a space, to some ex-
can be greatly increased by turning wa- entirely system-specific. tent even past obstacles.
CLUBs US lH
PUMP UNIT
Water mist systems are designed on a Wherever possible, HI-FOG® systems are designs must be approved by local fire
performance basis. A water mist system designed in accordance with Marioff’s officials or authorities.
should never be designed using one sup- comprehensive range of approvals. In
plier’s system and another supplier’s test other cases they are designed on a pro- HI-FOG® system for a building is com-
results. The complete system offering ject-by-project basis according to results pliant with the NFPA 750 Standard on
should be fully fire-tested for the given from fire tests supervised and witnessed Water Mist Fire Protection Systems
application. by third parties. In most cases, system when the standard is applicable.
System types
HI-FOG® offers great flexibility: different tubes, valves and nozzles can be selected depending on the application and fire risk. A
HI-FOG® system can be a single configuration or a mixture of several configurations. In an office building, for example, the main
configuration could be a wet pipe system with a pre-action system configuration protecting the computer server room and a
deluge type system protecting back-up generators. All configurations would be fed by the same pump unit.
Wet pipe system Deluge systems are typically used for Pre-action system
A wet pipe system normally has closed, protecting machinery spaces because A pre-action system is very similar to dry
heat-activated sprinkler heads. The ac- they provide full, homogeneous protec- pipe except that it is connected to a fire
tivation bulb bursts when the ambient tion throughout the space. detection system. Typically, a pre-action
temperature at the sprinkler head ex- system valve requires both a sprinkler
ceeds the prescribed rating. Water mist Dry pipe system bulb to break and an activation signal
is discharge from that particular sprin- A dry pipe system operates in much the from an independent fire detection sys-
kler head. same way as a wet pipe system, but the tem before it opens.
valve keeps the water on the pump side
Wet pipe systems are the most common of the tubing in normal operation. The This type of system usually protects are-
type of system because they are the most tubes from the valve to the sprinklers as where the risk of accidental discharge
economical for medium-size and large are filled with compressed air, which is needs to be minimized. Pre-action sys-
areas that need to be protected against monitored. tems are ideal for buildings such as large
normal fire hazards. They also have the data centres and museums.
benefit of only discharging at the point The monitoring switch detects the loss
of detection. of air pressure when a sprinkler bulb Hydrant
beaks and opens the section valve. Water A manually operated hydrant can be
Deluge system fills the tubes to the sprinklers and water connected to HI-FOG® systems using
A deluge system normally has open mist is discharged from the activated single fluid pump units.
spray heads. The water flow is usually sprinklers.
controlled by a closed-type valve. When
a section valve is opened –manually or This type of system is typically used
by a detection system – water mist is dis- when the protected area is subject to
charged from all the spray heads in the freezing.
area controlled by that valve.
A typical HI-FOG® system The placement of HI-FOG® sprinkler and spray heads in a
comprises the following:
building is decided according to the system design guidelines,
• Water supply
application-specific fire tests, local fire regulations and the
• High-pressure pumps or building’s technical requirements. A control system, hydrants,
accumulators
panels, release devices, compressors and other equipment can
• Tubing network
be added as required.
• Section and/or machinery valves
SPU2 1716 / 70
1475 / 60
SPU3
2200 / 90
SPU4 2500 / 100
SPU5 2200 / 90
2241 / 90
SPU6
Tubing network
SPU. It can be carried through tight All of the tubes in the high-pressure
spaces in parts and then assembled in parts of a HI-FOG® system are made of
the final installation space. stainless steel. High-pressure fittings are
also supplied by Marioff for completing
The DPU unit can also be used for al- the tubing network and mounting the
most any application and comes in sev- sprinkler or spray heads.
eral different sizes and configurations.
The DPU400 will often be used instead HI-FOG® tubes are very small compared
of an SPU when power is insufficient. to traditional sprinkler system pipes.
They are bent into shape onsite, enabling
discrete installation in tight spaces – a
particular benefit at heritage sites. Con-
nections for the high-pressure tubing are
made using cutting rings for tube sizes
up to 38 mm (1.5 in) in diameter; flare
fittings are used for tubes larger than 38
Pipe diameter (mm / in) Bending radius (mm / in) Usage mm (1.5 in) in diameter. All tubes and
fittings are rated for high pressure and
12 / 0.5 30 / 1.2 Branch burst-tested to at least four times the
maximum operating pressure. During
25 / 1.0 63 / 2.5 Main distribution commissioning, the high-pressure tub-
30 / 1.2 75 / 3.0 Main riser ing is submitted to a pressure test fol-
lowing NFPA 750 guidelines to ensure
38 / 1.5 95 / 3.7 Main riser correct and leak-free installation.
60 / 2.4 150 / 5.9 Mega system riser
The HI-FOG® tubing network is some-
what different from traditional sprinkler
The HI-FOG® tube sizes are selected according to hydraulic calculations based on the piping. HI-FOG® systems are usually de-
Darcy-Weisbach calculation method as required by the NFPA 750 Standard on Water signed around a main supply tube from
Mist Fire Protection Systems. which smaller tubes branch off with their
own section valve. The nozzles are fed
At the end of each main tubing zone a closed, manually- operated ball valve is normally by 12 mm (0.5 in) tubes coming off the
installed for flushing the system as needed – especially if the system is a wet-pipe branch tube. Typically about two-thirds
system. of the tubing network is composed of 12
mm (0.5 in) tubing.
25 mm
30 mm
38 mm
60 mm