BLT MPK708C
BLT MPK708C
1-Preface
The manual is only provided to the debugging and maintenance personnel of BLT Elevator
Company after the qualified training. In order to keep safety for your own and others, please don’t
carry out any processing step without qualification and authorization.
Shenyang BLT Elevator Co., Ltd. reserves the right for all pictures and information within the
manual, being forbidden to directly and indirectly publish as well as hurt the BLT’s benefits. The
manual is prohibited copying for any reason. In case of debugging personnel’s leaving the company,
the profiles should be returned to BLT in time.
The debugging personnel should carefully read the manual in advance and strictly implement
the operation according to the procedures in the manual as well. During the debugging process, the
debugging personnel should wear insulated shoes and work cloths special for electrician. At least
one suit of debugging tools should be kept at each site.
This manual adopts MPK708C control system for the electric debugging of passenger elevator,
and it is suitable for the elevator system of mating test work when the control cabinet, traction machine
and encoder are delivered. This manual needs assorting the following Electric Installation Manual.
It makes all the difference for elevator safety, so that each debugging personnel should be
rather careful, never letting any doubtful point pass or carrying through the dangerous operation.
Please notify any problems on the manual to the BLT Electrical Department.
MPK708C Commissioning Manual Code:YETS-0002-C
2-Attentions
1. Check the well correspondingly and ensure the installation of elevator components and no barrier
within the well before the commissioning.
2. No water in the pit and no-leakage on well enclosure before the commissioning.
3. Before the commissioning, check the temperature and humidity of machine room to meet the demand,
ensure no ponding and no leakage on the ground.
4. Before the commissioning, check if the overall arrangement of machine room is reasonable and if the
lighting switch is available when passengers enter the gate.
5. Check each apparatus in the control cabinet as well as the wires connection before the commissioning.
6. Check each connector assembly and cable connection carefully without any looseness before the
commissioning.
7. Lay a remarkable sign at the entrance of each hall before the commissioning, in case the outsiders go
into the elevator mistakely.
8. Non-adjustor is forbidden to enter the machine room. The key should be kept by specially-assigned
person after the normal operation.
9. If electricity power is required to be switched off during the process of commissioning, an obvious
sign for No-Switch-In shall be hung or stuck at the switch in order to avoid an accident.
10. All instructions assigned by the primary adjustor during the process shall be repeated and carried out
after rechecking in order to avoid mistakes.
11. For long time working in the well during the process of commissioning, the hole in the floor of
machine room should be covered, avoiding accident caused by drops.
12. Safety helmet should be worn before entering the well during the process of commissioning.
13. Any person is forbidden to enter the pit or climb up to car top privately during the process of
commissioning.
14. Car top adjustor is forbidden to lean upon the guard or one foot on car top and the other on any
fixture in the well.
15. Car top adjustor is forbidden to expand any part of body out of the car, avoiding the crush injury.
16. Car top adjustor should pay attention to the relative distance between the counterweight and car top
at any moment.
17. Pit adjustor should pay attention to the dropping location of counterweight at any moment.
18. Pit adjustor is absolutely forbidden to remain just below the counterweight.
19. It is absolutely forbidden to operate the switch of trap door, safety gear and inner lock after shorting
of mechanical and electrical system during the process of commissioning.
MPK708C Commissioning Manual Code:YETS-0002-C
20. In case of pit in excess of 1.5m, it needs to climb up and down by ladder or staircase, forbidding
people to climb by catching traveling cable, car platform or the other part.
21. Check the quality of the cable and make sure the insulation protective film is in good condition
while using portable lamp during the process of commissioning.
22. It is forbidden to alter the circuit without permission during the process of commissioning. It should
be reported for approval and kept in the archives if necessary.
23. When the commissioning is not completed and the worker needs withdrawing temporarily, all the
landing doors should be closed, the doors that can’t be closed should be blocked and equipped with
the remarkable sign showing danger.
24. When the commissioning is not finished and the working personnel needs withdrawing temporarily,
the main switch should be switched off, the machine room should be locked.
25. Cut off all heat sources including blowtorch, strong light and soldering copper as the adjustor
momentarily leaves the site.
26. During the process of commissioning, tools and scrap wires shall not be left all around, and taken
away after the collection.
27. In case of accident or emergency stop, firstly release the trapped person and then carry out the
maintenance service.
28. After finishing the commissioning, reset all switches to normal status and remove all the billboards.
29. After finishing the commissioning, clean up the working site carefully, scrap wires are forbidden to
be left around control cabinet, service kit and all switches.
30. After finishing the commissioning, reconfirm the elevator’s normal operation, the quantity of
shorting connector assembly on elevator protective isolation device and its location.
31. According to the requirements, the adjustment shall not be cut for saving time.
32. After the normal operation, record should be filled in carefully, so as to do the hand-over works with
drivers or the related personnel.
MPK708C Commissioning Manual Code:YETS-0002-C
WARNING
Before check, confirm the main power of elevator and the lighting has been off state.
Cut off the corresponding air switch in control cabinet of elevator.
WARNING
During the following process of check, any problem happened
should be checked and solved carefully, confirming no influence
on equipment and people!
Push the key Enter, it will enter the main interface of main controller:
The followings are the corresponding explanation of the lower left/right corner :
Automatic(AUTO)
Test(TEST)
Fire control(FIRE)
Seism(SEISM)
Driver (MANUAL)
Fullload(FULLY)
Overload(OVER)
Lightload(LIGHT)
Self-learning(LEARNING)
Services JAB(LOCK)
The followings are the corresponding explanation of the lower right corner:
(2).Menu
In the main interface, push the Enter key, it will enter the selection of mode of main menu, for
example:
MPK708C Commissioning Manual Code:YETS-0002-C
In the menu: the first digit figure indicates the main menu, the second digit figure indicates the
corresponding submenu below the main menu.
At this time, push “↑” and“↓”key to choose main menu item, Esc key will exit from the selection
of main menu and return to main interface, Enter key will enter the selection of submenu item.
(3) The setting of power-on
Main controller has 10 main menus totally, push“↑”,“↓”key to alter options of main menu. After the
option is confirmed, push Enter key to enter the submenu of this menu. The operation after entering
submenu is the same as that at main menu. In the editing pattern, push“↑”,“↓”key to alter parameter
value. After the parameter value is confirmed, push Enter key to reserve parameter value. Esc key
are quitted modification. The defaults have been set up initially for all the parameters in controller
before ex-works. But some parameters must be set anew according to the position on site.
Main menu:
Configuration (10) CONFIG
Time setting (20) TIME
Setting of station (30) STATION
Call menu (40) CALL
Input and output (50) IO
Door (60) DOOR
Error history (70) ERROR HISTORY
Password (80) PASSWORD
Pulse monitor (90) PULSE MONITOR
Input select (A0) INPUT SELECT
The followings are the main controller parameters setting instruction of MPK708C system. (This is
the setting for Y standard single elevator; others are subject to the project)
MPK708C Commissioning Manual Code:YETS-0002-C
4.6.3.1 CONGFIG(10)
No. Sub menu Content Leave-factory setting value
Address of elevator in group control
or parallel, For elevator with different
ADDRESS:
11 floor at the bottom, the address
number of basement landing should
be odd number.
OFF-LINE normal working mode Y
CONNECT
12 ON-LINE automatic calling working
mode
<1.5 one-stage speed Setting before shaft
SPEED >1.6 two-stage speed learning according to
13
landing height and
>2.0 three-stage speed
speed
0~64,A~Z,-1~-9, 1A
,2A,1B,2B,1S,2S,A1,
A2,A3,B1,B2,B3, E1,E2
,F1,G1,G2,UB,DB, PB,
FLOOR DISPLAY
14 LG,L1,L2,M1,M2, P1,P2
,P3,S1,S2,S3,SS,RC,
5A,8A,3A,RG,PH,JP, NJ
,GH,MP,GF,π,TZ,NF,
SB,3B,P4,P5,B4, B5,UG
DATE Set up the current system
15
date
TIME Set up the current system
16
time
OFF: turn OFF automatically after
LEARNING Y
17 learning
ON: permit the learning operation
ON: press the door close button for a
MANUAL DOOR Y
18 long time
OFF: inch the door close button
MANUAL ON: hall call can’t stop the elevator Y
19 DIRECTION
OFF: hall call can stop the elevator
CONVERTER SIEI Y
1A SELECT
MICOCONTROL Equip with micro converter
0 no diferfloor Y
DIFERFLOOR
1B 1 with one diferfloor
2 with two diferfloors
SOFTWARE
1C VERSION Non-setting item.
PULSES PR
1D Default value 128
MPK708C Commissioning Manual Code:YETS-0002-C
4.6.3.2 TIME(20)
No. Sub menu Content Leave-factory setting value
STOP Default value 3s
21
START Default value 0.5s Stand-by
22
BRAKE Default value 0.5s Stand-by
23
DOOR OPEN Default value 2.0s.Set the time at
24
pre-opening
DOOR CLOSE Default value 5s
25
OPEN PROTECT Default value 8s
26
CLOSE PROTECT Default value 8s
27
RINGING Default value 10/T
28
GONG Default value 1s
29
SPEED STOP Default value 0.9s
2A
FLOOR PROTECT Default value 13s
2B
TIME1 Default value 10s
2C
TIME2 60s
2D
TIME3 Default value 0s Unused
2E
RUN TIMES Read only. Non-setting item
2F
4.6.3.4 CALL(40)
No. Sub menu Content Leave-factory setting value
UP CALL
41
DOWN CALL
42
CAR CALL
43
Instruction: FIRE MODE parameters setting: Adopting binary digit to set different fire modes. The
following is the specific instruction. It should be converted to decimal numbers while setting
parameters. Default value 00.
Leave-factory
No. Sub menu Content
setting value
A6 SAFEEDGE Of no use
00: Chinese mode: Elevator does not
run after returning to base station Y
while using standby power supply.
16: Chinese mode: Elevator continues
to run after returning to base station
CONTROL MODE while using standby power supply.
A7 01: Russia mode: Elevator does not
run after returning to base station
while using standby power supply.
09: Russia mode: Elevator continues
to run after returning to base station
while using standby power supply.
MPK708C Commissioning Manual Code:YETS-0002-C
Instruction: CONNTROL MODE parameters setting: Adopting binary digit to set different control
modes. The following is the specific instruction. It should be converted to decimal
numbers while setting parameters. Default value 03.
00: Chinese mode: No sub door locks detecting function. Elevator does not run after returning to base
station while using standby power supply.
16: Chinese mode: No sub door locks detecting function. Elevator continues to run after returning to
base station while using standby power supply.
03: Chinese mode: Sub door locks detecting function. Elevator does not run after returning to base
station while using standby power supply.
19: Chinese mode: Sub door locks detecting function. Elevator continues to run after returning to base
station while using standby power supply.
01: Russia mode: Elevator does not run after returning to base station while using standby power supply.
17: Russia mode: Elevator continues to run after returning to base station while using standby power
supply.
Instruction: RUN MODE parameters setting: Adopting binary digit to set different functions. The
following is the specific instruction. It should be converted to decimal numbers while setting
parameters. Default value 04.
Content above is the option for main controller menu. Set several menus after power on (referred in the
front), continue to describe corresponding menu setting in the following chapter.
4.7 Confirmation of safety circuit:
After main controller is powered on, confirmation of commissioning of safety circuit is conducted.
When car top inspection is on the ‘inspection’, the safety circuit commissioning is conducted, confirm
the following conditions:
a. The phase sequence of three phase input power source is correct. The indicator light of phase sequence
relay will shine.
b. Machine room 5SB5, pit 5SB6, car top 5SB3 emergency stop don’t act.
c. The other safety circuits don’t act.
When the above conditions are met, safety circuit will be available. At the same time, in the main
MPK708C Commissioning Manual Code:YETS-0002-C
controller menu option (50) IO, open to enter (51) I dot-monitor page layout. When 3.3 is highly bright,
safety circuit is available.
If normal display is not correct or there is error display, the following commissioning can only be
conducted until the error is treated in time.
4.8 Confirm the normal working state of inverter after power-up:
(1) Keyboard sign
Inverter keyboard is composed of LCD monitor, 7 indicator lights and function keys.
The state of inverter’s driving signal can be judged by indicator light, its content are as follows:
Name Color Function
-Torque Yellow The inverter output torque is minus.
+Torque Yellow The inverter output torque is positive.
ALARM Red Inverter fault
ENABLE Green Inverter enable
Zero speed Yellow The rotation speed of motor is zero.
Limit Yellow The inverter is under the current limiting
Activate the function of option 2 of the key
Shift Yellow
press.
Note: For the concrete operation instruction of inverter, see the 《SIEI inverter operation instruction》
(2).The power up display is normal.
R: 0 S: 0
MONITOR
Or after push key SHIFT, push key HOME, the above page layout will arise. The above page layout
is the inverter’s page layout of monitoring.
4.9 Initial setting of parameters of inverter:
A. Monitor
Function: Monitor the operation parameter of inverter
The list of the main contents monitored:
Monitor:
I/O status:
Name Content Unit /note
E: enable
DI 1, 2: direction
Input state
7654321E 4, 5, 6: speed
In accordance with drawing.
0: running contactor
1: braking contactor
DO 3210 Output state
2: Inverter failure
In accordance with drawing.
C. Travel(running menu)
Speed profile—Smooth start speed: 1mm/s
—Multi speed 0—7: Set corresponding speed value according to drawings and
commissioning on site.
—Max linear speed: This parameter is read-only parameter, showing the maximum
linear speed(mm/s).
Ramp profile—MR0: This parameter is set for operating slope. This manual use the defaulted
parameter group MRO. See the following chapters for the concrete commissioning method.
Lift sequence: Working sequence. (Setting of standard parameters)
Speed reg gains: Regulation of speed gain.
Speed threshold: Set the range of speed gain.
Ramp function: The effect of slew rate (Setting of standard parameters)
Save parameters: Parameter storing.
