Minimum Clearances Required For Indoor Termination Kits

This document provides tables of minimum clearance requirements for indoor cable termination kits according to different voltage standards. Table 1 gives minimum air clearances between live metal parts and between live metal and earth for terminations without bushing boots. Table 2 gives reduced minimum clearances when bushing boots are fitted. Table 3 gives minimum clearances between cable cores and between cores and earth. Table 4 gives minimum clearances between the top of stress control tubing and cable lugs. Table 5 provides impulse voltage withstand levels for indoor terminations installed with bushing boots.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views1 page

Minimum Clearances Required For Indoor Termination Kits

This document provides tables of minimum clearance requirements for indoor cable termination kits according to different voltage standards. Table 1 gives minimum air clearances between live metal parts and between live metal and earth for terminations without bushing boots. Table 2 gives reduced minimum clearances when bushing boots are fitted. Table 3 gives minimum clearances between cable cores and between cores and earth. Table 4 gives minimum clearances between the top of stress control tubing and cable lugs. Table 5 provides impulse voltage withstand levels for indoor terminations installed with bushing boots.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Unit E3, Crown Way, Crown Park Industrial Estate, Rushden, Northants, UK, NN10 6FD

Tel: +44 (0)1933 356758    Fax: +44 (0)1933 413821    Email: [email protected]
Skype: shrinkpolymersystems   www.shrinkpolymersystems.co.uk

Minimum Clearances Required for


Indoor Termination Kits

A B B

D
C C

• Check the cable box for minimum clearances and refer to table 1 below.
• If actual dimension ‘A’ and ‘B’ is less than the value given, a bushing boot must be fitted.

Table 1 – Minimum Air Clearances for Terminations in Cable Boxes in Accordance with BS 164 Class A.
Maximum System Voltage, Phase to Phase (kV) 7.2 12 24 36
Minimum Air Clearance Between Live Metal ‘A’ (mm) 90 127 242 356
Minimum Air Clearance Between Live Metal and Earth ‘B’ (mm) 65 75 140 222

Table 2 – M
 inimum Air Clearances for Terminations in Cable Boxes in Accordance with BS 164 Class A. with
Bushing Boots Fitted
Maximum System Voltage, Phase to Phase (kV) 7.2 12 24 36
Minimum Air Clearance Between Live Metal ‘A’ (mm) 45 75 100 125
Minimum Air Clearance Between Live Metal and Earth ‘B’ (mm) 32 60 75 100

Table 3 – Minimum Clearance Between Cores and Between Cores and Earth
Maximum System Voltage, Phase to Phase (kV) 7.2 12 24 36
Minimum Clearance ‘C’ (mm) Measured From top of Stress Tubes 15 20 40 50

Table 4 – Minimum Clearance Between top of The Stress Control Tubing and Base of the Cable Lug.
Maximum System Voltage, Phase to Phase (kV) 7.2 12 24 36
Minimum Clearance ‘D’ (mm) 30 50 95 250

Table 5 – Impulse Voltage Withstand for Indoor Terminations, Installed With Bushing Boots, on Bushings in
Accordance with BS2562.
Maximum System Voltage, Phase to Phase (kV) 7.2 12 24 36
Impulse Withstand Voltage (kV) 75 95 125 170

62