D. Leave-factory parameters setting of SIEI inverter
Input
Content Description
point
0.0 Inspection /normal Close is in normal running condition
0.1 Slow/up Close is effective
0.2 Slow/down Close is effective
0.3 Running inspection OFF when running, ON when stops.
0.4 Inverter malfunction ON indicates that the inverter is running normally.
0.5 Brake test ON when running
0.6 Brake arm test ON when switch off
0.7 Earthquake ON when earthquake happens
1.0 Power failure ON indicates the running of power failure emergency
emergency test
1.1 Back-up power ON indicates the running of back-up power
1.2 Fire detection ON when fire happens
1.3 Motor overheated ON indicates that it is running normally.
detection
1.4 Back-up
1.5 Lock elevator ON when it is locked
1.6 Door zone It is closed at door zone.
1.7 Firefighter It is closed during fire control.
2.0 Limit/ up Signal cut-off during upper limit
2.1 Limit/ down Signal cut-off during lower limit
2.2 V3/up Signal cut-off when speed V3 is at the up speed
MPK708C Commissioning Manual Code:YETS-0002-C
changing point
2.3 V3/down Signal cut-off when speed V3 is at the down speed
changing point
2.4 V2/up Signal cut-off when speed V2 is at the up speed
changing point
2.5 V2/down Signal cut-off when speed V2 is at the down speed
changing point
2.6 V1/up Signal cut-off when speed V1 is at the up speed
changing point
2.7 V1/down Signal cut-off when speed V1 is at the down speed
changing point
3.0 Speed test It is ON when the elevator running speed <0.3m/s
3.1 Landing door 110VAC inspects landing door lock
3.2 Car door 110VAC inspects car door lock.
3.3 Safety circuit 110VAC inspect safety circuit.
Note: The input point is effective in low potential (Observe from the display screen: high brightness)
5.3 The adjustment of emergency electro motion
(1) Commissioning procedure:
a. Close main supply, reset the switch of control cabinet emergency stop, ensure the inverter in the control
cabinet is electrified, and the display is operating. The main controller is in the status of TEST.
b. Car top inspect operation is in normal condition.
c .Ensure the input conditions of above list is available, main controller I/O menu can be monitored.
d. The inspection speed Vn of inverter is set to 300mm/s when delivery from factory.
e. Calculate the rotational speed of motor when the equipment runs at the inspection speed by the
rated speed and rotational speed, and make ALARM CONFIG/Over speed/OS threshold 1.1 times of
that value.
f. Push upward, downward button in controller cabinet, the door should close automatically.
(2) If input conditions are not available, conduct commissioning corresponding to collateral drawings and
find out the malfunction point. If there is concerned malfunction alarm, consult inverter malfunction
or main controller malfunction, and solve the problems in time.
(3) Notice for TEST running:
A. When elevator external safety circuit: speed limit switch 5SQ1, upper terminal landing switch 5SQ2,
lower terminal landing switch 5SQ4, car buffer switch 5SQ6, counterweight buffer switch 5SQ7,
safety gear switch 5SQ8 is running, the TEST running can be used.
MPK708C Commissioning Manual Code:YETS-0002-C
B. Before operating, make sure that the car door is closed completely and nobody is in the shaft.
C. TEST running can only be carried out by the professional adjustment and maintenance people
qualified by BLT ELEVATOR COMPANY. Others are forbidden to carry out these functions
privately.
(4) The treatment of malfunction in TEST running:
During TEST running, the commissioning engineer can monitor the current pulse count menu
CURRENT in PULSE MONITOR menu. If the impulse value doesn’t change, check the frequency
dividing output of inverter; if E9 Tach Direction Error appears, exchanges phase A (A+\A-), phase B
(B+/B-) of the pulse of main controller.
5.4 Commissioning procedures for car top inspection
After normal running TEST in machine room, inspection works on car top can be carried out on the
premise of confirming safety. Before car top inspection is carried out, the working line of car top
inspection should be confirmed right. All buttons act normally including car top emergency-stop safety
switch.
During the operation process of car top inspection, main controller displays TEST.
When car top inspection is operating, the machine room emergency electro motion is invalid.
If up and down buttons on car top inspection is different from elevator running direction, the working
line of car top inspection direction shall be checked. The change of direction instruction toward inverter
and other changes in control cabinet are not allowed.
If the door of elevator is open, it shall be closed automatically after pressing up and down button on car
top.
Notice for car top inspection:
Press ‘control’ and ‘direction’ button simultaneously when inspection running is operating. Release
‘direction’ button first to stop, and release ‘control’ button 2 seconds later. Thus, the elevator will stops
slowly, or else the safety circuit will be cut off after the ‘control’ button is released, and the elevator will
stop immediately, which result in ‘electric arc’ when contactor is off, and it will damage the contactor if
it is serious.
Professional on the car top shall be careful from time to time!
Door motor
Door controller
Bistable switch
6.3.1 Four bistable switches are taken to detect the moving position of door on door operator and they are:
“Open limit” “Open speed change” “Close limit” “Close speed change”. These four signals are connected
to elevator door controller directly. The functions of the 4 switches are described as follows:
MPK708C Commissioning Manual Code:YETS-0002-C
Socket
aperture Wire NO. Connecting position Function description
NO.
Door machine
P24 COM A B X1
terminal No.
Encoder line color red black green brown white
Door machine: Xiangshan sanhuan TYC135-1synchronous permanent magnet motor, rated current of
1.35 A, rated voltage 50 v, rated speed 180 r/min, the rated torque 2.7 Nm, rated frequency24 HZ, rated
power 50 W
Incremental encoder: MEC24IN1024PU2, input voltage 8-30V,1024 pulse encoder, output A B Z Z-
VDD GND
6.4.4 Door machine controller
Door machine controller input power is single-phase AC220V, which is output to the motor for three
phase voltage (according to the motor voltage), door machine parameter is set and displayed by keyboard
and segment codes.
MPK708C Commissioning Manual Code:YETS-0002-C
PRG:Programming key is used for switching among stop state or operating state and programming
state
FUNC/DATA:Function / data key is used for choosing data monitoring mode and data writing
confirmation
MPK708C Commissioning Manual Code:YETS-0002-C
Double right arrow:Shift key In the state of running and stop, choose the key to show the parameter;
when setting the data, choose the key to set the modification position of the data.
OD:Under the panel control, it is used for opening the door (forward)
CD: Under the panel, it is used for closing the door (reversal)
STOP/RESET:Stop/ fault reset key Under the panel operation mode, it is used for stopping or
Socket hole No. BLT wire No. Door machine terminal No. Function description
1 114 L Power supply
2 115 N Power supply
3 601 PC1 Open limit output signal
4 602 PC2 Close limit output signal
5 614 OD Door opening input signal
6 615 CD Door closing input signal
7 0V PA1 and PA2 Door controller output
signal common terminal
8 616 COM Door controller input
signal common terminal
9 617 X2 Door nudging input signal
PE PE Ground
Fault alarm state- due to fault from outside equipment or control interior or misoperation, the
controller alarms corresponding fault code and blocks the output
6.4.7.2 Operational mode description of the controller
The controller has four operational modes: speed control, distance control 1, distance control 2,
distance control 3. BLT uses distance control 1.
6.4.7.3 Function parameters classification
The series of controller has 141 function parameters, which can be divided into ten groups
according to the sequence number and function
1) Set the general inverter panel operation mode and set the functional parameters F0.02 to 0;
2) Set the control method as distance control 1(Closed loop vector control at the time); set
functional parameter F0.01 to 1;
3) Set motor type and set the functional parameter F6.00 to 1 (synchronous motor)
4) Input motor nameplate parameter, and correctly input corresponding motor nameplate
values have been set when leaving factory which shall be checked before tuning.
5) Set the pulse count of the encoder per revolution and functional parameter F4.01.
6) Set encoder type and set functional parameter F4.00 to 0 (24V encoder)or 1 (5V
encoder);
7) Set the enable signal of tuning parameters and set functional parameter F6.07 to1.
8) Press door opening key on the panel to start motor parameter tuning. Operation panel LED
displays “TUNE”. During tuning the motor shall run according to fixed mode unnecessary
for attention.
9) After finishing the tuning the controller automatically stop and F6.07 automatically revert to
10) If the panel displays faults when tuning, press stop/fault reset key for resetting. After
resetting there are the following two conditions:
a、 If fault code is E025 (encoder faults), change the setting value of F4.02 after resetting; if
it still displays E025 after tuning, check encoder connection.
b、 If there are other faults, check connection and related motor parameters after resetting to
ensure it is accurate.
11) The synchronous motor needs to be tuned at least twice. Compare whether the tuned
magnetic pole initial angle (F4.03) difference is less than 10°, if the difference is more than
10°, the error is too big, need to be tuned again; If the angle difference is (360°/ motor
pole-pairs number) integer multiple, tuning results are qualified.
12) After finishing the above work, set the parameter F0.02 to 2 (door motor terminal control
mode), at this time the terminal controls the opening and closing of door machine, namely
elevator controller controls the running of door machine.
Firstly ensure F4 group parameters setting is correct, and set F0.02 to 1, F4.05 to 1. Confirm
that the door can be normally opened and closed and press the door opening key on the panel to do
self-learning of door width. At the same time the door machine runs at self-learning speed
according to the operation procedure of close-open-close, and door machine saves door width
MPK708C Commissioning Manual Code:YETS-0002-C
information after completing the self-learning. After finishing the above work set F0.02 to 2. The
tuning and learning work is finished.
14)Parameters adjustment
Door machine parameters table is shown as follows for reference. According to the difference
of door width and weight on site set the parameters such as speed and moment and so on to satisfy
the needs of the users and national standard.
6.4.7.7 Parameters table (for reference)
In accordance with the motor and encoder in 6.3, door machine parameters table is shown as
follows for reference. According to the difference of door width and weight on site set the
parameters such as speed and torque and so on to satisfy the needs of the users and national
standard. ( * stands for read-only parameter)
Functional parameter Name Setting range Minimum unit Default BLT setting
F2.06 distance.
F2.08 speed
Bit2:Output voltage(V)
Bit3:Output current(A)
Bit4:Output torque(%)
9999)
9999)
Bit2:output voltage(V)
Bit3:output current(A)
Bit4:output torque(%)
9999)
9999)
MPK708C Commissioning Manual Code:YETS-0002-C
16:EEPROM
24:Tuning error(E024)
25:Encoder error(E025)
E001 Accelerated 1)Acceleration time is too short 1)Lengthen the acceleration time
running
overcurrent 2)When instantaneous stop happens, 2)Restart after stopping of the
restart the rotating motor. motor
3)Outer connection is wrong 3)Correct connection
E006 Constant speed 1) Input voltage abnormally 1) Install input electric reactor
running changes. 2) Externally connect brake
overvoltage Potential load produces resistance
regeneration energy.
E009 Output phase Three phase output disconnection, Check three phase output wiring or
loss phase loss or load symmetry
three phase load is seriously
asymmetric.
E014 Motor 1) Related motor current setting is 1) Check the setting of F6.03.
protection wrong. 2) Check the setting of F6.04
2) The setting of maximum 3) Select adaptive motor.
permitted running current is
too small.
3) Motor model selection is
improper.
E024 Tuning error 1) Motor nameplate parameter 1) Correctly set the parameter
setting is wrong. according to the parameter
2) Tuning timeout of motor nameplate
2) Confirm if motor is separated
from load or check motor
wiring
E025 Encoder error 1) Encoder signal disconnection 1) Check encoder connection and
2) Encoder signal is reversely reconnect
connected 2) Modify the setting value of
3) Output wiring is wrong or F4.02 (encoder reverse
disconnected (synchronous direction) or change two
machine) phase connection of the
motor
3) Check if output connection is
correct.(synchronous
machine)
MPK708C Commissioning Manual Code:YETS-0002-C
E029 Door width 1) Door width information from door 1) Check impulse encoder
self-learning width self-learning is 0. connection and related parameter.
error 2) Door width information from door 2) Check door machine
width self-learning is over-limit. mechanical system
3) Door width self-learning is timeout
MPK708C Commissioning Manual Code:YETS-0002-C
E030 Door opening 1) Motor running direction is opposite 1) Replace motor wiring phase
overtime error to door opening given direction. sequence or set F0.03 to1
2) Door opening contact signal fault
2) Check opening contact signal
or wrong setting
3) Impulse encoder disconnection 3) Check encoder wiring
Parameter
Parameter Factory Parameter Factory Factory
No.
No. default No. default default
Setting is
F0.00 not F0.01 1 F0.02 2
permitted.
F0.03 0 F0.04 24
MPK708C Commissioning Manual Code:YETS-0002-C
Group F1
Group F5
7-Self-learning running
7.1 During self-learning running commissioning, first you have to confirm the settings of the
following parameters are right:
The selection of speed parameters are based on landing height and rated running speed of elevator:
SPEED:
When elevator rated speed V<1.5m/s, the microcomputer will output one speed signal V1 only.
When elevator rated speed V>1.6m/s, the microcomputer will output two speed signals V1, V2.
When elevator rated speed V>2.0m/s, the microcomputer will output three speed signals V1, V2, V3.
The corresponding running speed of inverter should be set according to the collateral drawings.
When operating elevator shaft self-learning, the running speed is set as inspection speed Vn (It is set as
300mm/s usually).
7.2 After the above parameters are confirmed right, the following signal connection also need to be
inspected.
(1) The installation position of speed changing switch and limit switch.
a) The position of installation is shown as the following table 1 and 2:
If the system is set as V1=800mm/s; V2=200mm/s; V3=1750mm/s, then the braking distance should be
set as SV1=1.16m; SV2=2.16m; SV3=3.65m.
Table 1: Elevator rated speed ≤2000mm/s (MRO curve parameter value is 600)
MPK708C Commissioning Manual Code:YETS-0002-C
1750 3650±30
2000 4600±30
Table 2: Elevator rated speed =2500mm/s (MRO curve parameter value is 800)
This installation distance is the distance for speed changing when the elevator runs at different speeds.
This distance value is recorded by main controller through shaft self-learning. During elevator
commissioning, the switch of speed change should be installed correctly according to standard
documents.
MPK708C Commissioning Manual Code:YETS-0002-C
7.4 Renewal self-learning: When any change occurs in the door zone inspection of shaft or the
position of speed change switch is changed, an effective self-learning must be performed.
MPK708C Commissioning Manual Code:YETS-0002-C
8-Debugging operation
8.1 On-site inspection and confirmation
(1) The inspection and confirmation of machine assembling
A. The elevator pit components are installed in good condition. If hydraulic buffer has been used, confirm
the buffer oil is enough as requested; the pit should be dry.
B. There is no barrier in the shaft which can influence the running of the elevator.
C. The landing door is installed in good condition.
D. Good sealing between landing door upright and door opening.
E. The installation of guide rail has been approved qualified.
F. The installation of steel rope is correct and tight.
G. The installation and fixing of all sorts of switches.
H. The tension sheave of speed governor steel rope has been installed correctly.
I. The installation of car is complete, consolidate and tighten.
J. The traveling cable has been installed and fixed in good condition.
K. The positioning of machine room components comply with the national standards.
L. The fixing of main machine complies with the requirements of factory installation, and the main
machine beam should be fixed and sealed (concealed work) good.
M. If it is equipped with gear traction machine, confirm the oil in reduction gearbox is enough.
N. Confirm the encoder on the main machine is fixed firmly.
O. The positioning of speed governor is satisfied the national standards.
P. The wire duct is laid in order, and they should be connected by copper sheet and yellow green wire.
Q. The installation and positioning of control cabinet is in order.
R. The machine room and shaft should be kept clean.
S. The leveling sensor flashboard in every floor of shaft should be installed correctly.
T. The car door operator is installed correctly.
(2) The inspection and confirmation of electric assembling
WARNING
Any problem occurs during the process of the following inspections
should be checked and solved carefully. Make sure that there is no influence on
equipments and people.
A. The wiring of door operator should be correct; the wiring of infrared curtain should be correct.
MPK708C Commissioning Manual Code:YETS-0002-C
B. The wiring of car top leveling sensor should be correct, and ensure the installation dimension is correct
and firm.
C. Every safety switch in the shaft could act effectively.
D. The installation position of upper and lower inspection switches in the shaft should be correct, and the
action of switch is effective.
E. The wiring of interphone is correct, and ensures the call is normal.
F. The wiring of arrival gong is correct. (Skip this step if there is no arrival gong)
G. The wiring of external calling box is reliable and correct.
H. The wiring of car lighting and fan is correct.
Note: The installation position of shaft speed change switch (the distance of speed change for various
elevator speeds) should comply with the stipulated distance strictly in 7.2.1. During the debugging, after
the confirmation of the installation position of hardware , the installation position of speed change switch
will not be changed after shaft self-learning, which is to keep the hardware speed change distance in
accordance with that of the software.
(2) The confirmation of inverter parameter
MPK708C Commissioning Manual Code:YETS-0002-C
a. Confirm the corresponding speed setting value of inverter, and the relevant running parameters again.
b. Over speed protection under normal running. Set the parameter of ALARM CONFIG/ Over speed/OS
threshold as 1.1 times of the rotational speed of motor when the elevator is running at its highest
speed under the normal condition.
8.3 Machine room test running
After the above parameter settings are confirmed, the calling debugging in the machine room could be
started.
The calling running should be performed under the CALL menu:
(1) Operate the elevator at the speed of V3, V2, and V1 respectively.
(2) During calling running, check the status of door switch, any problems that appears should be solved
immediately.
8.4 Normal operation debugging
After the above debugging is complete, you can ride in the elevator and adjust the comfort.
(1) The comfort adjustment
A. The adjustment of acceleration and deceleration (menu: Travel/ Ramp profile)
The running curve of BLT elevator has been adjusted when delivery from factory, and usually, it is no
need to adjust.
In general: The vibration occurs frequently during accelerating, and this is extremely important for
passenger’s comfort feeling. And this will result in parts dumping or vibrating in drive system, what’s
more, many mechanical parts will suffer from heavy weight. Not everyone has the same feeling towards
vibration; it is related to people’s age, physique, and mental state.
B. The start adjustment
Due to the lack of special advance torque facility, the phenomenon of sliding to the bearing side may
occur when the elevator is starting. Adjust the Sdp P/I value for starting could solve this problem.
C. Vertical vibration during running
Mechanical reasons may lead to vertical vibration, and you can solve the problem by adjusting the
parameters in inverter.
MPK708C Commissioning Manual Code:YETS-0002-C
High-frequency vertical vibration could be adjusted so that the elevator will keep stable during
high-speed running. If the wave drifting sense appears during high-speed running, adjust Spd P/I.
Note: The Spd P is increasing gradually, which can speed up the system dynamic response. But, if it is too
large, the traction machine may become unstable; the Spd I is increasing gradually, but, if it is too large,
the traction machine may become unstable.
(2) The adjustment of creep distance
Install the decelerating switch according to the requirements of “7 Shaft self-learning” in this manual so
that appropriate creep distance is obtained. If the switch position is not correct, please adjust it again.
8.5 The adjustment of leveling precision
(1) The measurement of floor horizon deviation
The car should be stopped at the leveling position while installing door zone plate, so that the elevator can
level precisely and accelerate the process of debugging. (Please see the previous instructions)
When adjusting leveling for MPK708C system, firstly, adjusts and stops the elevator in the midst of door
zone when it runs upward and downward to the landing by the previous debugging.
(2) Adjust the V0 value, and achieve the leveling position. (Usually, V0=115~119mm/s)
8.6 The setting of external calling board
1) There is an 8-bit DIP switch on the external calling board, and NO.8 is the terminal resistor. When this
external calling board is at the lower landing, the NO.8 is ON and the other landings are OFF.
2)Based on the binary coding 1248 in turn, the other 7 bits from low to high should be dialed according to
the absolute landings. For instance, NO.5 landing, DIP switch 1st bit, 3rd bit is ON.
3) For elevator with opposite door, if the two doors need to be opened and closed solely, the 7th bit stands
for the external calling signal of 2# door.
8.7 The settings of running time limit
The running time eliminator of the electromotor should act ≤ the lower value of the following two time
values:
① 45s;
②The overall travel time of elevator adds 10s. If the overall travel time is less than 10s, the minimum
value is 20s. After the electromotor running time is determined, set the running time limit protection in
TIME/TIME2 of MPK708C main controller menu.
MPK708C Commissioning Manual Code:YETS-0002-C
9-Function confirmation
9.1 Car lighting and fan
In case of no calling landing signal when the time exceeds the set value in (AK) CLOSE LAMP (The
default value is 3 minutes), the car lighting and fan will be automatically closed and restarted as
re-operating.
9.2 Attendant travel
In the car, set the driver’s switch on and the displayer on the main controller appears the state of
MANUAL mode.
As the elevator is operated by the driver, the corresponding indicator light in the car is on if there is an
external call signal; but as for limited calling, driver can select the corresponding floor in the car;
9.3 Special functions:
In the car, set the special switch on and make it come into operation. When using the special functions,
the elevator will keep the signal if there are hall calls, but will not response to the hall call signals, that are
limit on calling. Calls are available for authorized person in the car.”
9.4 Full load/bypass
In case of the addition of 100% load in the car, the functional switch for full load (with full load
indication) comes into operation. (“FULLY” is displayed on major controller).
No response to the hall calls in case of full load, but only for the car call.
9.5 Fire detection
This signal is from the fire sensor device in building. When fire signal is detected by control system, the
elevator shall return to the fire main landing immediately with doors open.
9.6 Fire running
The elevator shall prohibit responding to the hall call and return to the fire main landing promptly after
the fire control switch is actuated under the running condition. That is, the elevator will stop and level at
the nearest landing. If the elevator is not at the fire main landing, it will run immediately towards the fire
main landing floor without doors open after stopping and leveling. After arriving there, the door will open
and will not close automatically. At this time, fire service begins to work and the system outputs fire
linkage signal. The elevator should run only in accordance with the registered command signal in car
after fire service. The door can open automatically only at the fire main landing door, but it cannot close
automatically. At other landings, the elevator should not open and close the door automatically. That is,
when the “open” button is pressed, the door will open and when it is released, the door will close
automatically; or when the “close” button is pressed, the door will close and when it is released, the door
will open automatically.
9.7 Firefighting feedback
MPK708C Commissioning Manual Code:YETS-0002-C
When elevator receives the fire alarm signal or fireman service signal, it will return to the firefight floor.
Interface with fire-service center or BAS system.
9.8 Overload
When there is the addition of over 100% load in the car, the overload switch acts (with overload
indication, and the panel of main controller displays “Over” state.) The overload signal is detected when
elevator stops. The elevator will stop operating with doors open as it is overloaded.
9.9 Anti-nuisance function
According to the setting in (A3) DISTURB PRO\(A4) DISTURB NUM, inspect whether the signal can
be cancelled when a couple of buttons on operation panel are pressed at the same time.
9.10 Brake switch detection
The elevator will level at the nearest landing and alarm E10 for inspection and reset if brake arm cannot
open completely while running. If the brake arm position signal does not break while stopping, the
elevator cannot start due to the alarm to E21. And it will recover to run after signal comes back.
9.11 Contact not release detection
When the contact of main contactor or brake contactor cannot release, prevent the elevator from
continuous running at latest before next starting. The elevator cannot start due to E8 alarm and it will
continue to run after the malfunction is removed.
9.12 Earthquake function
When the seismic sensors are actuated, the elevator will stop promptly at the nearest available floor and
park there with doors open until the signal is cancelled.
9.13 Emergency power supply function
If detected that the current power is supplied by the standby battery after starting, the elevator will find
the leveling running direction according to half load signal and cannot start with doors open after
leveling.
9.14 Standby power supply running
If detected that the current power is supplied by the second power (this signal is on) after starting for a
single system elevator, the elevator will return to main landing after leveling with doors open. It can be
set whether the elevator could continue to run in software.
In the state of group control or duplex control, when the normal power is supplied by standby, the
elevator could run to main landing with doors open according to a pre-established sequence. It can be set
which one will continue to run in software.
9.15 Limitator of runtime
Reduce the time set in (2D) TIME2 and inspect whether the limitator of runtime is effective.
9.16 Other functions stipulated in contract should also be tested.
MPK708C Commissioning Manual Code:YETS-0002-C
7. When the operation board of inverter displays “End”, self learning ends up.
8. During exiting menu, operate Load setup at the path of menus/Startup and choose YES-ENTER.
9. Save the parameters of self -learning at the path of menus/Startup/Save Config.
B Synchronism motor magnetic field adjustment
1. Power off and make coil power of contactor 4KM1 and 4KM2 be in short circuit so that contactor
4KM1 and 4KM2 could pull in after power on.(For example, make 478 and 519, 479 and 118 be in
short circuit. Check actual product and collateral drawing seriously to avoid difference from this
example due to product wire number change)
2. Power on and contactor 4KM1 and 4KM2 on output side pull in.
3. Enter inverter Service menu and input password (28622)
4. Open the Service/Brushless menu, press Autophasing Still button.
5. Make inverter ENA, FWD, V0 signal and 24VDC be in short circuit, there is magnetic field
self-learning pace on operation panel. When the pace is 100%, self-learning of magnetic field has
finished.
6. Save the parameters of self -learning at the path of menus/Startup/SaveConfig.
7. Record value of SinCos/Res pos and SinCos/Res off at the menu Service/Brushless. Repeat the
learning function of magnetic field position for several times in order to confirm that the value of
magnetic degree is right. Each learning result should be similar or same.
8. After self-learning, power off and renew the connecting wire of inverter and contactor.
MPK708C Commissioning Manual Code:YETS-0002-C
2) Set parameters
Set parameters in menu CONFIG:
ADDRESS: one elevator is 1#, the other is 2#.
a)ADDRESS: The elevator which has basement is 1#, the other is 2#.
When they are under group control, the address No. of elevator which has basement is odd number
address, the address No. of elevator which does not have basement is even number address.
b)DIFERFLOOR: Default value(00)
Differ floor parallel; set number of the lower terminal differ floor landing for
both elevators at the same time. The setting value is 1 or 2. For the elevator without basement, its
missing floor should be set zero in REPLY STATION of STATION menu.
(3) Set DIP switch (for example)
Set the DIP switch of landing call display board, the DIP switch of differ floor display board is set as
the absolute landing of both elevators.
Such as:
1# stop is: 1, 2, 3, 4…10
2# stop is: -1, 1, 2, 3, 4…10
So:
1# DIP switch of landing call display board is: 2, 3, 4…11;
2# DIP switch of landing call display board is the standard setting: 1, 2, 3, 4, …11
DIFFERFLOOR: Set 1.
(1) Set parameters: Modify the parameters in the state of inspection. Turn off power after
When the elevators are in group control, the address No. of elevator with basement shall be set to odd
number address, the address No. of elevator without basement shall be set to even number address.
DIFERFLOOR: Default value(00)
Differ floor parallel or in group control; set number of the differ floor landing for both elevators at the
same time. The setting value is 1 or 2.
For the elevator without basement, its missing floor should be set zero in REPLY STATION of STATION
menu.
(2) Set DIP switch
Set the DIP switch of hall call display board, the DIP switch of display board is set according to
landing of all the elevators. The setting method is the same as the setting of differ floor parallel elevator.
(3) There are two CAN interfaces in group control unit: When the number of group control elevator does
not exceed 6(including 6), CAN1 interface should be used and it can be set in group controller menu that
only CAN1 interface should be used. When the number of group control elevator exceeds 6, the seventh
and eighth elevator should connect to CAN2 interface and it can be set in group controller menu that
CAN1 and CAN2 interfaces should be used at the same time.
MPK708C Commissioning Manual Code:YETS-0002-C
Drawing 1
Note: If there is only pre-opening function, this operation shall not be needed.
Installation requirement:
1. When elevator is leveling, the horizontal center of 4SQ4 is as high as the center of door zone
leveling plate;
2. 16SQ2 and 16SQ3 distribute equidistantly according to the center of 4SQ4;
3. Adjust the distance between door zone leveling top edge and bottom edge of 16SQ2 to be 5~10
㎜;
4. Adjust the distance between door zone leveling bottom edge and top edge of 16SQ3 to be 5~10
㎜;
5. The vertical center lines of 16SQ2, 4SQ4 and 16SQ3 coincide.
When elevator stops, 16SQ2 or 16SQ3 is blocked by magnet vane of door zone because of some reason,
the elevator will run at releveling speed in the opposite direction to the blocked switch until the blocked
switch is away from the block; And only when 4SQ4 door zone switch is blocked by magnet vane of door
zone, should the elevator stop running immediately. Keep leveling error of elevator rational by
fine-adjustment of releveling speed.
13.3 The setting of main controller:
2. Opening time:
=24= TIME
DOOR OPEN: It suits for pre-opening function;
0000.2 /S On the premise that there is no E2 door interlock fault,
this time is set as short as possible.
3. PM card monitoring:
=AA= INPUT SELECT
PMCARD:
ON
4. Pre-opening:
=A9= INPUT SELECT
PRE-OPEN:
ON
5. Releveling:
=A8= INPUT SELECT
RE-LEVELING:
ON
13.4 The setting of inverter( SIEI inverter): ( As usual the setting has been finished when products
leave the factory)
1. BLT6.net is downloaded to inverter. (The setting has been finished when BLT leaves the factory).
2. TRAVEL/Speed profile/Multi Speed 5 = 20~50 ㎜/s (releveling speed)
3. I/O config/Digital outputs/Std digital outs/Std dig out src/DO 3 src = Compare 1 output
4. Custom Functions/Compare/Compare1/Compare1 src/Cmp 1 inp 0 src = speed
5. Custom Functions/Compare/compare1/Compare1 cfg/Cmp 1 inp 1 src = ≤16384×0.3/ elevator
rated speed(m/s)
6. Custom Functions/Compare/Compare1/Compare1 cfg/Cmp 1 function = |I0|<|I1|
MPK708C Commissioning Manual Code:YETS-0002-C
Microswitch is installed at the car bottom; when passengers come into the car, the car sinks and
overload or full-load will make this switch act.
After adjusting the fast running by commissioning staff and confirming landing call signal and inner
selection signal are normal, install and adjust the weighing device.
on car roof, stop the elevator and press emergency stop buttons on car roof and in pit.
(6) Install the weighing device on the car frame plank assembly according to the following picture
by the installation personnel in pit.
(7) Connect one end of weighing device cable with inspection box on car roof by installation
personnel on car roof, the other end is passed along car wall to the installation personnel in pit.
Then the installation personnel in pit connect the cable with the overload switch and full load
switch.
B. The adjustment of weighing device
(1) The position of overload switch, full-load switch and half-load switch on weighing device
corresponding to the press plate at car bottom is installed by installation personnel in pit as following
picture:
go out of car, “OVER LOAD” will disappear and the buzzer will stop buzzing, namely, over-load
switch has been adjusted well.
(4) After adjusting over-load switch and full-load switch well, the installation personnel outside
landing move the weight out of car and close landing door.
(5) Renew the emergency stop switches on car roof and in pit.
(6) The installation personnel on car roof make the elevator run to leveling position of the second
floor at inspection speed, then stop the elevator and press emergency stop buttons on car roof.
(7) Open landing door on the first floor by installation personnel outside landing and the people in
pit get out. Close the landing door.
(8) The installation personnel on car roof renews the emergency stop button on car roof and leaves
car roof. Renew elevator’s running to be normal.
(9) Install half-load switch on the elevator which has power failure emergency function. Put 50%
(Actually, it’s the product of elevator rated load and equilibrium coefficient) rated load in car
when adjusting, the adjustment method is the same as above mentioned.
14.2 The adjustment of electronic weighing device
14.2.1 The terminal function of controller (See picture One)
Picture Two
Picture Three
14.2.3 Adjustment
MPK708C Commissioning Manual Code:YETS-0002-C
(1) The controller and main board of the elevator are connected (connected to the control box of car top
or CAN bus inside the operation panel).
(2) The connecting box of the sensor in Picture Four and the sensor port of the controller are connected.
Picture Five shows the outline dimensions for the connecting box of sensor:
(3) The sensor and its connecting box are connected with accessory special cable (One to six sensors can
be connected simultaneously).Special cable refers to Picture Six:
Picture Six
(4) Initial check of the controller
The controller gives a long sound with power supply. At first 888 is shown on the nixie tube of three
figures. Then the percentage of the elevator loading amount is shown. (If the controller gives three long
sounds with power supply, please check whether the sensor and connecting cable are connected with the
MPK708C Commissioning Manual Code:YETS-0002-C
controller. If so, please check the sensor and connecting cable).When the main board communicates with
the controller, the percentage of elevator loading amount will increase with the increase of the elevator
loading amount.
(5) The operation of zero clearing
A. Power on the controller, and preheat for 10 minutes;
B. Elevator with no-load stops at the lightest floor of deadweight where the sensor bears the lightest force
to learn zero clearing. Push zero clearing button for three times with the three light sounds
simultaneously. 30 seconds later, three long sounds respond. 000 is shown on the three figures. Zero
clearing (not including tare) is over.
C. Put 99% of rated load at the heaviest floor of deadweight to learn on full load after zero clearing (not
including tare) is over. Push the zero clearing button for more than 5 seconds with one light sound
simultaneously. Then a long sound respond, and three figures show 099-100;
D. The adjustment is over.
Special Note:
1) Elevator sends the information to weighing device for asking the load status while stopping. The data
is sent by weighing device in the form of the percentage and shown on the nixie tube of weighing
device. It’s also shown on the MPK708C main controller menu (96) pulse monitor/floor/floor
61.Adjustment personnel may compare and test this data with the data shown on the weighing
controller of car top.
2) The weighing data exceeding 80% is considered by the system as full load, exceeding 100% as
overload.
3) When the elevator of MPK708C system owns two functions of“electric weighing” and “device of
power-off emergency rescue” simultaneously, the acquiescent balance coefficient for MPK708C system
of elevator is 47%.On the device of power-off emergency rescue supplying power, elevator approaches
to the level upwards when the load inside car is less than 47%.Elevator approaches to the level
downwards when the load inside car is more than 47%.Thus the balance coefficient of elevator is
adjusted close to 47% during commissioning at site. It’s avoided that too much discrepancy of
weighing device cause rescue device not to work normally.
MPK708C Commissioning Manual Code:YETS-0002-C
Picture 15-1
The displayer is composed of 7 sections LED in two horizontal lines in the Picture 15-1.
Upper row display zone shows the status of the inverter, current menu and parameter codes which is
previewed. Lower row display zone shows parameter value or concrete default type.
Picture 15-2
If starting-up L2 access (Pr 0.49), ← and → keys can be moved during the menus. Refer to parameter
access level and safety in part 6.The menu and parameters roll and cycle, namely, if it has shown the last
parameter, push the “↓” key and will show the first parameter.
Information
Output stage of
Instruction
of upper row inverter
displayer
dEC Decelerating
Permission
The inverter makes electric motor decelerate.
inh prohibition
The inverter is prohibited to use and couldn’t run. Effective
Prohibition
signal of the inverter isn’t sent to the terminal 31 or Pr 6.15 is
set as 0.
POS Orientation
Permission
The inverter is orientating the axle of the electric motor.
rdY Ready
Prohibition
The inverter gets ready and could run.
run running
Permission
Inverter is running.
SCAn Searching.
OL> When the inverter looks for the same step with the electric
Permission
motor which is rotating, search for the frequency of the electric
motor.
MPK708C Commissioning Manual Code:YETS-0002-C
Information
Output stage of
Instruction
of upper row inverter
displayer
triP Error.
The inverter has error and no longer control electric machine. Prohibition
Displayer shows error type code.
Press “↓” key to make the edit mode of parameters get back to read mode of parameters when changing
parameters in menu 0. New parameter value can be saved automatically. New parameter value couldn’t be
saved automatically if the parameter in advanced menu has been changed. Save function could be started
up to save the change. The steps are as follows:
a. Input 1000 into the Pr.xx.00 and press key to quit.
b. Press red reset key to carry out save function.
Revert default parameter according to the following method. The default value is saved in the memorizer
of the inverter (The step doesn’t influence Pr 0.49 and Pr 0.34)
Step
·Input 1233 into the Prxx.00(Europe, Setting value is 50Hz) or 1244(America, Setting value is 60Hz).
·Press red reset key
15.1.7 Parameter access level and authority
15.1.7.1 Parameter access level determines that users only access menu 0 or all advanced menu except
menu 0 (menu 1 to 21).
Users access authority determines that users access method is RO or RW.
Users access authority and parameter access level should be operated independently as following:
Parameter Users access State of menu Advanced
access level authority 0 menu state
L1 Open RW No display
L1 Close RO No display
L2 Open RW RW
MPK708C Commissioning Manual Code:YETS-0002-C
L2 close RO RO
RW= read and write RO= read only
The default setting value of the inverter belongs to parameter access level L1, and users access authority
is open. Namely, access menu 0 as RO. Advanced menu doesn’t show.
15.1.7.2 Access level
Access level and advanced menu save authority is set in Pr 0.49 and it allows or prohibits to access
advanced menu parameter.
Choosing L1 access level-show parameters of menu 0 only
Choosing L2 access level-show all parameters
15.1.7.3 Changing access level
Access level is determined by Pr 0.49 setting value shown in the following list:
Even if it has set users access authority, access level could be changed through the keyboard.
Users access authority which has been set could prevent write access for all parameters of all menus. (not
including Pr.0.49 access authority).
Open users access authority-all parameters can be access to be read and written.
Close users access authority-all parameters only can be access to be read.
Setting of users access authority
Input any number from1 to 999 in PR 0.34 and press key.
The value is set up as access authority code. Access level is set as Loc in Pr0.49 in order to make access
authority become effective. When the inverter restores, access authority code has been effective and the
inverter gets back to access level L1.Pr 0.34 returns to zero in order to hide the code. Now users could
only change 0.49 parameter of access level.
Choose a read-write parameter to be edited and press key. Now CodE is shown on the upper
displayer. Set access authority code with arrow keys and press key.
MPK708C Commissioning Manual Code:YETS-0002-C
Inputting correct access authority password, the displayer shows parameters to be chosen in the edit
mode.
If the entered password of access authority is wrong, the displayer returns to view mode of parameter.
If users access authority needs to be locked again, Pr 0.49 is set as Loc and press reset key .
Previous access authority code is unlocked according to the above method.Pr0.34 is set as 0 and press
key. Now users access authority becomes invalid. No need to unlock for turning on each time, the
inverter could be access to read and write for parameters.
15.2 The parameter setting of CT inverter
Parameter (This
parameter is applicable
Parameter name BLT factory default
No. to all kinds of CT
inverters)
1 Pr00.34 Set access authority 0: read-write operation
2 Pr00.49 Access level L2: access to all menu
3 Pr11.31 Modify control mode CL vect-closed loop vector
At xx.00, input 1253 (Asychronous)
(Europe, value 50Hz) or Servo-closed loop servo
1254(America, value (Sychronous)
60Hz), and enter 11.31to
get a necessary mode and
then press the red reset key
directly.
4 Pr18.45 Get an opposite direction Default OFF
(change motor’s rotating
direction, On: opposite to
the original direction)
5 Pr18.48 Gain changing Default On
(On: switch between
MPK708C Commissioning Manual Code:YETS-0002-C
of CT inverters)
1 Pr19.27 Denominator of reduction ratio Traction machine’s name
plate (Set for asynchronous
traction machine)
2 Pr19.29 Diameter of traction sheave Traction machine’s name
(mm) plate
3 Pr19.30 Numerator of reduction ratio Traction machine’s name
plate (Set for asynchronous
traction machine)
4 Pr20.10 Roping Asynchronous 1;
Synchronous 2
7 Pr18.16 Vr(mm/s) 10
8 Pr18.29 Elevator rated rotating speed Motor rated speed
(rpm)
9 Pr18.30 Elevator rated speed (mm/s) Elevator rated speed
MPK708C Commissioning Manual Code:YETS-0002-C
15.3.1.1 Input the motor parameters according to the nameplate of motor. And notice that “power factor”
should be input while doing the static learning.
Rated frequency of motor: Pr5.06(Hz)
Rated current of motor: Pr5.07(A)
Rated speed of motor: Pr5.08(rpm)
Rated voltage of motor: Pr5.09(V)
Rated pole of motor: Pr5.11
Power factor: Pr5.10
Highest rotational speed: Pr1.06(rpm)
15.3.1.5 Close the enable signal of inverter (For the matched MPK708C system, make ENA and 24V in
short circuit)
15.3.1.6 The lower row of displayer flashes “AUTO” and “tune” alternately, meanwhile, inverter does the
self-tuning.
15.3.1.7 Wait the inverter Pr5.12 to display “0”, and the self-tuning is finished.
15.3.1.10 Save the parameters, and input 1000 in Pr. Xx.00, press M and then press the red reset key.
15.3.2.5 Close the enable and direction signal of inverter (For the matched MPK708C system, make ENA
and FWD, or REV signal and 24V in short circuit)
15.3.2.6 The lower row of displayer flashes “AUTO” and “tune” alternately, meanwhile, inverter does the
self-tuning.
15.3.2.7 Wait the inverter Pr5.12 to display “0”, meanwhile the motor stops rotating and the self-tuning is
finished.
15.3.2.10 Save the parameters, and input 1000 in Pr. Xx.00, press M and then press the red reset key.
15.3.2.11 Repeat the dynamic self-tuning for several times to confirm that the angle learning is right,
learning result at every time should be proximate or the same.
Note:
a) Save the parameters after the self-tuning is finished
MPK708C Commissioning Manual Code:YETS-0002-C
b) When it is used for the machine roomless elevator, please install the extension cable of inverter control
panel, and notice that the cable plug should insert with “HXG►” up.
c) Please remove the bridge of inverter and contactor.
15.4 Diagnostics
15.4.1 Trip indications
If the inverter malfunctions, the output of inverter is disabled. And the inverter stops controlling the motor.
The lower display indicates that a trip has occurred and the upper display shows the trip.
Trips are listed alphabetically in Table 15.4.1 based on the trip indication shown on the displayer.
Explanation:
If the content in the following table is marked with “X”(1≤X≤8), “X” represents the malfunctioning
module of multiple modules inverter.
Trip Diagnosis
C.OPtn SMARTCARD trip: Solutions Modules fitted are different between source drive and
destination drive
MPK708C Commissioning Manual Code:YETS-0002-C
Parameter Function
2.08 Standard ramp voltage
4.05/6/7,21,27/8/9 Current limits
5.07,21.07 Motor rated current
5.09,21.09 Motor rated voltage
5.17,21.12 Stator resistance
5.18 Switching frequency
5.23,21.13 Voltage offset
5.24,21.14 Transient inductance
5.25,21.24 Stator inductance
6.06 DC injection braking current
C.TyP SMARTCARD trip: SMARTCARD parameter set not compatible with drive
187 Press the reset button
Ensure destination drive type is the same as the source parameter file drive type
dESt Two or more parameters are writing to the same destination parameter
199 Set Pr xx.00 = 12001, check all visible parameters in the menus for duplication
EEF EEPROM data corrupted - Drive mode becomes open loop and serial comms will
timeout with remote keypad on the drive RS485 comms port.
31 This trip can only be cleared by loading default parameters and saving parameters
Enc1 Drive encoder trip: Encoder power supply overload
189 Check encoder power supply wiring and encoder current requirement
Maximum current = 200mA @ 15V, or 300mA @ 8V and 5V
Enc2 Drive encoder trip: Wire break
190 Check cable continuity
Check wiring of feedback signals is correct
Check encoder power is set correctly
Replace feedback device
MPK708C Commissioning Manual Code:YETS-0002-C
Trip Diagnosis
Enc3 Drive encoder trip: UVW phase offset incorrect whilst running
Check the encoder signal for noise
191 Check encoder shielding
Check the integrity of the encoder mechanical mounting
Repeat the offset measurement test
Enc4 Drive encoder trip: Feedback device comms failure
Ensure encoder power supply is correct
192 Ensure baud rate is correct
Check encoder wiring Replace feedback device
Drive encoder trip: Hiperface encoder - The encoder type could not be
Enc12
identified during auto-configuration
Check encoder type can be auto-configured. Check encoder wiring.
162 Enter parameters manually.
Drive encoder trip: EnDat encoder -The number of encoder turns read from the
Enc13
encoder during auto-configuration is not a power of 2
Enc16 Drive encoder trip: EnDat encoder - The number of comms bits per period for a
linear encoder exceeds 225.
166 Select a different type of encoder. Faulty encoder.
Drive encoder trip: The periods per revolution obtained during auto-configuration
Enc17
for a rotary SINCOS encoder is not a power of two.
167 Select a different type of encoder. Faulty encoder.
ENP.Er Data error from electronic nameplate stored in selected position feedback device
178 Replace feedback device
Et External trip from input on terminal 31
Check terminal 31 signal
6 Check value of Pr 10.32. Enter 12001 in Pr xx.00 and check for parameter controlling
Pr 10.32;Ensure Pr 10.32 or Pr 10.38 (=6) are not being controlled by serial comms
MPK708C Commissioning Manual Code:YETS-0002-C
Trip Diagnosis
Ensure the load is not jammed / sticking; Check the load on the motor has not changed
Tune the rated speed parameter (closed loop vector only) ;Check feedback device
20 signal for noise; Check the feedback device mechanical coupling
It.br Braking resistor overload timed out – accumulator value can be seen in Pr 10.39
Ensure the values entered in Pr 10.30 and Pr 10.31 are correct;Increase the power
19 rating of the braking resistor and change Pr 10.30 and Pr 10.31
O.CtL Drive control board over temperature
Check cubicle / drive fans are still functioning correctly;Check cubicle ventilation paths
23 Check cubicle door filters
Check ambient temperature;Reduce drive switching frequency
O.ht1 Power device over temperature based on thermal model
Reduce drive switching frequency; Reduce duty cycle; Decrease acceleration /
21
deceleration rates; Reduce motor load
O.ht2 Heatsink over temperature
Check cubicle / drive fans are still functioning correctly; Check cubicle ventilation paths
22 Check cubicle door filters
Increase ventilation; Decrease acceleration / deceleration rates; Reduce drive switching
frequency; Reduce duty cycle; Reduce motor load
O.ht3 Drive over-temperature based on thermal model
Check cubicle / drive fans are still functioning correctly; Check cubicle ventilation paths
27 Check cubicle door filters; Increase ventilation;
Decrease acceleration / deceleration rates; Reduce duty cycle; Reduce motor load
OI.AC Instantaneous output over current detected: peak output current greater than 225%
MPK708C Commissioning Manual Code:YETS-0002-C
Acceleration /deceleration rate is too short. If seen during autotune reduce voltage boost
Pr 5.15
Check for short circuit on output cabling; Check integrity of motor insulation;
3 Check feedback device wiring; Check feedback device mechanical coupling;
Check feedback signals are free from noise; Is motor cable length within limits for that
frame size?
Reduce the values in speed loop gain parameters – Pr 3.10, Pr 3.11 and Pr 3.12 (closed
loop vector and servo modes only)
Has offset measurement test been completed? (servo mode only);
Reduce the values in current loop gain parameters - Pr 4.13 and Pr 4.14 (closed loop
vector and servo modes only)
OI.br Braking transistor over-current detected: short circuit protection for the braking
transistor activated
Check braking resistor wiring
4 Check braking resistor value is greater than or equal to the minimum resistance value
Check braking resistor insulation
O.Ld1 Digital output overload: total current drawn from 24V supply and digital outputs
exceeds 200mA
26 Check total load on digital outputs (terminals 24,25,26)and +24V rail (terminal 22)
OV DC bus voltage has exceeded the peak level or the maximum continuous level for 30
seconds
Reduce deceleration ramp; Decrease braking resistor value (staying above the minimum
value); Check nominal AC supply level ; Check for supply disturbances which could
cause the DC bus to rise – voltage overshoot after supply recovery from a notch induced
2
by DC drives. Check motor insulation
Drive voltage rating Peak voltage Maximum continuous voltage level
400 830 810
O.SPd The rotating speed of motor exceeds the overspeed threshold.
The rotating speed of motor exceeds the overspeed threshold.
Increase the overspeed fault threshold in parameter Pr3.08(only fitted for closed loop
mode)
7 The rotating speed exceeds 1.2×pr1.06 or pr1.07(open loop mode)
Reduce the speed loop P gain (pr3.10) to reduce the speed overshoot(only fitted for closed
loop mode)
PAd Keypad has been removed when the drive is receiving the speed reference from the
keypad
34 Fit keypad and reset; Change speed reference selector to select speed reference from
another source
Ph AC voltage input phase loss or large supply imbalance detected
MPK708C Commissioning Manual Code:YETS-0002-C
Trip Diagnosis
RS Failure to measure resistance during autotune or when starting in open loop
vector mode 0 or 3
33 Check motor power connection continuity
SCL Drive RS485 serial communications loss to remote keypad
Refit the cable between the drive and keypad
Check cable for damage
30 Replace cable
Replace keypad
SLX.Df Solutions Module slot X trip: the type of solution Module in slot X has changed.
204,209,214 Save the parameters and reset.
SLX.Er Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202.207.212 Check value in Pr 15/16.50. The following table lists the possible error codes for the
position feedback mode
Error Trip Description Diagnostic
code
0 No trip No fault detected
1 Encoder trip: Encoder power Check encoder power supply wiring and
supply overload encoder current requirement
Maximum current = 200mA @ 15V, or
300mA @ 8V and 5V
2 Encoder trip: Wire break Check cable continuity
Check wiring of feedback signals is correct
Check supply voltage level
Replace feedback device
MPK708C Commissioning Manual Code:YETS-0002-C
3 Encoder trip: UVW phase Check the encoder signal for noise
offset incorrect whilst running Check encoder shielding
Check the integrity of the encoder
mechanical mounting
Repeat the offset measurement test
4 Encoder trip: Feedback Ensure encoder power supply is correct
device communications Ensure baud rate is correct
failure Check encoder wiring
Replace feedback device
5 Encoder trip: Check sum or Check the encoder signal for noise
CRC error Check the encoder cable shielding
6 Encoder trip: Encoder has Replace encoder
indicated an error
7 Encoder trip: Initialisation Check the correct encoder type is entered
failed into Pr15/16/17.15
Check encoder wiring
Check supply voltage level
Replace feedback device
8 Encoder trip: Auto Change the setting of Pr 15/16/17.18 and
configuration on power up has manually enter the number of turns (Pr 15/
been requested and failed 16/17.09) and the equivalent number of
lines per revolution (Pr 15/16/17.10)
9 All Thermistor trip
10 All Thermistor short circuit
11 Resolver: Poles not compatible Check that the correct number of resolver
with motor poles has been set in Pr 15/16/17.15.
74 All The Solutions Module has over-heated
SLX.Er Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212 Check value in Pr 15/16.50. The following table lists the possible error codes for the
position feedback mode
Error code Reason for fault
39 User stack overflow
40 Unknown error
41 Parameter does not exist
42 Parameter read only
43 Parameter write only
44 Parameter value over range
45 Invalid synchronisation modes
46 Not Used
47 Sync lost with Virtual Master
48 RS485 not in user mode
49 Invalid RS485 configuration
50 Math fault
51 Array index out of range
52 Control word user trip
53 DPL program not compatible with this target
MPK708C Commissioning Manual Code:YETS-0002-C
tunE1* The position feedback did not change /autotune failed during the inertia test.
11 Ensure the motor is free to turn i.e. brake was released. Check encoder coupling to
motor.
TunE2 Position feedback direction is incorrect during the autotune.
12 Check motor cable wiring is correct
Check feedback device wiring is correct
Swap any two motor phases (closed loop vector only)
tunE3* Drive encoder communication signals connected incorrectly during the autotune.
13 Check motor cable wiring is correct. Check feedback device U,V and W
communication signal wiring is correct.
Trip Diagnosis
tunE4* Drive encoder U communication signal fail during an autotune
14 Check feedback device U phase commutation wires continuity. Replace encoder
tunE5* Drive encoder V communication signal fail during an autotune
15 Check feedback device V phase communication wires continuity. Replace encoder
tunE6* Drive encoder W communication signal fail during an autotune
16 Check feedback device W phase communication wires continuity. Replace encoder
tunE7* Motor number of poles set incorrectly
17 Check lines per revolution for feedback device. Check the number of poles in Pr 5.11 is
set correctly
Uflt Multi-module inverter: unidentified trip
171 Check all interconnecting cables between power modules. Ensure cables are routed
away from electrical noise sources.
UV DC bus under voltage threshold reached
1 Check AC supply voltage level
Drive voltage rating (Vac) Under voltage threshold (Vdc)
400 350
MPK708C Commissioning Manual Code:YETS-0002-C
X.oht2 Multi module inverter: module X has detected that the radiator overheats.
121-128 Check whether the airtight cabin or the fan of inverter operates well
Check the Ventilated path of airtight cabin
Check the filter of airtight cabin door
Check the environmental temperature
Reduce the carrier frequency of inverter
Accelerate ventilation
Multi module inverter: module X has detected that the overcurrent occurs in the
X.OI.AC
instance output. The peak output current exceeds by 225%.
111-118 The acceleration or deceleration speed is too high.
If it appears in the process of autotune, reduce the boost.(Pr5.15)
Check whether the short circuit happens on the output cable.
Check the insulation of motor
Check the wiring of feedback device (if any)
Check the mechanical coupling of feedback device(if any)
Check that the feedback signal should not be disturbed by noise
Check whether the length of motor cable meets the requirements of frame size
Reduce the values of speed loop gain parameters Pr 3.10, Pr 3.11 and Pr 3.12(only fit
for the closed loop vector and servo mode )
Check whether the test of offset measurement is finished(only fit for the servo mode)
Reduce the values of current loop gain parameters Pr 4.13 and Pr 4.14(only fit for the
closed loop vector and servo mode )
Multi module inverter: module X has detected that the overcurrent occurs in the
X.Ol.br
brake IGBT.
141-148 Short circuit protection of brake resistor.
Check the wiring of brake resistor.
Check that the value of brake resistor is more than or equal to the minimum value.
Check the insulation of brake resistor.
Trip Diagnosis
Multi module inverter: DC bus voltage on module X exceeds the peak level, or the
X.OV
maximum continuous level reaches 30 seconds.
151-158 Reduce the deceleration(Pr0.04)
Reduce the value of brake resistor(more than the minimum value)
Check the level of nominal AC voltage
Check whether the power interference, which will lead to the increase of DC bus
voltage, exists. The power interference refers to the voltage overshoot(the power is
recovered from the trap resulted from DC inverter and correction of power factor, and
other large-scale equipments which are in power-on or power-off state)
Check the insulation of motor.
Rated value of inverter voltage peak voltage maximum continuous voltage level
400 830 810
OI.AC, OI.Br,
Normal trips with
x.OIAC, Can be reset after 10.0s
extended reset
x.OlBr
HF20 to HF30,
Non-resettable SL1.HF,
trips SL2.HF, Cannot be reset. Requires the drive to be powered down.
SL3.HF
These indicate fatal problems and cannot be reset. The
drive is inactive after one of these trips and the display
Hardware faults
HF01 to HF19 shows HFxx. The Drive Healthy relay opens and the
serial comms will not function.
The drive retains a log of the last 10 trips that have occurred in Pr 10.20 to Pr 10.29 and the trip time
for each trip in Pr 10.43 to Pr 10.51. The time of the trip is recorded from the powered-up clock (if Pr
6.28 = 0) or from the run time clock (if Pr 6.28 = 1). Pr 10.20 is the most recent trip or the current trip
if the drive is in a trip condition (with the trip time stored in Pr 10.43). Pr 10.29 is the oldest trip
(with the module number or trip time stored in Pr 10.51). Each time a new trip occurs, all the
MPK708C Commissioning Manual Code:YETS-0002-C
parameters move down one, such that the current trip (and time) is stored in Pr 10.20 (and Pr 10.43)
and the oldest trip (and time) is lost out of the bottom of the log. If any parameter between Pr 10.20
and Pr 10.29 inclusive is read by serial communications, then the trip number in Table 4-1 is the
value transmitted.
16-Fault instruction
16.1 Fault code of MPK 708C system
Fault Fault cause and treatment Whether show Method of fault
Numb fault in the floors
recovery
er
Safety circuit open, resulting Yes. Main Safety circuit can
E1 in the emergency stop of controller records recover to normal state.
elevator. the fault.
Phenomena 1: The door Yes. Record the Switch-on of door lock
isn’t switched on while door is fault can recover to normal
closing, resulting in the simultaneously. state.
overtime of door closing.
E2 Phenomena 2: The lock of Yes. Record the Switch-on of door lock
door is open in service, fault simultaneously. can recover to normal
resulting in the emergency state.
stop of elevator.
The signal of door zone can No, record the fault Record only. There is no
E3 not be detected or the creeping only. need to stop the
is overtime (more than 10 elevator.
seconds).
Deceleration point can not be Yes. Record the Elevator can recover to
detected and the elevator fault simultaneously. normal state after car
decelerates and stops at the leveling opens the door.
nearest point (Deceleration
E4 point still can’t be found when
elevator running exceeds limit
time in “Floor protect” menu),
for example, record the data
different from the standard
data.
Up limit switch is open. The Yes. Record the Upper limit switch can
elevator can travel downward fault simultaneously. recover to normal state.
E5 or make an emergency stop at
up service, but can not restart
the upward running.
Down limit switch is open. Yes. Record the Lower limit switch can
MPK708C Commissioning Manual Code:YETS-0002-C
Pulse count is not consistent No, record the fault There is no need to
E15
with inductor count. only. stop the elevator.
Under the fault of E22, the No, record the fault Signal reset.
E16 signal of terminal landing is only.
not correct when elevator is at
down limit.
E17 Landing door opens in an Yes. Record the It needs inspection
abnormal condition. fault simultaneously. reset.
After elevator starts (within 5 Yes. Record the The elevator will level
seconds), the input point of fault simultaneously. at the nearest floor and
inverter could not be detected. could not start again,
E18 which could be
rectified after an
inspection operation is
applied or power
supply is cut off.
The monitoring point of Yes. Record the The fault can be
E19 inverter brake is not open; fault simultaneously. removed by the open of
elevator cannot restart. monitoring point.
Floor record is not consistent No, record the fault V1 occurs error─
with the forced changing only. emergency stop. V2 and
E20 switch. Switch is off while V3 occur error
elevator is not at terminal ─deceleration and stop.
landings.
The brake switch does not Yes. Record the The fault can be
E21 switch off (main machine), fault simultaneously. removed by the release
and elevator can not restart. of brake switch.
Floor record is not consistent No, record the fault The fault can be
with the forced changing only. removed by the
E22 switch. Switch is not off while inspection point.
elevator is at terminal
landings.
MPK708C Commissioning Manual Code:YETS-0002-C
E23 The button has jammed for No, record the fault The fault can be
more than 30 seconds. only. removed by the button.
The main controller will No, record the fault The fault can be
record the fault E24 when the only. removed if elevator is
door lock was open for over restored to inspection
E24 3s, but door closing limit operation, door lock is
switch has not been switched open for over 2 seconds,
off. Open the door in reverse. or the limit switch of
If there is no door operator of door closing is switched
No.2, a blank shall be left for off.
the input point for 2# door
operator’s door closing limit.
If PM708 expander board Yes. Record the The fault can be
cannot detect the input of door fault simultaneously. removed by detecting
zone with the function of door the input of door zone
E25 pre-opening, main machine or the elevator doing an
will record E25 error. inspection operation.
PM709 for car top board has a Yes. Record the The elevator is changed
communication fault (When fault simultaneously. into an inspection
parameter INPUT operation or PM 708
SELECT/PMCARD=ON) expander-plate is
inspected and the
E26 inspection function of
extended-plate is
cancelled, which all can
remove the fault.
Cannot detect the input of Yes. Record the The fault can be
E27 security contact (I3.5), with fault simultaneously. removed after detecting
the function of door signal restore or
pre-opening. changing into the
inspection mode.
Cannot detect the input of Yes. Record the The fault can be
E28 speed testing point (I3.0), with fault simultaneously. removed after detecting
the function of door signal restore or
pre-opening. changing into the
inspection mode.
E29 The code is standby.
If the trap door is opened in Yes. Record the The fault only can be
the Russian mode, the elevator fault simultaneously. removed by changing
E30 cannot start. Inspection reset is into the inspection
need after the trap door is mode.
closed.
Signal adhesion of leveling Yes. Record the The fault only can be
MPK708C Commissioning Manual Code:YETS-0002-C
16.2 The fault record of SIEI inverter is adequate. In the commissioning, the fault
alarmed shall be removed in time. The fault records are as follows:
16.3
Fault code Fault name Cause Remedies
Failure of The fault of power supply Check the power supply
Failure power supply voltage Power off and then power on. If the
supply voltage The internal fault of inverter fault still occurs, please contact
SIEI agent.
The DC BUS drops to below If it is temporary source voltage
65% of rated voltage. interruption, power off and then
Power supply fault power on.
Under Under
The internal fault of inverter Check the input of device.
voltage voltage
may cause under voltage. If the power supply is normal and
internal fault of inverter occurs,
please contact SIEI agent.
The internal direct voltage of
drive exceeds the rated voltage Adjust deceleration time
by 35%.
Over voltage Over voltage The deceleration time is too
short.
Device is affected by high over
voltage peak value.
The malfunction is detected by Power off and then power on. If the
IGBT IGBT bridge or its gate driver. fault still occurs, please contact
IGBT Fault
Desaturat Interference fault SIEI agent.
Component failure
MPK708C Commissioning Manual Code:YETS-0002-C
overhigh.
The temperature for air cooling Check the fan.
Intake air S Intake air S is overhigh. Check the intake of inverter.
OT OT Fan fault
The intake is blocked.
Fault of main contactor of Check the contactor of inverter.
Cont fbk fail Cont fbk fail
inverter
The communication fault of Power off and then power on. If the
Commcard Commcard
inverter. fault still occurs, please contact
fault fault
SIEI agent.
Read-in fault of application Check installation.
Appl card Appl card
card Please contact SIEI agent if the
fault fault
installation is no problem.
Drive Drive Inverter overload
overload overload
Motor Motor Motor overload Decrease the motor load.
overload overload
BU overload BU overload The brake unit is overloaded.
incorrect.
24V Power-
CAN CAN1
Terminal
resistance
CAN2
DEBUGGING
INTERFACE
CONFIRM
ESCAPE
RESET
DOWN
UP
This group control board provides two CAN ports for communicating with the microcomputer
controller of lift. Generally, when this system is running, only one of the ports will be used,
and the other one will function as the stand-by port.
MICO ARMEG
Ver 1.0
BltControl (c)
Copyright Jan 8 2008
After about 1 second, the system starts to load configuration stuff. If the loading is successful,
the information shown in Figure 2-2 will be displayed. If it is failed(Maybe the Flash on
board is damaged, or it is connected with the power for the first time.), the information shown
in Figure 2-3 will be displayed.
MICO ARMEG
Load Config... Done.
CFG Addr: 0x0007C800
CFG Size: 0x00000400
MICO ARMEG
Load Config..Failed.
Use Default Setting
When the loading of configuration stuff failed, the system will use the default setting and save
it to the Flash.
When the loading of configuration stuff is successful, the system will wait for the user to
reconfigure stuff. The waiting time will last about 5 seconds(as shown in Figure 2-4).During
the waiting time, if any key on the board is pressed, the system will prompt the user to input
password(as shown in Figure 2-5).If the password input is correct, the user can access to the
parameter configuration interface(as shown in Figure 2-6). If it is incorrect or the “ESC” key
is pressed when inputting password, the system will keep waiting for the user to input the
password again. The user can only restart by pressing the “Reset” key.
The initial password of the system is 000000.
MICO ARMEG
01/08/08 08:00:00
Any Key To Config
5 Seconds Remain.
Password: 000000
1. Basic Config
During the wait time, if no key is pressed, the system will start to run. Meanwhile, the system
will initialize the CANBUS communication port, if the initialization is successful (as shown
in Figure 2-7), the system will start to run normally after a short time. The normal run
interface is as shown in Figure 2-9.
MICO ARMEG
If CANBUS initialization is failed (as shown in Figure 2-8), although the software will
continue running, the system cannot run normally. The group control board should be checked
if there is anything wrong with the hardware.
MICO ARMEG
Init CANBUS.Failed.
pressed after the system runs normally for 30 seconds, LCD will not continue displaying the
above-mentioned information and the backlight of LCD will be turned off. If any key is
pressed after that, the backlight will be turned on again and continue displaying the
information above-mentioned.
2. Lift Address
Figure 3-1 Use the “∨”and“∧” keys to choose different main menu item
User Cancelled.
Any key restart …
MPK708C Commissioning Manual Code:YETS-0002-C
Figure 3-2 Pressing the “ESC” key under the main menu will make the system restart.
Due to the space limitation of the LCD, the logograms or abbreviations of English words were
used in the menu, and their meanings are as follows:
1. Basic Config Basic configuration
2. Lift Address Lift address setting
3. Waiting Floor Waiting floor setting
4. Catching Floors Catching distance (Number of floors) setting
5. Call Disabled permitted or disabled door opening/closing setting of
each lift
6. Power Management Power (Power off or firefighting)management
7. Schedule Policy Schedule policy setting
8. Default Setting Use the default setting of the system
9. Save Settings Save the settings configured
Item 1 to 7under the main menu mentioned above has sub-item parameters, but Item 8 to 9
does not.
After each modification, Item 9 must be selected to save the modification, through which the
modification can become effective. After modification, press the “RESET” key to restart, or
switch off and then switch on.
Following are the introductions of all items:
CONFIG 1 - Basic
Parameter Name
1.1 Number Of Lifts
4 Parameter Value
CONFIG 1 - Basic
Parameter Name
1.1 Number Of Lifts
4 Parameter Value
MPK708C Commissioning Manual Code:YETS-0002-C
0 –20kbps
1 –80kbps
17.3.1.9 PF Run Time (ms)
The average time required by lift for traveling one floor
Valuing range: 0-60000
Default: 2500
Note: The unit is “ms”. The increment of parameter modification is 50ms.
17.3.1.10 Dwell Time (ms)
The average time of door maintaining opening
Valuing range: 0-60000
Default: 12000
Note: The unit is “ms”. The increment of parameter modification is 50ms.
This time should include the deceleration time for leveling.
17.3.1.11 LongOpen Time(s)
The excessive door opening time (unit: s)
Valuing range: 0-255
Default: 30
17.3.1.12. LongWait Time(s)
The excessive waiting time (unit: s)
Valuing range: 0-255
Default: 180
17.3.1.13 Realloc Time (s)
Reallocated time(unit: s)
Valuing range: 0-255
Default: 30
17.3.1.14 No Task Time (s)
Idle lift reallocated time
Valuing range: 0-255
Default: 120
Recommendation: 120
17.3.1.15 Idle Sch Time(s)
The time required by all idle lifts to return to the predetermined Waiting
Floor
Valuing range: 0-255
MPK708C Commissioning Manual Code:YETS-0002-C
Default: 120
17.3.1.16 CatchFlr Enabled
Whether Catching Lift is enabled and Number of floors for Catching Lift
Valuing range: 0-10
Default: 0
The signification of the value:
0 – Catching Lift is disabled
Others – Number of floors for Catching Lift
17.3.1.17 Year
The year of the system time
Valuing range: 2008-2099
Default: 2008
17.3.1.18 Month
The month of the system time
Valuing range: 1-12
Default: 1
17.3.1.19 Day
The day of the system time
Valuing range: 1-31
Default: 8
Note: According to the month setting, the system will adjust the maximum
number of days in that month. It can deal with intercalary month.
17.3.1.20 Hour
The hour of the system time
Valuing range: 0-23
Default: 8
Note: The system adopts 24-hour system.
17.3.1.21 Minute
The minute of the system time
Valuing range: 0-59
Default: 0
17.3.1.22 Second
The second of the system time
Valuing range: 0-59
MPK708C Commissioning Manual Code:YETS-0002-C
Default: 0
17.3.1.23 Down Stream Floor
The Waiting Floor which no-duty lift situated during down peak time
Valuing range: 1-60
Default: 1
17.3.1.24 Password
The password used when entering into parameter modification interface
Valuing range: 000000-999999, a 6-digit figure
Default: 000000
CONFIG 1 - Address
Lift No.
2.1 Addr Of Lift#1
4 Address
CONFIG 3 - Waiting
Serial No.
3.1 1st Waiting Flr
1 Waiting Floor
MPK708C Commissioning Manual Code:YETS-0002-C
CONFIG 5 – DisCall
Lift No.
Lift: 1 Door: 0
Door No.
Figure3-8 Selection of the Lift and Door machine with Call Disabled
Floor No.
Lift No. Door No.
DisCall L1 D0 F4
10000000000000000000
00011111111111111111
Underline cursor 11111111111111111111
MPK708C Commissioning Manual Code:YETS-0002-C
In the interface of Call Disabled, in addition to Lift No., Door machine No. and Floor No.
displayed in top right corner, there is also an underline cursor to indicate floors. Each 0 or 1 in
the three lines of Figure means whether the lift door can be opened at this landing. 0 means
the door can be opened and 1 means the door can not be opened. The cursor can shift among
the floors by pressing the“∨” and“∧” keys. If the “ESC” key is pressed, the system will
return to the interface shown in Figure 3-8. If the “INT” key is pressed, this value can be
modified and then the cursor will become to be blinking blocking cursor.
When modifying this value, pressing the“∨” key can change the value to be 1, pressing the
“∧” key can change the value to be 0, pressing the “ESC” key can make the modification
invalid and pressing the “INT” key can make the modification valid.
Other landings can also be set according to the operation mentioned above.
CONFIG 6-PowerMan
Go Base:1 MaxLifts:1
Order: 1423
Avail: 0000
“Go Base” indicates whether the group control system needs to notice all lifts to return to fire
fighting home landing first after receiving the signal of power failure or fire fighting, and the
setting can be 0 or 1; 0 means returning to fire fighting home landing is not needed, 1 means
returning to fire fighting home landing is needed.
“MaxLifts” indicates the maximum Number of lifts can be scheduled at a time in the state of
power failure or fire fighting. It is related to the provision of backup power of lift system. Its
valuing range is from 0 to lift quantity in lift group.
“Order” indicates the sequence that the lifts are scheduled in the state of .power failure or
fire fighting. Each Number after “Order” indicates the schedule sequence Number for lift in
its corresponding position.
“Avail” indicates the schedulability of lift in the state of power failure or fire fighting, in
MPK708C Commissioning Manual Code:YETS-0002-C
other words, whether a lift can operate normally. Each Number after “Avail” indicates
whether the lift in corresponding position can operate. 0 means the lift can not operate and 1
means lift can operate in the state of power failure or fire fighting.
The operation of Power Management is as follows: The items can be shifted by pressing
the“∨” and“∧” keys, there is an underline cursor to indicate current item. If the “ESC” key
is pressed, the system will return to main menu. If the “INT” key is pressed, the settings of
this item can be modified.
In the state of modification, there is a blocking cursor indicates the items to be modified. At
this time, pressing the “∨” key can increase this value and pressing the “∧” key can
decrease this value. If the “ESC” key is pressed, the modification will be invalid; if the “INT”
key is pressed, the modification will be valid.
CONFIG 7 - Schedule
Time :12:00 Time
Policy:0
Schedule
There are four types of schedule policies, the set values are from 0 to 4. 0 means the Schedule
Policy of previous time period will be used continuously. Significations of the other Numbers
are as follows:
1- Schedule Policy for minimum energy consumption;
2- Schedule Policy for minimum waiting time;
3- Schedule Policy for up peak;
4- Schedule Policy for down peak.
When select this item in main menu, all settings set by users will be invalid, the system will
use the Default Setting to replace them, so be careful when using this function
Other Default Settings are as follows except for those introduced in 3.1:
Lift Address: They are all set to the corresponding Lift No.
Waiting Floor: They are all set to the 1st floor.
Catching Floor: They are all set to 0.
Call Disabled: All the lifts are permitted to open doors at all the landings.
Power Management: All the lifts do not return home landing.
The Number of the lifts can be scheduled at a time is 0.
All the lifts can not be operated.
Schedule sequence of the lift is the Lift No.
Schedule Policy: All the time is set to 0 , this means no Schedule Policy is available. In this
case, the minimum waiting time for Schedule Policy will be selected by system.
communication cable conforms to the standard of our company should be used to connect all
lifts together by concentrator / disconcentrator, and then connected to CAN1 port.
24 V power -
24V power +
CAN11
CAN2
DEBUGGING
INTERFACE
CANCEL
CONFI
DOWN
UP
Attention:
The CAN communication cable used in other situation is four-core cable consisting of two
groups of wires, one group is used for providing power supply for the other terminals (e.g.
hall call panel). This kind of cable can not be used directly, if it is used for connecting the
system and microcomputer controller of each lift, all the microcomputer controllers of lifts
will common ground, which will cause the failure of communication or damage of
microcomputer controllers, even safety accidents.
absolute floor
number. The seventh digit is set “1” which indicates call signal is on the side of 2#door.
Set terminal resistor on the eighth digit of the last external call board of CAN universal serial
bus.
3 2 1 Function Description
0 0 0 main operation panel
Sub-operation panel or opening and closing of two
0 1 0 doors at the same time or opposite door on differ
floor (OPEN-METHOD=0 or 1)
Opposite door operation panel. For the opposite
door on the same floor, the front door shall open
0 0 1 according to the order to main operation panel and
the rear door shall open according to the order to
sub-operation panel. ( OPEN-METHOD=2)
19- SD003 The instruction for voice report station board of elevator
CON4 or
Power, signal input
CON3
No. Vcc CANH CANL Gnd
CAN BUS high CAN BUS low
Power of
Power+ leveling signal leveling signal Power-
definition
connect point connect point
19.2.3 CH2 is output interface of a speaker, which can be connected to a speaker with the
resistance between 4Ω and 8Ω, the power below 1W.
19.3 Description for jumper:
J3 Report up and down running when Report up and down running when elevator
elevator starts. closes the door.
*Note: when connecting J6, choose whether clos.wav or open.wav is set for reporting
according to configuration document.
There are two potentiometers VR1 and VR2 on report station board to adjust the volume
of background music and floor music. VR1 is used to adjust the volume of background music;
VR2 is used to adjust the volume of floor music. First insert SD card into the board and then
connect the board to communication system through CAN socket in order to receive the order
and elevator state. After power-on background music is reported under no receiving of special
condition. If the background music is not needed, the volume of it can be adjusted to the
lowest.
%1 System set%
0; (Can Baudrate:0->20K,1->25K,2->40K,3->88K,4->5K,5->6K)
0; (when J6 On,1->open.wav,0->no open.wav)
1; (when J6 On,1->close.wav,0->no close.wav)
%end%
Note:
(Can Baudrate:0->20K,1->25K,2->40K,3->88K,4->5K)means that CAN Baud rate has
the following selection: “0” stands for 20K、“1” stands for 25K、“2”stands for 40K、“3”stands
for 88K、“4”stands for 5K. If 25K is used, “0” in front of the sentence shall be changed into
“1”. By that analogy choose other Baud rates. If selection is out of the mentioned above, the
system cannot work normally.
(when J6 On,1->open.wav,0->no open.wav)means: When the jumper J6 is connected,
if the “0”is in front of the sentence, select the setting of no reporting of door open; if “1” is in
front of the sentence, select the setting of reporting door open.
(when J6 On,1->close.wav,0->no close.wav) means: when the jumper J6 is connected, if
the “0”is in front of the sentence, select the setting of no reporting of door close; if “1” is in
front of the sentence, select the setting of reporting door close. When setting the jumper J6,
see whether there is audio file of reporting door open and close in SD card.
Note: the sentence (%1 System set% and %end%) shall not be modified
MPK708C Commissioning Manual Code:YETS-0002-C
Floor 1 1.wav
Floor 2 2.wav
...... ......
Floor 63 63.wav
Floor 64 64.wav
A 65.wav
B 66.wav
...... ......
Y 89.wav
Z 90.wav
Negative first layer 91.wav
Negative second layer 92.wav
...... ......
Negative ninth layer 99.wav
b1.wav b2.wav b3.wav b4.wav b5.wav ……. b39.wav b40.wav (They cannot be all
deleted, or report confusion will be caused.)
19.5.6 File naming of special floor report in SD card
20.1.1.1Floor information
The floor information is judged directly and displayed by the displayer through the floor signal
sent by CAN concentration line connector.
20.1.1.2 Time
The current time can be displayed in real-time.
Turn off back light automatically (Auto) after 3 minutes of no signal. The back light shines
constantly (Long).
DE key to enter adjustment mode, at this time press SET key to adjust corresponding
content. Then press MODE key to change the unit of adjustment. When adjustment unit is
“year”, press MODE key to finish the time setting. While adjusting the time, the time
setting will be over automatically by the system with no pressing the key within 3 minutes and
it will return normal time display.
20.2 DP003M liquid-crystal display panel instrument (hall call display small
liquid-crystal display panel)
MPK708C Commissioning Manual Code:YETS-0002-C
20.2.1.1 Type: M1 and M2 have the same function, but different screen colors.
DP003M1: Red film, yellow letter
DP003M2: Blue film, white letter
20.2.1.2 Size: Size of the circuit board: 195.50 (mm) X 95.00 (mm)
Size of Visible Zone: 174.10 (mm) X 58.40 (mm)
20.2.1.3 Information displayed: Direction, inspection, overload or full load; floor display.
20.2.3 Function setting and Wiring diagram
B K2 language selection
OFF: Chinese; ON: English
C S1-S7: setting of absolute address of hall call floors through Binary code mode
S7=high position, S1=low position. When turn to “ON”, value is “1”; “OFF”, value is “0”.
For example, when set on the ground floor, it shows “10000001”;first floor “00000010”;
second floor: ”00000011” …… 64th floor “01000000”.
S8 is the on-off of ultimate resistor of CAN BUS. Turn it to “ON” when the displaying
board is connected to the terminal of CAN BUS (very end, meaning the lowest floor),
otherwise set it at “OFF”.
If the displaying screen is installed inside the car, S1~S7 can all be set to “ON”. Now the
screen will not show “Full load”. When overload signal is detected, it will show
“Overload”.
D The two-cored white socket near the hall call pushbutton up arrow socket is used to joint
the GND of both display boards when two lifts are connected in parallel.
Background can be set to be fixed or changed according to the floor. The background picture
name is bg0.bmp~bg40.bmp. (bg0.bmp is fixed background picture.)
22.2 Parameters setting
(1) Configuration file
The configuration file is located in file folder MT70 under the root directory, the file name is
config.txt. The user should change the front parameter.
3 0 X0 function: 0->disable,1->enable
4 0 Display direction: 0->horizontal,1->vertical
5 3 Local floor number
6 0 Whether the arrow is in scroll display; 0 is for no scroll
display; >0 is for interval of brushing map ms
7 -5 Temperature offset, -99-99, 200->no display
8 50 Lcd backlight, it is between 0 and 100.
9 0 Not used
10 0 Date display mode:
0->year-month-day,1->day-month-year, other->not
display time and date
11 1 Error code display: 0->no, 1->yes
12 1677 Font color, RBG, if font is yellow it will be
4912 0xFF0000,if it is converted to be decimal, it will be
16774912
Note: if the local floor number is set 0, that indicates car display board, the number which is
more than 0 indicates the current floor number on external call board.
② Arrow window setting. The window is rectangle, only confirm the coordinates at the
upper left corner and lower right corner of the window. The unit of coordinate is pixel.
Row
Set value Note
No.
15 0 Start x
16 0 Start y
17 400 End x
18 300 End y
19 1
Examples: the display direction is transverse display (the fourth row is 0), the display effect
that customer hopes to see is shown in following picture.
The upper left corner coordinate of arrow window is (0,0), the lower right coordinate is
(400,300), please see the following picture block 1.
MPK708C Commissioning Manual Code:YETS-0002-C
Therefore, the set value is the same as that in the above table.
③ Setting of floor number window
Row
Set value Note
No.
22 400 Start x
23 0 Start y
24 800 End x
25 300 End y
26 1
The effect of setting values in the above table is shown in the following picture (transverse
display) block 2:
Row
Set value Note
No.
29 0 Start x
30 300 Start y
31 800 End x
32 420 End y
33 1
The effect of setting values in the above table is shown in the following picture block 3:
Row
Set value Note
No.
36 0 Start x
37 420 Start y
38 250 end x
39 468 end y
40 1
The effect of setting values in the above table is shown in the following picture block 4.
Note: the height of block 4 should be the whole number multiples of 48.
MPK708C Commissioning Manual Code:YETS-0002-C
(2) Jumper
The jumpers J2 and J3 need to be set
Not connect Connect
J3 Door A Door B
J4 Fixed background Switch the background on each
floor
J5 Normal running Update picture
J2 CAN non terminal CAN terminal
It is convenient to modify the floor in which the external call board is, time and date,
temperature drift and LCD backlight by the LCD menu.
Press the KEY1 for 4 seconds, and open the menu setting screen, select the menu through the
up and down buttons of elevator. Press the KEY1 to enter the selected menu, and adjust the
current value by the up and down buttons of elevator. After adjustment, press KEY1 to exit.
Finally, save and exit by “Save&Exit” menu. Please see the following picture:
The user can customize nine windows: arrow window, floor window, multifunction display
window, date window, time window, week window, temperature window and logo window
and fault code window. Please refer to configuration file 1 in Ⅱ parameter setting for window
size.
The arrow window displays the up or down run direction of elevator. The file name is shown
in the following table.
Arrow direction File name
up ArUp.bmp
down ArDown.bmp
The floor window displays the current floor at which the elevator is. The floor range is 0-512.
The file name is shown in the following table.
Floor number File name
0 Fn0.bmp
1 Fn1.bmp
2 Fn2.bmp
3 Fn3.bmp
… …
512 Fn512.bmp
The multifunction window can display the current floor information, special state in which the
elevator is such as over load, full load, and firefighting etc. there are three priority levels, and
the high level should be displayed preferentially. State 6, 7, 8, 9, repair, firefighting,
self-learning, and the elevator locking is the top priority.
File name Priority level
State 6 St6.bmp high
State 7 St7.bmp high
State 8 St8.bmp high
State 9 St9.bmp high
State 10 St10.bmp high
State 11 St11.bmp high
Repair Repair.bmp high
Firefighting Fire.bmp high
Self-learning Sl.bmp high
Elevator locking Lock.bmp high
In over load and full load priorities, the external call panel only displays the full load and car
display panel only show over load. While the over and full load and the high priority level
state happen at the same time, they should be displayed alternately.
File name Priority level
Full load Fl.bmp medium
Over load Ol.bmp medium
Background can be set to be fixed or changed according to the floor. The background picture
name is bg0.bmp~bg40.bmp. (bg0.bmp is fixed background picture.)
MPK708C Commissioning Manual Code:YETS-0002-C
Note: if the local floor number is set 0, that indicates car display board, the number which is
more than 0 indicates the current floor number on external call board.
② Arrow window setting. The window is rectangle; only confirm the coordinates at the upper
left corner and lower right corner of the window. The unit of coordinate is pixel.
Row No. Set value Note
15 0 Start x
16 20 Start y
MPK708C Commissioning Manual Code:YETS-0002-C
17 160 End x
18 140 End y
19 1
Examples: the display direction is transverse display (the fourth row is 0), the display effect
that customer hopes to see is shown in following picture.
The upper left corner coordinate of arrow window is (0, 20), the lower right coordinate is
(160,140), please see the following picture block 1.
26 1
The effect of setting values in the above table is shown in the following picture (transverse
display) block 2:
Row
Set value Note
No.
36 0 Start x
37 0 Start y
MPK708C Commissioning Manual Code:YETS-0002-C
38 0 end x
39 0 end y
40 1
。
The effect of setting values in the above table is shown in the following picture block 4.
Note: the height of block 4 should be the whole number multiples of 24
Row
Set value Note
No.
50 0 Start x
51 0 Start y
52 0 end x
53 0 end y
54 1
Row Set
Note
No. value
57 0 Start x
58 0 Start y
59 0 end x
60 0 end y
61 1
OFF ON
J2 Non terminal Terminal
J3 Door A Door B
Change background picture
J4 Not change background picture
at every floor
J5 Normal running Update the picture
J6 Stand-by, do not need to dial ON
MPK708C Commissioning Manual Code:YETS-0002-C
Preface
DTIC control system is developed and manufactured by Prospect Co. and is specially used
with IC card controller together. DTIC control system is composed of its software and its
reader.
This manual is suitable for the software of all around IC card controller as well as the
other type IC card controller. Due to all around type IC card controller has the full function,
so we take it as the example to introduce the software of DTIC control system.
The operation steps of DTIC control system is as follows: Installation→device
control→adding info of device→make setting card→user control→adding info of
users→make user card or other cards (when making cards, steps can be changed, but when
using it on the controller, setting card must be read first, then corresponding user card only
can be used). In this way, users operation is finished.
Tips:
Please connect serial port of reader of DTIC control system and USB port with
computer correctly before operation.
After DTIC control system put into operation, please backup the file “data” under
the installation directory of DTIC control system regularly.
If you appoint target directory of the file, single click “browse” and the following
window will appear, select directory you want and single click “OK” for saving.
If select default target directory, single click “next step”, appear dialogbox, and go on single
clicking “next step”, DTIC control system will be installed into your computer, as below:
MPK708C Commissioning Manual Code:YETS-0002-C
Single click menu “start” -program-DTIC control system. Or double click icon of
“DTIC control system” on the table top to carry on program of DTIC control system.
When program is started, “Login” interface will appear first. Enter user’s name and password.
After “user’s name” and “password” is entered, single click “login”. After the user’s name and
password is validated, below interface will appear and operator can start to operate the
program.
MPK708C Commissioning Manual Code:YETS-0002-C
Login successfully.
Single click “serial port settings” and the following window will appear:
Set serial port of reader: this function is used for appointing the number of serial port that
reader connects with computer. Single click “test connection of reader”, system will set serial
port number that the reader actual being connected automatically.
Set 485 wire serial port: when system has 485 communication module, this function only can
be adapted. The operator can select serial port number connected with 485 communication.
After setting is finished, single click “save info”. Then close the window.
Adding users: single click “build account” and the following window will appear:
Enter name, password of the user’s account and enter password again for confirming,
select type of the account. Select administrative, he can add, modify and delete the users but
the operator only can modify his own account information.
Modify user: single click “modify account” or double click user’s account that will be
modified in the account directory. The dialogbox will appear (same one with “build account”),
operating method will be as per “adding user”.
Delete user: select the user that will be deleted, single click “delete account”, it will ask
you whether you want to delete it or not, if yes, single click “yes”.
24.2.3.3 Charging standard setting
This function is for setting charging standard when charging according to time or times.
Single click “charge standard”, the following window will appear.
MPK708C Commissioning Manual Code:YETS-0002-C
Adding charging standard, single click “build standard”, the following window will
appear:
Delete charging standard: select charging standard that will be deleted, single click
“delete standard”, a dialogbox will appear to ask you if you delete it or not, single click “yes”.
This charging standard will be deleted.
Single click button “add” under the device list at the right, the following window will
appear:
Device number is produced by the system automatically. Enter device name (device
name can not be entered twice). Enter info of the elevator installed by this controller:
including building name, unit and the floor number.
Setting of floor selector wire: floor corresponding with terminal of floor selector can be
set, but normally this is not set.
Time limitation setting: When user wants to use the function of time limitation in group
8 of the controller, single click “the eight group limited” and fill in time in the group and
select group numbers that will be set, as following window:
MPK708C Commissioning Manual Code:YETS-0002-C
Virtual card setting: this function is used for administrative to use elevator with
password without using card. Two passwords can be saved in the controller, and the setting
method is the same. Single click “virtual card 1” or “virtual card 2”, the following window
will appear. In this interface, password and available floor controlled by password can be set
(password can be 8 figures at most). If floor controlled by password is not set, then password
only control the action of main controller.
Single click “set password time”, the following interface will appear. In this window,
password expiry, available time of the password and time limitation in 8 groups of the
controller used with password can be set.
MPK708C Commissioning Manual Code:YETS-0002-C
After all settings being finished, single click “save” and return to the previous interface.
In this way, a main controller is added successfully. Any device in the device list can be
selected, information of this device can be looked over in the left information bar.
Notice: 254 controllers can be added in the system at most.
Single click “make setting card”, when the reminding window of “setting card being made
successfully” is found, card is made well. Reader of the system will write the device
information of the controller and the current time to IC card. Only after the card is read in the
controller, the device information only can be saved in the controller.
Note: Reading setting card in the controller will send a signal, it means card reading is
completed.
24.2.4.5 Search function of the controller
Select conditions of search (device name, device number or building name), enter
related device information, single click “search”, controller being searched will be found in
the device list. As below window:
the list.
After enter related user information in the user information bar at the right, single click “read
card applying record”, using information of this user will be displayed in the list. If you want
to save the information, please single click button of “invert into Excel”.
Enter basic information of user, including name, telephone number, building name, unit and family number
of the card holder.
Single click “controller”—“add controller info”, following window will appear. Select controller
MPK708C Commissioning Manual Code:YETS-0002-C
being added first, then single click “add”, return to the precious window, adding controller is
completed. One user can add at most 10 controllers.
After controller is added, double click this controller, below window will appear.
MPK708C Commissioning Manual Code:YETS-0002-C
Select the available floor for the user, the function of selecting floor will be realized.
Set response time of the controller and response time of the floor selector. Normally 2-5
seconds is OK. Response time of the controller is waiting time that after user reads the card,
device operates the elevator. That is, after user reads the card, the elevator will operate it, after
setting time passed, the operation will be cancelled.( if response time is 2 seconds, the
elevator will cancel the operation 2 seconds after user reads the card), that is it will return to
the situation as before user reading card.)
Response time of floor selector: floor selector is used for controlling multiple floors,
function of response time of floor selector is the same with that of the controller.
Using time by user can be set too. Setting limitation time can control user to use the
elevator in controlled time. The user can not use elevator out of the using time in the same day.
Using period of the user is composed of two types: one is that use time saved in the card.
Select “group limited(in card)”, setting start time and end time. Another type is that use time
saved in the controller. Selecting limitation time in any several groups of the controller is ok.
If there is no setting limitation time in the controller, this option is not available.
After setting is completed, single click “save” and return to the previous window. After
operator finishes to set available controllers by the user, it also can be cancelled or reset by
“delete controller info” and “modify controller info” as below.
MPK708C Commissioning Manual Code:YETS-0002-C
When charging is required, select “charged by lift”. Select charging type and
corresponding charging standard. If charging is not required, do not select it.
Note: charging standard requires to be set in advance, operation steps see “system
setting operation”.
Single click “save information” for saving user information. If reminding window “adding
user’s information successfully” is found, click “OK” and return to the precious window.
After adding user, select the user, the basic information of the user will be seen in the
information bar at the left. Select device added by the user and look over the device
information. As below window:
MPK708C Commissioning Manual Code:YETS-0002-C
24.2.5.1.2 Modify user: select the user that will be modified, single click “modify”, window
of “build user card information” will appear, the operation is the same with “setting the user
information” in “adding user” window.
24.2.5.1.3 Delete user: select the user that will be deleted, single click “delete”, reminding
dialogbox will appear, single click “yes”, “deleting user” will be completed.
24.2.5.1.4 Make user card: this function is used for users not being charged. After user
information is set, user information being set will be written into IC card with this function.
Select user who needs to make card, single click “distribute”, when reminding window of
“user card is made successfully” is found, card making is completed.. If card making is failure,
check if reader connection is correct or not.
24.2.5.1.5 Recharge user card: this function is used for recharging the users who are charged
and made card for them.
Select user who will be recharged, single click “charging”,the window of “charging” will
appear. If the user is charged by times, enter times. If user is charged by time, enter the expiry
of recharging. The system will calculate the total amount according to the unit price of
charging standard.
MPK708C Commissioning Manual Code:YETS-0002-C
Recharging information of user can be read first before recharging. If information of the
user and the card is match, single click “read charging info”, the amount recharged last time
and left times (or expiry) will display. Enter times before recharging, times in the card will be
the left times and newly added times.
MPK708C Commissioning Manual Code:YETS-0002-C
Single click “charging user’s card”, if you find window of “ user card being recharged
successfully”, recharging is completed.
24.2.5.1.6. Withdraw the user
This function is for restricting the user to use card. If the operator wants to stop one user
using the elevator, he can add this user to the withdrawing list and make withdrawing number
card. After reading card, the card will not be used in this elevator.
First select the user that will be withdrawn from the user card list at the left, then select
the controller that will be used for withdrawing the user in the user controller list at the right,
single click “add card NO. to cancellation list”, this user will be added into the withdrawing
list of this controller. It can be operated repeatedly. More users can be added into the
withdrawing list. One controller can add at most 32 users into withdrawing list. After all
adding is finished, single click “release cancellation card”, when you find the window of
“withdrawing card is made successfully”, card making is completed. After reading this card
on corresponding controller, the user card withdrawn will not be used.
If you want to recover the withdrew card, select the user that you want to recover, single
click “save form cancellation list”, and make the number withdrawing card again and read it
in the corresponding controller, this user card can be used again.
The operation of setting basic user information, adding, modifying and deleting the
user’s available controller information and the option of “charged by lift” is the same with
those of the ordinary user card. Details is as per operation manual of ordinary user card.
Intellectual condition setting: there are two types of intellectual card: Password
intellectual card and telephone calling intellectual card. Password intellectual card is that user
can use elevator by entering the password that is set in advance but without card. After
selecting “password”, the function of password will be applied. After intellectual card is made,
read it in the elevator and set password. The functions of “telephone calling intellectual card”
MPK708C Commissioning Manual Code:YETS-0002-C
and the “password intellectual card” are almost the same. The user can use elevator by data
saved in the device getting by dialing mobile phone number without card. After selecting
“telephone number”, enter mobile number is OK. Then set “control floor” and “response
time”. “Control floor” are just those floors called by password or telephone. “Response time”
is that after user finishes to enter password or finish dialing telephone and validation is done,
after waiting time is end, elevator will select floor automatically. Waiting time at most can be
10 minutes.
Note: One user can not set password calling elevator and telephone calling elevator
at the same time.
After setting is completed, single click “save info”, when the reminding dialogbox appears,
single click “OK”. Then return to the precious window.
Other functions (modify user, delete user, make user card, recharge user card, withdraw
card) are the same with the ordinary user card. Details as per operation manual of ordinary
user card.
24.2.5.3 Operation of super user card
This function is used to inspect the system by administrative. Super user card can be
used in any controllers of this system and there is no limitation to using time, times and floor.
Single click “super user card”, enter interface of super user card.
MPK708C Commissioning Manual Code:YETS-0002-C
24.2.5.3.1 Adding user: single click “add”, window of “new built super card” will appear. Edit
the card holder’s information such as name, telephone, address etc. single click “save”, appear
a reminding dialogbox, single click “OK”. The system can add at most 134 super users.
24.2.5,3,2 Modify user: select the user that will be modified, single click “modify”, window
of “modify super card” will appear, save the information after finishing edition.
24.2.5.3.3 Delete user: select the user that will be deleted, single click “delete”, appear a
reminding dialogbox, single click “OK”.
24.2.5.3.4. Make super user card: select user from the list who will make card, single click
“make super card”. After the reminding of “super card is made successfully” is found, the
card making is completed.
24.2.5.3.5 Withdraw user: select the user that will be withdrawn, single click “add card NO. to
cancellation list”. Above operation can be repeated and more users can be added into the user
withdrawing list. After all adding is finished, single click “make cancellation card”. When the
reminding of “withdrawing card is made successfully” is found, the card making is completed.
After reading this card in corresponding controller, super card withdrew in the card will not be
applied in this elevator.
If you want to recover withdrew super card, select the user in withdrew card list, single click
“save form cancellation list” and make card again and read the card to the corresponding
controller. The card can be made again and can be used.
MPK708C Commissioning Manual Code:YETS-0002-C
Single click “add control condition” or “modify control condition”, there will appear the
window of “ editing controlling condition”.
In the window appeared, set floor that will be controlled and condition, and select
controlling type. There are two controlling types: timing control and control at once.
If the type of “timing control” is applied, open hour (start time and close time) of using
elevator should be set. “Start time of open elevator” is just that of starting time of timing of
using elevator and close time of using elevator is just that the elevator being controlled of
timing.
Note: when apply type of “timing control”, at the same floor, two groups condition
should be set, one group is that condition of timing open elevator, the other group is
condition of timing elevator being controlled. Being controlled period is that when
setting time is reached, user can use elevator only by using card. Timing open period is
that user can use elevator without using card.
“Control condition of timing” can be set to use repeatedly in a week. When the week is
MPK708C Commissioning Manual Code:YETS-0002-C
Single click “payment control” on the main interface, below interface will appear:
When recharging to user card, charging information will be saved into data base at the same
time. You can save these information with EXCEL and you also can print it.
When there is more set of charging record, user can search with the search function
supplied by the system. It also has the function of deleting function. But if you delete the
charging information, it will be not recovered. When using “delete”, select the searching
scope first, for example, the searching scope is “today”, the system will display all charging
record of today. Click “delete record”, system will delete all the charging record of today.
Other searching method is the same.
Single click “read card info”. After a signal is given by the reader, window will display
information in the card.
Control room host falls into two categories, with display (type: BLT12-254N) and without
display (type: BLT12-16N).
Extension calling the host: the elevator number indicating lamp corresponding to the control
room host is bright, five-way intercom is carried out by pressing the corresponding button
after off-hook of the phone.
Host calling: five-way intercom is carried out by pressing the extension number after off-hook
of the phone.
If there are multiple elevators calling control room host at the same time, all elevator number
lights corresponding to the control room host will be all bright. Press the corresponding
elevator number button to call back after off-hook of the phone.
Control room host without display shown as picture 1(BLT12-16N),connection terminals
shown as picture 2.
MPK708C Commissioning Manual Code:YETS-0002-C
Picture 1:BLT12-16N
Picture 2
25.1.2.2 Instruction for control room host
Picture 3:BLT12-254N
MPK708C Commissioning Manual Code:YETS-0002-C
(1)When extension calling host, host phone rings and calling indication light flashes and
display screen shows calling subsystem number. After off-hook of the phone subsystem
interphone is automatically connected so that calling can be carried out; Calling is ended
when phone is hung up.
(2)When host calling extension, enter three digit number subsystem number after off-hook
of the phone, e.g., when calling No.8 subsystem, directly enter 008 to connect it.
(3)When several extension calling host, the host phone rings and indication light flashes and
display screen shows calling ( 7 groups of calling are shown at the same time and the newest
calling is placed on the first place.) the first group of numbers is automatically connected at
once after off-hook of the phone. When subsystem is needed to switched, push the button of
“next” button or directly enter subsystem number and then hung up to end calling.(Note: at
any time only one subsystem is involved in intercom.)
1. The indicating lamp for off-hook phone is lit. The host for control room is in off-hook
status which can monitor whether the handset of the phone has been put in proper place.
2. Phone indicating lamp being lit shows control room host has been switched to calling status.
(Standby: no this function)
3. Flashing of call indicating lamp shows call needed for handling.
4. Fault indicating lamp being lit shows subsystem has fault and cannot return signal during
the routing inspection.
5. Standby/emergency indicating lamp being lit, control room host is in hung up status,
monitoring whether the handle is put in proper place.
6. Standby/emergency indicating lamp being lit shows cutting off with electric supply and
starting standby power supply.
1. “confirmation/exit” key is used for the functions such as coordination for calling, entering
and exiting the main menu or submenu.
MPK708C Commissioning Manual Code:YETS-0002-C
2. Call/test key is used for switching to the function of calling or testing call transfer.
(Standby: no this function)
3. Submenu/pages turning key, use the key when prompted after entering the submenu
4. Submenu/query key, the key is used to inquire the main menu repeatedly.
5. “△”is up key, “▽”is down key which coordinates submenu.
6. Next key is shortcut key used to switch next subsystem.
7. Browse key is shortcut key used to browse basic information of the machine.
8. Number key “0-9” is used for phone dialing and call dialing.
cancelled). Query hand is on Overall Situation Deletion. Press confirmation key to delete total
registered subsystem information.
12. Delete one by one (set the menu only when routing inspection is needed to be cancelled).
The query hand is on the “delete one by one”, press the confirmation key to enter and directly
enter three bits subsystem number to complete the deleting of single subsystem number. The
function can make subsystem stop using temporarily.
13. main machine and submachine setting (standby: no this function)
14. C-D type bus setting: the product of our company is defaulted to type D, modification is
not permitted.
15. Termination of emergency output: when query hand is Termination of Emergency Output,
press confirmation key to terminate emergency power output of control room host built-in
power supply, at the same time control room host enters power-off status. When control room
host is needed to restart, the plug is only needed to connect to electric supply in every
country.
Picture 4:BLT12-AC
Machine room extension schematic diagram is shown as picture 4
1. Call three sub machines after off-hook of the machine room extensions.
2. Push the calling button after off-hook of machine room extension and automatically call
back (with display)/manual callback (without display) for five-way call after off-hook of
machine room host.
3.Address setting
In the back of machine there are 8 bits dial switch to adopt binary system. The number rule is
shown as follows:
switch bit 1 2 3 4 5 6 7 8
value 1 2 4 8 16 32 64 128
Note: address code is binary code; it must be set in a power-off state, otherwise setting is
inoperative.
MPK708C Commissioning Manual Code:YETS-0002-C
Wiring terminal: there are eight terminals in the bottom of phone as input and output
interfaces shown as the following picture 5 according to product mark icons:
Picture 5
Picture 6:BLT12-B
The extension is internal installation type; the sponge on the panel has two functions of
buffering in prevention of rocking and collision and partition between microphone and horn
in prevention of voice interference.
B. Installation attentions
During the installation the hollow-out of microphone and horn must aim at inlet and outlet of
installation panel, otherwise it will affect the quality of calling. It should be as far as possible
from strong current environment such equipments producing electromagnet interference as
inverter, contactor and electromagnet coil, etc. if conditions permit. When arranging of wire,
traveling cable should keep away from strong current line as far as possible. It is suggested to
use shielded cable. As shown in picture 7
MPK708C Commissioning Manual Code:YETS-0002-C
C. Wiring
Picture 7
AN1 and AN2 are connection output terminals of calling buttons. T1 and T2 correspond to T1
and T2 connecting machine room host. OV and 12V connect external DC 12V power supply.
The positive and negative of the power should be correctly connected, positive connecting
12V, negative connecting OV; otherwise it will burn circuit board if polarity is reversed.
The connection of intercom system should be made in accordance with wiring drawing, the
requirement of which is shown as follows:
1. Four core shielded twisted pair cable of RVVPS2*2*0.75mm² should be adopted for the
communication wires between the host in control room and extension in machine room.
Both ends of shielded layers should be reliably earthed, and T1 and T2 is a twisted pair,
Y1 and Y2 is also a twisted pair.
2. As for 254-way control room host, 35 machine room extensions can be equipped within the
length of communication wire of 1500m.
3. As for 16-way control room host, 16 machine room extensions can be equipped within the
length of communication wire of 1500m.
4. In order to ensure the reliable communication, it is suggested not to increase the quantity of
machine room extension in the allowable range of length of bus .
Recommended use
Bus
Unavailable
Picture 8
◆Note: it is not allowed to adopt tree wiring or star wiring. All elevators have to directly
connect to Bus and the branches cannot be branched to connect other elevators.
All communication signal cables should be as far from interference source as possible
(performance in accordance with national standard GB50348-2004), signal cable shall go
through weak electrical well but not parallel with strong current (e.g. 220V residential power)
or radio-frequency signal line (e.g. CATV, strong signal audio cable). It is recommended to
use bus type but not to use tree or star type. If the lines are parallel, the distance shall be more
than 30cm.
The installation position for system equipments should be far away from the environment
such as voice, light, heat, vibration to avoid the effect on the use performance of the system
and should be damp proof and dustproof
MPK708C Commissioning Manual Code:YETS-0002-C